SOW and Attachments Mixing Valves 3 31 21.pdf
PDF 5 MB Posted
- Solicitation number
- 36C24221B0036
About this file
This solicitation is for installation of hot water mixing valves at the Northport VA Medical Center in Northport, New York. The contractor will replace existing hot and cold water stop valves, install hot water temperature limiting devices and hoses, replace pedal sink fixtures with motion-activated gooseneck faucets, replace shower control valves, test installed equipment, and document the work. The period of performance is 210 calendar days from notice to proceed. This service-disabled veteran-owned small business set-aside procurement will follow Public Law 109-461. Bidders must be registered in SAM, D&B, and VetBiz and submit annual Vets4212 reports. The magnitude of construction is between $500,000 and $1,000,000 under NAICS code 238220 with a business size of $16.5 million. A pre-bid site visit and bid opening will take place on the dates specified in the solicitation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Shower PT V 2.jpg | JPG image | |
| Shower PT V 3.jpg | JPG image | |
| Shower PT V 1.jpg | JPG image | |
| 36C24221B0036 0002.docx | DOCX document | |
| Mixing Valve Site Walk Sign-In Sheet 5 26 21.pdf | ||
| 36C24221B0036 0001.docx | DOCX document | |
| VHA Directive 1061_D_2014_08_15.pdf | ||
| 36C24221B0036 SOLICIATION 05142021 FNL.docx | DOCX document | |
| Davis Bacon Wage Determination.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Page 1 of 3 3/31/2021
MARCH 2020 INSTALLATION OF HOT WATER MIXING VALVES SOW
DEPARTMENT OF VETERANS AFFAIRS
Northport VA Medical Center
79 Middleville Road, Northport NY 11768
Statement of Work for
Installation of Hot Water Mixing Valves
Project Number: 632-21-116
The work shall be governed by
This Statement of Work, Attachment 1: “Equipment Schedule”
Attachment 2: “Equipment Location and Installation Schedule”
Attachment 3: “Building Floor Plans”
Attachment 4: “Project Specifications”
Work Tasks:
Task 1: Furnish all labor and materials to replace existing hot and cold water stop valves in sink and pedal sink water supply pipes at designated sinks. Most of this task shall be performed during evenings or weekends and will require shutting off the hot and cold water supply following lockout-and-tagout procedures in coordination with VA COR and Plumbing Shop. A total of 243 hot and 243 cold water stop valves shall be replaced.
Task 2: Furnish all labor and materials to install hot Water Temperature Limiting Devices at designated sinks. A total of 373 hot Water Temperature Limiting Devices shall be installed.
Task 3: Furnish all labor and materials to remove existing pedal valves and faucets and install Motion-Activated Gooseneck Faucets at designated sinks. A total of 86 pedal valve hardware and fixtures shall be replaced with Motion-Activated Gooseneck Faucets. Replacement of sinks is not part of this Scope.
Task 4: Furnish all labor and materials to remove and replace existing Pressure and Temperature controlling shower control valves in designated showers. A total of 12 shower control valves shall be replaced.
Page 2 of 3 3/31/2021
Task 5: After completion of the installation and initial testing of all new fixtures and devices installed, VAMC will increases the hot water loop temperature in the building to approximately 145° F. After the temperature is increased, test the operation of each of the new and existing temperature limiting devices to limit hot water temperature at the outlets to a maximum of 110° F. The desired hot water outlet temperature range is 105 to 110° F. This task shall be completed within 5 days after completion of work in the building, and within 1 day of the increase in temperature of the hot water supply to the building. Testing procedures are included in the specifications for Temperature Limiting Devices and Shower Pressure/Temperature Controllers.
A total of 409 water outlets shall be tested.
Task 6: After all installation and testing has been performed and accepted by the COR, bump pads shall be installed on the pipe and temperature limiting devices below all sinks. Bump pads shall be installed at 409 sinks.
Task 7: Perform an annual retest and readjustment of temperature limiting devices within 12 months of Task 5 completion date. A total of 409 water outlets shall be tested.
Task Sequence:
The work is broken into Tasks for ease of description. For some work locations at sinks, Tasks 1 and 2 will be able to be completed at the same time, i.e., during one location installation event.
Other locations will require completion of Task 1, then completion of task 2 during a subsequent installation visit.
Performance Period:
All Submittals must be approved by VA prior to beginning work. Work will begin after issuance of Notice to Proceed (NTP). The contractor shall submit the schedule of values for approval by the VA ten days after NTP. Contractor has 30 calendar days NTP to submit all products to be used during the project. Tasks 1 through 6 have a project completion time after all submittals have been approved is 180 days. The total project duration from NTP will be 210 days. Task 7 will have a completion date of within 575 days. VA anticipates that the Contractor will utilize more than one work crew to perform the work in the required time frame.
Place of Performance:
Department of Veterans Affairs VA Medical Center Northport NY 79 Middleville Rd.
Northport, NY 11768
Page 3 of 3 3/31/2021
Additional Notes:
The term “Mixing Valve” where used occasionally in this Statement of Work and associated documents is used generically, and is intended to mean a Water Temperature Limiting Device, a Lavatory Faucet (Sensor Control, Gooseneck Spout), or a Shower Bath Fixture (Type T/P Combination Valve) as described in the Specifications.
The Contractor shall coordinate valve installation locations and schedule with the VA contracting officer’s representative (COR) a minimum of 3 days in advance of the planned work. Scheduling of rooms to be worked in each week will be dependent upon the expected impact on patients, visitors, staff, and critical patient care areas. Scheduling of patient-occupied rooms and outpatient-utilized rooms will require coordination with medical staff. The VA COR will coordinate with medical staff.
The contractor shall prepare a spreadsheet showing details of each location’s requirements and status in detail and maintain the spreadsheet as a running status summary of the work. An electronic version of Attachment 2: “Equipment Location and Installation Schedule” will be provided to be used for this purpose.
No wall penetrations are anticipated to be required to be made during the performance of this contract. If any wall penetrations are anticipated to be required, the Contractor shall notify the COR in advance. The Contractor shall comply with all VA Fire Department (VAFD) penetration requirements including obtaining permits as required through fire rated assemblies (including floor slabs) as described in specification 22 07 11, section 3.1 (M)(1) and (2).
Contractor to provide 1 Year Warranty on parts & labor upon acceptance of the completed project.
Contractor to provide all close out documentation 30 days prior to completion of project.
Upon acceptance of closeout documentation by the VA contractor can apply for final payments.
Note that this contract does not involve VA sensitive information or data.
The Contractor shall first make a request in writing (email) requesting any interruption of any service two weeks in advance. Request for interruption of any utility services must approved by the COR.
Contractor shall be responsible to plan and coordinate all work with the COR who will coordinate and provide access. Contractor is responsible for safety, record keeping, security monitoring, and inspection of area. Contractor shall maintain Certified Payroll and Daily Logs.
Contractor shall provide the COR with a list of contractor staff participating in the work and shall submit in writing an ID request with company name, address, telephone number, name of each individual contractor employee and position title, SS# (by fax or encrypted email), home address, copy of OSHA 10-hour construction training certificate.
See Specification section 01 00 00 for a complete list of required documents.
ATTACHMENT 1
EQUIPMENT
SCHEDULE
VAMC Northport
INSTALLATION OF HOT WATER MIXING
VALVES
Project: 632-21-121
March 2021
NORTHPORT VAMC
INSTALLATION OF HOT WATER MIXING VALVES
PROJECT NO. 632-21-116 MARCH 2021
INCHES INCHES
Sinks and Pedal Sinks
Hot and Cold Water Angle Stop Valve
FPT X Compression Tamper-Proof
22 05 23
1/2" FPT X 3/8
Compression
Fitting
1/2" FPT X
3/8
Compression Fitting
Sinks and Pedal Sinks
Stainless Steel Braided Hose -
Fluidmaster - 3/8" Comp. X 1/2" F.I.P.
3/8"
Compression Fitting
3/8" Compression
Fitting
Sinks and Pedal Sinks
Water Temperature Limiting Device
22 05 23
Pedal Sinks
Lavatory Faucet Sensor Control
Gooseneck Spout Faucet
22 40 00
Sinks and Pedal Sinks
Bump Pads 22 40 00
Pedal Sink Sensor Operated
Gooseneck Faucet 22 40 00
Sink Pipe Guards Bump Pads 22 40 00
Showers Pressure/Temperature
Limiting Device 22 40 23
Showers Ball Valve 22 05 23
Various Locations as Needed
Copper Pipe Fittings 22 11 00
ATTACHMENT 1: EQUIPMENT SCHEDULE
LOCATION
SYSTEM
AND/OR
SERVICE
REMARKS
COLD WATER HOT WATER
As Specified in Attachment 2:
"Equipment Location and Installation Schedule"
SPECIFICATION
SECTION
DESCRIPTION
ATTACHMENT 2
LOCATION AND
INSTALLATION
SCHEDULE
Replace Cold and Hot Water
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
1 200 Basement Hallway Public B0-33 Sink 1 Yes No No No Yes Yes
2 200 Basement Hallway Public B0-33 Sink 2 Yes No No No Yes Yes
3 200 Basement Hallway Public B0-33 Sink 3 Yes No No No Yes Yes
4 200 Basement Hallway Public B0-35 Sink 1 Yes No No No Yes Yes
5 200 Basement Hallway Public B0-35 Sink 2 Yes No No No Yes Yes
6 200 Basement Hallway Public B0-35 Sink 3 Yes No No No Yes Yes
7 200 Basement Public Area Public B0-37 Sink 1 Yes Yes No No No Yes
8 200 Basement Public Area Public B0-37 Sink 2 Yes Yes No No No Yes
9 200 Basement Public Area Public B0-38C Sink 1 Yes Yes No No No Yes
10 200 Basement Public Area Public B0-38C Sink 2 Yes Yes No No No Yes
11 200 Basement Audiology Patient C0-1A Sink 1 Yes Yes No No No Yes
12 200 Basement Audiology Patient C0-1B Sink 1 Yes Yes No No No Yes
13 200 Basement Audiology Patient C0-1C Pedal Sink 1 Yes Yes Yes No No Yes
14 200 Basement Audiology Patient C0-1F Pedal Sink 1 Yes Yes Yes No No Yes
15 200 Basement Audiology Patient C0-5 Pedal Sink 1 Yes Yes Yes No No Yes
16 200 Basement Audiology Patient C0-6 Pedal Sink 1 Yes Yes Yes No No Yes
17 200 Basement Audiology Patient C0-8 Pedal Sink 1 Yes Yes Yes No No Yes
18 200 Basement Audiology Patient C0-9 Pedal Sink 1 Yes Yes Yes No No Yes
19 200 Basement Audiology Patient C0-9A Pedal Sink 1 Yes Yes Yes No No Yes
20 200 Basement Audiology Patient C0-9B Pedal Sink 1 Yes Yes Yes No No Yes
21 200 Basement Audiology Patient C0-11 Pedal Sink 1 Yes Yes Yes No No Yes
22 200 Basement Audiology Patient C0-11 Pedal Sink 2 Yes Yes Yes No No Yes
23 200 Basement Dental Suite Patient C0-12A Pedal Sink 1 Yes Yes Yes No No Yes
24 200 Basement Dental Suite Patient C0-12A Pedal Sink 2 Yes Yes Yes No No Yes
25 200 Basement Dental Suite Patient C0-12B Pedal Sink 1 Yes Yes Yes No No Yes
26 200 Basement Dental Suite Patient C0-12B Pedal Sink 2 Yes Yes Yes No No Yes
27 200 Basement Dental Suite Patient C0-12C Pedal Sink 1 Yes Yes Yes No No Yes
Devices and Equipment to be Installed or Tested
VAMC Northport Project No. 632-21-116
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
Page 1 of 16 4/1/2021
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
Devices and Equipment to be Installed or Tested
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
28 200 Basement Dental Suite Patient C0-12C Pedal Sink 2 Yes Yes Yes No No Yes
29 200 Basement Dental Suite Patient C0-12D Pedal Sink 1 Yes Yes Yes No No Yes
30 200 Basement Dental Suite Patient C0-12D Pedal Sink 2 Yes Yes Yes No No Yes
31 200 Basement Dental Suite Patient C0-12E Pedal Sink 1 Yes Yes Yes No No Yes
32 200 Basement Dental Suite Patient C0-12E Pedal Sink 2 Yes Yes Yes No No Yes
33 200 Basement Dental Suite Patient C0-12F Pedal Sink 1 Yes Yes Yes No No Yes
34 200 Basement Dental Suite Patient C0-12F Pedal Sink 2 Yes Yes Yes No No Yes
35 200 Basement Dental Suite Patient C0-13 Pedal Sink 1 Yes Yes Yes No No Yes
36 201 Basement Dental Suite Patient C0-13 Pedal Sink 1 Yes Yes Yes No No Yes
37 200 Basement Dental Suite Patient C0-14 Pedal Sink 1 Yes Yes Yes No No Yes
38 201 Basement Dental Suite Patient C0-15 Pedal Sink 1 Yes Yes Yes No No Yes
39 200 Basement Dental Suite Patient C0-16A Pedal Sink 1 Yes Yes Yes No No Yes
40 200 Basement Dental Suite Patient C0-16A Pedal Sink 2 Yes Yes Yes No No Yes
41 200 Basement Dental Suite Patient C0-16B Pedal Sink 1 Yes Yes Yes No No Yes
42 200 Basement Dental Suite Patient C0-16B Pedal Sink 2 Yes Yes Yes No No Yes
43 200 Basement Dental Suite Patient C0-16C Pedal Sink 1 Yes Yes Yes No No Yes
44 200 Basement Dental Suite Patient C0-16C Pedal Sink 2 Yes Yes Yes No No Yes
45 200 Basement Dental Suite Patient C0-16D Pedal Sink 1 Yes Yes Yes No No Yes
46 200 Basement Dental Suite Patient C0-16D Pedal Sink 2 Yes Yes Yes No No Yes
47 200 Basement Dental Suite Patient C0-16E Pedal Sink 1 Yes Yes Yes No No Yes
48 200 Basement Dental Suite Patient C0-16E Pedal Sink 2 Yes Yes Yes No No Yes
49 200 Basement Dental Suite Patient C0-16F Pedal Sink 1 Yes Yes Yes No No Yes
50 200 Basement Dental Suite Patient C0-16F Pedal Sink 2 Yes Yes Yes No No Yes
51 200 Basement PM&RS Patient C0-29 Sink 1 Yes Yes No No No Yes
52 200 Basement PM&RS Patient C0-30 Pedal Sink 1 Yes Yes Yes No No Yes
53 201 Basement PM&RS Patient C0-31 Sink 1 Yes Yes No No No Yes
54 200 Basement PM&RS Patient C0-32 Sink 1 Yes Yes No No No Yes
55 200 Basement PM&RS Patient C0-35 Sink 1 Yes Yes No No No Yes
Page 2 of 16 4/1/2021
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
Devices and Equipment to be Installed or Tested
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
56 200 Basement PM&RS Patient C0-35A Whirlpool 1 No Yes No No No No
57 200 Basement PM&RS Patient C0-35A Pedal Sink 1 Yes Yes Yes No No Yes
58 200 Basement PM&RS Patient C0-35C Pedal Sink 1 Yes Yes Yes No No Yes
59 200 Basement PM&RS Patient C0-35C Whirlpool 1 No Yes No No No No
60 200 Basement PM&RS Patient C0-35D Sink 1 Yes Yes No No No Yes
61 200 Basement PM&RS Patient C0-35D Shower 1 No No No Yes No No
62 200 Basement PM&RS Patient C0-38 Pedal Sink 1 Yes Yes Yes No No Yes
63 200 Basement PM&RS Patient C0-40 Pedal Sink 1 Yes Yes Yes No No Yes
64 200 Basement PM&RS Patient C0-41 Pedal Sink 1 Yes Yes Yes No No Yes
65 200 Basement PM&RS Patient C0-44 Sink 1 Yes Yes No No No Yes
66 200 Basement PM&RS Patient C0-45 Sink 1 Yes Yes No No No Yes
67 200 Basement Neurology Patient C0-50B Sink 1 Yes Yes No No No Yes
68 200 Basement Histology Patient C0-53 Sink 1 Yes Yes No No No Yes
69 200 Basement D0-C10 Sink 1 Yes Yes No No No Yes
70 200 Basement MRI Patient D0-11 Sink 1 Yes Yes No No No Yes
71 200 Basement MRI Patient D0-12 Sink 1 Yes Yes No No No Yes
72 200 Basement MRI Patient D0-19 Pedal Sink 1 Yes Yes Yes No No Yes
73 200 Basement MRI Patient D0-20 Pedal Sink 1 Yes Yes Yes No No Yes
74 200 Basement MRI Patient D0-25 Sink 1 Yes Yes No No No Yes
75 200 Basement MRI Patient D0-28 Sink 1 Yes Yes No No No Yes
76 200 Basement MRI Patient D0-34 Sink 1 Yes Yes No No No Yes
77 200 Basement MRI Patient D0-36 Pedal Sink 1 Yes Yes Yes No No Yes
78 200 Basement MRI Patient D0-37 Pedal Sink 1 Yes Yes Yes No No Yes
79 200 Basement MRI Patient D0-40 Sink 1 Yes Yes No No No Yes
80 200 Basement MRI Patient D0-42 Sink 1 Yes Yes No No No Yes
81 200 Basement MRI Patient D0-46 Sink 1 Yes Yes No No No Yes
82 200 Basement MRI Patient D0-47 Pedal Sink 1 Yes Yes Yes No No Yes
83 200 Basement Radiology Patient E0-2 Pedal Sink 1 Yes Yes Yes No No Yes
Page 3 of 16 4/1/2021
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
Devices and Equipment to be Installed or Tested
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
84 200 Basement Radiology Patient E0-2A Sink 1 Yes Yes No No No Yes
85 200 Basement Radiology Patient E0-3 Pedal Sink 1 Yes Yes Yes No No Yes
86 200 Basement Radiology Patient E0-3A Sink 1 Yes Yes No No No Yes
87 201 Basement Radiology Patient E0-5 Sink 1 Yes Yes No No No Yes
88 200 Basement Radiology Patient E0-5A Sink 1 Yes Yes No No No Yes
89 200 Basement Radiology Patient E0-6 Pedal Sink 1 Yes Yes Yes No No Yes
90 200 Basement Radiology Patient E0-8 Pedal Sink 1 Yes Yes Yes No No Yes
91 200 Basement Radiology Patient E0-9 Pedal Sink 1 Yes Yes Yes No No Yes
92 200 Basement Radiology Patient E0-10 Pedal Sink 1 Yes Yes Yes No No Yes
93 200 Basement Radiology Patient E0-11 Sink 1 Yes Yes No No No Yes
94 200 Basement Radiology Patient E0-12 Sink 1 Yes Yes No No No Yes
95 200 Basement Radiology Patient E0-13 Pedal Sink 1 Yes Yes Yes No No Yes
96 200 Basement Radiology Patient E0-14 Pedal Sink 1 Yes Yes Yes No No Yes
97 200 Basement Radiology Patient E0-28 Sink 1 Yes Yes No No No Yes
98 200 Basement Radiology Patient E0-33A Sink 1 Yes Yes No No No Yes
99 200 Basement Radiology Patient E0-33B Sink 1 Yes Yes No No No Yes
100 200 Basement Radiology Patient E0-35 Sink 1 Yes Yes No No No Yes
101 200 Basement Radiology Patient E0-37A Sink 1 Yes Yes No No No Yes
102 200 Basement Radiology Patient E0-42 Sink 1 Yes Yes No No No Yes
103 200 1 Cardiology A1-16 Pedal Sink 1 Yes Yes Yes No No Yes
104 200 1 Cardiology Patient A1-17 Sink 1 Yes Yes No No No Yes
105 200 1 Cardiology Patient A1-17A Sink 1 Yes Yes No No No Yes
106 200 1 Cardiology Patient A1-18 Sink 1 Yes Yes No No No Yes
107 200 1 Cardiology Patient A1-18 Sink 2 Yes Yes No No No Yes
108 200 1 Cardiology Patient A1-19 Sink 1 Yes Yes No No No Yes
109 200 1 Cardiology Patient A1-19 Sink 2 Yes Yes No No No Yes
110 200 1 Cardiology Patient A1-20 Sink 1 Yes Yes No No No Yes
111 200 1 Cardiology Patient A1-21 Sink Yes Yes No No No Yes
Page 4 of 16 4/1/2021
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
Devices and Equipment to be Installed or Tested
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
112 200 1 PAT_ASU Urology Patient A1-23 Sink 1 Yes Yes No No No Yes
113 200 1 PAT_ASU Urology Patient A1-24 Sink 1 Yes Yes No No No Yes
114 200 1 O.R. Staff A1-39A Sink 1 Yes Yes No No No Yes
115 200 1 O.R. Patient A1-45 Pedal Sink 1 Yes Yes Yes No No Yes
116 200 1 O.R. Patient A1-45B Sink 1 Yes Yes No No No Yes
117 200 1 O.R. Patient A1-45C Sink 1 Yes Yes No No No Yes
118 200 1 O.R. Patient A1-45D Sink 1 Yes Yes No No No Yes
119 200 1 O.R. Patient A1-68 Sink 1 Yes Yes No No No Yes
120 200 1 O.R. Patient A1-69 Sink 1 Yes Yes No No No Yes
121 200 1 O.R. Patient A1-70 Sink 1 Yes Yes No No No Yes
122 200 1 O.R. Patient A1-71 Sink 1 Yes Yes No No No Yes
123 200 1 Radiology Patient A1-73 Pedal Sink 1 Yes Yes Yes No No Yes
124 200 1 Radiology Patient A1-73 Pedal Sink 2 Yes Yes Yes No No Yes
125 200 1 Radiology Patient A1-75 Sink 1 Yes Yes No No No Yes
126 200 1 Radiology Patient A1-77A Sink 1 Yes Yes No No No Yes
127 200 1 Radiology Patient A1-78 Sink 1 Yes Yes No No No Yes
128 200 1 Radiology Patient A1-79 Sink 1 Yes Yes No No No Yes
129 200 1 Radiology Patient A1-80 Sink 1 Yes Yes No No No Yes
130 200 1 Radiology Patient A1-81 Sink 1 Yes Yes No No No Yes
131 200 1 Radiology Patient A1-87 Sink 1 Yes Yes No No No Yes
132 200 1 Radiology Patient A1-88 Sink 1 Yes Yes No No No Yes
133 200 1 Radiology Patient A1-89 Sink 1 Yes Yes No No No Yes
134 200 1 Radiology Patient A1-90 Sink 1 Yes Yes No No No Yes
135 200 1 Radiology Patient A1-92 Sink 1 Yes Yes No No No Yes
136 200 1 Radiology Patient A1-93 Sink 1 Yes Yes No No No Yes
137 200 1 Radiology Patient A1-94 Sink 1 Yes Yes No No No Yes
138 200 1 Radiology Patient A1-97 Sink 1 Yes Yes No No No Yes
139 200 1 Radiology Patient A1-99 Sink 1 Yes Yes No No No Yes
Page 5 of 16 4/1/2021
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
Devices and Equipment to be Installed or Tested
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
140 200 1 Radiology Patient A1-105 Sink 1 Yes Yes No No No Yes
141 200 1 Cardiology B1-8 Sink 1 Yes Yes No No No Yes
142 200 1 Cardiology B1-9A Sink 1 Yes Yes No No No Yes
143 200 1 Cardiology B1-13 Sink Yes Yes No No No Yes
144 200 1 Cardiology B1-13E Pedal Sink 1 Yes Yes Yes No No Yes
145 200 1 Cardiology B1-13F Pedal Sink 1 Yes Yes Yes No No Yes
146 200 1 Cardiology B1-13G Pedal Sink 1 Yes Yes Yes No No Yes
147 200 1 Cardiology B1-13H Pedal Sink 1 Yes Yes Yes No No Yes
148 200 1 Cardiology B1-13I Pedal Sink 1 Yes Yes Yes No No Yes
149 200 1 Cardiology B1-13J Pedal Sink 1 Yes Yes Yes No No Yes
150 200 1 Cardiology B1-21 Sink 1 Yes Yes No No No Yes
Page 6 of 16 4/1/2021
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
Devices and Equipment to be Installed or Tested
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
151 200 2 Unit 21 Patient A2-2C Sink 1 No Yes No No Yes Yes
152 200 2 Unit 21 Patient A2-7 Sink 1 No Yes No No No No
153 200 2 Unit 21 Patient A2-7 Shower 1 No No No No Yes No
154 200 2 Unit 21 Patient A2-8 Sink No Yes No No No No
155 200 2 Unit 21 Patient A2-9 Sink 1 No Yes No No No No
156 200 2 Unit 21 Patient A2-10 Sink 1 No Yes No No No No
157 200 2 Unit 21 Patient A2-10 Shower 1 No No No No Yes No
158 200 2 Unit 21 patient A2-13 Sink 1 No Yes No No No No
159 200 2 Unit 21 patient A2-14 Sink 1 No Yes No No No No
160 200 2 Unit 21 patient A2-14 Shower 1 No No No No Yes No
161 200 2 Unit 21 Patient A2-18 Shower 1 No No No No Yes No
162 200 2 Unit 21 Patient A2-18 Sink 1 No Yes No No No No
163 200 2 Unit 21 Patient A2-19 Sink 1 No Yes No No No No
164 200 2 Unit 21 Patient A2-20 Sink 1 No Yes No No No No
165 200 2 Unit 21 Patient A2-20 Shower 1 No No No No Yes No
166 200 2 Unit 21 Patient A2-25 Sink 1 No Yes No No No No
167 200 2 Unit 21 Patient A2-25 Shower 1 No No No No Yes No
168 200 2 Unit 21 Staff A2-26 Sink 1 No Yes No No No No
169 200 2 Unit 21 Staff A2-26A Sink 1 No Yes No No No No
170 200 2 Unit 21 Staff A2-29A Sink 1 No Yes No No No No
171 200 2 Unit 21 Staff A2-29A Shower 1 No No No No Yes No
172 200 2 Unit 21 Staff A2-30A Sink 1 No Yes No No No No
173 200 2 Unit 21 Staff A2-30A Shower 1 No No No No Yes No
174 200 2 Unit 21 Patient A2-35 Sink 1 No Yes No No No No
175 200 2 Unit 21 Patient A2-36 Sink 1 No Yes No No No No
176 200 2 Unit 21 A2-36 Shower 1 No No No No Yes No
177 200 2 Unit 21 Staff A2-44 Sink 1 No Yes No No No No
178 200 2 Unit 21 patient A2-46 Sink 1 No Yes No No No No
Page 7 of 16 4/1/2021
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
Devices and Equipment to be Installed or Tested
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
179 200 2 Unit 21 Staff A2-49 Sink 1 No Yes No No No No
180 200 2 Unit 21 Patient A2-50 Washer 1 No Yes No No No No
181 200 2 Unit 21 Patient A2-50 Sink 1 No No No No Yes No
182 200 2 Unit 21 Patient A2-51 Sink 1 No Yes No No No No
183 200 2 Unit 21 Patient A2-52 Sink 1 No Yes No No No No
184 200 2 Unit 21 Patient A2-52 Bed Pan Sink 1 No Yes No No No No
185 200 2 Unit 21 Patient A2-54 Sink 1 No Yes No No No No
186 200 2 Unit 21 Patient A2-54 Shower 1 No No No No Yes No
187 200 2 Unit 22 patient A2-59 Sink 1 Yes Yes No No No No
188 200 2 Unit 22 patient A2-60 Sink 1 Yes Yes No No No No
189 200 2 Unit 22 patient A2-61 Sink 1 Yes Yes No No No No
190 200 2 Unit 22 patient A2-61 Shower 1 No No No No Yes No
191 200 2 Unit 22 patient A2-64 Sink 1 Yes Yes No No No No
192 200 2 Unit 22 patient A2-65 Sink 1 Yes Yes No No No No
193 200 2 Unit 22 patient A2-65 Shower 1 No No No No Yes No
194 200 2 Unit 22 patient A2-68 Sink 1 Yes Yes No No No No
195 200 2 Unit 22 patient A2-68 Sink 2 Yes Yes No No No No
196 200 2 Unit 22 patient A2-69 Sink 1 Yes Yes No No No No
197 200 2 Unit 22 patient A2-69 Shower 1 No No No No Yes No
198 200 2 Unit 22 patient A2-71 Sink 1 Yes Yes No No No No
199 200 2 Unit 22 patient A2-71 Shower 1 No No No No Yes No
200 200 2 Unit 22 patient A2-72 Sink 1 Yes Yes No No No No
201 200 2 Unit 22 patient A2-72 Sink 2 Yes Yes No No No No
202 200 2 Unit 22 patient A2-75 Sink 1 Yes Yes No No No No
203 200 2 Unit 22 patient A2-75 Shower 1 No No No No Yes No
204 200 2 Unit 22 patient A2-77 Sink 1 Yes Yes No No No No
205 200 2 Unit 22 patient A2-77 Sink 2 Yes Yes No No No No
206 200 2 Unit 22 patient A2-79 Sink 1 Yes Yes No No No No
Page 8 of 16 4/1/2021
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
Devices and Equipment to be Installed or Tested
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
207 200 2 Unit 22 patient A2-79 Shower 1 No No No No Yes No
208 200 2 Unit 22 patient A2-81 Sink 1 Yes Yes No No No No
209 200 2 Unit 22 patient A2-81 Sink 2 Yes Yes No No No No
210 200 2 Unit 22 patient A2-82 Sink 1 Yes Yes No No No No
211 200 2 Unit 22 patient A2-82 Shower 1 No No No No Yes No
212 200 2 Unit 22 Staff A2-85A Sink 1 Yes Yes No No No No
213 200 2 Unit 22 patient A2-86 Sink 1 Yes Yes No No No No
214 200 2 Unit 22 patient A2-86 Sink 2 Yes Yes No No No No
215 200 2 Unit 22 A2-87 Sink 1 Yes Yes No No No No
216 200 2 Unit 22 A2-87 Shower 1 No No No No Yes No
217 200 2 Unit 22 Staff A2-89 Sink 1 Yes Yes No No No No
218 200 2 Unit 22 A2-89A Sink 1 Yes Yes No No No No
219 200 2 Unit 22 A2-89A Shower 1 No No No No Yes No
220 200 2 Unit 22 Staff A2-95 Sink 1 Yes Yes No No No No
221 200 2 Unit 22 Staff A2-97 Sink 1 Yes Yes No No No No
222 200 2 Unit 22 Staff A2-97 Bed Pan Sink 1 No Yes No No No No
223 200 2 Unit 22 patient A2-98 Sink 1 Yes Yes No No No No
224 200 2 Unit 22 Staff A2-99 Sink 1 Yes Yes No No No No
225 200 2 Unit 22 patient A2-100 Sink 1 Yes Yes No No No No
226 200 2 Unit 22 patient A2-101 Sink 1 Yes Yes No No No No
227 200 2 Unit 22 patient A2-101 Washer 1 No Washer No No Yes No
228 200 2 Unit 22 patient A2-103 Sink 1 Yes Yes No No No No
229 200 2 Unit 23/24 Public B2-3 Sink 2 Yes Yes No No No No
230 200 2 Unit 23/24 Public B2-5 Sink 3 Yes Yes No No No No
231 200 2 Unit 23 Patient B2-6A Sink 1 No Yes No No No No
232 200 2 Unit 23 Patient B2-7 Sink 1 No Yes No No No No
233 200 2 Unit 23 Patient B2-8 Sink 1 No Yes No No No No
234 200 2 Unit 23 Patient B2-9 Sink 1 No Yes No No No No
Page 9 of 16 4/1/2021
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
Devices and Equipment to be Installed or Tested
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
235 200 2 Unit 23 Patient B2-10 Pedal Sink 1 No Yes Yes No No No
236 200 2 Unit 23 Patient B2-10A Shower 1 No No No No Yes No
237 200 2 Unit 23 Patient B2-10A Bathtub 1 No No No No Yes No
238 200 2 Unit 23 Patient B2-11 Sink 1 No Yes No No No No
239 200 2 Unit 23 Staff B2-12A Sink 1 No Yes No No No No
240 200 2 Unit 23 Staff B2-12A Shower 1 No No No No Yes No
241 200 2 Unit 23 Staff B2-12B Pedal Sink 1 No Yes Yes No No No
242 200 2 Unit 23 Staff B2-14 Sink 1 No Yes No No No No
243 200 2 Unit 23 Staff B2-14 Pedal Sink 1 No Yes Yes No No No
244 200 2 Unit 23 Staff B2-15A Pedal Sink 1 No Yes Yes No No No
245 200 2 Unit 23 Staff B2-15B Sink 1 No Yes No No No No
246 200 2 Unit 23 Staff B2-15B Shower 1 No No No Yes Yes No
247 200 2 Unit 23 Staff B2-17A Sink 1 No Yes No No No No
248 200 2 Unit 23 Staff B2-18 Pedal Sink 1 No Yes Yes No No No
249 200 2 Unit 23 Staff B2-18D Sink 1 No Yes No No No No
250 200 2 Unit 23 Staff B2-18D Shower 1 No No No No Yes No
251 200 2 Unit 23 patient B2-18 Shower 1 No No No No Yes No
252 200 2 Unit 23 patient B2-19 Shower 2 No No No No Yes No
253 200 2 Unit 23 Staff B2-19A Sink 1 No Yes No No No No
254 200 2 Unit 23 Staff B2-21 Sink 1 No Yes No No No No
255 200 2 Unit 23 Staff B2-22 Sink 1 No Yes No No No No
256 200 2 Unit 23 Staff B2-24 Sink 1 No Yes No No No No
257 200 2 Unit 23 Staff B2-25 Sink 1 No Yes No No No No
258 200 2 Unit 23 Staff B2-25 Sink 1 No Yes No No No No
259 200 2 Unit 23 Staff B2-27 Sink 1 No Yes No No No No
260 200 2 Unit 23 Staff B2-28 Sink 1 No Yes No No No No
261 200 2 Unit 23 Staff B2-29 Pedal Sink 1 No Yes Yes No No No
262 200 2 Unit 23 Staff B2-30 Sink 1 No Yes No No No No
Page 10 of 16 4/1/2021
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
Devices and Equipment to be Installed or Tested
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
263 200 2 Unit 23 Staff B2-33A Sink 2 No Yes No No No No
264 200 2 Unit 23 patient B2-34 Sink 1 No Yes No No No No
265 200 2 Unit 23 patient B2-34A Sink 1 No Yes No No No No
266 200 2 Unit 23 patient B2-35 Sink 1 No Yes No No No No
267 200 2 Unit 23 patient B2-38 Sink 1 No Yes No No No No
268 200 2 Unit 23 patient B2-40A Sink 1 No Yes No No No No
269 200 2 Unit 23 patient B2-41 Sink 1 No Yes No No No No
270 200 2 Unit 23 patient B2-42 Sink 1 No Yes No No No No
271 200 2 Unit 23 patient B2-43 Sink 1 No Yes No No No No
272 200 2 Unit 23 Staff B2-44 Sink 1 No Yes No No No No
273 200 2 Unit 23 patient B2-45 Sink 1 No Yes No No No No
274 200 2 Unit 23 Staff B2-46 Sink 1 No Yes No No No No
275 200 2 Unit 23 Staff B2-47 Sink 1 No Yes No No No No
276 200 2 Unit 23 Staff B2-48 Sink 1 No Yes No No No No
277 200 2 Unit 23 Staff B2-49 Sink 1 No Yes No No No No
278 200 2 Unit 23 Staff B2-50 Pedal Sink 1 No Yes Yes No No No
279 200 2 Unit 23 Staff B2-51 Sink 1 No Yes No No No No
280 200 2 Unit 23 Staff B2-53 Sink 1 No Yes No No No No
281 200 2 Unit 23 Staff B2-54 Sink 1 No Yes No No No No
282 200 2 Unit 23 Staff B2-55 Sink 1 No Yes No No No No
283 200 2 Unit 23 Staff B2-56 Sink 1 No Yes No No No No
284 200 2 Unit 23 Staff B2-57 Sink 1 No Yes No No No No
285 200 2 Unit 23 Staff B2-60 Sink 1 No Yes No No No No
286 200 2 Unit 23 Staff B2-60 Bathtub 1 No No No No Yes No
287 200 2 Unit 23 Staff B2-63 Sink 1 No Yes No No No No
288 200 2 Unit 23 Staff B2-65 Pedal Sink 1 No Yes Yes No No No
289 200 2 Unit 23 Staff B2-66 Sink 1 No Yes No No No No
290 200 3 Unit 31 Staff A3-2B Pedal Sink 1 No Yes Yes No No Yes
Page 11 of 16 4/1/2021
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
Devices and Equipment to be Installed or Tested
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
291 200 3 Unit 31 Staff A3-C3B Sink 1 No Yes No No No Yes
292 200 3 Unit 31 Staff A3-4 Pedal Sink 1 No Yes Yes No No Yes
293 200 3 Unit 31 Staff A3-4 Pedal Sink 1 No Yes Yes No No Yes
294 200 3 Unit 31 Staff A3-C4F Sink 1 No Yes No No No Yes
295 200 3 Unit 31 Staff A3-7 Sink 1 No Yes No No No Yes
296 200 3 Unit 31 Staff A3-8 Sink 1 No Yes No No No Yes
297 200 3 Unit 31 Staff A3-9 Sink 1 No Yes No No No Yes
298 200 3 Unit 31 Staff A3-10 Sink 1 No Yes No No No Yes
299 200 3 Unit 31 Staff A3-11 Sink 1 No Yes No No No Yes
300 200 3 Unit 31 Staff A3-12 Sink 1 No Yes No No No Yes
301 200 3 Unit 31 Staff A3-13 Sink 1 No Yes No No No Yes
302 200 3 Unit 31 Staff A3-15 Sink 1 No Yes No No No Yes
303 200 3 Unit 31 Staff A3-16 Sink 1 No Yes No No No Yes
304 200 3 Unit 31 Staff A3-16A Sink 1 No Yes No No No Yes
305 200 3 Unit 31 Staff A3-17B Sink 1 No Yes No No No Yes
306 200 3 Unit 31 Staff A3-18 Sink 2 No Yes No No No Yes
307 200 3 Unit 31 Staff A3-18C Sink 1 No Yes No No No Yes
308 200 3 Unit 31 Staff A3-18D Sink 1 No Yes No No No Yes
309 200 3 Unit 31 Patient A3-18E Sink 1 No Yes No No No Yes
310 200 3 Unit 31 A3-20 Sink 1 No Yes No No No Yes
311 200 3 Unit 31 Staff A3-21 Sink 1 No Yes No No No Yes
312 200 3 Unit 31 Staff A3-22 Sink 1 No Yes No No No Yes
313 200 3 Unit 31 Staff A3-23 Sink 1 No Yes No No No Yes
314 200 3 Unit 31 Staff A3-25 Sink 1 No Yes No No No Yes
315 200 3 Unit 31 Staff A3-27A Sink 1 No Yes No No No Yes
316 200 3 Unit 31 A3-27B Sink 1 No Yes No No No Yes
317 200 3 Unit 31 A3-28 Sink 1 No Yes No No No Yes
318 200 3 A3-29 Sink 1 Yes Yes No No No Yes
Page 12 of 16 4/1/2021
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
Devices and Equipment to be Installed or Tested
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
319 200 3 Unit 32 Staff A3-35 Sink 1 Yes Yes No No No Yes
320 200 3 Unit 32 Staff A3-36 Sink 1 Yes Yes No No No Yes
321 200 3 Unit 32 Staff A3-37 Sink 1 Yes Yes No No No Yes
322 200 3 Unit 32 Staff A3-38 Sink 1 Yes Yes No No No Yes
323 200 3 Unit 32 Staff A3-39 Sink 1 Yes Yes No No No Yes
324 200 3 Unit 32 Staff A3-39A Shower 1 No Yes No Yes No No
325 200 3 Unit 32 Staff A3-41B Sink 1 Yes Yes No No No Yes
326 200 3 Unit 32 Staff A3-42 Sink 1 Yes Yes No No No Yes
327 200 3 Unit 32 Staff A3-43 Pedal Sink 1 Yes Yes Yes No No Yes
328 200 3 Unit 32 Staff A3-44 Sink 1 Yes Yes No No No Yes
329 200 3 Unit 32 Staff A3-45 Sink 1 Yes Yes No No No Yes
330 200 3 Unit 32 Staff A3-46 Sink 1 Yes Yes No No No Yes
331 200 3 Unit 32 Staff A3-48 Pedal Sink 1 Yes Yes Yes No No Yes
332 200 3 Unit 32 Staff A3-49 Sink 1 Yes Yes No No No Yes
333 200 3 Unit 32 Staff A3-50 Pedal Sink 1 Yes Yes Yes No No Yes
334 200 3 Unit 32 Staff A3-50 Pedal Sink 2 Yes Yes Yes No No Yes
335 200 3 Unit 32 Staff A3-50 Pedal Sink 3 Yes Yes Yes No No Yes
336 200 3 Unit 32 Staff A3-50 Pedal Sink 4 Yes Yes Yes No No Yes
337 200 3 Staff A3-51 Sink 1 Yes Yes No No No Yes
338 200 3 Unit 34 Public B3-2 Sink 1 Yes Yes No No No Yes
339 200 3 Unit 34 Public B3-2 Sink 2 Yes Yes No No No Yes
340 200 3 Unit 34 Public B3-4 Sink 1 Yes Yes No No No Yes
341 200 3 Unit 34 Public B3-4 Sink 2 Yes Yes No No No Yes
342 200 3 Unit 34 Staff B3-5 Sink 1 Yes Yes No No No Yes
343 200 3 Unit 34 Staff B3-6 Sink 1 Yes Yes No No No Yes
344 200 3 Unit 34 Staff B3-7 Sink 1 Yes Yes No No No Yes
345 200 3 Unit 34 Staff B3-8 Sink 1 Yes Yes No No No Yes
346 200 3 Unit 34 Staff B3-9 Sink 1 Yes Yes No No No Yes
Page 13 of 16 4/1/2021
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
Devices and Equipment to be Installed or Tested
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
347 200 3 Unit 34 Staff B3-9A Shower 1 No Yes No Yes No No
348 200 3 Unit 34 Staff B3-10 Sink 1 Yes Yes No No No Yes
349 200 3 Unit 34 Staff B3-11 Sink 1 Yes Yes No No No Yes
350 200 3 Unit 34 Staff B3-12 Sink 1 Yes Yes No No No Yes
351 200 3 Unit 34 Staff B3-13 Sink 1 Yes Yes No No No Yes
352 200 3 Unit 34 Staff B3-14 Sink 1 Yes Yes No No No Yes
353 200 3 Unit 34 B3-14A Sink 1 Yes Yes No No No Yes
354 200 3 Unit 34 B3-14A Shower 1 No Yes No Yes No No
355 200 3 Unit 34 B3-17 Sink 1 Yes Yes No No No Yes
356 200 3 Unit 34 B3-18 Shower 1 No Yes No Yes No No
357 200 3 Unit 34 B3-18 Shower 2 No Yes No Yes No No
358 200 3 Unit 34 B3-19 Sink 1 Yes Yes No No No Yes
359 200 3 Unit 34 B3-20 Sink 1 Yes Yes No No No Yes
360 200 3 Unit 34 B3-21 Sink 1 Yes Yes No No No Yes
361 200 3 Unit 34 B3-23 Sink 1 Yes Yes No No No Yes
362 200 3 Unit 34 B3-24 Sink 1 Yes Yes No No No Yes
363 200 3 Unit 34 B3-27 Sink 1 Yes Yes No No No Yes
364 200 3 Unit 34 Staff B3-29 Sink 1 Yes Yes No No No Yes
365 200 3 Unit 34 Staff B3-40 Sink 1 Yes Yes No No No Yes
366 200 3 Unit 34 Staff B3-40A Sink 1 Yes Yes No No No Yes
367 200 3 Unit 34 Staff B3-43 Sink 1 Yes Yes No No No Yes
368 200 3 Unit 34 Staff B3-44 Sink 1 Yes Yes No No No Yes
369 200 3 Unit 34 Staff B3-44A Shower 1 No Yes No Yes No No
370 200 3 Unit 34 Staff B3-45 Sink 1 Yes Yes No No No Yes
371 200 3 Unit 34 Staff B3-46 Sink 1 Yes Yes No No No Yes
372 200 3 Unit 34 Staff B3-47 Sink 1 Yes Yes No No No Yes
373 200 3 Unit 34 Staff B3-48 Pedal Sink 1 Yes Yes Yes No No Yes
374 200 3 Unit 34 Staff B3-49 Sink 1 Yes Yes No No No Yes
Page 14 of 16 4/1/2021
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
Devices and Equipment to be Installed or Tested
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
375 200 3 Unit 34 Staff B3-51 Sink 1 Yes Yes No No No Yes
376 200 3 Unit 34 Staff B3-52 Sink 1 Yes Yes No No No Yes
377 200 3 Unit 34 B3-53 Shower 1 No Yes No Yes No No
378 200 3 Unit 34 B3-53 Shower 2 No Yes No Yes No No
379 200 3 Unit 34 Staff B3-54 Sink 1 Yes Yes No No No Yes
380 200 3 Unit 34 Staff B3-55 Sink 1 Yes Yes No No No Yes
381 200 3 Unit 34 Staff B3-56 Sink 1 Yes Yes No No No Yes
382 200 3 Unit 34 Staff B3-58 Sink 1 Yes Yes No No No Yes
383 200 3 Unit 34 Staff B3-59 Sink 1 Yes Yes No No No Yes
384 200 3 Unit 34 Staff B3-61 Sink 1 Yes Yes No No No Yes
385 200 3 Unit 34 Staff B3-62 Sink 1 Yes Yes No No No Yes
386 200 3 Unit 34 Staff B3-63 Sink 1 Yes Yes No No No Yes
387 200 3 Unit 34 Staff B3-64 Sink 1 Yes Yes No No No Yes
388 200 4 Unit 42 A4-69 Sink 1 Yes Yes No No No Yes
389 200 4 Unit 43 B4-2 Sink 1 No Yes No No No Yes
390 200 4 Unit 43 B4-2 Sink 2 No Yes No No No Yes
391 200 4 Unit 43 B4-4 Sink 1 No Yes No No No Yes
392 200 4 Unit 43 B4-4 Sink 2 No Yes No No No Yes
393 200 4 Unit 43 B4-C4A Pedal Sink 1 No Yes Yes No No Yes
394 200 4 Unit 43 B4-5A Sink 1 No Yes No No No Yes
395 200 4 Unit 43 B4-7A Sink 1 No Yes No No No Yes
396 200 4 Unit 43 B4-9A Sink 1 No Yes No No No Yes
397 200 4 Unit 43 B4-10A Sink 1 No Yes No No No Yes
398 200 4 Unit 43 B4-12A Sink 1 No Yes No No No Yes
399 200 4 Unit 43 B4-16A Sink 1 No Yes No No No Yes
400 200 4 Unit 43 B4-20A Sink 1 No Yes No No No Yes
401 200 4 Unit 43 B4-21B Sink 1 No Yes No No No Yes
402 200 4 Unit 43 B4-23A Sink 1 No Yes No No No Yes
Page 15 of 16 4/1/2021
Stop Valves
Install Temperature Limiting Device and
Hoses
Replace Pedal Sink Fixture and Pedals with
Motion-Activated Gooseneck Faucet
Replace Shower Water P/T Control
Valve
Test Existing Temp. Limiting
Device
Install Bump Pads Under Sink
Devices and Equipment to be Installed or Tested
Attachment 2 - Equipment Location and Installation Schedule
Building Number
Floor Number
Unit or Service or Area Use
Room Use:
Patient, Staff, Public, Resident
Room Number
Outlet Number
Fixture Type Number at Location
403 200 4 Unit 43 B4-23A Shower 1 No Yes No Yes No No
404 200 4 Unit 43 B4-24A Sink 1 No Yes No No No Yes
405 200 4 Unit 43 B4-24A Shower 1 No Yes No Yes No No
406 200 4 Unit 43 B4-28A Sink 1 No Yes No No No Yes
407 200 4 Unit 43 B4-29A Sink 1 No Yes No No No Yes
408 200 4 Unit 43 B4-32A Sink 1 No Yes No No No Yes
409 200 4 Unit 43 B4-33 Sink 1 No Yes No No No Yes
Page 16 of 16 4/1/2021
ATTACHMENT 3
BUILDING
FLOOR PLANS
ATTACHMENT 4
SPECIFICATIONS
NORTHPORT VAMC INSTALLATION OF HOT WATER MIXING VALVES
PROJECT 632-21-116 MARCH 2021
00 01 10-1
TABLE OF CONTENTS
Section 00 01 10
SECTION NO. DIVISION AND SECTION TITLES
DIVISION 01 - GENERAL REQUIREMENTS
01 00 00 General Requirements 01 32 16.15 Project Schedules (Small Projects – Design/Bid/Build 01 33 23 Shop Drawings, Product Data, and Samples 01 35 26 Safety Requirements 01 42 19 Reference Standards 01 74 19 Construction Waste Management
DIVISION 22 – PLUMBING
22 05 11 Common Work Results for Plumbing 22 05 23 General-Duty Valves for Plumbing Piping 22 11 00 Facility Water Distribution 22 40 00 Plumbing Fixtures
Northport VAMC Installation of Hot Water Mixing Valves
Project 632-21-116 March 2021 i
SECTION 01 00 00
GENERAL REQUIREMENTS
TABLE OF CONTENTS
1.1 SAFETY REQUIREMENTS
1.2 GENERAL INTENTION
1.3 STATEMENT OF BID ITEM(S)
1.4 SPECIFICATIONS AND DRAWINGS FOR CONTRACTOR(NOT USED)
1.5 CONSTRUCTION SECURITY REQUIREMENTS
1.6 OPERATIONS AND STORAGE AREAS
1.8 DISPOSAL AND RETENTION
1.9 PROTECTION OF EXISTING VEGETATION, STRUCTURES, EQUIPMENT,
UTILITIES, AND IMPROVEMENTS
1.10 RESTORATION
1.11 PHYSICAL DATA(NOT USED)
1.12 PROFESSIONAL SURVEYING SERVICES(NOT USED)
1.13 LAYOUT OF WORK(NOT USED)
1.14 AS-BUILT DRAWINGS
1.15 WARRANTY MANAGEMENT
1.16 USE OF ROADWAYS
1.17 'S FIELD OFFICE(NOT USED)
1.18 TEMPORARY USE OF MECHANICAL AND ELECTRICAL EQUIPMENT(NOT USED)
1.19 TEMPORARY USE OF EXISTING ELEVATORS
1.20 TEMPORARY USE OF NEW ELEVATORS(NOT USED)
1.21 TEMPORARY TOILETS(NOT USED)
1.22 AVAILABILITY AND USE OF UTILITY SERVICES(NOT USED)
1.23 NEW TELEPHONE EQUIPMENT(NOT USED)
1.24 TESTS
1.25 INSTRUCTIONS
Project 632-21-116 March 2021 ii
1.26 GOVERNMENT-FURNISHED PROPERTY(NOT USED)
1.27 RELOCATED EQUIPMENT ITEMS (NOT USED)
1.28 STORAGE SPACE FOR DEPARTMENT OF VETERANS AFFAIRS EQUIPMENT(NOT
USED)
1.29 CONSTRUCTION SIGN(NOT USED)
1.30 SAFETY SIGN(NOT USED)
1.31 PHOTOGRAPHIC DOCUMENTATION(NOT USED)
1.32 FINAL ELEVATION Digital Images(NOT USED)
1.33 HISTORIC PRESERVATION(NOT USED)
1.34 VA TRIRIGA CPMS(NOT USED)
Project 632-21-116 December 2020
01 00 00 -1
SECTION 01 00 00
GENERAL REQUIREMENTS
1.1 SAFETY REQUIREMENTS
Refer to section 01 35 26, SAFETY REQUIREMENTS for safety and infection control requirements.
1.2 GENERAL INTENTION
A. Contractor shall completely prepare site for building operations, including removal of existing valves, and furnish labor and materials and perform work for installation of hot water mixing valves in multiple locations, as required by drawings and specifications.
B. Visits to the site by Bidders may be made only by appointment with the
Medical Center Engineering Officer.
E. All employees of general contractor and subcontractors shall comply with VA security management program and obtain permission of the VA police, be identified by project and employer, and restricted from unauthorized access.
1.3 STATEMENT OF BID ITEM(S)
A. ITEM I, GENERAL CONSTRUCTION: Not Applicable.
ITEM II, Electrical Work: Not Applicable.
ITEM III, Mechanical Work: Work includes all labor, material, equipment, and supervision to perform the required Mechanical construction work on this project including the replacement of angle stop valves, installation and testing of hot water mixing valves and associated hoses and fittings. Documentation of the work.
1.4 SPECIFICATIONS AND DRAWINGS FOR CONTRACTOR (NOT USED)
1.5 CONSTRUCTION SECURITY REQUIREMENTS
A. Security Plan:
1. The security plan defines both physical and administrative security procedures that will remain effective for the entire duration of the project.
01 00 00 -2
2. The General Contractor is responsible for assuring that all sub-contractors working on the project and their employees also comply with these regulations.
B. Security Procedures:
1. General Contractor’s employees shall not enter the project site without appropriate badge. They may also be subject to inspection of their personal effects when entering or leaving the project site.
2. Before starting work the General Contractor shall give one week’s notice to the Contracting Officer so that security arrangements can be provided for the employees. This notice is separate from any notices required for utility shutdown described later in this section.
3. No photography of VA premises is allowed without written permission of the Contracting Officer.
4. VA reserves the right to close or shut down the project site and order General Contractor’s employees off the premises in the event of a national emergency. The General Contractor may return to the site only with the written approval of the Contracting Officer.
C. Guards: (NOT USED)
D. Key Control: (NOT USED)
E. Document Control:
1. Before starting any work, the General Contractor/Sub Contractors shall submit an electronic security memorandum describing the approach to following goals and maintaining confidentiality of
“sensitive information”.
2. The General Contractor is responsible for safekeeping of all drawings, project manual and other project information. This information shall be shared only with those with a specific need to accomplish the project.
3. Certain documents, sketches, videos or photographs and drawings may be marked “Law Enforcement Sensitive” or “Sensitive Unclassified”.
01 00 00 -3
Secure such information in separate containers and limit the access to only those who will need it for the project. Return the information to the Contracting Officer upon request.
4. These security documents shall not be removed or transmitted from the project site without the written approval of Contracting
Officer.
5. 6. Notify Contracting Officer and Site Security Officer immediately when there is a loss or compromise of “sensitive information”.
7. All electronic information shall be stored in specified location following VA standards and procedures using an Engineering Document
Management Software (EDMS).
a. Security, access and maintenance of all project drawings, both scanned and electronic shall be performed and tracked through the
EDMS system.
b. “Sensitive information” including drawings and other documents may be attached to e-mail provided all VA encryption procedures are followed.
F. Motor Vehicle Restrictions
1. Vehicle authorization request shall be required for any vehicle entering the site and such request shall be submitted 24 hours before the date and time of access. Access shall be restricted to picking up and dropping off materials and supplies.
2. A limited number of (2 to 5) permits shall be issued for General
Contractor and its employees for parking in designated areas only.
1.6 OPERATIONS AND STORAGE AREAS
A. The Contractor shall confine all operations (including storage of materials) on Government premises to areas authorized or approved by the Contracting Officer. The Contractor shall hold and save the
Government, its officers and agents, free and harmless from liability of any nature occasioned by the Contractor's performance.
01 00 00 -4
B. Temporary buildings (e.g., storage sheds, shops, offices) and utilities may be erected by the Contractor only with the approval of the
Contracting Officer and shall be built with labor and materials furnished by the Contractor without expense to the Government. The temporary buildings and utilities shall remain the property of the
Contractor and shall be removed by the Contractor at its expense upon completion of the work. With the written consent of the Contracting
Officer, the buildings and utilities may be abandoned and need not be removed.
C. The Contractor shall, under regulations prescribed by the Contracting
Officer, use only established roadways, or use temporary roadways constructed by the Contractor when and as authorized by the Contracting
Officer. When materials are transported in prosecuting the work, vehicles shall not be loaded beyond the loading capacity recommended by the manufacturer of the vehicle or prescribed by any Federal, State, or local law or regulation. When it is necessary to cross curbs or sidewalks, the Contractor shall protect them from damage. The
Contractor shall repair or pay for the repair of any damaged curbs, sidewalks, or roads.
D. Working space and space available for storing materials shall be as determined by the COR.
E. Workers are subject to rules of Medical Center applicable to their conduct.
F. Execute work so as to interfere as little as possible with normal functioning of the Medical Center as a whole, including operations of utility services, fire protection systems and any existing equipment, and with work being done by others. Use of equipment and tools that transmit vibrations and noises through the building structure, are not permitted in buildings that are occupied, during construction, jointly by patients or medical personnel, and Contractor's personnel, except as permitted by the COR.
1. Do not store materials and equipment in other than assigned areas.
01 00 00 -5
2. Schedule delivery of materials and equipment to immediate construction working areas within buildings in use by Department of
Veterans Affairs in quantities sufficient for not more than two work days. Provide unobstructed access to the Medical Center areas required to remain in operation.
3. Where access by Medical Center personnel to vacated portions of…
This is the start of the file's text. The full file is on GovTribe.