The provided document is a National Park Service Annual Inspection and Testing of Automatic Fire Sprinkler System - Wet Pipe (Form AS-1A). It covers the minimum requirements of NFPA 25 for fire sprinkler systems connected to distribution systems without supplemental tanks or fire pumps. The form includes inspection, testing, and maintenance tasks to be performed on a weekly, monthly, quarterly, annual, third-year, and fifth-year basis. Key items assessed include control valves, gauges, backflow prevention devices, fire department connections, sprinklers, pipes, and waterflow alarm devices. The form also covers maintenance procedures such as obstruction investigations, flushing, and replacement of sprinklers and hoses. The completed form includes signatures from the contractor representative and the NPS employee. This appears to be a standard inspection and testing form rather than a specific contract opportunity.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SOS_Attach_11_DEVA_336624_AS1A_AS2A_FS1A_RFP1_Part_1.pdf | ||
| Attach_1_Scope_of_Services_(SOS).pdf | ||
| SOS_Attach_12_DEVA_336624_Reference_Manual_58_Structural_Fire_Management_reduced.pdf | ||
| SOS_Attach_1_2A_2B_3_DEVA_336624_Structural_Fire_-_Maps.pdf | ||
| SOS_Attach_8_DEVA_336624_-_Residential_Sprinkler_Systems_List_for_ITM.pdf | ||
| Attach_3_SCA_Wage_Determination.pdf | ||
| SOS_Attach_6_DEVA_336624_-_Fire_Alarm_Systems_List_for_ITM.pdf | ||
| Sol_140P8124Q0055.pdf | ||
| SOS_Attach_10_DEVA_336624_-_NPS_Standard_ITM_Forms.pdf | ||
| Attach_2_Contract_Price_Schedule.docx | DOCX document | |
| SOS_Attach_5_DEVA_336624_Scope_of_Repairs_by_Building_Number.pdf | ||
| SOS_Attach_7_DEVA_336624_-_Commercial_Sprinkler_Systems_List_for_ITM.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
National Park Service Annual Inspection and Testing of Automatic Fire Sprinkler System - Wet Pipe (Form AS-1A)
Information on this form covers the minimum requirements of NFPA 25 for fire sprinkler systems connected to distribution systems without supplemental tanks or fire pumps. Separate forms are available to inspect, test an maintain other fire protection systems. More frequent inspection, testing and maintenance may be necessary depending on the conditions of the occupancy and the water supply. These tasks include all applicable weekly, monthly and quarterly inspection, testing and maintenance tasks.
Date Previous Inspection:
Date of Inspection:
Asset ID No: Asset Description:
Park: Site No and Name:
Location ID No: Location Name:
Note: All questions are to be answered 'Yes', 'No', or 'N/A' (Non-applicable ). All 'No' answers, and additional comments, are to be explained in Part V of this form. Inspection, testing and maintenance are to be performed with water supplies (including fire pumps), in service, unless the impairment of NFPA 25 and the appropriate NPS Job Plan are followed.
Part I – GENERAL
1. Is building occupied? Yes No N/A
2. Has the occupancy classification and hazard of contents remained the same since the last inspection?
Yes No N/A
3. Are all fire protection systems in service? Yes No N/A
4. Has the system remained in service without modification since the last inspection? Yes No N/A
5. Was the system free of actuation of devices or alarms since the last inspection? Yes No N/A
Part II – INSPECTION
6. Control valves with locks or electrical supervision in correct (open or closed), position? Yes No N/A
7. Sprinkler wrench with spare sprinklers heads (at least two of each type of head found in system), located in spare head cabinet? Yes No N/A
8. Gauges ( Wet Pipe Only ) - Supply and system gauges show the same water pressure and are free from physical damage? Yes No N/A
9. Backflow prevention device valves in correct (open or closed position)? Yes No N/A
10. Backflow prevention device valves sealed, locked or supervised and accessible? Yes No N/A
11. Backflow prevention device relief port RPZ device not discharging? Yes No N/A
12. Pressure Reducing Valves: In open position, not leaking, maintaining downstream pressure per design criteria, and in good condition with hand wheels not broken? Yes No N/A
13. Hydraulic nameplate (calculated systems), securely attached to riser and legible? Yes No N/A
14. Hydraulic nameplate (calculated systems), securely attached to riser and legible? Yes No N/A
15. Fire Department Connections: Visible, accessible, couplings and swivels not damaged and rotate smoothly, plugs or caps in place and in good condition, identification signs(s) in place, check valve is not leaking, clapper is in place and operating properly and automatic drain valve in place and operating properly (if plugs or caps are not in place, inspect interior for obstructions)?
Yes No N/A
16. Alarm notification device (bell/horn), free from physical damage and obstruction? Yes No N/A
17. Visible sprinklers free from corrosion? Yes No N/A
18. Visible sprinklers free of obstructions? Yes No N/A
19. Visible sprinklers free o foreign materials including paint? Yes No N/A
20. All visible glass bulb sprinklers contain their heat sensitive liquid within bulb? Yes No N/A
21. Visible pipe In good condition, no external corrosion? Yes No N/A
22. Visible pipe has no mechanical damage and no leaks? Yes No N/A
23. Visible pipe properly aligned and has no external loads (wires, decorations, clothing hangers, etc.), applied? Yes No N/A
24. Visible pipe hangers and seismic braces not damaged or loose? Yes No N/A
25. Hose, hose couplings and nozzles on sprinkler system passed inspection in accordance with NFPA 1962? Yes No N/A
26. Adequate heat in areas with wet piping? Yes No N/A
27. Has an internal inspection of the pipe been performed by removing the flushing connection and one sprinkler near the end of the branch line within the last 5 years (if the answer is "No" conduct an internal inspection)?
Yes No N/A
28. Check valves internally inspected and all parts operate properly, move freely and are in good condition? Yes No N/A
29. Strainers filters, restricted orifices and diaphragm chambers on dry-pipe valves in good condition? Yes No N/A
30. Mechanical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed? Yes No N/A
Part III – FIFTH YEAR ONLY INSPECTION ( in addition to above items )
31. Check valves internally inspected and all parts operate properly, move freely and are in good condition? Yes No N/A
32. Strainers filters, restricted orifices and diaphragm chambers on dry-pipe valves in good condition? Yes No N/A
Part IV – ANNUAL TESTING
33. Mechanical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed?
Yes No N/A
34. Post indicating valves opened until spring or torsion is felt in the rod, then closed back one-quarter turn?
Yes No N/A
35. Main drain test of system downstream of backflow prevention device or pressure reducing valve - Static Pressure (psi).
_______ psi
36 . Main drain test of system downstream of backflow prevention device or pressure reducing valve - Residual Pressure (psi).
_______ psi
37. Was flow observed? Yes No N/A
38. Are results comparable to previous tests? Yes No N/A
39. Electrical waterflow alarm devices passed test by opening the inspector's test connection or bypass connection with alarms actuating and flow observed?
Yes No N/A
40. Are all sprinkler dated 1920 or later? Yes No N/A
41. Fast response sprinklers 20 or more years old replaced or successfully sample tested within last 10 years?
Yes No N/A
42. Standard response sprinklers 50 or more years old replaced or successfully sample tested within last 10 years?
Yes No N/A
43. Standard response sprinklers 75 or more years old replaced or successfully sample tested within last 5 years?
44. Dry-type sprinklers replaced or successfully sample tested within last 10 years? Yes No N/A
45. All control valves operated through full range and returned to normal position? Yes No N/A
46. Backflow devices passed backflow test? Yes No N/A
47. Backflow devices passed full flow test? Yes No N/A
48. Pressure reducing valves passed partial flow test? Yes No N/A
Part IV – THIRD YEAR TESTING ( test to be done every third year )
49. Hose (more than 5 years old), connected to the system has been service tested in accordance with NFPA 1962. Water discharged and waterflow alarms operated? Yes No N/A
Part IVb – FIFTH YEAR TESTING ( test to be done every fifth year )
50. Sprinkler(s) rated above High temperature tested? Yes No N/A
51. Gauges checked by calibrated gauge or replaced? Yes No N/A
52. Pressure reducing valves passed full flow test? Yes No N/A
Part V – MAINTENANCE
53. If sprinklers have been replaced, were they proper replacements? Yes No N/A
54. Used hose was cleaned, drained and dried before being placed back in service?
Hose exposed to hazardous materials was disposed of or decontaminated in an approved manner?
Yes No N/A
55. Systems normally filled with fresh water were drained and refilled twice if raw water got into the system?
Yes No N/A
56. If defective intake screen on pump with suction from open sources was discovered, was an obstruction investigation conducted?
Explain reason(s) and obstruction investigation findings in Part III.
Yes No N/A
57. If obstructive material discharged during waterflow tests was discovered, was an obstruction investigation conducted? Yes No N/A
58. If foreign materials were found in dry-pipe valves, check valves or pumps was an obstruction investigation conducted? Yes No N/A
59. If foreign material in water during drain test or plugging of inspector's test was discovered, was an obstruction investigation conducted? Yes No N/A
60. If plugging of pipe or sprinkler found during activation or alteration was discovered, was an obstruction investigation conducted? Yes No N/A
61. If failure to flush yard piping or surrounding public mains following new installation or repairs was discovered, was an obstruction investigation conducted? Yes No N/A
62. Is their record or history of broken water mains in the vicinity? Yes No N/A
63. If foreign materials were found in dry-pipe valves, check valves or pumps was an obstruction investigation conducted? Yes No N/A
64. Is there a practice of seasonal shut-down of system where system is returned to service after an extended period out or service? Yes No N/A
65. Is there reason to believe the system contains sodium silicate or its derivatives of highly corrosive fluxes in copper pipe system? Yes No N/A
66. If conditions were found that required flushing was flushing of system conducted? Yes No N/A
67. Operating stem of all OS&Y valves lubricated, completely closed, and replaced? Yes No N/A
68. Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced, except for bulb-type which show no signs of grease buildup?
Yes No N/A
Part VI – Deficiency Notes and Additional Comments
Any deficiencies found, or other site or system specific problems, or general comments or concerns must be explained here.
Also, note here any products noticed on the systems that have been the subject of a recall.
Item No Comment
Part VII – Signatures
I state that the information on this form is correct at the time and place of my inspection, and that all equipment tested at his time was left in operational condition upon completion of this inspection except as noted in Part III above.
Contractor Information
Representative's Name:
Company:
Company Address:
Company Phone:
Signature:
Date:
NPS Information
Employee’s Name:
Park Division and Office:
Phone Number:
Employee’s Signature:
Date:
Automatic Fire Sprinkler System - Wet Pipe (Form AS-1A)
Date Previous Inspection:
Asset ID No:
Description:
Park: Site:
Location No: Name:
Automatic Fire Sprinkler System - Wet Pipe (Form AS-1A)
Information on this form covers the minimum requirements of NFPA 25 for fire sprinkler systems connected to distribution systems without supplemental tanks or fire pumps. Separate forms are available to inspect, test an maintain other fire protection systems. More frequent inspection, testing and maintenance may be necessary depending on the conditions of the occupancy and the water supply. These tasks include all applicable weekly, monthly and quarterly inspection, testing and maintenance tasks.
Date Previous Inspection:
Date of Inspection:
Asset ID No: Asset Description:
Park: Site No and Name:
Location ID No: Location Name:
Note: All questions are to be answered 'Yes', 'No', or 'N/A' (Non-applicable ). All 'No' answers, and additional comments, are to be explained in Part V of this form. Inspection, testing and maintenance are to be performed with water supplies (including fire pumps), in service, unless the impairment of NFPA 25 and the appropriate NPS Job Plan are followed.
Part I – GENERAL
1. Is building occupied? Yes No N/A
2. Has the occupancy classification and hazard of contents remained the same since the last inspection?
Yes No N/A
3. Are all fire protection systems in service? Yes No N/A
4. Has the system remained in service without modification since the last inspection? Yes No N/A
5. Was the system free of actuation of devices or alarms since the last inspection? Yes No N/A
Part II – INSPECTION
6. Control valves with locks or electrical supervision in correct (open or closed), position? Yes No N/A
7. Sprinkler wrench with spare sprinklers heads (at least two of each type of head found in system), located in spare head cabinet? Yes No N/A
8. Gauges ( Wet Pipe Only ) - Supply and system gauges show the same water pressure and are free from physical damage? Yes No N/A
9. Backflow prevention device valves in correct (open or closed position)? Yes No N/A
10. Backflow prevention device valves sealed, locked or supervised and accessible? Yes No N/A
11. Backflow prevention device relief port RPZ device not discharging? Yes No N/A
12. Pressure Reducing Valves: In open position, not leaking, maintaining downstream pressure per design criteria, and in good condition with hand wheels not broken? Yes No N/A
13. Hydraulic nameplate (calculated systems), securely attached to riser and legible? Yes No N/A
14. Hydraulic nameplate (calculated systems), securely attached to riser and legible? Yes No N/A
15. Fire Department Connections: Visible, accessible, couplings and swivels not damaged and rotate smoothly, plugs or caps in place and in good condition, identification signs(s) in place, check valve is not leaking, clapper is in place and operating properly and automatic drain valve in place and operating properly (if plugs
18. Visible sprinklers free of obstructions? Yes No N/A
19. Visible sprinklers free o foreign materials including paint? Yes No N/A
20. All visible glass bulb sprinklers contain their heat sensitive liquid within bulb? Yes No N/A
21. Visible pipe In good condition, no external corrosion? Yes No N/A
22. Visible pipe has no mechanical damage and no leaks? Yes No N/A
23. Visible pipe properly aligned and has no external loads (wires, decorations, clothing hangers, etc.), applied? Yes No N/A
24. Visible pipe hangers and seismic braces not damaged or loose? Yes No N/A
25. Hose, hose couplings and nozzles on sprinkler system passed inspection in accordance with NFPA 1962? Yes No N/A
26. Adequate heat in areas with wet piping? Yes No N/A
27. Has an internal inspection of the pipe been performed by removing the flushing connection and one sprinkler near the end of the branch line within the last 5 years (if the answer is "No" conduct an internal inspection)?
Yes No N/A
28. Check valves internally inspected and all parts operate properly, move freely and are in good condition? Yes No N/A
29. Strainers filters, restricted orifices and diaphragm chambers on dry-pipe valves in good condition? Yes No N/A
30. Mechanical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed? Yes No N/A
Part III – FIFTH YEAR ONLY INSPECTION ( in addition to above items )
31. Check valves internally inspected and all parts operate properly, move freely and are in good condition? Yes No N/A
32. Strainers filters, restricted orifices and diaphragm chambers on dry-pipe valves in good condition? Yes No N/A
Part IV – ANNUAL TESTING
33. Mechanical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed?
Yes No N/A
34. Post indicating valves opened until spring or torsion is felt in the rod, then closed back one-quarter turn?
Yes No N/A
35. Main drain test of system downstream of backflow prevention device or pressure reducing valve - Static Pressure (psi).
_______ psi
36 . Main drain test of system downstream of backflow prevention device or pressure reducing valve - Residual Pressure (psi).
_______ psi
37. Was flow observed? Yes No N/A
38. Are results comparable to previous tests? Yes No N/A
39. Electrical waterflow alarm devices passed test by opening the inspector's test connection or bypass connection with alarms actuating and flow observed?
Yes No N/A
40. Are all sprinkler dated 1920 or later? Yes No N/A
41. Fast response sprinklers 20 or more years old replaced or successfully sample tested within last 10 years?
Yes No N/A
42. Standard response sprinklers 50 or more years old replaced or successfully sample tested within last 10 years?
Yes No N/A
43. Standard response sprinklers 75 or more years old replaced or successfully
46. Backflow devices passed backflow test? Yes No N/A
47. Backflow devices passed full flow test? Yes No N/A
48. Pressure reducing valves passed partial flow test? Yes No N/A
Part IV – THIRD YEAR TESTING ( test to be done every third year )
49. Hose (more than 5 years old), connected to the system has been service tested in accordance with NFPA 1962. Water discharged and waterflow alarms operated? Yes No N/A
Part IVb – FIFTH YEAR TESTING ( test to be done every fifth year )
50. Sprinkler(s) rated above High temperature tested? Yes No N/A
51. Gauges checked by calibrated gauge or replaced? Yes No N/A
52. Pressure reducing valves passed full flow test? Yes No N/A
Part V – MAINTENANCE
53. If sprinklers have been replaced, were they proper replacements? Yes No N/A
54. Used hose was cleaned, drained and dried before being placed back in service?
Hose exposed to hazardous materials was disposed of or decontaminated in an approved manner?
Yes No N/A
55. Systems normally filled with fresh water were drained and refilled twice if raw water got into the system?
Yes No N/A
56. If defective intake screen on pump with suction from open sources was discovered, was an obstruction investigation conducted?
Explain reason(s) and obstruction investigation findings in Part III.
Yes No N/A
57. If obstructive material discharged during waterflow tests was discovered, was an obstruction investigation conducted? Yes No N/A
58. If foreign materials were found in dry-pipe valves, check valves or pumps was an obstruction investigation conducted? Yes No N/A
59. If foreign material in water during drain test or plugging of inspector's test was discovered, was an obstruction investigation conducted? Yes No N/A
60. If plugging of pipe or sprinkler found during activation or alteration was discovered, was an obstruction investigation conducted? Yes No N/A
61. If failure to flush yard piping or surrounding public mains following new installation or repairs was discovered, was an obstruction investigation conducted? Yes No N/A
62. Is their record or history of broken water mains in the vicinity? Yes No N/A
63. If foreign materials were found in dry-pipe valves, check valves or pumps was an obstruction investigation conducted? Yes No N/A
64. Is there a practice of seasonal shut-down of system where system is returned to service after an extended period out or service? Yes No N/A
68. Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced, except for bulb-type which show no signs of grease buildup?
Yes No N/A
Part VI – Deficiency Notes and Additional Comments
Any deficiencies found, or other site or system specific problems, or general comments or concerns must be explained here.
I state that the information on this form is correct at the time and place of my inspection, and that all equipment tested at his time was left in operational condition upon completion of this inspection except as noted in Part III above.
Contractor Information
Representative's Name:
Company:
Company Address:
Company Phone:
Signature:
Date:
NPS Information
Employee’s Name:
Park Division and Office:
Phone Number:
Automatic Fire Sprinkler System - Wet Pipe (Form AS-1A)
Date Previous Inspection:
Asset ID No:
Description:
Automatic Fire Sprinkler System - Wet Pipe (Form AS-1A)
Information on this form covers the minimum requirements of NFPA 25 for fire sprinkler systems connected to distribution systems without supplemental tanks or fire pumps. Separate forms are available to inspect, test an maintain other fire protection systems. More frequent inspection, testing and maintenance may be necessary depending on the conditions of the occupancy and the water supply. These tasks include all applicable weekly, monthly and quarterly inspection, testing and maintenance tasks.
Date Previous Inspection:
Date of Inspection:
Asset ID No: Asset Description:
Park: Site No and Name:
Location ID No: Location Name:
Note: All questions are to be answered 'Yes', 'No', or 'N/A' (Non-applicable ). All 'No' answers, and additional comments, are to be explained in Part V of this form. Inspection, testing and maintenance are to be performed with water supplies (including fire pumps), in service, unless the impairment of NFPA 25 and the appropriate NPS Job Plan are followed.
Part I – GENERAL
1. Is building occupied? Yes No N/A
2. Has the occupancy classification and hazard of contents remained the same since the last inspection?
Yes No N/A
3. Are all fire protection systems in service? Yes No N/A
4. Has the system remained in service without modification since the last inspection? Yes No N/A
5. Was the system free of actuation of devices or alarms since the last inspection? Yes No N/A
Part II – INSPECTION
6. Control valves with locks or electrical supervision in correct (open or closed), position? Yes No N/A
7. Sprinkler wrench with spare sprinklers heads (at least two of each type of head found in system), located in spare head cabinet? Yes No N/A
8. Gauges ( Wet Pipe Only ) - Supply and system gauges show the same water pressure and are free from physical damage? Yes No N/A
9. Backflow prevention device valves in correct (open or closed position)? Yes No N/A
10. Backflow prevention device valves sealed, locked or supervised and accessible? Yes No N/A
11. Backflow prevention device relief port RPZ device not discharging? Yes No N/A
12. Pressure Reducing Valves: In open position, not leaking, maintaining downstream pressure per design criteria, and in good condition with hand wheels not broken? Yes No N/A
13. Hydraulic nameplate (calculated systems), securely attached to riser and legible? Yes No N/A
14. Hydraulic nameplate (calculated systems), securely attached to riser and legible? Yes No N/A
15. Fire Department Connections: Visible, accessible, couplings and swivels not damaged and rotate smoothly, plugs or caps in place and in good condition, identification signs(s) in place, check valve is not leaking, clapper is in place and operating properly and automatic drain valve in place and operating properly (if plugs or caps are not in place, inspect interior for obstructions)?
iPad
18. Visible sprinklers free of obstructions? Yes No N/A
19. Visible sprinklers free o foreign materials including paint? Yes No N/A
20. All visible glass bulb sprinklers contain their heat sensitive liquid within bulb? Yes No N/A
21. Visible pipe In good condition, no external corrosion? Yes No N/A
22. Visible pipe has no mechanical damage and no leaks? Yes No N/A
23. Visible pipe properly aligned and has no external loads (wires, decorations, clothing hangers, etc.), applied? Yes No N/A
24. Visible pipe hangers and seismic braces not damaged or loose? Yes No N/A
25. Hose, hose couplings and nozzles on sprinkler system passed inspection in accordance with NFPA 1962? Yes No N/A
26. Adequate heat in areas with wet piping? Yes No N/A
27. Has an internal inspection of the pipe been performed by removing the flushing connection and one sprinkler near the end of the branch line within the last 5 years (if the answer is "No" conduct an internal inspection)?
Yes No N/A
28. Check valves internally inspected and all parts operate properly, move freely and are in good condition? Yes No N/A
29. Strainers filters, restricted orifices and diaphragm chambers on dry-pipe valves in good condition? Yes No N/A
30. Mechanical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed? Yes No N/A
Part III – FIFTH YEAR ONLY INSPECTION ( in addition to above items )
31. Check valves internally inspected and all parts operate properly, move freely and are in good condition? Yes No N/A
32. Strainers filters, restricted orifices and diaphragm chambers on dry-pipe valves in good condition? Yes No N/A
Part IV – ANNUAL TESTING
33. Mechanical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed?
Yes No N/A
34. Post indicating valves opened until spring or torsion is felt in the rod, then closed back one-quarter turn?
Yes No N/A
35. Main drain test of system downstream of backflow prevention device or pressure reducing valve - Static Pressure (psi).
_______ psi
36 . Main drain test of system downstream of backflow prevention device or pressure reducing valve - Residual Pressure (psi).
_______ psi
37. Was flow observed? Yes No N/A
38. Are results comparable to previous tests? Yes No N/A
39. Electrical waterflow alarm devices passed test by opening the inspector's test connection or bypass connection with alarms actuating and flow observed?
Yes No N/A
40. Are all sprinkler dated 1920 or later? Yes No N/A
41. Fast response sprinklers 20 or more years old replaced or successfully sample tested within last 10 years?
Yes No N/A
42. Standard response sprinklers 50 or more years old replaced or successfully sample tested within last 10 years?
Yes No N/A
43. Standard response sprinklers 75 or more years old replaced or successfully
46. Backflow devices passed backflow test? Yes No N/A
47. Backflow devices passed full flow test? Yes No N/A
48. Pressure reducing valves passed partial flow test? Yes No N/A
Part IV – THIRD YEAR TESTING ( test to be done every third year )
49. Hose (more than 5 years old), connected to the system has been service tested in accordance with NFPA 1962. Water discharged and waterflow alarms operated? Yes No N/A
Part IVb – FIFTH YEAR TESTING ( test to be done every fifth year )
50. Sprinkler(s) rated above High temperature tested? Yes No N/A
51. Gauges checked by calibrated gauge or replaced? Yes No N/A
52. Pressure reducing valves passed full flow test? Yes No N/A
Part V – MAINTENANCE
53. If sprinklers have been replaced, were they proper replacements? Yes No N/A
54. Used hose was cleaned, drained and dried before being placed back in service?
Hose exposed to hazardous materials was disposed of or decontaminated in an approved manner?
Yes No N/A
55. Systems normally filled with fresh water were drained and refilled twice if raw water got into the system?
Yes No N/A
56. If defective intake screen on pump with suction from open sources was discovered, was an obstruction investigation conducted?
Explain reason(s) and obstruction investigation findings in Part III.
Yes No N/A
57. If obstructive material discharged during waterflow tests was discovered, was an obstruction investigation conducted? Yes No N/A
58. If foreign materials were found in dry-pipe valves, check valves or pumps was an obstruction investigation conducted? Yes No N/A
59. If foreign material in water during drain test or plugging of inspector's test was discovered, was an obstruction investigation conducted? Yes No N/A
60. If plugging of pipe or sprinkler found during activation or alteration was discovered, was an obstruction investigation conducted? Yes No N/A
61. If failure to flush yard piping or surrounding public mains following new installation or repairs was discovered, was an obstruction investigation conducted? Yes No N/A
62. Is their record or history of broken water mains in the vicinity? Yes No N/A
63. If foreign materials were found in dry-pipe valves, check valves or pumps was an obstruction investigation conducted? Yes No N/A
64. Is there a practice of seasonal shut-down of system where system is returned to service after an extended period out or service? Yes No N/A
68. Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced, except for bulb-type which show no signs of grease buildup?
Yes No N/A
Part VI – Deficiency Notes and Additional Comments
Any deficiencies found, or other site or system specific problems, or general comments or concerns must be explained here.
Also, note here any products noticed on the systems that have been the subject of a recall.
I state that the information on this form is correct at the time and place of my inspection, and that all equipment tested at his time was left in operational condition upon completion of this inspection except as noted in Part III above.
Contractor Information
Representative's Name:
Company:
Company Address:
Company Phone:
Signature:
Date:
NPS Information
Employee’s Name:
Park Division and Office:
Phone Number:
Automatic Fire Sprinkler System - Wet Pipe (Form AS-1A)
Date Previous Inspection:
Asset ID No:
Description:
Automatic Fire Sprinkler System - Wet Pipe (Form AS-1A)
Information on this form covers the minimum requirements of NFPA 25 for fire sprinkler systems connected to distribution systems without supplemental tanks or fire pumps. Separate forms are available to inspect, test an maintain other fire protection systems. More frequent inspection, testing and maintenance may be necessary depending on the conditions of the occupancy and the water supply. These tasks include all applicable weekly, monthly and quarterly inspection, testing and maintenance tasks.
Date Previous Inspection:
Date of Inspection:
Asset ID No: Asset Description:
Park: Site No and Name:
Location ID No: Location Name:
Note: All questions are to be answered 'Yes', 'No', or 'N/A' (Non-applicable ). All 'No' answers, and additional comments, are to be explained in Part V of this form. Inspection, testing and maintenance are to be performed with water supplies (including fire pumps), in service, unless the impairment of NFPA 25 and the appropriate NPS Job Plan are followed.
Part I – GENERAL
1. Is building occupied? Yes No N/A
2. Has the occupancy classification and hazard of contents remained the same since the last inspection?
Yes No N/A
3. Are all fire protection systems in service? Yes No N/A
4. Has the system remained in service without modification since the last inspection? Yes No N/A
5. Was the system free of actuation of devices or alarms since the last inspection? Yes No N/A
Part II – INSPECTION
6. Control valves with locks or electrical supervision in correct (open or closed), position? Yes No N/A
7. Sprinkler wrench with spare sprinklers heads (at least two of each type of head found in system), located in spare head cabinet? Yes No N/A
8. Gauges ( Wet Pipe Only ) - Supply and system gauges show the same water pressure and are free from physical damage? Yes No N/A
9. Backflow prevention device valves in correct (open or closed position)? Yes No N/A
10. Backflow prevention device valves sealed, locked or supervised and accessible? Yes No N/A
11. Backflow prevention device relief port RPZ device not discharging? Yes No N/A
12. Pressure Reducing Valves: In open position, not leaking, maintaining downstream pressure per design criteria, and in good condition with hand wheels not broken? Yes No N/A
13. Hydraulic nameplate (calculated systems), securely attached to riser and legible? Yes No N/A
14. Hydraulic nameplate (calculated systems), securely attached to riser and legible? Yes No N/A
15. Fire Department Connections: Visible, accessible, couplings and swivels not damaged and rotate smoothly, plugs or caps in place and in good condition, identification signs(s) in place, check valve is not leaking, clapper is in place and operating properly and automatic drain valve in place and operating properly (if plugs
18. Visible sprinklers free of obstructions? Yes No N/A
19. Visible sprinklers free o foreign materials including paint? Yes No N/A
20. All visible glass bulb sprinklers contain their heat sensitive liquid within bulb? Yes No N/A
21. Visible pipe In good condition, no external corrosion? Yes No N/A
22. Visible pipe has no mechanical damage and no leaks? Yes No N/A
23. Visible pipe properly aligned and has no external loads (wires, decorations, clothing hangers, etc.), applied? Yes No N/A
24. Visible pipe hangers and seismic braces not damaged or loose? Yes No N/A
25. Hose, hose couplings and nozzles on sprinkler system passed inspection in accordance with NFPA 1962? Yes No N/A
26. Adequate heat in areas with wet piping? Yes No N/A
27. Has an internal inspection of the pipe been performed by removing the flushing connection and one sprinkler near the end of the branch line within the last 5 years (if the answer is "No" conduct an internal inspection)?
Yes No N/A
28. Check valves internally inspected and all parts operate properly, move freely and are in good condition? Yes No N/A
29. Strainers filters, restricted orifices and diaphragm chambers on dry-pipe valves in good condition? Yes No N/A
30. Mechanical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed? Yes No N/A
Part III – FIFTH YEAR ONLY INSPECTION ( in addition to above items )
31. Check valves internally inspected and all parts operate properly, move freely and are in good condition? Yes No N/A
32. Strainers filters, restricted orifices and diaphragm chambers on dry-pipe valves in good condition? Yes No N/A
Part IV – ANNUAL TESTING
33. Mechanical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed?
Yes No N/A
34. Post indicating valves opened until spring or torsion is felt in the rod, then closed back one-quarter turn?
Yes No N/A
35. Main drain test of system downstream of backflow prevention device or pressure reducing valve - Static Pressure (psi).
_______ psi
36 . Main drain test of system downstream of backflow prevention device or pressure reducing valve - Residual Pressure (psi).
_______ psi
37. Was flow observed? Yes No N/A
38. Are results comparable to previous tests? Yes No N/A
39. Electrical waterflow alarm devices passed test by opening the inspector's test connection or bypass connection with alarms actuating and flow observed?
Yes No N/A
40. Are all sprinkler dated 1920 or later? Yes No N/A
41. Fast response sprinklers 20 or more years old replaced or successfully sample tested within last 10 years?
Yes No N/A
42. Standard response sprinklers 50 or more years old replaced or successfully sample tested within last 10 years?
Yes No N/A
43. Standard response sprinklers 75 or more years old replaced or successfully
46. Backflow devices passed backflow test? Yes No N/A
47. Backflow devices passed full flow test? Yes No N/A
48. Pressure reducing valves passed partial flow test? Yes No N/A
Part IV – THIRD YEAR TESTING ( test to be done every third year )
49. Hose (more than 5 years old), connected to the system has been service tested in accordance with NFPA 1962. Water discharged and waterflow alarms operated? Yes No N/A
Part IVb – FIFTH YEAR TESTING ( test to be done every fifth year )
50. Sprinkler(s) rated above High temperature tested? Yes No N/A
51. Gauges checked by calibrated gauge or replaced? Yes No N/A
52. Pressure reducing valves passed full flow test? Yes No N/A
Part V – MAINTENANCE
53. If sprinklers have been replaced, were they proper replacements? Yes No N/A
54. Used hose was cleaned, drained and dried before being placed back in service?
Hose exposed to hazardous materials was disposed of or decontaminated in an approved manner?
Yes No N/A
55. Systems normally filled with fresh water were drained and refilled twice if raw water got into the system?
Yes No N/A
56. If defective intake screen on pump with suction from open sources was discovered, was an obstruction investigation conducted?
Explain reason(s) and obstruction investigation findings in Part III.
Yes No N/A
57. If obstructive material discharged during waterflow tests was discovered, was an obstruction investigation conducted? Yes No N/A
58. If foreign materials were found in dry-pipe valves, check valves or pumps was an obstruction investigation conducted? Yes No N/A
59. If foreign material in water during drain test or plugging of inspector's test was discovered, was an obstruction investigation conducted? Yes No N/A
60. If plugging of pipe or sprinkler found during activation or alteration was discovered, was an obstruction investigation conducted? Yes No N/A
61. If failure to flush yard piping or surrounding public mains following new installation or repairs was discovered, was an obstruction investigation conducted? Yes No N/A
62. Is their record or history of broken water mains in the vicinity? Yes No N/A
63. If foreign materials were found in dry-pipe valves, check valves or pumps was an obstruction investigation conducted? Yes No N/A
64. Is there a practice of seasonal shut-down of system where system is returned to service after an extended period out or service? Yes No N/A
68. Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced, except for bulb-type which show no signs of grease buildup?
Yes No N/A
Part VI – Deficiency Notes and Additional Comments
Any deficiencies found, or other site or system specific problems, or general comments or concerns must be explained here.
I state that the information on this form is correct at the time and place of my inspection, and that all equipment tested at his time was left in operational condition upon completion of this inspection except as noted in Part III above.
Contractor Information
Representative's Name:
Company:
Company Address:
Company Phone:
Signature:
Date:
NPS Information
Employee’s Name:
Park Division and Office:
Phone Number:
Automatic Fire Sprinkler System - Wet Pipe (Form AS-1A)
Date Previous Inspection:
Asset ID No:
Description:
Automatic Fire Sprinkler System - Wet Pipe (Form AS-1A)
Information on this form covers the minimum requirements of NFPA 25 for fire sprinkler systems connected to distribution systems without supplemental tanks or fire pumps. Separate forms are available to inspect, test an maintain other fire protection systems. More frequent inspection, testing and maintenance may be necessary depending on the conditions of the occupancy and the water supply. These tasks include all applicable weekly, monthly and quarterly inspection, testing and maintenance tasks.
Date Previous Inspection:
Date of Inspection:
Asset ID No: Asset Description:
Park: Site No and Name:
Location ID No: Location Name:
Note: All questions are to be answered 'Yes', 'No', or 'N/A' (Non-applicable ). All 'No' answers, and additional comments, are to be explained in Part V of this form. Inspection, testing and maintenance are to be performed with water supplies (including fire pumps), in service, unless the impairment of NFPA 25 and the appropriate NPS Job Plan are followed.
Part I – GENERAL
1. Is building occupied? Yes No N/A
2. Has the occupancy classification and hazard of contents remained the same since the last inspection?
Yes No N/A
3. Are all fire protection systems in service? Yes No N/A
4. Has the system remained in service without modification since the last inspection? Yes No N/A
5. Was the system free of actuation of devices or alarms since the last inspection? Yes No N/A
Part II – INSPECTION
6. Control valves with locks or electrical supervision in correct (open or closed), position? Yes No N/A
7. Sprinkler wrench with spare sprinklers heads (at least two of each type of head found in system), located in spare head cabinet? Yes No N/A
8. Gauges ( Wet Pipe Only ) - Supply and system gauges show the same water pressure and are free from physical damage? Yes No N/A
9. Backflow prevention device valves in correct (open or closed position)? Yes No N/A
10. Backflow prevention device valves sealed, locked or supervised and accessible? Yes No N/A
11. Backflow prevention device relief port RPZ device not discharging? Yes No N/A
12. Pressure Reducing Valves: In open position, not leaking, maintaining downstream pressure per design criteria, and in good condition with hand wheels not broken? Yes No N/A
13. Hydraulic nameplate (calculated systems), securely attached to riser and legible? Yes No N/A
14. Hydraulic nameplate (calculated systems), securely attached to riser and legible? Yes No N/A
15. Fire Department Connections: Visible, accessible, couplings and swivels not damaged and rotate smoothly, plugs or caps in place and in good condition, identification signs(s) in place, check valve is not leaking, clapper is in place and operating properly and automatic drain valve in place and operating properly (if plugs
18. Visible sprinklers free of obstructions? Yes No N/A
19. Visible sprinklers free o foreign materials including paint? Yes No N/A
20. All visible glass bulb sprinklers contain their heat sensitive liquid within bulb? Yes No N/A
21. Visible pipe In good condition, no external corrosion? Yes No N/A
22. Visible pipe has no mechanical damage and no leaks? Yes No N/A
23. Visible pipe properly aligned and has no external loads (wires, decorations, clothing hangers, etc.), applied? Yes No N/A
24. Visible pipe hangers and seismic braces not damaged or loose? Yes No N/A
25. Hose, hose couplings and nozzles on sprinkler system passed inspection in accordance with NFPA 1962? Yes No N/A
26. Adequate heat in areas with wet piping? Yes No N/A
27. Has an internal inspection of the pipe been performed by removing the flushing connection and one sprinkler near the end of the branch line within the last 5 years (if the answer is "No" conduct an internal inspection)?
Yes No N/A
28. Check valves internally inspected and all parts operate properly, move freely and are in good condition? Yes No N/A
29. Strainers filters, restricted orifices and diaphragm chambers on dry-pipe valves in good condition? Yes No N/A
30. Mechanical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed? Yes No N/A
Part III – FIFTH YEAR ONLY INSPECTION ( in addition to above items )
31. Check valves internally inspected and all parts operate properly, move freely and are in good condition? Yes No N/A
32. Strainers filters, restricted orifices and diaphragm chambers on dry-pipe valves in good condition? Yes No N/A
Part IV – ANNUAL TESTING
33. Mechanical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed?
Yes No N/A
34. Post indicating valves opened until spring or torsion is felt in the rod, then closed back one-quarter turn?
Yes No N/A
35. Main drain test of system downstream of backflow prevention device or pressure reducing valve - Static Pressure (psi).
_______ psi
36 . Main drain test of system downstream of backflow prevention device or pressure reducing valve - Residual Pressure (psi).
_______ psi
37. Was flow observed? Yes No N/A
38. Are results comparable to previous tests? Yes No N/A
39. Electrical waterflow alarm devices passed test by opening the inspector's test connection or bypass connection with alarms actuating and flow observed?
Yes No N/A
40. Are all sprinkler dated 1920 or later? Yes No N/A
41. Fast response sprinklers 20 or more years old replaced or successfully sample tested within last 10 years?
Yes No N/A
42. Standard response sprinklers 50 or more years old replaced or successfully sample tested within last 10 years?
Yes No N/A
43. Standard response sprinklers 75 or more years old replaced or successfully
46. Backflow devices passed backflow test? Yes No N/A
47. Backflow devices passed full flow test? Yes No N/A
48. Pressure reducing valves passed partial flow test? Yes No N/A
Part IV – THIRD YEAR TESTING ( test to be done every third year )
49. Hose (more than 5 years old), connected to the system has been service tested in accordance with NFPA 1962. Water discharged and waterflow alarms operated? Yes No N/A
Part IVb – FIFTH YEAR TESTING ( test to be done every fifth year )
50. Sprinkler(s) rated above High temperature tested? Yes No N/A
51. Gauges checked by calibrated gauge or replaced? Yes No N/A
52. Pressure reducing valves passed full flow test? Yes No N/A
Part V – MAINTENANCE
53. If sprinklers have been replaced, were they proper replacements? Yes No N/A
54. Used hose was cleaned, drained and dried before being placed back in service?
Hose exposed to hazardous materials was disposed of or decontaminated in an approved manner?
Yes No N/A
55. Systems normally filled with fresh water were drained and refilled twice if raw water got into the system?
Yes No N/A
56. If defective intake screen on pump with suction from open sources was discovered, was an obstruction investigation conducted?
Explain reason(s) and obstruction investigation findings in Part III.
Yes No N/A
57. If obstructive material discharged during waterflow tests was discovered, was an obstruction investigation conducted? Yes No N/A
58. If foreign materials were found in dry-pipe valves, check valves or pumps was an obstruction investigation conducted? Yes No N/A
59. If foreign material in water during drain test or plugging of inspector's test was discovered, was an obstruction investigation conducted? Yes No N/A
60. If plugging of pipe or sprinkler found during activation or alteration was discovered, was an obstruction investigation conducted? Yes No N/A
61. If failure to flush yard piping or surrounding public mains following new installation or repairs was discovered, was an obstruction investigation conducted? Yes No N/A
62. Is their record or history of broken water mains in the vicinity? Yes No N/A
63. If foreign materials were found in dry-pipe valves, check valves or pumps was an obstruction investigation conducted? Yes No N/A
64. Is there a practice of seasonal shut-down of system where system is returned to service after an extended period out or service? Yes No N/A
68. Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced, except for bulb-type which show no signs of grease buildup?
Yes No N/A
Part VI – Deficiency Notes and Additional Comments
Any deficiencies found, or other site or system specific problems, or general comments or concerns must be explained here.
I state that the information on this form is correct at the time and place of my inspection, and that all equipment tested at his time was left in operational condition upon completion of this inspection except as noted in Part III above.
Contractor Information
Representative's Name:
Company:
Company Address:
Company Phone:
Signature:
Date:
NPS Information
Employee’s Name:
Park Division and Office:
Phone Number:
Automatic Fire Sprinkler System - Wet Pipe (Form AS-1A)
Date Previous Inspection:
Asset ID No:
Description:
Automatic Fire Sprinkler System - Wet Pipe (Form AS-1A)
Information on this form covers the minimum requirements of NFPA 25 for fire sprinkler systems connected to distribution systems without supplemental tanks or fire pumps. Separate forms are available to inspect, test an maintain other fire protection systems. More frequent inspection, testing and maintenance may be necessary depending on the conditions of the occupancy and the water supply. These tasks include all applicable weekly, monthly and quarterly inspection, testing and maintenance tasks.
Date Previous Inspection:
Date of Inspection:
Asset ID No: Asset Description:
Park: Site No and Name:
Location ID No: Location Name:
Note: All questions are to be answered 'Yes', 'No', or 'N/A' (Non-applicable ). All 'No' answers, and additional comments, are to be explained in Part V of this form. Inspection, testing and maintenance are to be performed with water supplies (including fire pumps), in service, unless the impairment of NFPA 25 and the appropriate NPS Job Plan are followed.
Part I – GENERAL
1. Is building occupied? Yes No N/A
2. Has the occupancy classification and hazard of contents remained the same since the last inspection?
Yes No N/A
3. Are all fire protection systems in service? Yes No N/A
4. Has the system remained in service without modification since the last inspection? Yes No N/A
5. Was the system free of actuation of devices or alarms since the last inspection? Yes No N/A
Part II – INSPECTION
6. Control valves with locks or electrical supervision in correct (open or closed), position? Yes No N/A
7. Sprinkler wrench with spare sprinklers heads (at least two of each type of head found in system), located in spare head cabinet? Yes No N/A
8. Gauges ( Wet Pipe Only ) - Supply and system gauges show the same water pressure and are free from physical damage? Yes No N/A
9. Backflow prevention device valves in correct (open or closed position)? Yes No N/A
10. Backflow prevention device valves sealed, locked or supervised and accessible? Yes No N/A
11. Backflow prevention device relief port RPZ device not discharging? Yes No N/A
12. Pressure Reducing Valves: In open position, not leaking, maintaining downstream pressure per design criteria, and in good condition with hand wheels not broken? Yes No N/A
13. Hydraulic nameplate (calculated systems), securely attached to riser and legible? Yes No N/A
14. Hydraulic nameplate (calculated systems), securely attached to riser and legible? Yes No N/A
15. Fire Department Connections: Visible, accessible, couplings and swivels not damaged and rotate smoothly, plugs or caps in place and in good condition, identification signs(s) in place, check valve is not leaking, clapper is in place and operating properly and automatic drain valve in place and operating properly (if plugs or caps are not in place, inspect interior for obstructions)?
18. Visible sprinklers free of obstructions? Yes No N/A
19. Visible sprinklers free o foreign materials including paint? Yes No N/A
20. All visible glass bulb sprinklers contain their heat sensitive liquid within bulb? Yes No N/A
21. Visible pipe In good condition, no external corrosion? Yes No N/A
22. Visible pipe has no mechanical damage and no leaks? Yes No N/A
23. Visible pipe properly aligned and has no external loads (wires, decorations, clothing hangers, etc.), applied? Yes No N/A
24. Visible pipe hangers and seismic braces not damaged or loose? Yes No N/A
25. Hose, hose couplings and nozzles on sprinkler system passed inspection in accordance with NFPA 1962? Yes No N/A
26. Adequate heat in areas with wet piping? Yes No N/A
27. Has an internal inspection of the pipe been performed by removing the flushing connection and one sprinkler near the end of the branch line within the last 5 years (if the answer is "No" conduct an internal inspection)?
Yes No N/A
28. Check valves internally inspected and all parts operate properly, move freely and are in good condition? Yes No N/A
29. Strainers filters, restricted orifices and diaphragm chambers on dry-pipe valves in good condition? Yes No N/A
30. Mechanical waterflow alarm devices passed tests by opening the inspector's test connection or bypass connection with alarms actuating and flow observed? Yes No N/A
Part III – FIFTH YEAR ONLY INSPECTION ( in addition to above items )
31. Check valves internally inspected and all parts operate…