This is a sole source justification letter from Carey's Heating & Air Conditioning, Inc. to the Orlando Police Department in Orlando, Florida, supporting a maintenance and diagnostic services contract for the indoor small arms range ventilation systems. The letter details Carey's role as the exclusive designer and installer of the specialized range ventilation systems currently operating at the Orlando Police Department's indoor firing ranges. The proposed contract includes weekly, quarterly, and annual maintenance services encompassing ventilation system monitoring, equipment inspections, filter replacement, system recommissioning, air balancing, and smoke testing. The sole source procurement (S27-0112) has a response deadline of Thursday, November 26, 2026, at 5:00 p.m. ET, with a seven-day protest period for competing suppliers to submit qualifications to the Procurement Agent at cynthia.jordan@orlando.gov.
Carey's justifies the sole source designation by emphasizing that the ventilation systems are proprietary in design and control programming, making Carey's the only contractor capable of providing remote technical support and ensuring compliance with OSHA, EPA, IMC, and NIOSH standards for safe lead and contaminant exposure management. The letter specifies that Carey's requires pollution liability insurance with limits not less than $3,000,000 and errors and omissions insurance of at least $1,000,000. No pricing information, funding amounts, or contract term details are provided in this justification letter; however, the document establishes that any maintenance, service, or repairs not performed by Carey's would void performance guarantees and create potential occupant safety hazards due to the complex, interdependent nature of the specialized range ventilation equipment and control systems.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Ventilation_System_Diagnostic_and_Maintenance_Services.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Carey’s Heating & Air Conditioning, Inc.
8201 West 183rd St., Unit B, Tinley Park, IL 60487
8201 W 183rd St; Suite B Tinley Park, IL 60487 Phone: 708-532-2449
Fax: 708-429-2150 Website: careyscentral.com
October 29, 2026
Orlando Police Department Orlando, FL Attn.: Sgt Mike Perales RE: Indoor Small Arms Range Ventilation System
To whom it may concern:
Orlando Police Department Existing Range Ventilation Systems Upgrade
Carey’s Small Arms Ventilation is the sole designer and installer of the specialty range ventilation systems currently installed in the Orlando Police Department indoor firing ranges. The system has been designed, installed and calibrated by Carey’s to ensure safe operation of each range resulting in exposures to lead and other contaminates below the OSHA allowable levels. The design, installation, control, and commissioning of the range ventilation system can be the difference between an unsafe range and a range that meets the IMC, OSHA, EPA and NIOSH standards. Unlike traditional HVAC systems that are designed for comfort cooling, the range ventilation systems are complex in nature due to the amount of airflow required to control occupant exposure levels. The equipment, ductwork, and controls systems for each individual range are intertwined and symbiotic with each other. The systems are reliant on proper controls integration of each other for safety, building integrity, and performance guarantee.
Improper design, installation, balance, and control by another contractor can not only expose occupants to unsafe conditions, but also cause the equipment to damage itself and the building.
Any repairs, service, maintenance, or replacement parts not provided by Carey’s cannot be supported by Carey’s and thus will void any guarantee to provide an OSHA and EPA compliant range. The system design & controls programming is proprietary and if the system needs service or fails, Carey’s will be the only contractor to support and service the controls. We currently provide remote technical support for no charge. Any changes in the controls will prohibit us from responding for remote technical support
Indoor Firing Range Ventilation is a health and safety system that is required to provide laminar or even airflow at the shooters respiratory zone throughout all firing lines. The system should provide this airflow with a lack of turbulence at all shooting positions.
There are three primary considerations for the design of small arms ranges:
1. The primary purpose for the ventilation of an indoor firing range is to remove from the respiratory zone of the occupants harmful contaminates created during the firing of a weapon. Exploding primers containing lead styphnate and friction from the lead slug against the gun barrel create airborne lead.
There is also carbon monoxide as well as other contaminates created during the firing of a weapon.
2. The second and equally important reason for the properly designed and installed ventilation and control system is to keep the range at a negative pressure to the surrounding base building space. Contaminates created on a small arms range need to be contained within the range space. This will prevent the ingestion of contaminates as well as keeping the surfaces free of contaminates in non-range spaces of the base building.
3. The final purpose is to remove the smoke from the range for properly seeing the targets.
The standards followed and required are summarized below:
NIOSH (National Institute of Occupational Safety and Health) has set the standard for range design. This design criteria has been found to consistently produce conditions that keep exposure in the respiratory zone below the allowable limits for lead exposure.
The following is a summary of the IMC 2009, EPA, NIOSH and OSHA standards as they apply to small arms range ventilation:
IMC 2009 502.19 Indoor firing ranges. Ventilation shall be provided in an approved manner in areas utilized as indoor firing ranges. Ventilation shall be designed to protect employees and the public in accordance with OSHA 29 CFR 1910.1025 where applicable.
EPA:
TITLE 40--PROTECTION OF ENVIRONMENT CHAPTER I--ENVIRONMENTAL
PROTECTION AGENCY PART 50--NATIONAL PRIMARY AND SECONDARY
AMBIENT AIR QUALITY STANDARDS--Table of Contents Sec. 50.12 National primary and secondary ambient air quality standards for lead. National primary and secondary ambient air quality standards for lead and its compounds, measured as elemental lead by a reference method based on appendix G to this part, or by an equivalent method, are: 1.5 micrograms per cubic meter, maximum arithmetic mean averaged over a calendar quarter. (Secs. 109, 301(a) Clean Air Act as amended (42 U.S.C. 7409, 7601(a))) On November 12th, 2008, the EPA issued a final rule that revised the NAAQS for lead and associated ambient air lead monitoring requirements strengthening the requirement to 0.15 micrograms per cubic meter as total suspended particles measured as a three-month rolling average. (73 FR 66964, codified at 40 CFR part 58)
NIOSH and OSHA:
Established by NIOSH, the performance intent for firing range ventilation systems shall meet all the requirements outlined as recommendations and design considerations in HEW publication no. (NIOSH) 76-130, dated December, 1975, entitled "Lead Exposure Design Considerations for Indoor Firing Ranges". This design standard prefers an air flow velocity of 75 feet per minute average on the empty range. This design has consistently provided for the compliance within the established federal standards for airborne inorganic lead concentration limits.
When properly executed, lead concentrations are consistently maintained below the action level of 30 micrograms per cubic meter (30ug/m3) in an area where the limit shall not exceed 50 micrograms of lead per cubic meter (50ug/m3) of air over a time weighted average of eight hours as measured at the respiration zone of the shooters and the range officer when firing from the firing booths per OSHA 29 CFR. 1910.1025 and 1926.62.
Airflow The air flow in the range is designed to maintain an average velocity of 75 feet per minute at the firing lines over the entire cross-sectional areas. The safety of the occupants is the primary focus of the design for the range mechanical system. The exhaust airflow has been sized 10% greater than the supply airflow to maintain a negative pressure in the range of 0.05” of static pressure. This is measured between the range and the base building area. This will prevent contaminate created inside the range from spreading to the base building area.
Range Ventilation System Contractor Traditional HVAC contractors do not have the experience or knowledge to effectively, safely, guarantee that a ventilation system design, installation, balance, and control will provide a safe environment for occupant use in an indoor firing range. It is in the best interest for the owner and the occupants to use a Range Ventilation Contractor that has experience, will guarantee the performance of the system installed, and has the insurance to back up their guarantee. The range ventilation contractor shall show proof of pollution liability insurance. The range ventilation contractor shall procure and pay for pollution liability insurance with an insurance company currently rated no less than “A VII” by A.M. Best, and acceptable to the owner. The coverage must provide for third-party coverage for bodily injury, property damage, defense, cleanup, and related costs as a result of pollution conditions (sudden/accidental or gradual) arising from contracting operations performed by or on behalf of the range ventilation contractor. The limit of the policy shall not be less than $3,000,000 and not subject to a retention greater than $15,000. The range ventilation contractor shall show proof of errors and omissions insurance of not less than $1,000,000.00.
Please let me know if there are any questions.
Respectfully, Brian Wright Carey's Heating and Air Conditioning, Inc.