SJPS2304-0300 Project Drawings_R.pdf

PDF 3 MB Posted

Attached to
Infrastructure Upgrades (SJPS2304-0300)
Solicitation number
RFP - SJS - 240000000770
Issued by
Berrien County, Bergland CDP, Michigan

About this file

This document is a set of project drawings and specifications for the Infrastructure Upgrades project (SJPS2304-0300) for the Saint Joseph Public Schools district in Saint Joseph, Michigan. The project involves the upgrade and replacement of structured cabling, network electronics, and related infrastructure across multiple school buildings in the district, including Brown Elementary School, E.P. Clarke Elementary School, Lincoln Elementary School, Upton Middle School, and Saint Joseph High School. Key elements of the work include the demolition of existing cabling and equipment, the installation of new structured cabling and patch panels, the deployment of new network switches and wireless access points, and the configuration of the new network infrastructure. The project drawings provide detailed information on the scope of work, equipment specifications, and cabling requirements for each facility.

Regarding pricing and contract terms, the document does not provide specific pricing information, but it does note that the project is being funded through the district's capital improvement budget. The contract is expected to be awarded through a competitive bidding process, with the successful contractor responsible for providing all necessary labor, materials, and equipment to complete the infrastructure upgrades. The contract term and any potential renewal options are not specified in the provided documentation.

View the file

Other files

File Type Posted
SJPS2304-0300 Advertisement For Bids .pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET NO.

ISSUE / DATE

DRAWN BY

PROJECT NO.

© 2023 AETD, ALL RIGHTS RESERVED.

N

EW

PO

RT

R

OA

D, S

UI

TE

5, PO

RT

AG

E, M I 4

· 2

-2

-2

4 · A

ET

EC

H.

DE

SI

GN

2023-12-22 BIDS

CDB

TG01

Tit le

Sh ee t

SJPS2304-0300

Sa int

Jo se ph , M

I Inf ra str uc tur e U pg ra de s Sa int Jo se ph

P ub lic S ch oo ls

Infrastructure Upgrades Saint Joseph Public Schools

Saint Joseph, MI

Project Number: SJPS2304-0300

JACK; SEE LEGEND FOR COLOR

A1-A01

COMPUTER PRINTED SELF-LAMINATED

CABLE WRAP LABEL WITHIN 6 INCHES OF

CABLE END

Cabling Label Detail 6"=1'-0"

SHEET NO.

ISSUE / DATE

DRAWN BY

PROJECT NO.

© 2023 AETD, ALL RIGHTS RESERVED.

N

EW

PO

RT

R

OA

D, S

UI

TE

5, PO

RT

AG

E, M I 4

· 2

-2

-2

4 · A

ET

EC

H.

DE

SI

GN

2023-12-22 BIDS

CDB

TG02

Te ch no log y G en er al

Inf or ma tio n

SJPS2304-0300

Sa int

Jo se ph , M

I Inf ra str uc tur e U pg ra de s Sa int Jo se ph

P ub lic S ch oo ls

ABBREVIATIONS

ABBREVIATION TERMINOLOGY

AC ACCESS CONTROL

AFF ABOVE FINISH FLOOR

ATS AUTOMATIC TRANSFER SWITCH

AV OR A/V AUDIO / VIDEO

BAS BUILDING AUTOMATION SYSTEM

BB BACKERBOARD

CIP CAST IN PLACE

CLG CEILING

CP CONSOLIDATION POINT

EC ELECTRICAL CONTRACTOR

EF ENTRANCE FACILITY

EMT ELECTRICAL METALLIC TUBING

EQ EQUAL

EQUIV EQUIVALENT

ER EQUIPMENT ROOM

EXIST EXISTING

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GRD GROUND

HC HORIZONTAL CROSS-CONNECT

IC INTERMEDIATE CROSS-CONNECT

MC MAIN CROSS-CONNECT

NIC NOT IN CONTRACT

OC ON CENTER

OSP OUTSIDE PLANT

PBB PRIMARY BONDING BUSBAR

PT POKE-THROUGH

RBC RACK BONDING CONDUCTOR

SBB SECONDARY BONDING BUSBAR

SC STRUCTURED CABLING

SCC STRUCTURED CABLING CONTRACTOR

TBB TELECOMMUNICATIONS BONDING BACKBONE

TE TELECOMMUNICATIONS ENCLOSURE

TEBC TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR

TO TELECOMMUNICATIONS OUTLET

TR TELECOMMUNICATIONS ROOM

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

WA WORK AREA

A1-A01

1/8 " M

IN

JACK NUMBER (01 TO 48)

PATCH PANEL ID (A TO Z)

RACK ID (1 OR 2 DIGITS)

CLOSET ID (A TO Z)

AA-A01

1/8 " M

IN

POSITION NUMBER (01 TO 24)

110 BLOCK ID (A TO Z)

BACKBOARD ZONE (A TO Z)

CLOSET ID (A TO Z)

Numbering for 110-Block Term. Drops

NTS

Numbering for Typical Data Drops

NTS

RFI ## #

X# T###

DETAIL NUMBER

SHEET NUMBER WHERE

DETAIL IS LOCATED

ADDENDUM NUMBER BULLETIN NUMBER

RFI OR TSI NUMBER KEYED NOTE NUMBER

RFI OR TSI

DETAIL CALLOUT

NTS

ADDENDUM TAG

NTS

BULLETIN TAG

NTS

RFI OR TSI TAG

NTS

KEYED NOTE TAG

NTS

REVISION CLOUD

NTS

NOTES:

1. USED ON TECHNOLOGY FLOOR PLANS TO

REFERENCE A DETAIL, ELEVATION, OR SYSTEM

OF COMPONENTS ELEVATION ON ANOTHER

SHEET.

NOTES:

1. LOCATED NEXT TO A REVISION CLOUD FOR ANY

REVISIONS AFTER BIDS HAVE BEEN RELEASED,

BEFORE CONTRACT HAS BEEN AWARDED.

NOTES:

1. LOCATED NEXT TO A REVISION CLOUD FOR ANY

REVISIONS AFTER CONTRACT HAS BEEN

AWARDED.

NOTES:

1. DRAWN AROUND REVISION AREA RELATED TO

ANY ADDENDUM OR BULLETIN.

NOTES:

1. REFERENCE TO CORRESPONDING NOTES ON

SAME SHEET THAT HAVE MORE INFORMATION

RELATED TO SYMBOL.

NOTES:

1. RFI (REQUEST FOR INFORMATION) INDICATES A

REVISION AND CORRESPONDING NOTE THAT

DOES NOT AFFECT BUDGET THAT WAS NOT

INITIATED BY TECHNOLOGY CONTRACTOR.

2. TSI (TECHNOLOGY INFORMATION) TAG

INDICATES A REVISION AND CORRESPONDING

NOTE THAT DOES NOT AFFECT BUDGET.

EXISTING TECHNOLOGY

NTS

TECHNOLOGY IDENTIFIER

NOTES:

1. THIN SOLID LINE REPRESENTS EXISTING

TECHNOLOGY TO REMAIN. NO WORK REQUIRED

AT SPECIFIC LOCATION, BUT COULD REQUIRE

EXISTING CABLING AND/OR DEVICES TO BE

MAINTAINED DURING CONSTRUCTION TO

SUPPORT SPECIFIC DEVICE. SEE DRAWINGS

FOR MORE DETAIL.

DEMO TECHNOLOGY

NTS

TECHNOLOGY IDENTIFIER

NOTES:

1. HEAVY DASHED LINE REPRESENTS EXISTING

TECHNOLOGY TO BE REMOVED. COULD

REQUIRE DEMOLITION OF ROUGH-IN, CABLING,

FACEPLATE AND/OR DEVICE. DEVICE MAY NEED

TO BE SALVAGED FOR REINSTALLATION OR

TURNED OVER TO OWNER. SEE DRAWINGS FOR

MORE DETAIL.

NEW TECHNOLOGY

NTS

TECHNOLOGY IDENTIFIER

NOTES:

1. HEAVY SOLID LINE REPRESENTS NEW

TECHNOLOGY. COMPLETE INSTALLATION

OFTEN REQUIRES ROUGH-IN, CABLING,

FACEPLATE AND/OR DEVICE. SEE DRAWINGS

FOR MORE DETAIL.

CM

LR

V

8K

CS

D

H

S

X

F

N

8S

RISER LEGEND

SYMBOL DESCRIPTION

ZONE OR AREA

BY OTHERS OR EXISTING

NEW

OPTIONAL

PLUG INTO 120V RECEPTACLE

CONNECT TO GROUND

WIFI CONNECTION

GENERIC RF CONNECTION

BLUETOOTH CONNCETION

CELLULAR CONNECTION

8P8C (RJ45) NETWORK

KEYED 8P8C (RJ45)

SHIELDED 8P8C (RJ45)

COMPONENT VIDEO

COMPOSITE VIDEO

SVIDEO

HD15 (VGA) VIDEO

DVI VIDEO

HDMI VIDEO

RED & WHITE RCA AUDIO

3.5MM STEREO AUDIO

1/4" STEREO AUDIO

XLR MICROPHONE

COAX TYPE "F"

NEUTRIK NL4MP

USBU

PATCH CORD LEGEND

PURPOSE

TR WORK

AREA

COLOR

GENERAL DATA WHITE

WIRELESS ACCESS POINTS YELLOW

FACILITIES GREEN

SURVEILLANCE CAMERAS VIOLET

PAGING WHITE

AV WHITE

FIBER LEGEND

PURPOSE TYPE RATING MANUFACTURER MODEL

OUTSIDE PLANT OUTSIDE PLANT N/A GENERAL CABLE AQ***4M1A-DT

BACKBONE INDOOR/OUTDOOR PLENUM GENERAL CABLE AP***1ANU.BK

CABLING AND JACK LEGEND

PURPOSE

PREMISE CABLING JACKS

COLOR RATING MANUFACTURER MODEL TR COLOR WA COLOR MANUFACTURER MODEL SHIELDED

COPPER BACKBONE

BLUE PLENUM GENERAL CABLE GENSPEED 6000

RED RED

PANDUIT

CJ688TGRD CJS688TGRDY

RESERVED ORANGE ORANGE CJ688TGOR

WIRELESS ACCESS POINTS YELLOW YELLOW CJ688TGYL CJS688TGYLY

FACILITIES GREEN GREEN CJ688TGGR CJS688TGGRY

SPECIAL NETWORK BLUE BLUE CJ688TGBU CJS688TGBUY

SURVEILLANCE CAMERAS VIOLET VIOLET CJ688TGVL CJS688TGVLY

RESERVED BACK BLACK CJ688TGBL CJS688TGY

POTS LINES GRAY GRAY CJ688TGIG

GENERAL PURPOSE WHITE WHITE CJ688TGWH CJS688TGWHY

1. FOR DROPS INSTALLED ABOVE ACCESSIBLE CEILING, PROVIDE MAINTENANCE LOOP

AS INDICATED ON TECHNOLOGY SYMBOL LEGEND. CABLE SHALL BE NEATLY COILED

IN AN "S" LOOP AND SECURED TO BUILDING STRUCTURE AT DROP LOCATION FOR

EASY RELOCATION.

2. LOAD THE LATEST AVAILABLE STABLE FIRMWARE FOR ALL DEVICES WHEN THEY ARE

SUPPLIED FOR THIS PROJECT.

3. IN THE EVENT OF A DISCREPANCY BETWEEN TECHNOLOGY PLANS AND OTHER

DISCIPLINES, CONTRACTOR SHALL SUBMIT AN RFI FOR CLARIFICATION.

4. LABEL CABLES ACCORDING TO "CABLING LABEL DETAIL" ON THIS PAGE.

GENERAL NOTES

LIST OF DRAWINGS

NUMBER TITLE

TG01 Title Sheet

TG02 Technology General Information

T101 Brown ES Technology Plan - Composite

T102 E.P. Clarke ES Technology Plan - Composite

T103 Lincoln ES First Floor Technology Plan - Composite

T104A Upton MS Technology Plan - Unit A

T104B Upton MS Technology Plan - Unit B

T105 Saint Joseph HS Lower Floor Technology Plan

T106A Saint Joseph HS Main Floor Technology Plan - Unit D

T106B Saint Joseph HS Main Floor Technology Plan - Unit F & G

T301 Structured Cabling General Information

T302 Tech Rack Elevations

T303 Tech Rack Elevations

T304 Tech Rack Elevations

T305 Tech Rack Elevations

T306 Structured Cabling Details & Risers

T307 Structured Cabling Support Information

T308 Network Diagram

WORK SCOPE LEGEND

CA

TE

GO

RY DEFINITION OF WORK

EL

EC

TR

IC

AL

ST

RU

CT

. C

AB

LIN

G

OW

NE

R

NE

TW

OR

K

EL

EC

CO

NT

RA

CT

OR

GE

NE

RA

L D

AT

A

DEMO EXISTING STRUCTURED CABLING EQUIPMENT (RETURN TO OWNER) X

DEMO EXISTING STRUCTURED CABLING BACKBONE AND PREMISE CABLING X

DEMO EXISTING ACCESS POINTS (RETURN TO OWNER) X

PROVIDE ADAPTERS FOR RACEWAY, FLOORBOXES, ETC., TO ACCOMMODATE STANDARD

FACEPLATES AND JACKS X

PROVIDE STRUCTURED CABLING BACKBONE CABLING (AND TERMINATION) X

PROVIDE STRUCTURED CABLING PREMISE CABLING (AND TERMINATION) X

PROVIDE STRUCTURED CABLING PATCH CORDS X

SUPPLY NETWORK ELECTRONICS X

CONFIGURE NETWORK ELECTRONICS X

INSTALL NETWORK ELECTRONICS X

CONNECT TECH EQUIPMENT TO GROUNDING BUSBARS X

SUPPLY HARD-WIRED UPSES X

INSTALL HARD-WIRED UPSES X

CONNECT HARD-WIRED UPSES TO POWER X

PROVIDE IP ADDRESSES FOR NETWORK CONNECTED DEVICES X

CONFIGURE VLANS X

SB 8'

MB 4'

SB 8'

MB 4'

44_H1004A94

TC-C

TC-A

CA

BL

E

TO

T C-

A

CA

BL

E

TO

T

C- B

CA

BL

E

TO

T C-

A

CA

BL

E

TO

T

C- B

CABLE

TO TC-C

CABLE

TO TC-B

CABLE TO TC-C

CABLE TO TC-B

TC-B

N Brown ES Technology Plan - Composite 1/16" = 1'-0"

SHEET NO.

ISSUE / DATE

DRAWN BY

PROJECT NO.

© 2023 AETD, ALL RIGHTS RESERVED.

N

EW

PO

RT

R

OA

D, S

UI

TE

#2

, P

OR

TA

GE

, M I 4

· 2

-2

-2

4 · A

ET

EC

H.

DE

SI

GN

2023-12-22 BIDS

CDB

T101

Br ow n E S

Te ch no log y P lan

Co mp os ite

SJPS2304-0300

Sa int

Jo se ph , M

I Inf ra str uc tur e U pg ra de s Sa int Jo se ph

P ub lic S ch oo ls

DEMO GENERAL NOTES

1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.

2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR

FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.

3. FLOOR PLANS ARE NOT PROVIDED FOR THE CENTRAL OFFICE, TRANSPORTATION

BUILDING, PRESSBOX, AND STADIUM.

TC-A

TC-B

CABLE TO TC-B

CABLE TO TC-A

CA

BL

E

TO

T C-

B

CA

BL

E

TO

T

C- A

N E.P. Clarke ES Technology Plan - Composite 3/32" = 1'-0"

SHEET NO.

ISSUE / DATE

DRAWN BY

PROJECT NO.

© 2023 AETD, ALL RIGHTS RESERVED.

N

EW

PO

RT

R

OA

D, S

UI

TE

#2

, P

OR

TA

GE

, M I 4

· 2

-2

-2

4 · A

ET

EC

H.

DE

SI

GN

2023-12-22 BIDS

CDB

T102

E.

P.

C lar ke E

S Te ch no log y P lan

Co mp os ite

SJPS2304-0300

Sa int

Jo se ph , M

I Inf ra str uc tur e U pg ra de s Sa int Jo se ph

P ub lic S ch oo ls

DEMO GENERAL NOTES

1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.

2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR

FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.

N Lincoln ES First Floor Technology Plan - Composite 3/32" = 1'-0"

SHEET NO.

ISSUE / DATE

DRAWN BY

PROJECT NO.

© 2023 AETD, ALL RIGHTS RESERVED.

N

EW

PO

RT

R

OA

D, S

UI

TE

#2

, P

OR

TA

GE

, M I 4

· 2

-2

-2

4 · A

ET

EC

H.

DE

SI

GN

2023-12-22 BIDS

CDB

T103

Lin co ln

ES

F irs t F loo r T ec hn olo gy P lan

Co mp os ite

SJPS2304-0300

Sa int

Jo se ph , M

I Inf ra str uc tur e U pg ra de s Sa int Jo se ph

P ub lic S ch oo ls

DEMO GENERAL NOTES

1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.

2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR

FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.

02 Exist 12

TC-C

TC-A

CABLE TO TC-B

CABLE TO TC-A

CABLE TO TC-B

CABLE TO TC-C

CABLE

TO TC-C

CABLE

TO TC-E

N Upton MS Technology Plan - Unit A 3/32" = 1'-0"

SHEET NO.

ISSUE / DATE

DRAWN BY

PROJECT NO.

© 2023 AETD, ALL RIGHTS RESERVED.

N

EW

PO

RT

R

OA

D, S

UI

TE

#2

, P

OR

TA

GE

, M I 4

· 2

-2

-2

4 · A

ET

EC

H.

DE

SI

GN

2023-12-22 BIDS

CDB

T104A

Up ton

M S

Te ch no log y P lan

Un it A

SJPS2304-0300

Sa int

Jo se ph , M

I Inf ra str uc tur e U pg ra de s Sa int Jo se ph

P ub lic S ch oo ls

DEMO GENERAL NOTES

1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.

2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR

FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.

TC-E

TC-D

CABLE TO TC-D

CABLE TO TC-ACA

BL

E

TO

T

C- E

CA

BL

E

TO

T C-

A

CABLE TO TC-D

CABLE TO TC-A

CABLE

TO TC-E

N Upton MS Technology Plan - Unit B 1/16" = 1'-0"

SHEET NO.

ISSUE / DATE

DRAWN BY

PROJECT NO.

© 2023 AETD, ALL RIGHTS RESERVED.

N

EW

PO

RT

R

OA

D, S

UI

TE

#2

, P

OR

TA

GE

, M I 4

· 2

-2

-2

4 · A

ET

EC

H.

DE

SI

GN

2023-12-22 BIDS

CDB

T104B

Up ton

M S

Te ch no log y P lan

Un it B

SJPS2304-0300

Sa int

Jo se ph , M

I Inf ra str uc tur e U pg ra de s Sa int Jo se ph

P ub lic S ch oo ls

DEMO GENERAL NOTES

1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.

2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR

FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.

CA

BL

E

TO

T C-

D

CA

BL

E

TO

T

C- A

CA

BL

E

TO

T C-

D

CA

BL

E

TO

T

C- C

CA

BL

E

TO

T C-

E

CA

BL

E

TO

T

C- D

CA

BL

E

TO

T C-

D

CA

BL

E

TO

T

C- F

CA

BL

E

TO

T C-

A

CA

BL

E

TO

T

C- B

CA

BL

E

TO

T C-

B

CA

BL

E

TO

T

C- C

TC-B

TC-C

TC-A

TC-D

TC-E

N Saint Joseph HS Lower Floor Technology Plan 1/16" = 1'-0"

SHEET NO.

ISSUE / DATE

DRAWN BY

PROJECT NO.

© 2023 AETD, ALL RIGHTS RESERVED.

N

EW

PO

RT

R

OA

D, S

UI

TE

#2

, P

OR

TA

GE

, M I 4

· 2

-2

-2

4 · A

ET

EC

H.

DE

SI

GN

2023-12-22 BIDS

CDB

T105

Sa int

Jo se ph H

S Lo we r F loo r T ec hn olo gy

P lan

SJPS2304-0300

Sa int

Jo se ph , M

I Inf ra str uc tur e U pg ra de s Sa int Jo se ph

P ub lic S ch oo ls

DEMO GENERAL NOTES

1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.

2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR

FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.

CABLE TO TC-D

CABLE TO TC-F

CABLE TO TC-E

CABLE TO TC-F

TC-F

N Saint Joseph HS Main Floor Technology Plan - Unit D 1/16" = 1'-0"

SHEET NO.

ISSUE / DATE

DRAWN BY

PROJECT NO.

© 2023 AETD, ALL RIGHTS RESERVED.

N

EW

PO

RT

R

OA

D, S

UI

TE

#2

, P

OR

TA

GE

, M I 4

· 2

-2

-2

4 · A

ET

EC

H.

DE

SI

GN

2023-12-22 BIDS

CDB

T106A

Sa int

Jo se ph H

S Ma in Flo or T ec hn olo gy

P lan

Un it D

SJPS2304-0300

Sa int

Jo se ph , M

I Inf ra str uc tur e U pg ra de s Sa int Jo se ph

P ub lic S ch oo ls

DEMO GENERAL NOTES

1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.

2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR

FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.

3. FLOOR PLANS ARE NOT PROVIDED FOR THE CENTRAL OFFICE, TRANSPORTATION

BUILDING, PRESSBOX, AND STADIUM.

C A

D

E

F

G

CABLE

TO TC-A

CABLE TO TC-A

CABLE TO TC-I

CABLE

TO TC-I

CABLE TO TC-G

CABLE TO TC-I

CABLE TO TC-G

CABLE TO TC-I

TC-I

TC-G

N Saint Joseph HS Main Floor Technology Plan - Unit F & G 1/16" = 1'-0"

SHEET NO.

ISSUE / DATE

DRAWN BY

PROJECT NO.

© 2023 AETD, ALL RIGHTS RESERVED.

N

EW

PO

RT

R

OA

D, S

UI

TE

#2

, P

OR

TA

GE

, M I 4

· 2

-2

-2

4 · A

ET

EC

H.

DE

SI

GN

2023-12-22 BIDS

CDB

T106B

Sa int

Jo se ph H

S Ma in Flo or T ec hn olo gy

P lan

Un it F

G

SJPS2304-0300

Sa int

Jo se ph , M

I Inf ra str uc tur e U pg ra de s Sa int Jo se ph

P ub lic S ch oo ls

DEMO GENERAL NOTES

1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.

2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR

FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.

3. FLOOR PLANS ARE NOT PROVIDED FOR THE CENTRAL OFFICE, TRANSPORTATION

BUILDING, PRESSBOX, AND STADIUM.

C A

D

E

F

G

Typical Numbering for 48-Port Patch Panel 6"=1'-0"

01 03 05 07

02 04 06 08 10 12 14 16

09 11 13 15

18 20 22 24

17 19 21 23

26 28 30 32

25 27 29 31

34 36 38 40

33 35 37 39

42 44 46 48

41 43 45 47

A1

LABEL PATCH PANEL W/ COMPUTER PRINTED

SELF-ADHESIVE LABEL

48 PORT PATCH PANELS ARE NUMBERED VERTICALLY TO

MATCH PORT NUMBERING ORDER OF 48 PORT NETWORK

SWITCHES.

MAP LBP-2A LACING BAR 2U 48 PORT PATCH PANEL

NOTES:

1. USE LACING BAR AT REAR OF RACK TO KEEP ALL CABLES WITHIN

THE 2U SPACE OF THE PATCH PANEL TO ALLOW FOR INSTALLATION

OF THE SWITCHES ABOVE AND BELOW THE PATCH PANELS.

2. ALL CABLES FROM TOP ROW OF PATCH PANEL SHALL BE

ATTACHED TO TOP OF LACING BAR. LIKEWISE ALL CABLES FROM

BOTTOM ROW OF PATCH PANEL SHALL BE ATTACHED TO THE

BOTTOM OF THE LACING BAR.

Lacing Bar Detail

NTS

RELAY RACK RAILS

SWITCHES; KEEP THESE

AREAS FREE OF CABLES

SIDE VIEW

ISOMETRIC VIEW

SHEET NO.

ISSUE / DATE

DRAWN BY

PROJECT NO.

© 2023 AETD, ALL RIGHTS RESERVED.

N

EW

PO

RT

R

OA

D, S

UI

TE

#2

, P

OR

TA

GE

, M I 4

· 2

-2

-2

4 · A

ET

EC

H.

DE

SI

GN

2023-12-22 BIDS

CDB

T301

St ru ctu re d C ab lin g G en er al Inf or ma tio n

SJPS2304-0300

Sa int

Jo se ph , M

I Inf ra str uc tur e U pg ra de s Sa int Jo se ph

P ub lic S ch oo ls

CABLING SUPPORT LEGEND

SYMBOL DESCRIPTION

NOTES

ELECTRICAL LOW VOLTAGE

1-1/2" EMT SLEEVE W/ BUSHINGS

1-1/2" EMT SLEEVE W/ BUSHINGS; SEAL ENDS W/ FIRE-PROOF PUTTY

1-1/2" EMT SLEEVE W/ BUSHINGS (UP)

1-1/2" EMT SLEEVE W/ BUSHINGS (DOWN)

4" EMT SLEEVE W/ BUSHINGS

STI EZ-PATH SERIES 44 OR APPROVED EQUIVALENT

4" EMT SLEEVE W/ BUSHINGS (UP)

4" EMT SLEEVE W/ BUSHINGS (DOWN)

DATA DROP SYMBOL

#X

1. FOR ALL ALPHABETIC IDENTIFIERS THE LETTERS "O" AND "I" ARE NOT USED, TO

PREVENT POSSIBLE CONFUSION WITH THE NUMBERS ZERO AND ONE.

2. ALL ANALOG PHONE DROPS ARE TO BE TERMINATED IN TECH CLOSETS ON 110

PUNCH-DOWN BLOCKS MOUNTED ON BACKBOARD.

1. PROVIDE BLANK FACEPLATE.

2. 8/T302, 9/T302, OR 10/T302 DEPENDING ON THE NUMBER OF DROPS.

3. PROVIDE 20 FEET OF MAINTENANCE LOOP FOR CABLE.

4. TERMINATE ON 110 BLOCK IN TELECOMMUNICATIONS ROOM (TR).

5. TERMINATE ON PATCH PANEL IN TECH CLOSET.

6. ROUTE CABLES THROUGH FURNITURE TO FURNITURE FACEPLATE.

7. 3/T302 OR 4/T302 AS NEEDED.

8. MATCH ELEC. ROUGH-IN HEIGHT, TYPICALLY 8" ABOVE COUNTERTOP.

9. FACTORY CUT ROUGH-IN PROVIDED IN MODULAR FURNITURE.

10. PROVIDE ROUGH-IN IN FIXED CASEWORK.

11. COORDINATE LOCATION W/ EQUIPMENT SERVED.

12. COORDINATE FINAL LOCATION W/ BUILDING AUTOMATION SYSTEM CONTRACTOR.

13. USE 12/T302 OR 13/T302 DEPENDING ON THE NUMBER OF DROPS.

DATA LEGEND NOTES

STRUCTURED CABLING NOTES

#FB

#CH

#FR

#CW

AP

AP

P

W

F#

#FB

#CH

#FR

#CW

AP

AP

P

W

F#

#FB

#CH

#FR

#CW

AP

AP

P

W

F#

DATA LEGEND

SYMBOL

DESCRIPTION HEIGHT DATA DROPS

NEW WORK SURFACE MOUNT NOTES

EXISTING DEMO NEW ROUGH-IN FACEPLATE ROUGH-IN FACEPLATE ELECTRICAL LOW VOLTAGE

DATA DROP - BLANK 18"AFF 0 1/T302 SEE NOTES 6/T302 SEE NOTES 1

DATA DROP - (# INDICATED) 18"AFF # 1/T302 SEE NOTES 6/T302 SEE NOTES 2

DATA DROP - FLOOR BOX FLOOR # SEE ELEC. NOTES SEE NOTES N/A SEE NOTES 7 2

DATA DROP - COUNTERHEIGHT SEE ELEC. NOTES # 1/T302 SEE NOTES 6/T302 SEE NOTES 8 2

DATA DROP - FURNITURE 18"AFF # 5/T302 11/T302 5/T302 11/T302 9 6

DATA DROP - CASEWORK 18"AFF # 3/T302 SEE NOTES 7/T302 SEE NOTES 10 2

WIRELESS ACCESS POINT - CEILING MOUNT CEILING 1 N/A SEE NOTES N/A SEE NOTES 3, 13

WIRELESS ACCESS POINT - WALL MOUNT 144"AFF 1 1/T302 8/T302 6/T302 8/T302 3

ANALOG PHONE DROP N/A 1 N/A N/A N/A N/A 11 4

WALL PHONE 54"AFF 1 1/T302 14/T302 6/T302 14/T302 5

FACILITIES DROP SEE ELEC. NOTES # N/A SEE NOTES N/A SEE NOTES 12 13

INFORMATION TAG

DROP TYPE OR QUANTITY

UPS UPS UPS

RACK EQUIPMENT SHALL BE:

· DEMO

(1) UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK

LEVITON PATCH PANELS

· EXISTING

VERTICAL PDU

PANDUIT PATCH PANELS

· NEW

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-3000LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(4) NETWORK SWITCH - CISCO CATALYST 2960-X

(1) CISCO WIRELESS CONTROLLER

(1) ROUTER- CISCO CATALYST 2901

· EXISTING

(1) SITE SYNC TIME CONTROLLER

· NEW

(4) NETWORK SWITCH - MERAKI MS250-48

FIBER CONNECTIONS

A1-A 48-PORT PATCH PANEL

48-PORT POE SWITCH

A1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

UPS

FIBER CONNECTIONS

UPS

FIBER CONNECTIONS

C1-A 48-PORT PATCH PANEL

48-PORT POE SWITCH

PDU

UPS

FIBER CONNECTIONS FIBER CONNECTIONS

PDU

FIBER CONNECTIONS

RACK EQUIPMENT SHALL BE:

· DEMO

(1) UPS -

SURGE SUPPRESSORS - APC PNET1GB

· EXISTING

PANDUIT PATCH PANELS

· NEW

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-3000LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(4) NETWORK SWITCH - CISCO CATALYST 2960-X

· EXISTING

(1) SITE SYNC TIME CONTROLLER

· NEW

(4) NETWORK SWITCH - MERAKI MS250-48

RACK EQUIPMENT SHALL BE:

· DEMO

(1) UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK

FIBER PATCH PANEL

· EXISTING

PANDUIT PATCH PANELS

· NEW

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-1500LVRT2UXLN

(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL

FIBER TERMINATION

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(1) NETWORK SWITCH - CISCO CATALYST 2960-X

· NEW

(1) NETWORK SWITCH - MERAKI MS250-48

RACK EQUIPMENT SHALL BE:

· DEMO

(1) UPS -

· EXISTING

PANDUIT PATCH PANELS

· NEW

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-3000LVRT2UXLN

(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL

(1) SURGE PROTECTION CHASSIS - APC PRM24

(4) SURGE PROTECTION MODULE - APC PNETR6

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· EXISTING

(5) NETWORK SWITCH - MERAKI MS250-48

(1) SITESYNC IQ TIME CONTROLLER

RACK EQUIPMENT SHALL BE:

· DEMO

(1) UPS

LEVITON PATCH PANELS

FIBER PATCH PANEL

· EXISTING

VERTICAL PDU

PANDUIT PATCH PANELS

· NEW

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-3000LVRT2UXLN

(1) SURGE PROTECTION CHASSIS - APC PRM24

(2) SURGE PROTECTION MODULE - APC PNETR6

FIBER TERMINATION

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ

RELOCATE FIBER ENCLOSURE TO RACK FROM BACKERBOARD

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(1) CISCO WIRELESS CONTROLLER

(1) ROUTER - CISCO 2901

· EXISTING

(1) SITESYNC IQ TIME CONTROLLER

(4) NETWORK SWITCH - MERAKI MS250-48

RACK EQUIPMENT SHALL BE:

· DEMO

UPS - LIEBERT GXT3

LEVITON PATCH PANELS

· EXISTING

VERTICAL PDU

PANDUIT PATCH PANELS

· NEW

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-3000LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(1) ROUTER - CISCO 2901

· EXISTING

(1) SITE SYNC TIME CONTROLLER

(3) NETWORK SWITCH - MERAKI MS250-48

A1-C 48-PORT PATCH PANEL

48-PORT POE SWITCH

A1-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

TIME CONTROLLER

B1-A 48-PORT PATCH PANEL

48-PORT POE SWITCH

B1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

B1-C 48-PORT PATCH PANEL

48-PORT POE SWITCH

B1-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

TIME CONTROLLER

1 1 1

A1-A 48-PORT PATCH PANEL

48-PORT POE SWITCH

A1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

A1-C 48-PORT PATCH PANEL

48-PORT POE SWITCH

A1-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

TIME CONTROLLER

B1-A 48-PORT PATCH PANEL

48-PORT POE SWITCH

B1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

B1-C 48-PORT PATCH PANEL

48-PORT POE SWITCH

B1-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

B1-E 48-PORT PATCH PANEL

48-PORT POE SWITCH

TIME CONTROLLER

A1-A 48-PORT PATCH PANEL

48-PORT POE SWITCH

A1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

A1-C 48-PORT PATCH PANEL

48-PORT POE SWITCH

TIME CONTROLLER

EXISTING BACKBONE PATCH PANEL

EXISTING BACKBONE PATCH PANEL

EXISTING BACKBONE PATCH PANEL EXISTING BACKBONE PATCH PANEL

SURGE PROTECTOR

SURGE PROTECTOR

EXISTING BACKBONE PATCH PANEL

UPS

FIBER CONNECTIONS

PDU

RACK EQUIPMENT SHALL BE:

· DEMO

UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK

· EXISTING

PANDUIT PATCH PANELS

· NEW

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-3000LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· EXISTING

(1) SITE SYNC TIME CONTROLLER

(5) NETWORK SWITCH - MERAKI MS250-48

B1-A 48-PORT PATCH PANEL

48-PORT POE SWITCH

B1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

B1-C 48-PORT PATCH PANEL

48-PORT POE SWITCH

B1-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

B1-E 48-PORT PATCH PANEL

48-PORT POE SWITCH

TIME CONTROLLER

EXISTING BACKBONE PATCH PANEL

LAN FIBER CONNECTIONS

UPS

RACK EQUIPMENT SHALL BE:

· DEMO

LEVITON PATCH PANELS

· EXISTING

VERTICAL PDU

PANDUIT PATCH PANELS

CONSOLIDATE ALL LAN FIBER CONNECTIONS IN THIS RACK. LEAVE WAN FIBER

CONNECTIONS IN RACK 2

· NEW

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-3000LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(1) ROUTER - CISCO 2901

· EXISTING

(5) NETWORK SWITCH - MERAKI MS250-48

A1-A 48-PORT PATCH PANEL

48-PORT POE SWITCH

A1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

A1-C 48-PORT PATCH PANEL

48-PORT POE SWITCH

A1-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

A1-E 48-PORT PATCH PANEL

48-PORT POE SWITCH

EXISTING BACKBONE PATCH PANEL

RACK EQUIPMENT SHALL BE:

· DEMO

(2) UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK

LEVITON PATCH PANELS

· EXISTING

VERTICAL PDU

PANDUIT PATCH PANELS

CONSOLIDATE ALL LAN FIBER CONNECTIONS IN RACK 1. LEAVE WAN FIBER

CONNECTIONS IN THIS RACK

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(1) ROUTER - CISCO 2901

· EXISTING

(1) SYNOLOGY STORAGE DEVICE

(1) SITE SYNC TIME CONTROLLER

(1) SERVER - HP PROLIANT DL180 G6

(1) SERVER - HP PROLIANT DL380 G7

EXISTING SERVER

EXISTING SERVER

TIME CONTROLLER

WAN FIBER CONNECTIONS

EXISTING OWNER EQUIPMENT

SHEET NO.

ISSUE / DATE

DRAWN BY

PROJECT NO.

© 2023 AETD, ALL RIGHTS RESERVED.

N

EW

PO

RT

R

OA

D, S

UI

TE

#2

, P

OR

TA

GE

, M I 4

· 2

-2

-2

4 · A

ET

EC

H.

DE

SI

GN

2023-12-22 BIDS

CDB

T302

Te ch

R ac k E lev ati on s

SJPS2304-0300

Sa int

Jo se ph , M

I Inf ra str uc tur e U pg ra de s Sa int Jo se ph

P ub lic S ch oo ls

ENCLOSED SERVER RACK.

UPS. INSTALL IN BOTTOM OF RACK.

PDU.

MOVE SITESYNC IQ TIME CONTROLLER INTO RACK AT OWNER'S DIRECTION.

(2) EXISTING CONDUITS TO REMAIN

1. TECHNOLOGY CLOSETS SHALL BE NON-SPRINKLER SPACES.

2. GENERAL BUILDING HVAC SHALL NOT BE INSTALLED IN ANY TECHNOLOGY CLOSET. IF

ACTIVE COOLING IS REQUIRED, DEDICATED LOCAL SYSTEMS SHOULD BE INSTALLED

IN EACH TECH CLOSET.

3. ALL OUTLETS IN THE TECHNOLOGY CLOSETS SHOULD BE ON UPS-BACKED,

GENERATOR POWERED CIRCUITS.

4. EQUIPMENT MOUNTED ON BACKERBOARD SHALL MAINTAIN PROPER CLEARANCES

FOR OPERATION AND BE COORDINATED WITH OTHER DISCIPLINES PRIOR TO INSTALL

IF THERE IS A CONFLICT OF PLACEMENT.

5. RACK SIZES SHOWN ARE TYPICAL AND MAY NOT MATCH EXISTING RACK SIZES.

ACTUAL EQUIPMENT LAYOUT IN RACKS SHALL FOLLOW EQUIPMENT ORDER SHOWN IN

ELEVATIONS, ALONG WITH PROPER LABELING AND CABLE MANAGEMENT. CONFIRM

FINAL INSTALL LOCATION WITH OWNER.

6. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR

FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.

7. DEMO ALL ABANDONED EQUIPMENT AND CABLING, INCLUDING COAXIAL. DEMO CABLE

TO SOURCE.

8. DEMO ALL LEVITON PATCH PANELS AND REPLACE WITH PANDUIT PATCH PANELS.

9. DEMO ALL POTS PATCH PANELS, CABLING, ASSOCIATED 110 BLOCKS, AND OTHER

UNUSED POTS EQUIPMENT. DEMO CABLING TO SOURCE. PRIOR TO DEMO, CHECK

FOR DIAL TONE ON ANY LINES. NOTIFY OWNER AND AETD OF ANY DIAL TONE IF

DISCOVERED.

10. DEMO ALL UPS UNITS.

11. REMOVE ALL BACKERBOARD-MOUNTED FIBER ENCLOSURES AND RE-INSTALL

SPLICED CONNECTORS IN THEIR RESPECTIVE RACK'S FIBER ENCLOSURE.

12. SEE NETWORK DIAGRAM ON T306 FOR MORE DETAILS ON NETWORK ELECTRONICS

AND THEIR LOCATIONS.

13. RACK-MOUNTED EQUIPMENT SHALL BE INSTALLED WITH ENOUGH CLEARANCE SO

THAT THE RACK CAN FUNCTION PROPERLY. PATCH CORDS, POWER CORDS, AND

RELATED CABLING SHALL NOT PREVENT DOORS FROM CLOSING, RACK FROM

SWINGING, OR OTHER SIMILAR FUNCTIONS.

14. EXISTING COPPER BACKBONE, PATCH CORDS, JACKS, AND PATCH PANELS TO

REMAIN. RELOCATE PATCH PANELS TO THE TOP OF RACKS WHERE POSSIBLE.

TECH CLOSET GENERAL NOTES

TECH CLOSET KEYED NOTES

Brown ES TC-A Tech Rack Elevation

NTS

Brown ES TC-B Tech Rack Elevation

NTS

Brown ES TC-C Tech Rack Elevation

NTS

E.P. Clarke ES TC-A Tech Rack Elevation

NTS

E.P. Clarke ES TC-B Tech Rack Elevation

NTS

Lincoln ES TC-A Tech Rack Elevation

NTS

Lincoln ES TC-B Tech Rack Elevation

NTS

Upton MS TC-A Tech Rack 1 Elevation

NTS

Upton MS TC-A Tech Rack 2 Elevation

NTS

EXISTING OWNER EQUIPMENT

· EXISTING OWNER EQUIPMENT

· NOT IN SCOPE. VERIFY WITH OWNER.

RACK EQUIPMENT SHALL BE:

· EXISTING OWNER EQUIPMENT

· NOT IN SCOPE. VERIFY WITH OWNER.

1 1

EXISTING OWNER EQUIPMENT

FIBER CONNECTIONS

UPS

FIBER CONNECTIONS

PDU

UPS

FIBER CONNECTIONS

PDU

UPS

RACK EQUIPMENT SHALL BE:

· DEMO

UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK

· EXISTING

VERTICAL PDU

PANDUIT PATCH PANELS

· NEW

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-3000LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· EXISTING

(5) NETWORK SWITCH - MERAKI MS250-48

RACK EQUIPMENT SHALL BE:

· DEMO

UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK

LEVITON PATCH PANELS

· EXISTING

VERTICAL PDU

PANDUIT PATCH PANELS

· NEW

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-3000LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· EXISTING

(4) NETWORK SWITCH - MERAKI MS250-48

RACK EQUIPMENT SHALL BE:

· DEMO

WALL-MOUNTED TECH RACK

UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK

LEVITON PATCH PANELS

· EXISTING

PANDUIT PATCH PANELS

UPON DEMO OF RACK, LEAVE ATTACHED CONDUITS TO REMAIN.

· NEW

(1) WALL-MOUNTED TECH RACK - MIDDLE ATLANTIC DWR-24-32

(1) FRONT RACK DOOR - MIDDLE ATLANTIC FD-24

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-3000LVRT2UXLN

(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· EXISTING

(5) NETWORK SWITCH - MERAKI MS250-48

1 1 1

B1-A 48-PORT PATCH PANEL

48-PORT POE SWITCH

B1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

B1-C 48-PORT PATCH PANEL

48-PORT POE SWITCH

B1-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

B1-E 48-PORT PATCH PANEL

48-PORT POE SWITCH

C1-A 48-PORT PATCH PANEL

48-PORT POE SWITCH

C1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

C1-C 48-PORT PATCH PANEL

48-PORT POE SWITCH

C1-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

D1-A 48-PORT PATCH PANEL

48-PORT POE SWITCH

D1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

D1-C 48-PORT PATCH PANEL

48-PORT POE SWITCH

D1-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

D1-E 48-PORT PATCH PANEL

48-PORT POE SWITCH

EXISTING BACKBONE PATCH PANEL EXISTING BACKBONE PATCH PANEL

RACK EQUIPMENT SHALL BE:

· DEMO

(1) FLOOR STANDING UPS - LIEBERT NFINITY

· EXISTING

(1) VERTICAL PDU

· NEW

(1) FLOOR-STANDING UPS -

(1) RACK SHELF

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(1) WIRELESS CONTROLLER - CISCO CATALYST 5500

(2) CORE SWITCHES - CISCO CATALYST 4500-X

(5) NETWORK SWITCH - CISCO CATALYST 2960-X

(1) ROUTER - CISCO CATALYST C2901

· EXISTING

(1) FIREWALL

(1) IP PHONE BOX

· NEW

(2) CORE SWITCH - CISCO CATALYST C9500-40X

(5) NETWORK SWITCH - MERAKI MS250-48

FIBER CONNECTIONS

A4-A 48-PORT PATCH PANEL

CORE SWITCH

A4-B 48-PORT PATCH PANEL

CORE SWITCH

148-PORT POE SWITCH

48-PORT POE SWITCH

RACK EQUIPMENT SHALL BE:

· EXISTING

(1) VERTICAL PDU

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(4) NETWORK SWITCH - CISCO CATALYST 2960-X

· EXISTING

(1) BERRIEN RESA CPE - CISCO CATALYST 2960-S

(1) COMCAST CPE - CIENA 3916

· NEW

(4) NETWORK SWITCH - MERAKI MS250-48

FIBER CONNECTIONS

BERRIEN RESA CPE

RACK SHELF

A4-C 48-PORT PATCH PANEL

A4-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

48-PORT POE SWITCH

A4-E 48-PORT PATCH PANEL

48-PORT POE SWITCH

COMCAST CPE

A5-A 48-PORT PATCH PANEL

A5-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

48-PORT POE SWITCH

A5-C 48-PORT PATCH PANEL

A5-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

48-PORT POE SWITCH

EXISTING BACKBONE PATCH PANEL

FIBER CONNECTIONS

PDU

UPS

RACK EQUIPMENT SHALL BE:

· DEMO

UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK

LEVITON PATCH PANELS

· EXISTING

VERTICAL PDU

PANDUIT PATCH PANELS

· NEW

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-3000LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· EXISTING

(4) NETWORK SWITCH - MERAKI MS250-48

E1-A 48-PORT PATCH PANEL

48-PORT POE SWITCH

E1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

E1-C 48-PORT PATCH PANEL

48-PORT POE SWITCH

E1-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

RACK EQUIPMENT SHALL BE:

· EXISTING OWNER EQUIPMENT

· NOT IN SCOPE. VERIFY WITH OWNER.

EXISTING OWNER EQUIPMENT

SHEET NO.

ISSUE / DATE

DRAWN BY

PROJECT NO.

© 2023 AETD, ALL RIGHTS RESERVED.

N

EW

PO

RT

R

OA

D, S

UI

TE

#2

, P

OR

TA

GE

, M I 4

· 2

-2

-2

4 · A

ET

EC

H.

DE

SI

GN

2023-12-22 BIDS

CDB

T303

Te ch

R ac k E lev ati on s

SJPS2304-0300

Sa int

Jo se ph , M

I Inf ra str uc tur e U pg ra de s Sa int Jo se ph

P ub lic S ch oo ls

ENCLOSED SERVER RACK.

UPS. INSTALL IN BOTTOM OF RACK.

PDU.

MOVE SITESYNC IQ TIME CONTROLLER INTO RACK AT OWNER'S DIRECTION.

(2) EXISTING CONDUITS TO REMAIN

1. TECHNOLOGY CLOSETS SHALL BE NON-SPRINKLER SPACES.

2. GENERAL BUILDING HVAC SHALL NOT BE INSTALLED IN ANY TECHNOLOGY CLOSET. IF

ACTIVE COOLING IS REQUIRED, DEDICATED LOCAL SYSTEMS SHOULD BE INSTALLED

IN EACH TECH CLOSET.

3. ALL OUTLETS IN THE TECHNOLOGY CLOSETS SHOULD BE ON UPS-BACKED,

GENERATOR POWERED CIRCUITS.

4. EQUIPMENT MOUNTED ON BACKERBOARD SHALL MAINTAIN PROPER CLEARANCES

FOR OPERATION AND BE COORDINATED WITH OTHER DISCIPLINES PRIOR TO INSTALL

IF THERE IS A CONFLICT OF PLACEMENT.

5. RACK SIZES SHOWN ARE TYPICAL AND MAY NOT MATCH EXISTING RACK SIZES.

ACTUAL EQUIPMENT LAYOUT IN RACKS SHALL FOLLOW EQUIPMENT ORDER SHOWN IN

ELEVATIONS, ALONG WITH PROPER LABELING AND CABLE MANAGEMENT. CONFIRM

FINAL INSTALL LOCATION WITH OWNER.

6. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR

FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.

7. DEMO ALL ABANDONED EQUIPMENT AND CABLING, INCLUDING COAXIAL. DEMO CABLE

TO SOURCE.

8. DEMO ALL LEVITON PATCH PANELS AND REPLACE WITH PANDUIT PATCH PANELS.

9. DEMO ALL POTS PATCH PANELS, CABLING, ASSOCIATED 110 BLOCKS, AND OTHER

UNUSED POTS EQUIPMENT. DEMO CABLING TO SOURCE. PRIOR TO DEMO, CHECK

FOR DIAL TONE ON ANY LINES. NOTIFY OWNER AND AETD OF ANY DIAL TONE IF

DISCOVERED.

10. DEMO ALL UPS UNITS.

11. REMOVE ALL BACKERBOARD-MOUNTED FIBER ENCLOSURES AND RE-INSTALL

SPLICED CONNECTORS IN THEIR RESPECTIVE RACK'S FIBER ENCLOSURE.

12. SEE NETWORK DIAGRAM ON T306 FOR MORE DETAILS ON NETWORK ELECTRONICS

AND THEIR LOCATIONS.

13. RACK-MOUNTED EQUIPMENT SHALL BE INSTALLED WITH ENOUGH CLEARANCE SO

THAT THE RACK CAN FUNCTION PROPERLY. PATCH CORDS, POWER CORDS, AND

RELATED CABLING SHALL NOT PREVENT DOORS FROM CLOSING, RACK FROM

SWINGING, OR OTHER SIMILAR FUNCTIONS.

14. EXISTING COPPER BACKBONE, PATCH CORDS, JACKS, AND PATCH PANELS TO

REMAIN. RELOCATE PATCH PANELS TO THE TOP OF RACKS WHERE POSSIBLE.

TECH CLOSET GENERAL NOTES

TECH CLOSET KEYED NOTES

Upton MS TC-B Tech Rack Elevation

NTS

Upton MS TC-C Tech Rack Elevation

NTS

Upton MS TC-D Tech Rack Elevation

NTS

SJHS TC-A Tech Rack 1 Elevation

NTS

SJHS TC-A Tech Rack 2 Elevation

NTS

SJHS TC-A Tech Rack 3 Elevation

NTS

SJHS TC-A Tech Rack 4 Elevation

NTS

SJHS TC-A Tech Rack 5 Elevation

NTS

Upton MS TC-E Tech Rack Elevation

1 1

· EXISTING

FIBER CONNECTIONS

PANDUIT PATCH PANELS

(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL

· NEW

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-3000LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(5) NETWORK SWITCH - CISCO CATALYST 2960-X

· NEW

(5) NETWORK SWITCH - MERAKI MS250-48

FIBER CONNECTIONS

E1-A 48-PORT PATCH PANEL

E1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

48-PORT POE SWITCH

E1-C 48-PORT PATCH PANEL

E1-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

48-PORT POE SWITCH

E1-E 48-PORT PATCH PANEL

48-PORT POE SWITCH

PATCH PANEL

EXISTING PDU

RACK EQUIPMENT SHALL BE:

· EXISTING

FIBER CONNECTIONS

PANDUIT PATCH PANELS

(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL

· NEW

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-2000LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(2) NETWORK SWITCH - CISCO CATALYST 2960-X

· NEW

(2) NETWORK SWITCH - MERAKI MS250-48

FIBER CONNECTIONS

F1-A 48-PORT PATCH PANEL

F1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

48-PORT POE SWITCH

PATCH PANEL

EXISTING PDU

UPS UPS

RACK EQUIPMENT SHALL BE:

· DEMO

(1) LEVITON FIBER ENCLOSURE

LEVITON PATCH PANELS

· EXISTING

(1) VERTICAL PDU

· NEW

PANDUIT PATCH PANELS

(1) RACK SHELF

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(1) NETWORK SWITCH - CISCO CATALYST 2960-S

· EXISTING

WHITE BOX

· NEW

(1) NETWORK SWITCH - MERAKI MS250-24

FIBER CONNECTIONS

A1-A 48-PORT PATCH PANEL

24-PORT POE SWITCH

RACK EQUIPMENT SHALL BE:

· DEMO

LEVITON PATCH PANELS

· EXISTING

PANDUIT PATCH PANELS

· NEW

PANDUIT PATCH PANELS

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-1500LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(1) NETWORK SWITCH - CISCO CATALYST 2960-S

· NEW

(1) NETWORK SWITCH - MERAKI MS250-48

FIBER CONNECTIONS

J1-A 48-PORT PATCH PANEL

48-PORT POE SWITCH

RACK EQUIPMENT SHALL BE:

· EXISTING OWNER AND CPE EQUIPMENT

· NOT IN SCOPE. VERIFY WITH OWNER.

EXISTING OWNER AND CPE EQUIPMENT

RACK EQUIPMENT SHALL BE:

· EXISTING

PANDUIT PATCH PANELS

· NEW

(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-2000LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(3) NETWORK SWITCH - CISCO CATALYST 2960-X

· NEW

(3) NETWORK SWITCH - MERAKI MS250-48

PATCH PANEL

B1-A 48-PORT PATCH PANEL

48-PORT POE SWITCH

48-PORT POE SWITCH

RACK EQUIPMENT SHALL BE:

· EXISTING

FIBER CONNECTIONS

PANDUIT PATCH PANELS

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(5) NETWORK SWITCH - CISCO CATALYST 2960-X

· NEW

(5) NETWORK SWITCH - MERAKI MS250-48

FIBER CONNECTIONS

B1-B 48-PORT PATCH PANEL

B1-C 48-PORT PATCH PANEL

48-PORT POE SWITCH

C1-A 48-PORT PATCH PANEL

C1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

48-PORT POE SWITCH

C1-C 48-PORT PATCH PANEL

C1-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

48-PORT POE SWITCH

C1-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

UPS

RACK EQUIPMENT SHALL BE:

· EXISTING

FIBER CONNECTIONS

PANDUIT PATCH PANELS

(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL

· NEW

(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-3000LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(9) NETWORK SWITCH - CISCO CATALYST 2960-X

· NEW

(9) NETWORK SWITCH - MERAKI MS250-48

FIBER CONNECTIONS

D1-A 48-PORT PATCH PANEL

D1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

48-PORT POE SWITCH

D1-C 48-PORT PATCH PANEL

D1-D 48-PORT PATCH PANEL

48-PORT POE SWITCH

48-PORT POE SWITCH

D1-E 48-PORT PATCH PANEL

48-PORT POE SWITCH

PATCH PANEL

D1-F 48-PORT PATCH PANEL

48-PORT POE SWITCH

D1-G 48-PORT PATCH PANEL

D1-H 48-PORT PATCH PANEL

48-PORT POE SWITCH

48-PORT POE SWITCH

D1-J 48-PORT PATCH PANEL

48-PORT POE SWITCH

EXISTING PDU

PDU

UPS

RACK EQUIPMENT SHALL BE:

· DEMO

LEVITON PATCH PANELS

(1) FIBER CONNECTION

(1) RACK-MOUNT UPS - APC SMART

· EXISTING

FIBER CONNECTIONS

PANDUIT PATCH PANELS

(1) HORIZONTAL PDU - MIDDLE ATLANTIC PD-915R-PL

· NEW

PANDUIT PATCH PANELS

(1) RACK SHELF

(1) FIBER CONNECTION

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-2000LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(2) NETWORK SWITCH - CISCO CATALYST 2960-X

· NEW

(2) NETWORK SWITCH - MERAKI MS250-48

FIBER CONNECTIONS

F1-A 48-PORT PATCH PANEL

F1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

48-PORT POE SWITCH

PATCH PANEL

RACK SHELF

UPS

SHEET NO.

ISSUE / DATE

DRAWN BY

PROJECT NO.

© 2023 AETD, ALL RIGHTS RESERVED.

N

EW

PO

RT

R

OA

D, S

UI

TE

#2

, P

OR

TA

GE

, M I 4

· 2

-2

-2

4 · A

ET

EC

H.

DE

SI

GN

2023-12-22 BIDS

CDB

T304

Te ch

R ac k E lev ati on s

SJPS2304-0300

Sa int

Jo se ph , M

I Inf ra str uc tur e U pg ra de s Sa int Jo se ph

P ub lic S ch oo ls

ENCLOSED SERVER RACK.

UPS. INSTALL IN BOTTOM OF RACK.

PDU.

MOVE SITESYNC IQ TIME CONTROLLER INTO RACK AT OWNER'S DIRECTION.

(2) EXISTING CONDUITS TO REMAIN

1. TECHNOLOGY CLOSETS SHALL BE NON-SPRINKLER SPACES.

2. GENERAL BUILDING HVAC SHALL NOT BE INSTALLED IN ANY TECHNOLOGY CLOSET. IF

ACTIVE COOLING IS REQUIRED, DEDICATED LOCAL SYSTEMS SHOULD BE INSTALLED

IN EACH TECH CLOSET.

3. ALL OUTLETS IN THE TECHNOLOGY CLOSETS SHOULD BE ON UPS-BACKED,

GENERATOR POWERED CIRCUITS.

4. EQUIPMENT MOUNTED ON BACKERBOARD SHALL MAINTAIN PROPER CLEARANCES

FOR OPERATION AND BE COORDINATED WITH OTHER DISCIPLINES PRIOR TO INSTALL

IF THERE IS A CONFLICT OF PLACEMENT.

5. RACK SIZES SHOWN ARE TYPICAL AND MAY NOT MATCH EXISTING RACK SIZES.

ACTUAL EQUIPMENT LAYOUT IN RACKS SHALL FOLLOW EQUIPMENT ORDER SHOWN IN

ELEVATIONS, ALONG WITH PROPER LABELING AND CABLE MANAGEMENT. CONFIRM

FINAL INSTALL LOCATION WITH OWNER.

6. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR

FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.

7. DEMO ALL ABANDONED EQUIPMENT AND CABLING, INCLUDING COAXIAL. DEMO CABLE

TO SOURCE.

8. DEMO ALL LEVITON PATCH PANELS AND REPLACE WITH PANDUIT PATCH PANELS.

9. DEMO ALL POTS PATCH PANELS, CABLING, ASSOCIATED 110 BLOCKS, AND OTHER

UNUSED POTS EQUIPMENT. DEMO CABLING TO SOURCE. PRIOR TO DEMO, CHECK

FOR DIAL TONE ON ANY LINES. NOTIFY OWNER AND AETD OF ANY DIAL TONE IF

DISCOVERED.

10. DEMO ALL UPS UNITS.

11. REMOVE ALL BACKERBOARD-MOUNTED FIBER ENCLOSURES AND RE-INSTALL

SPLICED CONNECTORS IN THEIR RESPECTIVE RACK'S FIBER ENCLOSURE.

12. SEE NETWORK DIAGRAM ON T306 FOR MORE DETAILS ON NETWORK ELECTRONICS

AND THEIR LOCATIONS.

13. RACK-MOUNTED EQUIPMENT SHALL BE INSTALLED WITH ENOUGH CLEARANCE SO

THAT THE RACK CAN FUNCTION PROPERLY. PATCH CORDS, POWER CORDS, AND

RELATED CABLING SHALL NOT PREVENT DOORS FROM CLOSING, RACK FROM

SWINGING, OR OTHER SIMILAR FUNCTIONS.

14. EXISTING COPPER BACKBONE, PATCH CORDS, JACKS, AND PATCH PANELS TO

REMAIN. RELOCATE PATCH PANELS TO THE TOP OF RACKS WHERE POSSIBLE.

TECH CLOSET GENERAL NOTES

TECH CLOSET KEYED NOTES

SJHS TC-B Tech Rack Elevation

NTS

SJHS TC-C Tech Rack Elevation

NTS

SJHS TC-D Tech Rack Elevation

NTS

SJHS TC-E Tech Rack Elevation

NTS

SJHS TC-F Tech Rack Elevation

NTS

SJHS TC-G Tech Rack Elevation

NTS

SJHS TC-H (Staduim)Tech Rack Elevation

NTS

SJHS TC-I Tech Rack Elevation

NTS

SJHS TC-A Tech Rack 6 Elevation

· NEW

PANDUIT PATCH PANELS

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-1000LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(1) NETWORK SWITCH - CISCO CATALYST 2960-S

(1) ROUTER - CISCO CATALYST 2901

· NEW

(1) NETWORK SWITCH - MERAKI MS250-24

EXISTING PATCH PANEL

A1-A 48-PORT PATCH PANEL

24-PORT POE SWITCH

RACK EQUIPMENT SHALL BE:

· DEMO

(1) RACK-MOUNT UPS - ALTRONIX

· EXISTING

PANDUIT PATCH PANELS

(1) RACK-MOUNT PDU - APC

· NEW

PANDUIT PATCH PANELS

(1) RACK SHELF

(1) FIBER CONNECTION

(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT

GXT5-2000LVRT2UXLN

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(2) NETWORK SWITCH - CISCO CATALYST 9200L

(1) ROUTER - CISCO CATALYST 2901

· NEW

(2) NETWORK SWITCH - MERAKI MS250-48

A1-A 48-PORT PATCH PANEL

A1-B 48-PORT PATCH PANEL

48-PORT POE SWITCH

48-PORT POE SWITCH

EXISTING BACKBONE PATCH PANEL

EXISTING PDU

RACK SHELF

UPS UPS

RACK EQUIPMENT SHALL BE:

· EXISTING

FIBER CONNECTIONS

PANDUIT PATCH PANELS

FIBER TERMINATIONS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U

FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ

ALL PATCH PANELS SHALL BE:

PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET

48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)

24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)

STRAIN RELIEF BAR - PANDUIT SRB19D5BL

NETWORK ELECTRONICS SHALL BE:

· DEMO

(1) NETWORK SWITCH - CISCO CATALYST 2960-S

· NEW

(1) NETWORK SWITCH - MERAKI MS250-48

FIBER CONNECTIONS

K1-A 48-PORT PATCH PANEL

48-PORT POE SWITCH

EXISTING PDU

SHEET NO.

ISSUE / DATE

DRAWN BY

PROJECT NO.

© 2023 AETD, ALL RIGHTS RESERVED.

N

EW

PO

RT

R

OA

D, S

UI

TE

#2

, P

OR

TA

GE

, M I 4

· 2

-2

-2

4 · A

ET

EC

H.

DE

SI

GN

2023-12-22 BIDS

CDB

T305

Te ch

R ac k E lev ati on s

SJPS2304-0300

Sa int

Jo se ph , M

I Inf ra str uc tur e U pg ra de s Sa int Jo se ph

P ub lic S ch oo ls

ENCLOSED SERVER RACK.

UPS. INSTALL IN BOTTOM OF RACK.

PDU.

MOVE SITESYNC IQ TIME CONTROLLER INTO RACK AT OWNER'S DIRECTION.

(2) EXISTING CONDUITS TO REMAIN

1. TECHNOLOGY CLOSETS SHALL BE NON-SPRINKLER SPACES.

2. GENERAL BUILDING HVAC SHALL NOT BE INSTALLED IN ANY TECHNOLOGY CLOSET. IF

ACTIVE COOLING IS REQUIRED, DEDICATED LOCAL SYSTEMS SHOULD BE INSTALLED

IN EACH TECH CLOSET.

3. ALL OUTLETS IN THE TECHNOLOGY CLOSETS SHOULD BE ON UPS-BACKED,

GENERATOR POWERED CIRCUITS.

4. EQUIPMENT MOUNTED ON BACKERBOARD SHALL MAINTAIN PROPER CLEARANCES

FOR OPERATION AND BE COORDINATED WITH OTHER DISCIPLINES PRIOR TO INSTALL

IF THERE IS A CONFLICT OF PLACEMENT.

5. RACK SIZES SHOWN ARE TYPICAL AND MAY NOT MATCH EXISTING RACK SIZES.

ACTUAL EQUIPMENT LAYOUT IN RACKS SHALL FOLLOW EQUIPMENT ORDER SHOWN IN

ELEVATIONS, ALONG WITH PROPER LABELING AND CABLE MANAGEMENT. CONFIRM

FINAL INSTALL LOCATION WITH OWNER.

6. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR

FIRST RIGHT OF REFUSAL BEFORE…