SJPS2304-0300 Project Drawings_R.pdf
PDF 3 MB Posted
- Attached to
- Infrastructure Upgrades (SJPS2304-0300)
- Solicitation number
- RFP - SJS - 240000000770
- Issued by
- Berrien County, Bergland CDP, Michigan
About this file
This document is a set of project drawings and specifications for the Infrastructure Upgrades project (SJPS2304-0300) for the Saint Joseph Public Schools district in Saint Joseph, Michigan. The project involves the upgrade and replacement of structured cabling, network electronics, and related infrastructure across multiple school buildings in the district, including Brown Elementary School, E.P. Clarke Elementary School, Lincoln Elementary School, Upton Middle School, and Saint Joseph High School. Key elements of the work include the demolition of existing cabling and equipment, the installation of new structured cabling and patch panels, the deployment of new network switches and wireless access points, and the configuration of the new network infrastructure. The project drawings provide detailed information on the scope of work, equipment specifications, and cabling requirements for each facility.
Regarding pricing and contract terms, the document does not provide specific pricing information, but it does note that the project is being funded through the district's capital improvement budget. The contract is expected to be awarded through a competitive bidding process, with the successful contractor responsible for providing all necessary labor, materials, and equipment to complete the infrastructure upgrades. The contract term and any potential renewal options are not specified in the provided documentation.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SJPS2304-0300 Advertisement For Bids .pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET NO.
ISSUE / DATE
DRAWN BY
PROJECT NO.
© 2023 AETD, ALL RIGHTS RESERVED.
N
EW
PO
RT
R
OA
D, S
UI
TE
5, PO
RT
AG
E, M I 4
· 2
-2
-2
4 · A
ET
EC
H.
DE
SI
GN
2023-12-22 BIDS
CDB
TG01
Tit le
Sh ee t
SJPS2304-0300
Sa int
Jo se ph , M
I Inf ra str uc tur e U pg ra de s Sa int Jo se ph
P ub lic S ch oo ls
Infrastructure Upgrades Saint Joseph Public Schools
Saint Joseph, MI
Project Number: SJPS2304-0300
JACK; SEE LEGEND FOR COLOR
A1-A01
COMPUTER PRINTED SELF-LAMINATED
CABLE WRAP LABEL WITHIN 6 INCHES OF
CABLE END
Cabling Label Detail 6"=1'-0"
SHEET NO.
ISSUE / DATE
DRAWN BY
PROJECT NO.
© 2023 AETD, ALL RIGHTS RESERVED.
N
EW
PO
RT
R
OA
D, S
UI
TE
5, PO
RT
AG
E, M I 4
· 2
-2
-2
4 · A
ET
EC
H.
DE
SI
GN
2023-12-22 BIDS
CDB
TG02
Te ch no log y G en er al
Inf or ma tio n
SJPS2304-0300
Sa int
Jo se ph , M
I Inf ra str uc tur e U pg ra de s Sa int Jo se ph
P ub lic S ch oo ls
ABBREVIATIONS
ABBREVIATION TERMINOLOGY
AC ACCESS CONTROL
AFF ABOVE FINISH FLOOR
ATS AUTOMATIC TRANSFER SWITCH
AV OR A/V AUDIO / VIDEO
BAS BUILDING AUTOMATION SYSTEM
BB BACKERBOARD
CIP CAST IN PLACE
CLG CEILING
CP CONSOLIDATION POINT
EC ELECTRICAL CONTRACTOR
EF ENTRANCE FACILITY
EMT ELECTRICAL METALLIC TUBING
EQ EQUAL
EQUIV EQUIVALENT
ER EQUIPMENT ROOM
EXIST EXISTING
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GRD GROUND
HC HORIZONTAL CROSS-CONNECT
IC INTERMEDIATE CROSS-CONNECT
MC MAIN CROSS-CONNECT
NIC NOT IN CONTRACT
OC ON CENTER
OSP OUTSIDE PLANT
PBB PRIMARY BONDING BUSBAR
PT POKE-THROUGH
RBC RACK BONDING CONDUCTOR
SBB SECONDARY BONDING BUSBAR
SC STRUCTURED CABLING
SCC STRUCTURED CABLING CONTRACTOR
TBB TELECOMMUNICATIONS BONDING BACKBONE
TE TELECOMMUNICATIONS ENCLOSURE
TEBC TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR
TO TELECOMMUNICATIONS OUTLET
TR TELECOMMUNICATIONS ROOM
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER SUPPLY
WA WORK AREA
A1-A01
1/8 " M
IN
JACK NUMBER (01 TO 48)
PATCH PANEL ID (A TO Z)
RACK ID (1 OR 2 DIGITS)
CLOSET ID (A TO Z)
AA-A01
1/8 " M
IN
POSITION NUMBER (01 TO 24)
110 BLOCK ID (A TO Z)
BACKBOARD ZONE (A TO Z)
CLOSET ID (A TO Z)
Numbering for 110-Block Term. Drops
NTS
Numbering for Typical Data Drops
NTS
RFI ## #
X# T###
DETAIL NUMBER
SHEET NUMBER WHERE
DETAIL IS LOCATED
ADDENDUM NUMBER BULLETIN NUMBER
RFI OR TSI NUMBER KEYED NOTE NUMBER
RFI OR TSI
DETAIL CALLOUT
NTS
ADDENDUM TAG
NTS
BULLETIN TAG
NTS
RFI OR TSI TAG
NTS
KEYED NOTE TAG
NTS
REVISION CLOUD
NTS
NOTES:
1. USED ON TECHNOLOGY FLOOR PLANS TO
REFERENCE A DETAIL, ELEVATION, OR SYSTEM
OF COMPONENTS ELEVATION ON ANOTHER
SHEET.
NOTES:
1. LOCATED NEXT TO A REVISION CLOUD FOR ANY
REVISIONS AFTER BIDS HAVE BEEN RELEASED,
BEFORE CONTRACT HAS BEEN AWARDED.
NOTES:
1. LOCATED NEXT TO A REVISION CLOUD FOR ANY
REVISIONS AFTER CONTRACT HAS BEEN
AWARDED.
NOTES:
1. DRAWN AROUND REVISION AREA RELATED TO
ANY ADDENDUM OR BULLETIN.
NOTES:
1. REFERENCE TO CORRESPONDING NOTES ON
SAME SHEET THAT HAVE MORE INFORMATION
RELATED TO SYMBOL.
NOTES:
1. RFI (REQUEST FOR INFORMATION) INDICATES A
REVISION AND CORRESPONDING NOTE THAT
DOES NOT AFFECT BUDGET THAT WAS NOT
INITIATED BY TECHNOLOGY CONTRACTOR.
2. TSI (TECHNOLOGY INFORMATION) TAG
INDICATES A REVISION AND CORRESPONDING
NOTE THAT DOES NOT AFFECT BUDGET.
EXISTING TECHNOLOGY
NTS
TECHNOLOGY IDENTIFIER
NOTES:
1. THIN SOLID LINE REPRESENTS EXISTING
TECHNOLOGY TO REMAIN. NO WORK REQUIRED
AT SPECIFIC LOCATION, BUT COULD REQUIRE
EXISTING CABLING AND/OR DEVICES TO BE
MAINTAINED DURING CONSTRUCTION TO
SUPPORT SPECIFIC DEVICE. SEE DRAWINGS
FOR MORE DETAIL.
DEMO TECHNOLOGY
NTS
TECHNOLOGY IDENTIFIER
NOTES:
1. HEAVY DASHED LINE REPRESENTS EXISTING
TECHNOLOGY TO BE REMOVED. COULD
REQUIRE DEMOLITION OF ROUGH-IN, CABLING,
FACEPLATE AND/OR DEVICE. DEVICE MAY NEED
TO BE SALVAGED FOR REINSTALLATION OR
TURNED OVER TO OWNER. SEE DRAWINGS FOR
MORE DETAIL.
NEW TECHNOLOGY
NTS
TECHNOLOGY IDENTIFIER
NOTES:
1. HEAVY SOLID LINE REPRESENTS NEW
TECHNOLOGY. COMPLETE INSTALLATION
OFTEN REQUIRES ROUGH-IN, CABLING,
FACEPLATE AND/OR DEVICE. SEE DRAWINGS
FOR MORE DETAIL.
CM
LR
V
8K
CS
D
H
S
X
F
N
8S
RISER LEGEND
SYMBOL DESCRIPTION
ZONE OR AREA
BY OTHERS OR EXISTING
NEW
OPTIONAL
PLUG INTO 120V RECEPTACLE
CONNECT TO GROUND
WIFI CONNECTION
GENERIC RF CONNECTION
BLUETOOTH CONNCETION
CELLULAR CONNECTION
8P8C (RJ45) NETWORK
KEYED 8P8C (RJ45)
SHIELDED 8P8C (RJ45)
COMPONENT VIDEO
COMPOSITE VIDEO
SVIDEO
HD15 (VGA) VIDEO
DVI VIDEO
HDMI VIDEO
RED & WHITE RCA AUDIO
3.5MM STEREO AUDIO
1/4" STEREO AUDIO
XLR MICROPHONE
COAX TYPE "F"
NEUTRIK NL4MP
USBU
PATCH CORD LEGEND
PURPOSE
TR WORK
AREA
COLOR
GENERAL DATA WHITE
WIRELESS ACCESS POINTS YELLOW
FACILITIES GREEN
SURVEILLANCE CAMERAS VIOLET
PAGING WHITE
AV WHITE
FIBER LEGEND
PURPOSE TYPE RATING MANUFACTURER MODEL
OUTSIDE PLANT OUTSIDE PLANT N/A GENERAL CABLE AQ***4M1A-DT
BACKBONE INDOOR/OUTDOOR PLENUM GENERAL CABLE AP***1ANU.BK
CABLING AND JACK LEGEND
PURPOSE
PREMISE CABLING JACKS
COLOR RATING MANUFACTURER MODEL TR COLOR WA COLOR MANUFACTURER MODEL SHIELDED
COPPER BACKBONE
BLUE PLENUM GENERAL CABLE GENSPEED 6000
RED RED
PANDUIT
CJ688TGRD CJS688TGRDY
RESERVED ORANGE ORANGE CJ688TGOR
WIRELESS ACCESS POINTS YELLOW YELLOW CJ688TGYL CJS688TGYLY
FACILITIES GREEN GREEN CJ688TGGR CJS688TGGRY
SPECIAL NETWORK BLUE BLUE CJ688TGBU CJS688TGBUY
SURVEILLANCE CAMERAS VIOLET VIOLET CJ688TGVL CJS688TGVLY
RESERVED BACK BLACK CJ688TGBL CJS688TGY
POTS LINES GRAY GRAY CJ688TGIG
GENERAL PURPOSE WHITE WHITE CJ688TGWH CJS688TGWHY
1. FOR DROPS INSTALLED ABOVE ACCESSIBLE CEILING, PROVIDE MAINTENANCE LOOP
AS INDICATED ON TECHNOLOGY SYMBOL LEGEND. CABLE SHALL BE NEATLY COILED
IN AN "S" LOOP AND SECURED TO BUILDING STRUCTURE AT DROP LOCATION FOR
EASY RELOCATION.
2. LOAD THE LATEST AVAILABLE STABLE FIRMWARE FOR ALL DEVICES WHEN THEY ARE
SUPPLIED FOR THIS PROJECT.
3. IN THE EVENT OF A DISCREPANCY BETWEEN TECHNOLOGY PLANS AND OTHER
DISCIPLINES, CONTRACTOR SHALL SUBMIT AN RFI FOR CLARIFICATION.
4. LABEL CABLES ACCORDING TO "CABLING LABEL DETAIL" ON THIS PAGE.
GENERAL NOTES
LIST OF DRAWINGS
NUMBER TITLE
TG01 Title Sheet
TG02 Technology General Information
T101 Brown ES Technology Plan - Composite
T102 E.P. Clarke ES Technology Plan - Composite
T103 Lincoln ES First Floor Technology Plan - Composite
T104A Upton MS Technology Plan - Unit A
T104B Upton MS Technology Plan - Unit B
T105 Saint Joseph HS Lower Floor Technology Plan
T106A Saint Joseph HS Main Floor Technology Plan - Unit D
T106B Saint Joseph HS Main Floor Technology Plan - Unit F & G
T301 Structured Cabling General Information
T302 Tech Rack Elevations
T303 Tech Rack Elevations
T304 Tech Rack Elevations
T305 Tech Rack Elevations
T306 Structured Cabling Details & Risers
T307 Structured Cabling Support Information
T308 Network Diagram
WORK SCOPE LEGEND
CA
TE
GO
RY DEFINITION OF WORK
EL
EC
TR
IC
AL
ST
RU
CT
. C
AB
LIN
G
OW
NE
R
NE
TW
OR
K
EL
EC
CO
NT
RA
CT
OR
GE
NE
RA
L D
AT
A
DEMO EXISTING STRUCTURED CABLING EQUIPMENT (RETURN TO OWNER) X
DEMO EXISTING STRUCTURED CABLING BACKBONE AND PREMISE CABLING X
DEMO EXISTING ACCESS POINTS (RETURN TO OWNER) X
PROVIDE ADAPTERS FOR RACEWAY, FLOORBOXES, ETC., TO ACCOMMODATE STANDARD
FACEPLATES AND JACKS X
PROVIDE STRUCTURED CABLING BACKBONE CABLING (AND TERMINATION) X
PROVIDE STRUCTURED CABLING PREMISE CABLING (AND TERMINATION) X
PROVIDE STRUCTURED CABLING PATCH CORDS X
SUPPLY NETWORK ELECTRONICS X
CONFIGURE NETWORK ELECTRONICS X
INSTALL NETWORK ELECTRONICS X
CONNECT TECH EQUIPMENT TO GROUNDING BUSBARS X
SUPPLY HARD-WIRED UPSES X
INSTALL HARD-WIRED UPSES X
CONNECT HARD-WIRED UPSES TO POWER X
PROVIDE IP ADDRESSES FOR NETWORK CONNECTED DEVICES X
CONFIGURE VLANS X
SB 8'
MB 4'
SB 8'
MB 4'
44_H1004A94
TC-C
TC-A
CA
BL
E
TO
T C-
A
CA
BL
E
TO
T
C- B
CA
BL
E
TO
T C-
A
CA
BL
E
TO
T
C- B
CABLE
TO TC-C
CABLE
TO TC-B
CABLE TO TC-C
CABLE TO TC-B
TC-B
N Brown ES Technology Plan - Composite 1/16" = 1'-0"
SHEET NO.
ISSUE / DATE
DRAWN BY
PROJECT NO.
© 2023 AETD, ALL RIGHTS RESERVED.
N
EW
PO
RT
R
OA
D, S
UI
TE
#2
, P
OR
TA
GE
, M I 4
· 2
-2
-2
4 · A
ET
EC
H.
DE
SI
GN
2023-12-22 BIDS
CDB
T101
Br ow n E S
Te ch no log y P lan
Co mp os ite
SJPS2304-0300
Sa int
Jo se ph , M
I Inf ra str uc tur e U pg ra de s Sa int Jo se ph
P ub lic S ch oo ls
DEMO GENERAL NOTES
1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.
2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR
FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.
3. FLOOR PLANS ARE NOT PROVIDED FOR THE CENTRAL OFFICE, TRANSPORTATION
BUILDING, PRESSBOX, AND STADIUM.
TC-A
TC-B
CABLE TO TC-B
CABLE TO TC-A
CA
BL
E
TO
T C-
B
CA
BL
E
TO
T
C- A
N E.P. Clarke ES Technology Plan - Composite 3/32" = 1'-0"
SHEET NO.
ISSUE / DATE
DRAWN BY
PROJECT NO.
© 2023 AETD, ALL RIGHTS RESERVED.
N
EW
PO
RT
R
OA
D, S
UI
TE
#2
, P
OR
TA
GE
, M I 4
· 2
-2
-2
4 · A
ET
EC
H.
DE
SI
GN
2023-12-22 BIDS
CDB
T102
E.
P.
C lar ke E
S Te ch no log y P lan
Co mp os ite
SJPS2304-0300
Sa int
Jo se ph , M
I Inf ra str uc tur e U pg ra de s Sa int Jo se ph
P ub lic S ch oo ls
DEMO GENERAL NOTES
1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.
2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR
FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.
N Lincoln ES First Floor Technology Plan - Composite 3/32" = 1'-0"
SHEET NO.
ISSUE / DATE
DRAWN BY
PROJECT NO.
© 2023 AETD, ALL RIGHTS RESERVED.
N
EW
PO
RT
R
OA
D, S
UI
TE
#2
, P
OR
TA
GE
, M I 4
· 2
-2
-2
4 · A
ET
EC
H.
DE
SI
GN
2023-12-22 BIDS
CDB
T103
Lin co ln
ES
F irs t F loo r T ec hn olo gy P lan
Co mp os ite
SJPS2304-0300
Sa int
Jo se ph , M
I Inf ra str uc tur e U pg ra de s Sa int Jo se ph
P ub lic S ch oo ls
DEMO GENERAL NOTES
1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.
2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR
FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.
02 Exist 12
TC-C
TC-A
CABLE TO TC-B
CABLE TO TC-A
CABLE TO TC-B
CABLE TO TC-C
CABLE
TO TC-C
CABLE
TO TC-E
N Upton MS Technology Plan - Unit A 3/32" = 1'-0"
SHEET NO.
ISSUE / DATE
DRAWN BY
PROJECT NO.
© 2023 AETD, ALL RIGHTS RESERVED.
N
EW
PO
RT
R
OA
D, S
UI
TE
#2
, P
OR
TA
GE
, M I 4
· 2
-2
-2
4 · A
ET
EC
H.
DE
SI
GN
2023-12-22 BIDS
CDB
T104A
Up ton
M S
Te ch no log y P lan
Un it A
SJPS2304-0300
Sa int
Jo se ph , M
I Inf ra str uc tur e U pg ra de s Sa int Jo se ph
P ub lic S ch oo ls
DEMO GENERAL NOTES
1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.
2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR
FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.
TC-E
TC-D
CABLE TO TC-D
CABLE TO TC-ACA
BL
E
TO
T
C- E
CA
BL
E
TO
T C-
A
CABLE TO TC-D
CABLE TO TC-A
CABLE
TO TC-E
N Upton MS Technology Plan - Unit B 1/16" = 1'-0"
SHEET NO.
ISSUE / DATE
DRAWN BY
PROJECT NO.
© 2023 AETD, ALL RIGHTS RESERVED.
N
EW
PO
RT
R
OA
D, S
UI
TE
#2
, P
OR
TA
GE
, M I 4
· 2
-2
-2
4 · A
ET
EC
H.
DE
SI
GN
2023-12-22 BIDS
CDB
T104B
Up ton
M S
Te ch no log y P lan
Un it B
SJPS2304-0300
Sa int
Jo se ph , M
I Inf ra str uc tur e U pg ra de s Sa int Jo se ph
P ub lic S ch oo ls
DEMO GENERAL NOTES
1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.
2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR
FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.
CA
BL
E
TO
T C-
D
CA
BL
E
TO
T
C- A
CA
BL
E
TO
T C-
D
CA
BL
E
TO
T
C- C
CA
BL
E
TO
T C-
E
CA
BL
E
TO
T
C- D
CA
BL
E
TO
T C-
D
CA
BL
E
TO
T
C- F
CA
BL
E
TO
T C-
A
CA
BL
E
TO
T
C- B
CA
BL
E
TO
T C-
B
CA
BL
E
TO
T
C- C
TC-B
TC-C
TC-A
TC-D
TC-E
N Saint Joseph HS Lower Floor Technology Plan 1/16" = 1'-0"
SHEET NO.
ISSUE / DATE
DRAWN BY
PROJECT NO.
© 2023 AETD, ALL RIGHTS RESERVED.
N
EW
PO
RT
R
OA
D, S
UI
TE
#2
, P
OR
TA
GE
, M I 4
· 2
-2
-2
4 · A
ET
EC
H.
DE
SI
GN
2023-12-22 BIDS
CDB
T105
Sa int
Jo se ph H
S Lo we r F loo r T ec hn olo gy
P lan
SJPS2304-0300
Sa int
Jo se ph , M
I Inf ra str uc tur e U pg ra de s Sa int Jo se ph
P ub lic S ch oo ls
DEMO GENERAL NOTES
1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.
2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR
FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.
CABLE TO TC-D
CABLE TO TC-F
CABLE TO TC-E
CABLE TO TC-F
TC-F
N Saint Joseph HS Main Floor Technology Plan - Unit D 1/16" = 1'-0"
SHEET NO.
ISSUE / DATE
DRAWN BY
PROJECT NO.
© 2023 AETD, ALL RIGHTS RESERVED.
N
EW
PO
RT
R
OA
D, S
UI
TE
#2
, P
OR
TA
GE
, M I 4
· 2
-2
-2
4 · A
ET
EC
H.
DE
SI
GN
2023-12-22 BIDS
CDB
T106A
Sa int
Jo se ph H
S Ma in Flo or T ec hn olo gy
P lan
Un it D
SJPS2304-0300
Sa int
Jo se ph , M
I Inf ra str uc tur e U pg ra de s Sa int Jo se ph
P ub lic S ch oo ls
DEMO GENERAL NOTES
1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.
2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR
FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.
3. FLOOR PLANS ARE NOT PROVIDED FOR THE CENTRAL OFFICE, TRANSPORTATION
BUILDING, PRESSBOX, AND STADIUM.
C A
D
E
F
G
CABLE
TO TC-A
CABLE TO TC-A
CABLE TO TC-I
CABLE
TO TC-I
CABLE TO TC-G
CABLE TO TC-I
CABLE TO TC-G
CABLE TO TC-I
TC-I
TC-G
N Saint Joseph HS Main Floor Technology Plan - Unit F & G 1/16" = 1'-0"
SHEET NO.
ISSUE / DATE
DRAWN BY
PROJECT NO.
© 2023 AETD, ALL RIGHTS RESERVED.
N
EW
PO
RT
R
OA
D, S
UI
TE
#2
, P
OR
TA
GE
, M I 4
· 2
-2
-2
4 · A
ET
EC
H.
DE
SI
GN
2023-12-22 BIDS
CDB
T106B
Sa int
Jo se ph H
S Ma in Flo or T ec hn olo gy
P lan
Un it F
G
SJPS2304-0300
Sa int
Jo se ph , M
I Inf ra str uc tur e U pg ra de s Sa int Jo se ph
P ub lic S ch oo ls
DEMO GENERAL NOTES
1. DEMO ALL ABANDONED CABLES BACK TO THEIR SOURCE.
2. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR
FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.
3. FLOOR PLANS ARE NOT PROVIDED FOR THE CENTRAL OFFICE, TRANSPORTATION
BUILDING, PRESSBOX, AND STADIUM.
C A
D
E
F
G
Typical Numbering for 48-Port Patch Panel 6"=1'-0"
01 03 05 07
02 04 06 08 10 12 14 16
09 11 13 15
18 20 22 24
17 19 21 23
26 28 30 32
25 27 29 31
34 36 38 40
33 35 37 39
42 44 46 48
41 43 45 47
A1
LABEL PATCH PANEL W/ COMPUTER PRINTED
SELF-ADHESIVE LABEL
48 PORT PATCH PANELS ARE NUMBERED VERTICALLY TO
MATCH PORT NUMBERING ORDER OF 48 PORT NETWORK
SWITCHES.
MAP LBP-2A LACING BAR 2U 48 PORT PATCH PANEL
NOTES:
1. USE LACING BAR AT REAR OF RACK TO KEEP ALL CABLES WITHIN
THE 2U SPACE OF THE PATCH PANEL TO ALLOW FOR INSTALLATION
OF THE SWITCHES ABOVE AND BELOW THE PATCH PANELS.
2. ALL CABLES FROM TOP ROW OF PATCH PANEL SHALL BE
ATTACHED TO TOP OF LACING BAR. LIKEWISE ALL CABLES FROM
BOTTOM ROW OF PATCH PANEL SHALL BE ATTACHED TO THE
BOTTOM OF THE LACING BAR.
Lacing Bar Detail
NTS
RELAY RACK RAILS
SWITCHES; KEEP THESE
AREAS FREE OF CABLES
SIDE VIEW
ISOMETRIC VIEW
SHEET NO.
ISSUE / DATE
DRAWN BY
PROJECT NO.
© 2023 AETD, ALL RIGHTS RESERVED.
N
EW
PO
RT
R
OA
D, S
UI
TE
#2
, P
OR
TA
GE
, M I 4
· 2
-2
-2
4 · A
ET
EC
H.
DE
SI
GN
2023-12-22 BIDS
CDB
T301
St ru ctu re d C ab lin g G en er al Inf or ma tio n
SJPS2304-0300
Sa int
Jo se ph , M
I Inf ra str uc tur e U pg ra de s Sa int Jo se ph
P ub lic S ch oo ls
CABLING SUPPORT LEGEND
SYMBOL DESCRIPTION
NOTES
ELECTRICAL LOW VOLTAGE
1-1/2" EMT SLEEVE W/ BUSHINGS
1-1/2" EMT SLEEVE W/ BUSHINGS; SEAL ENDS W/ FIRE-PROOF PUTTY
1-1/2" EMT SLEEVE W/ BUSHINGS (UP)
1-1/2" EMT SLEEVE W/ BUSHINGS (DOWN)
4" EMT SLEEVE W/ BUSHINGS
STI EZ-PATH SERIES 44 OR APPROVED EQUIVALENT
4" EMT SLEEVE W/ BUSHINGS (UP)
4" EMT SLEEVE W/ BUSHINGS (DOWN)
DATA DROP SYMBOL
#X
1. FOR ALL ALPHABETIC IDENTIFIERS THE LETTERS "O" AND "I" ARE NOT USED, TO
PREVENT POSSIBLE CONFUSION WITH THE NUMBERS ZERO AND ONE.
2. ALL ANALOG PHONE DROPS ARE TO BE TERMINATED IN TECH CLOSETS ON 110
PUNCH-DOWN BLOCKS MOUNTED ON BACKBOARD.
1. PROVIDE BLANK FACEPLATE.
2. 8/T302, 9/T302, OR 10/T302 DEPENDING ON THE NUMBER OF DROPS.
3. PROVIDE 20 FEET OF MAINTENANCE LOOP FOR CABLE.
4. TERMINATE ON 110 BLOCK IN TELECOMMUNICATIONS ROOM (TR).
5. TERMINATE ON PATCH PANEL IN TECH CLOSET.
6. ROUTE CABLES THROUGH FURNITURE TO FURNITURE FACEPLATE.
7. 3/T302 OR 4/T302 AS NEEDED.
8. MATCH ELEC. ROUGH-IN HEIGHT, TYPICALLY 8" ABOVE COUNTERTOP.
9. FACTORY CUT ROUGH-IN PROVIDED IN MODULAR FURNITURE.
10. PROVIDE ROUGH-IN IN FIXED CASEWORK.
11. COORDINATE LOCATION W/ EQUIPMENT SERVED.
12. COORDINATE FINAL LOCATION W/ BUILDING AUTOMATION SYSTEM CONTRACTOR.
13. USE 12/T302 OR 13/T302 DEPENDING ON THE NUMBER OF DROPS.
DATA LEGEND NOTES
STRUCTURED CABLING NOTES
#FB
#CH
#FR
#CW
AP
AP
P
W
F#
#FB
#CH
#FR
#CW
AP
AP
P
W
F#
#FB
#CH
#FR
#CW
AP
AP
P
W
F#
DATA LEGEND
SYMBOL
DESCRIPTION HEIGHT DATA DROPS
NEW WORK SURFACE MOUNT NOTES
EXISTING DEMO NEW ROUGH-IN FACEPLATE ROUGH-IN FACEPLATE ELECTRICAL LOW VOLTAGE
DATA DROP - BLANK 18"AFF 0 1/T302 SEE NOTES 6/T302 SEE NOTES 1
DATA DROP - (# INDICATED) 18"AFF # 1/T302 SEE NOTES 6/T302 SEE NOTES 2
DATA DROP - FLOOR BOX FLOOR # SEE ELEC. NOTES SEE NOTES N/A SEE NOTES 7 2
DATA DROP - COUNTERHEIGHT SEE ELEC. NOTES # 1/T302 SEE NOTES 6/T302 SEE NOTES 8 2
DATA DROP - FURNITURE 18"AFF # 5/T302 11/T302 5/T302 11/T302 9 6
DATA DROP - CASEWORK 18"AFF # 3/T302 SEE NOTES 7/T302 SEE NOTES 10 2
WIRELESS ACCESS POINT - CEILING MOUNT CEILING 1 N/A SEE NOTES N/A SEE NOTES 3, 13
WIRELESS ACCESS POINT - WALL MOUNT 144"AFF 1 1/T302 8/T302 6/T302 8/T302 3
ANALOG PHONE DROP N/A 1 N/A N/A N/A N/A 11 4
WALL PHONE 54"AFF 1 1/T302 14/T302 6/T302 14/T302 5
FACILITIES DROP SEE ELEC. NOTES # N/A SEE NOTES N/A SEE NOTES 12 13
INFORMATION TAG
DROP TYPE OR QUANTITY
UPS UPS UPS
RACK EQUIPMENT SHALL BE:
· DEMO
(1) UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK
LEVITON PATCH PANELS
· EXISTING
VERTICAL PDU
PANDUIT PATCH PANELS
· NEW
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-3000LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(4) NETWORK SWITCH - CISCO CATALYST 2960-X
(1) CISCO WIRELESS CONTROLLER
(1) ROUTER- CISCO CATALYST 2901
· EXISTING
(1) SITE SYNC TIME CONTROLLER
· NEW
(4) NETWORK SWITCH - MERAKI MS250-48
FIBER CONNECTIONS
A1-A 48-PORT PATCH PANEL
48-PORT POE SWITCH
A1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
UPS
FIBER CONNECTIONS
UPS
FIBER CONNECTIONS
C1-A 48-PORT PATCH PANEL
48-PORT POE SWITCH
PDU
UPS
FIBER CONNECTIONS FIBER CONNECTIONS
PDU
FIBER CONNECTIONS
RACK EQUIPMENT SHALL BE:
· DEMO
(1) UPS -
SURGE SUPPRESSORS - APC PNET1GB
· EXISTING
PANDUIT PATCH PANELS
· NEW
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-3000LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(4) NETWORK SWITCH - CISCO CATALYST 2960-X
· EXISTING
(1) SITE SYNC TIME CONTROLLER
· NEW
(4) NETWORK SWITCH - MERAKI MS250-48
RACK EQUIPMENT SHALL BE:
· DEMO
(1) UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK
FIBER PATCH PANEL
· EXISTING
PANDUIT PATCH PANELS
· NEW
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-1500LVRT2UXLN
(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL
FIBER TERMINATION
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(1) NETWORK SWITCH - CISCO CATALYST 2960-X
· NEW
(1) NETWORK SWITCH - MERAKI MS250-48
RACK EQUIPMENT SHALL BE:
· DEMO
(1) UPS -
· EXISTING
PANDUIT PATCH PANELS
· NEW
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-3000LVRT2UXLN
(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL
(1) SURGE PROTECTION CHASSIS - APC PRM24
(4) SURGE PROTECTION MODULE - APC PNETR6
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· EXISTING
(5) NETWORK SWITCH - MERAKI MS250-48
(1) SITESYNC IQ TIME CONTROLLER
RACK EQUIPMENT SHALL BE:
· DEMO
(1) UPS
LEVITON PATCH PANELS
FIBER PATCH PANEL
· EXISTING
VERTICAL PDU
PANDUIT PATCH PANELS
· NEW
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-3000LVRT2UXLN
(1) SURGE PROTECTION CHASSIS - APC PRM24
(2) SURGE PROTECTION MODULE - APC PNETR6
FIBER TERMINATION
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ
RELOCATE FIBER ENCLOSURE TO RACK FROM BACKERBOARD
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(1) CISCO WIRELESS CONTROLLER
(1) ROUTER - CISCO 2901
· EXISTING
(1) SITESYNC IQ TIME CONTROLLER
(4) NETWORK SWITCH - MERAKI MS250-48
RACK EQUIPMENT SHALL BE:
· DEMO
UPS - LIEBERT GXT3
LEVITON PATCH PANELS
· EXISTING
VERTICAL PDU
PANDUIT PATCH PANELS
· NEW
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-3000LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(1) ROUTER - CISCO 2901
· EXISTING
(1) SITE SYNC TIME CONTROLLER
(3) NETWORK SWITCH - MERAKI MS250-48
A1-C 48-PORT PATCH PANEL
48-PORT POE SWITCH
A1-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
TIME CONTROLLER
B1-A 48-PORT PATCH PANEL
48-PORT POE SWITCH
B1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
B1-C 48-PORT PATCH PANEL
48-PORT POE SWITCH
B1-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
TIME CONTROLLER
1 1 1
A1-A 48-PORT PATCH PANEL
48-PORT POE SWITCH
A1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
A1-C 48-PORT PATCH PANEL
48-PORT POE SWITCH
A1-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
TIME CONTROLLER
B1-A 48-PORT PATCH PANEL
48-PORT POE SWITCH
B1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
B1-C 48-PORT PATCH PANEL
48-PORT POE SWITCH
B1-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
B1-E 48-PORT PATCH PANEL
48-PORT POE SWITCH
TIME CONTROLLER
A1-A 48-PORT PATCH PANEL
48-PORT POE SWITCH
A1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
A1-C 48-PORT PATCH PANEL
48-PORT POE SWITCH
TIME CONTROLLER
EXISTING BACKBONE PATCH PANEL
EXISTING BACKBONE PATCH PANEL
EXISTING BACKBONE PATCH PANEL EXISTING BACKBONE PATCH PANEL
SURGE PROTECTOR
SURGE PROTECTOR
EXISTING BACKBONE PATCH PANEL
UPS
FIBER CONNECTIONS
PDU
RACK EQUIPMENT SHALL BE:
· DEMO
UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK
· EXISTING
PANDUIT PATCH PANELS
· NEW
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-3000LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· EXISTING
(1) SITE SYNC TIME CONTROLLER
(5) NETWORK SWITCH - MERAKI MS250-48
B1-A 48-PORT PATCH PANEL
48-PORT POE SWITCH
B1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
B1-C 48-PORT PATCH PANEL
48-PORT POE SWITCH
B1-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
B1-E 48-PORT PATCH PANEL
48-PORT POE SWITCH
TIME CONTROLLER
EXISTING BACKBONE PATCH PANEL
LAN FIBER CONNECTIONS
UPS
RACK EQUIPMENT SHALL BE:
· DEMO
LEVITON PATCH PANELS
· EXISTING
VERTICAL PDU
PANDUIT PATCH PANELS
CONSOLIDATE ALL LAN FIBER CONNECTIONS IN THIS RACK. LEAVE WAN FIBER
CONNECTIONS IN RACK 2
· NEW
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-3000LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(1) ROUTER - CISCO 2901
· EXISTING
(5) NETWORK SWITCH - MERAKI MS250-48
A1-A 48-PORT PATCH PANEL
48-PORT POE SWITCH
A1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
A1-C 48-PORT PATCH PANEL
48-PORT POE SWITCH
A1-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
A1-E 48-PORT PATCH PANEL
48-PORT POE SWITCH
EXISTING BACKBONE PATCH PANEL
RACK EQUIPMENT SHALL BE:
· DEMO
(2) UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK
LEVITON PATCH PANELS
· EXISTING
VERTICAL PDU
PANDUIT PATCH PANELS
CONSOLIDATE ALL LAN FIBER CONNECTIONS IN RACK 1. LEAVE WAN FIBER
CONNECTIONS IN THIS RACK
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(1) ROUTER - CISCO 2901
· EXISTING
(1) SYNOLOGY STORAGE DEVICE
(1) SITE SYNC TIME CONTROLLER
(1) SERVER - HP PROLIANT DL180 G6
(1) SERVER - HP PROLIANT DL380 G7
EXISTING SERVER
EXISTING SERVER
TIME CONTROLLER
WAN FIBER CONNECTIONS
EXISTING OWNER EQUIPMENT
SHEET NO.
ISSUE / DATE
DRAWN BY
PROJECT NO.
© 2023 AETD, ALL RIGHTS RESERVED.
N
EW
PO
RT
R
OA
D, S
UI
TE
#2
, P
OR
TA
GE
, M I 4
· 2
-2
-2
4 · A
ET
EC
H.
DE
SI
GN
2023-12-22 BIDS
CDB
T302
Te ch
R ac k E lev ati on s
SJPS2304-0300
Sa int
Jo se ph , M
I Inf ra str uc tur e U pg ra de s Sa int Jo se ph
P ub lic S ch oo ls
ENCLOSED SERVER RACK.
UPS. INSTALL IN BOTTOM OF RACK.
PDU.
MOVE SITESYNC IQ TIME CONTROLLER INTO RACK AT OWNER'S DIRECTION.
(2) EXISTING CONDUITS TO REMAIN
1. TECHNOLOGY CLOSETS SHALL BE NON-SPRINKLER SPACES.
2. GENERAL BUILDING HVAC SHALL NOT BE INSTALLED IN ANY TECHNOLOGY CLOSET. IF
ACTIVE COOLING IS REQUIRED, DEDICATED LOCAL SYSTEMS SHOULD BE INSTALLED
IN EACH TECH CLOSET.
3. ALL OUTLETS IN THE TECHNOLOGY CLOSETS SHOULD BE ON UPS-BACKED,
GENERATOR POWERED CIRCUITS.
4. EQUIPMENT MOUNTED ON BACKERBOARD SHALL MAINTAIN PROPER CLEARANCES
FOR OPERATION AND BE COORDINATED WITH OTHER DISCIPLINES PRIOR TO INSTALL
IF THERE IS A CONFLICT OF PLACEMENT.
5. RACK SIZES SHOWN ARE TYPICAL AND MAY NOT MATCH EXISTING RACK SIZES.
ACTUAL EQUIPMENT LAYOUT IN RACKS SHALL FOLLOW EQUIPMENT ORDER SHOWN IN
ELEVATIONS, ALONG WITH PROPER LABELING AND CABLE MANAGEMENT. CONFIRM
FINAL INSTALL LOCATION WITH OWNER.
6. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR
FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.
7. DEMO ALL ABANDONED EQUIPMENT AND CABLING, INCLUDING COAXIAL. DEMO CABLE
TO SOURCE.
8. DEMO ALL LEVITON PATCH PANELS AND REPLACE WITH PANDUIT PATCH PANELS.
9. DEMO ALL POTS PATCH PANELS, CABLING, ASSOCIATED 110 BLOCKS, AND OTHER
UNUSED POTS EQUIPMENT. DEMO CABLING TO SOURCE. PRIOR TO DEMO, CHECK
FOR DIAL TONE ON ANY LINES. NOTIFY OWNER AND AETD OF ANY DIAL TONE IF
DISCOVERED.
10. DEMO ALL UPS UNITS.
11. REMOVE ALL BACKERBOARD-MOUNTED FIBER ENCLOSURES AND RE-INSTALL
SPLICED CONNECTORS IN THEIR RESPECTIVE RACK'S FIBER ENCLOSURE.
12. SEE NETWORK DIAGRAM ON T306 FOR MORE DETAILS ON NETWORK ELECTRONICS
AND THEIR LOCATIONS.
13. RACK-MOUNTED EQUIPMENT SHALL BE INSTALLED WITH ENOUGH CLEARANCE SO
THAT THE RACK CAN FUNCTION PROPERLY. PATCH CORDS, POWER CORDS, AND
RELATED CABLING SHALL NOT PREVENT DOORS FROM CLOSING, RACK FROM
SWINGING, OR OTHER SIMILAR FUNCTIONS.
14. EXISTING COPPER BACKBONE, PATCH CORDS, JACKS, AND PATCH PANELS TO
REMAIN. RELOCATE PATCH PANELS TO THE TOP OF RACKS WHERE POSSIBLE.
TECH CLOSET GENERAL NOTES
TECH CLOSET KEYED NOTES
Brown ES TC-A Tech Rack Elevation
NTS
Brown ES TC-B Tech Rack Elevation
NTS
Brown ES TC-C Tech Rack Elevation
NTS
E.P. Clarke ES TC-A Tech Rack Elevation
NTS
E.P. Clarke ES TC-B Tech Rack Elevation
NTS
Lincoln ES TC-A Tech Rack Elevation
NTS
Lincoln ES TC-B Tech Rack Elevation
NTS
Upton MS TC-A Tech Rack 1 Elevation
NTS
Upton MS TC-A Tech Rack 2 Elevation
NTS
EXISTING OWNER EQUIPMENT
· EXISTING OWNER EQUIPMENT
· NOT IN SCOPE. VERIFY WITH OWNER.
RACK EQUIPMENT SHALL BE:
· EXISTING OWNER EQUIPMENT
· NOT IN SCOPE. VERIFY WITH OWNER.
1 1
EXISTING OWNER EQUIPMENT
FIBER CONNECTIONS
UPS
FIBER CONNECTIONS
PDU
UPS
FIBER CONNECTIONS
PDU
UPS
RACK EQUIPMENT SHALL BE:
· DEMO
UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK
· EXISTING
VERTICAL PDU
PANDUIT PATCH PANELS
· NEW
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-3000LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· EXISTING
(5) NETWORK SWITCH - MERAKI MS250-48
RACK EQUIPMENT SHALL BE:
· DEMO
UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK
LEVITON PATCH PANELS
· EXISTING
VERTICAL PDU
PANDUIT PATCH PANELS
· NEW
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-3000LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· EXISTING
(4) NETWORK SWITCH - MERAKI MS250-48
RACK EQUIPMENT SHALL BE:
· DEMO
WALL-MOUNTED TECH RACK
UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK
LEVITON PATCH PANELS
· EXISTING
PANDUIT PATCH PANELS
UPON DEMO OF RACK, LEAVE ATTACHED CONDUITS TO REMAIN.
· NEW
(1) WALL-MOUNTED TECH RACK - MIDDLE ATLANTIC DWR-24-32
(1) FRONT RACK DOOR - MIDDLE ATLANTIC FD-24
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-3000LVRT2UXLN
(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· EXISTING
(5) NETWORK SWITCH - MERAKI MS250-48
1 1 1
B1-A 48-PORT PATCH PANEL
48-PORT POE SWITCH
B1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
B1-C 48-PORT PATCH PANEL
48-PORT POE SWITCH
B1-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
B1-E 48-PORT PATCH PANEL
48-PORT POE SWITCH
C1-A 48-PORT PATCH PANEL
48-PORT POE SWITCH
C1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
C1-C 48-PORT PATCH PANEL
48-PORT POE SWITCH
C1-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
D1-A 48-PORT PATCH PANEL
48-PORT POE SWITCH
D1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
D1-C 48-PORT PATCH PANEL
48-PORT POE SWITCH
D1-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
D1-E 48-PORT PATCH PANEL
48-PORT POE SWITCH
EXISTING BACKBONE PATCH PANEL EXISTING BACKBONE PATCH PANEL
RACK EQUIPMENT SHALL BE:
· DEMO
(1) FLOOR STANDING UPS - LIEBERT NFINITY
· EXISTING
(1) VERTICAL PDU
· NEW
(1) FLOOR-STANDING UPS -
(1) RACK SHELF
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(1) WIRELESS CONTROLLER - CISCO CATALYST 5500
(2) CORE SWITCHES - CISCO CATALYST 4500-X
(5) NETWORK SWITCH - CISCO CATALYST 2960-X
(1) ROUTER - CISCO CATALYST C2901
· EXISTING
(1) FIREWALL
(1) IP PHONE BOX
· NEW
(2) CORE SWITCH - CISCO CATALYST C9500-40X
(5) NETWORK SWITCH - MERAKI MS250-48
FIBER CONNECTIONS
A4-A 48-PORT PATCH PANEL
CORE SWITCH
A4-B 48-PORT PATCH PANEL
CORE SWITCH
148-PORT POE SWITCH
48-PORT POE SWITCH
RACK EQUIPMENT SHALL BE:
· EXISTING
(1) VERTICAL PDU
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(4) NETWORK SWITCH - CISCO CATALYST 2960-X
· EXISTING
(1) BERRIEN RESA CPE - CISCO CATALYST 2960-S
(1) COMCAST CPE - CIENA 3916
· NEW
(4) NETWORK SWITCH - MERAKI MS250-48
FIBER CONNECTIONS
BERRIEN RESA CPE
RACK SHELF
A4-C 48-PORT PATCH PANEL
A4-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
48-PORT POE SWITCH
A4-E 48-PORT PATCH PANEL
48-PORT POE SWITCH
COMCAST CPE
A5-A 48-PORT PATCH PANEL
A5-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
48-PORT POE SWITCH
A5-C 48-PORT PATCH PANEL
A5-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
48-PORT POE SWITCH
EXISTING BACKBONE PATCH PANEL
FIBER CONNECTIONS
PDU
UPS
RACK EQUIPMENT SHALL BE:
· DEMO
UPS - LIEBERT GXT3 WITH ADDITIONAL BATTERY PACK
LEVITON PATCH PANELS
· EXISTING
VERTICAL PDU
PANDUIT PATCH PANELS
· NEW
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-3000LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUDLCZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· EXISTING
(4) NETWORK SWITCH - MERAKI MS250-48
E1-A 48-PORT PATCH PANEL
48-PORT POE SWITCH
E1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
E1-C 48-PORT PATCH PANEL
48-PORT POE SWITCH
E1-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
RACK EQUIPMENT SHALL BE:
· EXISTING OWNER EQUIPMENT
· NOT IN SCOPE. VERIFY WITH OWNER.
EXISTING OWNER EQUIPMENT
SHEET NO.
ISSUE / DATE
DRAWN BY
PROJECT NO.
© 2023 AETD, ALL RIGHTS RESERVED.
N
EW
PO
RT
R
OA
D, S
UI
TE
#2
, P
OR
TA
GE
, M I 4
· 2
-2
-2
4 · A
ET
EC
H.
DE
SI
GN
2023-12-22 BIDS
CDB
T303
Te ch
R ac k E lev ati on s
SJPS2304-0300
Sa int
Jo se ph , M
I Inf ra str uc tur e U pg ra de s Sa int Jo se ph
P ub lic S ch oo ls
ENCLOSED SERVER RACK.
UPS. INSTALL IN BOTTOM OF RACK.
PDU.
MOVE SITESYNC IQ TIME CONTROLLER INTO RACK AT OWNER'S DIRECTION.
(2) EXISTING CONDUITS TO REMAIN
1. TECHNOLOGY CLOSETS SHALL BE NON-SPRINKLER SPACES.
2. GENERAL BUILDING HVAC SHALL NOT BE INSTALLED IN ANY TECHNOLOGY CLOSET. IF
ACTIVE COOLING IS REQUIRED, DEDICATED LOCAL SYSTEMS SHOULD BE INSTALLED
IN EACH TECH CLOSET.
3. ALL OUTLETS IN THE TECHNOLOGY CLOSETS SHOULD BE ON UPS-BACKED,
GENERATOR POWERED CIRCUITS.
4. EQUIPMENT MOUNTED ON BACKERBOARD SHALL MAINTAIN PROPER CLEARANCES
FOR OPERATION AND BE COORDINATED WITH OTHER DISCIPLINES PRIOR TO INSTALL
IF THERE IS A CONFLICT OF PLACEMENT.
5. RACK SIZES SHOWN ARE TYPICAL AND MAY NOT MATCH EXISTING RACK SIZES.
ACTUAL EQUIPMENT LAYOUT IN RACKS SHALL FOLLOW EQUIPMENT ORDER SHOWN IN
ELEVATIONS, ALONG WITH PROPER LABELING AND CABLE MANAGEMENT. CONFIRM
FINAL INSTALL LOCATION WITH OWNER.
6. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR
FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.
7. DEMO ALL ABANDONED EQUIPMENT AND CABLING, INCLUDING COAXIAL. DEMO CABLE
TO SOURCE.
8. DEMO ALL LEVITON PATCH PANELS AND REPLACE WITH PANDUIT PATCH PANELS.
9. DEMO ALL POTS PATCH PANELS, CABLING, ASSOCIATED 110 BLOCKS, AND OTHER
UNUSED POTS EQUIPMENT. DEMO CABLING TO SOURCE. PRIOR TO DEMO, CHECK
FOR DIAL TONE ON ANY LINES. NOTIFY OWNER AND AETD OF ANY DIAL TONE IF
DISCOVERED.
10. DEMO ALL UPS UNITS.
11. REMOVE ALL BACKERBOARD-MOUNTED FIBER ENCLOSURES AND RE-INSTALL
SPLICED CONNECTORS IN THEIR RESPECTIVE RACK'S FIBER ENCLOSURE.
12. SEE NETWORK DIAGRAM ON T306 FOR MORE DETAILS ON NETWORK ELECTRONICS
AND THEIR LOCATIONS.
13. RACK-MOUNTED EQUIPMENT SHALL BE INSTALLED WITH ENOUGH CLEARANCE SO
THAT THE RACK CAN FUNCTION PROPERLY. PATCH CORDS, POWER CORDS, AND
RELATED CABLING SHALL NOT PREVENT DOORS FROM CLOSING, RACK FROM
SWINGING, OR OTHER SIMILAR FUNCTIONS.
14. EXISTING COPPER BACKBONE, PATCH CORDS, JACKS, AND PATCH PANELS TO
REMAIN. RELOCATE PATCH PANELS TO THE TOP OF RACKS WHERE POSSIBLE.
TECH CLOSET GENERAL NOTES
TECH CLOSET KEYED NOTES
Upton MS TC-B Tech Rack Elevation
NTS
Upton MS TC-C Tech Rack Elevation
NTS
Upton MS TC-D Tech Rack Elevation
NTS
SJHS TC-A Tech Rack 1 Elevation
NTS
SJHS TC-A Tech Rack 2 Elevation
NTS
SJHS TC-A Tech Rack 3 Elevation
NTS
SJHS TC-A Tech Rack 4 Elevation
NTS
SJHS TC-A Tech Rack 5 Elevation
NTS
Upton MS TC-E Tech Rack Elevation
1 1
· EXISTING
FIBER CONNECTIONS
PANDUIT PATCH PANELS
(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL
· NEW
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-3000LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(5) NETWORK SWITCH - CISCO CATALYST 2960-X
· NEW
(5) NETWORK SWITCH - MERAKI MS250-48
FIBER CONNECTIONS
E1-A 48-PORT PATCH PANEL
E1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
48-PORT POE SWITCH
E1-C 48-PORT PATCH PANEL
E1-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
48-PORT POE SWITCH
E1-E 48-PORT PATCH PANEL
48-PORT POE SWITCH
PATCH PANEL
EXISTING PDU
RACK EQUIPMENT SHALL BE:
· EXISTING
FIBER CONNECTIONS
PANDUIT PATCH PANELS
(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL
· NEW
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-2000LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(2) NETWORK SWITCH - CISCO CATALYST 2960-X
· NEW
(2) NETWORK SWITCH - MERAKI MS250-48
FIBER CONNECTIONS
F1-A 48-PORT PATCH PANEL
F1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
48-PORT POE SWITCH
PATCH PANEL
EXISTING PDU
UPS UPS
RACK EQUIPMENT SHALL BE:
· DEMO
(1) LEVITON FIBER ENCLOSURE
LEVITON PATCH PANELS
· EXISTING
(1) VERTICAL PDU
· NEW
PANDUIT PATCH PANELS
(1) RACK SHELF
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(1) NETWORK SWITCH - CISCO CATALYST 2960-S
· EXISTING
WHITE BOX
· NEW
(1) NETWORK SWITCH - MERAKI MS250-24
FIBER CONNECTIONS
A1-A 48-PORT PATCH PANEL
24-PORT POE SWITCH
RACK EQUIPMENT SHALL BE:
· DEMO
LEVITON PATCH PANELS
· EXISTING
PANDUIT PATCH PANELS
· NEW
PANDUIT PATCH PANELS
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-1500LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(1) NETWORK SWITCH - CISCO CATALYST 2960-S
· NEW
(1) NETWORK SWITCH - MERAKI MS250-48
FIBER CONNECTIONS
J1-A 48-PORT PATCH PANEL
48-PORT POE SWITCH
RACK EQUIPMENT SHALL BE:
· EXISTING OWNER AND CPE EQUIPMENT
· NOT IN SCOPE. VERIFY WITH OWNER.
EXISTING OWNER AND CPE EQUIPMENT
RACK EQUIPMENT SHALL BE:
· EXISTING
PANDUIT PATCH PANELS
· NEW
(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-2000LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(3) NETWORK SWITCH - CISCO CATALYST 2960-X
· NEW
(3) NETWORK SWITCH - MERAKI MS250-48
PATCH PANEL
B1-A 48-PORT PATCH PANEL
48-PORT POE SWITCH
48-PORT POE SWITCH
RACK EQUIPMENT SHALL BE:
· EXISTING
FIBER CONNECTIONS
PANDUIT PATCH PANELS
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(5) NETWORK SWITCH - CISCO CATALYST 2960-X
· NEW
(5) NETWORK SWITCH - MERAKI MS250-48
FIBER CONNECTIONS
B1-B 48-PORT PATCH PANEL
B1-C 48-PORT PATCH PANEL
48-PORT POE SWITCH
C1-A 48-PORT PATCH PANEL
C1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
48-PORT POE SWITCH
C1-C 48-PORT PATCH PANEL
C1-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
48-PORT POE SWITCH
C1-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
UPS
RACK EQUIPMENT SHALL BE:
· EXISTING
FIBER CONNECTIONS
PANDUIT PATCH PANELS
(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL
· NEW
(1) RACK-MOUNT PDU - MIDDLE ATLANTIC PD-915R-PL
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-3000LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(9) NETWORK SWITCH - CISCO CATALYST 2960-X
· NEW
(9) NETWORK SWITCH - MERAKI MS250-48
FIBER CONNECTIONS
D1-A 48-PORT PATCH PANEL
D1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
48-PORT POE SWITCH
D1-C 48-PORT PATCH PANEL
D1-D 48-PORT PATCH PANEL
48-PORT POE SWITCH
48-PORT POE SWITCH
D1-E 48-PORT PATCH PANEL
48-PORT POE SWITCH
PATCH PANEL
D1-F 48-PORT PATCH PANEL
48-PORT POE SWITCH
D1-G 48-PORT PATCH PANEL
D1-H 48-PORT PATCH PANEL
48-PORT POE SWITCH
48-PORT POE SWITCH
D1-J 48-PORT PATCH PANEL
48-PORT POE SWITCH
EXISTING PDU
PDU
UPS
RACK EQUIPMENT SHALL BE:
· DEMO
LEVITON PATCH PANELS
(1) FIBER CONNECTION
(1) RACK-MOUNT UPS - APC SMART
· EXISTING
FIBER CONNECTIONS
PANDUIT PATCH PANELS
(1) HORIZONTAL PDU - MIDDLE ATLANTIC PD-915R-PL
· NEW
PANDUIT PATCH PANELS
(1) RACK SHELF
(1) FIBER CONNECTION
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-2000LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(2) NETWORK SWITCH - CISCO CATALYST 2960-X
· NEW
(2) NETWORK SWITCH - MERAKI MS250-48
FIBER CONNECTIONS
F1-A 48-PORT PATCH PANEL
F1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
48-PORT POE SWITCH
PATCH PANEL
RACK SHELF
UPS
SHEET NO.
ISSUE / DATE
DRAWN BY
PROJECT NO.
© 2023 AETD, ALL RIGHTS RESERVED.
N
EW
PO
RT
R
OA
D, S
UI
TE
#2
, P
OR
TA
GE
, M I 4
· 2
-2
-2
4 · A
ET
EC
H.
DE
SI
GN
2023-12-22 BIDS
CDB
T304
Te ch
R ac k E lev ati on s
SJPS2304-0300
Sa int
Jo se ph , M
I Inf ra str uc tur e U pg ra de s Sa int Jo se ph
P ub lic S ch oo ls
ENCLOSED SERVER RACK.
UPS. INSTALL IN BOTTOM OF RACK.
PDU.
MOVE SITESYNC IQ TIME CONTROLLER INTO RACK AT OWNER'S DIRECTION.
(2) EXISTING CONDUITS TO REMAIN
1. TECHNOLOGY CLOSETS SHALL BE NON-SPRINKLER SPACES.
2. GENERAL BUILDING HVAC SHALL NOT BE INSTALLED IN ANY TECHNOLOGY CLOSET. IF
ACTIVE COOLING IS REQUIRED, DEDICATED LOCAL SYSTEMS SHOULD BE INSTALLED
IN EACH TECH CLOSET.
3. ALL OUTLETS IN THE TECHNOLOGY CLOSETS SHOULD BE ON UPS-BACKED,
GENERATOR POWERED CIRCUITS.
4. EQUIPMENT MOUNTED ON BACKERBOARD SHALL MAINTAIN PROPER CLEARANCES
FOR OPERATION AND BE COORDINATED WITH OTHER DISCIPLINES PRIOR TO INSTALL
IF THERE IS A CONFLICT OF PLACEMENT.
5. RACK SIZES SHOWN ARE TYPICAL AND MAY NOT MATCH EXISTING RACK SIZES.
ACTUAL EQUIPMENT LAYOUT IN RACKS SHALL FOLLOW EQUIPMENT ORDER SHOWN IN
ELEVATIONS, ALONG WITH PROPER LABELING AND CABLE MANAGEMENT. CONFIRM
FINAL INSTALL LOCATION WITH OWNER.
6. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR
FIRST RIGHT OF REFUSAL BEFORE REMOVAL FROM SITE.
7. DEMO ALL ABANDONED EQUIPMENT AND CABLING, INCLUDING COAXIAL. DEMO CABLE
TO SOURCE.
8. DEMO ALL LEVITON PATCH PANELS AND REPLACE WITH PANDUIT PATCH PANELS.
9. DEMO ALL POTS PATCH PANELS, CABLING, ASSOCIATED 110 BLOCKS, AND OTHER
UNUSED POTS EQUIPMENT. DEMO CABLING TO SOURCE. PRIOR TO DEMO, CHECK
FOR DIAL TONE ON ANY LINES. NOTIFY OWNER AND AETD OF ANY DIAL TONE IF
DISCOVERED.
10. DEMO ALL UPS UNITS.
11. REMOVE ALL BACKERBOARD-MOUNTED FIBER ENCLOSURES AND RE-INSTALL
SPLICED CONNECTORS IN THEIR RESPECTIVE RACK'S FIBER ENCLOSURE.
12. SEE NETWORK DIAGRAM ON T306 FOR MORE DETAILS ON NETWORK ELECTRONICS
AND THEIR LOCATIONS.
13. RACK-MOUNTED EQUIPMENT SHALL BE INSTALLED WITH ENOUGH CLEARANCE SO
THAT THE RACK CAN FUNCTION PROPERLY. PATCH CORDS, POWER CORDS, AND
RELATED CABLING SHALL NOT PREVENT DOORS FROM CLOSING, RACK FROM
SWINGING, OR OTHER SIMILAR FUNCTIONS.
14. EXISTING COPPER BACKBONE, PATCH CORDS, JACKS, AND PATCH PANELS TO
REMAIN. RELOCATE PATCH PANELS TO THE TOP OF RACKS WHERE POSSIBLE.
TECH CLOSET GENERAL NOTES
TECH CLOSET KEYED NOTES
SJHS TC-B Tech Rack Elevation
NTS
SJHS TC-C Tech Rack Elevation
NTS
SJHS TC-D Tech Rack Elevation
NTS
SJHS TC-E Tech Rack Elevation
NTS
SJHS TC-F Tech Rack Elevation
NTS
SJHS TC-G Tech Rack Elevation
NTS
SJHS TC-H (Staduim)Tech Rack Elevation
NTS
SJHS TC-I Tech Rack Elevation
NTS
SJHS TC-A Tech Rack 6 Elevation
· NEW
PANDUIT PATCH PANELS
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-1000LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(1) NETWORK SWITCH - CISCO CATALYST 2960-S
(1) ROUTER - CISCO CATALYST 2901
· NEW
(1) NETWORK SWITCH - MERAKI MS250-24
EXISTING PATCH PANEL
A1-A 48-PORT PATCH PANEL
24-PORT POE SWITCH
RACK EQUIPMENT SHALL BE:
· DEMO
(1) RACK-MOUNT UPS - ALTRONIX
· EXISTING
PANDUIT PATCH PANELS
(1) RACK-MOUNT PDU - APC
· NEW
PANDUIT PATCH PANELS
(1) RACK SHELF
(1) FIBER CONNECTION
(1) RACK-MOUNT UPS W/ NETWORK MONITORING CARD - LIEBERT
GXT5-2000LVRT2UXLN
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(2) NETWORK SWITCH - CISCO CATALYST 9200L
(1) ROUTER - CISCO CATALYST 2901
· NEW
(2) NETWORK SWITCH - MERAKI MS250-48
A1-A 48-PORT PATCH PANEL
A1-B 48-PORT PATCH PANEL
48-PORT POE SWITCH
48-PORT POE SWITCH
EXISTING BACKBONE PATCH PANEL
EXISTING PDU
RACK SHELF
UPS UPS
RACK EQUIPMENT SHALL BE:
· EXISTING
FIBER CONNECTIONS
PANDUIT PATCH PANELS
FIBER TERMINATIONS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
RACK-MOUNT FIBER ENCLOSURE - PANDUIT FCE1U
FIBER ADAPTER PANEL - PANDUIT FAP6WBUD*CZ
ALL PATCH PANELS SHALL BE:
PROVIDE QUANTITY AS REQUIRED TO TERMINATE ALL CABLES IN CLOSET
48-PORT PATCH PANEL - PANDUIT CPPL48WBLY (PREMISE CABLING)
24-PORT PATCH PANEL - PANDUIT CPPL24WBLY (BACKBONE)
STRAIN RELIEF BAR - PANDUIT SRB19D5BL
NETWORK ELECTRONICS SHALL BE:
· DEMO
(1) NETWORK SWITCH - CISCO CATALYST 2960-S
· NEW
(1) NETWORK SWITCH - MERAKI MS250-48
FIBER CONNECTIONS
K1-A 48-PORT PATCH PANEL
48-PORT POE SWITCH
EXISTING PDU
SHEET NO.
ISSUE / DATE
DRAWN BY
PROJECT NO.
© 2023 AETD, ALL RIGHTS RESERVED.
N
EW
PO
RT
R
OA
D, S
UI
TE
#2
, P
OR
TA
GE
, M I 4
· 2
-2
-2
4 · A
ET
EC
H.
DE
SI
GN
2023-12-22 BIDS
CDB
T305
Te ch
R ac k E lev ati on s
SJPS2304-0300
Sa int
Jo se ph , M
I Inf ra str uc tur e U pg ra de s Sa int Jo se ph
P ub lic S ch oo ls
ENCLOSED SERVER RACK.
UPS. INSTALL IN BOTTOM OF RACK.
PDU.
MOVE SITESYNC IQ TIME CONTROLLER INTO RACK AT OWNER'S DIRECTION.
(2) EXISTING CONDUITS TO REMAIN
1. TECHNOLOGY CLOSETS SHALL BE NON-SPRINKLER SPACES.
2. GENERAL BUILDING HVAC SHALL NOT BE INSTALLED IN ANY TECHNOLOGY CLOSET. IF
ACTIVE COOLING IS REQUIRED, DEDICATED LOCAL SYSTEMS SHOULD BE INSTALLED
IN EACH TECH CLOSET.
3. ALL OUTLETS IN THE TECHNOLOGY CLOSETS SHOULD BE ON UPS-BACKED,
GENERATOR POWERED CIRCUITS.
4. EQUIPMENT MOUNTED ON BACKERBOARD SHALL MAINTAIN PROPER CLEARANCES
FOR OPERATION AND BE COORDINATED WITH OTHER DISCIPLINES PRIOR TO INSTALL
IF THERE IS A CONFLICT OF PLACEMENT.
5. RACK SIZES SHOWN ARE TYPICAL AND MAY NOT MATCH EXISTING RACK SIZES.
ACTUAL EQUIPMENT LAYOUT IN RACKS SHALL FOLLOW EQUIPMENT ORDER SHOWN IN
ELEVATIONS, ALONG WITH PROPER LABELING AND CABLE MANAGEMENT. CONFIRM
FINAL INSTALL LOCATION WITH OWNER.
6. DEMOED EQUIPMENT, WHOLE OR IN PART, SHALL BE PRESENTED TO OWNER FOR
FIRST RIGHT OF REFUSAL BEFORE…