Server Room PDU Layout.xlsx
XLSX spreadsheet 20 KB Posted
- Solicitation number
- FA940124Q0023
- Issued by
-
Department of the Air Force
About this file
This document appears to be a Special Notice for a federal contract opportunity to perform a comprehensive assessment of the power infrastructure for the DMOC's 1st Floor Battlespace and Computer Room. The government intends to award a sole source firm fixed price commercial services contract to Dell Federal Systems L.P. to increase the overall power capacity to a 60A standard necessary to support the DMOC's new three-phase 208V/60A IT systems. The contract will not be competed, and the government is not issuing a solicitation package. Responses to this notice should be limited to 3 pages and should demonstrate the offeror's capability to provide the required services outlined in the attached Statement of Work documents. The Department of the Air Force is the procuring agency. Responses are due by the date mentioned in the notice and should be submitted via email to the points of contact.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SOW - DVS Server Room Power Expansion.pdf | ||
| Bldg_942 diagram w-Jumper add.pdf | ||
| PDU As-Builts 1.pdf | ||
| PDU As-Builts 2.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| PDU 5A | PDU 6 | |||||||||
| PDU Specifications (For PDU# 5 & 6) | Left Breaker: 225A | Left Breaker: 225A | ||||||||
| Mfg. | Power Distribution Inc. (PDI) | Circuits (#1, #2, #3) | Current Amp | Desired Merged Amp | Circuits (#1, #2, #3) | Current Amp | Desired Merged Amp | |||
| Model | PP13-1-3000-641 | 38, 40, 42 | 20A/ea | 60A | 1, 3, 5 | 20A/ea | 60A | |||
| KVA | 300 | 37, 39, 41 | 20A/ea | 60A | 7, 9, 11 | 20A/ea | 60A | |||
| Inspection Date | 8/25/88 | 1, 3, 5 | 20A/ea | 60A | 33, 35, 37 | 20A/ea | 60A | |||
| Input | Output | 2, 4, 6 | 20A/ea | 60A | 38, 40, 42 | 20A/ea | 60A | |||
| Voltage | 480 | 208/120 | ||||||||
| Amperage | 360 | 830 | Quantity (Ct.) | In-Use Breakers on the Left | In-Use Breakers on the Right | Quantity (Ct.) | In-Use Breakers on the Left | In-Use Breakers on the Right | ||
| Freq (Hz) | 60 | 60 | 8 | 20 | 4 | 20 | ||||
| Phase | 3 | 3 | 2 | 60 | 1 | 60 | ||||
| Main Breaker | 500 | 225 | 15 | 20 | 11 | 20 | ||||
| 1 | 60 | 1 | 60 | |||||||
| This information was acquire by physically inspecting the inside of the PDU panel on May 2nd 2024 by 1Lt Devlin. | Total Amps in-use: | 640 | Total Amps in-use: | 420 | ||||||
| By "in-use" I mean these breakers are flipped to the "ON" position. | By "in-use" I mean these breakers are flipped to the "ON" position. | |||||||||
| PDU5 has two panels, "PDU5A" and "PDU5B", they have four (4) 225A breaks between them. | ||||||||||
| Right Breaker: 225A | Right Breaker: 225A | |||||||||
| PDU6 has one panel, "PDU6" which has two (2) 225A breakers. It has a 2nd panel but it's naked and only has a 150A breaker. | Circuits (#1, #2, #3) | Current Amp | Desired Merged Amp | Circuits (#1, #2, #3) | Current Amp | Desired Merged Amp | ||||
| 58, 60, 62 | 20A/ea | 60A | 43, 45, 47 | 20A/ea | 60A | |||||
| Each PDU's 225 Breaker has 42 circuit slots, 21 on the left and 21 on the right. | 80, 82, 84 | 20A/ea | 60A | 53, 55, 57 | 20A/ea | 60A | ||||
| 75, 77, 79 | 20A/ea | 60A | 65, 67, 69 | 20A/ea | 60A | |||||
| 168 Circuits for PDU5A and B and 84 Circuits for PDU6 (+42 if you count the naked 150A PDU6 side panel). | 59, 61, 63 | 20A/ea | 60A | 80, 82, 84 | 20A/ea | 60A |
| Quantity (Ct.) | In-Use Breakers on the Left | In-Use Breakers on the Right | Quantity (Ct.) | In-Use Breakers on the Left | In-Use Breakers on the Right | ||||
| PDU/Panel | # of Desired 60A Circuits | # of Replaced 20A Circuits | 9 | 20 | 7 | 20 | |||
| PDU5A | 8 | 24 | 1 | 30 | 1 | 30 | |||
| PDU5B | 8 | 24 | 10 | 20 | 12 | 20 | |||
| PDU6 | 8 | 24 | 2 | 60 | |||||
| (Counting 3 merg'd 20A =1x 60A) | Total Amps in-use: | 530 | Total Amps in-use: | 410 | |||||
| By "in-use" I mean these breakers are flipped to the "ON" position. | By "in-use" I mean these breakers are flipped to the "ON" position. | ||||||||
| PDU 6 has a secondary naked panel (no circuits just filler breakers) that has a M.B. = 150A | |||||||||
| PDU 5B | |||||||||
| Left Breaker: 225A | |||||||||
| Circuits (#1, #2, #3) | Current Amp | Desired Merged Amp | |||||||
| 38, 40, 42 | 20A/ea | 60A | |||||||
| 37, 39, 41 | 20A/ea | 60A | |||||||
| 1, 3, 5 | 20A/ea | 60A | |||||||
| 2, 4, 6 | 20A/ea | 60A |
| Quantity (Ct.) | In-Use Breakers on the Left | In-Use Breakers on the Right |
| 11 | 20 | |
| 6 | 30 | |
| 13 | 20 | |
| 6 | 30 | |
| Total Amps in-use: | 840 | |
| By "in-use" I mean these breakers are flipped to the "ON" position. |
| Right Breaker: 225A | ||
| Circuits (#1, #2, #3) | Current Amp | Desired Merged Amp |
| 43, 45, 47 | 20A/ea | 60A |
| 44, 46, 48 | 20A/ea | 60A |
| 67, 69, 71 | 20A/ea | 60A |
| 68, 70, 72 | 20A/ea | 60A |
| Quantity (Ct.) | In-Use Breakers on the Left | In-Use Breakers on the Right |
| 14 | 20 | |
| 2 | 30 | |
| 11 | 20 | |
| 4 | 30 | |
| Total Amps in-use: | 680 | |
| By "in-use" I mean these breakers are flipped to the "ON" position. |