This document appears to be a Special Notice for a federal contract opportunity to perform a comprehensive assessment of the power infrastructure for the DMOC's 1st Floor Battlespace and Computer Room. The government intends to award a sole source firm fixed price commercial services contract to Dell Federal Systems L.P. to increase the overall power capacity to a 60A standard necessary to support the DMOC's new three-phase 208V/60A IT systems. The contract will not be competed, and the government is not issuing a solicitation package. Responses to this notice should be limited to 3 pages and should demonstrate the offeror's capability to provide the required services outlined in the attached Statement of Work documents. The Department of the Air Force is the procuring agency. Responses are due by the date mentioned in the notice and should be submitted via email to the points of contact.
On GovTribe
Work with this file
Download the original file
Contacts named in this file
Similar government files
Ask GovTribe AI about this file
Text version
The file's text, extracted by GovTribe without its formatting.
Sheet1
PDU 5A PDU 6
PDU Specifications (For PDU# 5 & 6) Left Breaker: 225A Left Breaker: 225A
Mfg. Power Distribution Inc. (PDI) Circuits (#1, #2, #3) Current Amp Desired Merged Amp Circuits (#1, #2, #3) Current Amp Desired Merged Amp
Model PP13-1-3000-641 38, 40, 42 20A/ea 60A 1, 3, 5 20A/ea 60A
KVA 300 37, 39, 41 20A/ea 60A 7, 9, 11 20A/ea 60A
Inspection Date 8/25/88 1, 3, 5 20A/ea 60A 33, 35, 37 20A/ea 60A
Input Output 2, 4, 6 20A/ea 60A 38, 40, 42 20A/ea 60A
Voltage 480 208/120
Amperage 360 830 Quantity (Ct.) In-Use Breakers on the Left In-Use Breakers on the Right Quantity (Ct.) In-Use Breakers on the Left In-Use Breakers on the Right
Freq (Hz) 60 60 8 20 4 20
Phase 3 3 2 60 1 60
Main Breaker 500 225 15 20 11 20
1 60 1 60
This information was acquire by physically inspecting the inside of the PDU panel on May 2nd 2024 by 1Lt Devlin. Total Amps in-use: 640 Total Amps in-use: 420
By "in-use" I mean these breakers are flipped to the "ON" position. By "in-use" I mean these breakers are flipped to the "ON" position.
PDU5 has two panels, "PDU5A" and "PDU5B", they have four (4) 225A breaks between them.
Right Breaker: 225A Right Breaker: 225A
PDU6 has one panel, "PDU6" which has two (2) 225A breakers. It has a 2nd panel but it's naked and only has a 150A breaker. Circuits (#1, #2, #3) Current Amp Desired Merged Amp Circuits (#1, #2, #3) Current Amp Desired Merged Amp
58, 60, 62 20A/ea 60A 43, 45, 47 20A/ea 60A
Each PDU's 225 Breaker has 42 circuit slots, 21 on the left and 21 on the right. 80, 82, 84 20A/ea 60A 53, 55, 57 20A/ea 60A
75, 77, 79 20A/ea 60A 65, 67, 69 20A/ea 60A
168 Circuits for PDU5A and B and 84 Circuits for PDU6 (+42 if you count the naked 150A PDU6 side panel). 59, 61, 63 20A/ea 60A 80, 82, 84 20A/ea 60A
Quantity (Ct.) In-Use Breakers on the Left In-Use Breakers on the Right Quantity (Ct.) In-Use Breakers on the Left In-Use Breakers on the Right
PDU/Panel # of Desired 60A Circuits # of Replaced 20A Circuits 9 20 7 20
PDU5A 8 24 1 30 1 30
PDU5B 8 24 10 20 12 20
PDU6 8 24 2 60
(Counting 3 merg'd 20A =1x 60A) Total Amps in-use: 530 Total Amps in-use: 410
By "in-use" I mean these breakers are flipped to the "ON" position. By "in-use" I mean these breakers are flipped to the "ON" position.
PDU 6 has a secondary naked panel (no circuits just filler breakers) that has a M.B. = 150A
PDU 5B
Left Breaker: 225A
Circuits (#1, #2, #3) Current Amp Desired Merged Amp
38, 40, 42 20A/ea 60A
37, 39, 41 20A/ea 60A
1, 3, 5 20A/ea 60A
2, 4, 6 20A/ea 60A
Quantity (Ct.) In-Use Breakers on the Left In-Use Breakers on the Right
11 20
6 30
13 20
6 30
Total Amps in-use: 840
By "in-use" I mean these breakers are flipped to the "ON" position.
Right Breaker: 225A
Circuits (#1, #2, #3) Current Amp Desired Merged Amp
43, 45, 47 20A/ea 60A
44, 46, 48 20A/ea 60A
67, 69, 71 20A/ea 60A
68, 70, 72 20A/ea 60A
Quantity (Ct.) In-Use Breakers on the Left In-Use Breakers on the Right
14 20
2 30
11 20
4 30
Total Amps in-use: 680
By "in-use" I mean these breakers are flipped to the "ON" position.