Server Room PDU Layout.xlsx

XLSX spreadsheet 20 KB Posted

Attached to
705 CTS Bldg. 942 DMOC Battlespace Power Expansion: Phase 1 - Assessment
Solicitation number
FA940124Q0023
Issued by

About this file

This document appears to be a Special Notice for a federal contract opportunity to perform a comprehensive assessment of the power infrastructure for the DMOC's 1st Floor Battlespace and Computer Room. The government intends to award a sole source firm fixed price commercial services contract to Dell Federal Systems L.P. to increase the overall power capacity to a 60A standard necessary to support the DMOC's new three-phase 208V/60A IT systems. The contract will not be competed, and the government is not issuing a solicitation package. Responses to this notice should be limited to 3 pages and should demonstrate the offeror's capability to provide the required services outlined in the attached Statement of Work documents. The Department of the Air Force is the procuring agency. Responses are due by the date mentioned in the notice and should be submitted via email to the points of contact.

View the file

Other files

File Type Posted
SOW - DVS Server Room Power Expansion.pdf PDF
Bldg_942 diagram w-Jumper add.pdf PDF
PDU As-Builts 1.pdf PDF
PDU As-Builts 2.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

PDU 5APDU 6
PDU Specifications (For PDU# 5 & 6)Left Breaker: 225ALeft Breaker: 225A
Mfg.Power Distribution Inc. (PDI)Circuits (#1, #2, #3)Current AmpDesired Merged AmpCircuits (#1, #2, #3)Current AmpDesired Merged Amp
ModelPP13-1-3000-64138, 40, 4220A/ea60A1, 3, 520A/ea60A
KVA30037, 39, 4120A/ea60A7, 9, 1120A/ea60A
Inspection Date8/25/881, 3, 520A/ea60A33, 35, 3720A/ea60A
InputOutput2, 4, 620A/ea60A38, 40, 4220A/ea60A
Voltage480208/120
Amperage360830Quantity (Ct.)In-Use Breakers on the LeftIn-Use Breakers on the RightQuantity (Ct.)In-Use Breakers on the LeftIn-Use Breakers on the Right
Freq (Hz)6060820420
Phase33260160
Main Breaker50022515201120
160160
This information was acquire by physically inspecting the inside of the PDU panel on May 2nd 2024 by 1Lt Devlin.Total Amps in-use:640Total Amps in-use:420
By "in-use" I mean these breakers are flipped to the "ON" position.By "in-use" I mean these breakers are flipped to the "ON" position.
PDU5 has two panels, "PDU5A" and "PDU5B", they have four (4) 225A breaks between them.
Right Breaker: 225ARight Breaker: 225A
PDU6 has one panel, "PDU6" which has two (2) 225A breakers. It has a 2nd panel but it's naked and only has a 150A breaker.Circuits (#1, #2, #3)Current AmpDesired Merged AmpCircuits (#1, #2, #3)Current AmpDesired Merged Amp
58, 60, 6220A/ea60A43, 45, 4720A/ea60A
Each PDU's 225 Breaker has 42 circuit slots, 21 on the left and 21 on the right.80, 82, 8420A/ea60A53, 55, 5720A/ea60A
75, 77, 7920A/ea60A65, 67, 6920A/ea60A
168 Circuits for PDU5A and B and 84 Circuits for PDU6 (+42 if you count the naked 150A PDU6 side panel).59, 61, 6320A/ea60A80, 82, 8420A/ea60A
Quantity (Ct.)In-Use Breakers on the LeftIn-Use Breakers on the RightQuantity (Ct.)In-Use Breakers on the LeftIn-Use Breakers on the Right
PDU/Panel# of Desired 60A Circuits# of Replaced 20A Circuits920720
PDU5A824130130
PDU5B82410201220
PDU6824260
(Counting 3 merg'd 20A =1x 60A)Total Amps in-use:530Total Amps in-use:410
By "in-use" I mean these breakers are flipped to the "ON" position.By "in-use" I mean these breakers are flipped to the "ON" position.
PDU 6 has a secondary naked panel (no circuits just filler breakers) that has a M.B. = 150A
PDU 5B
Left Breaker: 225A
Circuits (#1, #2, #3)Current AmpDesired Merged Amp
38, 40, 4220A/ea60A
37, 39, 4120A/ea60A
1, 3, 520A/ea60A
2, 4, 620A/ea60A
Quantity (Ct.)In-Use Breakers on the LeftIn-Use Breakers on the Right
1120
630
1320
630
Total Amps in-use:840
By "in-use" I mean these breakers are flipped to the "ON" position.
Right Breaker: 225A
Circuits (#1, #2, #3)Current AmpDesired Merged Amp
43, 45, 4720A/ea60A
44, 46, 4820A/ea60A
67, 69, 7120A/ea60A
68, 70, 7220A/ea60A
Quantity (Ct.)In-Use Breakers on the LeftIn-Use Breakers on the Right
1420
230
1120
430
Total Amps in-use:680
By "in-use" I mean these breakers are flipped to the "ON" position.

File details come from the government source that posted it. Updated .