Series V Engineering Data.pdf
PDF 336 KB Posted
- Attached to
- Cooling Tower Replacement Federal contract opportunity
- Solicitation number
- 70FBR023Q00000002
- Issued by
- Federal Emergency Management Agency
About this file
This document package includes an engineering data file and a related federal contract opportunity notice. The engineering data file provides specifications for Baltimore Aircoil Company's Series V closed-circuit cooling tower models, including dimensions, weights, connections, performance data, and engineering drawings.
The related federal solicitation seeks offers to replace cooling towers for the Federal Emergency Management Agency. The opportunity is open to all responsible sources and has an estimated value over $250,000. Proposals are due by April 15, 2023, with award anticipated by June 1, 2023. The selected contractor will be responsible for removing existing towers and installing new models per the specifications in the engineering data file.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SOO -Modification R10 FRC Cooling Tower Replacement (002) (002).pdf | ||
| DOL Wage Rates Construction.pdf | ||
| SOO R10 FRC Cooling Tower Replacement V.pdf | ||
| Best Value Qualifications V.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C127 Q U E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W . B A L T I M O R E A I R C O I L . C O M
Series V Engineering Data
Fluid In
Fluid out
1/2” FPT Vent
2” Drain
2” Overflow
1” Make-up
3’ 11-1/2” L
A M
F
H
L
M
1/2” FPT Vent Fluid In
Fluid Out
Access1” Make-up
3” Overflow
2” Drain
4’- 8 5/8”
H
F
M
L
Fluid In
Fluid Out
1/2” MPT Vent
2” Make-up
3” Overflow
Access
7’ - 10 3/8”
F
H
A
Side Elevation: Models VF1-009 to 036End Elevation: Models VF1-009 to 036
Side Elevation: Models VF1-072
Side Elevation: Models VF1-048
End Elevation: Models VF1-072
End Elevation: Models VF1-048
V F 1 M O D E L S
NOTES FOR OPPOSITE TABLE:
1. Nominal tons of cooling represents the capability to cool 3 USGPM of water from a 95°F entering water temperature to an 85°F leaving water temperature at a 78°F entering wet-bulb temperature.
2. Fan horsepower is at 0” external static pressure.
3. Operating weight is for the unit with the water level in the cold water basin at the overflow and a full coil.
4. Units marked with an asterisk ship in one piece. The coil section is the heaviest section.
5. Standard coil connections are beveled for welding.
6. The number and location of coil connections will vary with design flow and coil arrangement.
7. If discharge hoods with positive closure damper are furnished, see page C135 for added weight and height. Fan motor horsepower may increase; consult selection software for verification.
8. For VF1-009 to 048, the riser pipe diameter is 3”. For VF1-072 the riser pipe diameter is 4”.
Do not use for construction. Refer to factory certified dimensions. This catalog includes data current at the time of publication, which should be reconfirmed at the time of purchase.
P R O D U C T & A P P L I C A T I O N H A N D B O O K V O L U M E V C128
NOTE: Up-to-date engineering data, free product selection software, and more can be found at www.BaltimoreAircoil.com.
Model Number
Nominal Tons[1]
Motor HP
Airflow
(CFM)
Weights (lbs) Dimensions Connections Spray Pump
(USGPM)
Internal Coil Volume
(gal)Fan[2] Pump Operating[3] Shipping Heaviest Section[4] L H F A Coil[5,6] Overflow
VF1-009-12E 4 1.5
1/3
4,510 1,875 1,625 1,460*
3’-0”
7’-4” 1’-11”
3’-9” 3” 2” 35
VF1-009-12F 5 2 4,970 1,875 1,625 1,460* 7’-4” 1’-11” 20
VF1-009-12G 5 3 5,690 1,875 1,625 1,460* 7’-4” 1’-11” 20
VF1-009-22F 6 2 4,890 2,075 1,785 1,000 8’-1” 2’-8” 26
VF1-009-22G 7 3 5,590 2,075 1,785 1,000 8’-1” 2’-8” 26
VF1-009-32G 8 3 5,520 2,295 1,965 1,180 8’-9” 3’-4” 31
VF1-009-42G 9 3 5,470 2,495 2,125 1,340 9’-6” 4’-1” 36
VF1-018-12F 9 2
1/2
8,050 2,955 2,415 2,415*
6’-0”
7’-4” 1’-11”
3’-9” 4” 2” 75
VF1-018-12G 11 3 9,220 2,955 2,415 2,415* 7’-4” 1’-11” 38
VF1-018-12H 14 5 10,930 2,955 2,415 2,415* 7’-4” 1’-11” 38
VF1-018-22H 17 5 10,750 3,260 2,640 1,720 8’-1” 2’-8” 49
VF1-018-22J 20 7.5 12,310 3,260 2,640 1,720 8’-1” 2’-8” 49
VF1-018-32G 16 3 8,960 3,660 2,940 2,010 8’-9” 3’-3” 60
VF1-018-32H 19 5 10,620 3,660 2,940 2,010 8’-9” 3’-3” 60
VF1-018-32J 22 7.5 12,150 3,660 2,940 2,010 8’-9” 3’-3” 60
VF1-018-42H 21 5 10,510 4,010 3,190 2,260 9’-6” 4’-0” 71
VF1-018-42J 24 7.5 12,030 4,010 3,190 2,260 9’-6” 4’-0” 71
VF1-027-22H 24 5
3/4
14,060 4,860 3,750 2,470
9’-0”
8’-4” 2’-10”
3’-9” 4” 2” 115
VF1-027-22J 28 7.5 16,090 4,860 3,750 2,470 8’-4” 2’-10” 72
VF1-027-22K 32 10 17,710 4,860 3,750 2,470 8’-4” 2’-10” 72
VF1-027-32H 26 5 13,880 5,440 4,180 2,850 9’-1” 3’-7” 89
VF1-027-32J 31 7.5 15,890 5,440 4,180 2,850 9’-1” 3’-7” 89
VF1-027-32K 35 10 17,490 5,440 4,180 2,850 9’-1” 3’-7” 89
VF1-027-42H 28 5 13,740 5,970 4,570 3,240 9’-10” 4’-4” 106
VF1-027-42J 33 7.5 15,730 5,970 4,570 3,240 9’-10” 4’-4” 106
VF1-027-42K 37 10 17,310 5,970 4,570 3,240 9’-10” 4’-4” 106
VF1-036-21L 41 15
24,870 6,280 4,760 3,200
12’-0”
8’-4” 2’-10”
3’-9” 4” 2” 150
VF1-036-22J 35 7.5 19,740 6,280 4,760 3,200 8’-4” 2’-10” 95
VF1-036-22K 39 10 21,730 6,280 4,760 3,200 8’-4” 2’-10” 95
VF1-036-22L 47 15 24,870 6,280 4,760 3,200 8’-4” 2’-10” 95
VF1-036-31L 44 15 24,560 7,020 5,310 3,720 9’-1” 3’-7” 118
VF1-036-32J 37 7.5 19,490 7,020 5,310 3,720 9’-1” 3’-7” 118
VF1-036-41L 47 15 24,310 7,710 5,810 4,220 9’-10” 4’-4” 140
VF1-036-51L 49 15 24,100 8,390 6,310 4,720 10’-7” 4’-4” 163
VF1-048-21L 48 15
1 1/2
32,520 10,230 7,870 4,920
12’-0”
10’-0” 2’-10”
5’-5” 4” 3” 220
VF1-048-21M 55 20 35,790 10,230 7,870 4,920 10’-0” 2’-10” 137
VF1-048-31M 59 20 35,340 11,390 8,460 5,930 10’-9” 3’-7” 170
VF1-048-31N 65 25 38,070 11,390 8,460 5,930 10’-9” 3’-7” 170
VF1-048-41M 63 20 34,980 12,690 9,320 6,600 11’-7” 4’-4” 203
VF1-048-41N 70 25 37,690 12,690 9,320 6,600 11’-7” 4’-4” 203
VF1-072-21M 62 20
45,990 15,670 10,720 6,580
11’-8”
11’-4” 2’-10”
6’-9” 4” 3” 305
VF1-072-21N 69 25 49,540 15,670 10,720 6,580 11’-4” 2’-10” 190
VF1-072-21O 75 30 52,650 15,670 10,720 6,580 11’-4” 2’-10” 190
VF1-072-31M 67 20 45,420 17,380 12,050 7,950 12’-2” 3’-7” 235
VF1-072-31N 74 25 48,930 17,380 12,050 7,950 12’-2” 3’-7” 235
VF1-072-31O 81 30 51,990 17,380 12,050 7,950 12’-2” 3’-7” 235
VF1-072-41M 72 20 44,960 18,000 12,480 9,320 12’-11” 4’-4” 281
VF1-072-41N 80 25 48,430 18,000 12,480 9,320 12’-11” 4’-4” 281
VF1-072-41O 86 30 51,460 18,000 12,480 9,320 12’-11” 4’-4” 281
Side Elevation: Models VF1-009 to 036
Side Elevation: Models VF1-072
Side Elevation: Models VF1-048
JamieL Rectangle
C135 Q U E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W . B A L T I M O R E A I R C O I L . C O M
› Discharge Hoods with Positive Closure Dampers
| Both | tapered | and | straight | discharge | hoods | with | factory | mounted | positive | closure | dampers | and | damper | actuators | are | |||||
| available | for | all | Series | V | Closed | Circuit | Cooling | Towers. | Hoods | are | designed | to | minimize | heat | loss | from | convective | air | ||
| flow | through | an | idle | unit. | The | addition | of | factory | installed | insulation | to | the | hood | and | casing | further | reduces | the | heat | loss |
| by | minimizing | losses | due | to | conduction. | Heat | loss | data | is | presented | on page C136 for | units | without | hood, | with | hood, | ||||
| and | with | insulated | casing | and | hood. | Damper | actuators | and | linkage | are | factory | mounted | on | the | hood. |
| All | wiring | and | actuator | controls | must | be | furnished | by | others. | 115 | volt | single | phase | power | supply | is | required. | Damper |
| actuators | should | be | interlocked | with | the | temperature | control | system | so | that | the | dampers | are | open | when | the | pumps | are |
| running | and | closed | when | the | pumps | are | off. |
| The | additional | external | static | pressure | of | the | tapered | discharge | hood | with | dampers | may | require | the | use | of | a | larger | fan |
| motor; | consult | selection | software | for | verification. | Consult | your | local | BAC | Representative | for | a | unit | drawing | with | a | hood | ||
| and | positive | closure | dampers. |
L
1 1/2” 1 1/2”2”1 1/2”
W
1 1/2”
H
1 1/2” 1 1/2”
H
W
10” 10”
2” 1 1/2” 1 1/2”
L
Access Door
Access Door
Access Door
Access Door
Model Number
Number of Hoods Required
Tapered Total Shipping Weight (lbs)
Straight Total Shipping Weight (lbs)L W H L W H
VFL-012 1 2’-12” 2’-4” 2’-10”[2] 220[4] 3’ 3’-1” 3’-1”[2] 260[4]
VFL-024 1 3’-11” 2’-4” 2’-10”[2] 330[4] 5’-3” 3’-1” 3’-1”[2] 410[4]
VFL-036 1 6’-11” 2’-4” 2’-10”[2] 470[4] 8’-3” 3’-1” 3’-1”[2] 540[4]
VFL-048 1 9’-10” 2’-4” 2’-10”[2] 590[4] 11’-2” 3’-1” 3’-1”[2] 760[4]
VFL-072 1 6’-11” 4’-1” 4’-3”[2] 910 [4] 8’-3” 6’-4” 3’-1”[2] 960[4]
VFL-096 1 8’-3” 4’-1” 4’-3”[2] 1,100[4] 11’-2” 6’-4” 3’-1”[2] 1,200[4]
VF1-009 1 2’-11” 1’-5” 3’-2”[1] 280[3] 3’ 3’-1” 3’-1”[2] 300[3]
VF1-018 1 3’-11” 1’-5” 3’-2”[1] 470[3] 5’-1” 3’-1” 3’-1”[2] 490[3]
VF1-027 1 6’-11” 1’-5” 3’-2”[1] 640[3] 8’-3” 3’-1” 3’-1”[2] 680[3]
VF1-036 1 9’-10” 1’-5” 3’-2”[1] 760[3] 11’-2” 3’-1” 3’-1”[2] 840[3]
VF1-048 1 8’-3” 2’-4” 4’-9”[1] 1,240[3] 11’-2” 4’-1” 3’-10”[2] 1,220[3]
VF1-072 1 8’-3” 3’-1” 4’-9”[1] 1,540[3] 10’-6” 5’-10” 3’-10”[2] 1,620[3]
VF1-096 1 8’-3” 4’-1” 4’-5”[2] 1,200[4] 11’-2” 6’-4” 3’-10”[2] 1,320[4]
VF1-144N 1 14’-2” 3’-8” 4’-5”[2] 1,750[4] 16’-8” 6’-4” 3’-10”[2] 1,820[4]
VF1-144 1 8’-3” 6’-4” 4’-5”[2] 1,550[4] 11’-2” 10’-4” 3’-10”[2] 1,750[4]
VF1-192 2 8’-3” 4’-1” 4’-5”[2] 2,400[4] 11’-2” 6’-7” 3’-10”[2] 2,640[4]
VF1-216 1 14’-2” 5’-11” 4’-5”[2] 2,150[4] 16’-8” 10’-4” 3’-10”[2] 2,400[4]
VF1-288N 2 14’-2” 3’-8” 4’-5”[2] 3,500[4] 16’-8” 6’-4” 3’-10”[2] 3,640[4]
VF1-1012N 1 12’-0” 5’-3” 4’-10”[2] 1,180[4] 12’-0” 10’-10” 4’-11”[2] 1,510[4]
VF1-1018N 1 18’-0” 5’-3” 4’-10”[2] 1,580[4] 18’-0” 10’-10” 4’-11”[2] 2,110[4]
VF1-1024N 2 12’-0” 5’-3” 4’-10”[2] 2,360[4] 12’-0” 10’-10” 4’-11”[2] 3,020{4]
VF1-1036N 2 18’-0” 5’-3” 4’-10”[2] 3,160[4] 18’-0” 10’-10” 4’-11”[2] 4,220[4]
VF1-288 2 8’-3” 6’-4” 4’-5”[2] 3,100[4] 11’-2” 10’-4” 3’-10”[2] 3,500[4]
VF1-432 2 14’-2” 5’-11” 4’-5”[2] 4,300[4] 16’-8” 10’-4” 3’-10”[2] 4,800[4]
NOTES (APPLICABLE TO SPECIFIC MODELS ONLY):
1. On these models, the discharge hood surrounds the drift eliminators and is recessed into the drift eliminator frame; therefore, the overall height of the unit with hood equals H (of unit) plus H (of hood) minus 4”.
2. On these units, the hood sits directly on top of the casing.
3. Includes drift eliminators and skid.
4. Includes skid only. Drift eliminators are included in unit weight.
Series V Engineering Data
JamieL Rectangle
JamieL Highlight
JamieL Highlight
JamieL Highlight
Highlight
P R O D U C T & A P P L I C A T I O N H A N D B O O K V O L U M E V C136
V F L H E A T L O S S D A T A ( B T U H ) [ 1 ] V F 1 H E A T L O S S D A T A ( B T U H ) [ 1 ]
Model Number (VFL Models Only)
Standard Unit Heat Loss
(BTU/HR)
Unit w/ Hood & Positive Closure
Dampers
Unit w/ Hood, Positive Closure
Dampers & Insulation[2]
VFL-012-02 19,200 16,500 11,000
VFL-012-12 25,000 17,800 11,900
VFL-012-22 29,900 19,200 12,800
VFL-012-32 33,800 20,500 13,700
VFL-024-12 48,200 28,500 19,000
VFL-024-22 57,700 30,400 20,300
VFL-024-32 65,400 32,300 21,500
VFL-036-22 87,000 47,100 30,700
VFL-036-33 98,400 49,800 32,500
VFL-048-22 126,400 66,000 42,600
VFL-048-31 138,800 69,300 44,800
VFL-048-41 151,200 72,600 47,000
VFL-072-22 210,900 84,400 56,200
VFL-072-31 234,100 87,900 58,600
VFL-072-41 252,900 91,400 60,900
VFL-096-41 311,700 103,600 69,000
Model Number ( VF1 Models Only)
Standard Unit Heat Loss (BTU/hr)
Unit w/ Hood & Positive
Closure Dampers
Unit w/ Hood, Positive Closure
Dampers & Insulation[2]
VF1-009-12 24,300 17,100 10,300
VF1-009-22 29,400 18,800 12,000
VF1-009-32 32,900 20,500 12,000
VF1-009-42 34,800 22,200 13,700
VF1-018-02 34,700 25,600 15,400
VF1-018-12 46,200 27,300 15,400
VF1-018-22 56,000 29,100 17,100
VF1-018-32 64,300 30,800 17,100
VF1-018-42 70,950 32,550 18,800
VF1-027-22 86,100 46,100 27,300
VF1-027-32 97,700 49,500 29,100
VF1-027-42 106,300 52,900 29,100
VF1-036-21 112,600 63,200 39,300
VF1-036-31 128,900 66,600 39,300
VF1-036-41 145,200 70,000 43,600
VF1-036-51 161,500 73,400 43,600
VF1-048-21 154,900 80,200 52,900
VF1-048-31 177,200 83,700 52,900
VF1-048-41 197,000 85,600 54,600
VF1-072-21 212,400 83,700 51,200
VF1-072-31 241,100 87,100 51,200
VF1-072-41 269,800 90,500 56,800
VF1-096-31 286,700 97,600 60,000
VF1-096-41 312,100 102,600 60,900
VF1-096-51 329,800 107,900 61,700
VF1-144N-21 381,400 128,300 81,300
VF1-144N-31 429,900 134,700 82,800
VF1-144N-41 464,800 141,400 84,400
VF1-144-21 385,000 139,900 88,600
VF1-144-31 435,500 146,900 90,200
VF1-144-41 474,600 154,200 91,900
VF1-192-31 576,300 228,400 153,600
VF1-192-41 627,300 240,100 156,700
VF1-192-51 662,800 252,500 160,100
VF1-216-21 579,900 194,000 122,900
VF1-216-31 653,500 203,700 125,100
VF1-216-41 707,300 213,800 127,300
VF1-288N-21 762,800 256,600 162,600
VF1-288N-31 859,800 269,400 165,600
VF1288N-41 929,600 282,800 168,800
VF1-1012N 355,500 144,900 91,700
VF1-1018N 528,600 185,800 123,300
VF1-1024N 711,000 289,700 183,400
VF1-1036N 1,884,100 399,800 250,000
VF1-288-21 750,800 260,300 171,900
VF1-288-31 849,300 273,300 175,000
VF1-288-41 925,600 286,800 178,300
VF1-432-21 1,142,500 390,000 259,400
VF1-432-31 1,287,400 409,500 264,000
VF1-432-41 1,393,500 429,800 268,500
NOTES:
1. Heat loss is based on 50ºF (10˚C) coil water and -10ºF (-23˚C) ambient with a 45 MPH wind. Fan(s) and pump(s) are off.
2. One inch thick PVC nitrite rubber blend thermal insulation with protective paint.
C137 Q U E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W . B A L T I M O R E A I R C O I L . C O M
Series V Structural Support
| The | recommended | support | arrangement | for | the | Series | V | Closed | Circuit | Cooling | Tower | consists | of | parallel | structural | members | ||||||
| running | the | full | length | of | the | unit, | spaced | as | shown | in | the | following | drawing. | In | addition | to | providing | adequate | support, | the | ||
| members | also | serve | to | raise | the | unit | above | any | solid | foundation | to | ensure | access | to | the | bottom | of | the | tower. | To | support | a |
| Series | V | Closed | Circuit | Cooling | Tower | in | an | alternate | support | arrangement, | consult | your | local | BAC | Representative. |
VF1-009 thru -048, -072, -096, -144, & -1012NVFL Models
Model Number A B
VFL-012 3’ -11” 4’ -6”
VFL-024 3’ -11” 8’
VFL-036 3’ -11” 11’
VFL-048 3’ -11” 14’
VFL-072 7’ -9” 11’
VFL-096 7’ -9” 14’
VF1-009 3’ -10” 2’ -6”
VF1-018 3’ -10” 5’ -6”
VF1-027 3’ -10” 8’ -6”
VF1-036 3’ -10” 11’ -6”
VF1-048 4’ -7” 11’ -6”
VF1-072, 096 7’ -8” 10’ -8”
VF1-144N 7’ -8” 16’ -8”
VF1-192 7’ -8” 22’ -9”
VF1-288N 7’ -8” 34’ -9”
VF1-1012 9’ -8” 10’ -8”
VF1-1018 9’ -8” 10’ -8”
VF1-1024 9’ -8” 16’ -8”
VF1-1036 9’ -8” 22’ -11”
VF1-144 11’ -8” 33’ -7”
VF1-216 11’ -8” 16’ -8”
VF1-288 11’ -8” 22’ -9”
VF1-432 11’ -8” 34’ -9”
NOTES:
1. Support members and anchor bolts shall be designed, furnished, and installed by others.
2. Design of support members and anchor bolts shall be in accordance with the strength and serviceability requirements of the applicable building code and project specifications.
3. Support members shall be level at the top.
4. Refer to the certified unit support drawing for loading and additional support requirements.
5. If vibration isolation (provided by others) is used, the isolators should be located under a structural base that complies with one of the recommended support arrangements. Contact your local BAC Representative for all other isolator configurations.
VF1-288N, -432, & -1036NVF1-144N, -192, -216, -288, -1018N, & -1024