Series V Engineering Data.pdf

PDF 336 KB Posted

Attached to
Cooling Tower Replacement Federal contract opportunity
Solicitation number
70FBR023Q00000002
Issued by
Federal Emergency Management Agency

About this file

This document package includes an engineering data file and a related federal contract opportunity notice. The engineering data file provides specifications for Baltimore Aircoil Company's Series V closed-circuit cooling tower models, including dimensions, weights, connections, performance data, and engineering drawings.

The related federal solicitation seeks offers to replace cooling towers for the Federal Emergency Management Agency. The opportunity is open to all responsible sources and has an estimated value over $250,000. Proposals are due by April 15, 2023, with award anticipated by June 1, 2023. The selected contractor will be responsible for removing existing towers and installing new models per the specifications in the engineering data file.

View the file

Other files for this federal contract opportunity

Other files attached to Cooling Tower Replacement, newest first.
File Type Posted
SOO -Modification R10 FRC Cooling Tower Replacement (002) (002).pdf PDF
DOL Wage Rates Construction.pdf PDF
SOO R10 FRC Cooling Tower Replacement V.pdf PDF
Best Value Qualifications V.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C127 Q U E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W . B A L T I M O R E A I R C O I L . C O M

Series V Engineering Data

Fluid In

Fluid out

1/2” FPT Vent

2” Drain

2” Overflow

1” Make-up

3’ 11-1/2” L

A M

F

H

L

M

1/2” FPT Vent Fluid In

Fluid Out

Access1” Make-up

3” Overflow

2” Drain

4’- 8 5/8”

H

F

M

L

Fluid In

Fluid Out

1/2” MPT Vent

2” Make-up

3” Overflow

Access

7’ - 10 3/8”

F

H

A

Side Elevation: Models VF1-009 to 036End Elevation: Models VF1-009 to 036

Side Elevation: Models VF1-072

Side Elevation: Models VF1-048

End Elevation: Models VF1-072

End Elevation: Models VF1-048

V F 1 M O D E L S

NOTES FOR OPPOSITE TABLE:

1. Nominal tons of cooling represents the capability to cool 3 USGPM of water from a 95°F entering water temperature to an 85°F leaving water temperature at a 78°F entering wet-bulb temperature.

2. Fan horsepower is at 0” external static pressure.

3. Operating weight is for the unit with the water level in the cold water basin at the overflow and a full coil.

4. Units marked with an asterisk ship in one piece. The coil section is the heaviest section.

5. Standard coil connections are beveled for welding.

6. The number and location of coil connections will vary with design flow and coil arrangement.

7. If discharge hoods with positive closure damper are furnished, see page C135 for added weight and height. Fan motor horsepower may increase; consult selection software for verification.

8. For VF1-009 to 048, the riser pipe diameter is 3”. For VF1-072 the riser pipe diameter is 4”.

Do not use for construction. Refer to factory certified dimensions. This catalog includes data current at the time of publication, which should be reconfirmed at the time of purchase.

P R O D U C T & A P P L I C A T I O N H A N D B O O K V O L U M E V C128

NOTE: Up-to-date engineering data, free product selection software, and more can be found at www.BaltimoreAircoil.com.

Model Number

Nominal Tons[1]

Motor HP

Airflow

(CFM)

Weights (lbs) Dimensions Connections Spray Pump

(USGPM)

Internal Coil Volume

(gal)Fan[2] Pump Operating[3] Shipping Heaviest Section[4] L H F A Coil[5,6] Overflow

VF1-009-12E 4 1.5

1/3

4,510 1,875 1,625 1,460*

3’-0”

7’-4” 1’-11”

3’-9” 3” 2” 35

VF1-009-12F 5 2 4,970 1,875 1,625 1,460* 7’-4” 1’-11” 20

VF1-009-12G 5 3 5,690 1,875 1,625 1,460* 7’-4” 1’-11” 20

VF1-009-22F 6 2 4,890 2,075 1,785 1,000 8’-1” 2’-8” 26

VF1-009-22G 7 3 5,590 2,075 1,785 1,000 8’-1” 2’-8” 26

VF1-009-32G 8 3 5,520 2,295 1,965 1,180 8’-9” 3’-4” 31

VF1-009-42G 9 3 5,470 2,495 2,125 1,340 9’-6” 4’-1” 36

VF1-018-12F 9 2

1/2

8,050 2,955 2,415 2,415*

6’-0”

7’-4” 1’-11”

3’-9” 4” 2” 75

VF1-018-12G 11 3 9,220 2,955 2,415 2,415* 7’-4” 1’-11” 38

VF1-018-12H 14 5 10,930 2,955 2,415 2,415* 7’-4” 1’-11” 38

VF1-018-22H 17 5 10,750 3,260 2,640 1,720 8’-1” 2’-8” 49

VF1-018-22J 20 7.5 12,310 3,260 2,640 1,720 8’-1” 2’-8” 49

VF1-018-32G 16 3 8,960 3,660 2,940 2,010 8’-9” 3’-3” 60

VF1-018-32H 19 5 10,620 3,660 2,940 2,010 8’-9” 3’-3” 60

VF1-018-32J 22 7.5 12,150 3,660 2,940 2,010 8’-9” 3’-3” 60

VF1-018-42H 21 5 10,510 4,010 3,190 2,260 9’-6” 4’-0” 71

VF1-018-42J 24 7.5 12,030 4,010 3,190 2,260 9’-6” 4’-0” 71

VF1-027-22H 24 5

3/4

14,060 4,860 3,750 2,470

9’-0”

8’-4” 2’-10”

3’-9” 4” 2” 115

VF1-027-22J 28 7.5 16,090 4,860 3,750 2,470 8’-4” 2’-10” 72

VF1-027-22K 32 10 17,710 4,860 3,750 2,470 8’-4” 2’-10” 72

VF1-027-32H 26 5 13,880 5,440 4,180 2,850 9’-1” 3’-7” 89

VF1-027-32J 31 7.5 15,890 5,440 4,180 2,850 9’-1” 3’-7” 89

VF1-027-32K 35 10 17,490 5,440 4,180 2,850 9’-1” 3’-7” 89

VF1-027-42H 28 5 13,740 5,970 4,570 3,240 9’-10” 4’-4” 106

VF1-027-42J 33 7.5 15,730 5,970 4,570 3,240 9’-10” 4’-4” 106

VF1-027-42K 37 10 17,310 5,970 4,570 3,240 9’-10” 4’-4” 106

VF1-036-21L 41 15

24,870 6,280 4,760 3,200

12’-0”

8’-4” 2’-10”

3’-9” 4” 2” 150

VF1-036-22J 35 7.5 19,740 6,280 4,760 3,200 8’-4” 2’-10” 95

VF1-036-22K 39 10 21,730 6,280 4,760 3,200 8’-4” 2’-10” 95

VF1-036-22L 47 15 24,870 6,280 4,760 3,200 8’-4” 2’-10” 95

VF1-036-31L 44 15 24,560 7,020 5,310 3,720 9’-1” 3’-7” 118

VF1-036-32J 37 7.5 19,490 7,020 5,310 3,720 9’-1” 3’-7” 118

VF1-036-41L 47 15 24,310 7,710 5,810 4,220 9’-10” 4’-4” 140

VF1-036-51L 49 15 24,100 8,390 6,310 4,720 10’-7” 4’-4” 163

VF1-048-21L 48 15

1 1/2

32,520 10,230 7,870 4,920

12’-0”

10’-0” 2’-10”

5’-5” 4” 3” 220

VF1-048-21M 55 20 35,790 10,230 7,870 4,920 10’-0” 2’-10” 137

VF1-048-31M 59 20 35,340 11,390 8,460 5,930 10’-9” 3’-7” 170

VF1-048-31N 65 25 38,070 11,390 8,460 5,930 10’-9” 3’-7” 170

VF1-048-41M 63 20 34,980 12,690 9,320 6,600 11’-7” 4’-4” 203

VF1-048-41N 70 25 37,690 12,690 9,320 6,600 11’-7” 4’-4” 203

VF1-072-21M 62 20

45,990 15,670 10,720 6,580

11’-8”

11’-4” 2’-10”

6’-9” 4” 3” 305

VF1-072-21N 69 25 49,540 15,670 10,720 6,580 11’-4” 2’-10” 190

VF1-072-21O 75 30 52,650 15,670 10,720 6,580 11’-4” 2’-10” 190

VF1-072-31M 67 20 45,420 17,380 12,050 7,950 12’-2” 3’-7” 235

VF1-072-31N 74 25 48,930 17,380 12,050 7,950 12’-2” 3’-7” 235

VF1-072-31O 81 30 51,990 17,380 12,050 7,950 12’-2” 3’-7” 235

VF1-072-41M 72 20 44,960 18,000 12,480 9,320 12’-11” 4’-4” 281

VF1-072-41N 80 25 48,430 18,000 12,480 9,320 12’-11” 4’-4” 281

VF1-072-41O 86 30 51,460 18,000 12,480 9,320 12’-11” 4’-4” 281

Side Elevation: Models VF1-009 to 036

Side Elevation: Models VF1-072

Side Elevation: Models VF1-048

JamieL Rectangle

C135 Q U E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W . B A L T I M O R E A I R C O I L . C O M

› Discharge Hoods with Positive Closure Dampers

Bothtaperedandstraightdischargehoodswithfactorymountedpositiveclosuredampersanddamperactuatorsare
availableforallSeriesVClosedCircuitCoolingTowers.Hoodsaredesignedtominimizeheatlossfromconvectiveair
flowthroughanidleunit.Theadditionoffactoryinstalledinsulationtothehoodandcasingfurtherreducestheheatloss
byminimizinglossesduetoconduction.Heatlossdataispresentedon page C136 forunitswithouthood,withhood,
andwithinsulatedcasingandhood.Damperactuatorsandlinkagearefactorymountedonthehood.
Allwiringandactuatorcontrolsmustbefurnishedbyothers.115voltsinglephasepowersupplyisrequired.Damper
actuatorsshouldbeinterlockedwiththetemperaturecontrolsystemsothatthedampersareopenwhenthepumpsare
runningandclosedwhenthepumpsareoff.
Theadditionalexternalstaticpressureofthetapereddischargehoodwithdampersmayrequiretheuseofalargerfan
motor;consultselectionsoftwareforverification.ConsultyourlocalBACRepresentativeforaunitdrawingwithahood
andpositiveclosuredampers.

L

1 1/2” 1 1/2”2”1 1/2”

W

1 1/2”

H

1 1/2” 1 1/2”

H

W

10” 10”

2” 1 1/2” 1 1/2”

L

Access Door

Access Door

Access Door

Access Door

Model Number

Number of Hoods Required

Tapered Total Shipping Weight (lbs)

Straight Total Shipping Weight (lbs)L W H L W H

VFL-012 1 2’-12” 2’-4” 2’-10”[2] 220[4] 3’ 3’-1” 3’-1”[2] 260[4]

VFL-024 1 3’-11” 2’-4” 2’-10”[2] 330[4] 5’-3” 3’-1” 3’-1”[2] 410[4]

VFL-036 1 6’-11” 2’-4” 2’-10”[2] 470[4] 8’-3” 3’-1” 3’-1”[2] 540[4]

VFL-048 1 9’-10” 2’-4” 2’-10”[2] 590[4] 11’-2” 3’-1” 3’-1”[2] 760[4]

VFL-072 1 6’-11” 4’-1” 4’-3”[2] 910 [4] 8’-3” 6’-4” 3’-1”[2] 960[4]

VFL-096 1 8’-3” 4’-1” 4’-3”[2] 1,100[4] 11’-2” 6’-4” 3’-1”[2] 1,200[4]

VF1-009 1 2’-11” 1’-5” 3’-2”[1] 280[3] 3’ 3’-1” 3’-1”[2] 300[3]

VF1-018 1 3’-11” 1’-5” 3’-2”[1] 470[3] 5’-1” 3’-1” 3’-1”[2] 490[3]

VF1-027 1 6’-11” 1’-5” 3’-2”[1] 640[3] 8’-3” 3’-1” 3’-1”[2] 680[3]

VF1-036 1 9’-10” 1’-5” 3’-2”[1] 760[3] 11’-2” 3’-1” 3’-1”[2] 840[3]

VF1-048 1 8’-3” 2’-4” 4’-9”[1] 1,240[3] 11’-2” 4’-1” 3’-10”[2] 1,220[3]

VF1-072 1 8’-3” 3’-1” 4’-9”[1] 1,540[3] 10’-6” 5’-10” 3’-10”[2] 1,620[3]

VF1-096 1 8’-3” 4’-1” 4’-5”[2] 1,200[4] 11’-2” 6’-4” 3’-10”[2] 1,320[4]

VF1-144N 1 14’-2” 3’-8” 4’-5”[2] 1,750[4] 16’-8” 6’-4” 3’-10”[2] 1,820[4]

VF1-144 1 8’-3” 6’-4” 4’-5”[2] 1,550[4] 11’-2” 10’-4” 3’-10”[2] 1,750[4]

VF1-192 2 8’-3” 4’-1” 4’-5”[2] 2,400[4] 11’-2” 6’-7” 3’-10”[2] 2,640[4]

VF1-216 1 14’-2” 5’-11” 4’-5”[2] 2,150[4] 16’-8” 10’-4” 3’-10”[2] 2,400[4]

VF1-288N 2 14’-2” 3’-8” 4’-5”[2] 3,500[4] 16’-8” 6’-4” 3’-10”[2] 3,640[4]

VF1-1012N 1 12’-0” 5’-3” 4’-10”[2] 1,180[4] 12’-0” 10’-10” 4’-11”[2] 1,510[4]

VF1-1018N 1 18’-0” 5’-3” 4’-10”[2] 1,580[4] 18’-0” 10’-10” 4’-11”[2] 2,110[4]

VF1-1024N 2 12’-0” 5’-3” 4’-10”[2] 2,360[4] 12’-0” 10’-10” 4’-11”[2] 3,020{4]

VF1-1036N 2 18’-0” 5’-3” 4’-10”[2] 3,160[4] 18’-0” 10’-10” 4’-11”[2] 4,220[4]

VF1-288 2 8’-3” 6’-4” 4’-5”[2] 3,100[4] 11’-2” 10’-4” 3’-10”[2] 3,500[4]

VF1-432 2 14’-2” 5’-11” 4’-5”[2] 4,300[4] 16’-8” 10’-4” 3’-10”[2] 4,800[4]

NOTES (APPLICABLE TO SPECIFIC MODELS ONLY):

1. On these models, the discharge hood surrounds the drift eliminators and is recessed into the drift eliminator frame; therefore, the overall height of the unit with hood equals H (of unit) plus H (of hood) minus 4”.

2. On these units, the hood sits directly on top of the casing.

3. Includes drift eliminators and skid.

4. Includes skid only. Drift eliminators are included in unit weight.

Series V Engineering Data

JamieL Rectangle

JamieL Highlight

JamieL Highlight

JamieL Highlight

Highlight

P R O D U C T & A P P L I C A T I O N H A N D B O O K V O L U M E V C136

V F L H E A T L O S S D A T A ( B T U H ) [ 1 ] V F 1 H E A T L O S S D A T A ( B T U H ) [ 1 ]

Model Number (VFL Models Only)

Standard Unit Heat Loss

(BTU/HR)

Unit w/ Hood & Positive Closure

Dampers

Unit w/ Hood, Positive Closure

Dampers & Insulation[2]

VFL-012-02 19,200 16,500 11,000

VFL-012-12 25,000 17,800 11,900

VFL-012-22 29,900 19,200 12,800

VFL-012-32 33,800 20,500 13,700

VFL-024-12 48,200 28,500 19,000

VFL-024-22 57,700 30,400 20,300

VFL-024-32 65,400 32,300 21,500

VFL-036-22 87,000 47,100 30,700

VFL-036-33 98,400 49,800 32,500

VFL-048-22 126,400 66,000 42,600

VFL-048-31 138,800 69,300 44,800

VFL-048-41 151,200 72,600 47,000

VFL-072-22 210,900 84,400 56,200

VFL-072-31 234,100 87,900 58,600

VFL-072-41 252,900 91,400 60,900

VFL-096-41 311,700 103,600 69,000

Model Number ( VF1 Models Only)

Standard Unit Heat Loss (BTU/hr)

Unit w/ Hood & Positive

Closure Dampers

Unit w/ Hood, Positive Closure

Dampers & Insulation[2]

VF1-009-12 24,300 17,100 10,300

VF1-009-22 29,400 18,800 12,000

VF1-009-32 32,900 20,500 12,000

VF1-009-42 34,800 22,200 13,700

VF1-018-02 34,700 25,600 15,400

VF1-018-12 46,200 27,300 15,400

VF1-018-22 56,000 29,100 17,100

VF1-018-32 64,300 30,800 17,100

VF1-018-42 70,950 32,550 18,800

VF1-027-22 86,100 46,100 27,300

VF1-027-32 97,700 49,500 29,100

VF1-027-42 106,300 52,900 29,100

VF1-036-21 112,600 63,200 39,300

VF1-036-31 128,900 66,600 39,300

VF1-036-41 145,200 70,000 43,600

VF1-036-51 161,500 73,400 43,600

VF1-048-21 154,900 80,200 52,900

VF1-048-31 177,200 83,700 52,900

VF1-048-41 197,000 85,600 54,600

VF1-072-21 212,400 83,700 51,200

VF1-072-31 241,100 87,100 51,200

VF1-072-41 269,800 90,500 56,800

VF1-096-31 286,700 97,600 60,000

VF1-096-41 312,100 102,600 60,900

VF1-096-51 329,800 107,900 61,700

VF1-144N-21 381,400 128,300 81,300

VF1-144N-31 429,900 134,700 82,800

VF1-144N-41 464,800 141,400 84,400

VF1-144-21 385,000 139,900 88,600

VF1-144-31 435,500 146,900 90,200

VF1-144-41 474,600 154,200 91,900

VF1-192-31 576,300 228,400 153,600

VF1-192-41 627,300 240,100 156,700

VF1-192-51 662,800 252,500 160,100

VF1-216-21 579,900 194,000 122,900

VF1-216-31 653,500 203,700 125,100

VF1-216-41 707,300 213,800 127,300

VF1-288N-21 762,800 256,600 162,600

VF1-288N-31 859,800 269,400 165,600

VF1288N-41 929,600 282,800 168,800

VF1-1012N 355,500 144,900 91,700

VF1-1018N 528,600 185,800 123,300

VF1-1024N 711,000 289,700 183,400

VF1-1036N 1,884,100 399,800 250,000

VF1-288-21 750,800 260,300 171,900

VF1-288-31 849,300 273,300 175,000

VF1-288-41 925,600 286,800 178,300

VF1-432-21 1,142,500 390,000 259,400

VF1-432-31 1,287,400 409,500 264,000

VF1-432-41 1,393,500 429,800 268,500

NOTES:

1. Heat loss is based on 50ºF (10˚C) coil water and -10ºF (-23˚C) ambient with a 45 MPH wind. Fan(s) and pump(s) are off.

2. One inch thick PVC nitrite rubber blend thermal insulation with protective paint.

C137 Q U E S T I O N S ? C A L L 4 1 0 . 7 9 9 . 6 2 0 0 O R V I S I T W W W . B A L T I M O R E A I R C O I L . C O M

Series V Structural Support

TherecommendedsupportarrangementfortheSeriesVClosedCircuitCoolingTowerconsistsofparallelstructuralmembers
runningthefulllengthoftheunit,spacedasshowninthefollowingdrawing.Inadditiontoprovidingadequatesupport,the
membersalsoservetoraisetheunitaboveanysolidfoundationtoensureaccesstothebottomofthetower.Tosupporta
SeriesVClosedCircuitCoolingTowerinanalternatesupportarrangement,consultyourlocalBACRepresentative.

VF1-009 thru -048, -072, -096, -144, & -1012NVFL Models

Model Number A B

VFL-012 3’ -11” 4’ -6”

VFL-024 3’ -11” 8’

VFL-036 3’ -11” 11’

VFL-048 3’ -11” 14’

VFL-072 7’ -9” 11’

VFL-096 7’ -9” 14’

VF1-009 3’ -10” 2’ -6”

VF1-018 3’ -10” 5’ -6”

VF1-027 3’ -10” 8’ -6”

VF1-036 3’ -10” 11’ -6”

VF1-048 4’ -7” 11’ -6”

VF1-072, 096 7’ -8” 10’ -8”

VF1-144N 7’ -8” 16’ -8”

VF1-192 7’ -8” 22’ -9”

VF1-288N 7’ -8” 34’ -9”

VF1-1012 9’ -8” 10’ -8”

VF1-1018 9’ -8” 10’ -8”

VF1-1024 9’ -8” 16’ -8”

VF1-1036 9’ -8” 22’ -11”

VF1-144 11’ -8” 33’ -7”

VF1-216 11’ -8” 16’ -8”

VF1-288 11’ -8” 22’ -9”

VF1-432 11’ -8” 34’ -9”

NOTES:

1. Support members and anchor bolts shall be designed, furnished, and installed by others.

2. Design of support members and anchor bolts shall be in accordance with the strength and serviceability requirements of the applicable building code and project specifications.

3. Support members shall be level at the top.

4. Refer to the certified unit support drawing for loading and additional support requirements.

5. If vibration isolation (provided by others) is used, the isolators should be located under a structural base that complies with one of the recommended support arrangements. Contact your local BAC Representative for all other isolator configurations.

VF1-288N, -432, & -1036NVF1-144N, -192, -216, -288, -1018N, & -1024

File details come from the government source that posted it. Updated .