SECTION_J_3_Drawings.pdf
PDF 14 MB Posted
- Attached to
- Elevator Refurbishment and Fire Alarm System Repla Federal contract opportunity
- Solicitation number
- 140R1024B0008
About this file
This document is a set of drawings (SECTION_J_3_Drawings.pdf) that are part of the solicitation for the Elevator Refurbishment and Fire Alarm System Replacement project at the Colombia Basin Project Ephrata Field Office in Ephrata, Washington. The solicitation number is 140R1024B0008, and it was issued by the Department of the Interior Bureau of Reclamation. The project includes the refurbishment of the elevators and the replacement of the fire alarm system at the facility. The drawings provide detailed technical specifications and schematics for the required work. No additional information about pricing, response dates, award dates, set asides, or incumbent contractors is provided in this particular document.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140R1024B0008_Amd_0005.pdf | ||
| EFO-07032024_0004.pdf | ||
| AMD_0004-signed_0004.pdf | ||
| Sol_140R1024B0008_Amd_0004.pdf | ||
| Sol_140R1024B0008_Amd_0003.pdf | ||
| C06-01_SF30_140R1024B0008_and_QnA_0003.pdf | ||
| Fire_Alarm_Plan_0002.pdf | ||
| Pre-Bid_Const_Site_Visit_Att_Roster_0002.pdf | ||
| Sol_140R1024B0008_Amd_0002.pdf | ||
| Sol_140R1024B0008_Amd_0001.pdf | ||
| C06-01_Att_1_Newly_Conformed_Site_Visit_Clause_0001.pdf | ||
| C06-01_140R1024B0008_Amendment_0001_0001.pdf | ||
| Sol_140R1024B0008.pdf | ||
| C05-03_140R1024B0008_V4.pdf | ||
| SECTION_J_2_Bid_Bond.pdf | ||
| SECTION_J_1_Wage_Determination_WA20240026.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
LW
A
YS
T H
IN
K
S A
FE
TY
SHEET
D
C
B
A
D
C
B
A
B U
R
EA
U O
F R
EC
LA
M
A
TI
O N
U .S
D
EP
A R
TM
EN
T
O F
TH
E
IN
TE
R
IO
R
C A D
S
YS
TE
M
A ut oC A D
4.
0S
LM
S T
EC
H
C A D
F
IL
EN
A M
E
2-
0-
7-
R D
-1 .D
W G
LA
S T
S A V
ED
D A
TE
-0 5-
LA
S T
S A V
ED
B Y
R
LE
IJ
A
C O
LU
M
B
IA
B A S
IN
P R O
JE
C T
G R A V
IT
Y D
IV
IS
IO
N
EP
H
R A
TA
F
IE
LD
O
FF
IC
E B U
IL
D
IN
G
EL
EV
A
TO
R R
EF
U
R B
IS
H M
EN
T
A N
D F
IR
E
A
LA
R M
S
YS
TE
M
R
EP
LA
C
EM
EN
T
VICINITY AND SHEET
INDEX
BOISE, ID
222-100-61247
2023-05-31
DESIGNED
DRAWN
CHECKED
TECH. APPR.
APPROVED
ADMIN APPROVAL -
David Christensen
Rey Leija
Jeff McGuire
Christensen, David P.E.
Hovde, Jay B
Jay Hovde
SHEET INDEX
Sheet No. Drawing No. Contents
1 222-100-61247 Vicinity & Sheet Index
2 222-100-61248 Elevator Machine Room: Equipment Removal
3 222-100-61249 Elevator Pit: Equipment Removal
4 222-100-61250 Elevator Machine Room: Electrical and HVAC Indoor Installation
5 222-100-61251 Elevator Machine Room: HVAC Outdoor Installation
6 222-100-61252 Elevator Machine Room/Access Guardrail: Equipment Removal and Installation
7 222-100-61253 Elevator Pit: Electrical Installation
8 222-100-61254 Elevator Pit: Electrical Installation Sections A & C
9 222-100-61255 Machine Room and Elevator Pit Lighting Installation
10 222-100-61256 Electrical Details: Lighting
INFORMATION DRAWINGS
Sheet No. Drawing No. Contents
11 222-100-1337 Life Safety Improvements - Phase II - Panel Schedules - Electrical
12 222-D-14776 Architectural - Completion of Basement Plan and Finish Schedule
13 222-D-14780 Architectural - Exterior Elevations - Plot Plan & Storm Water Drainage Details
14 222-D-14781 Architectural - Exterior Elevations
15 222-D-14783 Architectural - Elevator Shaft - Miscellaneous Sections and Details
16 222-D-14815 Passenger Elevator Installation
17 222-D-14816 Outline and Reinforcement - Basement Plan
18-31 180913-005 BOR Ephrata Car 1
STANDARD DRAWINGS
Sheet No. Drawing No. Contents
32 40-D-7102 Government Drawing Format - Drawing Border, Sample Title Block and Signature Lines
33 104-D-254 Electrical Standards
34 104-D-286 Conduits
EPHRATA FIELD OFFICE BUILDING
ELEVATOR REFURBISHMENT AND FIRE ALARM SYSTEM REPLACEMENT
KEY PLAN PROJECT SITE
Project Site Ephrata Field Office 32 C St. NW Ephrata, WA 98823
Division Ave. W.
C St
. N W
Ba si n St
. N W
1st Ave. NW.
Division Ave. W.
1st Ave. NW.
C St
. N W
Ba si n St
. N W
Al de r St
. S W
1st Ave. SW.
D S t.
N
W
Al de r St
. N W
Re le as ed
YOUR ASS IS ON
FIRE. . .
CALL THE FIRE
DEPARTMENT
A
LW
A
YS
T H
IN
K
S A
FE
TY
SHEET
D
C
B
A
D
C
B
A
B U
R
EA
U O
F R
EC
LA
M
A
TI
O N
U .S
D
EP
A R
TM
EN
T
O F
TH
E
IN
TE
R
IO
R
C A D
S
YS
TE
M
A ut oC A D
4.
0S
LM
S T
EC
H
C A D
F
IL
EN
A M
E
2-
0-
8-
R D
-1 .D
W G
LA
S T
S A V
ED
D A
TE
-0 5-
LA
S T
S A V
ED
B Y
R
LE
IJ
A
C O
LU
M
B
IA
B A S
IN
P R O
JE
C T
G R A V
IT
Y D
IV
IS
IO
N
EP
H
R A
TA
F
IE
LD
O
FF
IC
E B U
IL
D
IN
G
EL
EV
A
TO
R R
EF
U
R B
IS
H M
EN
T
A N
D F
IR
E
A
LA
R M
S
YS
TE
M
R
EP
LA
C
EM
EN
T
ELEVATOR MACHINE
ROOM
EQUIPMENT REMOVAL
BOISE, ID
222-100-61248
2023-05-31
DESIGNED
DRAWN
CHECKED
TECH. APPR.
APPROVED
ADMIN APPROVAL -
David Christensen
Rey Leija
Matt Becker
Christensen, David P.E.
Hovde, Jay B
Jay Hovde
3'
6' -2
2' 4'1'0
MACHINE ROOM PLAN EL. 1326.36
1/2" = 1'
SECTION
1/2" = 1'
SECTION
1/2" = 1'
SECTION
1/2" = 1'
SECTION
1/2" = 1'
SECTION
1/2" = 1'
LEGEND
3' -9
NOTES:
1. Existing installations shown on drawings are for reference only. Some views are rotated with details removed for clarity. Not all details of existing installations are shown. Contractor shall verify compatibility of new installations with the extent of equipment removal prior to starting work.
2. Refer to Sheet Index on drawing -61247 for reference, information, and standard drawings.
Remove conduit to this point.
Remove conductors to butt splices inside panel
Remove existing elevator relays, panel and abandoned panel
Portable gantry crane shown for representation only. Use portable gantry crane or other portable methods to hoist equipment through hatch as needed
Remove luminaries
Remove existing guarding as needed to accommodate new guarding installation
Drive sheave disassembled from hoist and retained for refurbishmentRemove brake assembly
DO NOT
remove this outlet
Remove conduit and conductors as shown to the outlet box
DO NOT remove this outlet. See Section E
Remove conduit, outlets, and conductors as shown to top of elevator control panel. See Section A
Remove hoist ropes
Equipment to be removed
D
C
E
A B
Re le as
A
YS
T H
IN
K
S A
FE
TY
SHEET
D
C
B
A
D
C
B
A
B U
R
EA
U O
F R
EC
LA
M
A
TI
O N
U .S
D
EP
A R
TM
EN
T
O F
TH
E
IN
TE
R
IO
R
C A D
S
YS
TE
M
A ut oC A D
4.
0S
LM
S T
EC
H
C A D
F
IL
EN
A M
E
2-
0-
9-
R D
-1 .D
W G
LA
S T
S A V
ED
D A
TE
-0 5-
LA
S T
S A V
ED
B Y
R
LE
IJ
A
C O
LU
M
B
IA
B A S
IN
P R O
JE
C T
G R A V
IT
Y D
IV
IS
IO
N
EP
H
R A
TA
F
IE
LD
O
FF
IC
E B U
IL
D
IN
G
EL
EV
A
TO
R R
EF
U
R B
IS
H M
EN
T
A N
D F
IR
E
A
LA
R M
S
YS
TE
M
R
EP
LA
C
EM
EN
T
ELEVATOR PIT
EQUIPMENT REMOVAL
BOISE, ID
222-100-61249
2023-05-31
DESIGNED
DRAWN
CHECKED
TECH. APPR.
APPROVED
ADMIN APPROVAL -
DAVID CHRISTENSEN
REY LEIJA
MATT BECKER
Christensen, David P.E.
Hovde, Jay B
Jay Hovde
Patch conduit hole in wall
Existing phone line conductor removal to extend from terminal point in Communications Rm. No.
23 to existing terminal point in hoistway at approximately El. 1296.33
8'-4" REF
4" R
EF
25'-2" REF
LEGEND
NOTES:
1. Existing installations shown on drawings are for reference only. Some views are rotated with details removed for clarity. Not all details of existing installations are shown. Contractor shall verify compatibility of new installations with the extent of equipment removal prior to starting work.
2. Refer to Sheet Index on drawing -61247 for reference, information, and standard drawings.
Existing terminal point for telephone line approx. El. 1296.33
SECTION
1/2" = 1'
2' 4'1'0
SECTION
1/2" = 1'
PARTIAL BASEMENT PLAN EL. 1274.33
1/2" = 1'
Remove luminaire
Remove conduit, switch and conductors as shown
Conduit removal extends to point suitable to contractor above new wall penetration shown on installation drawing (-61253). Phone line conductor demolition extends to existing terminal point in hoistway approx. El. 1296.33
5"
12"
Equipment to be demolished
6'-10 1/2" Hoistway REF
A
B
Re le as
CALL THE FIRE
DEPARTMENT
A
LW
A
YS
T H
IN
K
S A
FE
TY
SHEET
D
C
B
A
D
C
B
A
B U
R
EA
U O
F R
EC
LA
M
A
TI
O N
U .S
D
EP
A R
TM
EN
T
O F
TH
E
IN
TE
R
IO
R
C A D
S
YS
TE
M
A ut oC A D
4.
0S
LM
S T
EC
H
C A D
F
IL
EN
A M
E
2-
0-
0-
R D
-1 .D
W G
LA
S T
S A V
ED
D A
TE
-0 5-
LA
S T
S A V
ED
B Y
R
LE
IJ
A
C O
LU
M
B
IA
B A S
IN
P R O
JE
C T
G R A V
IT
Y D
IV
IS
IO
N
EP
H
R A
TA
F
IE
LD
O
FF
IC
E B U
IL
D
IN
G
EL
EV
A
TO
R R
EF
U
R B
IS
H M
EN
T
A N
D F
IR
E
A
LA
R M
S
YS
TE
M
R
EP
LA
C
EM
EN
T
ELEVATOR MACHINE
ROOM
ELECTRICAL AND HVAC
INDOOR INSTALLATION
BOISE, ID
222-100-61250
2023-05-31
DESIGNED
DRAWN
CHECKED
TECH. APPR.
APPROVED
ADMIN APPROVAL -
DAVID CHRISTENSEN
REY LEIJA
MATT BECKER
Christensen, David P.E.
Hovde, Jay B
Jay Hovde
20'-0" REF
7' -1
1/
2" R
EF
6" M ax
NOTES:
1. Existing installations shown on drawings are for reference only. Some views are rotated with details removed for clarity. Not all details of existing installations are shown. Contractor shall verify compatibility of new installations with existing installations prior to starting work.
2. Route conduit and conductor paths as shown.
3. Refer to Sheet Index on drawing -61247 for reference, information, and standard drawings.
7'2" REF
37"
REF
R
EF
MACHINE ROOM PLAN EL. 1326.37
1/2" = 1'
SECTION
1/2" = 1'
2' 4'1'0
SECTION
1/2" = 1'
SECTION
1/2" = 1'
SECTION
1/2" = 1'
2'-2" REF
Existing exhaust fan
Existing storage cabinet
New conduit and conductors for HVAC.
See Note 2
Route conduit through existing hole in floor when possible
Use spare breaker slot in this existing panel for new 208VAC supply for
HVAC
New conduit and conductors. See Note 2
Existing GFCI outlet
Zone for refrigeration line set and conduit penetration
New conduit and conductors for HVAC.
See Note 2
Locate new indoor unit of ductless heat pump in area shown
New conduit and conductors for HVAC.
See Note 2
New 4-gang outlet
Existing outlet
Drill location area for new 208VAC supply for HVAC
Existing outlet
New panels and elevator fire service relays
New conduit and conductors.
See Note 2
Existing GFCI outlet
New 4-gang outlet
New conduit and conductors.
See Note 2
Route for refrigeration line set and conduit in close proximity to minimize width of exterior custom flashing
Existing disconnect
A
B
DC
Re le as
A
YS
T H
IN
K
S A
FE
TY
SHEET
D
C
B
A
D
C
B
A
B U
R
EA
U O
F R
EC
LA
M
A
TI
O N
U .S
D
EP
A R
TM
EN
T
O F
TH
E
IN
TE
R
IO
R
C A D
S
YS
TE
M
A ut oC A D
4.
0S
LM
S T
EC
H
C A D
F
IL
EN
A M
E
2-
0-
1-
R D
-1 .D
W G
LA
S T
S A V
ED
D A
TE
-0 5-
LA
S T
S A V
ED
B Y
R
LE
IJ
A
C O
LU
M
B
IA
B A S
IN
P R O
JE
C T
G R A V
IT
Y D
IV
IS
IO
N
EP
H
R A
TA
F
IE
LD
O
FF
IC
E B U
IL
D
IN
G
EL
EV
A
TO
R R
EF
U
R B
IS
H M
EN
T
A N
D F
IR
E
A
LA
R M
S
YS
TE
M
R
EP
LA
C
EM
EN
T
ELEVATOR MACHINE
ROOM
HVAC OUTDOOR
INSTALLATION
BOISE, ID
222-100-61251
2023-05-31
NOTES:
1. Installation of HVAC outdoor unit shall be done in a manner shown to minimize visual disturbance to the exterior of the building, maximize serviceability of the unit and roof, and maximize unit operation during snow accumulation on the roof.
2. Locate and drill holes for refrigeration line set starting inside Machine Room and as close as possible to Machine Room floor as shown. Contractor shall take care to drill pilot thru-hole and core drill both sides of brick wall to minimize damage to brick. Penetration zone shall be limited to area between door and down spout as shown.
3. Route refrigeration line set conduit together to minimize required width of custom flashing for aesthetics.
4. Furnish and install custom flashing for aesthetics. Flashing color shall match color of water down spout. Flashing shall be sized minimum width to cover refrigeration line set, conductors and conduit. Flashing cap at top shall be angled to prevent standing water.
Flashing shall extend at a minimum to top of the outdoor unit.
5. Furnish and install commercially available mounting brackets designed for HVAC outdoor units and L-style configured to allow base of unit within closest proximity to roof as shown.
Mounting brackets shall mount to the wall and shall not rest on the roof.
6. Refer to Sheet Index on drawing -61247 for reference, information, and standard drawings.
Surrounding Roof El. 1319.12
R
EF
3" Wall mounting brackets.
See Note 5. Line set and electrical not shown for clarity
6" maximum above floor. See Note 2
Ex te ri or
A pp ro x.
7"
-1
R
EF
O N
LY
S ee
N ot e
See Note 4
Existing rainwater down spout. See Note 4
See Note 4
6" maximum above floor.
See Note 2
Custom flashing.
See Note 4
Electrical disconnect
Top of roof membrane flashing
7'-2" REF
Line set, conductors, and conduit may be routed and hidden behind unit if space permits, otherwise protected with flashing across top of units as shown
R
EFHVAC
outdoor unit
Zone for refrigeration line set and conduit penetration
Existing door
7'10" REF2'-2" REF
2'-2" REF 2'-2" REF
Line set, conductors, and conduit shall not extend below the bottom of unitB
SECTION
1/2" = 1'
SECTION
1/2" = 1'
2' 4'1'0
FLOOR PLAN EL. 1318.79
1/2" = 1'
LEFT-PORT OPTION PREFERRED
1/2" = 1'
RIGHT-PORT OPTION ALTERNATIVE
1/2" = 1'
8" REF
2'2" REF
WALL PENETRATION
ZONE
DESIGNED
DRAWN
CHECKED
TECH. APPR.
APPROVED
ADMIN APPROVAL -
David Christensen
Rey Leija
Jeff McGuire
Christensen, David P.E.
Hovde, Jay B
Jay Hovde
HVAC
outdoor unit
Existing rainwater down spout. See Note 4
Zone for refrigeration line set and conduit penetration
Condensate line
Condensate line
A
Re le as
CALL THE FIRE
DEPARTMENT
PL 1/4" x 4" toe guard, typ. two stationary sides
Remove existing metal posts and safety chains as shown
2' 4'1'02' 4'1'0
2' 4'1'0
MACHINE ROOM PLAN EL. 1326.36
1/2" = 1'
SECTION
1/2" = 1'
SECTION
1/2" = 1'
DESIGNED
DRAWN
CHECKED
TECH. APPR.
APPROVED
ADMIN APPROVAL -
David Christensen
Rey Leija
Jeff McGuire
Christensen, David P.E.
Hovde, Jay B
Jay Hovde
1' 2' 3'0
SECTION
3/4" = 1'
1' 2' 3'0
SECTION
3/4" = 1'
1/4" Max.
gap, typ.
See Note 2
Ty p.
Ty p.
1 1/2" Sch 40 pipe, typ.
Ty p.
NOTES:
1. Contractor shall verify dimensions, incorporate design features as shown, and finalize design details in shop drawings.
2. Design shall have a welded vertical support sleeve on guardrail pipe post that locates over cast-in-place pipe extension left from partial removal of existing guardrail as shown.
3. Adhesive anchors shall be "Ø minimum threaded rod with 6¼" minimum effective embedment with adhesive. Installation and physical embedment depth to be per adhesive manufacturer's recommendations to provide noted minimum effective embedment depth.
4. Refer to Sheet Index on drawing -61247 for reference, information, and standard drawings.
1/2" Max.
clearance for gate
Swing gate
PL 1/4" x 4" toe guard for gate
1' 2' 3'0
SECTION
3/4" = 1'
C
1/2' 1' 1 1/2'0
DETAIL SECTION
1 1/2" = 1'
Swing gate hinge with automatic closing spring mechanism
DESIGN DETAIL 1
6" = 1'
Steel sleeve.
See Note 2
Locate tangent to vertical support as shown
Steel sleeve.
See Note 2
Butt toe plate into mating plate as shown
Remove existing metal posts and safety chains as shown
ATTENTION
See Note 2
Vertical pipe support. See Note 2
Partially remove guardrail. See Section A.
See Note 2
DESIGN DETAIL 2
6" = 1'
LEGEND
Equipment to be removed
Remove existing gates as shown
Adhesive wall anchors, typ.
See Note 3
Swing gate hinge with automatic spring closing mechanism
Steel angle 1 1/2" x 1 1/2" as needed for mounting hinge to pipe
DESIGN DETAIL 3
6" = 1'
6" C as t-in -p la ce pi pe e xt en si on
3" m in sl ee ve d ve rt ic al su pp or t
Remove existing metal post and safety chains as shown. Partially remove existing guardrail leaving the cast-in-place extensions as shown
Secure handrail sleeve over existing cast-in-place pipe stub with 5/8"Ø minimum hex head cap screws as shown
Steel sleeve.
See Note 2
1" 3"0 2" 4"
F
Locate 3 anchors at 16" min. O.C.
See Note 3
Angle 4" x 4" x 1/4" for wall mounted vertical supports
Locate 3 anchors at 16" min. O.C.
See Note 3
Angle 4" x 4" x 1/4" for wall mounted vertical support
Gate swing direction
8" R
EF
1 1/2" Sch 40 pipe for gate
Locate 1/4" thick contact plate welded to wall angle to match contact geometry of toe plate below
6" R em ai ni ng ca st
-i n-pl ac e pi pe ex te ns io n
Secure handrail to wall mounted angle with hardware as shown
A
LW
A
YS
T H
IN
K
S A
FE
TY
SHEET
D
C
B
A
D
C
B
A
B U
R
EA
U O
F R
EC
LA
M
A
TI
O N
U .S
D
EP
A R
TM
EN
T
O F
TH
E
IN
TE
R
IO
R
C A D
S
YS
TE
M
A ut oC A D
4.
0S
LM
S T
EC
H
C A D
F
IL
EN
A M
E
2-
0-
2-
R D
-1 .D
W G
LA
S T
S A V
ED
D A
TE
-0 5-
LA
S T
S A V
ED
B Y
R
LE
IJ
A
C O
LU
M
B
IA
B A S
IN
P R O
JE
C T
G R A V
IT
Y D
IV
IS
IO
N
EP
H
R A
TA
F
IE
LD
O
FF
IC
E B U
IL
D
IN
G
EL
EV
A
TO
R R
EF
U
R B
IS
H M
EN
T
A N
D F
IR
E
A
LA
R M
S
YS
TE
M
R
EP
LA
C
EM
EN
T
ELEVATOR MACHINE
ROOM AND ACCESS
GUARDRAIL
EQUIPMENT REMOVAL
AND INSTALLATION
BOISE, ID
222-100-61252
2023-05-31
PL 3" x 1/4" for mounting railing to angle with hardware in 6 clamping locations as shown
Angle 4" x 4" x 1/4" for wall mounted vertical supports
B
A
D
E
Re le as
New conduit and conductors
Existing conduit
Existing terminal point for telephone line. See Note 2.
Approx. El. 1296.33
Existing junction box. See Note 3
Approx. El. 1296.33
Existing terminal point. See Partial Basement Plan
4" R
EF
10'-4" REF
8' -3
/2
R
EF
14'-10" REF
New telephone line conduit and conductors
See Note 3
6' -0
R
EF
14"
Existing 3" conduit to elevator Machine Room
12" REF
14"
REF
After penetration, connect new conduit to existing conduit mounted in corner. See Note 3
Plug hole
2"
REF
7" REF
R
EF
12" REF
New light switch
New telephone line conduit and conductors
Route overhead and utilize existing mechanical chase above door for conduit
PARTIAL BASEMENT PLAN EL. 1274.33
1/2" = 1'
SECTION
1/2" = 1'
2' 4'1'0
SECTION
1/2" = 1'
NOTES:
1. Existing installations shown on drawings are for reference only. Not all details of existing installations are shown. Contractor shall verify compatibility of new installations with existing installations prior to starting work.
2. Route new phone line conductors as shown from terminal point in Communication Room No.
23 to existing hoistway terminal point at approximate El. 1296.33.
3. Route conduit for phone line as shown from existing junction box in Janitor Room No. 20 to existing conduit in hoistway as shown in Section B.
4. Refer to Sheet Index on drawing -61247 for reference, information, and standard drawings.
New luminaire (-61255)
4" R
EF
Existing electrical equipment
Existing electrical equipment
DESIGNED
DRAWN
CHECKED
TECH. APPR.
APPROVED
ADMIN APPROVAL -
DAVID CHRISTENSEN
REY LEIJA
MATT BECKER
Christensen, David P.E.
Hovde, Jay B
Jay Hovde
A
LW
A
YS
T H
IN
K
S A
FE
TY
SHEET
D
C
B
A
D
C
B
A
B U
R
EA
U O
F R
EC
LA
M
A
TI
O N
U .S
D
EP
A R
TM
EN
T
O F
TH
E
IN
TE
R
IO
R
C A D
S
YS
TE
M
A ut oC A D
4.
0S
LM
S T
EC
H
C A D
F
IL
EN
A M
E
2-
0-
3-
R D
-1 .D
W G
LA
S T
S A V
ED
D A
TE
-0 5-
LA
S T
S A V
ED
B Y
R
LE
IJ
A
C O
LU
M
B
IA
B A S
IN
P R O
JE
C T
G R A V
IT
Y D
IV
IS
IO
N
EP
H
R A
TA
F
IE
LD
O
FF
IC
E B U
IL
D
IN
G
EL
EV
A
TO
R R
EF
U
R B
IS
H M
EN
T
A N
D F
IR
E
A
LA
R M
S
YS
TE
M
R
EP
LA
C
EM
EN
T
ELEVATOR PIT
ELECTRICAL
INSTALLATION
BOISE, ID
222-100-61253
2023-05-31
See Note 2
B
A C
D
Re le as
El. 1267.66
El. 1274.33
El. 1285.33
New telephone line conduit and conductors
New conduit and conductors to new light switch
New light switch
Existing conduit
New conduit and conductors from existing junction box to new light switch as shown
Connection point of new conduit to existing conduit
3' -1
0"
Existing conduit
A
LW
A
YS
T H
IN
K
S A
FE
TY
SHEET
D
C
B
A
D
C
B
A
B U
R
EA
U O
F R
EC
LA
M
A
TI
O N
U .S
D
EP
A R
TM
EN
T
O F
TH
E
IN
TE
R
IO
R
C A D
S
YS
TE
M
A ut oC A D
4.
0S
LM
S T
EC
H
C A D
F
IL
EN
A M
E
2-
0-
4-
R D
-1 .D
W G
LA
S T
S A V
ED
D A
TE
-0 5-
LA
S T
S A V
ED
B Y
R
LE
IJ
A
C O
LU
M
B
IA
B A S
IN
P R O
JE
C T
G R A V
IT
Y D
IV
IS
IO
N
EP
H
R A
TA
F
IE
LD
O
FF
IC
E B U
IL
D
IN
G
EL
EV
A
TO
R R
EF
U
R B
IS
H M
EN
T
A N
D F
IR
E
A
LA
R M
S
YS
TE
M
R
EP
LA
C
EM
EN
T
ELEVATOR PIT
ELECTRICAL
INSTALLATION
SECTIONS A AND C
BOISE, ID
222-100-61254
2023-05-31
DESIGNED
DRAWN
CHECKED
TECH. APPR.
APPROVED
ADMIN APPROVAL -
DAVID CHRISTENSEN
REY LEIJA
MATT BECKER
Christensen, David P.E.
Hovde, Jay B
Jay Hovde
Existing outlet
Existing junction box for lighting
Existing conduit
Existing telephone line terminal point
SECTION
-61253
A 1/2" = 1'
2' 4'1'0
SECTION
-61253
C 1/2" = 1'
4" R
EF
New luminaire (-61255)
Existing electrical gutter
Existing conduit
NOTES:
1. Refer to Sheet Index on drawing -61247 for reference, information, and standard drawings.
Re le as
SL1 SL1 SL1
SL1
SL2 SL2
SL2 SL2
A
LW
A
YS
T H
IN
K
S A
FE
TY
SHEET
D
C
B
A
D
C
B
A
B U
R
EA
U O
F R
EC
LA
M
A
TI
O N
U .S
D
EP
A R
TM
EN
T
O F
TH
E
IN
TE
R
IO
R
C A D
S
YS
TE
M
A ut oC A D
4.
0S
LM
S T
EC
H
C A D
F
IL
EN
A M
E
2-
0-
5-
R D
-1 .D
W G
LA
S T
S A V
ED
D A
TE
-0 5-
LA
S T
S A V
ED
B Y
R
LE
IJ
A
C O
LU
M
B
IA
B A S
IN
P R O
JE
C T
G R A V
IT
Y D
IV
IS
IO
N
EP
H
R A
TA
F
IE
LD
O
FF
IC
E B U
IL
D
IN
G
EL
EV
A
TO
R R
EF
U
R B
IS
H M
EN
T
A N
D F
IR
E
A
LA
R M
S
YS
TE
M
R
EP
LA
C
EM
EN
T
MACHINE ROOM AND
ELEVATOR PIT
LIGHTING INSTALLATION
BOISE, ID
222-100-61255
2023-05-31
DESIGNED
DRAWN
CHECKED
TECH. APPR.
APPROVED
ADMIN APPROVAL -
DARIM YI
REY LEIJA
WESLEY JOHNSON
Christensen, David P.E.
Hovde, Jay B
Jay Hovde
Locate and mount SL1 fixtures so the bottom of fixture is 7.5' AFF as shown, typ.
LEIJA
SECTION
3/4" = 1'
MACHINE ROOM FLOOR PLAN EL. 1326.37
1/2" = 1'
1' 2' 3'0
2' 4'1'0
ELEVATOR PIT PLAN EL. 1267.66
3/4" = 1' 1' 2' 3'0
SECTION
3/4" = 1' 1' 2' 3'0
N:\CAD\Yakima\EFO\EFO Elevator 2022\CAD\Lighting\222-100-Lighting-03-15.dwg
7.
5'
Locate and mount SL1 fixtures so the bottom of fixture is 7.5' AFF as shown, typ.
ABBREVIATION
AFF . . . . . . Above Finished Floor
GENERAL NOTES:
1. Provide and install LED fixtures SL1 and SL2 as shown.
Provide adequate structural support and mounting hardware to install fixtures according to manufacturer's recommendations.
2. Contractor shall furnish, design, install all necessary hardware and supports for complete lighting installation.
3. Contractor shall determine conduit routes and home run to the lighting panelboard. Install additional pull points as required per the requirements of the NEC.
4. Contractor shall verify and install all equipment, field wiring, conduit, cabling, and between fixtures per NEC, NESC, ANSI, and manufacturer's requirements.
5. Coordinate locations and mounting heights of lighting fixtures in machine room and elevator pit with final locations of pipes, ducts and other equipment for the best arrangement. Fixtures shall be easily accessible for relamping. Pendant lengths indicated are estimates and the actual pendant length required shall be determined/provided based on field coordination with installed equipment.
6. The equipment placement and dimensions on this drawing are diagrammatical and are for reference only.
Contractor shall field verify placement of equipment and make adjustments as necessary.
7. Coordinate all electrical work with structural and mechanical requirement.
8. Contractor shall install all equipment per NEC, NESC, ANSI and manufacturer's requirement.
9. All electrical work shall be performed in a neat workmanship manner as defined by the National Electrical Contractors Association (NECA), and shall be in accordance with specifications, NEC and NESC.
10. Refer to drawing -61256 for lighting details.
11. Refer to Sheet Index on drawing -61247 for reference, information, and standard drawings.
1.
5'
1.
5'
Locate and mount SL2 fixtures so the bottom of fixture is 1.5' AFF as shown, typ.
Locate and mount SL2 fixtures so the bottom of fixture is 1.5' AFF as shown, typ.
B
A
Re le as
A
YS
T H
IN
K
S A
FE
TY
SHEET
D
C
B
A
D
C
B
A
B U
R
EA
U O
F R
EC
LA
M
A
TI
O N
U .S
D
EP
A R
TM
EN
T
O F
TH
E
IN
TE
R
IO
R
C A D
S
YS
TE
M
A ut oC A D
4.
0S
LM
S T
EC
H
C A D
F
IL
EN
A M
E
2-
0-
6-
R D
-1 .D
W G
LA
S T
S A V
ED
D A
TE
-0 5-
LA
S T
S A V
ED
B Y
R
LE
IJ
A
C O
LU
M
B
IA
B A S
IN
P R O
JE
C T
G R A V
IT
Y D
IV
IS
IO
N
EP
H
R A
TA
F
IE
LD
O
FF
IC
E B U
IL
D
IN
G
EL
EV
A
TO
R R
EF
U
R B
IS
H M
EN
T
A N
D F
IR
E
A
LA
R M
S
YS
TE
M
R
EP
LA
C
EM
EN
T
ELECTRICAL DETAILS
LIGHTING
BOISE, ID
222-100-61256
2023-05-31
DESIGNED
DRAWN
CHECKED
TECH. APPR.
APPROVED
ADMIN APPROVAL -
DARIM YI
REY LEIJA
WESLEY JOHNSON
Christensen, David P.E.
Hovde, Jay B
Jay Hovde
NOTES:
LAMP TYPE: LED, 4200 LUMENS, 5000K
ELECTRIC: MVOLT (120-277VAC), 60HZ, 1PH
HOUSING: FULLY CASKETED, POLYCARBONATE HOUSING
CRI: 80 CRI
NOM SIZE: 50.3" L x 5.4 W x 3.8" H
UL: LISTED FOR WET LOCATION
IP65, IP66 RATED
DRIVER: ELECTRONIC
MOUNTING: SURFACE MOUNTING
LIGHTING FIXTURE SCHEDULE
SYMBOL LAMP INFORMATION NO. TOTAL WATTS [ W ] LUMENS PER LAMP VOLTS MOUNTING/REMARKS
SL1 LED (5000K) 3 34 4200 MVOLT (120-277 VAC) SURFACE MOUNT/PENDANT
SL2 LED (5000K) 2 20 3000 MVOLT (120-277 VAC) SURFACE MOUNT
NOTES:
LAMP TYPE: LED, 3000 LUMENS, 5000K
ELECTRIC: MVOLT (120-277 VAC), 60HZ, 1PH
HOUSING: FULLY CASKETED, POLYCARBONATE, NEMA 4X RATED LENS AND HOUSING
CRI: 80 CRI
NOM SIZE: 27 3/4" L x 6.8" W x 4.2" H
UL: LISTED FOR WET LOCATION.
IP65, IP66 AND IP67 RATED.
DRIVER: ELECTRONIC
MOUNTING: SURFACE/WALL MOUNTING
GENERAL NOTES:
1. Components which constitute an electrical system shall be fully compatible with one another and shall be approved by the various manufacturers for use with all the other components within the system.
(One example of an electrical system is the building lighting system comprised of fixtures, lamps, switches, ballasts, lighting controller and other equipment).
2. All electrical work shall be performed in a neat workmanship manner as defined by the National Electrical Contractors Association (NECA).
3. Details shown are typical. Details may be modified to suit field conditions and recommendations by manufacturer installation. Refer to specifications for details.
4. Refer to Sheet Index on drawing -61247 for reference, information, and standard drawings.
N:\CAD\Yakima\EFO\EFO Elevator 2022\CAD\222-100-61256.dwg
SL1 FIXTURE
NOT TO SCALE
SL2 FIXTURE
NOT TO SCALE
Re le as
FOR INFORMATION ONLY
scarlson Line scarlson Line scarlson Text Box For Information Only scarlson Line scarlson Text Box For Information Only
Line
Line scarlson Text Box For Information Only scarlson Line scarlson Text Box For Information Only
Line scarlson Text Box For Information Only
Line scarlson Text Box For Information Only
Line scarlson Text Box For Information Only
Line scarlson Text Box For Information Only
Line scarlson Text Box For Information Only
Line scarlson Text Box For Information Only
Line scarlson Text Box For Information Only
Line scarlson Text Box For Information Only
Line scarlson Text Box For Information Only
Line scarlson Text Box For Information Only
File details come from the government source that posted it. Updated .