Section_2651_-_Television_Inspection.pdf
PDF 123 KB Posted
- Solicitation number
- PD 25-26.099
- Issued by
- Escambia County, Florida
About this file
This is an engineering manual section providing specifications and standards for closed-circuit television (CCTV) inspection services of sewer systems, issued by Escambia County Utilities Authority (ECUA) for the CDBG-DR Oakfield-Palafox Stormwater Upgrades project in Escambia County, Florida. The document outlines comprehensive requirements for television inspection of existing, new, and rehabilitated piping, including sewer mains and lateral connections, with inspections to be performed by National Association of Sewer Service Companies (NASSCO) Pipeline Assessment Certification Program (PACP) certified operators. All work must comply with PACP v7.0 standards and coding guidelines, and contractors must submit documentation of CCTV equipment specifications, PACP-certified software compatibility with IT Pipes software and ECUA's CCTV storage system, and current operator certifications prior to work commencement. The inspection process requires color video recording with minimum 470 lines of vertical resolution, pan-and-tilt camera capabilities, footage counters accurate to two-tenths of a foot, proper lighting systems, and digital recording delivery in MPEG format on USB 3.0 external flash drives viewable on standard computer media players at real-time and fast-forward speeds.
Execution requirements mandate that contractors clean sewer lines and laterals prior to inspection, notify the Engineer 48 hours in advance of television inspection operations, perform inspections from center-to-center of upstream and downstream manholes, maintain camera speeds not exceeding 30 feet per minute, stop at every joint for three seconds and at all lateral connections for thorough documentation, and control wastewater flow to specified depths during filming based on pipe diameter (10 percent for 6-10 inch pipes, 15 percent for 12-24 inch pipes, and 20 percent for over 24-inch pipes). Deliverables include written inspection reports with PACP defect codes and color still shot images of all defects, electronic reports in NASSCO PACP v7.0 certified ".mdb" database format, and digital inspection recordings organized by project with labeled hard drives containing file number, contractor name, project name, contract number, drawing number, inspection type, date televised, and pipe segment asset identification. Contractors are responsible for all equipment damage, facility damage, and restoration costs resulting from equipment malfunction, flow control failures, or camera retrieval operations, and must maintain master copies of all recordings and reports for two years following delivery.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Engineering Manual
2025 Edition Section 2651 – Television Inspection Page 1 of 6
Section 2651
Television Inspection
PART 1: General
1.1 Description – Provide all labor, materials, tools, equipment and incidentals as shown, specified, and required to perform closed-circuit television (CCTV) inspection of existing, new and rehabilitated piping including sewer mains and sewer lateral connections.
1.2 Definitions –
1.2.1 Pre-Construction Inspection – CCTV inspection of sewers and/or laterals to determine the location of construction, structural and O&M features and to ascertain that the condition of the pipe meets acceptable standards for the proposed rehabilitation.
1.2.2 Post-Construction Inspection – CCTV inspection of repaired or rehabilitated sewer mains, lateral connections, and laterals to verify (in association with other specified testing procedures) that all repairs have been performed.
1.3 Requirements – The Contractor shall be aware that this Contract requires work in active sewers and shall follow all federal, state and local requirements for safety in confined spaces.
1.4 Performance Requirements –
1.4.1 Inspection shall be performed by a National Association of Sewer Service Companies (NASSCO) Pipeline Assessment Certification Program (PACP) certified operator and shall meet the coding and reporting standards and guidelines as set by PACP. These same standards shall also be used for lateral inspections regardless of whether conducted using cleanout-launched or mainline-launched lateral camera. All report annotations, pipe conditions and pipe defects shall be identified properly using PACP codes as defined by PACP, and severity ratings shall be calculated according to PACP.
1.4.2 Quality of inspection recording shall be acceptable to ENGINEER when viewed on a standard computer monitor.
1.5 Submittals –
1.5.1 CCTV equipment, including make, model, age of video systems and tractors. , and documentation that CCTV software is PACP v7.0 -certified. PACP-compliant software will not be accepted.
1.5.2 Documentation of NASSCO PACP (version 7.0) certified Software and Access Database.
Database shall be compatible with IT Pipes software and ECUA’s CCTV storage and viewing system.
1.5.3 Documentation of NASSCO PACP current certification for all CCTV operators.
1.6 Reference Standards – Current NASSCO PACP standards.
2025 Edition Section 2651 – Television Inspection Page 2 of 6
PART 2: Products
2.1 Television Equipment –
2.1.1 Closed Circuit TV Equipment – Select and use closed-circuit television equipment that will produce a color recording. The camera and video system components shall have the following properties:
2.1.1.1 Equipped with footage counter accurate to two tenths of a foot that displays on the TV monitor the exact distance of the camera from the starting point of the recording.
2.1.1.2 Lighting system that allows the features and condition of the pipe to be clearly seen. Lighting shall not cause shadows or loss of color within the field of view of the camera.
2.1.1.3 Capable of operating in 100 percent humidity conditions.
2.1.1.4 Capable of producing a minimum 470 lines of vertical resolution color video picture. Picture quality and definition shall be to the satisfaction of the Engineer.
2.1.2 Pipe Inspection Camera – The pipe inspection camera and video components shall have the following additional properties:
2.1.2.1 Capable of producing a video recording using a pan-and-tilt, radial viewing, pipe inspection camera that pans ± 275 degrees and rotates 360 degrees.
2.1.2.2 Camera height adjustment so that the camera lens is always centered at one-half the inside diameter, or higher, in the pipe being televised.
2.1.2.3 Include a reflector in front of the camera if necessary to provide acceptable video image quality in large diameter pipe.
2.1.3 TV Studio – TV studio is to be contained in an enclosed truck, trailer or van. It shall have room and seating for the operator and the ENGINEER and also room for at least one standing visitor with the doors closed. The studio shall have air conditioning and heating.
Normal operation of all equipment, including the TV camera, monitor, and winches is to be from a control panel in the studio. When joint testing and sealing is to be performed, the equipment shall be contained in the same unit as its TV equipment and shall be operated from the same control panel.
2.1.4 Recording – All recordings are to be in digital format.
2.1.4.1 Image Capture – Digitized picture images shall be stored and be exportable as JPEG formats.
2025 Edition Section 2651 – Television Inspection Page 3 of 6
2.1.4.2 Video Capture – Full time live video and audio files shall be captured for each pipe segment and lateral inspected. The files shall be delivered in MPEG format on a USB 3.0 external flash drive (or better as approved by ECUA) and viewable at real time and fast forward speeds on an external personal computer that utilizes MicroSoft Media Player, current version. Alternate digital formats will not be accepted unless approved by the Engineer in advance of submittal. The video shall have a minimum resolution of 640 pixels (x) by 480 pixels (y) and an encoded frame rate of 29.97 frames per second. System shall perform an automatic disk image/file naming structure to allow saved video/data sections to be “Burned” to digital format. The video recording shall be free of electrical interference and shall produce a clear and stable image. The audio recording shall be sufficiently free of background and electrical noise as to produce an oral report that is clear and discernable. The digital recordings and inspection data shall be cross-referenced to allow instant access to any point of interest within the digital recording.
PART 3: Execution
3.1 Television Inspection –
3.1.1 Prior to TV inspection, clean sewer lines, laterals and manholes. Re-clean any sewer line or manhole found to be dirty during the TV inspection process.
3.1.2 Televise the sewer line to document the condition of the line. Notify the Engineer 48 hours in advance of any TV inspection so that the ENGINEER may observe inspection operations. Provide a color recording showing the completed Work.
3.1.3 For mainline sewer inspections, inspections shall be from center of the starting manhole to the center of the ending manhole. Record the condition of the entire circumference of the pipe penetration. Measure distances along the pipe from the center of the upstream manhole.
3.1.4 Prior to recording the location of defects, construction features and service connections, remove slack in the cable of the television inspection camera to ensure metering device is designating proper footage. Check accuracy of the measurement meters daily by use of a walking meter, roll-a-tape, or other suitable device.
3.1.5 Perform the preset before starting to record the inspection (i.e. the counter should not suddenly reset or jump during the recording). If a preset point on the CCTV cable is used to set the counter, Contractor shall back up the camera after setting the preset and record the entry to the pipe.
3.1.6 Center the camera in the middle of the pipe.
3.1.7 The speed of travel shall be slow enough to inspect each pipe joint, tee connection, structural deterioration, infiltration and inflow sources, and deposits, but should not, at any time, be faster than 30 feet per minute.
3.1.8 Stop at every joint for three seconds. When infiltration or other defects are evident, use pan and tilt to document pipe condition. Stop elsewhere when necessary to ensure proper documentation of the sewer’s condition.
2025 Edition Section 2651 – Television Inspection Page 4 of 6
3.1.9 Stop at every lateral connection. Center the camera so that the lighting and the pan and tilt view can be used to inspect as far into the lateral connection as possible. Pan the circumference of the tap, recording all defects found in the service connection. Where lateral flow is observed, observe flows from service connections for a sufficient amount of time to ascertain if the flow is sanitary or extraneous flow. The video recording may be paused during observation. Record results of the flow observed on video recording and inspection logs.
3.1.10 Capture color still shots of video recordings for all defects encountered.
3.1.11 Use manual winches, power winches, TV cable, and powered rewinds or other devices that do not obstruct the camera view or interfere with proper documentation of the sewer conditions to move the camera through the sewer line.
3.1.12 TV inspection recordings shall be continuous for each pipe segment.
3.1.13 Adjust light levels, clean fouled or fogged lens, and allow vapor to dissipate from camera lights in order to produce acceptable recordings. All TV inspection recordings that do not meet the specified requirements shall be re-televised at no additional cost to the Owner.
3.1.14 CCTV inspection is part of the acceptance test of a new sewer main or repair.
3.1.14.1 The sewer mains and laterals shall be flooded prior to the CCTV work to determine the sag (belly) existence and severity.
3.2 Flow Control –
3.2.1 Adequately control the flow in the section being televised. Plugging or bypassing of the flows may be used to accomplish this. Recordings made where the depths of wastewater flow shown below are exceeded will be rejected:
Flow Control During Television Inspection
Pipe Diameter (Inches) Depth of Flow (% of Pipe Diameter)
6-10 10
12-24 15
Over 24 20
3.2.2 Whenever flows in a sewer line are blocked, plugged, pumped, or bypassed, take sufficient precautions to protect the sewer lines from damage that might be inflicted by excess sewer surcharging. Further, take precautions to ensure that sewer flow control operations do not cause flooding or damage to public or private property being served by the sewers involved. No overflows are permitted. The Contractor is responsible for all damages.
3.2.3 Contractor is responsible for all damages to Contractor owned and operated equipment, Owner facilities, and privately-owned facilities caused by malfunction of plugs, pumps or other Contractor equipment. In the event of a failure or malfunction of Contractor equipment, Contractor is responsible for all work necessary to restore facilities to pre-construction condition including but not limited to excavation and restoration of sewer lines and roadways required to retrieve malfunctioning or stuck cameras, plugs and hoses.
2025 Edition Section 2651 – Television Inspection Page 5 of 6
3.2.4 It is anticipated that portions of the sanitary sewer are bowed or bellied and as a result the camera will be submerged. Wherever the camera encounters a submerged condition, or where the wastewater flow depth exceeds the maximum allowable, reduce the flow depth to an acceptable level by performing the survey TV inspection during minimum flow hours, or by pulling a camera with swab, high-velocity jet nozzle or other acceptable dewatering device. Recordings made while floating the camera are not acceptable unless approved by Engineer.
3.3 Passage of TV Camera – If during TV inspection of a pipe segment the camera is unable to pass an obstruction even though flow is unobstructed, televise the pipe segment from the opposite direction in order to obtain a complete recording of the line. Measure the distance between the manholes (centerline to centerline) with a tape or wheel to accurately determine the total length of the manhole segment.
3.4 Inspection Deliverables –
3.4.1 Written Inspection Reports – Provide printed location records to clearly identify the location of each defect, or lateral connection, in relation to adjacent manholes, using a standard stationing system zeroed on the upstream manhole. Record all information requested using proper NASSCO PACP defect codes. The reports shall include at least the minimum amount of information required by PACP, including required PACP header information. Color still shot images of all defects encountered shall be included with each pipe segment.
3.4.2 Electronic Inspection Reports –
3.4.2.1 Provide a NASSCO PACP v7.0 certified database listing all PACP required data fields for each pipe segment. The provided database shall be in “.mdb” format with no password protection on the file and shall be non-proprietary with regard to software manufacturer.
3.4.2.2 For each type of CCTV deliverable (Pre-Construction, Post-Construction, Warranty), provide a single database containing all the inspections for the Project.
3.4.2.3 Post Construction deliverables will contain a single inspection for each asset, inspected upon completion of all non-warranty Work on the asset.
3.4.2.3.1 Submit two inspection records for a single asset only if the asset cannot be completely inspected from one side due to the physical condition of the pipe. Properly use the PACP “MSA” coding for each such inspection record.
3.4.3 Inspection Recordings –
3.4.3.1 Provide digital inspection recordings for all recordings, unless otherwise specified in paragraph 3.4.4.
3.4.3.2 Recording shall be of a quality sufficient for Engineer to evaluate the condition of the sewer, locate the sewer service connections, and verify cleaning. If Engineer determines that the quality is not sufficient, re-televise the sewer segment and provide a new recording and report at no additional compensation. Camera distortions, inadequate lighting, dirty lens, or blurred/hazy picture will be cause for
2025 Edition Section 2651 – Television Inspection Page 6 of 6 rejection. Payment for televised inspection will not be made until Engineer approves the recordings and reports.
3.4.3.3 Only pipe segments from the same Project shall be included on a given hard drive.
Multiple deliverable types may be included on a given hard drive, but the files must be organized in individual project folders. TV Inspection recordings shall not be edited.
3.4.3.4 Digital recordings: Each pipe segment must be its own electronic file. Electronic recording file must allow snap scrolling to allow easy and quick access of the entire recording.
3.4.3.5 Each hard drive must have a file index whose name contains the pipe segment reference number.
3.4.3.6 Maintain a master copy of all recordings and Inspection Reports for two years after delivery of reports and recordings.
3.4.3.7 Label each hard drive with the following information:
3.4.3.7.1 File Number
3.4.3.7.2 Contractor’s Name
3.4.3.7.3 Project Name
3.4.3.7.4 Contract Number
3.4.3.7.5 Drawing Number
3.4.3.7.6 Inspection Type: Post Cleaning, Repair
3.4.3.7.7 Date Televised
3.4.3.7.8 Pipe Segment Asset Identification Number
3.4.4 Inspection – Inspection deliverables for different types of inspections are defined below:
3.4.4.1 Pre-Construction Inspection – One copy on a 5 Gbit/sec (minimum) USB 3.0 external hard drive of PACP formatted database including, but not limited to, digital inspection recordings, defect call-out tables, defect snapshots, notes fields and asset condition reports.
3.4.4.2 Post-Construction Inspection –
3.4.4.2.1 Two copies of Written Inspection Reports in bound report with project name on binder spine. Reports to be filed in ascending order by pipe segment number.
3.4.4.2.2 One copy on a 5 Gbit/sec (minimum) USB 3.0 external hard drive of the PACP formatted database including, but not limited to, digital inspection recordings, defect call-out tables, defect snapshots, notes fields and asset condition reports.
File details come from the government source that posted it. Updated .