SCRRF_Enclosed_Flare_Station_Installation_Project_-_IFB_Plans.pdf

PDF 31 MB Posted

Attached to
Santa Cruz RRF Enclosed Flare Station Installation Project
Solicitation number
IFB No. PW-0269
Issued by
Santa Cruz County, San Francisco City, California

About this file

This is an Invitation for Bids (IFB No. PW-0269) issued by the City of Santa Cruz, California Public Works Department for the Santa Cruz Resource Recovery Facility Enclosed Flare Station Installation Project. The project involves designing, constructing, and installing a low-nitrogen oxide (NOx) enclosed flare station at the facility located at 605 Dimeo Lane to serve as a backup landfill gas collection and destruction device. The scope of work includes construction of approximately 3,600 square feet of flare station infrastructure, installation of approximately 200 linear feet of landfill gas header pipe, condensate management and air pipelines, a 92-inch outer diameter by 420-foot tall flare stack with combustion air blower systems and gas handling equipment, trenching and electrical work, concrete foundations, structural steel installation, and a six-foot-high chain link fence with access gates. The mandatory pre-bid meeting is scheduled for February 23, 2026, at 10:00 a.m. at the project site. Sealed bids are due by March 10, 2026, at 2:00 p.m. at the Santa Cruz Public Works Department, 809 Center Street, Room 201, Santa Cruz, CA 95060. Questions and clarifications must be submitted by February 27, 2026, at 5:00 p.m. The project must be completed within 90 working days from the Notice to Proceed, with liquidated damages of $1,000 per calendar day for failure to meet the deadline.

The engineer's estimate for the project is $635,000. Bidders must provide firm-fixed pricing with no escalation and submit a minimum of three client references demonstrating relevant experience within the past five years. All contractors must comply with prevailing wage requirements and maintain current California Department of Industrial Relations registration. Proof of insurance is required, including Professional Liability, Commercial General Liability, Auto Liability, and Workers' Compensation coverage with minimum limits of $2,000,000 per occurrence for general liability and $1,000,000 for automobile liability. At contract award, the successful bidder must provide a performance bond equal to 100 percent of the contract price, a payment bond of 50 percent of the contract price, and a maintenance bond equal to 10 percent of the contract price, with the maintenance bond remaining in force for one year after official acceptance. Bid security of 10 percent of the proposal amount must accompany each bid submission. No specific set-aside designations for disadvantaged enterprises are identified in the solicitation. All contractors must comply with the City's Living Wage Ordinance and prevailing wage requirements. The City reserves the right to reject any and all bids and will award the contract to the lowest responsible and responsive bidder.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fi le

: X :\P

R O

JE

C

TS

\S

AN

TA

C R

U Z\

7-

-4

- S an ta

C ru z Lo w -N

O x

Fl ar e\ Pr oj ec t D ra w in gs \1

-2

4-

_T

IT

LE

S

H

EE

T.

dw g L ay ou t:

G

-0

U se r:

C

H

EL

SE

A.

EV

AN

S Ja n

, 2

- 6

:1 9p m

IS

S

U E

D F

O R

B

ID

D

IN

G

N O

T F

O R

C O

N S

T R

U C

T

IO

N

01-28-2026

REV REVISION DESCRIPTION

DESIGNED BY : LCM

DRAWN BY : GSW

DATE :

CITY OF SANTA CRUZ PUBLIC WORKS DEPARTMENT

DATE

SHEET

CHECKED BY : CME

APPROVED BY : PJS

SANTA CRUZ RRF

ENCLOSED FLARE STATION INSTALLATION PROJECT

21700 COPLEY DRIVE, SUITE 200

DIAMOND BAR, CA 91765

TEL: (909) 860-7777

FAX: (909)860-8017

LOCATION MAP

RECOVERY

FACILITY

SANTA CRUZ

RESOURCE

PROJECT MANAGER

DEPUTY DIRECTOR

SENIOR ENGINEER

RECOMMENDED:

APPROVED:

DATE

DATE

ACCEPTED:

CITY OF SANTA CRUZ

PUBLIC WORKS DEPARTMENT

809 CENTER STREET, ROOM 201

SANTA CRUZ, CA 95060

PAUL J. STOUT, P.E.

TETRA TECH

UNDERGROUND SERVICE ALERT

Call: TOLL FREED

AC

LL

YE OU

RFO

BE

GI

OWNER: CIVIL ENGINEER:

CITY OF SANTA CRUZ RESOURCE RECOVERY FACILITY

605 DIMEO LANE

SANTA CRUZ, CA 95060

COORDINATES SHOWN ARE BASED ON

NAD27, CALIFORNIA ZONE III COORDINATE

SYSTEM

ELEVATIONS WAS REFERENCE TO

CONTROL PROVIDED BY THE CITY OF

SANTA CRUZ.

BASIS OF BEARINGS:

AT LEAST TWO DAYS

BEFORE YOU DIG

SITE ADDRESS:

VENTURA

MONO

SAN BERNARDINO

INYO

TULARE

LOS

ANGELES

KERN

IMPERIAL

RIVERSIDE

ORANGE

SAN DIEGO

LASSEN

MODOC

BUTTE SIERRA

PLUMAS

SISKIYOU

TRINITY

TEHAMA

GLENN

MENDOCINO

SHASTA

ALPINE

SUTTER

M

EN

TO

SA

CR

A-

AMADOR

EL DORADO

PLACER

MARIPOSA

MADERACLARA

STANISLAUS

CALA

VERAS

TUOLUMNE

JO

AQUINSAN

COLUSA

LAKE

NAPASONOMA

SAN MATEO

SAN FRANCISCO

MARIN

CONTRA

SOLANO

SANTA

ALAMEDA

COSTA

YOLO

YUBA NEVADA

HUMBOLDT

DEL NORTE

FRESNO

KINGS

BENITO

MONTEREY

SAN

SANTA

OBISPO

BARBARA

LUIS

SAN

PROJECT LOCATION

MERCED

VICINITY MAP

SANTA CRUZ

CITY OF SANTA CRUZ

PUBLIC WORKS DEPARTMENT

RESOURCE RECOVERY FACILITY (RRF)

SANTA CRUZ, CALIFORNIA

SANTA CRUZ RRF ENCLOSED FLARE STATION

INSTALLATION PROJECT

COVER SHEET

NOT TO SCALE

NOT TO SCALE

SHEET INDEX

SHEET NUMBER DESCRIPTION

G-002

C-100 EXISTING SITE PLAN

M-101 CONSTRUCTION SITE PLAN

M-102 UTILITY SITE PLAN

M-301 FLARE STATION SECTIONS

M-501 TYPICAL DETAILS

SYMBOLS AND ABBREVIATIONS

D-601 PIPE INSTRUMENTATION DIAGRAM

S-001 STRUCTURAL NOTES

S-002 STRUCTURAL OBSERVATIONS SPECIAL INSPECTIONS

S-101 FLARE AND COMBUSTION BLOWER FOUNDATION

S-102

S-501 TYPICAL STRUCTURAL DETAILS

E-100 ELECTRICAL SITE PLAN

E-501 ELECTRICAL DETAILS

E-601 ELECTRICAL SINGLE LINE DIAGRAM

S-301 FENCING SECTIONS

BLOWER SKID FOUNDATION DETAILS

CIVIL DETAILSC-501

PA-001-1451

GAS HANDLING SYSTEM TOP ASSEMBLY

OS-009-0334 OVERALL SITE LAYOUT

FLARE TOP ASSEMBLY 92� OD X 420� TALL (1 OF 2)

PA-001-1451

PA-001-1454

PA-001-1452

COMBUSTION AIR BLOWER TOP ASSEMBLY

SHEET INDEX

SHEET NUMBER DESCRIPTION

ME-009-0717 FLARE P ID (1 OF 3)

ME-009-0717 FLARE P ID (2 OF 3)

ME-009-0717 FLARE P ID (3 OF 3)

PA-002-0801 CONTROL PANEL

EE-003-0697 480 V 3 PHASE ELEMENTARY (1 OF 2)

EE-003-0697 480 V 3 PHASE ELEMENTARY (2 OF 2)

EE-005-0853 120 VAC INSTRUMENTATION ELEMENTARY (1 OF 4)

EE-005-0853 120 VAC INSTRUMENTATION ELEMENTARY (2 OF 4)

EE-005-0853 120 VAC INSTRUMENTATION ELEMENTARY (3 OF 4)

EE-005-0853 120 VAC INSTRUMENTATION ELEMENTARY (4 OF 4)

FLARE TOP ASSEMBLY 92� OD X 420� TALL (2 OF 2)

21700 COPLEY DRIVE, SUITE 200

DIAMOND BAR, CA 91765

TEL 909.860.7777 FAX 909.860.8017

S-502 TYPICAL STRUCTURAL DETAILS

S-100 OVERALL FOUNDATION PLAN

G-001 CONSTRUCTION NOTES

DATE

C-101 OVERALL CONSTRUCTION SITE PLAN

C-102 GRADING PLAN

S-503 TYPICAL STRUCTURAL DETAILS

PA-001-1493 AIR COMPRESSOR TOP ASSEMBLY

JANUARY 2026

: X :\P

R O

JE

C

TS

\S

AN

TA

C R

U Z\

7-

-4

- S an ta

C ru z Lo w -N

O x

Fl ar e\ Pr oj ec t D ra w in gs \G

-0

C O

N

ST

R U

C

TI

O N

N O

TE

S.

dw g

L ay ou t:

G -0

U se r:

C H

EL

SE

A.

EV

AN

S

Ja n

, 2

- 6 :1

9p m

IS

S

U E

D F

O R

B

ID

D

IN

G

N O

T F

O R

C O

N S

T R

U C

T

IO

N

01-28-2026

REV REVISION DESCRIPTION

DESIGNED BY : LCM

DRAWN BY : GSW

DATE :

CITY OF SANTA CRUZ PUBLIC WORKS DEPARTMENT

DATE

SHEET

CHECKED BY : CME

APPROVED BY : PJS

SANTA CRUZ RRF

ENCLOSED FLARE STATION INSTALLATION PROJECT

G-001

NOTES:

1. CONTRACTOR TO SURVEY AND STAKE CONCRETE CORNER LOCATIONS AND OBTAIN APPROVAL FROM THE ENGINEER AND OWNER PRIOR TO

PROCEEDING.

2. THE CONTRACTOR SHALL LAY OUT THE PIPE TO CONFORM TO FIELD CONDITIONS. PROVIDE 36" MINIMUM COVER AND 5% MINIMUM SLOPE CROSSING BELOW PERIMETER AND MAIN HAUL ROADS. PROVIDE MINIMUM PIPE DRAINAGE SLOPES OF 3% WITHIN WASTE LIMIT AND 1% OUTSIDE OF WASTE LIMIT. CONTRACTOR RESPONSIBLE FOR CUT (12" MAX, UNLESS OTHERWISE NOTED PER PLAN) AND FILL BENEATH PIPE TO

ENSURE PROPER DRAINAGE, AS APPROVED BY THE ENGINEER AND OWNER.

3. FEATURES, CONTOURS, AND ELEVATIONS OF THESE BASE MAPS ARE APPROXIMATE INDICATIONS OF CURRENT AND FUTURE CONDITIONS.

CONTRACTOR IS RESPONSIBLE FOR INSPECTING WORK AREAS AT PRE-BID SITE WALK TO ASCERTAIN THE CURRENT CONDITIONS FOR BIDDING PURPOSES. CONTRACTOR SHALL VERIFY THE ACTUAL LOCATIONS OF THESE ELEMENTS PRIOR TO, AND DURING CONSTRUCTION, AND SHALL FINALIZE THE GAS SYSTEM LOCATIONS TO ACCOMMODATE FINAL FIELD CONDITIONS, AS APPROVED BY THE ENGINEER AND OWNER.

4. ALL CONNECTIONS TO EXISTING PIPING SHALL BE CONFIRMED BY THE CONTRACTOR PRIOR TO CONSTRUCTION. SOME CONNECTIONS MAY

REQUIRE EXCAVATION.

5. CONTRACTOR SHALL BE RESPONSIBLE FOR MAKING ALL DISCONNECTIONS AND RECONNECTIONS FOR INSTALLATION OF ALL PROJECT

RELATED PIPING WHERE NECESSARY.

6. WORK SHALL NOT VARY FROM DESIGN WITHOUT APPROVAL OF THE ENGINEER. WORK THAT VARIES FROM DESIGN WITHOUT APPROVAL WILL BE SUBJECT TO REWORK TO MAINTAIN ADHERENCE TO THE APPROVED DESIGN. ANY REWORK WILL BE PAID FOR BY THE CONTRACTOR ENTIRELY.

7. FORCE MAIN TO BE PRESSURE TESTED IN TRENCH FOR 30 MINUTES AT 4 PSIG THEN 30 MINUTES AT 100 PSIG. GREATER THAN 10% DROP IN PRESSURE OVER 1 HOUR SHALL INDICATE A LEAK EXISTS AND SHALL BE REPAIRED. PIPE SHALL BE TESTED IN SEGMENTS NO LONGER THAN

2,000 FEET UNLESS APPROVED BY THE ENGINEER.

8. ALL PIPING GREATER THAN 6 INCHES IN DIAMETER SHALL BE PRESSURE TESTED FOR 1 HOUR AT 10 PSIG. GREATER THAN 10% DROP IN PRESSURE OVER 1 HOUR SHALL INDICATE A LEAK EXISTS AND SHALL BE REPAIRED AND RETESTED. PIPE SHALL BE TESTED IN SEGMENTS NO

LONGER THAN 2,000 FEET UNLESS APPROVED BY THE ENGINEER.

9. CONTRACTOR TO REMOVE AND REUSE EXISTING PUMPS, PIPING AND FITTINGS WHERE APPLICABLE. CAP ALL ABANDONED PIPE. IF ABANDONED PIPE IS HDPE, USE FUSED ON HDPE CAP. IF ABANDONED PIPE IS PVC, USE PVC SCH 40 CAP SECURED WITH SET SCREWS AT 90° AND CEMENT.

10. ALL EXISTING PIPING THAT IS NOT IN USE, AS DIRECTED BY THE OWNER, SHALL BE RELOCATED BY THE CONTRACTOR TO THE ON-SITE

STORAGE FACILITY AS DIRECTED BY THE OWNER.

11. CONTRACTOR TO USE FACTORY MOLDED/FABRICATED CONCENTRIC REDUCER FITTINGS AS NECESSARY.

12. CONTRACTOR TO PROTECT IN PLACE THE EXISTING ABOVE AND BELOW GRADE LATERALS DURING CONSTRUCTION. IF EXISTING PIPING NEEDS TO BE RELOCATED TEMPORARILY DURING CONSTRUCTION, THE CONTRACTOR WILL ENSURE CONSTANT SLOPE IS MAINTAINED ON THE PIPE AND THE LATERALS WILL BE RETURNED TO THEIR EXISTING CONDITION FOLLOWING CONSTRUCTION ACTIVITIES.

13. ELECTROFUSION COUPLERS SHALL NOT BE USED UNLESS APPROVED BY THE ENGINEER AND OWNER.

14. ALL EQUIPMENT, CONDUIT, PIPING AND OTHER MATERIALS, UNLESS OTHERWISE NOTED, ARE TO BE PROVIDED BY THE CONTRACTOR.

15. THE CITY SHALL FURNISH, PROVIDE AND DELIVER THE PROPOSED EQUIPMENT OF THIS PROJECT. THE CONTRACTOR SHALL OFF-LOAD AND INSTALL THE EQUIPMENT FURNISHED BY THE CITY AND CONSTRUCT THE ASSOCIATED IMPROVEMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL LABOR, MATERIALS, TOOLS AND EQUIPMENT TO CONSTRUCT A NEW FLARE SYSTEM IN ACCORDANCE WITH THIS CONTRACT. THE WORK SHALL INCLUDE FURNISHING AND INSTALLING ALL MATERIALS NOT PROVIDED BY THE MANUFACTURER, AND COORDINATING WITH THE MANUFACTURER FOR ANY MISSING PARTS AND MATERIALS FOR THE PROPOSED SYSTEM, COMPLETE AND IN PLACE.

SEE THE CONSTRUCTION SPECIFICATIONS FOR THE MATERIALS TO BE PROVIDED BY THE MANUFACTURER.

1. 2025 AS-BUILT SURVEY INFORMATION PROVIDED BY PAUL-HANAGAN SURVEYING ON SEPTEMBER 11, 2025.

2. AERIAL SURVEY OF THE LANDFILL PROPERTY WAS PERFORMED BY ERIK OHLSON & ASSOCIATES PROFESSIONAL LAND SURVEYORS ON MARCH 7, 2025.

3. 2024 GCCS AS-BUILT INFORMATION PROVIDED BY OPAL FUELS, DATE OF RECORD DRAWINGS: MAY 29, 2024.

4. PROPERTY LINE INFORMATION PROVIDED BY PAUL-HANAGAN SURVEYING ON JULY 8, 2025.

GENERAL CONSTRUCTION NOTES:

CONSTRUCTION NOTES

S-101

M-501

S-102

M-501

S-502

CONSTRUCTION NOTES

S-102

B-B S-301

A-A S-301

M-501

M-501

M-501

M-501

S-502

M-501

C-501

C-501A-A

S-502

S-101

M-501

S-502

M-501

M-501

108108

M-501

M-501

E-501

S-502

S-502

: X :\P

R O

JE

C

TS

\S

AN

TA

C R

U Z\

7-

-4

- S an ta

C ru z Lo w -N

O x

Fl ar e\ Pr oj ec t D ra w in gs \1

-2

4-

_G

2_

SY

M

BO

LS

A

N D

A

BB

R

EV

IA

TI

O N

S.

dw g L ay ou t:

G

-0

U se r:

C

H

EL

SE

A.

EV

AN

S Ja n

, 2

- 5

:5 8p m

IS

S

U E

D F

O R

B

ID

D

IN

G

N O

T F

O R

C O

N S

T R

U C

T

IO

N

01-28-2026

REV REVISION DESCRIPTION

DESIGNED BY : LCM

DRAWN BY : GSW

DATE :

CITY OF SANTA CRUZ PUBLIC WORKS DEPARTMENT

DATE

SHEET

CHECKED BY : CME

APPROVED BY : PJS

SANTA CRUZ RRF

ENCLOSED FLARE STATION INSTALLATION PROJECT

G-002SYMBOLS AND ABBREVIATIONS

COMPRESSOR

SELECTOR

INSTRUMENT SYMBOLS

FILTER/REGULATOR/LUBRICATOR

VARIABLE SPEED DRIVE

GROUND

HIGH DENSITY POLYETHYLENE

HAND-OFF-AUTO

FLOW SWITCH OR FINISH SURFACE

FIBERGLASS REINFORCED PLASTIC

FLOW SAFETY VALVE (CHECK VALVE)

GROUND FAULT INTERRUPTER

GAS MONITOR

GROUND FAULT

FUSE HOLDER

GRADE BREAK

FLOW VALVE

FUTURE

FLOW SWITCH LOW

FLOW TRANSMITTER

FUSE

FLOW SWITCH HIGH

PRESSURE CONTROL VALVE

PRESSURE INDICATOR

POLYETHYLENE

PHONE

PILOT GAS

PRESSURE DIFFERENTIAL INDICATOR

PRESSURE ALARM LOW LOW

PRESSURE ALARM HIGH HIGH

PURGE AUTO

PRESSURE ALARM HIGH

PRESSURE ALARM LOW

PRESSURE DIFFERENTIAL INDICATOR

PRESSURE CONTROLLER

PUMP

EVENT INDICATOR CONTROLLER

POSITION SWITCH CLOSED

POSITION SWITCH OPENED

POSITION INDICATOR

POSITION SWITCH

POSITION CONTROLLER

POSITION ALARM

EVENT INDICATOR

VIBRATION SWITCH HIGH

VIBRATION TRANSMITTER

EVENT ALARM

EXPLOSION PROOF

WEATHER PROOF

TRANSFORMER

WATTS

WATER COLUMN

MOTOR OPERATED VALVE

EXISTING

TEMPERATURE

NAMEPLATE

FLOW ELEMENT (FLOW METER)

FLOW TOTALIZER INDICATOR

FLOW INDICATING RECORDER

FLOW INDICATING TRANSMITTER

FLARE

FLEXIBLE HOSE

FORWARD

FLOW RECORDER

FILTER REGULATOR

FAIL OPEN

PORT FILTER

FULL LOAD AMPS

FLOWLINE

FINISH GRADE

FLAME FAILURE ALARM

FLOW INDICATOR

OXYGEN ALARM HIGH HIGH

OXYGEN TRANSMITTER

OXYGEN INDICATING RECORDER

OXYGEN INDICATOR

OXYGEN ELEMENT

OVERLOAD

OXYGEN INDICATOR TRANSMITTER

OXYGEN SENSOR FAILURE

NOT TO SCALE

OPEN/CLOSE

OXYGEN

OXIDES OF NITROGEN

OXYGEN ANALYZER

OXYGEN ALARM HIGH

ON CENTER

FUSED DISCONNECT

FLOW CONTROL VALVE

FEEDER

FLOW ALARM LOW LOW

FAIL CLOSE

FLOW CONTROLLER

FURNISHED BY OTHERS

FILTER

FLOW ALARM HIGH HIGH

FLOW ALARM LOW

FLOW ALARM HIGH

FLAME ARRESTER

DEGREE FAHRENHEIT

EXPLOSION PROOF

NORMALLY OPEN TIMED TO CLOSE

NORMALLY CLOSED TIMED TO OPEN

NORMALLY CLOSED TIMED TO CLOSE

NORMALLY OPEN

NOT IN CONTRACT

NEGATIVE

NORMALLY OPEN TIMED TO OPEN

NEUTRAL BLOCK

NORMALLY CLOSED

NON-AUTOMATIC

MANWAY

MOUNTED

MAIN SWITCH BOARD

MOTOR STARTER

VIBRATION ALARM

VIBRATION INDICATING RECORDER

VIBRATION ALARM HIGH HIGH

VARIABLE FREQUENCY DRIVE

VIBRATION INDICATOR

VAPOR PROOF

VIBRATION SWITCH

VIBRATION ALARM HIGH

UNINTERRUPTIBLE POWER SUPPLY

TEMPERATURE TRANSMITTER

UNDERGROUND

VESSEL

ULTRAVIOLET SCANNER

TYPICAL

TEMPERATURE VALVE

TEMPERATURE SAFETY VALVE

TEMPERATURE SAFETY ELEMENT

TEMPERATURE SWITCH HIGH

TEMPERATURE SWITCH LOW

TEMPERATURE RECORDER

TIGHT SHUTOFF

TEMPERATURE SWITCH OR TOP OF SLAB

TIMER

TEMPERATURE INDICATOR RECORDER

TEMPERATURE ELEMENT WELL

TEMPERATURE ELEMENT SWITCH

TEMPERATURE INDICATOR

TEMPERATURE INDICATOR CONTROLLER

TEMPERATURE INDICATOR TRANSMITTER

THERMOSTAT

ELECTRICAL DISTRIBUTION PANEL

DIFFERENTIAL PRESSURE SWITCH

DIFFERENTIAL PRESSURE INDICATOR

ELECTRICAL METALLIC TUBING

VOLTAGE INDICATOR

EMERGENCY

EQUIPMENT

ENCLOSURE, ENCLOSED

ELAPSED TIME METER

EXHAUST

ELEVATION

DRAWING

VOLTAGE TRANSFORMER

ELECTRICAL MOTOR

DISCONNECT SWITCH

MANHOLE

METHANE INDICATOR

MODEM

METHANE INDICATING RECORDER

METHANE INDICATOR TRANSMITTER

MOTOR

MANUAL MOTOR STARTER

MINIMUM

METHANE ALARM LOW LOW

MOTOR CONTROL CENTER

MAIN CONTROL PANEL

THOUSAND CIRCULAR MILS

MAXIMUM

MANWAY

MAGNETIC

CONTROL VALVE (MODULATING)

CONTROL POWER TRANSFORMER

DISTRIBUTION

DAYLIGHT

CURRENT TRANSFORMER

DRYER

CURRENT SWITCH HIGH

METHANE ANALYZER

LUBRICATOR

METHANE ALARM LOW

MILLIAMPS

MOTOR

LIGHTING

LEVEL TRANSMITTER OR LIGHT(S)

LEVEL SWITCH LOW LOW

LEVEL SWITCH

LIGHTING PANEL

LOCK-OUT-STOP

LEVEL SWITCH LOW

LEVEL SWITCH HIGH HIGH

LEVEL SWITCH HIGH

LOCAL

TEMPERATURE ALARM LOW

TEMPERATURE ALARM LOW LOW

TEMPERATURE CONTROLLER POSITIONER

TEMPERATURE CONTROLLER

TEMPERATURE ELEMENT (THERMOCOUPLE)

TEMPERATURE CONTROL VALVE

TIME DELAY RELAY

TERMINAL BLOCK

TEMPERATURE ALARM HIGH HIGH

TEMPERATURE ALARM HIGH

TANK

TACHOMETER

STRAINER

SWITCH

SYSTEM

SURGE ARRESTOR

SHUNT TRIP

STATION

STANDARD

SOLENOID VALVE

SAMPLE PORT

STAINLESS STEEL

SPECIFICATION

SEQUENCE, SEQUENCER

SIGHT GLASS

SPEED INDICATOR

SHEET

SHIELD, SHIELDED

SUPPLEMENTAL FUEL

SENSOR FAILURE

MISCELLANEOUS SYMBOLS

RELAY FUNCTION DESIGNATIONS TYPES

CURRENT TRANSFORMER

ALUMINUM

KILOWATTS

COMBUSTIBLE GAS HIGH HIGH

COMBUSTIBLE GAS INDICATOR

CIRCUIT

CONDUIT ONLY

CHANNEL

LOWER EXPLOSIVE LIMIT

LEVEL GAGE

LANDFILL GAS

LUBE OIL

LEVEL ELEMENT

LATCHING CONTROL RELAY

LOCAL CONTROL PANEL

LAMP

LEVEL CONTROLLER HIGH

LEVEL CONTROLLER LOW

LEVEL CONTROLLER

LEVEL ALARM LOW LOW

LEVEL ALARM LOW

LEVEL ALARM HIGH HIGH

LEVEL ALARM HIGH

BARE COPPER

AUTOMATIC

BURNER ALARM LOW LOW

BLOWER

AMPERE TRIP

AMPERES, AMPERAGE

INSTRUMENT

KILOVOLTS

KILOVOLT AMPERES

TIME INDICATOR

CURRENT TRANSMITTER

SHORT CIRCUIT CURRENT

INVERT

CURRENT INDICATING RECORDER

IGNITOR

INSTRUMENT AIR SUPPLY

CURRENT ALARM LOW

CURRENT ALARM HIGH HIGH

CURRENT ALARM HIGH

INSTANTANEOUS

CURRENT ALARM LOW LOW

STANDARD CUBIC FEET PER MINUTE

SHUTDOWN OR ON

SECTION

SECONDARY, SECONDS

SHUTDOWN VALVE

SHUTDOWN

SCHEDULE

RETENTION TIME CALCULATOR

REVOLUTIONS PER MINUTE

RIGID GALVANIZED STEEL

AIR STRIPPER

RETENTION TIME

SPECTACLE BLIND

RELAY MODULE

RESISTOR

POLYVINYL CHLORIDE

RUPTURE DISK ALARM HIGH

RUPTURE DISK

RUPTURE DISK SWITCH

RECEPTACLE

TOTALIZER

POWER

REQUIRED

PRESSURE SAFETY ELEMENT

PRESSURE TRANSMITTER

POUNDS PER SQUARE INCH

PRESSURE RELIEF VALVE

PRESSURE SWITCH LOW

PRESSURE SWITCH HIGH

PRESSURE SWITCH

MISCELLANEOUS ABBREVIATIONS

ACTUAL CUBIC FEET PER MINUTE

ANALOG OUTPUT

ANALOG INPUT OUTPUT

ANALOG INPUT

AIR CONDITIONER

CURRENT INDICATOR

CURRENT

HAND VALVE PORT

HEAT TRACE

HAND VALVE

HEATER

HERTZ

HORSEPOWER OR HIGH POINT

HAND SWITCH

PROGRAMMABLE LOGIC CONTROLLER

POWER PANEL or POWER POLE

PRESSURE INDICATING RECORDER

POSITION, POSITIVE

POSITIONER

POTENTIOMETER

PANEL

PILOT

PIPING AND INSTRUMENTATION DIAGRAM

PRESSURE INDICATING CONTROLLER

INDUSTRIAL TECHNICAL CORPORATION

LEVEL INDICATOR

PUSH BUTTON

BUILDING PROTECTION SYSTEM

ACTUATOR

AUTO DIALER SYSTEM

AMPERE FRAME SIZE (CIRCUIT BREAKER)

ABOVE FINISH FLOOR

AMERICAN WIRE GAUGE

BATTERY

BURNER GLASS

BURNER ELEMENT (UV SCANNER)

BREAKER

BILL OF MATERIAL

BURNER SWITCH (FLAME SAFEGUARD)

BRITISH THERMAL UNIT

CONDUIT

CURRENT ALARM HIGH

CURRENT ALARM LOW

CABLE

CENTER TO CENTER

COMBUSTIBLE GAS HIGH

COMBUSTIBLE GAS TRANSMITTER

CHART RECORDER

CURRENT INDICATOR

COUNTER

COMMUNICATION

CONTROL PANEL

CHLORINATED POLYVINYL CHLORIDE

CONTROL RELAY

CARBON STEEL

CURRENT SWITCH LOW

COPPER

DIGITAL INPUT

DELTA OR DIFFERENTIAL PRESSURE

PLC CONTROLLED DEVICE

LOCALLY PANEL MOUNTED UNIT

INSTRUMENT MOUNTED BEHIND BOARD

CONTROL PANEL MOUNTED INSTRUMENT

LOCALLY MOUNTED INSTRUMENT

REMOTE CONTROL

REMOTE MONITORING

PILOT LIGHT (R=RED; G=GREEN; A=AMBER; B=BLUE;

INSTRUMENT MOUNTED BEHIND LOCAL BOARD

LOCAL BOARD MOUNTED INSTRUMENT

W=WHITE; C=CLEAR; N=NEON)

CONTROL PANEL MOUNTED INSTRUMENT

AUTO/MANUAL

LOCAL/REMOTE

HAND/OFF/AUTO

ANALOG/DIGITAL

CURRENT TO PNEUMATIC

DETAIL NUMBER

INTERLOCK IF ANY ONE OR MORE INPUTS EXIST

RESET FOR LATCH TYPE ACTUATOR

INTERLOCK

SOLENOID VALVE

INTERLOCK IF ALL INPUTS EXIST

SHEET NUMBER DETAIL IS DRAWN ON

I/P

A/M

A/D

L/R

HOA

S

I

R

AND

OR

PILOT TUBE OR PILOT VENTURI TUBE

PISTON OPERATED VALVE WITH HANDWHEEL,

SELF-CONTAINED PRESSURE CONTROL VALVE

HYDRAULIC OR PNEUMATIC (SPRING RETURN)

SOLENOID-OPERATED 2-WAY VALVE

INSTRUMENTATION DEVICES & ACCESSORIES

LINE & SIGNAL SYMBOLS

SIDE-MOUNTED

PISTON-OPERATED VALVE

SOLENOID-OPERATED 3-WAY VALVE

PRESSURE RELIEF VALVE

PISTON-OPERATED VALVE WITH OPEN AND

CLOSED POSITION SWITCHES AND WITH

HANDWHEEL, SIDE MOUNTED

CONTROL VALVE WITH I/P TRANSDUCER

BUTTERFLY VALVE, HAND OPERATED

BALL VALVE, HAND OPERATED

NEEDLE VALVE, HAND OPERATED

HAND VALVE, HAND OPERATED

3-WAY HAND VALVE, HAND OPERATED

PRESSURE REGULATOR W/PRESSURE GAUGE

BUTTERFLY VALVE, AUTOMATED

GEAR OPERATOR

Y-STRAINER

PNEUMATIC POSITIONER

FLEX CONNECTOR

FLEX CONNECTOR WITH FLANGE CONNECTION

FLANGE CONNECTION

BLIND FLANGE

UNION

CAP OR PLUG

CONCENTRIC REDUCER

ECCENTRIC REDUCER

SAMPLE PORT

MANUAL ACTUATOR/OVERRIDEMA

G

S

S

PRV

G

ZSO ZSC

P

G

A

PI

CMP or COMP

CV

CPT

DISTR

DL

CT

D

CSH

AL

CGHH

CGI

CIR

CO

CH

BC

AUTO

BALL

B

AT

AMP

ACFM

AOUT

AIO

AI

AC or A/C

BPS

A

ADS

AF

AFF

AWG

BATT

BG

BE

BKR

BOM

BS

BTU

C

CAH

CAL

CBL

CC

CGH

CGT

CHR

CI

CNT

COMM

CP

CPVC

CR

CS

CSL

CU

DI

DP

ETM

FALL

EXIST

F.C.

FCV

FAHH

FBO

FA

DWG

E

EMER

ENCL

EDP

DPI

DPS

E/E

EI

EL OR ELEV

EMT

EQPT

EXH

EXP

°F

FLT or F

FAH

FAL

FC

FD

DS

FDR

FE

FFA

FG

FI

FIR

FIT

FL

FLA

FLR

FX or FLEX

FLTP

F.O.

FOR

FQI

FR

FRG

FRL

FRP

FS

FSH

FSL

FSV

FT

FU

FUH

FUT

FV

GB

GF

GFI

GM

GND or GRND

HDPE

HOA

HP

HS

HT

HTR

HV

HVP

HZ

I

II

I/I

IAH

IAHH

IAL

IALL

IAS

IG or IGN

IIR

INST

INSTR

INV

ISC

IT

ITC

KI

KV

KVA

KW

LAH

LAHH

LAL

LALL

LC

LCH

LCL

LCP

LCR

LE

LEL

LFG

LG

LI

LMP

LO

LOC

LOS

LP

LS

LSH

LSHH

LSL

LSLL

LT

LTG

LUB

M

MA

M.A.

MAL

MALL

MAG

MAN

MAX

MCC

MCM

MCP

MH

MI

MIR

MIN

MIT

MMS

MOV

MS

MSB

MTD

M.W.

NA

NBK

N.C.

N.C.T.C.

N.C.T.O.

NEG

NIC

N.O.

N.O.T.C.

N.O.T.O.

NP

NTS

NOX

O O/C

O.C.

OA

OAH

OAHH

OE

OI

OIR

OT

OIT

OSF

OL

PDI

PMP or P

PB

PA

PAH

PAHH

PAL

PALL

PC

PCV

PDI

PE

PG

PH

PI

P&ID

PIC

PIR

PLC

PLT

PNL

POS

POT

POZ

PP

PS

PSE

PSH

PSI

PSL

PT

PRV

PVC

PWR

QL

REQD

RD

RDAH

RDS

RECEPT

RES

RGS

RM

RPM

RT

RTC

S

SB

SCFM

SCH

SD

SD/O

SDV

SEC

SECT

SEL

SEQ

SF

SFR

SG

SHLD

SHT

SI

SPECS

SS

SSR

ST

STA

STD

STR

SW

SYS

T or TK

TACH

TAH

TAHH

TAL

TALL

TB

TC

TCV

TCZ

TD or TDR

TE

TEMP

TES

TEW

THERM

TI

TIC

TIR

TIT

TMR

TR

TS

TSE

TSH

TSL

TSO

TSV

TT

TV

TYP

UG

UPS

UV

V

VA

VAH

VAHH

VFD

VI

VIR

VP

VS

VSD

VSH

VT

W

W.C.

WP

XFMR

XP

YA

YI

YIC

ZA

ZC

ZI

ZS

ZSC

ZSO

MOT

SP

MOD

SOV

GRANULAR ACTIVATED CARBONGAC

PRESSURE INDICATING TRANSMITTERPIT

GAS COLLECTION AND CONTROL SYSTEMGCCS

BOTTOMBTM

EXPANSION JOINT

VACUUM BREAKVB

STANDARD DIMENSION RATIOSDR

ANGLE VALVE

AUXILIARY PORTAP

BURNERBNR

BLACK IRONBI

CHECK VALVE

ELECTRIC MOTOR WITH FAN

BUTTERFLY VALVE, GEAR OPERATEDG

MAN WELL

BLOWER

EXISTING LFG HEADER OR LATERAL

PROPOSED PROPANE GAS PIPING

PROPOSED ABOVE GRADE AIR PIPING

PROPOSED 4-INCH X 2-INCH BELOW GRADE DUAL

CONTAINED CONDENSATE PIPING

PROPOSED LFG PIPING AND EQUIPMENT

PROPOSED 4-INCH X 2-INCH ABOVE GRADE DUAL

CONTAINED CONDENSATE PIPING

PROPOSED ABOVE GRADE CONDENSATE PIPING

PROPOSED BELOW GRADE AIR PIPING

246 244

W-3G

W-11G

W-2G

W-8G

W-19G-SR2,MR2

W-20G

W-7G

W-19G-DR2

W-11GR

W-21G W-4GR

CELL 2

CELL 3A

CELL 1

CELL 3B

LEGEND

EXISTING MAJOR CONTOUR

EXISTING MINOR CONTOUR

EXISTING POWER POLE

EXISTING OVERHEAD ELECTRIC

PROPERTY LINE

EXISTING 1-INCH AIR PIPING

EXISTING 2-INCH CONDENSATE PIPING

EXISTING 4-INCH LFG (BELOW GRADE)

EXISTING 4-INCH LFG

EXISTING 6-INCH LFG (BELOW GRADE)

EXISTING

EXISTING 6-INCH LFG

EXISTING 8-INCH LFG (BELOW GRADE)

EXISTING 8-INCH LFG

EXISTING 10-INCH LFG (BELOW GRADE)

EXISTING

EXISTING 10-INCH LFG

EXISTING 12-INCH LFG (BELOW GRADE)

EXISTING 12-INCH LFG

EXISTING LFG PIPING

EXISTING SUMP

EXISTING GAS WELL

EXISTING GAS PROBE

CELL LIMIT

EXISTING SHRUBBERY

EXISTING UNPAVED ROAD

EXISTING BUILDINGS

C-100EXISTING SITE PLAN

Fi le

: X :\P

R O

JE

C

TS

\S

AN

TA

C R

U Z\

7-

-4

- S an ta

C ru z Lo w -N

O x

Fl ar e\ Pr oj ec t D ra w in gs \C

-1

E

XI

ST

IN

G S

IT

E

PL

AN

.d w g L ay ou t:

C

-1

U se r:

C

H

EL

SE

A.

EV

AN

S Ja n

, 2

- 5

:5 8p m

IS

S

U E

D F

O R

B

ID

D

IN

G

N O

T F

O R

C O

N S

T R

U C

T

IO

N

01-28-2026

REV REVISION DESCRIPTION

DESIGNED BY : LCM

DRAWN BY : GSW

DATE :

CITY OF SANTA CRUZ PUBLIC WORKS DEPARTMENT

DATE

SHEET

CHECKED BY : CME

APPROVED BY : PJS

SANTA CRUZ RRF

ENCLOSED FLARE STATION INSTALLATION PROJECT

246 244

C P-

X

X

14% SLOPE

4% SLOPE

X X

X

XXXXXX

X

X X

X X

X X X X X X X X X

Fi le

: X :\P

R O

JE

C

TS

\S

AN

TA

C R

U Z\

7-

-4

- S an ta

C ru z Lo w -N

O x

Fl ar e\ Pr oj ec t D ra w in gs \1

-2

4-

_C

1_ C

O N

ST

R

U C

TI

O

N P

LA

N

.D W

G L ay ou t:

C

-1

U se r:

C

H

EL

SE

A.

EV

AN

S Ja n

, 2

- 5

:5 9p m

IS

S

U E

D F

O R

B

ID

D

IN

G

N O

T F

O R

C O

N S

T R

U C

T

IO

N

01-28-2026

REV REVISION DESCRIPTION

DESIGNED BY : LCM

DRAWN BY : GSW

DATE :

CITY OF SANTA CRUZ PUBLIC WORKS DEPARTMENT

DATE

SHEET

CHECKED BY : CME

APPROVED BY : PJS

SANTA CRUZ RRF

ENCLOSED FLARE STATION INSTALLATION PROJECT

C-101OVERALL CONSTRUCTION SITE PLAN

LEGEND

NOTES:

1. ENDANGERED SPECIES AREA. CONTRACTOR TO AVOID ANY AND ALL CONSTRUCTION ACTIVITIES

IN THIS AREA TO MINIMIZE ANY DISTURBANCES.

EXISTING LFG HEADER OR LATERAL (4-INCH , 6-INCH , OR 8-INCH )

EXISTING MAJOR CONTOUR

PROPOSED FENCE

EXISTING STORM DRAIN

EXISTING MINOR CONTOUR

TREE LINE/SHRUBBERY

PROPOSED WALL

PROPOSED CONCRETE FOUNDATION

EXISTING CONDENSATE PIPING

EXISTING AIR PIPING

WOODRAT MIDDEN ENDANGERED SPECIES AREA (SEE NOTE 1)

PROPOSED LFG PIPING AND EQUIPMENT

92 13

95 96 97

CONSTRUCTION NOTES

PROPOSED 4-INCH X 2-INCH BELOW GRADE DUAL CONTAINED CONDENSATE PIPING

PROPOSED PROPANE GAS PIPING

PROPOSED 1-INCH ABOVE GRADE HDPE SDR-9 AIR PIPING

PROPOSED 4-INCH X 2-INCH ABOVE GRADE DUAL CONTAINED CONDENSATE PIPING

M-501

M-501 1

M-501

M-501

M-501

M-501

108108

M-501

M-501

X X

PROPOSED 1-INCH BELOW GRADE HDPE SDR-9 AIR PIPING

246 244

14 1

LIMITS OF

GRADING

T/CONC EL:240.60

T/CONC EL:240.60

X X

XX

X

X X

X X

X X

X

XXXXXXXXXXXX

X

X X

X X

X X

X X

X

X X X X X X X X X X X X X X X X X X X

243.00

T/WALL-3

239.70

FLR-1

239.84

FLR-3

239.96

BLR-1

242.11

T/WALL-2

239.44

B/WALL-2

239.68

RD-1

239.80

BLR-2

239.44

FLR-2

242.37

T/WALL-1

239.26

B/FNC-1

239.55

RD-2

239.95

RD-4

239.95

RD-3

240.02

BLR-4

242.73

T/WALL-4

240.06

B/WALL-4

240.30

BLR-3

240.33

B/WALL-3

239.62

FLR-4

239.70

B/WALL-1

2:

(M

AX

Fi le

: X :\P

R O

JE

C

TS

\S

AN

TA

C R

U Z\

7-

-4

- S an ta

C ru z Lo w -N

O x

Fl ar e\ Pr oj ec t D ra w in gs \C

-1

G R

AD

IN

G P

LA

N

.d w g L ay ou t:

C

-1

U se r:

C

H

EL

SE

A.

EV

AN

S Ja n

, 2

- 5

:5 9p m

IS

S

U E

D F

O R

B

ID

D

IN

G

N O

T F

O R

C O

N S

T R

U C

T

IO

N

01-28-2026

REV REVISION DESCRIPTION

DESIGNED BY : LCM

DRAWN BY : GSW

DATE :

CITY OF SANTA CRUZ PUBLIC WORKS DEPARTMENT

DATE

SHEET

CHECKED BY : CME

APPROVED BY : PJS

SANTA CRUZ RRF

ENCLOSED FLARE STATION INSTALLATION PROJECT

GRADING PLAN

EXISTING LFG HEADER OR LATERAL (4-INCH , 6-INCH , OR 8-INCH )

EXISTING MAJOR CONTOUR

PROPOSED FENCE

C-102

PROPOSED GRAVEL

ADL

ADL

MAS

GRB

EXISTING STORM DRAIN

EXISTING MINOR CONTOUR238

TREE LINE/SHRUBBERY

CONSTRUCTION NOTES

EXISTING STORM DRAIN TO BE REMOVED AND RELOCATED

RELOCATED STORM DRAIN

PROPOSED WALL

PROPOSED ASPHALT DRIVEWAY

PROPOSED CONCRETE FOUNDATION

PROPOSED CONTOUR

EXISTING LEACHATE PIPING

CONSTRUCTION NOTES

LEGEND

PROPOSED LIMIT OF GRADING

EXISTING LFG HEADER OR LATERAL (4-INCH , 6-INCH , OR 8-INCH )

C-501 A-A

S-502

PROPOSED GRATED LINE DRAIN

* NOTE:

ELEVATIONS SHOWN ARE ON GROUND

SURFACE ADJACENT TO CONCRETE

PAD. TOP OF CONCRETE PAD

ELEVATIONS ARE 240.60 AS NOTED ON

EACH PAD.

B-B S-301 A-A

S-301

C-501

C-501

: X :\P

R O

JE

C

TS

\S

AN

TA

C R

U Z\

7-

-4

- S an ta

C ru z Lo w -N

O x

Fl ar e\ Pr oj ec t D ra w in gs \1

-2

4-

_C

1_ C

IV

IL

D

ET

AI

LS

.d w g L ay ou t:

C

-5

U se r:

C

H

EL

SE

A.

EV

AN

S Ja n

, 2

- 5

:5 9p m

IS

S

U E

D F

O R

B

ID

D

IN

G

N O

T F

O R

C O

N S

T R

U C

T

IO

N

01-28-2026

REV REVISION DESCRIPTION

DESIGNED BY : LCM

DRAWN BY : GSW

DATE :

CITY OF SANTA CRUZ PUBLIC WORKS DEPARTMENT

DATE

SHEET

CHECKED BY : CME

APPROVED BY : PJS

SANTA CRUZ RRF

ENCLOSED FLARE STATION INSTALLATION PROJECT

C-501

ADL

ADL

MAS

GRB

DETAIL - PAVEMENT STRUCTURAL SECTION

REFERENCE SHEET: C-101 NTS

DETAIL - PAVEMENT THICKENED EDGE2

REFERENCE SHEET: C-101 NTS

DETAIL3

REFERENCE SHEET: C-101NTS

8" 8"

4" ASPHALTIC CONCRETE PAVING

8" AGGREGATE BASE COURSE

(COMPACTED TO 95% ASTM D-1557)

SUBGRADE (COMPACTED EARTH FILL OR

UPPER 12" OF EXISTING SCARIFIED AND

RECOMPACTED TO 95% ASTM D-1557)

ASPHALTIC CONCRETE PAVING

8" AGGREGATE BASE COURSE

(COMPACTED TO 95% ASTM D-1557)

SUBGRADE

(95% COMPACTION)

CIVIL DETAILS

DESIGN GRADE

(SEE C-101)

__" GRAVEL COVER

(D50 =__")

GEOTEXTILE

WEED MAT

SUBGRADE (COMPACTED

EARTH FILL OR UPPER 12"

OF EXISTING SCARIFIED

AND RECOMPACTED TO

95% ASTM D-1557)

X

X

X X

XX

X

X

4% SLOPE

X X

X X

X X

X X

X

XX

XXXXXXXXXXXXXXXXXX

X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

Fi le

: X :\P

R O

JE

C

TS

\S

AN

TA

C R

U Z\

7-

-4

- S an ta

C ru z Lo w -N

O x

Fl ar e\ Pr oj ec t D ra w in gs \1

-2

4-

_M

0- M

2_

C O

N

ST

R U

C

TI

O N

P

LA

N S.

D W

G L ay ou t:

M

-1

U se r:

C

H

EL

SE

A.

EV

AN

S Ja n

, 2

- 6

:0 0p m

IS

S

U E

D F

O R

B

ID

D

IN

G

N O

T F

O R

C O

N S

T R

U C

T

IO

N

01-28-2026

REV REVISION DESCRIPTION

DESIGNED BY : LCM

DRAWN BY : GSW

DATE :

CITY OF SANTA CRUZ PUBLIC WORKS DEPARTMENT

DATE

SHEET

CHECKED BY : CME

APPROVED BY : PJS

SANTA CRUZ RRF

ENCLOSED FLARE STATION INSTALLATION PROJECT

M-101CONSTRUCTION SITE PLAN

CONSTRUCTION NOTES

A-A' M-301

B-B' M-301

30 35

LEGEND

PROPOSED LFG PIPING AND EQUIPMENT

EXISTING MAJOR CONTOUR

PROPOSED FENCE

EXISTING STORM DRAIN

EXISTING MINOR CONTOUR

TREE LINE/SHRUBBERY

PROPOSED CONCRETE FOUNDATION

EXISTING LEACHATE PIPING

PROPOSED WALL

S-101

S-502

S-502

M-501

M-501

S-102

S-102

S-101

S-502

SITE ACCESS ROADS

X

X X

XX

X

X

4% SLOPE

X X

X X

X X

X X

X

XX

XXXXXXXXXXXXXXXXXX

X

X X

X X

X X

X X

X X

X X

X X

X X

X X

X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

Fi le

: X :\P

R O

JE

C

TS

\S

AN

TA

C R

U Z\

7-

-4

- S an ta

C ru z Lo w -N

O x

Fl ar e\ Pr oj ec t D ra w in gs \1

-2

4-

_M

0- M

2_

C O

N

ST

R U

C

TI

O N

P

LA

N S.

D W

G L ay ou t:

M

-1

U se r:

C

H

EL

SE

A.

EV

AN

S Ja n

, 2

- 6

:0 0p m

IS

S

U E

D F

O R

B

ID

D

IN

G

N O

T F

O R

C O

N S

T R

U C

T

IO

N

01-28-2026

REV REVISION DESCRIPTION

DESIGNED BY : LCM

DRAWN BY : GSW

DATE :

CITY OF SANTA CRUZ PUBLIC WORKS DEPARTMENT

DATE

SHEET

CHECKED BY : CME

APPROVED BY : PJS

SANTA CRUZ RRF

ENCLOSED FLARE STATION INSTALLATION PROJECT

M-102UTILITY SITE PLAN

M-501

LEGEND

CONSTRUCTION NOTES

PROPOSED PROPANE GAS PIPING

PROPOSED PRESSURE REGULATOR WITH PRESSURE GAUGE

PROPOSED HOSE WITH ADAPTER

PROPOSED SOLENOID VALVE

PROPOSED BALL VALVE

PROPOSED PIPING AND EQUIPMENT

EXISTING MAJOR CONTOUR

PROPOSED FENCE

PROPOSED EQUIPMENT FOUNDATIONEXISTING MINOR CONTOURS

TREE LINE/SHRUBBERY

EXISTING LEACHATE PIPE

SITE ACCESS ROADS

EXISTING STORM DRAIN

90 90

102103101

PROPOSED WALL

M-501

M-501

PROPOSED 4-INCH X 2-INCH BELOW GRADE DUAL CONTAINED CONDENSATE PIPING

PROPOSED 1-INCH ABOVE GRADE HDPE SDR-9 AIR PIPING

PROPOSED 4-INCH X 2-INCH ABOVE GRADE DUAL CONTAINED CONDENSATE PIPING

X X

PROPOSED 1-INCH BELOW GRADE HDPE SDR-9 AIR PIPING

S-501

S-50198

: X :\P

R O

JE

C

TS

\S

AN

TA

C R

U Z\

7-

-4

- S an ta

C ru z Lo w -N

O x

Fl ar e\ Pr oj ec t D ra w in gs \1

-2

4-

_M

1_

FL

AR

E

ST

AT

IO

N

S

EC

TI

O

N S.

dw g

L ay ou t:

M -3

U se r:

C H

EL

SE

A.

EV

AN

S

Ja n

, 2

- 5 :5

9p m

IS

S

U E

D F

O R

B

ID

D

IN

G

N O

T F

O R

C O

N S

T R

U C

T

IO

N

01-28-2026

REV REVISION DESCRIPTION

DESIGNED BY : LCM

DRAWN BY : GSW

DATE :

CITY OF SANTA CRUZ PUBLIC WORKS DEPARTMENT

DATE

SHEET

CHECKED BY : CME

APPROVED BY : PJS

SANTA CRUZ RRF

ENCLOSED FLARE STATION INSTALLATION PROJECT

M-301FLARE STATION SECTIONS

CONSTRUCTION NOTES

M-105

S-1013

M-501

S-502

M-501

S-502

2 A-A S-502

NTS

SECTION A-A'

NTS

SECTION B-B'

27 2337

S-102

S-502

S-102

M-501

S-502

: X :\P

R O

JE

C

TS

\S

AN

TA

C R

U Z\

7-

-4

- S an ta

C ru z Lo w -N

O x

Fl ar e\ Pr oj ec t D ra w in gs \1

-2

4-

_M

1_

TY

PI

C

AL

D

ET

AI

LS

.d w g

L ay ou t:

M -5

U se r:

C H

EL

SE

A.

EV

AN

S

Ja n

, 2

- 6 :0

0p m

IS

S

U E

D F

O R

B

ID

D

IN

G

N O

T F

O R

C O

N S

T R

U C

T

IO

N

01-28-2026

REV REVISION DESCRIPTION

DESIGNED BY : LCM

DRAWN BY : GSW

DATE :

CITY OF SANTA CRUZ PUBLIC WORKS DEPARTMENT

DATE

SHEET

CHECKED BY : CME

APPROVED BY : PJS

SANTA CRUZ RRF

ENCLOSED FLARE STATION INSTALLATION PROJECT

M-501TYPICAL DETAILS

NTS REFERENCE SHEET: M-102

1 ABOVE GRADE VALVE DETAIL

EXISTING GRADE

GEAR OPERATOR WITH REMOVABLE VALVE WHEEL

FOR VALVE AND LEVER OPERATOR

BUTTERFLY VALVE, SIZE PER PLAN

TAP AND THREAD 1/4" LABCOCK VALVE INTO PIPE.

WRAP THREADS WITH TEFLON TAPE. (TYP)

HDPE HEADER OR LATERAL

ON GRADE OR PIPE SUPPORTS

(SIZE PER PLAN)

HDPE FLANGE ADAPTER WITH DUCTILE IRON

BACK-UP RING AND RUBBER GASKETS (TYP

OF 2, SIZE PER PLAN)

VALVE SPACERS TO BE INSTALLED FOR

PIPES LARGER THAN 6" (SIZE PER PLAN)

NTS REFERENCE SHEET: M-101

HDPE OR SS FLANGE ADAPTER

ZINC PLATED NUTS, BOLTS,

AND WASHERS

CARBON STEEL OR DUCTILE IRON

BACK-UP RING (TYP)

NEOPRENE FULL FACE

FLANGE GASKET

HDPE OR SS PIPE

FLANGE CONNECTION2

REFERENCE SHEET: M-102NTS

LFG TIE-IN WITH TEE

HDPE LFG HEADER

HDPE MOLDED TEE

HDPE LFG PIPE

NOTES:

1. ELECTROFUSION COUPLERS SHALL NOT

BE USED UNLESS PRE-APPROVED BY

OWNER AND ENGINEER.

PIPE

GROUND

SURFACE

SOIL MOUND

NOTES:

1. SOIL MOUNDING TO BE PLACED EVERY 25 FEET AT MINIMUM.

2. MOUND SHALL EXTEND A MINIMUM OF ONE FOOT ABOVE TOP OF

PIPE AND THREE FEET WIDTH AND COMPLETED USING CLEAN

SOIL.

NTS REFERENCE SHEET: M-101, M-102

4 SOIL MOUNDING FOR ABOVE GRADE PIPE STABILIZATION

PROVIDE A MINIMUM OF 1' OF COVER

OVER THE PIPE, WITH A MINIMUM

COVERAGE LENGTH OF 3' ALONG THE

PIPE

HDPE OR SS PIPE

NTS REFERENCE SHEET: C-101, M-102

5 BURIED PIPE TRENCH

OPAL LFGTE

FACILITY

"Ø

H D

PE

S

D R

-1

FLR-1

EXISTING

TEMPORARY FLARE

" S

D R

-1

H D

PE

AIR

EXHAUST & AIR

3/4" DRAIN HOLES

NC

TYP

1/4"

8"SS101/2"SS

3/ 8"

SS

T

P

S

FLR-2

1/4"SSTSE-301

3/4"SS

1/4"SS

H

0-100" WC

1/2"SS

8"SS10

0-250°F

1/2"SS

3/ 8"

SS

T

0-60"

WC

NC

1/4"SS

K TYPEFT-301

8"SS108"SS10

7,200

SCFM MAX

50 HP

SCFM AIR

1/4"SS3/4"SS

1/4"

BLR-401

FT-401

0-8,000

SP:

0.50" WC

~24"x34"

0-5" WC

4"SS

FLT-301

BLR-301

M M

12" CLEAN-OUT

PDI

LS

M

HV-301

FCV-301 FCV-302 FCV-303

HV-213 HV-214 HV-215

HV-302 HV-303 HV-304

HVP-304HVP-305

HVP-307

HVP-306

6" S

S1

0 8" SS10

1/2" SST

TK-101/

TK-101TK-102

FCV-704

FCV-705

FCV-706

CMP-2

1/ 2"

S C

H

BI

BLR-302 BLR-303

FX-301 FX-304 FX-302 FX-305 FX-303 FX-306

6" S

S1

6" S

S1

2" S

S1

1/ 2"

S S

1/ 2"

S S

1/ 2"

S S

1/ 2"

S S

2"x1/2" 2"x1/2" 2"x1/2" 2"x1/2" 2"x1/2" 2"x1/2"

G/H

TI

TE

PT

HVP

FLTP

HVP

PT

FT

TE

HVP

FCV

FLTP

HVP

PI

HVP

FLTP

ZS

FV

FLTP

HV

BE

BG

BG

FT

M1

PS

PI

BLR

TE

TE

TE

BE

BG

FCV

BG

BG

BG

BG

AP

FCV

AP

AP

AP

TE

BG

BNR-2

IGN

PS

FX

FV

FLT-301 BLR-401

PROPOSED COMBUSTION

AIR BLOWER

MFR: INDUSTRIAL AIR TECH.

MODEL: BCHS, 227

FLOW RATE: 7,200 SCFM

SHAFT: 1045 (STANDARD)

STAINLESS STEEL DRAIN

50 HP 3550 RPM 460 V 3 PH

PROPOSED FUEL FILTER/MOISTURE SEPARATOR

MFR: PEI

MATERIAL: SS

NOZZLE SIZE: 10" INLET, 8" OUTLET

99% REMOVAL OF 6 MICRON OR LARGER

PROPOSED FLAME

ARRESTER

MFR: ENARDO

TYPE: ECCENTRIC

CONNECTION: 8" FLANGE

MATERIAL: ALUMINUM

HOUSING AND SS ELEMENT

DRAIN/PRESSURE PORTS

FLR-2

PROPOSED FLARE

MFR: PEI

SIZE: 33 MMBTU/h

FLOW: 1,000 SCFM MAX.

(30% TO 55% CH4)

FT-401

PROPOSED THERMAL MASS FLOW

METER/TRANSMITTERS

MFR: KURZ

MODEL: 756053

TYPE: INTEGRAL

POWER: 24VDC

OUTPUT: 4-20mA

FLOW: 0-8000 SCFM

BLR-301/302/303

PROPOSED CENTRIFUGAL BLOWER

MFR: CONTINENTAL

MODEL:031A-06

MOTOR: 40 HP TEFC, 3600 RPM PER

BLOWER (3 TOTAL)

TK-101/102

PROPANE BOTTLES

2 PROPOSED

SIZE: 40 LB (10 GALLON)

CMP-801

PROPOSED AIR COMPRESSOR

MFR: ATLAS COPCO

MODEL: GA 22

SIZE: 30 HP

134 CFM @125 PSIG

TSE-301

G

FT-301

PROPOSED THERMAL MASS FLOW

METER/TRANSMITTERS

MFR: KURZ

MODEL: 756410

TYPE: INTEGRAL

POWER: 24VDC

OUTPUT: 4-20mA

FLOW: 0-1500 SCFM

TO EXISTING PIPE

TO EXISTING SUMP

INCOMING LFG

FROM WELLFIELD

1/4" SS

1/4" SS

0-10" WC

G

1/4" SS 2"x1/4"

6" S

S1

8"x6" 8"x6" 8"x6"

TO EXISTING AIRLINE

AND WELLFIELD

HV-701

50/ 50

CH4/CO2

0-1500 SCFM

DRY-801

DRY-801/FLT-801

MANUFACTURER: ATLAS COPCO

DRYER: FX-61N

FILTER: UD-110+

SIZE: 400 GAL

8"x6"8"x6"8"x6"

HV-702

FCV-304

Fi le

: X :\P

R O

JE

C

TS

\S

AN

TA

C R

U Z\

7-

-4

- S an ta

C ru z Lo w -N

O x

Fl ar e\ Pr oj ec t D ra w in gs \1

-2

4-

_M

1_

PR

O C

ES

S

FL

O

W .d w g

L ay ou t:

M -6

U se r:

C H

EL

SE

A.

EV

AN

S

Ja n

, 2

- 5 :5

9p m

IS

S

U E

D F

O R

B

ID

D

IN

G

N O

T F

O R

C O

N S

T R

U C

T

IO

N

01-28-2026

REV REVISION DESCRIPTION

DESIGNED BY : LCM

DRAWN BY : GSW

DATE :

CITY OF SANTA CRUZ PUBLIC WORKS DEPARTMENT

DATE

SHEET

CHECKED BY : CME

APPROVED BY : PJS

SANTA CRUZ RRF

ENCLOSED FLARE STATION INSTALLATION PROJECT

D-601PIPING AND INSTRUMENTATION DIAGRAM

FCV-701 FCV-702 FCV-703

1/ 2"

S S

1/ 2"

S S

L

H

LI-701

8" SS10

8" SS10

HVP-301

HVP-302

HVP-303

PT

1/ 4"

S S

3/4" SS

3/8" SST

3/8" SST

PDI

0-100" WC

L

LFLTP

FLTP

BG

BG

BG

BG

STP: 14.7 PSIA,

60 °F

S

C

FH

P R

O

PA

N E

,0

B

TU

/H

R

PS

FX

HVP

HVP

HVP

PT

HVP

1/4"SS

FLTP

NOx 0.025 LB/MMBTU

CO 0.06 LB/MMBTU

≥ 98% DRE NMOC'S

≥ 98% DRE NMOC'S

2"-4# INSULATION

2"-8#

HVP

HNC

0-80" WC

HVP

HVP

PS

1/4"SS

FX

FX

FX

FX

HVP

HVP

PCV

PI

1/4"SS

0-30 PSI

SP:15 PSI

HV

PCV

102PI

FV

FV

102S

S

0-6 PSI 1/2"SS

4" X2

" H D

PE

S

D R

-1

2" SS10

1" H

D

PE

S D

R -9

FLR-1

TEMPORARY FLARE

FLOW: 2,100 SCFM AT 50% CH4 MAX.

BLOWER (1 TOTAL)

BLOWER FLOW: 1,350 SCFM

10" SS10

" S

D R

-1

H D

PE

STRUCTURAL NOTES

THESE NOTES SHALL APPLY UNLESS SHOWN/INDICATED OTHERWISE ELSEWHERE IN THE STRUCTURAL DRAWINGS.

GENERAL

1. ALL MATERIALS AND CONSTRUCTION SHALL CONFORM TO THE 2022 EDITION OF THE CALIFORNIA BUILDING CODE (C.B.C.).

2. THE CONTRACTOR ACKNOWLEDGES RESPONSIBILITY FOR JOBSITE SAFETY AND ACKNOWLEDGES THAT THE ENGINEER WILL NOT HAVE SUCH RESPONSIBILITY. IF A LAWSUIT IS FILED BY ONE OF THE CONTRACTOR'S OR SUBCONTRACTOR'S EMPLOYEES, OR ANY ONE ELSE, THE CONTRACTOR WILL INDEMNIFY, DEFEND AND HOLD THE OWNER AND TETRA TECH, INC., THEIR PARENT AND SUBSIDIARY COMPANIES HARMLESS OF ANY AND ALL SUCH CLAIMS.

3. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS BEFORE STARTING WORK. SHOULD CONDITIONS EXIST WHICH ARE CONTRARY TO THOSE SHOWN ON PLANS, THE ENGINEER SHALL BE NOTIFIED IN WRITING BEFORE

PROCEEDING WITH WORK.

4. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE THAT ALL WORK IS ADEQUATELY BRACED AND SHORED DURING CONSTRUCTION. ALL BRACING/SHORING SHALL BE DESIGNED BY A REGISTERED ENGINEER HIRED BY THE

CONTRACTOR.

5. UNLESS DETAILED, SPECIFIED, OR INDICATED OTHERWISE, CONSTRUCTION SHALL BE AS INDICATED IN THE APPLICABLE TYPICAL DETAILS AND THESE GENERAL NOTES. TYPICAL DETAILS ARE MEANT TO APPLY EVEN THOUGH NOT REFERENCED AT

SPECIFIC LOCATIONS ON DRAWINGS WHERE THEY OCCUR.

6. THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE, WORKERS AND PEDESTRIANS DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, TEMPORARY STRUCTURES, AND PARTIALLY COMPLETED WORK, ETC. OBSERVATION VISITS TO THE SITE BY THE ENGINEER SHALL NOT BE CONSIDERED AS INSPECTION OF SUCH ITEMS.

7. DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON DRAWINGS.

8. ALL WORK SHALL CONFORM TO THE PLANS AND SPECIFICATIONS IN ALL RESPECTS AND SHALL BE SUBJECT TO APPROVAL BY

THE ENGINEER.

9. BY ACCEPTING THIS CONTRACT, CONTRACTOR HEREBY RELEASES AND AGREES TO INDEMNIFY, DEFEND, HOLD HARMLESS THE OWNER, ENGINEER, (HEREINAFTER TETRA TECH, INC.), THEIR PARENT AND SUBSIDIARY COMPANIES, AGENTS, EMPLOYEES, CONSULTANTS AND REPRESENTATIVES FOR ANY AND ALL DAMAGE TO PERSONS OR PROPERTY OR WRONGFUL DEATH REGARDLESS OF WHETHER OR NOT SUCH CLAIM, DAMAGE, LOSS OR EXPENSE IS CAUSED IN WHOLE OR IN PART BY THE NEGLIGENCE, ACTIVE OR PASSIVE, OF OWNER, ENGINEER, THEIR PARENT AND SUBSIDIARY COMPANIES AS WELL AS THEIR AGENTS AND EMPLOYEES, TO THE FULLEST EXTENT PERMITTED BY LAW. SUCH INDEMNIFICATION SHALL EXTEND TO ALL CLAIMS, DEMANDS, ACTIONS, OR LIABILITY FOR INJURIES, DEATH OR DAMAGES OCCURRING AFTER COMPLETION OF THE PROJECT, AS WELL AS DURING THE WORK'S PROGRESS. CONTRACTOR FURTHER AGREES THAT IT SHALL ACCOMPLISH THE ABOVE AT ITS OWN COST, EXPENSE AND RISK EXCLUSIVE OF AND REGARDLESS OF ANY APPLICABLE INSURANCE POLICY OR

POSITION TAKEN BY ANY INSURANCE COMPANY REGARDING COVERAGE.

10.CONTRACTOR SHALL VERIFY LOCATION OF ALL SITE UTILITIES PRIOR TO STARTING WORK, BOTH ABOVE GROUND AND BELOW GROUND, WHICH MAY BE IMPACTED BY THE WORK SHOWN ON THESE DRAWINGS. ANY CONFLICTS SHALL BE BROUGHT TO

THE ATTENTION OF THE ENGINEER.

11.CONTRACTOR SHALL DEFEND, INDEMNIFY AND HOLD THE CLIENT AND TETRA TECH, INC. THEIR PARENT AND SUBSIDIARY COMPANIES, ITS EMPLOYEES, OFFICERS, OR AGENTS, HARMLESS AGAINST ANY AND ALL CLAIMS BY ANY PARTIES ARISING FROM, OR RELATED TO, ANY AND ALL DAMAGES, INCLUDING LEGAL COSTS AND ATTORNEY'S FEES, RESULTING FROM INTERFERENCE WITH, INTERRUPTION OF, DAMAGE TO, OR ANY AND ALL INJURIES WHICH RESULT FROM DAMAGE CAUSED TO SUBSURFACE INSTALLATION, WHICH IS UNFORESEEN AND DESPITE ENGINEER'S EFFORT DURING THE DESIGN PROCESS WAS NOT LOCATED, EXCEPTING ONLY THE GROSS NEGLIGENCE OR WILLFUL MISCONDUCT OF ENGINEER IN PROVIDING ITS

SERVICES.

12. ALL ITEMS SHOWN ON THESE PLANS ARE NEW UNLESS NOTED (E), EXIST. OR EXISTING.

REINFORCING NOTES

1. REINFORCEMENT FOR CONCRETE SHALL BE DEFORMED BARS CONFORMING TO A.S.T.M. SPECIFICATION A615. GRADE 60 .

WELDED REINFORCEMENT SHALL CONFORM TO ASTM A706 OR EQUAL.

2. ALL REINFORCEMENT, ANCHOR BOLTS, AND OTHER ANCHORAGES PLACED IN CONCRETE SHALL BE ACCURATELY PLACED AND POSITIVELY SECURED AND SUPPORTED BY CONCRETE BLOCKS, METAL CHAIRS, SPACERS, OR METAL HANGERS, AND SHALL BE IN POSITION BEFORE CONCRETE PLACING OR GROUTING IS BEGUN. DETAILING AND PLACING OF BARS SHALL

CONFORM TO THE A.C.I. MANUAL OF STANDARD PRACTICES.

3. BARS SPECIFIED AS "CONTINUOUS" SHALL EXTEND THE FULL LENGTH OF THE MEMBER CONTAINING THEM AND MAY BE SPLICED (UNLESS NOTED OR SHOWN WITHOUT SPLICES ON THE PLANS). IN CONCRETE, PROVIDE LAPS PER TYPICAL DETAILS.

STAGGER ALL SPLICES.

4. DOWELS SHALL BE PROVIDED AT ALL POUR JOINTS AND SHALL BE THE SAME SIZE AND SPACING AS REINFORCING DIRECTLY

BEYOND POUR JOINTS.

5. WELDING OF REINFORCING STEEL, METAL INSERTS AND CONNECTIONS IN REINFORCED CONCRETE OR MASONRY CONSTRUCTION SHALL CONFORM TO ANSI/AWS D1.4-11. USE LOW HYDROGEN E-70 SERIES ELECTRODES FOR WELDING OF REINFORCING BARS. CONTINUOUS INSPECTION IS REQUIRED OF ALL FIELD WELDING IN ACCORDANCE WITH C.B.C. CHAPTER 17.

6. THE SPECIFIED DIMENSIONS OF THE VERTICAL LEGS OF "L" DOWELS, WHOSE HORIZONTAL LEGS ARE CAST INTO A FOOTING OR SLAB CAST ON TOP OF EARTH, ARE BASED UPON THE SLAB THICKNESS AS SHOWN ON THE DRAWINGS. IF A SLAB IS POURED THICKER THAN SHOWN ON THE DRAWINGS, SUCH AS FOR THE SUBGRADE OCCURRING AT A LOWER ELEVATION THAN SHOWN, THE VERTICAL LEGS MUST BE FABRICATED TO A LONGER LENGTH OR THE HORIZONTAL TAILS MUST BE SUPPORTED ABOVE SUBGRADE HIGH ENOUGH TO PROVIDE THE SAME AMOUNT OF LAP LENGTH BETWEEN THE DOWEL AND

THE WALL VERTICAL REINFORCING.

CONCRETE NOTES

1. ALL CONCRETE SHALL BE IN ACCORDANCE WITH ACI 318-19 AND SHALL HAVE A MINIMUM ULTIMATE COMPRESSIVE STRENGTH OF 4000 PSI AT 28 DAYS, UNLESS OTHERWISE NOTED ON THESE DRAWINGS OR IN THE PROJECT SPECIFICATIONS.

AGGREGATES SHALL CONFORM TO A.S.T.M. C33. AGGREGATES FOR LIGHTWEIGHT CONCRETE SHALL CONFORM TO A.S.T.M.

C330.

2. CEMENT FOR CONCRETE SHALL BE TYPE II OR TYPE V PORTLAND CEMENT CONFORMING TO A.S.T.M. C150.

3. CONCRETE COVER FOR REINFORCING BARS SHALL BE:

CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH = 3"

EXPOSED TO EARTH OR WEATHER: NO. 6 THROUGH NO. 18 BARS = 2"

NO. 5 BARS AND SMALLER = 1 1/2"

4. DRYPACK SHALL BE 1 PART CEMENT AND 3 PARTS SAND (BY VOLUME).

5. NO PIPES OR DUCTS SHALL BE PLACED IN STRUCTURAL CONCRETE UNLESS SPECIFICALLY DETAILED. SEE MECHANICAL, PROCESS AND/OR ELECTRICAL DRAWINGS FOR LOCATION OF SLEEVES THROUGH WALLS AND FLOORS.

6. THE LOCATION OF ALL CONSTRUCTION JOINTS NOT SPECIFICALLY NOTED OR SHOWN SHALL BE APPROVED BY THE

STRUCTURAL ENGINEER.

7. "ROUGHENED SURFACES", WHERE SPECIFIED ON THE DRAWINGS, SHALL BE MECHANICALLY ROUGHENED SUCH THAT A 1/4" AMPLITUDE (±) IS ACHIEVED BETWEEN HIGH AND LOW SPOTS OF THE ROUGHENED SURFACE. THE SURFACE SHALL BE CLEAN

AND FREE OF LAITANCE.

8. BOTH FACES OF CONCRETE WALLS, EDGES OF CONCRETE FOUNDATIONS, AND OTHER FORMED CONCRETE SURFACES WHERE THE SPECIFIED CONCRETE COVER IS 2 INCHES, SHALL BE PLACED AGAINST FORMWORK WHICH COMPLIES WITH THE PROJECT SPECIFICATIONS. CONCRETE FOR THESE ELEMENTS SHALL NOT BE CAST AGAINST EARTH.

9. IF NOT SPECIFIED ON DRAWINGS, ALL JOINTS SHOWN ON STRUCTURAL DRAWINGS SHALL BE ROUGHENED. SEE NOTE 7 FOR

MORE INFORMATION.

10. PROVIDE 3/4" CHAMFER AT ALL EXPOSED CONCRETE CORNERS.

STRUCTURAL STEEL NOTES

1. ALL WIDE FLANGE MEMBERS, CHANNELS, AND ANGLES SHALL BE IN ACCORDANCE WITH A.S.T.M. A-992. ALL OTHER STRUCTURAL AND MISCELLANEOUS STEEL SHALL BE ASTM A36 UNLESS NOTED OTHERWISE. STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH THE AISC SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS. SPECIAL INSPECTION SHALL BE PROVIDED FOR ALL STRUCTURAL STEEL IN ACCORDANCE WITH CBC SECTION 1705.2.1, UNLESS FABRICATION IS PERFORMED ON THE PREMISES OF A FABRICATOR REGISTERED AND APPROVED TO PERFORM SUCH WORK WITHOUT SPECIAL INSPECTION, IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS AND SECTION 1704.2.5.1 OF THE 2019 CBC. AT THE COMPLETION OF FABRICATION, THE APPROVED FABRICATOR SHALL SUBMIT A CERTIFICATE OF COMPLIANCE TO THE CITY BUILDING OFFICIAL (OR OWNER IF THE PROJECT IS NOT UNDER THE JURISDICTION OF A BUILDING DEPARTMENT) AND TO THE ENGINEER STATING THAT THE WORK WAS

PERFORMED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.

2. HSS STEEL RECTANGULAR AND ROUND SHALL CONFORM TO A.S.T.M. A500, GRADE C OR BETTER, UNLESS NOTED

OTHERWISE.

3. STEEL PIPES SHALL CONFORM TO A.S.T.M. A53 GR. B.

4. BOLTS SHALL CONFORM TO A.S.T.M. F3125 GR. A325 OR BETTER, UNLESS NOTED OTHERWISE.

5. HOLES FOR BOLTS IN STEEL SHALL BE OF SAME DIAMETER AS BOLT +1/16" MAXIMUM.

6. ALL WELDING SHALL BE PERFORMED BY A CERTIFIED WELDER IN A FABRICATION SHOP REGISTERED AND APPROVED IN ACCORDANCE WITH NOTE 1 ABOVE. CONTINUOUS INSPECTION IS REQUIRED OF ALL FIELD WELDING IN ACCORDANCE WITH

AWS D1.1.

7. NO STRUCTURAL STEEL MEMBER SHALL BE CUT FOR PIPES, DUCTS, ETC. UNLESS SPECIFICALLY DETAILED AND APPROVED

BY STRUCTURAL ENGINEER.

8. STAINLESS STEEL SHALL CONFORM TO A.S.T.M. A276/A.I.S.I. 316. STAINLESS STEEL BOLTS SHALL CONFORM TO A.S.T.M. F593.

STAINLESS STEEL NUTS SHALL CONFORM TO A.S.T.M. F594.

9. WELDING OF STAINLESS STEEL SHALL CONFORM TO STRUCTURAL WELDING CODE - STAINLESS STEEL, ANSI/AWS D1.6-07.

10. WHERE SPECIFIED, USE OF HIGH-STRENGTH BOLTS SHALL CONFORM TO THE PROVISIONS OF THE "SPECIFICATION FOR STRUCTURAL JOINTS USING A.S.T.M. A325 OR A490 BOLTS" APPROVED BY THE RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS OF THE ENGINEERING FOUNDATION (RCSC). SPECIAL INSPECTION OF HIGH-STRENGTH BOLT CONNECTIONS IS

REQUIRED.

11. ALL NON-STAINLESS STEEL EXPOSED TO WEATHER SHALL BE HOT-DIP GALVANIZED IN ACCORDANCE WITH ASTM A123 OR A153, AS APPLICABLE. REPAIR OF DAMAGED GALVANIZED COATING SHALL BE IN ACCORDANCE WITH ASTM A780. ALL OTHER

NON-STAINLESS STEEL SHALL BE COATED WITH TWO COATS OF SHOP APPLIED PRIMER

12. WELDING EQUIPMENT SHALL BE CHECKED PRIOR TO WELDING AS REQUIRED BY AISC 360-16 TABLE N5.4-1.

POST-INSTALLED ANCHORS (HILTI)

1. ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST ICC REPORT.

2. SPECIAL INSPECTION SHALL BE PROVIDED DURING ANCHOR INSTALLATION. SEE SHEET S-002.

3. ALTERNATIVE ANCHOR PRODUCT MAY BE SUBMITTED TO THE ENGINEER FOR APPROVAL, PROVIDED THAT IT HAS A CURRENT

I.C.C. EVALUATION REPORT APPROVAL.

4. ALL ABANDONED HOLES SHALL BE FILLED WITH A DRYPACK GROUT A MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 5,000 PSI.

THE FILLED HOLE(S) SHALL BE PREPARED AND CLEANED AS REQUIRED BY THE GROUT MANUFACTURER.

5. LOCATE EXISTING REINFORCING USING A NON-DESTRUCTIVE METHOD (PACHOMETER OR OTHER), PRIOR TO STEEL FABRICATION OF THE AFFECTED COMPONENTS AND PRIOR TO DRILLING HOLES FOR ANCHORS. MAINTAIN A MINIMUM CLEARANCE OF 1" BETWEEN THE REINFORCEMENT AND THE ANCHOR. NOTIFY ENGINEER IF ADHESIVE ANCHORS CANNOT BE INSTALLED DUE TO REBAR INTERFERENCE(S) SO STRUCTURAL STEEL DETAILING SHOWN HEREON CAN BE MODIFIED TO

ACCOMMODATE.

FLARE STACK AND AIR COMBUSTION BLOWER EQUIPMENT NOTES

1. ANCHORAGE FOR TRAILERS, CONTAINERS, TANKS AND EQUIPMENT NOT SPECIFICALLY DETAILED IN THESE DRAWINGS SHALL BE DESIGNED AND PROVIDED BY THE GENERAL CONTRACTOR OR THE TANK OR EQUIPMENT MANUFACTURER. THE CALCULATIONS AND SHOP DRAWINGS FOR THE ANCHORAGE SHALL BE SUBMITTED TO THE ENGINEER PRIOR TO FABRICATION. ALL CALCULATIONS AND ANCHORAGE SHOP DRAWINGS SHALL BE SIGNED, SEALED AND DATED BY A

REGISTERED CIVIL OR STRUCTURAL ENGINEER LICENSED IN THE STATE OF CALIFORNIA.

A. FLARE STACK

WEIGHT = 30,000 LBS

CENTER OF GRAVITY = 19' - 0 1/2" (FROM BOT OF BASE PLATE)

B. COMBUSTION AIR BLOWER

WEIGHT = 3,000 LBS

CENTER OF GRAVITY = 3'-6 1/2" (FROM BOT OF BASE PLATE)

C. BLOWER SKID (GAS HANDLING SYSTEM)

WEIGHT = 46,000 LBS

CENTER OF GRAVITY = 3'-3 9/16" (FROM BOT OF BASE PLATE)

D. COMPRESSOR SKID (GAS HANDLING SYSTEM)

WEIGHT = 2,500 LBS

CENTER OF GRAVITY = 2'-3" (FROM BOT OF BASE PLATE)

2. THE DESIGN OF ANY EQUIPMENT NOT SPECIFICALLY DETAILED SHALL BE DONE IN ACCORDANCE TO THE 2022 CALIFORNIA BUILDING CODE AND THE ASCE 7-16. TANKS OR EQUIPMENT MOUNTED TO A CONCRETE FOUNDATION SHALL BE DESIGNED AS A "NONBUILDING STRUCTURE" PER CHAPTER 15 OF ASCE 7-16. REFER TO DESIGN CRITERIA SECTION FOR

ADDITIONAL INFORMATION.

3. CAST-IN-PLACE SHALL MEET ALL OF THE REQUIREMENTS OF ACI 318-19 CHAPTER 17, INCLUDING SEISMIC LOADING AND DUCTILE FAILURE REQUIREMENTS FOR TANKS ONLY. THE EMBEDMENT OF ANCHORS IN CONCRETE SHALL BE AS MEASURED FROM THE TOP OF THE FOUNDATION. THE PORTION OF ANCHORS IN CONCRETE HOUSEKEEPING PADS, WHERE SUCH PADS OCCUR, SHALL NOT BE INCLUDED IN THE EMBEDMENT OF THE ANCHORS.

4. CAST-IN-PLACE ANCHORS SHALL BE H.D.G. STEEL CAST-IN-PLACE ANCHOR BOLTS OR POST-INSTALLED ADHESIVE ANCHORS. EXPANSION ANCHORS MAY NOT BE USED FOR TANK ANCHORAGE TO CONCRETE.

DESIGN CRITERIA

DESIGN CODES AND REFERENCES:

- 2022 CALIFORNIA BUILDING CODE

- ASCE 7-16, MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS AND OTHER STRUCTURES

- AISC SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS 15TH EDITION

- ACI 318-19, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE

SEISMIC DESIGN PARAMETERS:

LOCATION: LAT.: 36.989126, LONG.: -122.100983

SITE CLASS: C

SEISMIC DESIGN CATEGORY: D

Fa = 1.20 Fv = 1.40 Ss = 1.650 S1 = 0.625 Sds = 1.320 Sd1 = 0.583

FLARE STACK:

R = 2 (STEEL CHIMNEYS AND STACKS, ASCE 7-16 TABLE 15.4-2)

Ω = 2

RISK CATEGORY = II

Ie = 1.0 Cs = 0.47

COMBUSTION AIR BLOWER:

R = 1.25 (ALL OTHER SELF-SUPPORTING STRUCTURES, TANKS, AND VESSELS, ASCE 7-16 TABLE 15.4-2) Ω = 2.00

RISK CATEGORY = II

Ie = 1.0 Cs = 1.06

BLOWER SKID (GAS HANDLING SYSTEM) AND COMPRESSOR SKID:

R = 1.25 (ALL OTHER SELF-SUPPORTING STRUCTURES, ASCE 7-16, TABLE 15.4-2)

Ω = 2.00 Ie = 1.0 Cs = 1.06

PIPE SUPPORTS:

R = 1.25(ALL OTHER SELF-SUPPORTING STRUCTURES, ASCE 7-16, TABLE 15.4-2)

Ω = 2.00 Ie = 1.00 Cs = 1.06

WIND LOAD DESIGN PARAMETERS:

RISK CATEGORY = II

ULTIMATE DESIGN WIND SPEED = 92 MPH

EXPOSURE CATEGORY = C

SOIL DESIGN PARAMETERS: (GEOTECH REPORT #BAS 23-212E: "NEW FLARE STATION BY TETRA TECH, DATED DECEMBER 4, 2024)

(i) MAT FOUNDATIONS

ALLOWABLE BEARING CAPACITY (NET): 1,200 PSF (1/3 INCREASE FOR TRANSIENT LOADS)

COEFFICIENT OF FRICTION: 0.3

UNIT MODULES OF SUBGRADE REACTION: 200 PCI (TO BE ADJUSTED BASED ON MAT SIZE)

PASSIVE RESISTANCE: (NEGLECT UPPER 12 INCHES) 180 PSF/FT (1/3 INCREASE FOR TRANSIENT LOADS)

(ii) RETAINING WALL AND FOUNDATIONS

ALLOWABLE BEARING CAPACITY (NET): 2,500 PSF (1/3 INCREASE FOR TRANSIENT LOADS)

COEFFICIENT OF FRICTION: 0.3

PASSIVE RESISTANCE: (NEGLECT UPPER 12 INCHES) 180 PSF/FT (1/3 INCREASE FOR TRANSIENT LOADS) LATERAL ACTIVE PRESSURE: 59z + 0.47 x Q

(iii) EMBEDDED POSTS AND PIPE SUPPORTS

ALLOWABLE BEARING CAPACITY (NET): 1,500 SF

PASSIVE RESISTANCE: (NEGLECT UPPER 12 INCHES) 150 PSF/FT

300 PFS/FT (FOUND NOT AFFECTED BY 0.5" MOVEMENT)

ANCHOR BOLT

AMERICAN CONCRETE

INSTITUTION

AMERICAN INSTITUTE OF

STEEL CONSTRUCTION

ARCHITECT

AMERICAN SOCIETY FOR

TESTING AND MATERIALS

AMERICAN WELDING

SOCIETY

BOTTOM

CALIFORNIA BUILDING

CODE

CAST-IN-DRILLED HOLE

PILE

CONSTRUCTION JOINT

CLEAR

CONCRETE

CONSTRUCTION

CONTINUOUS

CONCRETE REINFORCING

STEEL INSTITUTE

DIAMETER

EXISTING

EACH

EACH FACE

ELEVATION

ELEVATION

EQUAL

EACH WAY

EXISTING

FOUNDATION

FINISH FLOOR

FINISH GRADE

GAUGE

GALVANIZED

GENERAL CONTRACTOR

GENERAL

HIGH

HOT DIP GALVANIZED

HORIZONTAL

HOLLOW STEEL SECTION

HEIGHT

INTERNATIONAL CODE

COUNCIL

INVERT

KIPS

KIPS PER SQUARE INCH

MAXIMUM

MECHANICAL

MANUFACTURER

MINIMUM

NUMBER

NOT TO SCALE

ON CENTER

POUNDS PER CUBIC FOOT

POUNDS PER SQUARE

FOOT

POUNDS PER SQUARE

INCH

REINFORCING

REQUIRED

SQUARE FEET

SIMILAR

SPECIFICATIONS

SHEET METAL SCREW

SQUARE

STRUCTURAL

TOP OF

TOP OF FOOTING

TOP OF STEEL

TYPICAL

UNLESS NOTED

OTHERWISE

VERTICAL

WIDE

WITH

WIDE FLANGE

WORKING POINT

AT

AND

NUMBER

A.B.

A.C.I.

A.I.S.C.

ARCH.

A.S.T.M.

A.W.S.

BTM.

C.B.C.

CIDH

C/J

CLR.

CONC.

CONST.

CONT.

C.R.S.I.

DIA.

(E)

EA.

E.F.

EL.

ELEV.

EQ.

E.W.

EXIST.

FDN.

F.F.

F.G.

GA.

GALV.

G.C.

GEN.

H H.D.G.

HORIZ.

HSS

HT.

ICC

INV

K

KSI

MAX.

MECH.

MFR.

MIN.

No.

N.T.S.

O.C.

PCF

PSF

PSI

REINF.

REQ'D.

SF

SIM.

SPECS.

S.M.S.

SQ.

STRUCT.

T.O.

T.O.F.

T.O.S.

TYP.

U.N.O.

VERT.

W w/

WF

W.P.

STRUCTURAL ABBREVIATIONS

S-001STRUCTURAL NOTES

Fi Oe

: X :?P

R O

JE

C

TS

?S

AN

TA

C R

U Z?

7-

-4

- S aQ Wa

C

UX

z Lo w -N

O x

FO

aU e?

PU

oM eF

W D Ua w iQ

Js ?1

-2

4-

BS

1B

ST

R U

C

TU

R

AL

N O

TE

S.

dw J

L a\ oX W:

S-

U se U:

C H

EL

SE

A.

EV

AN

S

Ja Q

, 2

- 5 :5

9S P

IS

S

U E

D F

O R

B

ID

D

IN

G

N O

T F

O R

C O

N S

T R

U C

T

IO

N

01-28-2026

REV REVISION DESCRIPTION

DESIGNED BY : LCM

DRAWN BY : GSW

DATE :

CITY OF SANTA CRUZ PUBLIC WORKS DEPARTMENT

DATE

SHEET

CHECKED BY : CME

APPROVED BY : PJS

SANTA CRUZ RRF

ENCLOSED FLARE STATION INSTALLATION PROJECT

MJB

STEEL CONSTRUCTION (STRUCTURAL STEEL):

P - INSPECT THESE ITEMS ON A PERIODIC BASIS. OPERATIONS NEED NOT BE DELAYED PENDING

THESE INSPECTIONS

C - INSPECT THESE ITEMS ON A CONTINUOUS BASIS

1. INSPECTION TASKS PRIOR TO WELDING

A. WELDER QUALIFICATION RECORDS AND CONTINUITY RECORDS

B. WELDING PROCEDURE SPECIFICATIONS (WPSs) AVAILABLE

C. MANUFACTURERS CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE

D. MATERIAL IDENTIFICATION (TYPE/GRADE)

E. WELDER IDENTIFICATION SYSTEM

F. FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY)

- JOINT PREPARATION

- DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL)

- CLEANLINESS (CONDITION OF STEEL SURFACES)

- TACKING (TACK WELD QUALITY AND LOCATION)

- BACKING TYPE AND FIT (IF APPLICABLE)

G. FIT-UP OF CJP GROOVE WELDS OF HSS T-, Y- AND K- JOINTS WITHOUT BACKING

(INCLUDING JOINT GEOMETRY)

- JOINT PREPARATIONS

- DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL)

- CLEANLINESS (CONDITION OF STEEL SURFACES)

- TACKING (TACK WELD QUALITY AND LOCATION)

H. CONFIGURATION AND FINISH OF ACCESS HOLES

I. FIT-UP OF FILLET WELDS

- DIMENSIONS (ALIGNMENT, GAPS AT ROOT)

- CLEANLINESS (CONDITION OF STEEL SURFACES)

- TACKING (TACK WELD QUALITY AND LOCATION)

2. INSPECTION TASKS DURING WELDING

A. CONTROL AND HANDLING OF WELDING CONSUMABLES

- PACKAGING

- EXPOSURE CONTROL

B. NO WELDING OVER CRACKED TACK WELDS

C. ENVIRONMENTAL CONDITIONS

- WIND SPEED WITHIN LIMITS

- PRECIPITATION AND TEMPERATURE

D. WPS FOLLOWED

- SETTINGS ON WELDING EQUIPMENT

- TRAVEL SPEED

- SELECTED WELDING MATERIALS

- SHIELDING GAS TYPE/FLOW RATE

- PREHEAT APPLIED

- INTERPASS TEMPERATURE MAINTAINED (MIN./MAX.)

- PROPER POSITION (F, V, H, OH)

E. WELDING TECHNIQUES

- INTERPASS AND FINAL CLEANING

- EACH PASS WITHIN PROFILE LIMITATIONS

- EACH PASS MEETS QUALITY REQUIREMENTS

F. PLACEMENT AND INSTALLATION OF STEEL HEADED STUD ANCHORS

3. INSPECTION TASKS AFTER WELDING

A. WELDS CLEANED

B. SIZE, LENGTH AND LOCATION OF WELDS

C. WELDS MEET VISUAL ACCEPTANCE CRITERIA

- CRACK PROHIBITION

- WELD/BASE-METAL FUSION

- CRATER CROSS SECTION

- WELD PROFILES

- WELD SIZE

- UNDERCUT

- POROSITY

D. ARC STRIKES

E. K-AREA

- WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES OR STIFFENERS

HAS BEEN PERFORMED IN THE K-AREA, VISUALLY INSPECT THE WEB K-AREA

FOR CRACKS WITHIN 3 IN. (75 MM) OF THE WELD

F. WELD ACCESS HOLES IN ROLLED HEAVY SHAPES AND BUILT-UP HEAVY SHAPES

- AFTER ROLLED HEAVY SHAPES (SEE AISC SECTION A3.1C) AND BUILT-UP SHAPES

(SEE AISC SECTION A3.1D) ARE WELDED, VISUALLY INSPECT THE WELD ACCESS

HOLE FOR CRACKS

G. BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED)

H. REPAIR ACTIVITIES

I. DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR MEMBER

J. NO PROHIBITED WELDS HAVE BEEN ADDED WITHOUT THE APPROVAL OF THE EOR

SPECIAL INSPECTIONS

REQUIRED ( YES NO)

P C N/A

CONCRETE CONSTRUCTION:

1. INSPECT REINFORCMENT, INCLUDING PRESTRESSING

TENDONS, AND PLACEMENT

2. REINFORCING BAR WELDING:

A. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM A706

B. INSPECT SINGLE-PASS FILLET WELD, MAXIMUM 5/16"; AND

C. INSPECT ALL OTHER WELDS.

3. INSPECTION OF ANCHORS CAST IN CONCRETE.

4. INSPECTION OF ANCHORS POST-INSTALLED IN HARDENED CONCRETE MEMBERS

A. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY…