SC-0510 Rehab of Sewer Lift Stations - Final Plans.pdf

PDF 20 MB Posted

Attached to
Rehabilitation of Sewer Lift Stations S-19, S-28 and S-29 Project
Solicitation number
UD-26-350
Issued by
California

About this file

This is a comprehensive set of construction design drawings and specifications for the Long Beach Public Utilities Department in Long Beach, California, detailing the rehabilitation of three sewer lift stations: S-19 at 651 Queensway Drive, S-28 at 5751 Boathouse Lane, and S-29 at 1126 Queens Highway. The project (SC-0510, WD-08-26) is organized into multiple phases across four main construction stages: Phase 1 and 2A involve a 6-inch sewer lateral extension to the S-30 sewer lift station; Phase 2B and 3A cover replacement of a 10-inch sewer force main; Phase 3B addresses S-29 mechanical demolition; and Phase 4A and 4B involve comprehensive rehabilitation of S-19 and S-28 lift stations, including mechanical demolition, bypass assembly installation, and new equipment integration. The design was completed by JIG Consultants (318 W. Katella Avenue, Suite A, Orange, CA 92867) and submitted by Thomas Bekele, Senior Director of Engineering, with approval from General Manager B. Anatole Falagán. The drawing set includes 31 sheets covering title sheets, general notes, benchmark and location maps, civil details, mechanical details, electrical systems, PLC I/O diagrams, control panel elevations, and traffic control plans.

The project encompasses extensive mechanical and electrical improvements to replace and rehabilitate pumping equipment, control systems, and associated infrastructure at all three stations. Key mechanical components include new submersible pumps, pressure transducers, sump pumps, float switches, bypass assemblies, check valves, and isolation equipment. Electrical work involves installation of new RTU/pump control panels (NEMA 4X stainless steel enclosures), PLC-based automation systems with M340 controllers, multiple transformer enclosures rated at 37.5 KVA, manual transfer switches, circuit breakers, and comprehensive instrumentation including ultrasonic level transmitters and flow meters. The project includes provisions for optional use of existing panels to power new pumping equipment at S-28. Traffic control plans are provided for Queens Highway (S-29) and Queensway Drive (S-19) with speed limits of 15 and 30 mph respectively, including temporary railing, delineators, crash cushions, and pavement markings per California Manual on Uniform Traffic Control Devices standards. Construction is designed to occur in phased operations with provisions for temporary bypass systems to maintain lift station operations during rehabilitation activities.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LONG BEACH PUBLIC UTILITIES DEPARTMENT

LONG BEACH, CALIFORNIA

SUBMITTED BY:

THOMAS BEKELE

PROJECT MANAGER:

(EXPIRES: DECEMBER 31, 2026)

JOSEPH GUTIERREZ R.C.E. 55604 DATE

SENIOR DIRECTOR OF ENGINEERING

TITLE SHEET AND SHEET INDEX

SHEET INDEX

SHT # DWG # SHEET TITLE

1 G-01 TITLE SHEET AND SHEET INDEX

2 G-02 GENERAL NOTES, PUBLIC AGENCIES & UTILITIES, & UTILITY LEGEND

C-02

M-08

C-01 PHASE 1 AND 2A 6" SEWER LATERAL EXTENSION TO S-30 SEWER LIFT STATION PLAN & PROFILE

PHASE 2B AND 3A REPLACEMENT OF 10" SEWER FORCE MAIN PLAN & PROFILE

G-03 BENCHMARK, BASIS OF BEARINGS, AND LOCATION MAPS

PHASE 1A-3B

DIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004 6518010005

PHASE 4A S-19 MECHANICAL DEMOLITION PLAN & SECTION

PHASE 4B S-28 DEMOLITION SITE PLAN

M-01

PHASE 4A S-19 SEWER LIFT STATION BYPASS ASSEMBLY SITE PLAN, MECHANICAL PLAN, & SECTION

M-07

PHASE 4B S-28 SEWER LIFT STATION SITE PLAN, MECHANICAL PLAN, & SECTION

PHASE 4A S-19 SEWER LIFT STATION IMPROVEMENTS SITE PLAN, MECHANICAL PLAN, & SECTION

PHASE 4A

PHASE 4B12

PHASE 3B S-29 MECHANICAL DEMOLITION PLAN & SECTION

C-03 MISCELLANEOUS CIVIL DETAILS - 1

C-04 MISCELLANEOUS CIVIL DETAILS - 2

M-02

M-03

M-04

M-05

13 M-06

MECHANICAL DETAILS - 1

MECHANICAL DETAILS - 2

E-01 ELECTRICAL SYMBOLS AND NOTES

E-02

E-03

E-04

E-05

E-06

E-07

E-08

E-09

S-19 ELECTRICAL PLANS

S-28 ELECTRICAL PLANS

S-28 SINGLE LINE DIAGRAM AND SCHEDULES

S-28 CONTROL DIAGRAMS

S-28 PLC POWER AND COMMUNICATION DIAGRAM

S-28 CONTROL PANEL ELEVATIONS

RTU LAYOUT (INTERIOR)

S-19 & S-28 PLC I/0 DIAGRAMS

DATE

E-10

S-29 ELECTRICAL DEMOLITION PLAN

E-11

S-28 ELECTRICAL DETAILS

M-09 MECHANICAL DETAILS - 3

TC-01 TITLE SHEET

TC-02

QUEENS HIGHWAY AND QUEENSWAY DRIVE TRAFFIC CONTROL PLANS

M-10 MECHANICAL DETAILS - 4

E-12 OPTIONAL - USE OF EXISTING PANELS TO POWER NEW PUMPING EQUIPMENT

08/03/2026 wadepew Image wadepew Text Box 8/3/2026 wadepew Image wadepew Text Box 8/5/2026

GENERAL NOTES, PUBLIC AGENCIES & UTILITIES, &

UTILITY LEGENDDIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004 6518010005

08/03/2026 wadepew Image wadepew

BENCHMARK, BASIS OF BEARINGS, AND LOCATION MAPS

DIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004 6518010005

S-28 SEWER

LIFT STATION

PHASE 4B SITE

S-19 SEWER

LIFT STATION

PHASE 4A SITE

S-29 SEWER

LIFT STATION

PHASE 3B SITE

PHASE 1 & 2A SITE

PHASE 2B & 3A SITE

08/03/2026 wadepew Image wadepew

PHASE 1 AND 2A

6" SEWER LATERAL EXTENSION TO S-30 SEWER LIFT STATION

PLAN & PROFILEDIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004 6518010005

BEGIN CONSTRUCTION

END CONSTRUCTION

BEGIN CONSTRUCTION

END CONSTRUCTION

08/03/2026 wadepew Image wadepew

PHASE 2B AND 3A

REPLACEMENT OF 10" SEWER FORCE MAIN

PLAN & PROFILE

B

EG

IN

C

O N

ST

R

U C

TI

O

N

EN

D

C O

N

ST

R U

C

TI

O N

DIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004 6518010005

BEGIN CONSTRUCTION

END CONSTRUCTION

08/03/2026 wadepew Image wadepew

MISCELLANEOUS CIVIL DETAILS - 1

DIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004 6518010005

08/03/2026 wadepew Image wadepew

MISCELLANEOUS CIVIL DETAILS - 2

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004 6518010005

08/03/2026 wadepew Image wadepew

PHASE 4A

S-19 MECHANICAL DEMOLITION

PLAN & SECTIONDIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004 6518010005

08/03/2026 wadepew Image wadepew

PHASE 4A

S-19 SEWER LIFT STATION BYPASS ASSEMBLY

SITE PLAN, MECHANICAL PLAN, & SECTIONDIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004 6518010005

08/03/2026 wadepew Image wadepew

PHASE 4A

S-19 SEWER LIFT STATION IMPROVEMENTS

SITE PLAN, MECHANICAL PLAN, & SECTIONDIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004 6518010005

08/03/2026 wadepew Image wadepew

PHASE 4B

S-28 DEMOLITION SITE PLANDIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004 6518010005

08/03/2026 wadepew Image wadepew

PHASE 4B

S-28 SEWER LIFT STATION

SITE PLAN, MECHANICAL PLAN, & SECTIONDIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/28/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/28/26

6518010004 6518010005

08/03/2026 wadepew Image wadepew

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004 6518010005

PHASE 3B

S-29 MECHANICAL DEMOLITION

PLAN & SECTION

08/03/2026 wadepew Image wadepew

MECHANICAL DETAILS - 1

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004 6518010005

08/03/2026 wadepew Image wadepew

MECHANICAL DETAILS - 2

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004 6518010005

08/03/2026 wadepew Image wadepew

LEVEL SENSOR BRACKET

BASE CHANNEL LEG CHANNEL

SUPPORT CHANNEL

BRACKET ASSEMBLY

MOUNTING BRACKETS CHANNEL BRACKETS HARDWARE ASSEMBLY

PIVOT ASSEMBLY LOCKING ROD

WEDGE ANCHOR

DIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004

6518010005MECHANICAL DETAILS - 3

08/03/2026 wadepew Image wadepew

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/21/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

RJO

JOE G.

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT: 6518010003

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/21/26

6518010004

6518010005MECHANICAL DETAILS - 4

08/03/2026 wadepew Image wadepew

ABBREVIATIONS

GROUNDGRD

PA PUBLIC ADDRESS

UNDERGROUND PULL SECTION

VOLTAGE DROP

UNINTERRUPTABLE POWER SYSTEM

TRANSFORMER

VARIABLE AIR VOLUME

SHORT CIRCUIT CURRENT

TRANSIENT VOLTAGE SURGE

STRUCTURED CABLING SYSTEM

ROOT MEAN SQUARE

RECEPTACLE

WEATHERPROOF

UNLESS OTHERWISE NOTED

VOLT AMPERES

RIGID GALVANIZED STEEL

600 VOLTS AND LESS

TELEPHONE AND DATA

REFRIGERATOR

VD

U.P.S.

XFMR

VAV

VA

V

W

WP

VOLTS

WIRE

U.G.P.S.

SCC

T.V.S.S.

SCS

RMS

REF

RGS

SQ.

TV

TC

TEL/DATA

U.O.N.

TYP

REC, RECEPT

SECONDARY

SQUARE

TYPICAL

TELEVISION

TIMECLOCK

MERCURY VAPOR

POWER DISTRIBUTION UNIT

POLY VINYL CHLORIDE

PLUMBING CONTRACTOR

PERCENT IMPEDANCE

NOT TO SCALE

NATIONAL ELECTRICAL

MINIMUM CIRCUIT AMPS

MOTOR CIRCUIT PROTECTOR

NON AUTOMATIC DISCONNECT

MANUFACTURER

THOUSAND CIRCULAR MILS

MOTOR CONTROL CENTER

METAL HALIDE

POTENTIAL TRANSFORMER

FURNISH, INSTALL AND CONNECT.

OVER 600 VOLTS

NORMALLY OPENED

NORMALLY CLOSED

NOT IN CONTRACT

OWNER FURNISHED, CONTRACTOR

PDU

PVC

P.C.

%Z

N.T.S.

OFCI

NL

NO. or #

PC

PH. or Ø

PRIMARY

PT

PROVIDE

P POLE

NUMBER

PHASE

PHOTOCELL

NIGHT LIGHT

NEMA

MCA

MIN.

MCP

MCC

MCM

NEC

MTD

MW

MFR.

MH

NO

NC

NF

NIC

MOUNTED

MICROWAVE

NON-FUSED

MINIMUM

MECHANICAL CONTRACTOR

MAXIMUM OVERCURRENT PROTECTION

KILOWATT HOUR

GROUND FAULT CIRCUIT INTERRUPTER.

GROUND FAULT PROTECTION

GROUNDING ELECTRODE CONDUCTOR

HEATING AIR CONDITIONING

LONG CONTINUOUS LOAD

KILOVOLT AMPERES

HIGH PRESSURE SODIUM

ISOLATED GROUND

JUNCTION BOX

DEGREE KELVIN

HIGH INTENSITY DISCHARGE

HEIGHT, WIDTH, DEPTH, LENGTH

HAND-OFF-AUTO

HORSEPOWER

LOW PRESSURE SODIUM

MAIN CIRCUIT BREAKER

MAIN LUGS ONLY

HEATING, VENTILATING AND AIR

M.C.

MOCP

M/M M

KWH

L.F.

LCL

KW

KVA

LPS

MAX.

MCB

MV

MLO

LTG, LTS

MAXIMUM

METER MAIN

METER

LINEAR FEET

KILOWATT

LIGHTING

GFCI

GFP

GEC

HACR

HOA

HVAC

H.,W.,D.,L.

HPS

HP

HID

I/G

JBOX

K

IN. or '' INCHES

AVERAGEAVG

CURRENT TRANSFORMER

CURRENT LIMITING FUSE

CONTROL POWER TRANSFORMER

CONDUIT ONLY, COMPLETE WITH

CIRCUIT BREAKER

COMBINATION SMOKE FIRE DAMPER

CURRENT LIMITING CIRCUIT BREAKER

DISTRIBUTION

ENERGY MANAGEMENT CONTROL

ELECTRICAL METALLIC TUBING

ELECTRIC WATER COOLER

ELECTRICAL NON-METALLIC TUBING

ELECTRICAL CONTRACTOR

EMERGENCY POWER OFF

END-OF-LINE CIRCUIT TERMINATOR.

EQUIPMENT GROUND (GREEN)

EXISTING EQUIP. TO BE REOLCATED

FULL LOAD AMPS

EXHAUST FAN

DIST

EMS

EMT

ENT

EWC

E.C.

E.P.O.

E-O-L

E/G

ER*

FA

FLA

FT or '

EF

FEET

FIRE ALARM

C C.O.

BR

BLDG

CB

CIRC., CKT.

CSFD

DIA

CT

CLF

CPT

CLCB

DISC

CONN CONNECTED

DIAMETER

DISCONNECT

CONDUIT

BUILDING

CIRCUIT

BRANCH

AMERICAN WITH DISABILITIES ACT

4" SQUARE BY 2 1/8" DEEP BOX

ABOVE FINISH FLOOR

AMPERES INTERRUPTING CAPACITY

AMERICAN WIRE GAUGE

AMP FRAME, AMP TRIP

AMP SWITCH, AMP FUSE

AUTOMATIC TRANSFER SWITCH

ABOVE FINISH GRADE

A.F.F.

4S/DP

ADA

AS/AF

AF/AT

A.I.C.

AMP, A

AWG

ATS

A.F.G.

AMPERE

SFD SMOKE FIRE DAMPER

NATS

NATIONAL ELECTRICAL CODE

AUTHORITY HAVING JURISDICTIONAHJ

CEC CALIFORNIA ELECTRICAL CODE

INTERMEDIATE DISTRIBUTION FRAMEIDF

MAIN DISTRIBUTION FRAMEMDF

BDF BUILDING DISTRIBUTION FRAME

SHEET METAL & AIR COND.SMACNA

THOUSAND CIRCULAR MILSKCMIL

CONTRACTORS' NAT'L ASSOC.

(SYMMETRICAL)

CONDITIONING

MANUFACTURERS' ASSOCIATION

INSTALLED.

SUPPRESSION

PULLSTRING

SYSTEM

REFRIGERATION

EXISTING EQUIP. TO BE DEMO'DXX

N NEW EQUIP.

EXISTING EQUIP. TO REMAINE

EXPLOSION PROOFEP

(* CORRESPONDS TO NEW LOCATION)

NEW LOCATION FOR REOLCATED EQUIP.ERT*

(* CORRESPONDS TO PREVIOUS LOCATION)

DELTA CONFIGURATION

DETAIL CALLOUT, "3" INDICATES DETAIL NUMBER "E-1" INDICATES SHEET NUMBER.

UNIT NUMBER. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION AND

MECHANICAL EQUIPMENT CALLOUT, "AC" INDICATES UNIT TYPE AND "2" INDICATES

PLAN NOTE REFERENCE, REFER TO NOTES ON SHEET, OR AS DIRECTED.

ANNOTATIONS

GROUND

WYE CONFIGURATION

REVISION REFERENCE.

ELECTRICAL REQUIREMENTS.

A-1&3&5

A-1,3,5

A-1+3+5

FLEXIBLE CONNECTION AS REQUIRED. NUMBER OF CONDUCTORS AS REQUIRED. VERIFY CONNECTION

REQUIREMENTS WITH MANUFACTURER PRIOR TO ROUGH-IN.

CONDUIT STUB OUT, CAP, MARK AND RECORD ON AS-BUILT DRAWINGS

TANDEM WIRING CONNECTION.

CONDUIT CONTINUATION.

BRANCH CIRCUIT SYMBOLS

CONDUIT/ BRANCH CIRCUIT/FEEDER CONTINUATION DOWN WALL TO FLOOR BELOW

CONDUIT/ BRANCH CIRCUIT/FEEDER CONTINUATION UP WALL TO FLOOR ABOVE

HOME RUN TO PANEL. LETTER DESIGNATES PANEL, NUMBERS INDICATE CIRCUITS. HASH MARKS INDICATE

NUMBER OF CONDUCTORS IN CONDUIT RUN, #12 AWG MINIMUM UNLESS OTHERWISE NOTED.

HOME RUN TO PANEL. LETTER DESIGNATES PANEL, NUMBERS INDICATE CIRCUITS WITH SEPARATE

NEUTRALS. "&" INDICATES SEPARATE NEUTRALS.

HOME RUN TO PANEL. LETTER DESIGNATES PANEL, NUMBERS INDICATE CIRCUITS. "+" INDICATES SEPARATE #10 NEUTRAL THROUGHOUT BRANCH CIRCUIT. HASH MARK " " INDICATES AN ISOLATED GROUND

CONDUCTOR.

CONCEALED CONDUIT OR BRANCH CIRCUIT UNLESS OTHERWISE NOTED. 1/2" CONDUIT MINIMUM, (2) #12 AWG

CONDUCTORS MINIMUM

CONDUIT OR BRANCH CIRCUIT CONCEALED BELOW GRADE, 3/4" CONDUIT MINIMUM WITH (2) 12 AWG

CONDUCTORS MINIMUM AND A CODE SIZED EQUIPMENT GROUND.

E-1

EF

LIGHTING FIXTURE DESIGNATION

X

XXX-X

SURFACE-MOUNTED CONDUIT OR BRANCH CIRCUIT UNLESS OTHERWISE NOTED. 1/2" CONDUIT MINIMUM, (2) #12 AWG CONDUCTORS MINIMUM. CONDUIT SHALL BE PAINT TO MATCH ADJUCENT SURFACE. COORDINATE

COLOR WITH ARCHITECT/INTERIORS.

CONCEALED CONDUIT OR BRANCH CIRCUIT ROUTED IN FLOOR SLAB OR CONCRETE. COORDINATE

INSTALLATION WITH GENERAL CONTRACTOR AND SUPPORT AS REQUIRED. 1/2" CONDUIT (2) #12 AWG

CONDUCTORS MINIMUM.

OR

UTILITY COMPANY METER. PROVIDE "CT's" AND "PT's" AS REQUIRED, REFER TO SINGLE LINE DIAGRAM.

NON-FUSED DISCONNECT SWITCH, HP RATED AND WEATHERPROOF AS REQUIRED. PROVIDE FINAL CONNECTION

TO UNIT EQUIPMENT. SEE MOTORIZED EQUIPMENT SCHEDULE FOR DISCONNECT SIZES.

FUSED DISCONNECT SWITCH, HP RATED, OR COMBINATION MOTOR STARTER/DISCONNECT SWITCH WITH FUSES PER EQUIPMENT MANUFACTURER AND WEATHERPROOF AS REQUIRED. PROVIDE FINAL CONNECTION TO UNIT

EQUIPMENT. SEE MOTORIZED EQUIPMENT SCHEDULE FOR DISCONNECT AND STARTER SIZES.

P - PILOT LIGHT

GROUND CONNECTION, SIZE AS INDICATED OR AS REQUIRED.

M - MOTOR STARTING

LV - LOW VOLTAGE

PULLBOX, SIZED PER N.E.C. OR AS NOTED.

R - REMOTE CONTROL

2 - DOUBLE POLE

K - KEY OPERATED

3 - THREE WAY

4 - FOUR WAY

THERMOSTAT OUTLET BOX, PROVIDE 1/2"C.O. TO RESPECTIVE MECHANICAL UNIT.

EXHAUST FAN, OR MOTOR LOAD. REFER TO MECHANICAL, PLUMBING OR KITCHEN DRAWINGS FOR SPECIFIC

LOAD REQUIREMENTS OR AS NOTED.

FLUSH MOUNTED ELECTRICAL PANELBOARD OR LOAD CENTER. REFER TO PANEL SCHEDULE.

SURFACE MOUNTED ELECTRICAL PANELBOARD OR LOAD CENTER. REFER TO PANEL SCHEDULE.

DISTRIBUTION SWITCHBOARD. REFER TO SINGLE LINE DIAGRAM.

TRANSFORMER, REFER TO SINGLE LINE DIAGRAM.

T

M CT.

PPB

CLASS J

3P

50AF

60AS

150AF

150AT

3P

CIRCUIT BREAKER, LINE 1 REPRESENTS FRAME SIZE/RATING; LINE 2 REPRESENTS TRIP SIZE/RATING; LINE 3 REPRESENTS NUMBER OF POLES AND LINE 4 REPRESENTS MISCELLANEOUS BREAKER INFO. (SEE BELOW):

ST = PROVIDE SHUNT TRIP MECHANISM.

HACR = PROVIDE HACR-RATED BREAKER.

GFP = GROUND FAULT PROTECTION

CLCB = CURRENT LIMITING CIRCUIT BREAKER

SS = PROVIDE SOLID STATE CIRCUIT BREAKER

FUSIBLE SWITCH: LINE 1 REPRESENTS SWITCH SIZE/RATING; LINE 2 REPRESENTS NUMBER OF POLES; LINE 3 REPRESENTS FUSE SIZE/RATING; LINE 4 REPRESENTS FUSE TYPE; LINE 5 REPRESENTS MISCELLANEOUS

FUSE INFO. (SEE BELOW):

SHUNT= PROVIDE SHUNT TRIP MECHANISM.

GFP = GROUND FAULT PROTECTION

CLF = CURRENT LIMITING FUSE

SINGLE POLE SWITCHES, MOUNTING HEIGHT PER ADA DEVICE MOUNTING REQUIREMENTS. SUBSCRIPTS AT

SYMBOL INDICATE THE FOLLOWING:

NOTE: ALL WALL SWITCHES CONTROLLING EMERGENCY CIRCUITS SHALL BE ENGRAVED WITH "EMERGENCY"

F ab

POWER SYMBOLS

WALL MOUNTED JUNCTION BOX. MOUNTING HEIGHT AS NOTED. 4S/DP MINIMUM OR AS REQUIRED BY N.E.C..

JUNCTION BOX, MOUNTED IN ACCESSIBLE CEILING FOR APPLICATION DENOTED ON PLAN. 4S/DP MINIMUM OR

AS REQUIRED BY N.E.C..

J

J

DUPLEX RECEPTACLE - MOUNTING HEIGHT PER ADA DEVICE MOUNTING REQUIREMENTS OR AS NOTED.

DOUBLE DUPLEX RECEPTACLE, MOUNTING HEIGHT PER ADA DEVICE MOUNTING REQUIREMENTS OR AS NOTED.

DUPLEX, GFCI RECEPTACLE, MOUNTING HEIGHT PER ADA DEVICE MOUNTING REQUIREMENTS OR AS NOTED.

WP INDICATES WEATHERPROOF, REFER TO THE GENERAL PRODUCT SPECIFICATIONS.

DOUBLE DUPLEX, GFCI RECEPTACLE, MOUNTING HEIGHT PER ADA DEVICE MOUNTING REQUIREMENTS OR AS

NOTED. WP INDICATES WEATHERPROOF, REFER TO THE GENERAL PRODUCT SPECIFICATIONS.

SPECIAL RECEPTACLE, MOUNTING HEIGHT PER ADA DEVICE MOUNTING REQUIREMENTS OR AS NOTED. REFER TO

PLAN NOTES.

T

1. THE ELECTRICAL CONTRACTOR (EC) SHALL INCLUDE AND PROVIDE IN BID

ALL LABOR AND MATERIALS NECESSARY FOR A COMPLETE AND

OPERATIONAL INSTALLATION OF ALL ELECTRICAL SYSTEMS.

2. EC SHALL COORDINATE AND OBTAIN ALL APPROVALS, PERMITS, AND

DOCUMENTS FROM REGULATORY AGENCIES AND UTILITY COMPANIES.

3. ALL CONDUIT RACEWAY SYSTEMS ARE TO BE INSTALLED AS FOLLOWS:

a. RIGID GALVANIZED STEEL IS TO BE INSTALLED IN ALL AREAS WHICH

ARE EXPOSED TO WEATHER AND/OR PHYSICAL DAMAGE.

b. WP FLEXIBLE METALLIC CONDUIT I S PERMITTED FOR SHORT

CONNECTIONS TO LIGHT FIXTURES (6'-0" MAX). FLEXIBLE CONDUIT

SHALL ALSO BE INSTALLED FOR EQUIPMENT REQUIRING VIBRATION

AND ISOLATION.

d. P.V.C. CONDUIT SHALL BE USED FOR UNDERGROUND

CONDUITS. ROUTE CODE SIZED GROUND WIRE INSIDE OF

CONDUIT. CONDUIT RISERS AND STUBS ABOVE GRADE SHALL BE

RGS WITH HALF-LAPPED TAPE COVERING OR P.V.C. COATING.

4. UNLESS OTHERWISE NOTED OR REFERENCED ON THE DRAWINGS ALL N

NEW ELECTRICAL WIRING IS TO BE 600V RATED COPPER WITH TYPE

"THHN/THWN" INSULATION.

5. ALL MOUNTING HEIGHTS REFERENCED ON DRAWINGS ARE MEASURED

FROM FINISHED FLOOR UNLESS OTHERWISE REFERENCED OR INDICATED

ON THE DRAWINGS.

6. ALL ELECTRICAL EQUIPMENT LOCATIONS (LIGHTING, RECEPTACLE, FLOOR

BOX, ETC.) ARE TO BE VERIFIED WITH THE ARCHITECT AND/OR EQUIPMENT

SUPPLIER PRIOR TO BEGINNING ANY ROUGH-IN.

7. ALL LIGHTING FIXTURES SHALL BE MOUNTED AND SUPPORTED IN

ACCORDANCE WITH OSHA STANDARDS, AND ALL STATE, LOCAL, SEISMIC,

AND NATIONAL ELECTRIC CODES.

8. THE DRAWINGS INCLUDED IN THIS DOCUMENT SET ARE DIAGRAMMATIC.

THEY ARE REPRESENTATIVE OF THE ENGINEER OF RECORDS DESIGN

INTENT FOR ALL ELECTRICAL DEVICES/EQUIPMENT AND THE INDIVIDUAL

POWER FEEDS THEY ARE TO BE CONNECTED TO. THE SELECTED EC

SHALL BE RESPONSIBLE FOR PROVIDING ALL J-BOXES, CONDUIT, WIRING/

CABLING, ETC. AS REQUIRED FOR A COMPLETE AND OPERATIONAL

ELECTRICAL INSTALLATION.

9. ALL ELECTRICAL EQUIPMENT (PANELS, RECEPTACLES, J-BOXES, ETC.)

SHALL BE WEATHERPROOF AND/OR INSTALLED IN A NEMA 3R ENCLOSURE

WHERE APPLICABLE OR INSTALLED OUTDOORS.

10. ALL ELECTRICAL WORK SHALL BE PERFORMED ACCORDING TO STATE,

LOCAL, NATIONAL, AND DISTRICT STANDARDS AND CODES. COORDINATE

SPECIFIC REQUIREMENTS WITH DISTRICT STANDARDS AND AUTHORITY

HAVING JURISDICTION.

11. ALL ELECTRICAL EQUIPMENT SHALL BE NEW AND IS TO BE CLEARLY

LABELED/IDENTIFIED AS UNDERWRITER LABORATORIES (UL) COMPLIANT

UNLESS OTHERWISE NOTED OR REFERENCED IN THE DRAWINGS OR

SPECIFICATIONS.

12. EC IS RESPONSIBLE FOR SECURING ALL REQUIRED BUILDING PERMITS

AND SHALL INCLUDE THE COST TO SECURE BUILDING PERMITS IN THEIR

FINAL BID.

13. UNLESS OTHERWISE WRITTEN, STATED, OR REFERENCED IN DRAWINGS

OR SPECIFICATIONS CONTRACTOR SHALL GUARANTEE THE COMPLETE

ELECTRICAL INSTALLATION FOR A PERIOD OF 1-YEAR.

14. ALL ELECTRICAL DISTRIBUTION EQUIPMENT (PANELS, DISTRIBUTION

BOARDS, TRANSFORMERS, ETC), FEEDERS (CONDUIT, CONDUCTOR SIZE,

AND QUANTITY), MECHANICAL EQUIPMENT, ELEVATORS, VARIABLE

FREQUENCY DRIVES (VFD'S), ETC. MAY ONLY BE REFERENCED ON THE

SINGLE-LINE DRAWING AND NOT INDIVIDUAL PLAN SHEETS. EC SHALL

REVIEW AND VERIFY ALL REFERENCED INFORMATION ON THE SINGLE-LINE

DRAWING.

15. EC SHALL BE RESPONSIBLE FOR ALL REQUIRED SAW-CUTTING, CORE

DRILLING, PATCHING, REFINISHING, ETC. AS REQUIRED FOR INSTALLATION

OF ELECTRICAL EQUIPMENT AND SYSTEMS. ANY PENETRATIONS OR

OPENINGS MADE IN WALLS OR STRUCTURES SHALL BE PATCHED AND/OR

SEALED AS REQUIRED TO MAINTAIN THE INTEGRITY AND/OR RATING OF

THE WALL OR STRUCTURE.

16. EC SHALL VISIT THE SITE PRIOR TO SUBMISSION OF THEIR FINAL BID TO

VERIFY ALL EXISTING SITE CONDITIONS WHICH MAY AFFECT THE

COMPLETION OF THE ELECTRICAL INSTALLATION. ALL METHODS AND

REQUIREMENTS FOR INSTALLATION SHALL BE DETERMINED PRIOR TO

BID DATE. ELECTRICAL EC SHALL NOTIFY THE ENGINEER OF RECORD

OF ANY REQUIRED MODIFICATIONS WHICH ARE NOT REFERENCED ON

THESE ELECTRICAL PLANS. SUBMITTAL OF THE EC'S BID DEMONSTRATES

THE CONTRACTOR'S AWARENESS OF ALL SITE CONDITIONS AND

REQUIRED WORK TO BE PERFORMED.

17. ALL CEILINGS AND CEILING SYSTEMS AS A RULE ARE CONSIDERED TO BE

INACCESSIBLE. ALL ELECTRICAL DEVICES AND EQUIPMENT INSTALLED

ABOVE CEILINGS ARE TO BE MOUNTED IN A LOCATION WHICH IS

ACCESSIBLE. IN SITUATIONS WHERE ELECTRICAL DEVICES AND

EQUIPMENT MUST BE INSTALLED IN AN AREA WHICH IS INACCESSIBLE,

EC SHALL INSTALL AN ADEQUATELY SIZED, CODE COMPLIANT ACCESS

PANEL AS REQUIRED BY CURRENT CODES - LOCATION OF THE REQUIRED

ACCESS PANEL SHALL BE COORDINATE WITH THE ARCHITECT AND

INTERIOR DESIGNER PRIOR TO ROUGH-IN.

18. EC IS RESPONSIBLE FOR COMPLETING ALL FINAL ELECTRICAL

CONNECTIONS TO OWNER FURNISHED EQUIPMENT AND SHALL PROVIDE

ALL MOTOR START SWITCHES, DISCONNECTS, ETC. AS REQUIRED.

19. ALL ELECTRICAL EQUIPMENT CONNECTIONS, MOUNTING LOCATIONS,

ELECTRICAL REQUIREMENTS, ETC. ARE TO BE COORDINATED AND

VERIFIED PRIOR TO COMMENCEMENT OF ELECTRICAL ROUGH-IN.

20. EC TO SUBMIT SHOP DRAWINGS FOR THE APPROVAL OF THE ELECTRICAL

ENGINEER OF RECORD FOR ALL ELECTRICAL EQUIPMENT AND MATERIALS

TO BE UTILIZED IN THE ELECTRICAL INSTALLATION. ALL APPROVALS BY

THE ENGINEER OF RECORD MUST BE SECURED PRIOR TO COMPLETION

OF ANY PURCHASE ORDERS OR ROUGH-IN WORK.

21. THESE ELECTRICAL DRAWINGS AND ASSOCIATED SPECIFICATIONS ARE

TO BE CONSIDERED CONTRACT DOCUMENTS FOR AGENCY

REVIEW/APROVAL AND EC BIDDING PURPOSES.

22. THE COMPLETE ELECTRICAL SYSTEM SHALL BE GROUNDED IN

ACCORDANCE WITH NEC/CEC ARTICLE 250. ALL POWER AND LIGHTING

CIRCUITS SHALL BE INSTALLED WITH A MINIMUM #12AWG CU GROUND

WIRE UNLESS OTHERWISE NOTED OR REFERENCED.

23. EC TO PROVIDE ENGRAVED PHENOLIC NAMEPLATES ON ALL DISCONNECT

SWITCHES, DISTRIBUTION EQUIPMENT, J-BOXES ETC. WITH METALLIC

COVERS. SEE GENERAL NOTES ON SINGLE-LINE DIAGRAM FOR SPECIFIC

INFORMATION REGARDING NAMEPLATE REQUIREMENTS.

24. ALL COVER PLATES FOR LIGHT SWITCHES AND OUTLETS SHALL BE

STAINLESS STEEL WITH PANEL AND CIRCUIT ENGRAVED NAMEPLATES

25. AT THE COMPLETION OF THE PROJECT THE EC SHALL PROVIDE THE

OWNER WITH A COMPLETE SET OF AS-BUILT ELECTRICAL DRAWINGS.

26. ANY AND ALL WORK THAT REQUIRES AN INTERRUPTION TO A BUILDING(S)

ELECTRICAL SERVICE MUST BE COORDINATED WITH THE DISTRICT A

MINIMUM OF 48 HOURS IN ADVANCE. ANY SERVICE DOWNTOWN SHALL

NOT OCCUR DURING SCHOOL HOURS.

27. EC SHALL BE RESPONSIBLE FOR FOR ENSURING THAT ALL LOW VOLTAGE

SYSTEMS ARE COMPATIBLE AND ARE COMPLETE AND OPERATIONAL.

28. EC SHALL PERMANENTLY TAG ALL CONDUCTORS IN EACH ELECTRICAL

AND LOW VOLTAGE SYSTEM AS REFERENCED IN THE SPECIFICATIONS.

29. ANY SURFACE MOUNTED EXPOSED CONDUIT IN VIEW OF THE PUBLIC

SHALL BE PAINTED TO MATCH THE FINISH OF THE SURFACE TO WHICH IT

IS MOUNTED WITH TWO (2) COATS OF PAINT. ALL EXTERIOR SURFACE

MOUNTED EXPOSED CONDUITS ARE TO BE PAINTED WITH TWO (2) COATS

OF WEATHERPROOF LATEX PAINT.

30. EC TO PROVIDE ALL CONDUIT ONLY (C.O.) INFRASTRUCTURE WITH A 3/16"

NYLON PULL ROPE. LABEL PULL ROPE AT EACH END WITH THE LOCATIONS

OF ORIGIN AND TERMINATION.

31. IN INSTANCES WHERE A CONFLICT BETWEEN THE ELECTRICAL DRAWINGS

AND THE SPECIFICATIONS FOR THE PROJECT EXISTS, THE EC SHALL

ADHERE TO THE MORE STRINGENT REQUIREMENT.

32. THE SEISMIC ANCHORAGE OF ELECTRICAL EQUIPMENT SHALL CONFORM

TO C.C.R. TITLE 24, 2016 CBC SECTION 1613A AND ASCE7-05 SECTION 13.3

THRU 13.6. ANCHORAGE DETAILS NOT SHOWN ON THE APPROVED PLANS

OR OTHERWISE APPROVED BY DSA ARE SUBJECT TO FIELD APPROVAL BY

THE ARCHITECT AND/OR STRUCTURAL ENGINEER OF RECORD AND DSA.

33. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC. AS SUCH, ALL ELECTRICAL

EQUIPMENT LOCATIONS, CONDUIT ROUTING, ETC. ARE NOT PRECISE AND

SHALL BE COORDINATED, VERIFIED, AND DETERMINED IN THE FIELD. EC

TO INSTALL ALL ELECTRICAL EQUIPMENT AND ROUTE ALL CONDUITS IN

LOCATIONS WHICH MEET CODE REQUIREMENTS FOR

ACCESSIBILITY/MOUNTING AND DO NOT INTERFERE WITH ANY BUILDING

STRUCTURES, UTILITIES, OR OTHER TRADE EQUIPMENT.

34. ALL EXISTING SITE RELATED ELECTRICAL EQUIPMENT (I.E. UNDERGROUND

UTILITIES, DUCTS, STRUCTURES, PULL BOXES, ETC.) LOCATIONS ARE

DIAGRAMMATIC IN NATURE AND ONLY REFLECT APPROXIMATE

LOCATIONS, QUANTITIES, AND/OR ROUTING INFORMATION. ALL

REFERENCED INFORMATION HAS EITHER BEEN SURVEYED, REPORTED BY

THE OWNER/OWNERS REP, AND/OR REFERENCED ON AN AS-BUILT

RECORD DOCUMENTS. ALL EXISTING ELECTRICAL EQUIPMENT

REFERENCED ON THESE DRAWINGS IS TO BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO COMMENCEMENT OF WORK. BY ACCEPTING

THESE PLANS OR PROCEEDING WITH ELECTRICAL SCOPE OF WORK,

AGREES TO ACCEPT LIABILITY AND SHALL RENDER THE ENGINEER OF

RECORD HARMLESS FOR ANY ELECTRICAL EQUIPMENT NOT REPORTED

TO THE ENGINEER DURING THE DESIGN PROCESS. THE CONTRACT TO

TAKE THE REQUIRED PRECAUTIONARY MEASURES TO ENSURE ALL

EXISTING ELECTRICAL EQUIPMENT IS PROTECTED IN PLACE.

35. ANY EXISTING BUILDING STRUCTURES OR SURFACES DAMAGED BY

DEMOLITION OR DURING INSTALLATION ACTIVITIES SHALL BE REPAIRED,

PATCHED, AND/OR REFINISHED TO THE SATISFACTION OF THE OWNER.

36. ALL EXISTING ELECTRICAL EQUIPMENT INDICATED TO BE DEMOLISHED

SHALL BE REMOVED ENTIRELY AND ALL AFFECTED SURFACES OR

STRUCTURES SHALL BE REPAIRED, REPLACED, AND/OR REFINISHED TO

MATCH THE ADJACENT SURFACES OR DAMAGED ITEM(S).

37. FOR CLARITY ONLY RECONSTRUCTION OR NEW WORK RELATED

ELEMENTS AND SELECT EXISTING FACILITIES SPECIFICALLY REQUIRING

COORDINATION WITH ANY NEW WORK.

38. ALL CONDUITS, BOXES, SURFACE MOUNTED RACEWAYS, SUPPORT

DEVICES, AND ASSOCIATED FITTINGS SHALL BE MOUNTED IN CONCEALED

LOCATIONS ABOVE CEILINGS, DUCTS, TRUSSES, BEAMS, ETC. IN AREAS

WHERE A CONCEALED MOUNTING LOCATION IS NOT AVAILABLE

EQUIPMENT SHALL BE PAINTED TO MATCH THE ADJACENT SURFACES.

39. ANY PENETRATIONS BY CONDUITS OR OTHER ELECTRICAL EQUIPMENT

THROUGH A FIRE RATED WALL - WHETHER EXISTING OR NEW - SHALL

MAINTAIN THE APPROPRIATE FIRE RATING BY SEALING THE PENETRATION

WITH THE APPROPRIATE UL-LISTED FIRE-STOP MATERIAL/SYSTEM.

GENERAL NOTES

18 CONDUIT IDENTIFICATION

TIMER CONTACT

LIMIT SWITCH

NORMALLY OPEN, NORMALLY CLOSED SWITCH

PUSHBUTTON

CONTROL DIAGRAM SYMBOLS

TIMER CONTACT

CONTROL POWER TRANSFORMER

MOTOR, M = HORSEPOWER

RELAY COIL

SOLENOID VALVE

PUSH TO TEST LED INDICATOR LIGHT, G = GREEN, R = RED,

A = AMBER, W = WHITE

2 POLE, 3 POLE CIRCUIT BREAKERS

2 POLE, 3 POLE DISCONNECT SWITCHES

NORMALLY CLOSED, NORMALLY OPEN CONTACTS

HAND-OFF-AUTO SWITCH

DIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/30/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

CHC

AS

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT:

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/30/26

6518010004 6518010003 6518010005

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

SI

TE

RE

G

G

RF

TE OO I

C

No. E 18589

ELESTA TRIC A

NIAL

IN

RE

E

ORP

RE

D

O SFE SI N

NE

LA

A D

A M S L O

A N

ELECTRICAL SYMBOLS

AND NOTES

7.30.2026 100% Electrical Submittal

08/03/2026 wadepew Image wadepew

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/30/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

CHC

AS

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT:

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/30/26

6518010004 6518010003 6518010005

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

SI

TE

RE

G

G

RF

TE OO I

C

No. E 18589

ELESTA TRIC A

NIAL

IN

RE

E

ORP

RE

D

O SFE SI N

NE

LA

A D

A M S L O

A N

S-19 ELECTRICAL PLANS

SHEET NOTES:

(E) MAIN SERVICE PEDESTAL - 240/120V, 1Ø, 3W, 200 AMP WITH MANUAL

TRANSFER SWITCH ON RAISED CONCRETE PAD

(E) RTU/PUMP CONTROL PANEL ON RAISED CONCRETE PAD, REMOVE RUST

AND REPAINT, INSTALL FLOW TRANSMITTER, FLOW INDICATOR, AND

PRESSURE INDICATOR SEE DETAIL 2, SHEET E-02

(E) WETWELL

VALVE VAULT

FLOW ELEMENT

STUB UP CONDUIT WITH "LB" FITTING, PROVIDE MYERS SCRU-TITE HUB, WP

CONNECTION TO EXISTING PANEL,

POLE MOUNTED ANTENNA, SEE CIVIL DRAWINGS FOR DETAIL

FLOW INDICATOR

PRESSURE INDICATOR

FLOW TRANSMITTER

STUB UP CONDUIT TO "LB" FITTING

MEYERS SCRU-TITE HUB

(E) CONCRETE PAD

REMOVABLE GUARD POST, SEE CIVIL DRAWINGS FOR DETAIL, PROVIDE 3'

CLEARANCE TO CONTROL PANEL)

PRESSURE TRANSMITTER

DEMO (E) ANTENNA POLE AND STRUCTURAL FOOTING, RELOCATE

ANTENNA TO NEW POLE

FE

J

J

ELECTRICAL POWER PLAN

3/8"=1'-0"

1"C-FLOWMETER CABLE

1"C - 2/C#16SH (PRESSURE

TRANSMITTER)

PIT

J

J

2"C - 2-LMR 400 CABLES

RTU/PUMP CONTROL PANEL

NTS

FRONT VIEW END VIEW

13 13

2 2

TYP.

12'

7.30.2026 100% Electrical Submittal

08/03/2026 wadepew Image wadepew

5751 BOATHOUSE LANE

S-28 ELECTRICAL PLANS

ELECTRICAL POWER PLAN

3/8"=1'-0"

1/2

ELECTRICAL SITE PLAN

1"=10'

P0

SHEET NOTES:

(E) TRANSFORMER ENCLOSURE #3, SEE DETAIL 3, SHEET E-11

NEMA 4X PANEL "MS" - 240/120V, 1Ø, 3W, 150 AMP - WALL MOUNTED.

NEMA 4X MANUAL TRANSFER SWITCH, 240/120V, 1Ø, 3W, 200 AMP -

WALL MOUNTED.

NEMA 4X RTU/PUMP CONTROL PANEL ON RAISED CONCRETE PAD,

SEE DETAILS 1 & 2 ON SHEET E-07.

24" X 36" TRAFFIC RATED H20 LOAD PULL BOX WITH BOLT DOWN

COVER, SEAL ALL CONDUIT TO WETWELL

STAINLESS STEEL CONDUIT WITH BUSHING AT WETWELL AND

CONDUIT SEAL AT PULL BOX

SUBMERSIBLE PUMP

WETWELL - CLASS 1, DIVISION 1 AREA PER CEC ARTICLE 501.

ULTRASONIC LEVEL TRANSMITTER, AIM AT CENTER OF WETWELL,

SEE CIVIL DRAWINGS FOR DETAIL.

SUMP PUMP, GFCI RECEPTACLE +18" AFF WITH WP IN-USE COVER

VALVE VAULT

FLOAT SWITCHES, SEE DETAIL 1, SHEET E-11

(E) WET WELL

GROUND ROD IN GROUND WELL, SEE DETAIL 4, SHEET E-11.

FLOW ELEMENT

(E) BUILDING

PRESSURE TRANSMITTER

RELOCATE TWO (E) BUILDING MOUNTED ANTENNAS TO NEW

ANTENNA POLE

37.5 KVA 4160V, 1Ø TO 120/240V, 1Ø FUSED PAD MOUNTED

TRANSFORMER, PROVIDE CONCRETE PAD PER MANUFACTURER

REQUIREMENTS

REMOVABLE GUARD POST, SEE CIVIL DRAWINGS FOR DETAIL,

PROVIDE 3' CLEARANCE TO CONTROL PANEL)

POLE MOUNTED ANTENNA, SEE CIVIL DRAWING FOR DETAIL

NON CONTACT PROXIMITY TYPE HATCH INTRUSION SWITCH

PROTECT IN PLACE (E) PUMP STARTER WITH HOA, DEMO PANEL AT

END OF PROJECT.

PROTECT IN PLACE (E) PLC CONTROL PANEL, DEMO PANEL AT END

OF PROJECT.

(E) WET WELL PULL BOX, INTERCEPT AND EXTEND (E)

CONDUCTORS/CABLES FOR (E) 2 HP SEWAGE PUMP AND (E) LEVEL

SENSOR TO (E) PANELS AS SHOWN

8" X 8" X 6" NEMA 3R PULLBOX

E-03

LT LS

P1

P2

TYP.

TYP.

DIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/30/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

CHC

AS

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT:

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/30/26

6518010004 6518010003 6518010005

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

SI

TE

RE

G

G

RF

TE OO I

C

No. E 18589

ELESTA TRIC A

NIAL

IN

RE

E

ORP

RE

D

O SFE SI N

NE

LA

A D

A M S L O

A N

BOATHOUSE LANE

R/W R/W

P7

P0

C2

P3

P2

P5 C1 P6 C2

C1 P6P5

14 TYP.14

P4

FE

J

C3

PIT

J

C4

J J

C6

P1

20 TYP.

IS

22 C5

C5

P8C7

C7 P8

7.30.2026 100% Electrical Submittal

08/03/2026 wadepew Image wadepew

2P 20A

2P 20A

9.4A

PUMP

P-1

9.4A

PUMP

P-2

100A

MANUAL TRANSFER SWITCH

WITH CAM-LOCKS

120/240V,1Ø,3W

120/240V,1Ø,3W 22KAIC RATED

P6P5

P2

P4

120/240V,1Ø, 3W 200A BUS

SINGLE LINE DIAGRAM

M

P1

DIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/30/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

CHC

AS

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT:

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/30/26

6518010004 6518010003 6518010005

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

SI

TE

RE

G

G

RF

TE OO I

C

No. E 18589

ELESTA TRIC A

NIAL

IN

RE

E

ORP

RE

D

O SFE SI N

NE

LA

A D

A M S L O

A N

S-28 SINGLE LINE DIAGRAM AND SCHEDULES

P3

LOAD SCHEDULE - LIFT STATION

LOAD AMPS

PUMP #1 9.4A

PUMP #2 9.4A

MISC. 15A

25% OF LARGEST

MOTOR

2.4A

TOTAL 36.2A

2P 100A

SYMBOL

PLAN CONDUIT

Qty Size Size

WIRE

Qty From

CONTROL CONDUIT SCHEDULE

Use

DESCRIPTION LOCATION

To

REMARKS

NOTE: PROVIDE 200# PULLROPE IN ALL EMPTY CONDUITS

C1 1 2" FLOAT CABLES CONTROL FLOATS LSLL, LSHH RTU/PUMP CONTROL PANEL

C2 1 1" LEVEL TRANSDUCER CABLE CONTROL ULTRASONIC LEVEL TRANSDUCER RTU/PUMP CONTROL PANEL

C3 1 FLOWMETER CABLE CONTROL FLOWMETER RTU/PUMP CONTROL PANEL1"

SYMBOL

PLAN CONDUIT

Qty Size Size

WIRE

Qty From

POWER CONDUIT SCHEDULE

Use

DESCRIPTION LOCATION

To

REMARKS

NOTE: PROVIDE 200# PULLROPE IN ALL EMPTY CONDUITS

P1 1 2" 3#3/0, 1#2G POWER PAD MOUNTED TRANSFORMER T3 PANEL "MS"

P2 1 2" 3#1/0, 1#2G POWER PANEL "MS" MANUAL TRANSFER SWITCH

P3 1 3#1/0, 1#2G POWER MANUAL TRANSFER SWITCH RTU/PUMP CONTROL PANEL

P4 1 1#2G PANEL "MS", PAD MOUNTED TRANSFORMER GROUND RODS

P6

P7

2"

1" GROUND

1 PUMP CABLE RTU/PUMP CONTROL PANEL PUMP P22" POWER

1 2#12, 1#12G RTU/PUMP CONTROL PANEL SUMP PUMP RECEPTACLE3/4" POWER

P5 1 PUMP CABLE RTU/PUMP CONTROL PANEL PUMP P12" POWER

PUMP CONTROL

PANEL

PANEL "MS"

C4 1 2/C#16SH CONTROL PRESSURE TRANSMITTER RTU/PUMP CONTROL PANEL1"

2P 100A

120/240V,1Ø, 3W 200A BUS

2P 100A

2P 200A

TO RESTROOM BUILDING

3P

30E

5KV

30A

4160V,3Ø

T1

4160V,1Ø PRI

10KVA (AØ,BØ)

120/240V,1Ø SEC

TO 120/240V

LOADS

T2

4160V,1Ø PRI

10KVA (BØ,CØ)

120/240V,1Ø SEC

TO 120/240V

LOADS

4160V,1Ø PRI

10KVA

120/240V,1Ø SEC

TO 120/240V

LOADS

T4

4160V,3Ø PRI

112.5KVA

120/208V,3Ø SEC

TO 120/208V

LOADS

T3

4160V,1Ø PRI (FUSED)

37.5KVA (AØ,CØ)

120/240V,1Ø SEC

PAD MOUNTED

22KAIC RATED

SERVICE

RATED

P4 P0

TRANSFORMER

ENCLOSURE #1

P0 1 3" 2#6 5KV, 1#6G 5KV POWER (E) TRANSFORMER ENCLOSURE #3 PAD MOUNTED TRANSFORMER T3

TRANSFORMER

ENCLOSURE #2

TRANSFORMER

ENCLOSURE #3

MAIN SERVICE

SOUTH SIDE

FEEDER

3#6,5KV

183.75KVA

25.5A +/- 900'

Vd = 0.81%

3#6,5KV

183.75KVA

25.5A +/- 1077'

Vd = 0.97%

3#6,5KV

168.75KVA

23.4A +/- 846'

Vd = 0.70%

3#6,5KV

112.5KVA

15.63A +/- 271'

Vd = 0.15%

2#6,1#6G,5KV

37.5KVA

9A +/- 50'

Vd = 0.01%

TYP.

SCOPE

EXISTING

LOAD SCHEDULE - MAIN SERVICE

LOAD AØ KVA BØ KVA CØ KVA

T1 5 5 0

T2 0 5 5

T3 18.75 0 18.75

T4 37.5 37.5 37.5

TOTAL 61.25 47.5 61.25

SHEET NOTES:

(E) 5KV POT HEAD TERMINATATION

NEMA 4X STAINLESS STEEL ENCLOSURE, VANDAL RESISTANT

WITH LOCKABLE HANDLES

REVENUE GRADE POWER METER 0.2% ACCURACY, SHARK

200-60-10-V4-D2-IN100S-X OR APPROVED EQUAL

MAINTAIN (E) PHASING FOR NEW TRANSFORMER

SAWCUT (E) PAVING AND CONCRETE, TRENCH, BACKFILL,

COMPACT AND PATCH TO MATCH EXISTING

FIELD VERIFY(E) CONDUCTOR SIZE.

PHASE FAIL RELAY, PROVIDE CONTACT TO PLC

REDUCED VOLTAGE SOFT STARTER

E-11

C5 1 2#14 CONTROL HATCH MOUNTED INTRUSION SWITCH RTU/PUMP CONTROL PANEL1"

C6 1 2 - LMR 400 CABLES CONTROL POLE MOUNTED ANTENNAS RTU/PUMP CONTROL PANEL2"

1/2

9.8A

SUMP PUMP

(RECEPTACLE)

P7

1P

AØ

1P

BØ

TO POWER

DISTRIBUTION

DIAGRAM,

DETAIL 1, SHEET

E-06

2P

PFR

6 TYP.

8 8

P8 1 2#10, 1#10G (E) WETWELL PULLBOX - SEWAGE PUMP (E) PUMP STARTER/HOA1 1/4" POWER

C7 1 LEVEL SENSOR CABLE (E) WETWELL PULL BOX - LEVEL SENSOR (E) PLC CONTROL PANEL1 1/4" CONTROL

7.30.2026 100% Electrical Submittal

08/03/2026 wadepew Image wadepew

SHEET NOTE:

ALL INDICATING LIGHTS SHALL BE LED PUSH TO TEST

ALL WIRING TO FIELD DEVICES SHALL BE FAIL SAFE

ALL CONTACTS ARE SHOWN IN NORMALLY

DE-ENERGIZED STATE

FLYGT MINICAS II SUPERVISORY RELAY

INTRINSICALLY SAFE RELAY

LOW LEVEL FLOAT

HIGH LEVEL FLOAT

RELAY SHALL DE-ENERGIZE ON HIGH-HIGH LEVEL

REDUCED VOLTAGE SOFT STARTER

DIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/30/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

CHC

AS

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT:

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/30/26

6518010004 6518010003 6518010005

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

SI

TE

RE

G

G

RF

TE OO I

C

No. E 18589

ELESTA TRIC A

NIAL

IN

RE

E

ORP

RE

D

O SFE SI N

NE

LA

A D

A M S L O

A N

S-28 CONTROL DIAGRAMS

MTR

CB

L2

T1

T2

1FU

O

AH

L1

2HP

MOTOR

HAND

AUTO

CR2

CR4

PUMP

RUNNING

HOA IN

HANDCR1

WETWELL LEVEL CONTROL

CR11

LOW LEVEL

ALARM

PUMP CALL

DELAY

CR11-2

CR11-3

CR11-4

CR13

CR13

R

HIGH LEVEL CR12-3

L N

ISR

L N

ISR

CR10

CR10-1

R

LOW LEVEL

CR12

CR12-1

TRC

SET @ 2 MIN.

0-30 MIN.

CR12-2

CR16

R

FLOAT

CONTROL MODE

CR15

CR14

CR16-1

120VAC

SEE

E-06

L N

SUPERVISORY RELAY

C-1

C-1

POWER

DISTRIBUTION

BLOCK

240V, 1Ø

C

O/LCR1-1

CR2-1

AT PLC

START/STOP

AT WW CONT.

CR14 (P1)

CR15 (P2)

AT WW CONT.

CR11

AT WW CONT.

CR17

CR5-1

TRA

0-60 SEC.

O/L

C-2

G

PUMP RUN

CR5-2

CR6-1

ETM

CR5

R

PUMP FAIL

CR7-1

CR6-2

CR6

R

HIGH TEMPERATURE

CR7-2

CR8-1

RESET

FROM PLC

CR7

CR8

CR9

A

LEAK

PUMP LEAK SIGNAL

O/L

CR2-2

CR1-2

CR4-1

HOA IN AUTO

PLC DI

HOA IN HAND

PLC DI

PUMP RUN

PLC DI

CR5-3

PUMP FAIL

PLC DI

CR6-3

HIGH TEMP.

PLC DI

CR9-1

LEAK DETECTED

PLC DI

P1 CONTROL DIAGRAM

TRD

SET @ 15S

0-5 MIN.

CR14

CR15

TRC

TRB

TRD

TRA

HOA IN

AUTO

PUMP ON

DELAY TIMER

ELAPSED

TIME METER

FAIL

ALARM

HIGH

TEMPERATURE

RESET

REMOTE

PLC RESET

TRB

SET @ 5S

0-30S

RESET

HIGH LEVEL

ALARM

FLOAT CONTROL

MODE

PUMP 2

FLOAT MODE

START

PUMP 1

FLOAT MODE

START

LSLL

LSHH

CR11-1

PUMP

CALL

HIGH

TEMP.

LEAK

DETECTED

MOTOR TEMP. SWITCH

N

120V

TYPICAL FOR P2

CB

CIRCUIT BREAKER TRIPPED

PLC DI

CR17-1

CR17-2

CR17-3

MAINTENANCE MODE

TO P1 CONTROLS

MAINTENANCE MODE

TO PLC

FLOAT CONTROL MODE

PLC DI

HIGH LEVEL

PLC DI

LOW LEVEL

PLC DI

LOW LEVEL TO P2

CONTROLS

LOW LEVEL TO P1

CONTROLS

MAINTENANCE MODE

TO P2 CONTROLS

CR17

MAINTENANCE

MODE

R

MAINTENANCE MODE

C-3

7.30.2026 100% Electrical Submittal

08/03/2026 wadepew Image wadepew

M340 PLC

RJ45

MODBUS

USB

CPS

24 VDC DI

RJ45

ETHERNET

00 01 05 06 10 11

CPU

PLC P.S.

CAT. 5e 1

ETHERNET SWITCH

5 6

HMI

COAXIAL CABLE

SURGE SUPPRESSOR

ORBIT RADIO

COAXIAL CABLE

ANTENNA

(SIGNAL HILL)

CAT. 5e

CAT. 5e

DI

DO

AI

04 07

SPACE

08 09

SURGE

SUPPRESSOR

L N

FAN

PANEL LIGHT

LED FIXTURE

T-STAT1

120VAC FROM PUMP

CONTROL PANEL SEE

DETAIL 1 SHEET E-04

HOT NEUTRAL

DUPLEX

RECEPTACLE15A 1P

PFR

ETHERNET SWITCH

PLC POWER

SUPPLY

10A 1P

RADIO

DIGITAL

OUTPUT MODULE

HMI

DIGITAL

INPUT MODULE

DIGITAL

INPUT MODULE

1 2

15A 1P

120VAC INPUT

24VDC OUTPUT

24 VOLT BATTERY

MODULE

24VDC

BATT

CHARGE

24 VOLT DC UPS

MODULE

L N

1 2

5A 1P

SPACE SPACE SPACE SPACE

ANALOG

INPUT MODULE

FIT-1

DIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/30/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

CHC

AS

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT:

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/30/26

6518010004 6518010003 6518010005

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

SI

TE

RE

G

G

RF

TE OO I

C

No. E 18589

ELESTA TRIC A

NIAL

IN

RE

E

ORP

RE

D

O SFE SI N

NE

LA

A D

A M S L O

A N

S-28 PLC POWER AND COMMUNICATION DIAGRAM

RADIO

1A 1P

1A 1P

2A 1P

3A 1P

3A 1P

1A 1P

1A 1P

1A 1P

1A 1P

1A 1P

WET WELL LEVEL

CONTROL

5A 1P

5A 1P

COAXIAL CABLE

SURGE SUPPRESSOR

MDS iNET II RADIO

COAXIAL CABLE

ANTENNA

(S-06)

CAT. 5e

INSTRUMENT

LOOP POWER

1A 1P

24VDC

POWER FAIL

1A 1P

SHEET NOTE:

PROVIDE CONTACT TO PLC DIGITAL INPUT FOR

POWER FAILURE

PROVIDE CONTACT TO PLC DIGITAL INPUT FOR UPS

FAULT AND UPS ON BATTERY

CONTRACTOR TO VERIFY PROTECTIVE DEVICE AMP

RATING WITH LOAD MANUFACTURER REQUIREMENTS

120VAC

POWER FAIL 1

1PFR

TYP.

RTU DIAGRAM

POWER DISTRIBUTION DIAGRAM

AO

RJ45

ETHERNET

CAT. 5e

LIT-1

1A 1P

4-20MA SIGNAL SPLITTER

1A 1P

4-20MA SIGNAL SPLITTER

1A 1P

7.30.2026 100% Electrical Submittal

08/03/2026 wadepew Image wadepew

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/30/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

REHABILITATION OF SEWER LIFT STATIONS

S-19, S-28, AND S-29

CHC

AS

FI

LE

N

AM

E:

M c_ dw g D

ES

IG

N B

Y:

N/A

MUNIS PROJECT:

SHEET OF SHEETSDWG.

318 W. KATELLA AVENUE, SUITE A

ORANGE, CA 92867

(714) 978-4407 www.jigconsultants.com

7/30/26

6518010004 6518010003 6518010005

B. Anatole Falagán

GENERAL MANAGER

LONG BEACH

PUBLIC UTILITIES DEPARTMENT

SI

TE

RE

G

G

RF

TE OO I

C

No. E 18589

ELESTA TRIC A

NIAL

IN

RE

E

ORP

RE

D

O SFE SI N

NE

LA

A D

A M S L O

A N

S-28 CONTROL PANEL ELEVATIONS

3 4 5 6

7 8

9 14

10 11 15 16

12 13 17 18

1 2

3 3

6 6 6 6 6 8

7 6

5 5

7 6

MATERIAL SCHEDULE

ITEM DESCRIPTION

1 FREE STANDING, NEMA 4X, 60"H X 72"W X 24"D

2 HUMAN MACHINE INTERFACE (HMI)

3 PROCESS METER, LOCAL DISPLAY

4 30MM 2 POSITION SWITCH

5 30MM 3 POSITION SWITCH

6 30MM RED INDICATING LIGHT

7 30MM GREEN INDICATING LIGHT

8 30MM AMBER INDICATING LIGHT

X NAMEPLATE SCHEDULE

TAG SIZE INSCRIPTION

1 2" X 4" RTU

2 2" X 4" PUMP CONTROL

3 1" X 3" FLOAT CONTROL MODE

4 1" X 3" LOW LEVEL

5 1" X 3" HIGH LEVEL

6 1" X 3" MAINTENANCE MODE

7 1" X 3" LEVEL

8 1" X 3" FLOW

9 1" X 3" P1 HOA

10 1" X 3" P1 RUN

11 1" X 3" P1 FAIL

12 1" X 3" P1 HIGH TEMPERATURE

13 1" X 3" P1 LEAK

14 1" X 3" P2 HOA

15 1" X 3" P2 RUN

16 1" X 3" P2 FAIL

17 1" X 3" P2 HIGH TEMPERATURE

18 1" X 3" P2 LEAK

19 1" X 3" PRESSURE

X

SHEET NOTES:

SEE DETAIL 1, SHEET E-08 FOR RTU LAYOUT

MAIN CIRCUIT BREAKER, PUMP P1 AND P2 STARTERS, AND

CONTROL RELAYS.

ENCLOSURE LIGHT WITH SWITCH

CONTROL PANEL INTRUSION SWITCH

60"H X 72"W X 24"D NEMA 4X STAINLESS STEEL CONTROL

PANEL WITH VANDAL RESISTANT LOCKABLE DOORS, FULL

HEIGHT REAR MOUNTING PANELS AND FULL HEIGHT INNER

DOORS.

CONCRETE EQUIPMENT PAD, EXTEND 2" ON FRONT 3 SIDES

OF CONTROL PANEL AND 3" ABOVE GRADE.

1 3

RTU/PUMP CONTROL PANEL

NTS

SHOWN WITH OUTER DOORS OPEN

RTU/PUMP CONTROL PANEL

NTS

SHOWN WITH INNER DOORS OPEN

72"

7.30.2026 100% Electrical Submittal

08/03/2026 wadepew Image wadepew

GENERAL NOTES:

LEGEND:

DIRECTOR OF WATER/SEWER ENGINEERING

MANAGER OF ENGINEERING

APPROVED

RECOMMENDED

DEPARTMENT DATE

BY CK'D.

CITY ENG.

VERIZON

EDISON CO.

LB ENERGY

FIRE

INPUT BY

AS-BUILT BY

POSTED GIS

CONSTRUCTED BY

GIS TILE

SPEC. NO

SECTION MAP

SERVICE ATLAS PAGE

GATE VALVES REC.

AS SHOWNSCALE

N/A

CONTRACT NO.

CHECKED BY

DESIGNED BY

DATE

DATE

CORRECTED BY

DATE

DATE

DATE

DATE

DATE 7/30/26

VARIOUS

DESCRIPTIONDATEREV.

SC - 0510

DRAWING / FILE NUMBER:

DATE

DATE

REHABILITATION OF SEWER LIFT STATIONS

S-19,…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .