Revised Specifications
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Chiller_Specifications_Attachment_A.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment A
Specifications
Chiller to Produce -50 F Brine at 13 GPM and 8-10 Tons of Refrigeration
Background
The Heating, Ventilation, Air Conditioning, and Refrigeration (HVAC&R) Equipment Performance Group of the National Institute of Standards and Technology (NIST) researches the heat transfer performance of new alternative refrigerants. The focus of the work is to develop design tools for end-users to ensure the design of energy efficiency air-conditioning and heating equipment for buildings. The chiller will be used to supply cooling to the heat transfer test rigs located at NIST Gaithersburg, MD.
Deliverables Summary
Item Quantity Delivery Date
8-10 Ton Chiller 1 8 weeks after order date
Specification criteria – Minimum Requirements
The minimum specifications criteria for the Chiller is shown in the following tables.
Specification criteria: Chiller
Parameter Criteria
Documentation: 1. Operation manual
2.1. Calibration report
Evaporator Brine Temperature Range: -50 °F to -20 °F (Lower brine temperatures result in additional consideration)
Brine Temperature Stability at Setpoint: ±1 °F
Maximum Width to Fit in Elevator:Footprint to Fit in Elevator:
5 feet (this criteria can be exceeded if the vendor can ensure that the unit can be turned into the elevator space)5 feet square or less
Maximum Height to Fit in Elevator: 90 81 inches
Maximum Weight for Elevator: 6000 lbm
Electrical Controls For Remote Operation: Yes
Power: 480V/3PH/60HZ
Dynalene HFLO Brine Pump: At least 13 GPM and -50 °F and 90 psi
Electrical: Wired and Ready to operate
Oil Safety Control: Yes
Refrigerant Pressure Controls Yes
Attachment A
Minimum Warranty: 90 days
Pre-Wired Electrical System For Single Point Connection
Yes
Operate With 26 GPM Of 40°F Chiller Water Flow In Condenser
Yes
Capacity Control Via VFD Or Bypass Down To 30% Capacity
Yes
Quantity
Quantity needed: 1
Example model #s:
Manufacturer Model Model #
TEMPEST, Inc. LTAC-10
Acceptance/Inspection Criteria
The chiller will be tested by the HVAC&R group, and verified to deliver -50 F at ten eight tons of refrigeration. The item will be inspected at a government site.
File details come from the government source that posted it. Updated .