Attachment A Specifications Chiller to Produce -50 F Brine at 13 GPM and 8-10 Tons of Refrigeration Background The Heating, Ventilation, Air Conditioning, and Refrigeration (HVAC&R) Equipment Performance Group of the National Institute of Standards and Technology (NIST) researches the heat transfer performance of new alternative refrigerants. The focus of the work is to develop design tools for end-users to ensure the design of energy efficiency air-conditioning and heating equipment for buildings. The chiller will be used to supply cooling to the heat transfer test rigs located at NIST Gaithersburg, MD.
Deliverables Summary
| Item |
| Quantity |
| Delivery Date |
| 8-10 Ton Chiller |
| 1 |
| 8 weeks after order date |
Specification criteria – Minimum Requirements The minimum specifications criteria for the Chiller is shown in the following tables.
Specification criteria: Chiller
| Documentation: |
| 1. Operation manual |
2. Calibration report
| Evaporator Brine Temperature Range: |
| -50 °F to -20 °F |
| Brine Temperature Stability at Setpoint: |
| ±1 °F |
| Footprint to Fit in Elevator: |
| 5 feet square or less |
| Maximum Height to Fit in Elevator: |
| 90 inches |
| Maximum Weight for Elevator: |
| 6000 lbm |
| Electrical Controls For Remote Operation: |
| Yes |
| Dynalene HFLO Brine Pump: |
| At least 13 GPM and -50 °F |
| Electrical: |
| Wired and Ready to operate |
| Refrigerant Pressure Controls |
| Yes |
| Minimum Warranty: |
| 90 days |
| Pre-Wired Electrical System For Single Point Connection |
| Yes |
| Operate With 26 GPM Of 40°F Chiller Water Flow In Condenser |
| Yes |
| Capacity Control Via VFD Or Bypass Down To 30% Capacity |
| Yes |
Quantity Quantity needed: 1 Example model #s:
| Manufacturer |
| Model |
| Model # |
TEMPEST, Inc.
LTAC-10
Acceptance/Inspection Criteria The chiller will be tested by the HVAC&R group, and verified to deliver -50 F at ten tons of refrigeration. The item will be inspected at a government site.