This is a battery inspection report generated by the City of Tampa's Solid Waste & Environmental Program Management Department for the McKay Bay Waste-to-Energy Facility's UPS system. The document contains detailed technical data on an Enersys EC-11M station battery installed on May 1, 2011, with readings taken on September 26, 2023. The report documents cell-by-cell voltage measurements across 60 cells, internal resistance values, intercell resistance, temperature readings in Fahrenheit, and specific gravity measurements. Cells 1 through 30 show zero values for internal resistance, intercell resistance, temperature, and specific gravity, while cells 31 through 60 display active operational data with voltages ranging from 2.159 to 2.354 volts, internal resistances between 309 and 350 ohms, intercell resistances of 9 to 287 ohms, temperatures between 86.8°F and 88.3°F, and specific gravity readings between 1.204 and 1.211. The overall voltage reading is 136.6 volts with summary statistics showing high, average, and low measurements across all parameters.

The technical data contained in this report supports the ongoing maintenance and inspection services being procured under City of Tampa Bid No. 26-P-00198 for full-service preventative maintenance of six Liebert APS AS3 Series UPS units and associated station batteries at the McKay Bay facility. The battery readings and condition data inform the scope of required services, which includes quarterly UPS inspections, quarterly battery inspections, annual battery load testing, and 24-hour emergency response capabilities. This inspection report demonstrates the operational status of the existing equipment that qualified contractors must be prepared to maintain and service according to manufacturer specifications and industry standards including OSHA, NFPA, and NEC requirements throughout the contract period.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Battery Name: Station Battery Install Date: 05/01/2011

String Name: Station Battery Location Name: Wheelabrator McKay Bay

Model Number: Enersys EC-11M d/c 5/11

Readings taken on 09/26/2023 O.V. = 136.6

Cell/Jar Voltage Internal Res. Intercell 1 Temp. (F) S.G.

1 2.290 0 0 0.0 0.000

2 2.259 0 0 0.0 0.000

3 2.213 0 0 0.0 0.000

4 2.172 0 0 0.0 0.000

5 2.182 0 0 0.0 0.000

6 2.173 0 0 0.0 0.000

7 2.256 0 0 0.0 0.000

8 2.225 0 0 0.0 0.000

9 2.287 0 0 0.0 0.000

10 2.332 0 0 0.0 0.000

11 2.251 0 0 0.0 0.000

12 2.326 0 0 0.0 0.000

13 2.274 0 0 0.0 0.000

14 2.263 0 0 0.0 0.000

15 2.313 0 0 0.0 0.000

16 2.315 0 0 0.0 0.000

17 2.266 0 0 0.0 0.000

18 2.172 0 0 0.0 0.000

19 2.272 0 0 0.0 0.000

20 2.326 0 0 0.0 0.000

21 2.315 0 0 0.0 0.000

22 2.161 0 0 0.0 0.000

23 2.309 0 0 0.0 0.000

24 2.344 0 0 0.0 0.000

25 2.328 0 0 0.0 0.000

26 2.350 0 0 0.0 0.000

27 2.298 0 0 0.0 0.000

28 2.338 0 0 0.0 0.000

29 2.326 0 0 0.0 0.000

30 2.234 0 0 0.0 0.000

31 2.318 328 13 87.6 1.204

32 2.332 327 13 88.2 1.206

33 2.261 309 12 88.2 1.208

34 2.244 313 14 88.3 1.207

35 2.312 330 13 88.0 1.208

36 2.202 311 13 88.2 1.206

37 2.216 311 13 88.1 1.208

38 2.310 329 13 87.9 1.208

39 2.287 332 14 87.7 1.206

40 2.218 331 13 87.5 1.209

41 2.233 330 13 87.2 1.205

42 2.249 332 13 87.4 1.209

43 2.264 329 12 87.2 1.209

44 2.254 335 13 87.2 1.208

45 2.340 332 287 87.5 1.204

46 2.290 329 12 87.1 1.209

47 2.274 329 12 86.8 1.209

48 2.264 331 12 87.6 1.206

49 2.246 331 13 87.4 1.205

50 2.238 313 13 87.0 1.209

51 2.320 331 13 87.4 1.208

52 2.337 330 13 88.1 1.205

53 2.159 313 13 87.9 1.205

54 2.344 332 13 87.8 1.209

55 2.354 330 13 88.0 1.208

56 2.321 334 13 88.3 1.208

57 2.349 333 13 88.1 1.208

58 2.283 331 14 87.7 1.210

59 2.261 350 13 88.0 1.211

60 2.332 332 9 87.4 1.207

Summary: High 2.354 350 287 88.3 1.211

Avg 2.276 328 22 87.7 1.207

Low 2.159 309 9 86.8 1.204

This report was generated on: 09/26/2023 3:16:33 PM Page 1

26-P-00198 Addendum #1 (Attachment F) Station Battery Annual

Model Number: Enersys EC-11M d/c 5/11

This report was generated on: 09/26/2023 3:16:33 PM Page 2

This report was generated on: 09/26/2023 3:16:33 PM Page 3

This report was generated on: 09/26/2023 3:16:33 PM Page 4