The Salient Characteristics document details technical specifications for an AC Current Transducer required by the government. The transducer must provide a self-powered 0-5Vdc output with specific input and output characteristics, including an AC amp range of 0-30 amps, 50-60Hz frequency, and 0.25% full-scale accuracy. Key specifications include a self-powered 5Vdc output, response time of 300ms, and temperature effect of +/- 1% reading between -20C to +60C.

Additional requirements include a maximum size of 4 inches long by 1 inch wide by 3 inches high, inclusion of linearity and set point features, and a minimum 90-day warranty covering all components. The contractor must use standard commercial packaging methods to ensure delivery in good condition, and the equipment will be inspected for compliance with design, functionality, construction, materials, components, and workmanship. Any deviation from the specified requirements will result in rejection of the equipment.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SALIENT CHARACTERISTICS

AC CURRENT TRANSDUCER

1. GOVERNMENT NEEDS: An AC Current Transducer which provides a self-powered 0-5Vdc output, in conjunction with the specific options and accessories described in this purchase description.

2. SPECIFICATIONS: The following specifications detail the basic characteristics of the AC Current Transducer.

INPUT

• AC AMPS = 0 – 30 AMPS.

• Current Overload = 1.3x Rating Continuous, 5x rating for 10 sec./Hr.

• Frequency = 50-60Hz

• Dielectric Test. Input/Output/Case = 1800 VAC

• Self-Powered

OUTPUT

• Self-powered 5Vdc

• Load on Output = >10Mohms

• Ripple = < +/- 0.5% F.S

• Response Time 90% (Typical) = 300ms

• 5A & 10A = <750ms

• Accuracy = 0.25%F.S.

• Temperature effect (-20C to +60C) = +/- 1% Reading

• Weight = Approximately 5 OZ

3. OPTIONS/ACCESSORIES:

• Transducer includes Linearity, Set point and Repeatability @ 60 Hz.

• Size no greater than 4 inch length, 1 inch width and 3 inch height.

4. WARRANTY: A 90 day minimum warranty shall be furnished with the provided equipment. The warranty shall cover all components. The warranty period begins when the LEAD Contracting Officer provides official confirmation that the equipment has satisfied all operational provisions of the contract.

5. PRESERVATION, PACKAGING AND DELIVERY: The contractor shall utilize standard commercial methods for preservation and packaging appropriate for the provided equipment and acceptable to commercial carriers. As a minimum, all areas susceptible to damage from exposure to the elements shall be preserved and/or packed to prevent damage. The contractor shall be responsible for ensuring the equipment is delivered to LEAD in good condition.

6. INSPECTION AND ACCEPTANCE: The provided equipment shall be examined for design, functionality, construction, materials, components, and workmanship to determine compliance with the contract and this specification. Any deviation from these requirements shall be cause for rejection