Salient Characteristics
The following battery salient characteristics are provided to ensure that the replacement batteries are compatible with the existing batteries that will not be replaced.
Module Voltage 6 Volts
Number of Cells 3
Number of Plates per Cell 27
Cell Voltage 1.75
Capacity @ 25 Hr. Rate 1468 AHr
Capacity @ 100 Hr. Rate 1748 AHr
Interlock Module Length 33.15 in.
Interlock Module Depth 27.88 in.
Interlock Module Height 9.54 in.
Interlock Module Weight 644 lbs.
Non-Interlock Module Length 33.15 in.
Non-Interlock Module Depth 27.12 in.
Non-Interlock Module Height 9.48 in.
Non-Interlock Module Weight 618 lbs.