This document provides details for a federal solicitation for construction services. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22 is seeking construction services for Project 664-20-501 Electronic Health Records Modernization Infrastructure Upgrades at the VA San Diego Healthcare System, VA San Diego Medical Center located in San Diego, California. Work includes general construction, alterations, mechanical, electrical and utility systems work, necessary demolition and removal of existing structures. The project magnitude is between $10,000,000 to $20,000,000. The solicitation will be issued on July 6, 2021 via sam.gov as a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses listed as verified in Vendor Information Pages. The point of contact is James Barber, Contracting Specialist, Network Contracting Office 22 Long Beach who can be reached at james.barber@va.gov.

View the file

Other files for this federal contract opportunity

Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T G

B

EX. PANEL D4CEX

5-20R 5-20R

1-FCUC 8.2

M

1-FCUC 8.1

M

J

M

J

L01A L01A

TR124-2a TR124-2a b

5-20R

5-20R

5-20R

1-DX 8.3

1-DX 8.1

1-DX 8.2

PANEL TR124 TR124-1

TR124-3

TR124-5

TR124-7

TR124-7

TR124-9

TR124-9

TR124-11

TR124-13

M

J

M

J

M

J

TR124-4

TR124-4

TR124-4

L01AL01A

b TR104-2b

TR104-2b

5-20R

5-20R

5-20R

1-DX 7.1

PANEL TR104

TR104-1

TR104-3

TR104-5

TR104-7

TR104-7

TR104-9

TR104-9

TR104-11

TR104-13

M

J

1-DX 7.2

M

J

1-DX 7.3

M

J

TR104-4

TR104-4

TR104-4

T G

B

5-20R5-20R

1-FCUC 9.2

1-FCUC 9.1

M

5-20R

J

M

J

L02

L02 L023

L01AL01A

b

L01AL01A

TR125-2a TR125-2a b

5-20R

5-20R

5-20R

5-20R

PANEL TR125

TR125-3

TR125-1

TR125-5

TR125-7

TR125-9

TR125-11

TR125-11

TR125-9

TR125-13

TR125-15

1-DX 10.3

1-DX 10.1

1-DX 10.2

M

J

M

J

M

J

TR125-4

TR125-4

TR125-4

TR 10-5

L01AL01A

b TR105-2b 5-20R

5-20R

5-20R

5-20R

PANEL TR105

TR105-1

TR105-3

TR105-5

TR105-7 TR105-2b

TR105-9

TR105-9

TR105-11

TR105-11

TR105-15

TR105-13

1-DX 9.1

M

J

1-DX 9.2

M

J

1-DX 9.3

M

J

TR104-4

TR104-4

TR104-4

DRAWING NUMBER

VA FORM 08 - 6231

A

OFFICE OF

CONSTRUCTION AND

REAL ESTATE

MANAGEMENT

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 5 6 7 8 9 10

664-20-501

F

BUILDING NUMBER

PROJECT NUMBERPROJECT TITLE

PROJECT LOCATION

ISSUE DATE CHECK BY DRAWN BY

PROJECT PHASE

BUILDING CONSTRUCTION

SHEET TITLE

APPROVED PROJECT DIRECTOR

U.S. Department of Veterans Affairs

ARCHITECT/ DESIGNER OF RECORD

REVISIONS DATE

1 0 5 3 T E N T H A V E N U E

S A N D I E G O , C A 9 2 1 0 1

P H O N E 6 1 9 . 2 3 8 . 3 8 1 1

D I S A B L E D V E T E R A N + E M P L OY E E O W N E D

www.davyarchitecture.com

NORTH

VASDHCS PLANNING AND ENGINEERING

1455 Frazee Rd., Suite 600

San Diego, CA 92108 ph 619.232.4673 www.coffman.com

CEI Project # 201794

ENGINEER/DESIGNER OF RECORD

TYPE IA - FULLY SPRINKLERED

VA SAN DIEGO

EHRM INFRASTRUCTURE UPGRADES

3350 LA JOLLA VILLAGE DRIVE, SAN DIEGO, CA 92161

JUNE 09, 2021

100% CONSTRUCTION DOCUMENTS

E-01.43

JC MC

BLDG 1 - ENLARGED EQUIPMENT RM PLAN

GENERAL NOTES

KEY NOTES

MAIN

BLDG 1 - RM TR 10-4 ENLARGED PLAN

SCALE: 3/8" = 1'-0"

BLDG 1 - RM TR 12-4 ENLARGED PLAN

SCALE: 3/8" = 1'-0"

BLDG 1 - RM 4044 ENLARGED PLAN

SCALE: 3/8" = 1'-0"

BLDG 1 - RM 4155 ENLARGED PLAN

SCALE: 3/8" = 1'-0"

BLDG 1 - RM TR 12-5 ENLARGED PLAN

SCALE: 3/8" = 1'-0"

BLDG 1 - RM TR 10-5 ENLARGED PLAN

SCALE: 3/8" = 1'-0"

EXISTING LIGHTING AND LIGHTING CONTROLS TO REMAIN.

SECURE COPPER GROUNDING STRAP FOR ESD FLOORING TO ELECTRICAL OUTLET LOCATED AT +18" AFF.

COORDINATE INSTALLATION WITH ARCHITECT AND FLOORING MANUFACTURER PRODUCT INFORMATION.

DISCONNECT AND REMOVE EXISTING LIGHTING. PROVIDE NEW LIGHTING AS INDICATED AND CONNECT TO

EXISTING LIGHTING CIRCUIT.

1. ALL ELECTRICAL DEVICES AND EQUIPMENT OUTSIDE OF SCOPE ARE NOT SHOWN FOR CLARITY.

AutoCAD SHX Text

TELECOM

http://www.coffman.com

5 EAST AREA

TGB

1-DX 11.1

1-DX 11.2

5-20R

5-20R

5-20R

M J

M

J

TR 12-6

L01A L01A

TR126-2a TR126-2a a

5-20R

1-DX 14.3

1-DX 14.2

1-DX 14.1

5-20R

5-20R

TR126-1

TR126-3

TR126-5

TR126-7

TR126-9

TR126-7

TR126-11

TR126-9

TR126-13

PANEL TR126

M

J

M

J M

J

TR126-4

TR126-4

TR126-4

TR 10-6

L01A L01A b TR106-2b TR106-2b

5-20R

1-DX 13.3

1-DX 13.2

1-DX 13.1

5-20R

5-20R

PANEL TR106

TR106-1

TR106-3

TR106-5

TR106-7

TR106-9

TR106-7

TR106-9

TR106-11

TR106-13

M

J

M

J

M

J

TR106-4

TR106-4

TR106-4

TGB

6CEXFA-20

6CEXFA

5-20R5-20R

1-DX 12.2

1-DX 12.1

M J

M J

6CEXFA-20

DRAWING NUMBER

VA FORM 08 - 6231

A

OFFICE OF

CONSTRUCTION AND

REAL ESTATE

MANAGEMENT

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 5 6 7 8 9 10

664-20-501

F

BUILDING NUMBER

PROJECT NUMBERPROJECT TITLE

PROJECT LOCATION

ISSUE DATE CHECK BY DRAWN BY

PROJECT PHASE

BUILDING CONSTRUCTION

SHEET TITLE

APPROVED PROJECT DIRECTOR

U.S. Department of Veterans Affairs

ARCHITECT/ DESIGNER OF RECORD

REVISIONS DATE

1 0 5 3 T E N T H A V E N U E

S A N D I E G O , C A 9 2 1 0 1

P H O N E 6 1 9 . 2 3 8 . 3 8 1 1

D I S A B L E D V E T E R A N + E M P L OY E E O W N E D

www.davyarchitecture.com

NORTH

VASDHCS PLANNING AND ENGINEERING

1455 Frazee Rd., Suite 600

San Diego, CA 92108 ph 619.232.4673 www.coffman.com

CEI Project # 201794

ENGINEER/DESIGNER OF RECORD

TYPE IA - FULLY SPRINKLERED

VA SAN DIEGO

EHRM INFRASTRUCTURE UPGRADES

3350 LA JOLLA VILLAGE DRIVE, SAN DIEGO, CA 92161

JUNE 09, 2021

100% CONSTRUCTION DOCUMENTS

E-01.44

JC MC

BLDG 1 - ENLARGED EQUIPMENT RM PLAN

GENERAL NOTES

KEY NOTES

MAIN

BLDG 1 - RM 5 EAST AREA ENLARGED PLAN

SCALE: 1/2" = 1'-0"

EXISTING LIGHTING AND LIGHTING CONTROLS TO REMAIN.

SECURE COPPER GROUNDING STRAP FOR ESD FLOORING TO ELECTRICAL OUTLET LOCATED AT +18" AFF.

COORDINATE INSTALLATION WITH ARCHITECT AND FLOORING MANUFACTURER PRODUCT INFORMATION.

1. ALL ELECTRICAL DEVICES AND EQUIPMENT OUTSIDE OF SCOPE ARE NOT SHOWN FOR CLARITY.

BLDG 1 - RM TR 12-6 ENLARGED PLAN

SCALE: 1/2" = 1'-0"

BLDG 1 - RM TR 10-6 ENLARGED PLAN

SCALE: 1/2" = 1'-0"

BLDG 1 - RM 6135 ENLARGED PLAN

SCALE: 1/2" = 1'-0"

TELECOMMUNICATION DEVICES

SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES

T

WORK DEFINITION

AC 3" ABOVE COUNTER BACKSPLASH

AFF ABOVE FINISHED FLOOR

AG ABOVE GRADE

AHJ AUTHORITY HAVING JURISDICTION

A/V AUDIO/VISUAL

CATV COMMUNITY ACCESS TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CEC CALIFORNIA ELECTRICAL CODE

CKT CIRCUIT

CLG CEILING

COMM COMMUNICATIONS

C CONDUIT

CO CONDUIT ONLY

COR CONTRACTING OFFICER'S REPRESENTATIVE

CTRL CONTROL

CU COPPER

D DATA, DEDICATED

DIST DISTRIBUTION

DOR DESIGNER OF RECORD

EG EQUIPMENT GROUND

ENT ELECTRIC NON-METALLIC CONDUIT

EX,EXIST. EXISTING

FA FIRE ALARM

FMC FLEXIBLE METAL CONDUIT

FO FIBER OPTIC(AL)

FOPP FIBER OPTIC PATCH PANEL

G,GND GROUND

IDF INTERMEDIATE DISTRIBUTION FRAME/FACILITY

ISP INSIDE PLANT

J-BOX JUNCTION BOX

LTG LIGHTING

MCC MOTOR CONTROL CENTER

MDF MAIN DISTRIBUTION FRAME/FACILITY

MTD MOUNTED

NEC NATIONAL ELECTRICAL CODE

NIC NOT IN CONTRACT

OC OBJECT CENTER

OSP OUTSIDE PLANT

PH PHASE

PNL PANEL, PANELBOARD

POC POINT OF CONNECTION

POTS PLAIN OLD TELEPHONE SYSTEM

RECEPT RECEPTACLE

RO RACEWAY ONLY

SM SINGLE MODE

TELECOM TELECOMMUNICATIONS

TGB TELECOMMUNICATIONS GROUNDING BUSBAR

TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

TV TELEVISION

TYP TYPICAL

UG UNDER GROUND

UON UNLESS OTHERWISE NOTED

V VOICE

W WIRE, WATT, WALLPHONE

WAP WIRELESS ACCESS POINT

XR EXISTING RELOCATED

ABBREVIATIONS

HEAVY LINEWORK INDICATES NEW WORK

LIGHT LINEWORK INDICATES EXISTING TO REMAIN

CROSS HATCHING INDICATES EXISTING DEVICE OR RACEWAY TO BE REMOVED -

MAINTAIN CIRCUIT CONTINUITY

CONDUIT: ROUTED BELOW FINISHED FLOOR LEVEL

NEW TELECOMMUNICATIONS SYSTEM RACEWAY

NEW SURFACE MOUNTED COMBINATION TELEPHONE/COMPUTER

DATA OUTLET 3 - RJ-45 JACKS. OUTLET SHALL BE MOUNTED 44"

AFF TO THE BOTTOM.

EXISTING CONDUIT: ROUTED UNDERGROUNDUG

KEYNOTE

NEW JUNCTION PULL BOX. MINIMUM SIZE FOR FIBER CABLE

24"Wx24"Hx6"D

CMH EXISTING COMMUNICATIONS MANHOLE

A

C

EXISTING WIRELESS ACCESS POINT. LOCATION OF NEW TELECOM

BISCUIT.

EXISTING SECURITY CAMERA

NEW TELECOMMUNICATIONS GROUNDING BAR

NEW KEY PAD / SCRAMBLE PAD

DS

CR

ES

TGB

NEW DOOR POSITION SWITCH (RECESSED IN DOOR FRAME)

NEW ELECTRIC STRIKE

NEW CLOSED CIRCUIT TELEVISION CAMERA

NEW CABLE TRAY (SNAKE TRAY TYPE)

MS EXISTING MOTION DETECTOR

NEW TELECOM RACK

NEW CONDUIT SLEEVE

1. PROVIDE ALL MATERIALS, LABOR AND EQUIPMENT REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION. MATERIALS AND WORKMANSHIP SHALL FULLY COMPLY WITH THE REQUIREMENTS OF OIT INFRASTRUCTURE STANDARD FOR TELECOM SPACES, BICSI/TDMM, AND TIA/EIA STANDARDS

UNLESS OTHERWISE INDICATED ON THE DRAWINGS.

2. THE ELECTRICAL INSTALLATION SHALL COMPLY WITH THE CURRENT NATIONAL ELECTRICAL CODE, NFPA 72, ASME A17.1, STATE AMENDMENTS, CURRENT VA STANDARDS AND NECA STANDARDS OF

INSTALLATION.

3. ALL BACKBONE CABLE RUNS SHALL HAVE 10' MAINTENANCE LOOPS AT BOTH ENDS. ALL HORIZONTAL

CABLE RUNS SHALL HAVE 10' MAINTENANCE LOOPS AT THE TR END.

4. ALL ELECTRICAL / TELECOM / SECURITY EQUIPMENT AND MATERIALS SHALL BE LISTED AND LABELED

FOR THEIR INTENDED APPLICATION BY A NATIONALLY RECOGNIZED TESTING LABORATORY

ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.

5. PLANS DO NOT REFLECT ALL EXISTING UTILITIES AND STRUCTURES. VERIFY LOCATION OF ALL EXISTING UTILITIES AND STRUCTURES AFFECTING THE WORK. NOTIFY THE CONTRACTING OFFICER IN

WRITING OF ANY DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THOSE SHOWN IN THE

CONTRACT DOCUMENTS WHICH ADVERSELY IMPACT THE WORK.

6. EXISTING EQUIPMENT INFORMATION SHOWN ON THESE DRAWINGS SHOULD BE FIELD VERIFIED.

CONFIRM NEW EQUIPMENT LOCATIONS WITH OWNER AND ADJUST AS REQUIRED.

7. MAINTAIN A MINIMUM 6" CLEARANCE BETWEEN CONDUIT AND PIPING. MAINTAIN A MINIMUM 12" CLEARANCE BETWEEN CONDUIT AND HEAT SOURCES SUCH AS FLUES, HEATING PIPES, AND HEATING

APPLIANCES.

8. ANY PENETRATION OF THE BUILDING VAPOR BARRIER SYSTEM SHALL BE APPROPRIATELY SEALED TO RETAIN THE INTEGRITY OF THE WALL SYSTEM. THIS INCLUDES, BUT IS NOT LIMITED TO, CONDUITS AND

RECESSED BACK BOXES.

9. DRAWINGS ARE SCHEMATIC ONLY AND DO NOT SHOW ALL EXISTING AND NEW CONDUIT AND

CONNECTIONS BETWEEN RESPECTIVE DEVICES AND FIXTURES. CONTRACTOR SHALL DETERMINE THE EXACT ROUTING OF CONDUIT, CABLE TRAY, CABLE, AND WIRING CONNECTIONS BETWEEN RESPECTIVE

DEVICES AND FIXTURES FOR A COMPLETE AND OPERATIONAL SYSTEM.

10. IDS AND ACS ENCLOSURES, CABINETS, HOUSINGS, BOXES, AND FITTINGS HAVING HINGED DOORS OR REMOVABLE COVERS WHICH CONTAIN CIRCUITS OR CONNECTIONS OF THE SYSTEM AND ITS POWER SUPPLIES SHALL BE PROVIDED WITH COVER OPERATED, CORROSION RESISTANT TAMPER SWITCHES ARRANGED TO INITIATE AN ALARM SIGNAL WHEN THE DOOR OR COVER IS REMOVED. PROVIDE TAMPER

SWITCHES IN ACCORDANCE WITH SPECIFICATION SECTION 28 16 00.

11. COORDINATE DOOR HARDWARE SELECTION AND INSTALLATION REQUIREMENTS BETWEEN

ARCHITECTURAL, SECURITY, TELECOM, FIRE ALARM, AND ELECTRICAL. DOOR PROCUREMENT AND INSTALLATIONS SHALL BE COORDINATED TO FACILITATE IDS AND ACS SYSTEM INSTALLATION. REFER

TO DRAWINGS AND SPECIFICATION 28 05 00 FOR ADDITIONAL INFORMATION.

12. COORDINATE CABLE TRAY ROUTING AND INSTALLATION TO AVOID CONFLICTS BETWEEN ALL TRADES.

MAINTAIN A MINIMUM 12" WORKING CLEARANCE ABOVE TOP OF CABLE TRAY.

13. CONTRACTOR SHALL VERIFY THE SIZE OF ALL CONDUCTORS, CONDUIT, AND JUNCTION BOXES (40 % MAXIMUM FILL). INSTALLATION SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE (NEC)

AND ALL LOCAL CODES HAVING JURISDICTION.

14. CONTRACTOR SHALL PROVIDE AND INSTALL EQUIPMENT AND HARDWARE IN ORDER TO MEET THE INTENT OF THE DESIGN AND TO PROVIDE THE OWNER WITH A COMPLETE AND FULLY OPERATIONAL SYSTEM AS SPECIFIED. QUESTIONS REGARDING THE INTENT OF THE DESIGN SHALL BE PROMPTLY

BROUGHT TO THE ATTENTION OF THE DOR.

15. ALL CONDUIT RUNS AND CABLE TRAY SHOWN ARE DIAGRAMMATICAL. REPORT ANY MAJOR DEVIATION

TO DOR FOR REVIEW.

16. THE GENERAL LOCATION OF THE BACKBONE CONDUIT FOR THE TELECOM ROOMS HAS BEEN ON THESE DRAWINGS. CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF THE CONDUIT(S) AND LADDER RACK

TYPE CABLE TRAY(S).

17. PROVIDE PHASING PLAN TO VA COR. REFER TO PLANS AND SPECIFICATIONS FOR DETAILS OF ALL

WORK REQUIRED FOR EACH COVERAGE AREA AND TELECOM ROOM/AREA.

18. BUILDING 1 NOTE ONLY - DEMOLITION OF EXISTING CABLE TRAY, AS SHOWN, SHALL BE PERFORMED AFTER ALL NEW CABLE HAS BEEN INSTALLED AND EXISTING ABANDONED CABLE IS REMOVED. A SURVEY SHALL BE PERFORMED WITH THE VA COR TO CONFIRM THE CABLE TRAY TO BE REMOVED.

REFER TO DIVISION 1 SPECIFICATIONS FOR ADDITIONAL BIDDING REQUIREMENTS FOR THIS WORK.

19. ALL DATA CONNECTIONS (MODIFIED IN THIS SCOPE OF WORK) ARE REQUIRED TO BE FIELD VERIFIED AND DOCUMENTED IN AS-BUILT DRAWINGS. A TONER, OR SIMILAR APPROVED DEVICE/METHOD, SHALL

BE USED TO TRACE EXISTING DATA CONNECTIONS PRIOR TO DEMOLITION.

20. WHERE THE TERM "DATA DROP" IS USED THROUGHOUT THIS PACKAGE, THIS TERM IS INCLUSIVE OF

DATA AND PHONE CONNECTIONS.

21. NOT ALL DIMENSIONS ARE SHOWN ON THESE PLANS. REFER TO ARCHITECTURAL PLANS FOR

ADDITIONAL DIMENSIONS .

GENERAL NOTES

EXISTING REQUEST TO EXITREX

EXISTING CABLE TRAY

EXISTING CABLE TRAY (CABLE LADDER RACK)

EXISTING ACCESS CONTROL PANEL

* - INDICATES WHERE MULTIPLE PANELS ARE LOCATED IN AN

AREA. FOR EXAMPLE X3 WOULD INDICATE THERE ARE THREE (3)

ACCESS CONTROL PANELS IN THIS AREA

ACP

NEW CABLE TRAY (CABLE LADDER RACK)

EXISTING CABLE TROUGH / GUTTER

WORKING CLEARANCE

EXISTING COMBINATION TELEPHONE/COMPUTER DATA

OUTLET, 3 - RJ-45 JACKS

EXISTING TELECOMMUNICATIONS GROUNDING BAR

EXISTING KEY PAD / SCRAMBLE PADCR

ES

TGB

EXISTING ELECTRIC STRIKE

EXISTING TELECOM RACK

NEW VERTICAL CABLE MANAGER

EXISTING VERTICAL CABLE MANAGER

NEW PROTECTED ENTRANCE TERMINALPET

NEW TELECOMMUNICATIONS MAIN GROUNDING BAR (TMGB)TMGB

DS EXISTING DOOR POSITION SWITCH (RECESSED IN DOOR FRAME)

EXISTING JUNCTION PULL BOX

WORK AREA CLEARANCE

DRAWING NUMBER

VA FORM 08 - 6231

A

OFFICE OF

CONSTRUCTION AND

REAL ESTATE

MANAGEMENT

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 5 6 7 8 9 10

664-20-501

F

BUILDING NUMBER

PROJECT NUMBERPROJECT TITLE

PROJECT LOCATION

ISSUE DATE CHECK BY DRAWN BY

PROJECT PHASE

BUILDING CONSTRUCTION

SHEET TITLE

APPROVED PROJECT DIRECTOR

U.S. Department of Veterans Affairs

ARCHITECT/ DESIGNER OF RECORD

REVISIONS DATE

1 0 5 3 T E N T H A V E N U E

S A N D I E G O , C A 9 2 1 0 1

P H O N E 6 1 9 . 2 3 8 . 3 8 1 1

D I S A B L E D V E T E R A N + E M P L OY E E O W N E D

www.davyarchitecture.com

NORTH

VASDHCS PLANNING AND ENGINEERING

1455 Frazee Rd., Suite 600

San Diego, CA 92108 ph 619.232.4673 www.coffman.com

CEI Project # 201794

ENGINEER/DESIGNER OF RECORD

TYPE IA - FULLY SPRINKLERED

VA SAN DIEGO

EHRM INFRASTRUCTURE UPGRADES

3350 LA JOLLA VILLAGE DRIVE, SAN DIEGO, CA 92161

JUNE 09, 2021

100% CONSTRUCTION DOCUMENTS

T-00.00

JD MC

TELECOMMUNICATION SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES

MAIN,11,14,23,25,27

Fire Lane

Pedestrian Bridge

South Road

N o r t h

R o a d

G i l m a n

D r i v e

E a s t

R o a d

COURTYARD

UCSD OWNED

S

A

N

D

A

G

M

C

C o l l e y

S a t i o n

C

O M

M

C

O N

D U

I T

D

I A

P

V

U R

F A

C E

CALL BOX

D

U

E

L

E

N

T

R

A

L

O

N

T

R

O

L

F

A

D

I A

P

V

M

I N

UG

4-5" DUCTS

UG

D

U

C

T

S

CALL BOX

UG

CMHCMH

UG

UG

UG

CMH

CMH

T T

T T

T

CMH

T T

T

CMH

T

T

T

T

T

T

T

DRAWING NUMBER

VA FORM 08 - 6231

A

OFFICE OF

CONSTRUCTION AND

REAL ESTATE

MANAGEMENT

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 5 6 7 8 9 10

664-20-501

F

BUILDING NUMBER

PROJECT NUMBERPROJECT TITLE

PROJECT LOCATION

ISSUE DATE CHECK BY DRAWN BY

PROJECT PHASE

BUILDING CONSTRUCTION

SHEET TITLE

APPROVED PROJECT DIRECTOR

U.S. Department of Veterans Affairs

ARCHITECT/ DESIGNER OF RECORD

REVISIONS DATE

1 0 5 3 T E N T H A V E N U E

S A N D I E G O , C A 9 2 1 0 1

P H O N E 6 1 9 . 2 3 8 . 3 8 1 1

DI S A B L E D V E T E R A N + E M P L OY E E OW N E D

www.davyarchitecture.com

NORTH

VASDHCS PLANNING AND ENGINEERING

1455 Frazee Rd., Suite 600

San Diego, CA 92108 ph 619.232.4673 www.coffman.com

CEI Project # 201794

ENGINEER/DESIGNER OF RECORD

TYPE IA - FULLY SPRINKLERED

VA SAN DIEGO

EHRM INFRASTRUCTURE UPGRADES

3350 LA JOLLA VILLAGE DRIVE, SAN DIEGO, CA 92161

JUNE 09, 2021

100% CONSTRUCTION DOCUMENTS

T-00.02

JC MC

TELECOMMUNICATION SITE PLAN

GENERAL NOTES

TELECOMMUNICATION SITE PLAN

SCALE: 1" = 40'

1. EXISTING UNDERGROUND AND ABOVE GROUND TELECOM INFRASTRUCTURE SHOWN IS BASED ON AS

BUILT DATA. PRIOR TO CONSTRUCTION, ALL UNDERGROUND AND ABOVE GROUND ROUTING SHALL BE

CONFIRMED AND PRESENTED TO THE VA COR.

2. ALL OUTSIDE PLANT FIBER SHALL BE PULLED IN EXISTING INFRASTRUCTURE.

3. PROVIDE PULL STRING WITH NEW FIBER CABLE PULLS.

4. REFER TO SHEETS T-00.60, T-00.61, AND T-00.62 FOR IT SYSTEM RISER DIAGRAMS.

MAIN,11,14,23,25,27

SEE SHEETS T-11.1* FOR

OVERALL FLOOR PLANS

SEE SHEETS T-27.1* FOR

OVERALL FLOOR PLANS

MDF ROOM 1119.B

1ST FLOOR

MDF ROOM BB102A IN

BASEMENT

MDF ROOM B165 IN

BASEMENT

MDF ROOM 126

1ST FLOOR

MDF ROOM 104

1ST FLOOR

SEE SHEET T-23.11 FOR

OVERALL FLOOR PLAN

SEE SHEET T-25.11 FOR

OVERALL FLOOR PLAN

MDF ROOM 101 (FOR

BLDG 14) 1ST FLOOR

SEE SHEET T-14.11 FOR

OVERALL FLOOR PLAN

SEE SHEETS T-01.1* FOR

OVERALL FLOOR PLANS

KEY NOTES

PROVIDE SIX (6) 2" INNERDUCTS FOR NEW BACKBONE FIBER FROM BUILDING 11 ROOM BB102A TO TELECOM

ROOMS IN BUILDINGS 1, 14, 23, AND 25. INNERDUCT SHALL BE SECURED TO EXISTING PIPE RACK. LOCATION

OF NEW INNERDUCT SHALL NOT IMPEDE ACCESS TO EXISTING PIPING ON RACK.

INNERDUCT 1 - TWO (2) 96 STRAND FIBER TO BUILDING 1 ROOM B165.

INNERDUCT 2 - ONE (1) 96 STRAND FIBER AND ONE (1) 72 STRAND FIBER TO BUILDING 1 ROOM B165.

INNERDUCT 3 - SEVEN (7) 24 STRAND FIBER TO BUILDING 1 TELECOM ROOMS.

INNERDUCT 4 - SEVEN (7) 24 STRAND FIBER TO BUILDING 1 TELECOM ROOMS.

INNERDUCT 5 - SIX (6) 24 STRAND FIBER TO BUILDING 1 TELECOM ROOMS.

INNERDUCT 6 - THREE (3) 24 STRAND FIBER TO BUILDINGS 14, 23, AND 25 TELECOM ROOMS.

FOR CONTINUATION, REFER TO SHEET T-01.10.

FOR CONTINUATION, REFER TO SHEET T-11.10.

EXISTING PATHWAY BETWEEN BUILDING 27 AND BUILDING 11. PROVIDE ONE (1) 24 STRAND OS2 FIBER CABLE

IN EXISTING INFRSTRUCTURE. EXISTING SINGLE MODE AND MULTIMODE FIBER CABLE SHALL BE REMOVED

BACK TO SOURCE ONCE NEW FIBER CABLE IS INSTALLED. BUILDING 27 SHALL REMAIN OPERATIONAL DURING

THIS FIBER UPGRADE. CONTACT VA COR IMMEDIATELY IF SHUT DOWN IS REQUIRED.

EXISTING PATHWAY BETWEEN BUILDING 14 AND BUILDING 1. PROVIDE ONE (1) 24 STRAND OS2 FIBER CABLE

IN AND ONE (1) 25 PAIR CAT 3 COPPER CABLE IN EXISTING INFRASTRUCTURE. EXISTING FIBER CABLE AND

COPPER CABLE SHALL BE REMOVED BACK TO SOURCE ONCE NEW FIBER CABLE IS INSTALLED. BUILDING 14

SHALL REMAIN OPERATIONAL DURING THIS FIBER UPGRADE. CONTACT VA COR IMMEDIATELY IF SHUT DOWN

IS REQUIRED.

EXISTING PATHWAY BETWEEN BUILDING 23 AND BUILDING 1. PROVIDE ONE (1) 24 STRAND OS2 FIBER CABLE

IN EXISTING INFRASTRUCTURE. EXISTING FIBER CABLE SHALL BE REMOVED BACK TO SOURCE ONCE NEW

FIBER CABLE IS INSTALLED. BUILDING 23 SHALL REMAIN OPERATIONAL DURING THIS FIBER UPGRADE.

CONTACT VA COR IMMEDIATELY IF SHUT DOWN IS REQUIRED.

EXISTING PATHWAY BETWEEN BUILDING 25 AND BUILDING 1. PROVIDE ONE (1) 24 STRAND OS2 FIBER CABLE

IN EXISTING INFRASTRUCTURE. EXISTING FIBER CABLE SHALL BE REMOVED BACK TO SOURCE ONCE NEW

FIBER CABLE IS INSTALLED. BUILDING 25 SHALL REMAIN OPERATIONAL DURING THIS FIBER UPGRADE.

CONTACT VA COR IMMEDIATELY IF SHUT DOWN IS REQUIRED.

ROOM B135

DRAWING NUMBER

VA FORM 08 - 6231

A

OFFICE OF

CONSTRUCTION AND

REAL ESTATE

MANAGEMENT

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 5 6 7 8 9 10

664-20-501

F

BUILDING NUMBER

PROJECT NUMBERPROJECT TITLE

PROJECT LOCATION

ISSUE DATE CHECK BY DRAWN BY

PROJECT PHASE

BUILDING CONSTRUCTION

SHEET TITLE

APPROVED PROJECT DIRECTOR

U.S. Department of Veterans Affairs

ARCHITECT/ DESIGNER OF RECORD

REVISIONS DATE

1 0 5 3 T E N T H A V E N U E

S A N D I E G O , C A 9 2 1 0 1

P H O N E 6 1 9 . 2 3 8 . 3 8 1 1

D I S A B L E D V E T E R A N + E M P L OY E E O W N E D

www.davyarchitecture.com

VASDHCS PLANNING AND ENGINEERING

1455 Frazee Rd., Suite 600

San Diego, CA 92108 ph 619.232.4673 www.coffman.com

CEI Project # 201794

ENGINEER/DESIGNER OF RECORD

TYPE IA - FULLY SPRINKLERED

VA SAN DIEGO

EHRM INFRASTRUCTURE UPGRADES

3350 LA JOLLA VILLAGE DRIVE, SAN DIEGO, CA 92161

JUNE 09, 2021

100% CONSTRUCTION DOCUMENTS

T-00.40

JC MC

TELECOMMUNICATIONS OVERVIEW TABLE

MAIN,11,14,23,25,27

GENERAL NOTES

1. THIS TABLE REFLECTS MAJOR TELECOMMUNICATIONS WORK UNDER THIS SCOPE. NOT ALL

SCOPE ITEMS ARE SHOWN.

NOTES:

* CATEGORY CABLE SHALL BE REPLACED FOR FEEDS TO ROOMS IN THE COVERAGE AREAS OF B165. CABLE FEEDING DEVICES WITHIN THIS ROOM ARE EXISTING TO REMAIN.

** OUTLETS INCLUDE NEW FACEPLATES AND CAT6A RJ-45 JACKS. FOR WIRELESS ACCESS POINTS, THE OUTLETS INCLUDE BISCUITS AND CAT6A RJ-45 JACKS.

DETAIL NOTES:

TO DATA OUTLETS

CA

T6

A

CA

T6

LADDER TRAY

SINGLEMODE OR MULTIMODE

FIBER OPTIC CABLE

REFER TO RISER FOR

QUANTITY AND TYPE

1. PROVIDE WIRING IN ACCORDANCE WITH T568A.

2. ONLY RACK 1 AND RACK 2 ARE SHOWN. REFER

TO RACK RISERS FOR ADDITIONAL RACKS.

3. TELECOM RACK ELEVATIONS ARE DIAGRAMMATIC

AND DO NOT REPRESENT EXACT EQUIPMENT

LOCATIONS. SEE TELECOM PLANS FOR

EQUIPMENT LOCATIONS.

4. THIS DETAIL APPLIES TO NEW AND EXISTING

TELECOM ROOMS. HOWEVER, EXISTING

TELECOM ROOMS MAY NOT REQUIRE NEW

CONDUIT SLEEVES, DATA RACKS, AND LADDER

TRAY. REFER TO ENLARGED PLANS OF EACH

TELECOM ROOM FOR REQUIREMENTS.

KEY NOTES:

REFER TO RACK LAYOUTS ON SHEETS T-01.70 - T-01.78,

T-11.70 - T-11.71, T-14.70, T-23.70, T-25.70, AND T-27.70 FOR

TOTAL NUMBER OF PATCH PANELS AND WIRE

MANAGEMENT FOR RACK 2 AND ADDITIONAL RACKS (IF

APPLICABLE) IN EACH TELECOM ROOM.

2U HORIZONTAL CABLE MANAGER.

7 FOOT VERTICAL WIRE MANAGEMENT. REQUIRED ON EACH

SIDE OF THE RACK AND BETWEEN RACKS.

TWO POST RACK.

2U, 48 PORT COPPER PATCH PANEL WITH CAT 6A

KEYSTONES.

1U, 24 LC CONNECTOR FIBER OPTIC PATCH PANEL. LC

CONNECTORS SHALL BE PROVIDED.

5 FOOT, VERTICAL RACK MOUNTED POWER DISTRIBUTION

UNIT (PDU).

2U UNINTERRUPTIBLE POWER SUPPLY(UPS). PROVIDE ONE

(1) UPS IN EACH RACK 1 AND RACK 2. IF THERE ARE RACKS

1A AND 1B, PROVIDE UPS IN THESE RACKS AND OMIT THE

UPS IN RACK 2.

8 FOOT, 3/4 INCH FIRE RATED PLYWOOD BACKBOARD.

BOARD MUST BE PAINTED BUT ALLOW FOR FIRE RATING

LABELS TO BE VISIBLE.

CONDUIT SLEEVES FOR NEW TELECOM ROOMS ONLY.

REFER TO PLAN SHEETS FOR QUANTITY. REUSE EXISTING

SLEEVES FOR EXISTING TELECOM ROOMS.

1U, 24 PORT, 110-STYLE COPPER PATCH PANEL WITH CAT6

KEYSTONES. PROVIDE ONE PAIR PER JACK. PAIRS 24 AND

25 WILL BE A SINGLE TWO PAIR JACK IN POSITION 24

ALL HORIZONTAL CABLE SHALL BE CAT6A EXCEPT WHERE

EXISTING CABLE IS CAT6 TO BE REUSED.

WHERE RACK 1 IS SPLIT INTO RACKS 1A AND 1B, ALL

COMPONENTS SHOWN SHALL BE PROVIDED. HOWEVER,

ONLY ONE (1) FIBER PATCH PANEL AND ONE (1) 110-TYPE

PATCH PANEL SHALL BE PROVIDED PER TELECOM ROOM

LISTED IN THIS SCOPE UNLESS OTHERWISE INDICATED IN

THESE PLANS.

RACK 2 REPRESENTS ALL RACKS BEYOND RACK 1.

THEREFORE, IF RACKS 3, 4, 5, AND BEYOND ARE INDICATED

ON THESE PLANS, PROVIDE ALL COMPONENTS FOR

AFOREMENTIONED RACKS AS SHOWN FOR RACK 2. WITH

THE EXCEPTION OF THE UPS AND PDU WHICH ARE ONLY

PROVIDED FOR RACKS 1 AND 2.

EZ PATH FIRE STOPPING MATERIAL. REFER TO ENLARGED

PLANS FOR FILL REQUIREMENTS. PROVIDED ONLY FOR NEW

TELECOMMUNICATIONS ROOMS.

PROVIDE ONE (1) CABLE WATERFALL / DROPOUT FOR EACH

RACK.

REFER TO ENLARGED PLANS FOR LADDER RACK

DIMENSIONS.

INSTALL CLIENT PROVIDED CISCO SWITCHES. INSTALLATION

INCLUDES PLACING EQUIPMENT ON THE RACK,

CONNECTING PATCH CABLE, AND STACKING SWITCHES.

SWITCHES SHALL BE STACKED USING THE CISCO RING

TOPOLOGY. WHERE EXISTING SWITCHES ARE REMOVED

DURING CONSTRUCTION AND REINSTALLED, DOCUMENT

STACKING WIRING PRIOR TO REMOVAL. RECONNECT AS

PREVIOUSLY INSTALLED. STACKING CABLE FOR NEW

SWITCHES SHALL BE PROVIDED BY THE CONTRACTOR.

WIRE MANAGEMENT

LOOP (10 FT MINIMUM)

RACK 1

TYPICAL

RACK 1 OR 1A

FIBER OPTIC PATCH PANEL

SPACE ALLOCATED FOR VA EQUIPMENT

4" CONDUIT SLEEVES

(TYP)

UPS

2U HORIZONTAL CABLE MANAGER

SPACE

DEDICATED

FOR VA

PROVIDED

EQUIPMENT

UPS UPS

CA

T3

ST

CA

T6

A CA

T6

A

RACK 2

INTERSTITIAL SPACE

CABLE TRAY

(SNAKE TRAY TYPE)

(TYP.)

(TYP.)

(TYP.)

(TYP.)

25 PR

24 PORT 110 STYLE PATCH PANEL

(TYP.)

CA

T3

ST

REFER TO RISER DIAGRAMS

FOR CABLE QUANITITY

AND TYPE

(TYP.)

TGB

"D" RING (TYP.)

4" CONDUIT SLEEVES

(TYP)

LADDER TRAY

TYPICAL

RACK 1B (IF APPLICABLE)

UPS

SPACE

SPACE ALLOCATED FOR VA EQUIPMENT

2U HORIZONTAL CABLE MANAGER

SPACE ALLOCATED FOR VA EQUIPMENT

2U HORIZONTAL CABLE MANAGER

SPACE ALLOCATED FOR VA EQUIPMENT

2U HORIZONTAL CABLE MANAGER

SPACE ALLOCATED FOR VA EQUIPMENT

2U HORIZONTAL CABLE MANAGER

SPACE ALLOCATED FOR VA EQUIPMENT

2U HORIZONTAL CABLE MANAGER

SPACE ALLOCATED FOR VA EQUIPMENT

2U HORIZONTAL CABLE MANAGER

SPACE ALLOCATED FOR VA EQUIPMENT

2U HORIZONTAL CABLE MANAGER

SPACE ALLOCATED FOR VA EQUIPMENT

2U HORIZONTAL CABLE MANAGER

SPACE ALLOCATED FOR VA EQUIPMENT

2U HORIZONTAL CABLE MANAGER

SPACE ALLOCATED FOR VA EQUIPMENT

2U HORIZONTAL CABLE MANAGER

SPACE ALLOCATED FOR VA EQUIPMENT

2U HORIZONTAL CABLE MANAGER

SPACE ALLOCATED FOR VA EQUIPMENT

AND ADDITIONAL CABLE MANAGERS AS

NEEDED. REFER TO THE TABLE ON THIS

SHEET.

SPACE ALLOCATED FOR VA EQUIPMENT

2U HORIZONTAL CABLE MANAGER

SPACE ALLOCATED FOR VA EQUIPMENT

2U HORIZONTAL CABLE MANAGER

SPACE ALLOCATED FOR VA EQUIPMENT

2U HORIZONTAL CABLE MANAGER

SPACE ALLOCATED FOR VA EQUIPMENT

2U HORIZONTAL CABLE MANAGER

SPACE

DRAWING NUMBER

VA FORM 08 - 6231

A

OFFICE OF

CONSTRUCTION AND

REAL ESTATE

MANAGEMENT

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 5 6 7 8 9 10

664-20-501

F

BUILDING NUMBER

PROJECT NUMBERPROJECT TITLE

PROJECT LOCATION

ISSUE DATE CHECK BY DRAWN BY

PROJECT PHASE

BUILDING CONSTRUCTION

SHEET TITLE

APPROVED PROJECT DIRECTOR

U.S. Department of Veterans Affairs

ARCHITECT/ DESIGNER OF RECORD

REVISIONS DATE

1 0 5 3 T E N T H A V E N U E

S A N D I E G O , C A 9 2 1 0 1

P H O N E 6 1 9 . 2 3 8 . 3 8 1 1

D I S A B L E D V E T E R A N + E M P L OY E E OW N E D

www.davyarchitecture.com

VASDHCS PLANNING AND ENGINEERING

1455 Frazee Rd., Suite 600

San Diego, CA 92108 ph 619.232.4673 www.coffman.com

CEI Project # 201794

ENGINEER/DESIGNER OF RECORD

TYPE IA - FULLY SPRINKLERED

VA SAN DIEGO

EHRM INFRASTRUCTURE UPGRADES

3350 LA JOLLA VILLAGE DRIVE, SAN DIEGO, CA 92161

JUNE 09, 2021

100% CONSTRUCTION DOCUMENTS

T-00.50

JC MC

TELECOMMUNICATIONS DETAILS

GENERAL NOTES

MAIN,11,14,23,25,27

1. ALL PATCH CORDS SHALL BE CAT6A TYPE. PATCH CORD LENGTH SHALL BE

DETERMINED BASED ON THE WIRE MANAGEMENT PATH AND LOCATION OF

PORT CONNECTIONS. CABLE LENGTH SHALL NOT BE EXCESSIVE.

STRUCTURED CABLING SHALL HAVE SLACK, BUT ALSO SHALL BE

PRESENTABLE AND ORGANIZED.

2. WHERE IT IS UNCLEAR WHICH CABLE TO COLOR TO USE FOR HORIZONTAL

AND PATCH CABLE, CONTACT THE VA COR FOR DIRECTION.

3. EXISTING TO REMAIN CAT6 AND CAT6A CABLE SHALL BE DISCONNECTED

FROM EXISTING PATCH PANELS DURING DEMOLITION OF TELECOM

EQUIPMENT IN THIS ROOM. CABLE SHALL BE PROTECTED DURING

DEMOLITION. THE EXISTING CAT6 CABLE SHALL BE RECONNECTED TO NEWLY

INSTALLED PATCH PANELS. CAT6 CABLE SHALL BE CONNECTED TO PATCH

PANELS LOCATED CLOSEST TO THE TOP OF THE TELECOM RACK. WHERE

EXISTING CAT6 CABLE LENGTHS CANNOT REACH NEW PATCH PANEL

LOCATIONS, THE ENTIRE CABLE RUN SHALL BE REPLACED WITH CAT6A

CABLE.

4. REFER TO ARCHITECTURAL PLANS FOR TELECOMMUNICATIONS ROOM

DIMENSIONS.

5. ALL TELECOMMUNICATIONS ROOMS (NEW AND EXISTING) SHALL HAVE RACK

LAYOUTS PRESENTED TO THE VA COR FOR FINAL APPROVAL.

6, CABLE COLOR CODING TABLES ARE APPLICABLE FOR NEW CABLE ONLY.

EXISTING CABLE COLORS MAY OR MAY NOT FOLLOW THE INFORMATION ON

THESE TABLES. EXISTING TO REMAIN CABLE CONNECTIONS SHALL BE

VERIFIED AS NEEDED.

TYPICAL RACK RISER DETAIL FOR TELECOMMUNICATIONS ROOMS

SCALE: 3/4" = 1'-0"

TYPICAL LAYOUT FOR RACK 1 (1A / 1B)

SCALE: N.T.S.

NOTE:

1. WHERE ONLY ONE RACK/CABINET IS PROVIDED, FOR

SPECIFIC TELECOMMUNICATIONS ROOMS, PROVIDE A

MINIMUM SIX (6) 2U HORIZONTAL CABLE MANAGERS IN

RACK/CABINET 1.

2. THE QUANTITY OF 2U HORIZONTAL CABLE MANAGERS

PROVIDED IN RACK 2 SHALL BE PROVIDED FOR RACK 1.

A MINIMUM OF SIX (6) IS REQUIRED FOR BOTH

RACKS/CABINETS.

NOTES:

1. NOT ALL EQUIPMENT / DEVICES ARE SHOWN IN THIS TABLE. CONTRACTOR IS RESPONSIBLE TO PROVIDE ALL ITEMS REQUIRED TO ENSURE

SYSTEMS ARE FULL FUNCTIONAL AND CODE COMPLIANT.

2. WHERE MODEL NUMBERS ARE NOT SHOWN, PROVIDE EQUIPMENT / DEVICES THAT ARE UL OR NTL COMPLIANT.

3. REFER TO SPECIFICATION AND DETAIL SHEETS FOR ADDITIONAL EQUIPMENT, DEVICES, ACCESSORIES, ETC. THAT MAY NOT BE LISTED IN THIS

TABLE.

F

G B

F

M G

B

24 [610]

FRONT VIEW

1.12 [28] (x3)

INSULATION

MOUNTING

HOLES

UNITS: INCHES [MM]

SIZING OF TELECOM BONDING BACKBONE

TBB LENGTH

LINEAR FT

<=52

53-66

67-84

85-105

106-125

INSULATOR POST

STANDOFF BRACKET

2" MINIMUM

SIDE VIEW

126-150

151-175

176-250

1/0

2/0

3/0

4/0

250 kcmil

300 kcmil

350 kcmil

500 kcmil

4.2790

5.8 [147]

6.75 [171]

MOUNT

4" MINIMUM

TWO HOLE COMPRESSION LUG

CONNECTOR WITH INSPECTION WINDOW

1.5000

M

I N

END VIEW

12.5

LABELING:

EXAMPLE CONDUCTOR ROUTING

Ø

Ø x

Ø

Ø

P

C

S

Ø

Ø

P

C

S

TBB SIZE (AWG)

NO RADIUS

BENDS >90°

TGB IN

ADJACENT TR

CABLE TRAY

STRUCTURAL STEEL

12.2

12.6

DO NOT OBSTRUCT

HOLES

DO NOT ROUTE

ENTRANCE BEHIND

BAR

DUCT (IF

APPLICABLE)

ACEG

TGB OR TMGB

12.1

12.3

A. "TGB" OR "TMGB" ON BUSBAR.

B. EACH TBC SHALL BE GREEN OR MARKED WITH GREEN.

C. EACH CONDUCTOR SHALL BE LABELED AS SHOWN IN THIS

DETAIL.

BEVELED

ENTRY

DIE AND COLOR CODE

INSPECTION WINDOW

ELECTRO-TIN PLATED

IF THIS CONNECTOR OR CABLE IS

LOOSE OR MUST BE REMOVED,

PLEASE CALL THE BUILDING

TELECOMMUNICATIONS MANAGER

FROM

MAIN

GROUND

BAR (FOR TMGB)

OR

TMGB

(FOR TGB)

12.4

TGB AND TMGB BONDING DETAIL

SCALE: N.T.S.

RACKS

12.7

251-300

>=301

600 kcmil

750 kcmil

A

4" ID RGS CONDUIT

FIRESTOP MATERIAL

5" ID RGS SLEEVE

4" ID RGS CONDUIT

1" ABOVE SLAB

FINISHED CONCRETE

FLOOR SLAB

TYP. FOUR CONCRETE

ANCHORS

FIRESTOP MATERIAL

SEE NOTE BELOW

5" ID RGS SLEEVE

SECTION A

CONDUIT SLEEVES BETWEEN FLOORS

SCALE: N.T.S.

NOTE: COORDINATE WITH ARCHITECTURAL PLANS AND FIRE STOPPING SPECIFICATION FOR FIRE STOP RATING REQUIREMENTS.

FRONT VIEW

SIDE VIEW

INTUMESCENT MATERIAL

EZ-PATH FIRESTOP DEVICE

STEEL WALL PLATE

AND GASKET

TELECOMMUNICATIONS

COPPER AND OPTICAL

FIBER CABLES

EZ-PATH FIRESTOP DEVICE TELECOMMUNICATIONS

COPPER AND OPTICAL

FIBER CABLES

STEEL WALL PLATE

AND GASKET (TYPICAL)

AFFIX CABLE TRAY TO

WALL THAT SHALL BE

NO MORE THAN 2" FROM

BOTTOM OF SLEEVE

GYPSUM BOARD OPENING

SHALL

BE 3-1/4"Wx3-1/4"H MAX.

GYPSUM BOARD

OPENING SHALL

BE AS SHOWN ON

ARCHITECTURAL

DETAILS.

SCALE: N.T.S.

THROUGH WALL FIRE STOPPING (EZ PATH) DETAIL

FOR NEW TELECOM ROOMS

PET

(IF APPLICABLE)

12.8

DRAWING NUMBER

VA FORM 08 - 6231

A

OFFICE OF

CONSTRUCTION AND

REAL ESTATE

MANAGEMENT

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 5 6 7 8 9 10

664-20-501

F

BUILDING NUMBER

PROJECT NUMBERPROJECT TITLE

PROJECT LOCATION

ISSUE DATE CHECK BY DRAWN BY

PROJECT PHASE

BUILDING CONSTRUCTION

SHEET TITLE

APPROVED PROJECT DIRECTOR

U.S. Department of Veterans Affairs

ARCHITECT/ DESIGNER OF RECORD

REVISIONS DATE

1 0 5 3 T E N T H A V E N U E

S A N D I E G O , C A 9 2 1 0 1

P H O N E 6 1 9 . 2 3 8 . 3 8 1 1

D I S A B L E D V E T E R A N + E M P L OY E E O W N E D

www.davyarchitecture.com

NORTH

VASDHCS PLANNING AND ENGINEERING

1455 Frazee Rd., Suite 600

San Diego, CA 92108 ph 619.232.4673 www.coffman.com

CEI Project # 201794

ENGINEER/DESIGNER OF RECORD

TYPE IA - FULLY SPRINKLERED

VA SAN DIEGO

EHRM INFRASTRUCTURE UPGRADES

3350 LA JOLLA VILLAGE DRIVE, SAN DIEGO, CA 92161

JUNE 09, 2021

100% CONSTRUCTION DOCUMENTS

T-00.51

JC MC

TELECOMMUNICATIONS DETAILS

GENERAL NOTES

MAIN,11,14,23,25,27

1. THE COMPLETED INSTALLATION SHALL COMPLY WITH THE VA TELECOMMUNICATIONS AND SPECIAL

TELECOMMUNICATIONS SYSTEMS DESIGN MANUAL, SPECIFICATION SECTION 27 05 26, AND ANSI/TIA-607-B.

2. PROVIDE ALL TELECOMMUNICATION SPACES AND CABLING PATHWAYS IN ACCORDANCE WITH TIA-569-B.

3. TGB SHALL HAVE MINIMUM DIMENSION OF 2"W X 24"L X 1/4" THICK.

TMGB SHALL HAVE MINIMUM DIMENSION OF 4"W X 24"L X 1/4" THICK.

PROVIDE LENGTH SO AS TO PROVIDE NO. OF CONDUCTOR MOUNTING HOLES FOR CURRENT PROJECT PLUS

100% SPARES.

4. TGB/TMGB SHALL BE LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.

5. TGB/TMGB SHALL BE INSULATED FROM ITS SUPPORT BY A MINIMUM OF 2".

6. TGBTMGB SHALL BE PREDRILLED WITH 2-HOLE PATTERN.

7. TGB/TMBG SHALL BE LOCATED SO THAT IT IS ACCESSIBLE TO TELECOMMUNICATIONS PERSONNEL WHILE

PROVIDING SHORTEST PATH TO GROUND.

8. THE BUSBAR SHALL BE CLEANED PRIOR TO FASTENING OF CONDUCTORS AND AN ANTI-OXIDANT SHALL BE

APPLIED TO THE LUG CONTACT AREA TO CONTROL CORROSION AND REDUCE CONTACT RESISTANCE.

9. PROVIDE TWO HOLE COMPRESSION LUGS ON CONDUCTORS.

10. PROVIDE ONE CONDUCTOR PER SET OF HOLES UTILIZING BOLTS MATCHING HOLE SIZE.

11. REFER TO SPECIFICATION 27 05 26 FOR GROUND BAR MATERIALS.

12. TGB CONNECTIONS:

12.1. ENTRANCE DUCT/CONDUIT.

12.2. BUILDING STRUCTURAL STEEL.

12.3. PANEL BOARD ALTERNATING CURRENT ELECTRICAL GROUND (ACEG).

12.4. TELECOM BONDING CONDUCTOR (TBC).

12.5. TELECOM BONDING BACKBONE (TBB).

12.6. TELECOM CABLE TRAY, LADDER, RACEWAY.

12.7. TELECOM RACKS & ELECTRONIC EQUIPMENT .

12.8. TELECOM PROTECTED ENTRANCE TERMINALS (PET).

CABLE TRAY

CABLE TRAY TO OUTLET DETAIL (CAT6A)

SCALE: N.T.S.

INTERSTITIAL SPACE

WALL OUTLET

OR END DEVICE

INSTALL CAT6A TO

TELECOM OUTLET VIA

EXISTING CONDUIT IF

CABLE REQUIRES

UPGRADE.

THREE (3) NEW CAT6A

CABLE IN EXISTING

CONDUIT.

TO ROOM

PATCH RACK

DATA

CONNECTOR TYPE

DATA

RJ45

RJ45

CABLE TERMINATION SCHEDULE

RJ-45 CAT 6A

DATA

MODULE

(TYP OF 3)

TYPICAL DATA/TELEPHONE

OUTLET

XX-XXXXX-X-XX

BUILDING NUMBER

IDF ROOM NUMBER

PATCH PANEL PORT NUMBER

PATCH PANEL

BLANK COVER

RJ45

COLOR

WHITE

BLUE

GRAY

TELECOMMUNICATION ROOM XXX

TELECOM OUTLET DETAIL (TYPICAL)

SCALE: N.T.S.

(WHITE)

(BLUE)

(GRAY)

NOTE: FOR EXISTING OUTLETS TO BE REPLACED, OUTLET HEIGHT AND LOCATION SHALL MATCH EXISTING

TELECOMMUNICATION ROOM XXX

TELECOMMUNICATION ROOM XXX

W-BR

PAIR 4

31 2 4 65

W-O

G W-BL OBL

PAIR 3

PAIR 1

PAIR 2

7 8

BR

RJ-45 CONNECTOR

8 POSITION/8 CONDUCTOR, CATEGORY 6A

W-G

EIA/TIA - 568A WIRING

SCALE: N.T.S.

ENCLOSURE IS EQUIPPED TO HOUSE SPLICE TRAYS (NOT SHOWN)

IN REAR COMPARTMENT AND MODULAR LC CONNECTOR PLATES

ON FRONT.

TYP. 1 RMU FIBER OPTIC

SPLICING/PATCHING

ENCLOSURE

TYP. FO CONNECTOR PLATE.

(24 STRAND, 12 DUPLEX LC

CONNECTORS SHOWN)

TYPICAL 1U RACK-MOUNTED FIBER OPTIC PATCH PANEL

SCALE: N.T.S.

DETAIL 3 NOTES:

1. DATA DROPS WILL BE IN A THREE JACK CONFIGURATION ON A FOUR PORT

FACEPLATE MOUNTED ON A SINGLE GANG BOX OR MUD RING.

2. ALL DROPS SHALL BE WIRED TO A T568A STANDARD.

3. ONLY WHITE, SINGLE GANG WITH FOUR (4) OPENINGS, FLUSH MOUNT VERTICAL

CLASSIC SERIES FACEPLATES SHALL BE USED.

4. FACEPLATES MUST BE MOUNTED WITH RJ45 TABS FACING DOWN.

5. FACEPLATES WILL BE LABELED IN ACCORDANCE WITH VA SPECIFICATIONS

5.1. NUMBERING CONVENTION

5.1.1. BUILDING NUMBER (WHERE APPLICABLE).

5.1.2. FLOOR, TO INCLUDE WING DESIGNATION IF APPLICABLE

5.1.3. PANEL

5.2. JACKS ARE TO BE LABELED AS: BUILDING – IDF – PATCH PANEL – JACK PORT

NUMBER. FOR EXAMPLE, IN A TYPICAL 3 JACK FACEPLATE BUILDING 1, IDF

ROOM NUMBER B116, PATCH PANEL C, JACK LOCATION 07 IS TO BE

IDENTIFIED AS 1-B116-C-07. FROM THIS IT WILL BE ASSUMED THAT THE BLUE

AND WHITE JACKS ARE C-08 AND C-09 RESPECTIVELY.

6. PRIOR TO LABELING, CONTRACTOR SHALL OBTAIN APPROVAL FROM VA COR TO

ENSURE PROPOSED NUMBERING SCHEME MEETS OIT STANDARDS.

7. ALL 48-PORT PATCH PANELS SHALL HAVE GRAY, BLUE, AND WHITE. TERMINATE

THE WORKSTATION END WITH GRAY, BLUE, AND WHITE KEYSTONE JACKS IN THE

LAYOUT SHOWN, AND TERMINATE THE IDF END WITH THE CORRESPONDING

GRAY, BLUE, OR WHITE RJ45 PORT ON THE PATCH PANEL

DATA

DETAIL 6 NOTES:

1. ALL 48-PORT PATCH PANELS SHALL HAVE GRAY, BLUE,

AND WHITE.

2. PATCH PANELS SHALL BE LABELED ALPHABETICALLY IN

SEQUENTIAL ORDER FROM THE TOP POSITION DOWN,

STARTING WITH “A” BUT SKIPPING “I” AND “O.”

3. SINGLE CABLE DROPS (WALL PHONES, WALL MOUNTED

DISPLAY SCREENS, ETC.) SHOULD BE TERMINATED AT THE

BOTTOM OF THE LAST PANEL, SO AS TO NOT DISRUPT THE

THREE-JACK CONSECUTIVE NUMBERING SCHEME.

4. JACKS ON THE PATCH PANELS DO NOT NEED TO BE

INDIVIDUALLY LABELED, PROVIDED THEY FOLLOW THE

THREE-JACK SEQUENCE NUMBERING SCHEME AS

INDICATED ON DETAIL 3 ON SHEET T-00.52 AND

CORRESPOND TO THE FACEPLATES IN WHICH THEY ARE

CONNECTED.

5. PATCH PANELS MUST BE MOUNTED WITH RJ45 TABS

FACING DOWN.

CAT6A PATCH PANEL

SCALE: N.T.S.

CORE SWITCH RACK (BB102A) FIBER PATCH PANEL RACK (BB102)

FIBER PATCH PANEL RACK (B165) TYPICAL TELECOM ROOM RACK 1

PRIMARY CORE SWITCH

(NIC)

SECONDARY CORE SWITCH

(NIC)

24 PORT FIBER PATCH PANEL

72 PORT FIBER PATCH PANEL

96 PORT FIBER PATCH PANEL

72 PORT FIBER PATCH PANEL

96 PORT FIBER PATCH PANEL

24 PORT FIBER PATCH PANEL

48 PORT SWITCH (NIC)

DIAGRAMMATIC DETAIL OF FIBER CABLE CONNECTIONS

SCALE: N.T.S.

DETAIL 4 NOTES:

1. PROVIDE ONE (1) 2 STRAND FIBER CABLE WITH SFP

TRANSCEIVER CONNECTOR FOR CONNECTION TO SWITCH.

LC CONNECTORS SHALL BE PROVIDED ON OPPOSITE END.

ALL CONNECTIONS TO THE CORE SWITCHES SHALL BE

COORDINATED WITH THE VA COR.

2. PROVIDE ONE (1) 72 STRAND FIBER CABLE WITH LC

CONNECTORS ON BOTH ENDS.

3. PROVIDE ONE (1) 96 STRAND FIBER CABLE WITH LC

CONNECTORS ON EACH END.

4. PROVIDE ONE (1) 24 STRAND FIBER CABLE WITH LC

CONNECTORS ON EACH END.

5. PROVIDE ONE (1) 2 STRAND FIBER CABLE WITH SFP

TRANSCEIVER CONNECTOR FOR CONNECTION TO SWITCH.

LC CONNECTORS SHALL BE PROVIDED ON OPPOSITE END.

THI CONNECTION SHALL BE FROM THE PRIMARY CORE

SWITCH.

6. PROVIDE ONE (1) 2 STRAND FIBER CABLE WITH SFP

TRANSCEIVER CONNECTOR FOR CONNECTION TO SWITCH.

LC CONNECTORS SHALL BE PROVIDED ON OPPOSITE END.

THI CONNECTION SHALL BE FROM THE SECONDARY CORE

SWITCH.

7. TWO (2) 48 PORT SWITCHES SHALL BE CONNECTED

DIRECTLY TO THE FIBER PATCH PANEL. ONE SWITCH

SHALL CONNECTED TO THE PRIMARY CORE, ONE SWITCH

SHALL CONNECT TO THE SECONDARY CORE. WHERE

MORE THAN TWO (2) SWITCHES ARE PROVIDED, THEY

SHALL BE "STACKED" WITH CONNECTIONS TO THE TWO

MAIN CORE SWITCHES.

48 PORT SWITCH (NIC)

TYP. 2 RMU FIBER OPTIC

SPLICING/PATCHING

ENCLOSURE

NOTE:

NOT ALL FIBER CONNECTIONS ARE SHOWN. THE INTENT OF THIS DIAGRAM IS TO SHOW GENERAL CONNECTIONS

BETWEEN DIFFERENT PATCH PANEL SIZES. ALL CONNECTIONS TO THE CORE SWITCHES SHALL BE VERIFIED WITH

THE VA COR.

1" (TYP) TO CABLE

TRAY/ LADDER RACK

INSULATED THROAT

COMPRESSION TYPE

STEEL CONNECTOR

4-11/16" (119mm) SQUARE x 2-1/8" (54mm)

DEEP OUTLET BOX

DOUBLE GANG

PLASTER REDUCTION

RING

8P8C JACK

KEYSTONE MODULE

SINGLE GANG

FACEPLATE, KEYSTONE

COMP.

CAT 6A UTP

NOTES:

1. EACH DEVICE PLATE SHALL BE 4 PORT.

2. FILL ACTIVE PORTS IN FACEPLATE FROM LEFT TO

RIGHT AND TOP TO BOTTOM.

3. TERMINATE EACH CAT 6A CABLE ON RJ-45 CAT 6A

RATED JACK WITH T568A CONFIGURATION.

4. PROVIDE BLANK SPARE PORT COVER ON TOP

RIGHT.

5. ALL LABELS SHALL BE PRINTED WITH THERMAL OR

LASER PRINTER SYSTEM,.

TELECOMMUNICATION RJ45 OUTLET TYPE

SCALE: N.T.S.

DRAWING NUMBER

VA FORM 08 - 6231

A

OFFICE OF

CONSTRUCTION AND

REAL ESTATE

MANAGEMENT

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 5 6 7 8 9 10

664-20-501

F

BUILDING NUMBER

PROJECT NUMBERPROJECT TITLE

PROJECT LOCATION

ISSUE DATE CHECK BY DRAWN BY

PROJECT PHASE

BUILDING CONSTRUCTION

SHEET TITLE

APPROVED PROJECT DIRECTOR

U.S. Department of Veterans Affairs

ARCHITECT/ DESIGNER OF RECORD

REVISIONS DATE

1 0 5 3 T E N T H A V E N U E

S A N D I E G O , C A 9 2 1 0 1

P H O N E 6 1 9 . 2 3 8 . 3 8 1 1

D I S A B L E D V E T E R A N + E M P L OY E E O W N E D

www.davyarchitecture.com

VASDHCS PLANNING AND ENGINEERING

1455 Frazee Rd., Suite 600

San Diego, CA 92108 ph 619.232.4673 www.coffman.com

CEI Project # 201794

ENGINEER/DESIGNER OF RECORD

TYPE IA - FULLY SPRINKLERED

VA SAN DIEGO

EHRM INFRASTRUCTURE UPGRADES

3350 LA JOLLA VILLAGE DRIVE, SAN DIEGO, CA 92161

JUNE 09, 2021

100% CONSTRUCTION DOCUMENTS

T-00.52

JC MC

TELECOMMUNICATIONS DETAILS

MAIN,11,14,23,25,27

CORNER BRACKET

DETAIL 2 NOTES:

1. CABLE TRAY MAY BE SUPPORTED WITH OTHER SUPPORT

MECHANISMS THAT THE APPROVED MANUFACTURER HAS

TO OFFER.

2. CABLE TRAY SHALL BE ROUTED AROUND, OVER OR UNDER

ANY OBSTACLES THAT INTERFERE WITH THE DECLARED

PATH. CONTRACTOR SHALL FOLLOW CUTTING AND

BENDING RECOMMENDATIONS FROM THE

MANUFACTURER'S INSTALLATION GUIDE AS WELL AS THE

MINIMUM CABLE BEND RADIUS ALLOWED PER ANSI/TIA/EIA

STANDARDS. CABLE TRAY SHALL NOT IMPEDE ANY

MECHANICAL DUCT SYSTEMS. STRIVE TO MAINTAIN

MINIMUM 12" OF CLEARANCE OVER CABLE TRAY FROM

ANY OBSTRUCTION. CABLE TRAY SHALL MAINTAIN A 36"

HORIZONTAL CLEARANCE FROM SPRINKLER HEADS AND

SHALL NOT BE PLACED ABOVE SPRINKLER HEADS.

3. PROVIDE GROUNDING JUMPER BETWEEN EACH SECTION

OF TRAY (MOUNTED ON SIDE) AND FROM TRAY TO EACH

HORIZONTAL DISTRIBUTION CONDUIT.

4. NOT ALL PARTS ARE SHOWN. THE CONTRACTOR IS

RESPONSIBLE FOR A COMPLETE WORKING INSTALLATION

INCLUDING MISCELLANEOUS APPURTENANCES.

5. PROVIDE A CABLE TRAY SHOP DRAWING PRIOR TO

INSTALLATION.

6. CATWALKS SHALL REMAIN UNOBSTRUCTED. COORDINATE

DETAILS FOR CABLE TRAY CROSSING CATWALKS TO

ENSURE CATWALK ACCESS IS NOT COMPROMISED.

TRAPEZE HANGING CLIPS WITH THREADED ROD

AT 5 FOOT INTERVALS, STARTING AT 1 FOOT

OFF THE FIRST AND LAST SEGMENTS OF CABLE TRAY.

MAINTAIN 12" MIN CLEARANCE ABOVE

TRAY TO OBSTRUCTIONS OR CEILING

DETAIL 3 NOTES:

1. POSITION ERICO CAT64HPAB STYLE ONTO JOIST, WALL

OR CONCRETE.

2. PROVIDE

INCH DIA. HILTI 'KH-EZ' SCREW ANCHOR

(ESR-3027) WITH 1

INCH EMBED TO THE 5 INCH

EXISTING FLOOR SLAB ABOVE (150# MAX PER HOOK).

3. MAXIMUM CABLE CAPACITY - 140 CAT6A

4. FOR WALL MOUNTED APPLICATIONS, USE ERICO

CAT64HP STYLE J-HOOK.

CABLE LADDER RETAINING POST

LOCKING NUT

WASHER

WASHER

CLAMP

GALVANIZED

THREADED ROD

PER STRUCTURAL

12 INCH OR 30 INCH

WIDE

HOT DIPPED

GALVANIZED STEEL

CABLE RUNWAY

RUNWAY DROPS

NOTE:

SUPPORT RUNWAY AT 5 FOOT

INTERVALS. CABLE LADDER FOR USE IN

COMMUNICATIONS ROOMS ONLY.

LADDER TYPE CABLE TRAY

90° RETURN

LADDER TYPE CABLE TRAY

TEE INTERSECTION

NOTE:

PROVIDE RETAINING POST EVERY 12

INCHES ON BOTH SIDES OF THE CABLE

LADDER.

PERPENDICULAR MOUNTING ON RACK WITH 3"Ø CHANNEL

PARALLEL MOUNTING ON RACK WITH 3"Ø CHANNEL VERTICAL WALL BRACKETS

GENERAL NOTES

1. REFER TO SHEET T-00.00 FOR "TELECOMMUNICATION GENERAL NOTES."

2. PROVIDE ALL TELECOMMUNICATION SPACES AND CABLING PATHWAYS IN

ACCORDANCE WITH TIA-569-B.

3. REFER TO STRUCTURAL DRAWINGS/DETAILS FOR MOUNTING OF CABLE TRAY

AND LADDER RACK.

WALL ANGLE SUPPORT

NOTE:

TWO (2) ¼” SMS EACH BRACKET TO STUDS (OR

TO BACKING PLATE PER 4/SE-00.52).

DRAWING NUMBER

VA FORM 08 - 6231

A

OFFICE OF

CONSTRUCTION AND

REAL ESTATE

MANAGEMENT

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 5 6 7 8 9 10

664-20-501

F

BUILDING NUMBER

PROJECT NUMBERPROJECT TITLE

PROJECT LOCATION

ISSUE DATE CHECK BY DRAWN BY

PROJECT PHASE

BUILDING CONSTRUCTION

SHEET TITLE

APPROVED PROJECT DIRECTOR

U.S. Department of Veterans Affairs

ARCHITECT/ DESIGNER OF RECORD

REVISIONS DATE

1 0 5 3 T E N T H A V E N U E

S A N D I E G O , C A 9 2 1 0 1

P H O N E 6 1 9 . 2 3 8 . 3 8 1 1

D I S A B L E D V E T E R A N + E M P L OY E E O W N E D

www.davyarchitecture.com

VASDHCS PLANNING AND ENGINEERING

1455 Frazee Rd., Suite 600

San Diego, CA 92108 ph 619.232.4673 www.coffman.com

CEI Project # 201794

ENGINEER/DESIGNER OF RECORD

TYPE IA - FULLY SPRINKLERED

VA SAN DIEGO

EHRM INFRASTRUCTURE UPGRADES

3350 LA JOLLA VILLAGE DRIVE, SAN DIEGO, CA 92161

JUNE 09, 2021

100% CONSTRUCTION DOCUMENTS

T-00.53

JC MC

TELECOMMUNICATIONS DETAILS

MAIN,11,14,23,25,27

OVERHEAD CABLE TRAY (SNAKE TRAY) DETAIL

SCALE: NOT TO SCALE

J-HOOK ANGLE BRACKET DETAIL

SCALE: NOT TO SCALE

CABLE RUNWAY (LADDER RACK) DETAILS

SCALE: NOT TO SCALE

24ST

25PR

6TH FLR

R1

FIBER PP

COPPER PP

RM 6135

R1

FIBER PP

COPPER PP

R1

FIBER PP

COPPER PP

R1

FIBER PP

COPPER PP

R1

FIBER PP

COPPER PP

R1

FIBER PP

COPPER PP

24ST

25PR

PR

x2

24ST

25PR

PR

x3

24ST

25PR

PR

x4

24ST

25PR

PR

x5

24ST

25PR

R1

FIBER PP

COPPER PP

R1

FIBER PP

COPPER PP

R1

FIBER PP

COPPER PP

R1

FIBER PP

COPPER PP

R1

FIBER PP

COPPER PP

24ST

25PR

PR

x2

24ST

25PR

PR

x3

24ST

25PR

PR

x4

ST

x3

24ST

25PR

PR

x5

RM 5 EAST

R1

FIBER PP

COPPER PP

24ST

5TH FLR

RM 4155

R1

FIBER PP

COPPER PP

24ST

RM 4044A

R1

RM 3136

R1

FIBER PP

COPPER PP

3RD FLR

4TH FLR

2ND FLR

RM 2100

R1

FIBER PP

COPPER PP

24ST

RM 2505A

R1

FIBER PP

COPPER PP

24ST

2 2

OS2

OS2

1 1

OM4 OM4

1 3

CAT3

OS2

CAT3

RM 12-6

RM 12-5

RM 12-4

RM 12-3

RM 12-2

RM 10-6

RM 10-5

RM 10-4

RM 10-3

RM 10-2

ST

x5

ST

x5

ST

x6

ST

x6

ST

x5

ST

x4

CAT3

OM4

OS2

OM4

CAT3

CAT3

OS2

OS2

CAT3

CAT3

OS2

OS2

CAT3

CAT3

OS2

CAT3

CAT3

OS2

OM4

CAT3

OS2

CAT3

OS2

CAT3

ST

x3

ST

x3

OS2 OS2

CAT3 CAT3

CAT3

OS2

CAT3

6TH FLR INTERSTITIAL

5TH FLR INTERSTITIAL

4TH FLR INTERSTITIAL

2ND FLR INTERSTITIAL

3RD FLR INTERSTITIAL

ST

x2

OS2

OS2 OS2OS2

24ST

OS2

FIBER PP

COPPER PP

DRAWING NUMBER

VA FORM 08 - 6231

A

OFFICE OF

CONSTRUCTION AND

REAL ESTATE

MANAGEMENT

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 5 6 7 8 9 10

664-20-501

F

BUILDING NUMBER

PROJECT NUMBERPROJECT TITLE

PROJECT LOCATION

ISSUE DATE CHECK BY DRAWN BY

PROJECT PHASE

BUILDING CONSTRUCTION

SHEET TITLE

APPROVED PROJECT DIRECTOR

U.S. Department of Veterans Affairs

ARCHITECT/ DESIGNER OF RECORD

REVISIONS DATE

1 0 5 3 T E N T H A V E N U E

S A N D I E G O , C A 9 2 1 0 1

P H O N E 6 1 9 . 2 3 8 . 3 8 1 1

D I S A B L E D V E T E R A N + E M P L OY E E O W N E D

www.davyarchitecture.com

VASDHCS PLANNING AND ENGINEERING

1455 Frazee Rd., Suite 600

San Diego, CA 92108 ph 619.232.4673 www.coffman.com

CEI Project # 201794

ENGINEER/DESIGNER OF RECORD

TYPE IA - FULLY SPRINKLERED

VA SAN DIEGO

EHRM INFRASTRUCTURE UPGRADES

3350 LA JOLLA VILLAGE DRIVE, SAN DIEGO, CA 92161

JUNE 09, 2021

100% CONSTRUCTION DOCUMENTS

T-00.60

JC MC

IT SYSTEM RISER DIAGRAM

PULL EXISTING FIBER CABLE BACK TO SOURCE. PULL NEW FIBER CABLE FROM BB102 TO FIBER PATCH

PANEL.

EXISTING BACKBONE COPPER CABLE TO REMAIN. REFER TO ENLARGED PLANS FOR ROOMS THAT REQUIRE

REMOVAL OF WALL MOUNTED 110 BLOCKS. ALL EXISTING BACKBONE COPPER CABLE SHALL LAND ON NEW 24

PORT, 110-STYLE PATCH PANEL IN RACK 1 OF THE TELECOM ROOM/AREA. REFER TO ENLARGED PLANS AND

T-00.50 FOR ADDITIONAL DETAILS.

EXISTING BACKBONE FIBER TO REMAIN.

GENERAL NOTES

KEY NOTES

BLDG 1 - IT SYSTEM RISER DIAGRAM

SCALE: NONE

1. ALL NEW 25 PAIR COPPER CABLE SHALL BE CAT3 TYPE.

2. NEW FIBER CABLE SHALL BE OF TYPE SHOWN ON RISER, OM4 OR OS2.

3. RACK LAYOUTS ARE SHOWN FOR CONNECTION CLARIFICATION ONLY. REFER TO SHEET T-00.50 FOR

TYPICAL RACK LAYOUT FOR RACK 1 IN NEW TELECOM ROOMS.

4. NOT ALL RACKS AND PATCH PANELS ARE SHOWN IN DESIGNATED ROOMS. REFER TO ENLARGED PLANS

AND RACK LAYOUTS FOR MORE DETAILS.

5. RACKS AND DEVICES SHOWN IN GRAY ARE CONSIDERED EXISTING TO REMAIN.

MAIN,11,14,23,25,27

MATCH LINE - SEE DRAWING NUMBER T-00.61

RM B165 RM B167 RM B116

R1

FIBER PP

COPPER PP

24ST

BUILDING 1 BASEMENT

RM B217B

R1

FIBER PP

COPPER PP

24ST

PBX PUNCH DOWN AREA

R1

FIBER PP

FIBER PP

FIBER PP

FIBER PP

2 2

RM BB102

R2

FIBER PP

RM 104

R1

FIBER PP

COPPER PP

24ST

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

R3

FIBER PP

FIBER PP

FIBER PP

FIBER PP

BLDG 23BLDG 11

OS2

RM 1535A

R1

FIBER PP

COPPER PP

RM 1190

R1

FIBER PP

COPPER PP

RM 1047

R1

FIBER PP

COPPER PP

24ST

1ST FLR

RM 1251

R1

FIBER PP

COPPER PP

24ST24ST

2 2 2 2

ST

x6

PR

x5

ST

x1

PR

x5

25PR x10

24ST x2

ST

X

CAT3

OM4

OS2

ST

x6

OS2

OM4

OM4

OM4

OM4

OM4

CAT3

OM4

OM4

CAT3

R1

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

1ST FLR INTERSTITIAL

RM A1100

R1

FIBER PP

COPPER PP

ST

x9

ST

x1

OS2

OM4

EXISTING 110 PUNCH DOWN BLOCKS

FOR 300 PAIR

110- PUNCH DOWN BLOCKS

24ST x2

RM 126

R1

FIBER PP

COPPER PP

24ST

BLDG 25

OS2

RM 101

R1

FIBER PP

COPPER PP

24ST

BLDG 14

24ST x124ST x1

25PRX1

25PR

ST

x3

OS2

CAT3

OS2

TO CAN 3

ST

x1

CAT3

OS2 OS2

OS2

24ST

OM4

DRAWING NUMBER

VA FORM 08 - 6231

A

OFFICE OF

CONSTRUCTION AND

REAL ESTATE

MANAGEMENT

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 5 6 7 8 9 10

664-20-501

F

BUILDING NUMBER

PROJECT NUMBERPROJECT TITLE

PROJECT LOCATION

ISSUE DATE CHECK BY DRAWN BY

PROJECT PHASE

BUILDING CONSTRUCTION

SHEET TITLE

APPROVED PROJECT DIRECTOR

U.S. Department of Veterans Affairs

ARCHITECT/ DESIGNER OF RECORD

REVISIONS DATE

1 0 5 3 T E N T H A V E N U E

S A N D I E G O , C A 9 2 1 0 1

P H O N E 6 1 9 . 2 3 8 . 3 8 1 1

D I S A B L E D V E T E R A N + E M P L OY E E O W N E D

www.davyarchitecture.com

NORTH

VASDHCS PLANNING AND ENGINEERING

1455 Frazee Rd., Suite 600

San Diego, CA 92108 ph 619.232.4673 www.coffman.com

CEI Project # 201794

ENGINEER/DESIGNER OF RECORD

TYPE IA - FULLY SPRINKLERED

VA SAN DIEGO

EHRM INFRASTRUCTURE UPGRADES

3350 LA JOLLA VILLAGE DRIVE, SAN DIEGO, CA 92161

JUNE 09, 2021

100% CONSTRUCTION DOCUMENTS

T-00.61

JC MC

IT SYSTEM RISER DIAGRAM

MAIN,11,14,23,25,27

PULL EXISTING FIBER CABLE BACK TO SOURCE. PULL NEW FIBER CABLE FROM BB102 TO FIBER PATCH

PANEL.

EXISTING BACKBONE COPPER CABLE TO REMAIN. REFER TO ENLARGED PLANS FOR ROOMS THAT REQUIRE

REMOVAL OF WALL MOUNTED 110 BLOCKS. ALL EXISTING BACKBONE COPPER CABLE SHALL LAND ON NEW 24

PORT, 110-STYLE PATCH PANEL IN RACK 1 OF THE TELECOM ROOM/AREA. REFER TO ENLARGED PLANS AND

T-00.50 FOR ADDITIONAL DETAILS.

EXISTING BACKBONE FIBER TO REMAIN.

PULL EXISTING COPPER CABLE BACK TO SOURCE. PULL NEW COPPER CABLE FROM B167 TO COPPER

(110-STYLE) PATCH PANEL. ALL NEW BACKBONE COPPER CABLE SHALL LAND ON NEW 24 PORT, 110-STYLE

PATCH PANEL IN RACK 1 OF THE TELECOM ROOM/AREA. REFER TO ENLARGED PLANS AND T-00.50 FOR

ADDITIONAL DETAILS.

NEW 25 PAIR COPPER CABLE FOR NEW TELECOM ROOMS IN BUILDING 1 SHALL BE CONNECTED TO THE

EXISTING 110 BLOCKS ALLOCATED AS SPARE FOR THIS PROJECT SCOPE. NEW 25 PAIR FOR EXISTING ROOMS

101 (BLDG 14) AND 1i (BLDG 11) SHALL BE RECONNECTED TO THE EXISTING PUNCH DOWNS IN THIS ROOM.

GENERAL NOTES

KEY NOTES

IT SYSTEM RISER DIAGRAM

SCALE: NONE

1. ALL NEW 25 PAIR COPPER CABLE SHALL BE CAT3 TYPE.

2. NEW FIBER CABLE SHALL BE OF TYPE SHOWN ON RISER, OM4 OR OS2.

3. RACK LAYOUTS ARE SHOWN FOR CONNECTION CLARIFICATION ONLY. REFER TO SHEET T-00.50 FOR

TYPICAL RACK LAYOUT FOR RACK 1 IN NEW TELECOM ROOMS.

4. NOT ALL RACKS ARE AND PATCH PANELS SHOWN IN DESIGNATED ROOMS. REFER TO ENLARGED PLANS

AND RACK LAYOUTS FOR MORE DETAILS.

5. RACKS AND DEVICES SHOWN IN GRAY ARE CONSIDERED EXISTING TO REMAIN.

MATCH LINE - SEE DRAWING NUMBER T-00.60

RM 2A140

R1

FIBER PP

COPPER PP

RM 1A116

R1

FIBER PP

COPPER PP

RM 2B119

R1

FIBER PP

COPPER PP

RM 1i (INTERSTITIAL SPACE)

R1

FIBER PP

COPPER PP

1ST FLR

24ST

24ST

24ST24ST

RM BB115

R1

FIBER PP

COPPER PP

24ST

BLDG 11 BASEMENT

2 2

OM4

BLDG 27

2ND FLR

RM 1119B

R1

FIBER PP

COPPER PP

24ST

OS2

OM4

OM4

OM4

OM4

1ST FLR INTERSTITIAL

RM BB102

R2

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

R1

FIBER PP

FIBER PP

FIBER PP

FIBER PP

R3

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

FIBER PP

RM 2119B

R1

FIBER PP

COPPER PP

24ST

OS2

RM 3119B

R1

FIBER PP

COPPER PP

24ST

OS2

24ST X2

ST OM4

ST OM4

ST OM4

25PR

CAT3

EXISTING 110

BLOCKS

1 1

1 1

DRAWING NUMBER

VA FORM 08 - 6231

A

OFFICE OF

CONSTRUCTION AND

REAL ESTATE

MANAGEMENT

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 5 6 7 8 9 10

664-20-501

F

BUILDING NUMBER

PROJECT NUMBERPROJECT TITLE

PROJECT LOCATION

ISSUE DATE CHECK BY DRAWN BY

PROJECT PHASE

BUILDING CONSTRUCTION

SHEET TITLE

APPROVED PROJECT DIRECTOR

U.S. Department of Veterans Affairs

ARCHITECT/ DESIGNER OF RECORD

REVISIONS DATE

1 0 5 3 T E N T H A V E N U E

S A N D I E G O , C A 9 2 1 0 1

P H O N E 6 1 9 . 2 3 8 . 3 8 1 1

D I S A B L E D V E T E R A N + E M P L OY E E O W N E D

www.davyarchitecture.com

NORTH

VASDHCS PLANNING AND ENGINEERING

1455 Frazee Rd., Suite 600

San Diego, CA 92108 ph 619.232.4673 www.coffman.com

CEI Project # 201794

ENGINEER/DESIGNER OF RECORD

TYPE IA - FULLY SPRINKLERED

VA SAN DIEGO

EHRM INFRASTRUCTURE UPGRADES

3350 LA JOLLA VILLAGE DRIVE, SAN DIEGO, CA 92161

JUNE 09, 2021

100% CONSTRUCTION DOCUMENTS

T-00.62

JC MC

IT SYSTEM RISER DIAGRAM

IT SYSTEM RISER DIAGRAM

SCALE: NONE

MAIN,11,14,23,25,27

PULL EXISTING FIBER CABLE BACK TO SOURCE. PULL NEW FIBER CABLE FROM BB102TO FIBER PATCH

PANEL.

EXISTING BACKBONE COPPER CABLE TO REMAIN. REFER TO ENLARGED PLANS FOR ROOMS THAT REQUIRE

REMOVAL OF WALL MOUNTED 110 BLOCKS. ALL EXISTING BACKBONE COPPER CABLE SHALL LAND ON NEW 24

PORT, 110-STYLE PATCH PANEL IN RACK 1 OF THE TELECOM ROOM/AREA. REFER TO ENLARGED PLANS AND

T-00.50 FOR ADDITIONAL DETAILS.

PULL EXISTING COPPER CABLE BACK TO SOURCE. PULL NEW COPPER CABLE FROM 1A116 TO COPPER

(110-STYLE) PATCH PANEL. ALL NEW BACKBONE COPPER CABLE SHALL LAND ON NEW 24 PORT, 110-STYLE

PATCH PANEL IN RACK 1 OF THE TELECOM ROOM/AREA. REFER TO ENLARGED PLANS AND T-00.50 FOR

ADDITIONAL DETAILS.

GENERAL NOTES

KEY NOTES

1. ALL NEW 25 PAIR COPPER CABLE SHALL BE CAT3 TYPE.

2. NEW FIBER CABLE SHALL BE OF TYPE SHOWN ON RISER, OM4 OR OS2.

3. RACK LAYOUTS ARE SHOWN FOR CONNECTION CLARIFICATION ONLY. REFER TO SHEET T-00.50 FOR

TYPICAL RACK LAYOUT FOR RACK 1 IN NEW TELECOM ROOMS.

4. NOT ALL RACKS AND PATCH PANELS ARE SHOWN IN DESIGNATED ROOMS. REFER TO ENLARGED PLANS

AND RACK LAYOUTS FOR MORE DETAILS.

5. RACKS AND DEVICES SHOWN IN GRAY ARE CONSIDERED EXISTING TO REMAIN.

CAT6A

PATCH PANEL

115VAC

DOOR XXX TELECOM

ROOM XXX

HIRSCH MX-8 CONTROL PANEL

J

CR ES

PATCH PANEL

OIT RACK

(LOCATED IN

TELECOM

ROOM/AREA)

DS

ALTRONIX

POWER

SUPPLY

AL600ULPD8

115VAC

1" C, CAT6A (TYP)

CAT6A

NOTE:

1. COORDINATE ALL DEVICE ROUGH-IN LOCATIONS.

6"x6" SURFACE MOUNTED

J-BOX LOCATED ABOVE

CEILING SECURED SIDE

WALL

SCRAMBLEPAD (CR) AT 48" AFF

OC, UON

LOCKSET

2-1" CONDUIT

HOMERUN TO

HIRSCH CONTROLLER

3/4" CONDUITS

6"x6" SURFACE MOUNTED J-BOX

LOCATED ABOVE CEILING

SECURED SIDE

ELECTRIC DOOR STRIKE

TO HIRSCH CONTROLLER

3/4" CONDUITS

SCRAMBLEPAD (CR)

NON-SECURE SIDE

PLAN ELEVATION

FLOOR

CEILING

REQUEST TO EXIT INTEGRAL

WITH DOOR HANDLE

REQUEST TO EXIT CONTROLLER

1 - 2C/14 STP

1- 4C/22 STP

1 - 2C/18 STP

IN 1"C

1 - 4C/22 STP

IN 3 4"C

1 - 2C/18 STP

IN 3 4"C

ELECTRIC DOOR STRIKE

(ES)

DOOR POSITION SWITCH (DS)

3/4" CONDUITS

DOOR POSITION SWITCH (DS)

1 - 2C/14 STP

POE SWITCH

(CISCO 9300)

OIT RACK

(LOCATED IN

TELECOM

ROOM/AREA)

EXISTING NVR

EXISTING HTM

RACK

CAT6A PATCH CORD

DRAWING NUMBER

VA FORM 08 - 6231

A

OFFICE OF

CONSTRUCTION AND

REAL…