S02 DRAWINGS.pdf
PDF 28 MB Posted
- Solicitation number
- 36C24221B0034
About this file
This document outlines requirements for a federal construction contract opportunity for the replacement of condenser water piping at a Department of Veterans Affairs medical center. Key details include:
-
The scope of work involves replacing condenser water piping from the chiller plant to cooling towers on the east side of Building 4, including replacement of valves, electrical heat tracing, and installation of a centrifugal separator/cleaner package and support piers on the roof.
-
The period of performance is 260 days from notice to proceed. The general contractor must submit preliminary schedules, payment and performance bonds, insurance, a schedule of values, and a construction schedule within ten days of contract award.
-
Work must be performed according to the statement of work, specifications, drawings, and applicable federal, state and local codes. Coordination is required for utility interruptions and tie-ins.
-
The general contractor is responsible for all required submittals, including a master submittal list, site superintendent designation, and key personnel contact information. Notification is required for tests and inspections.
-
Safety, infection control, hazardous materials reporting and environmental protection requirements are outlined. The general contractor must comply with privacy training, security requirements, and coordinate with the infection control practitioner.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S02 ALL POSTERS.pdf | ||
| S02 ADDITIONAL INSERTS.pdf | ||
| S02 BID SHEET Updated.docx | DOCX document | |
| S02 SPECS.pdf | ||
| S02 Participation Goals for Minorities and Females.pdf | ||
| 36C24221B0034.docx | DOCX document | |
| S02 VA ID PACKAGE UPDATED 01-16-2019.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SITE
LOCATION
1 5
4A
8A
B
U
S
L
A
N
E
O
N
L
Y
T
A
X
I
M
B
U
L
E
T
T
E
T E
N A
N T
P A
R K
I N
G
4B
POLY PL.
SCALE: N.T.S.
N
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT:
Facilities
Management1
NUCLEAR MEDICINE
SPECT-CT SITE PREP
Services
4-7-21
FE PROJECT #
630A4-20-424
Revisions: Date
20-176
NEW YORK HARBOR
HEALTH CARE SYSTEM
BROOKLYN, NY
www.fellp.com
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704 fx 855-320-8735
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
ENGINEERING LLPLiscum
181 CHURCH STREET
POUGHKEEPSIE, NEW YORK 12601
PHONE 845-452-2268 FAX 845-452-3752
ARCHITECTURE
PLANNING INTERIORS
McCormack VanVoorhis LLP
100% CONSTRUCTION DOCUMENTS
GI-001
SHEET #: DRAWING #: DRAWING TITLE
1-MH-001
HVAC: SYMBOLS, ABBREVIATIONS & NOTES
1-ES-001 ELECTRICAL: SYMBOLS, ABBREVIATIONS & NOTES
1-FX-001
FIRE PROTECTION: SYMBOLS, ABBREVIATIONS & NOTES
HVAC:
ELECTRICAL:
FIRE PROTECTION SPRINKLER:
GENERAL:
1-ES-801 ELECTRICAL: SCHEDULES
1-MH-201 HVAC: DEMOLITION & NEW WORK
1-PL-001 PLUMBING: SYMBOLS, ABBREVIATIONS & NOTES
PLUMBING:
1-PL-101
1-ES-101 ELECTRICAL: POWER PLANS DEMOLITION & NEW WORK
1-FX-201 FIRE PROTECTION: RCP DEMOLITION & NEW WORK
1-ES-201 ELECTRICAL: LIGHTING PLANS DEMOLITION & NEW WORK
PLUMBING: MEDICAL GAS DEMOLITION & NEW WORK
1-AS-001
GENERAL INFORMATION: TITLE SHEET WITH INDEX OF DRAWINGS
ARCHITECTURAL:
1-LS-100 ARCHITECTURAL: LIFE SAFETY FLOOR PLAN
ARCHITECTURAL: SYMBOLS, ABBREVIATIONS & NOTES
1-PH-100
AS-D-100 ARCHITECTURAL: DEMOLITION FLOOR PLAN
ARCHITECTURAL: PHASING PLAN, SUMMARY, AND NOTES
1-AS-100
1-AS-101
1-AS-600
ARCHITECTURAL: PROPOSED PLAN OPTIONS 1 & 2
ARCHITECTURAL: ROOM FINISH SCHEDULE, FINISH SCHEDULE
ARCHITECTURAL: REFLECTED CEILING PLAN
C1-A2 COVER SHEET, DISCLAIMER - SITE READINESS, GENERAL NOTES & EQUIPMENT LAYOUT
GE DRAWINGS:
M1-E3
HVAC, ELECTRICAL NOTES, LAYOUT & ELEVATIONS
A3-A6 RADIATION PROTECTION, EQUIPMENT DETAILS & DELIVERY
S1-S4 STRUCTURAL NOTES, LAYOUT & DETAILS
E4-E5 POWER REQUIREMENTS & ELECTRICAL DETAILS - INTERCONNECTIONS
1-ES-102 ELECTRICAL: POWER PLANS, 3RD., 4TH, & 5TH FLOORS NEW WORK
1-S-100
1-S-200 STRUCTURAL: NOTES & SPECIAL INSPECTIONS
STRUCTURAL: SECOND FLOOR FRAMING REINFORCEMENT PLAN AND SECTIONS
STRUCTURAL:
1-AS-102
ARCHITECTURAL: EQUIPMENT PLAN AND SCHEDULE
1-T-200
STRUCTURAL: TEMPORARY SUPPORT FOR EQUIPMENT INSTALLATION
PDU
661#
CART
728#
CART
728#
CART
728#
CART
728#
PDU
661#
B
8 9
W12X35
W12X35
(E)W12X45
W12X35
W
X
W
X
W
X
W X
W
X
W
X
W
X
W
X
(E)W12X35
(E)W12X35
7'-0"X7'-0"X
A36 PL.
3'-8"X4'-0"X
A36 PL.
3'-8"X8'-8"X
A36 PL.
3'-8"X7'-0"X
A36 PL.
7'-0"X7'-0"X
A36 PL.
S100
S100
20'-4" 20'-4"
E
C
X
E
C
X
E
C
X
E
C
X
E
C
X
E
C
X
E
W
X
E
W
X
E
W
X
±2'-0"
2'-7
" ±8'-5
±2'-0"
REMOVE EXISTING TOPPING
& REPLACE WITH NEW
2" THICK CONCRETE
REINF. W/ 4X4-W2.9XW2.9 W.W.F.
S100
PARTIAL SECOND FLOOR FRAMING REINFORCEMENT PLAN AT ROOMS 508 & 510
SCALE:
" = 1'-0"
W12X35
W12X35
W12X35
(E)W16X40
(E)W16X40 (E)W16X40
(E)W16X40
(E)W16X50(E)W16X50
(E)W16X50
(E)W16X50
E
C
X
E
C
X
20'-4"
W12X35
W12X35
PATIENT
LIFT COLUMN
(BY ARJO)
PATIENT
LIFT COLUMN
(BY ARJO)
PATIENT
LIFT COLUMN
(BY ARJO)
PATIENT
LIFT COLUMN
(BY ARJO)
PATIENT
LIFT COLUMN
(BY ARJO)
PATIENT
LIFT COLUMN
(BY ARJO)
PATIENT
LIFT COLUMN
(BY ARJO)
PATIENT
LIFT COLUMN
(BY ARJO)
C
C
S100
SIM.
S100
1'-6"X1'-6"X
" PL.
1'-6"X1'-6"X
" PL.
1'-6"X1'-6"X
" PL.
±6'-1
" (COORD. W/ G.E.)
±4'-1
" 1'-0
C
C O
R D
W
G
E
±9'-4
" (COORD. W/ G.E.)
1'-0
" 2'-7
" ±7'-2
C
O O
R D
W
G
E
CABLE INLET OPN'G
(COORD. W/ G.E.)
CABLE INLET OPN'G
(COORD. W/ G.E.)
CABLE INLET OPN'G
(COORD. W/ G.E.)
CABLE INLET OPN'G
(COORD. W/ G.E.)
ISO-CENTER
ISO-CENTER
S100
S100
S100
S100
S100
S100
S100
S100
S100
REMOVE EXIST.
W8X15 IF REQ'D
AT CABLE INLET
W
X
W
X
W
X
10'-2"
NOTES:
- FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS &
ELEVATIONS, TYP.
- LOCATIONS OF CONCRETE BEAMS & EXISTING BEAMS
SHOWN ARE APPROXIMATE, BASED ON LIMITED
INFORMATION. ACTUAL LOCATIONS MAY VARY.
2'-4"±3'-5"
NEW STEEL
BEAM (SEE PLAN)
NEW STEEL
BEAM (SEE PLAN)
PACK W/ NON-
SHRINK GROUT
PACK W/ NON-
SHRINK GROUT TYP.
EXISTING
C13X31.8
3-SIDES
TYP.
NEW STEEL BEAM
(SEE PLAN)
L3
"X3
"X
"X5
EA. FACE
LEVEL 2
SECTION - NEW BEAM SHEAR CONNECTION TO EXISTING
SCALE:
" = 1'-0"
S100
SECTION - CT ANCHORAGE AT ROOM 508
SCALE:
" = 1'-0"
S100
RETURN WELD
AT TOP TYP.
EXISTING STEEL
BEAM (SEE PLAN)
WHERE ANCHOR BOLT CONFLICTS
W/ CONCRETE BEAM, DO NOT DRILL
THROUGH BEAM. WELD THREADED
ANCHOR TO STEEL PLATE, TYP.
FASTEN STEEL PL. TO
FLOOR W/
" DIA. THRU-BOLTS
AT 1'-8" O.C. MAX. IN EA.
DIRECTION TYP.
ANCHOR CT W/ THRU-BOLTS
(BY CT INSTALLER, TYP.)
LEAD SHIELDING (SEE ARCH.)
STEEL PLATE
(SEE PLAN)
SECTION - CT ANCHORAGE AT ROOM 510
SCALE:
" = 1'-0"
S100
EXISTING STEEL
BEAMS (SEE PLAN)
ANCHOR CT W/ THRU-BOLTS
(BY CT INSTALLER, TYP.)
LEAD SHIELDING (SEE ARCH.)
REMOVE EXISTING TOPPING & REPLACE
W/ NEW 2" CONCRETE W/4X4XW2.9XW2.9 W.W.F.
STEEL PLATE
(SEE PLAN)
SECTION - CT ANCHORAGE AT ROOM 510
SCALE:
" = 1'-0"
S100
EXISTING STEEL
BEAMS (SEE PLAN)
LEAD SHIELDING (SEE ARCH.)
STEEL PLATE
(SEE PLAN)
WHERE ANCHOR BOLT
CONFLICTS W/ CONCRETE
BEAM OR STEEL BEAM,
WELD THREADED ANCHOR
TO STEEL PLATE, TYP.
FASTEN STEEL PL. TO
FLOOR W/
" DIA. THRU-BOLTS
AT 1'-8" O.C. MAX. IN EA.
DIRECTION TYP.
FASTEN STEEL PL. TO
FLOOR W/
" DIA.
THRU-BOLTS AT
1'-8" O.C. MAX. IN EA.
DIRECTION TYP.
NEW STEEL
BEAMS (SEE PLAN)
2'-4"±3'-5"
NEW STEEL
BEAM (SEE PLAN)
NEW STEEL
BEAM (SEE PLAN)
PACK W/ NON-
SHRINK GROUT
PACK W/ NON-
SHRINK GROUT
SECTION - CT ANCHORAGE AT ROOM 508
SCALE:
" = 1'-0"
S100
EXISTING STEEL
BEAM (SEE PLAN)
LEAD SHIELDING (SEE ARCH.)
STEEL PLATE
(SEE PLAN)
WHERE ANCHOR BOLT
CONFLICTS W/ CONCRETE
BEAM OR STEEL BEAM,
WELD THREADED ANCHOR
TO STEEL PLATE, TYP.
TABLE ANCHOR PL. &
THRU-BOLTS
BY CT INSTALLER
L3X3X
"X2'-0"
(TOTAL OF TWO [2])
IF REQ'D, CORE SLAB FOR ALT.
CABLE INLET LOCATION. DO NOT DRILL
THROUGH OR DAMAGE CONCRETE BEAMS
SECTION - TABLE ANCHORAGE ROOM 510
SCALE:
" = 1'-0"
S100
TABLE ANCHOR PL. &
EXPANSION ANCHORS
BY CT INSTALLER
SECTION - TABLE ANCHORAGE ROOM 508
SCALE:
" = 1'-0"
S100
IF REQ'D, CORE SLAB FOR ALT.
CABLE INLET LOCATION.
DO NOT DRILL THRU OR DAMAGE
CONCRETE BEAMS TYP.
±10
V.I.F.
±1'-1
V.I.F.
±10
V.I.F.
±1'-1
V.I.F.
3"X3"X
" PL.
WASHER TYP.
NEW STEEL BEAM
(SEE PLAN)
±1'-5"2'-0" 2'-0"
REMOVE EXISTING TOPPING & REPLACE
W/ NEW 2" CONCRETE W/4X4XW2.9XW2.9 W.W.F.
REMOVE EXISTING TOPPING &
REPLACE W/ NEW 2" CONCRETE
W/4X4XW2.9XW2.9 W.W.F.
REMOVE EXISTING TOPPING & REPLACE
W/ NEW 2" CONCRETE W/4X4XW2.9XW2.9 W.W.F.
WHERE ANCHOR BOLT
CONFLICTS W/ CONCRETE
BEAM OR STEEL BEAM,
WELD THREADED ANCHOR
TO STEEL PLATE, TYP.
EXISTING C13X31.8
ENCASED
IN CONCRETE
±1'-7"
I S
O
C E
N T
E R
±1'-5" ±1'-7"
I S
O
C E
N T
E R
±7"
I S
O
C E
N T
E R
±7"
I S
O
C E
N T
E R
NOTE:
DO NOT DRILL THROUGH
OR DAMAGE ANY EXISTING
CONCRETE BEAMS TYP.
EXISTING C13X31.8
ENCASED
IN CONCRETE
2"
2"
NOTCH ANGLE
AT BEAM
NOTES:
- REMOVE & REPLACE EXISTING
SPRAY-FIREPROOFING AS REQ'D TO
MAKE CONNECTIONS TO EXISTING
STEEL BEAMS.
- PROVIDE SPRAY FIRE-PROOFING AT
ALL NEW STEEL BEAMS. SEE ARCH.
FOR ADDITIONAL REQUIREMENTS TYP.
N
O
C
DEPTH B N WT
" 28"
"12"
"16"
L 4"x3
"xTxB
B
GIRDER
W
" CLR.
"Ø A325-N-STD
" CLR.
B
D E
P T
H
DETAIL - STEEL BEAM TO STEEL BEAM SHEAR CONNECTION
NOTE TO SCALE
S100
634#
AT PIVOT
488#
ON WHEELS
1863#
1863#
552#
552#
553#
553#
503#
503#
CT FLOOR LOAD DIAGRAM
SCALE:
" = 1'-0"
S100
VERIFY LOADS
W/ FINAL G.E.
DRAWINGS.
A
LEVEL 2
EL. = 52-0"
LEVEL 3
EL. = 66'-0"
1'-3
SIMPSON SCS62-5/118
CLIP EA. FACE
(TOTAL OF TWO [2])
W/ (3)-#14 SHOULDERED
SCREWS TO STUD IN
"PATTERN S1" & (2)-1/4" DIA.
TITEN HD TO CONCRETE (2
" EMBED.)
M
I N
G A
P
M
I N
LIFT COLUMN
(BY ARJO)
ATTACHMENT SCREWS
TO STUD FRAMING (BY ARJO)
600T125-43
362S162-43
362S162-43
" GYPSUM BOARD
7 8
600T125-43
#10 SCREWS @ 1'-0" O.C. TYP.
" MAX.
STANDOFF
L3X3X
"X6"
EA. FACE
(4)-#10 TEK SCREWS
TO COLUMN TYP.
STEEL PL.
(SEE PLAN)
" DIA. THRU-BOLT TYP.
" DIA. HAS ROD W/ HILTI
HIT HY200 (2-3/4" EMBED.) TYP.
AA
BUILT-UP STUD
BRACE COLUMN "C1"
PATIENT LIFT
COLUMN
(BY ARJO)
SECTION - BUILT-UP STUD BRACE COLUMN "C1" AT PATIENT LIFT COLUMN
SCALE:
" = 1'-0"
S100
PATIENT LIFT RAIL
(BY ARJO)
A - A
BUILDING DESIGN LOADS:
ROOMS 508 & 510 LIVE LOAD: 40 PSF
SITE CLASS: D (ASSUMED)
OCCUPANCY CATEGORY: IV
Ss: 0.2775
S1: 0.0714
Sds: 0.292
Sd1: 0.114
SEISMIC DESIGN CATEGORY: C
SEISMIC IMPORTANCE FACTOR Ie: 1.5
PATIENT LIFT SAFE WORKING LOAD: 440 LBS.
PATIENT LIFT LIFTER SELF-WEIGHT: 27 LBS.
MISC. G.E. CT EQUIPMENT: SEE PLAN & CT FLR LOAD DIAGRAM
BASIC WIND SPEED: 98 MPH (AT 33FT ASD LEVEL)
WIND IMPORTANCE FACTOR: 1.15
WIND EXPOSURE: C
70 South Franklin Street, Wilkes-Barre, PA 18701
570 | 824-6340 info@edpons.comedpons.com
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT:
Facilities
Management o n e e i g h t h i n c o e f o t t h r e e i n c h e s o t o n e a d a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
NUCLEAR MEDICINE
SPECT-CT SITE PREP
Services
4-07-21
FE PROJECT #
630A4-20-424
Revisions: Date
20-176
NEW YORK HARBOR
HEALTH CARE SYSTEM
BROOKLYN, NY
www.fellp.com
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704 fx 855-320-8735
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
ENGINEERING LLPLiscum
181 CHURCH STREET
POUGHKEEPSIE, NEW YORK 12601
PHONE 845-452-2268 FAX 845-452-3752
ARCHITECTURE
PLANNING INTERIORS
McCormack VanVoorhis LLP
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
2ND FLOOR FRAMING
AutoCAD SHX Text
REINFORCEMENT PLAN
AutoCAD SHX Text 1-S-100
AutoCAD SHX Text
ME
AutoCAD SHX Text
ME
AutoCAD SHX Text Designed By:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text FE Project No.
AutoCAD SHX Text 20-176
AutoCAD SHX Text
ME
AutoCAD SHX Text
ME
DESIGN STRESSES
CONCRETE (STRENGTH DESIGN) MINIMUM COMPRESSIVE STRENGTH IN 28 DAYS:
ALL INTERIOR CONCRETE-------------------------------------------------------------------------F'C=4,000PSI
REINFORCING BARS (ASTM A615 OR ASTM A706, GRADE 60)-------------------------------- FY=60,000PSI
WELDED WIRE REINFORCEMENT (ASTM A185)---------------------------------------------------- FS=30,000PSI
STRUCTURAL STEEL W AND S SHAPES
(ASTM A992 OR ASTM A572/50)-------------------------------------------------------------------FY=50,000PSI
STRUCTURAL STEEL OTHER SHAPES (ASTM A36)------------------------------------------------FY=36,000PSI
ANCHOR RODS (F1554, GRADE 36) UNLESS OTHERWISE NOTED-------------------------- FY=36,000PSI
HOLLOW STRUCTURAL SECTIONS (ASTM A500, GRADE B)
RECTANGULAR-----------------------------------------------------------------------------------------FY=46,000PSI
ROUND-----------------------------------------------------------------------------------------------------FY=42,000PSI
CODES AND STANDARDS
1. BUILDING HAS BEEN DESIGNED TO, AND SHALL BE CONSTRUCTED IN ACCORDANCE WITH
THE FOLLOWING BUILDING CODES AND STANDARDS:
1.1. 2014 NEW YORK CITY BUILDING CODE
2. UNLESS EXPLICITLY MODIFIED IN THE CONTRACT DRAWINGS AND SPECIFICATIONS, THE
CONTRACTOR SHALL COMPLY WITH THE FOLLOWING STANDARDS:
2.1. ASCE/SEI 7-05, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES.
2.2. ACI 301-10, SPECIFICATIONS FOR STRUCTURAL CONCRETE.
2.3. ACI 318-14, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE.
2.4. ACI 530-13 / ASCE 5-13 / TMS 402-2013, BUILDING CODE REQUIREMENTS FOR MASONRY
STRUCTURES.
2.5. ANSI/AISC 341-10, SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS.
2.6. ANSI/AISC 360-10, SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS.
2.7. AWS D1.4/D1.4M-2011, STRUCTURAL WELDING CODE - STEEL.
2.8. SJI 44TH EDITION CATALOG OF STANDARD SPECIFICATIONS AND LOAD TABLES FOR
STEEL JOISTS AND JOIST GIRDER.
2.9. SDI - NO. MOC2, SDI MANUAL OF CONSTRUCTION WITH STEEL DECK, 2006.
2.10. AISI S100-12, NORTH AMERICAN SPECIFICATION FOR DESIGN OF COLD-FORMED STEEL
STRUCTURE MEMBERS.
CONCRETE CONSTRUCTION
1. ALL CONCRETE CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST BUILDING CODES REQUIREMENTS
FOR REINFORCED CONCRETE ACI 318 AND ACI DETAIL MANUAL, EXCEPT THAT CONSTRUCTION AND REMOVAL OF
FORMS AND RESHORING SHALL BE INSPECTED BY THE CONTRACTOR'S ENGINEER.
2. REINFORCING STEEL SHALL HAVE THE FOLLOWING MINIMUM COVERAGE. PLACE BARS AS NEAR TO THE
CONCRETE SERVICE AS THE MINIMA PERMIT WHEREVER POSSIBLE, UNLESS NOTED OTHERWISE:
2.1. CONCRETE POURED AGAINST EARTH 3"
2.2. FORMED CONCRETE IN CONTACT WITH EARTH 2"
2.3. EXTERIOR FACE OF WALLS 2"
2.4. ALL OTHER WALL FACES AND SLABS
2.5. BEAMS AND COLUMNS 1
" (2" FOR EXTERIOR)
3. WELDED WIRE REINFORCEMENT FOR SLABS ON GROUND SHALL HAVE A MINIMUM COVERAGE OF 1" AND
MAXIMUM TOP COVERAGE OF 1
", UNLESS OTHERWISE NOTED. REINFORCEMENT SHALL BE POSITIVELY
SUPPORTED AND MAINTAINED IN THIS POSITION DURING PLACEMENT OF CONCRETE.
4. FURNISH BAR SUPPORTS WHERE NECESSARY DURING CONSTRUCTION.
5. PROVIDE PLASTIC-COATED (NOT PLASTIC-TIPPED) OR STAINLESS STEEL CHAIRS IN ALL CONCRETE EXPOSED TO
VIEW IN COMPLETED STRUCTURE.
6. PROVIDE PIPE SLEEVES AND INSERTS IN CONCRETE WORK WHERE REQUIRED. SEE ARCHITECTURAL AND
MECHANICAL DRAWINGS.
7. UNLESS NOTED OTHERWISE, PROVIDE THE FOLLOWING MINIMUM REINFORCING:
7.1. SLAB ON GROUND, SLAB ON DECK, AND TOPPINGS (2" MINIMUM): 4 X 4-W2.9 X W2.9 WELDED WIRE
REINFORCEMENT IN FLAT SHEETS.
7.2. WALLS: #4 @ 12" ON CENTER EACH WAY (FOR EACH 6" OF WALL THICKNESS).
8. CONSTRUCTION JOINTS SHALL BE POSITIONED SO AS NOT TO CHANGE THE STRUCTURAL DESIGN
REQUIREMENTS. FRAMED FLOORS AND ROOFS SHALL HAVE CONSTRUCTION JOINTS SO THAT THE RATIO OF
LENGTH TO WIDTH OF A SINGLE POUR SHALL NOT EXCEED 2. THE LOCATION AND SIZE OF ALL CONSTRUCTION
JOINTS SHALL BE APPROVED BY THE ENGINEER. SUBMIT PROPOSED POUR LAYOUT FOR ENGINEER'S REVIEW
AND APPROVAL TWO WEEKS PRIOR TO PLACING CONCRETE.
9. WELDING REINFORCING BARS (INCLUDING TACK WELDING) IS NOT PERMITTED WITHOUT PERMISSION OF
ENGINEER IN WRITING. WHERE AND WHEN PERMITTED, WELDING REBARS SHALL COMPLY WITH ASTM A706 (FY=60
KSI) AND WELDING SHALL CONFORM TO AWS D1.4. WELDING SHALL BE PERFORMED BY CERTIFIED WELDERS.
10. PROVIDE HORIZONTAL KEYWAYS IN CONSTRUCTION JOINTS IN SUPPORTED SLABS AND WALL FOOTINGS;
MINIMUM 1
" DEPTH WITH HEIGHT EQUAL TO ONE-THIRD OF MEMBER DEPTH, UNLESS OTHERWISE SHOWN OR
NOTED.
11. ALL EXPOSED CORNERS OF COLUMNS, WALLS, AND STEEL MEMBERS ENCASED IN CONCRETE ARE TO BE
CHAMFERED 45°. MINIMUM CHAMFER TO BE
12. UNLESS NOTED OTHERWISE IN PROJECT SPECIFICATIONS OR DRAWINGS, ALL EXPOSED CONCRETE SUBJECTED
TO FREEZING AND THAWING SHALL HAVE A MINIMUM CEMENT CONTENT OF 610 POUNDS PER YARD, A MAXIMUM
WATER/CEMENT RATIO OF 0.40, AND 6% ±1% OF ENTRAINED AIR.
13. SLAB THICKNESS INDICATED OVER STEEL FORM DECK INCLUDES FORM DEPTH. PROVIDE FORM DECK
CONTINUOUS OVER AT LEAST THREE SUPPORTS AND WELD TO EACH SUPPORT AT MINIMUM 12" INTERVALS. USE
DECKING THAT WILL SAFELY SUPPORT ALL CONSTRUCTION LOADS, INCLUDING WET WEIGHT OF CONCRETE. LIMIT
DEFLECTION OF DECKING TO 1/240 OF SPAN WHEN LOADED WITH WET WEIGHT OF CONCRETE AND
CONSTRUCTION LOADS
14. BEND ALL HORIZONTAL WALL AND FOOTING BARS 1'-0" AROUND CORNERS OR PROVIDE CORNER BARS WITH 2'-0"
LAP.
15. KEY AND DOWEL ALL AREAWAYS AND OTHER PROJECTING ELEMENTS TO SUPPORTING WALLS WITH #4 @ 12" ON
CENTER EXTENDING 1'-0" INTO SUPPORTING WALLS UNLESS NOTED
16. PROVIDE FOUNDATION DOWELS FOR ALL WALLS, PIERS, AND COLUMNS SAME SIZE AND SPACING AS VERTICAL
STEEL.
17. HORIZONTAL FLOORS SUPPORTED BY DEFLECTING STRUCTURAL MEMBERS (STEEL JOISTS, UNSHORED STEEL
BEAMS, ETC) SHALL BE FINISHED LEVEL. THE SLAB THICKNESS NOTED IS MINIMUM. ADD CONCRETE AS
NECESSARY TO OVERCOME MEMBER DEFLECTIONS. SHORED CONSTRUCTION SHALL BE FINISHED TO A
CONSTANT DEPTH.
18. ALL BARS INTERRUPTED BY STRUCTURAL STEEL SHALL EXTEND TO WITHIN 1" OF STRUCTURAL STEEL FLANGE OR
WEB AND HAVE A 90° HOOK UNLESS OTHERWISE SHOWN.
19. DRAWINGS SHOW TYPICAL REINFORCING CONDITIONS. CONTRACTOR SHALL PREPARE DETAILED PLACEMENT
DRAWINGS OF ALL CONDITIONS SHOWING QUANTITY, SPACING, SIZES, CLEARANCES, LAPS, INTERSECTIONS, AND
COVERAGE REQUIRED BY THE STRUCTURAL DETAILS, APPLICABLE CODE, AND TRADE STANDARDS. CONTRACTOR
SHALL NOTIFY REINFORCING INSPECTOR OF ANY ADJUSTMENTS FROM TYPICAL CONDITIONS WHICH ARE
PROPOSED IN PLACEMENT DRAWINGS TO FACILITATE FIELD PLACEMENT OR REINFORCING STEEL AND
CONCRETE.
20. BAR BENDS ARE TO BE MADE COLD. BARS SHALL NOT BE BENT AFTER ANY PORTION OF THE BAR IS ENCASED IN
CONCRETE.
21. SPLICES (GRADE 60 DEFORMED BARS):
21.1. LAP ALL COMPRESSION SPLICES 30 BAR DIAMETERS OF THE LARGER BAR.
21.2. LAP ALL TENSION SPLICES IN ACCORDANCE WITH THE FOLLOWING TABLES. PROVIDE CLASS B TENSION LAP
SPLICES UNLESS OTHERWISE NOTES.
21.3. INCREASE TENSION OR COMPRESSION SPLICE LENGTHS BY THE FOLLOWING FACTORS. INCREASES ARE
CUMULATIVE:
21.3.1. EPOXY-COATED TOP BARS 1.3
21.3.2. EPOXY-COATED OTHER BARS 1.5
21.3.3. LIGHTWEIGHT CONCRETE 1.3
21.4. TOP BARS ARE DEFINED AS HORIZONTAL BARS WITH MORE THAN 12" OF FRESH CONCRETE BELOW.
21.5. MECHANICAL SPLICES SHALL DEVELOP 125% OF THEIR YIELD STRENGTH OF THE BAR AND ARE REQUIRED
FOR TENSION TIE MEMBERS. MECHANICAL SPLICES IN ADJACENT BARS SHALL BE STAGGERED AT LEAST 30".
CLASS B TENSION LAP SPLICE
BAR F'C=3000PSI F'C=4000PSI F'C=5000PSI
SIZE TOP OTHER TOP OTHER TOP OTHER
#3 28" 22" 24" 19" 22" 17"
#4 37" 29" 33" 25" 29" 23"
#5 47" 36" 41" 31" 36" 28"
#6 56" 43" 49" 37" 43" 34"
#7 81" 63" 71" 54" 63" 49"
#8 93" 72" 81" 62" 72" 56"
#9 105" 81" 91" 70" 81" 63"
#10 118" 91" 102" 79" 92" 70"
CLASS A DEVELOPMENT LENGTH, LD
BAR F'C=3000PSI F'C=4000PSI F'C=5000PSI
SIZE TOP OTHER TOP OTHER TOP OTHER
#3 22" 17" 19" 15" 17" 13"
#4 29" 22" 25" 19" 23" 17"
#5 36" 28" 31" 24" 28" 22"
#6 43" 33" 37" 29" 34" 26"
#7 63" 48" 54" 42" 49" 38"
#8 72" 55" 62" 48" 56" 43"
#9 81" 62" 70" 54" 63" 48"
#10 91" 70" 79" 61" 70" 54"
GENERAL
1. ALL NEW CONSTRUCTION SHALL COMPLY WITH THE CONTRACT DOCUMENTS AND THE BUILDING CODE.
2. TYPICAL DETAILS AND GENERAL NOTES APPLY TO ALL PARTS OF THE WORK EXCEPT WHERE
SPECIFICALLY DETAILED OR UNLESS OTHERWISE NOTED.
3. THE STRUCTURAL DRAWINGS ILLUSTRATE STRUCTURAL MEMBERS. REFER TO ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR NON-STRUCTURAL ITEMS WHICH REQUIRE SPECIAL
PROVISIONS DURING THE CONSTRUCTION OF THE STRUCTURAL MEMBERS.
4. DRAWINGS ARE NOT TO BE SCALED.
5. REFER TO ARCHITECTURAL PLANS FOR FLOOR DEPRESSIONS, OPENINGS, SLOPES, DRAINS, CURBS, PADS, EMBEDDED ITEMS, NON-BEARING PARTITIONS, ETC. REFER TO MECHANICAL AND ELECTRICAL
PLANS FOR SLEEVES, OPENINGS, AND HANGERS FOR PIPES, DUCTS, AND EQUIPMENT.
6. THE CONTRACTOR SHALL VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS WHICH
IMPACT THE WORK. FIELD VERIFY SIZES, ELEVATIONS, HOLE LOCATIONS, ETC., PRIOR TO FABRICATION.
7. THE CONTRACTOR SHALL CAREFULLY REVIEW THE DRAWINGS TO IDENTIFY THE SCOPE OF WORK
REQUIRED, VISIT THE SITE TO RELATE THE SCOPE OF WORK TO EXISTING CONDITIONS AND DETERMINE
THE EXTENT TO WHICH THOSE CONDITIONS AND PHYSICAL SURROUNDINGS WILL IMPACT THE WORK.
8. EXISTING CONDITIONS AS SHOWN ON THESE PLANS ARE FOR REFERENCE ONLY. CONTRACTOR IS
REQUIRED TO FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO CONSTRUCTION.
9. THE CONTRACTOR SHALL RESOLVE ANY CONFLICTS ON THE DRAWINGS OR IN THE SPECIFICATIONS
WITH THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH THE WORK.
10. ANY DEVIATION, MODIFICATION, OR SUBSTITUTION FROM THE APPROVED SET OF STRUCTURAL
DRAWINGS SHALL BE SUBMITTED TO THE OWNER, ARCHITECT, AND ENGINEER FOR REVIEW/APPROVAL
PRIOR TO ITS USE OR INCLUSION ON THE SHOP DRAWINGS.
11. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY SHORES, BRACES, AND GUYS REQUIRED TO
SUPPORT ALL LOADS TO WHICH THE BUILDING STRUCTURE AND COMPONENTS, SOILS, OTHER
STRUCTURES AND UTILITIES MAY BE SUBJECTED DURING CONSTRUCTION. SHORING SYSTEMS SHALL
BE DESIGNED , SIGNED , AND SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE JURISDICTION
WHERE THE PROJECT IS LOCATED.
12. THE CONTRACTOR SHALL PROVIDE MEANS, METHOD , TECHNIQUES, SEQUENCES, AND PROCEDURE OF
CONSTRUCTION AS REQUIRED.
13. THE CONTRACTOR SHALL PROTECT ALL WORK, MATERIALS, AND EQUIPMENT FROM DAMAGE AND
SHALL PROVIDE PROPER STORAGE FACILITIES FOR MATERIALS AND EQUIPMENT DURING
CONSTRUCTION.
14. SITE VISITS PERFORMED BY ARCHITECT/ENGINEER DO NOT INCLUDE INSPECTIONS OF MEANS AND
METHODS OF CONSTRUCTION PERFORMED BY CONTRACTOR.
15. STRUCTURAL OBSERVATIONS PERFORMED BY ARCHITECT/ ENGINEER DURING CONSTRUCTION ARE
NOT THE CONTINUOUS AND SPECIAL INVESTIGATION SERVICES AND DO NOT WAIVE THE
RESPONSIBILITY FOR THE INSPECTIONS REQUIRED OF THE BUILDING DEPARTMENT INSPECTOR OR THE
TESTING AGENCY. OBSERVATIONS ALSO DO NOT GUARANTEE CONTRACTOR'S PERFORMANCE AND
SHALL NOT BE CONSIDERED AS SUPERVISION OF CONSTRUCTION.
16. THE CONTRACTOR SHALL REVIEW SHOP DRAWINGS FOR COMPLETENESS AND COMPLIANCE WITH
CONTRACT DOCUMENTS. CONTRACTOR SHALL STAMP SHOP DRAWINGS PRIOR TO SUBMISSION TO
ARCHITECT AND ENGINEER.
17. REVIEW OF THE SHOP DRAWINGS BY THE ARCHITECT'S ENGINEERS SHALL NOT BE CONSTRUED AS AN
AUTHORIZATION TO DEVIATE FROM THE CONTRACT DOCUMENTS.
18. SHOP DRAWINGS WILL NOT BE PROCESSED IF THEY ARE INCOMPLETE , LACK COORDINATION WITH
RELEVANT PORTION OF CONTRACT DOCUMENTS, LACK CALCULATIONS IF REQUIRED, OR IF
DEVIATIONS, MODIFICATIONS, AND SUBSTITUTIONS ARE INDICATED WITHOUT PRIOR WRITTEN
APPROVAL FROM ARCHITECT/ENGINEER.
19. ALL POST INSTALLED ANCHORS AND REBAR SHALL BE INSTALLED PER THE MANUFACTURER'S
PRESCRIBED INSTALLATION INSTRUCTIONS.
19.1. THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER'S REPRESENTATIVE TO PROVIDE
ON-SITE TRAINING FOR ALL OF THEIR ANCHORING PRODUCTS SPECIFIED. THE STRUCTURAL
ENGINEER OF RECORD MUST RECEIVE DOCUMENTED CONFIRMATION THAT ALL OF THE
CONTRACTOR'S PERSONNEL WHO INSTALL ANCHORS ARE TRAINED PRIOR TO THE
COMMENCEMENT OF INSTALLING ANCHORS.
19.2. ANCHOR CAPACITY IS DEPENDANT UPON SPACING BETWEEN ADJACENT ANCHORS AND PROXIMITY
OF ANCHORS TO EDGE OF CONCRETE. INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND
EDGE CLEARANCES INDICATED ON THE DRAWINGS.
19.3. EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE MAY CONFLICT WITH SPECIFIC
ANCHOR LOCATIONS. UNLESS NOTED ON THE DRAWINGS THAT THE BARS CAN BE CUT, THE
CONTRACTOR SHALL REVIEW THE EXISTING STRUCTURAL DRAWINGS AND SHALL UNDERTAKE TO
LOCATE THE POSITION OF THE REINFORCING BARS AT THE LOCATION OF THE CONCRETE
ANCHORS, BY FERROSCAN, GPR, X-RAY, CHIPPING, OR OTHER MEANS.
19.4. THE CONTRACTOR SHALL RECORD THE ANCHOR EMBEDMENT, AMBIENT TEMPERATURE,
TEMPERATURE OF CONCRETE OR MASONRY SUBSTRATE, TEMPERATURE OF THE EPOXY, AND THE
SUBSTRATE MOISTURE CONDITIONS AT THE TIME OF ALL ADHESIVE ANCHOR AND ADHESIVE REBAR
DOWEL INSTALLATIONS. DO NOT INSTALL ANCHORS IF THE TEMPERATURES ARE OUT OF THE
MANUFACTURER'S PRESCRIBED ACCEPTABLE RANGE. DO NOT INSTALL ANCHORS IN
WATER-SATURATED CONCRETE OR SUBMERGED CONDITIONS, UNLESS SPECIFICALLY AUTHORIZED
TO DO SO BY THE ENGINEER OF RECORD. PREPARE THE ADHESIVE PER THE MANUFACTURER'S
INSTRUCTIONS. ALLOW FOR ADEQUATE CURING TIME, PRIOR TO APPLYING LOAD TO THE
ANCHORS. THE REQUIRED CURING TIME MAY BE DEPENDENT ON THE SUBSTRATE MOISTURE
CONDITIONS, TEMPERATURE AT THE TIME OF THE INSTALLATION, AND TEMPERATURE DURING THE
CURING PROCESS. REFER TO THE MANUFACTURER'S INSTRUCTIONS FOR THE REQUIRED CURING
TIME.
19.5. DO NOT DRILL FOR OR INSTALL POST-INSTALLED ANCHORS INTO CONCRETE UNTIL IT HAS CURED
FOR A MINIMUM OF 28 DAYS AND HAS REACHED THE REQUIRED DESIGN COMPRESSIVE STRENGTH.
19.6. OVER-HEAD ADHESIVE ANCHORS REQUIRE CONTINUOUS INSPECTIONS, PER THE IBC CODE. ALL
OTHER ADHESIVE ANCHOR INSTALLATIONS REQUIRE PERIODIC INSPECTIONS PER THE NYC CODE.
DEMOLITION
1. THE CONTRACTOR IS TO OBTAIN AND PAY FOR ALL NECESSARY PERMITS FOR THE DEMOLITION
AND REMOVAL WORK.
2. NOTIFY ALL LOCAL AGENCIES HAVING JURISDICTION.
3. LOCATE EXISTING UNDERGROUND UTILITIES IN ALL AREAS OF CONSTRUCTION. COORDINATE
WITH UTILITY COMPANIES FOR ANY SHUT-OFF REQUIREMENTS OF STILL ACTIVE LINES. CALL THE
NY ONE-CALL CENTER.
4. DEMOLITION PROCEDURES, SHORING REQUIREMENTS, SEQUENCE TECHNIQUES, ETC., EITHER
GIVEN IN OR IMPLIED BY THESE DRAWINGS, ARE SUGGESTIONS ONLY. CONTRACTOR SHALL
RETAIN, AT HIS OWN EXPENSE, A PROFESSIONAL ENGINEER LICENSED IN THE JURISDICTION
WHERE THE PROJECT IS LOCATED TO DETERMINE ALL CONSTRUCTION PHASE REQUIREMENTS.
CONTRACTOR SHALL SUBMIT DRAWINGS , SIGNED AND SEALED BY HIS ENGINEER, TO THE
OWNER AND ENGINEER FOR CONCEPT REVIEW AND RECORD PURPOSES. CONTRACTOR SHALL
BE SOLELY RESPONSIBLE FOR THE PROTECTION, STABILITY, ETC., OF EXISTING AND NEW
STRUCTURES DURING EXECUTION OF THE WORK.
5. BEFORE UNDERTAKING ANY DEMOLITION WORK, ASCERTAIN THE EXISTING CONDITIONS OF THE
PROPERTIES AND BUILDINGS ADJOINING OR IN CLOSE PROXIMITY OF THE PREMISES BY SURVEY.
6. CONTRACTOR SHALL PERFORM ALL WORK IN SUCH A MANNER AS TO PROTECT EXISTING AND
ADJACENT STRUCTURES AND BE RESPONSIBLE TO PROPERLY REPAIR ANY DAMAGE THAT
OCCURS AS A RESULT OF HIS WORK. CONTRACTOR SHALL REPAIR ALL DAMAGES TO STREETS,
SIDEWALK, UTILITY LINES, OR ANY OTHER PUBLIC OR PRIVATE PROPERTIES RESULTING FROM
THE EXECUTION OF THE WORK AT NO COST TO THE OWNER OR ENGINEER.
7. CEASE OPERATIONS AND NOTIFY OWNER AND ENGINEER IMMEDIATELY IF SAFETY OR INTEGRITY
OF STRUCTURE APPEAR TO BE ENDANGERED. PROPERLY BRACE AND SUPPORT STRUCTURE
BEFORE RESUMING OPERATIONS.
8. NOTIFY OWNER AND ENGINEER IMMEDIATELY IF ANY PORTION OF EXISTING STRUCTURE WHICH
IS NOT TO BE DEMOLISHED IS DAMAGED. CONTRACTOR SHALL PAY FOR ALL REPAIR COSTS,
INCLUDING DESIGN AND INSPECTION EXPENSES.
9. DO NOT CUT OR ALTER ANY STRUCTURAL MEMBERS WITHOUT WRITTEN AUTHORIZATION OF THE
ENGINEER UNLESS INDICATED ON THE STRUCTURAL DRAWINGS.
10. DO NOT ALLOW RESULTING DEBRIS TO ACCUMULATE. DISPOSE OF THE MATERIAL IN A LEGAL
MANNER.
STEEL CONSTRUCTION
1. STEEL DETAILING, FABRICATION, AND ERECTION SHALL CONFORM TO THE AISC SPECIFICATION FOR STRUCTURAL STEEL
BUILDINGS AND CODE OF STANDARD PRACTICE, AND THE AWS STRUCTURAL WELDING CODE.
2. STRESSES OCCURRING DURING FABRICATION, SHIPMENT, AND ERECTION SHALL BE TEMPORARY AND NOT EXCESSIVE.
STRESSES AT ALL TIMES SHALL BE LESS THAN DESIGN AND ALLOWABLE STRESSES. THE FULL DESIGN AND
LOAD-CARRYING CAPACITY OF THE STEEL WORK SHALL NOT BE IMPAIRED DUE TO FABRICATION, SHIPMENT, OR
ERECTION PROCEDURES. THROUGHOUT THE COMPLETE PROCESS, THE STABILITY OF ALL INDIVIDUAL MEMBERS AND
ASSEMBLIES SHALL BE MAINTAINED.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CONTROL OF ALL ERECTION PROCEDURES AND SEQUENCES WITH
RELATION TO TEMPERATURE DIFFERENTIALS AND WELD SHRINKAGE.
4. ALL ADDITIONAL STEEL REQUIRED FOR ERECTION PROCESSES SHALL BE PROVIDED AT NO ADDITIONAL COST AND SHALL
BE REMOVED UNLESS APPROVED BY THE OWNER IN WRITING.
5. CONNECTIONS - WELDED OR HIGH STRENGTH BOLTED:
5.1. HIGH-STENGTH BOLTS SHALL BE INSTALLED IN ACCORDANCE WITH "SPECIFICATIONS FOR STRUCTURAL JOINTS
USING ASTM A325 OR A490 BOLTS".
5.2. A325SC OR A490SC WITH HARDENED WASHERS: USE FOR ALL MOMENT CONNECTION, WIND CONNECTIONS, HANGERS, AND OTHER CONNECTIONS AS NOTED ON DRAWINGS.
5.3. A25N OR A490N WITH HARDENED WASHERS: USE FOR ALL CONNECTIONS OTHER THAN SLIP CRITICAL CONNECTIONS.
5.4. PROVIDE HARDENED WASHERS UNDER NUTS AT ALL HIGH-STRENGTH BOLTS, EXCEPT WHERE PLATE WASHERS ARE
USED PER AISC SPECIFICATIONS.
5.5. UNLESS SNUG TIGHT CONNECTIONS ARE NOTED ON THE DRAWINGS AS BEING PERMITTED, ALL BOLTS SHOULD BE
TIGHTENED TO FULL PRETENSIONING LOAD.
5.6. USE STANDARD HOLES WITH THE FOLLOWING EXCEPTIONS: OVERSIZE HOLES ARE PERMITTED WHEN BOLTS ARE
LOADED IN TENSION; SHORT SLOTTED HOLES ARE PERMITTED FOR SHEAR LOADING PERPENDICULAR TO THE SLOT.
5.7. PROVIDE BEVELED WASHERS ON ALL CONNECTION TO SLOPING FLANGES OF I SECTIONS AND CHANNELS WHERE
SLOPE EXCEEDS 1:20.
5.8. WHERE MINIMUM AISC FILLET WELD THICKNESS REQUIREMENT EXCEEDS WELDS SHOWN ON DETAILS, OR WELD SIZE
IS NOT SPECIFIED, PROVIDE MINIMUM AISC WELD.
5.9. WHEREVER POSSIBLE, USE FRAMED BEAM CONNECTIONS AS LISTED IN TABLE 10-1 TO 10-3 OF AISC MANUAL OF
STEEL CONSTRUCTION, 13TH EDITION. THE LENGTH OF CONNECTION SHALL NOT BE LESS THAN ONE-HALF OF THE T
DISTANCE OF BEAM WEB.
5.10. WHERE REACTION IS NOTED, DEVELOP SAME. WHERE NOT NOTED, FOR NON-COMPOSITE BEAMS, CONNECTIONS
SHALL DEVELOP ONE-HALF OF THE TOTAL UNIFORM LOAD CAPACITY OF THE BEAM; FOR COMPOSITE BEAMS, SEE
TABLE LISTED IN TYPICAL DETAILS.
6. WELDING ELECTRODES SHALL BE E70XX EXCEPT WHERE OTHER ELECTRODES ARE REQUIRED FOR COMPATIBILITY WITH
MATERIAL BEING WELDED
7. ALL SLIP CONNECTIONS SHALL BE PROVIDED WITH A MEANS OF PREVENTING THE NUTS FROM UNTHREADING.
8. SHOP DRAWINGS ARE REQUIRED AND SHALL NOTE TYPE OF ELECTRODES, SIZE OF ALL WELDS, AND TYPE AND SIZE OF
ALL BOLTS. SHOP DRAWINGS SHALL BE PREPARED UNDER SUPERVISION OF A PROFESSIONAL ENGINEER LICENSED IN
THE JURISDICTION WHERE THE PROJECT IS LOCATED.
9. PAINTING, UNLESS OTHERWISE NOTED:
9.1. PROVIDE ONE SHOP COAT AND ONE FIELD COAT OF RUST-INHIBITIVE PAINT.
9.2. DO NOT PAINT BEAMS THAT ARE ENCASED IN CONCRETE OR TO RECEIVE SPRAYED-ON FIREPROOFING.
9.3. OMIT PAINT AT SLIP CRITICAL CONNECTIONS AND AREAS TO BE WELDED.
10. SEE ALL CONTRACT DRAWINGS & SPECIFICATIONS FOR MISCELLANEOUS STEEL REQUIREMENTS.
11. ALL SHOP AND FIELD WELDING SHALL BE PERFORMED BY A RECENTLY CERTIFIED WELDER.
12. ALL WELDING AND HIGH STRENGTH BOLTING MUST BE INSPECTED BY A QUALIFIED TESTING LABORATORY. LABORATORY
SHALL BE APPROVED BY THE ARCHITECT AND/OR ENGINEER.
13. DO NOT WELD TO EXISTING STEEL WITHOUT WRITTEN APPROVAL FROM THE ENGINEER.
14. PROVIDE FILLS AT SPLICES OF PARTS DIFFERING BY MORE THAN
" IN THICKNESS.
15. MISCELLANEOUS HANGING LOADS SUCH AS STAIR STRINGERS, PIPES, MECHANICAL UNITS, ETC., SUPPORTED BY STEEL
MEMBERS SHALL BE APPLIED IN SUCH A MANNER THAT NO TORSIONAL FORCES ARE INDUCED IN THE STEEL MEMBERS, i.e., LOADS SHALL PASS THROUGH THE CENTERLINE OF WIDE FLANGE SECTIONS AND THROUGH THE SHEAR CENTER OF
CHANNELS.
VERIFICATION AND INSPECTION
1. INSPECTION OF REINFORCING STEEL, INCLUDING
PRESTRESSING TENDONS, AND PLACEMENT.
2. INSPECTION OF REINFORCING STEEL WELDING IN
ACCORDANCE WITH TABLE 1704.3, ITEM 5B.
3. INSPECT BOLTS TO BE INSTALLED IN CONCRETE PRIOR
TO AND DURING PLACEMENT OF CONCRETE WHERE
ALLOWABLE LOADS HAVE BEEN INCREASED.
4. VERIFYING USE OF REQUIRED DESIGN MIX.
5. AT THE TIME FRESH CONCRETE IS SAMPLED TO
FABRICATE SPECIMENS FOR STRENGTH TESTS,
PERFORM SLUMP AND AIR CONTENT TESTS, AND
DETERMINE THE TEMPERATURE OF THE CONCRETE.
6. INSPECTION OF CONCRETE AND SHOTCRETE
PLACEMENT FOR PROPER APPLICATION TECHNIQUES.
7. INSPECTION FOR MAINTENANCE OF SPECIFIED
CURING TEMPERATURE AND TECHNIQUES.
8. INSPECTION OF PRESTRESSED CONCRETE:
a. APPLICATION OF PRESTRESSING FORCES.
b. GROUTING OF BONDED PRESTRESSING TENDONS IN
THE SEISMIC-FORCE-RESISTING SYSTEM.
9. ERECTION OF PRECAST CONCRETE MEMBERS.
10. VERIFICATION OF IN-SITU CONCRETE STRENGTH,
PRIOR TO STRESSING OF TENDONS IN POSTTENSIONED
CONCRETE AND PRIOR TO REMOVAL OF SHORES AND
FORMS FROM BEAMS AND STRUCTURAL SLABS.
11. INSPECT FORMWORK FOR SHAPE, LOCATION AND
DIMENSIONS OF THE CONCRETE MEMBER BEING
FORMED.
CONTINUOUS PERIODIC
REFERENCED
STANDARD
REFERENCE
- ACI 318: 3.5,
7.1-7.7
X
X
X
X
N/AN/A
N/AN/A
N/AN/A
AWS D1.4
ACI 318: 3.5.2
ACI 318: CH. 4
5.2-5.4
X
ASTM C 172
ASTM C 31
ACI 318: 5.6, 5.8
X -
ACI 318: 5.9,
5.10
N/AN/A
ACI 318: 5.11 -
5.13
ACI 318: 18.2
ACI 318: 18.18.4
ACI 318: CH. 16
ACI 318: 6.2
ACI 318: 6.1.1
CONCRETE SPECIAL INSPECTIONS
VERIFICATION AND INSPECTION
1. MATERIAL VERIFICATION OF HIGH-STRENGTH BOLTS, NUTS AND WASHERS:
a. IDENTIFICATION MARKINGS TO CONFORM TO ASTM
STANDARDS SPECIFIED IN THE APPROVED
CONSTRUCTION DOCUMENTS.
b. MANUFACTURER’S CERTIFICATE OF COMPLIANCE REQUIRED.
2. INSPECTION OF HIGH-STRENGTH BOLTING:
a. BEARING-TYPE CONNECTIONS.
b. SLIP-CRITICAL CONNECTIONS.
3. MATERIAL VERIFICATION OF STRUCTURAL STEEL:
a. IDENTIFICATION MARKINGS TO CONFORM TO ASTM
STANDARDS SPECIFIED IN THE APPROVED
CONSTRUCTION DOCUMENTS.
b. MANUFACTURERS’ CERTIFIED MILL TEST REPORTS.
4. MATERIAL VERIFICATION OF WELD FILLER MATERIALS:
a. IDENTIFICATION MARKINGS TO CONFORM TO AWS
SPECIFICATION IN THE APPROVED CONSTRUCTION
DOCUMENTS.
b. MANUFACTURER’S CERTIFICATE OF COMPLIANCE REQUIRED.
5. INSPECTION OF WELDING:
a. STRUCTURAL STEEL:
1) COMPLETE AND PARTIAL PENETRATION GROOVE WELDS.
2) MULTIPASS FILLET WELDS.
3) SINGLE-PASS FILLET WELDS > 5/16 ˝
4) SINGLE-PASS FILLET WELDS < 5/16 ˝
5) FLOOR AND ROOF DECK WELDS.
b. REINFORCING STEEL:
1) VERIFICATION OF WELDABILITY OF REINFORCING
STEEL OTHER THAN ASTM A 706.
2) REINFORCING STEEL-RESISTING FLEXURAL AND
AXIAL FORCES IN INTERMEDIATE AND SPECIAL MOMENT
FRAMES, AND BOUNDARY ELEMENTS OF SPECIAL REINFORCED
CONCRETE SHEAR WALLS AND SHEAR REINFORCEMENT.
3) SHEAR REINFORCEMENT.
4) OTHER REINFORCING STEEL.
6. INSPECTION OF STEEL FRAME JOINT DETAILS FOR COMPLIANCE
WITH APPROVED CONSTRUCTION DOCUMENTS:
a. DETAILS SUCH AS BRACING AND STIFFENING.
b. MEMBER LOCATIONS.
C. APPLICATION OF JOINT DETAILS AT EACH CONNECTION.
CONTINUOUS PERIODIC
REFERENCED
STANDARD
REFERENCE
APPLICABLE ASTM
MATERIAL SPECIFICATIONS;
AISC 360, SECTION A3.3
X -
- X --
- X
N/A N/A
AISC 360, SECTION M2.5 -
ASTM A 6 OR ASTM A 568
ASTM A 6 OR ASTM A 568
AAISC 360, SECTION A3.5
AWS D1.1 -
N/AN/A
N/AN/A
N/AN/A
X
N/AN/A
AWS D1.3
N/AN/A
N/AN/A
N/A
N/A
X
AWS D1.4
ACI 318: 3.5.2
N/A
N/A
N/A N/A
N/A
N/A
STEEL SPECIAL INSPECTIONS
MINIMUM QUALIFICATIONS FOR SPECIAL INSPECTORS
N/AN/A
REINFORCED CONCRETE
WELDING
MASONRY
SPRAYED FIRE-
RESISTANT MATERIALS
INSPECTION OF FABRICATORS
EXTERIOR AND INTERIOR
ARCHITECTURAL WALL PANELS
SMOKE CONTROL
SEISMIC RESISTANCE
1.CURRENT ICC REINFORCED CONCRETE SPECIAL INSPECTOR OR ACI
CONCRETE CONSTRUCTION INSPECTOR.
2. CONCRETE FIELD TESTING CAN BE BY AN ACI
CONCRETE FIELD TESTING TECHNICIAN WITH GRADE 1 CERTIFICATION.
3. ENGINEER-IN-TRAINING (EIT) WITH RELEVANT EXPERIENCE.
4. NEW YORK STATE LICENSED PROFESSIONAL ENGINEER
(P.E.) WITH RELEVANT EXPERIENCE.
1. CURRENT AWS CERTIFIED WELDING INSPECTOR.
2. CURRENT ICC STRUCTURAL STEEL
AND WELDING CERTIFICATE PLUS ONE
YEAR OF RELEVANT EXPERIENCE.
3. CURRENT LEVEL II CERTIFICATION FROM THE AMERICAN
SOCIETY FOR NONDESTRUCTIVE TESTING (NDT).
4. CURRENT NDT LEVEL III PROVIDED PREVIOUSLY CERTIFIED
AS NDT LEVEL II.
1. CURRENT ICC STRUCTURAL MASONRY CERTIFICATION AND ONE
YEAR OF RELEVANT EXPERIENCE.
2. EIT WITH RELEVANT EXPERIENCE.
3. P.E. WITH RELEVANT EXPERIENCE.
1. CURRENT ICC SPRAY-APPLIED FIRE PROOFING CERTIFICATION
AND ONE YEAR OF RELEVANT EXPERIENCE.
2. EIT WITH RELEVANT EXPERIENCE.
3. P.E. WITH RELEVANT EXPERIENCE
1. PRECAST: CURRENT ICC REINFORCED CONCRETE
CERTIFICATION PLUS ONE YEAR RELEVANT EXPERIENCE.
2. BAR JOIST: SEE WELDING REQUIREMENTS.
3. METAL BUILDING: SEE WELDING REQUIREMENTS.
4. STRUCTURAL STEEL: SEE WELDING REQUIREMENTS
1. P.E. WITH RELEVANT EXPERIENCE.
2. EIT WITH RELEVANT EXPERIENCE.
3. SEE THE MASONRY REQUIREMENTS FOR THE SI OF MASONRY
VENEERS SUBJECT TO BCNYS SECTION 1704.10.
1. SEE THE REQUIREMENTS IN BCNYS SECTION 1704.14.2 2.
2. THE RDP RESPONSIBLE FOR DESIGN.
1. SEE THE APPLICABLE CATEGORIES IN THIS TABLE.
1.
2.
3.
4.
5.
1.
2.
1.
2.
3.
4.
A. SPECIAL INSPECTION
SPECIAL INSPECTION WILL BE IN ACCORDANCE WITH
NYC BUILDING CODE.
SPECIAL INSPECTION IS REQUIRED OF MATERIALS,
INSTALLATION, FABRICATION, ERECTION OR PLACEMENT OF
COMPONENTS AND CONNECTIONS REQUIRING SPECIAL
EXPERTISE TO ENSURE COMPLIANCE WITH APPROVED
CONSTRUCTION DOCUMENTS.
COORDINATE SCHEDULES WITH THE AGENCY PERFORMING
SPECIAL INSPECTIONS TO ENSURE AMPLE TIME IS AVAILABLE TO
PERFORM THE REQUIRED TASKS.
THE SPECIAL INSPECTOR SHALL PROVIDE REPORTS TO THE
LOCAL BUILDING OFFICIAL, REGISTERED DESIGN PROFESSIONAL
IN CHARGE, AND THE OWNER'S DESIGNATED REPRESENTATIVE.
THESE REPORTS MUST BE IN COMPLIANCE WITH THE NYC CODE.
THE SPECIAL INSPECTOR SHALL IMMEDIATELY NOTIFY
THE CONTRACTOR IN WRITING OF NON-CONFORMANCE TO THE
APPROVED CONSTRUCTION DOCUMENTS, NYC BUILDING CODE,
OR OTHER VIOLATIONS OF THE APPLICABLE REFERENCED
MATERIAL STANDARDS IN THE NYC BUILDING CODE WITHIN THE
SCOPE OF THE SPECIAL INSPECTION REQUIREMENTS.
THE SPECIAL INSPECTION AGENCY SHALL SUBMIT A FINAL
REPORT TO THE BUILDING OFFICIAL, REGISTERED DESIGN
PROFESSIONAL IN RESPONSIBLE CHARGE, AND OWNER'S
REPRESENTATIVE STATING WHETHER WORK REQUIRING
SPECIAL INSPECTION WAS INSPECTED, REPORTED, AND FOUND
TO BE IN COMPLIANCE WITH THE APPROVED CONSTRUCTION
DOCUMENTS, NYC BUILDING CODE, AND THE APPLICABLE
REFERENCED MATERIAL STANDARDS IN THE NYC BUILDING CODE.
FINAL REPORTS SHALL CATALOG ALL INSPECTION,
TESTING, AND RELATED ENGINEER SIGNED REPORTS.
B. STRUCTURAL OBSERVATION
STRUCTURAL OBSERVATION IS THE VISUAL OBSERVATION OF
THE STRUCTURAL SYSTEM BY A REGISTERED DESIGN
PROFESSIONAL FOR GENERAL CONFORMANCE TO THE
APPROVED CONSTRUCTION DOCUMENTS AT SIGNIFICANT
CONSTRUCTION STAGES AND AT COMPLETION OF THE
STRUCTURAL SYSTEM. THESE OBSERVATIONS DO NOT WAIVE
THE RESPONSIBILITY FOR THE INSPECTION AS DEFINED BY
SPECIAL INSPECTION.
THE STRUCTURAL OBSERVER IS NOT INSPECTING FOR OSHA
COMPLIANCE AND TEMPORARY CONSTRUCTION, SUCH AS
BRACING, SHORING, MEANS AND METHODS, ETC.
COMMENTS:
PERIODIC SPECIAL INSPECTION: THE PART-TIME OR
INTERMITTENT OBSERVATION OF WORK REQUIRING SPECIAL
INSPECTION BY AN APPROVED SPECIAL INSPECTOR WHO IS
PRESENT IN THE AREA WHERE THE WORK HAS BEEN OR IS
BEING PERFORMED AND AT THE COMPLETION OF WORK.
CONTINUOUS SPECIAL INSPECTION: THE FULL-TIME
OBSERVATION OF WORK REQUIRING SPECIAL INSPECTION BY AN
APPROVED SPECIAL INSPECTOR WHO IS PRESENT IN THE ARE
WHERE WORK IS BEING PERFORMED.
ITEMS NOT SHOWN MAY REQUIRE CONTINUOUS OR PERIODIC
SPECIAL STRUCTURAL INSPECTION AT THE DISCRETION OF THE
ENGINEER. ITEMS LISTED MAY REQUIRE ALTERNATE
FREQUENCIES OF INSPECTION OTHER THAN SHOWN.
WELDING OF REINFORCING STEEL IS NOT ACCEPTABLE UNLESS
DIRECTED BY THE ENGINEER OF RECORD.
COLD-FORMED STEEL
· THE STEEL STUD MANUFACTURERS ASSOCIATION
STANDARDS ARE USED IN THIS PACKAGE. ANY
MANUFACTURER WHOSE PRODUCT GEOMETRIES MEETS OR
EXCEEDS SSMA STANDARDS ARE ACCEPTABLE. SEE TABLES
BELOW FOR SSMA NOMENCLATURE.
362 S 162 - 33
THICKNESS (MILS)
FLANGE SIZE (
IN)
MEMBER TYPE
WEB SIZE (
IN)
· THE FIRST SET OF NUMBERS INDICATE THE WEB SIZE
(NOMINAL MEMBER DEPTH):
6" MEMBER = 600
" MEMBER = 362
14" MEMBER = 1400
· FLANGE DESIGNATIONS:
STRUCTURAL STUD/JOIST (1
" FLANGE) S162
STRUCTURAL STUD/JOIST (2" FLANGE) S200
RUNNER TRACK (1
" LEG) T150
· THE LAST TWO NUMBERS INDICATE THE STEEL THICKNESS:
GAGE DESIGN MINIMUM SSMA
20 0.0346" 0.0329" 33 MILS
18 0.0451" 0.0428" 43 MILS
16 0.0566" 0.0538" 54 MILS
14 0.0713" 0.0677" 68 MILS
12 0.1017" 0.0966" 97 MILS
STUD
· ALL FIELD CUTTING OF STUDS MUST BE DONE BY SAWING
OR SHEARING. TORCH CUTTING OF COLD-FORMED
MEMBERS IS UNACCEPTABLE.
· NO NOTCHING OR COPING OF STUDS IS ALLOWED, UNLESS
STATED WITHIN THIS DRAWING PACKAGE.
· ENDS OF STUDS MUST SEAT FIRMLY IN RUNNER TRACK,
WHICH MUST HAVE FULL BEARING ON STRUCTURE.
· SPLICING OF WALL STUDS IS NOT ALLOWED, UNLESS
OTHERWISE STATED WITHIN THIS DRAWING PACKAGE.
ALL 16GA AND HEAVIER MEMBERS MUST
BE 50KSI MINIMUM.
CONNECTIONS
· ALL SCREW CONNECTIONS BASED ON CCFSS TECHNICAL
BULLETIN VOL. 2, NO. 1 WHICH OUTLINES THE AISI
SPECIFICATION PROVISIONS FOR SCREW CONNECTIONS.
· FOR SCREWS
" MINIMUM CLEARANCE MUST BE
MAINTAINED FROM ALL EDGES OF THE STEEL MEMBERS. A
" MINIMUM ON CENTER SPACING MUST BE MAINTAINED
BETWEEN ADJACENT SCREWS.
· POWER DRIVEN FASTENER SYSTEMS, EXPANSION ANCHOR
SYSTEMS, MASONRY SCREW SYSTEMS, AND ADHESIVE
ANCHOR SYSTEMS CONNECTIONS ARE BASED ON
LITERATURE PUBLISHED BY HILTI FASTENING SYSTEMS, INC.
ALTERNATE MANUFACTURER'S FASTENERS OF
COMPARABLE SPECIFICATIONS AND LOAD CAPACITIES ARE
ACCEPTABLE.
FASTENER / CONNECTOR SCHEDULE
NOTES: SEE SECTIONS AND DETAILS FOR LOCATION
AND NUMBER OF CONNECTORS
CONNECTOR
SCREWS
SUBSTRATE
METAL TRACK
STUD - TO -
STUD
METAL - TO -
STRUCTURAL
STEEL
WOOD FRAMING
OR PLYWOOD
DESCRIPTION
#10-16 x 5/8"
PAN HEAD
#10-16 x 5/8"
HEX HEAD
#12-24 x 1 - 1/4"
HEX HEAD, #5 TIP
#14-20 x 2 - 3/4"
PHILIPS FLAT HEAD,
#4 WINGS
PRODUCT
BUILDEX "TEKS" COMPASS
"DARTS" GRABBER SELF
DRILLING
BUILDEX "TEKS" COMPASS
"DARTS" GRABBER SELF
DRILLING
BUILDEX "TEKS"
HILTI KWIK-PRO
BUILDEX "TEKS"
HILTI KWIK-PRO
70 South Franklin Street, Wilkes-Barre, PA 18701
570 | 824-6340 info@edpons.comedpons.com
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT:
Facilities
Management o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
NUCLEAR MEDICINE
SPECT-CT SITE PREP
Services
4-07-21
FE PROJECT #
630A4-20-424
Revisions: Date
20-176
NEW YORK HARBOR
HEALTH CARE SYSTEM
BROOKLYN, NY
www.fellp.com
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704 fx 855-320-8735
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
ENGINEERING LLPLiscum
181 CHURCH STREET
POUGHKEEPSIE, NEW YORK 12601
PHONE 845-452-2268 FAX 845-452-3752
ARCHITECTURE
PLANNING INTERIORS
McCormack VanVoorhis LLP
100% CONSTRUCTION DOCUMENTS
AutoCAD SHX Text
SECTIONS & NOTES
AutoCAD SHX Text 1-S-200
AutoCAD SHX Text
ME
AutoCAD SHX Text
ME
AutoCAD SHX Text Designed By:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text FE Project No.
AutoCAD SHX Text 20-176
AutoCAD SHX Text
ME
B
8 9
T100
PARTIAL SECOND FLOOR FRAMING PLAN - TEMPORARY SUPPORT FOR MOVING CT EQUIPMENT INTO PLACE
SCALE:
" = 1'-0"
±20'-4" TEMPORARILY REMOVE EXISTING WINDOW 20'-4" 20'-4"
±2'-8" ±14'-0" TEMPORARY WALL OPENING
T100
±3'-8"
T100
T100
MC8X20X10'-0" PLANK
REMOVE & REPLACE TOPPING,
PER DWG. S100, PRIOR TO THE
INSTALLATION OF ANY EQUIPMENT TYP.
INSTALL ALL REINFORCING BEAMS PER DWG.
S100, PRIOR TO THE INSTALLATION
OF ANY EQUIPMENT TYP.
T100
MC8X20X10'-0" PLANK MC8X20X10'-0" PLANKMC8X20X10'-0" PLANK
MC8X20X10'-0" PLANK
MC8X20X10'-0" PLANK
MC8X20X10'-0" PLANK MC8X20X10'-0" PLANK
INDICATES STEEL PLATES
BELOW TOPPING CONCRETE
(SEE DWG. S100.)
7 8 9
PARTIAL ELEVATION NORTH FACADE - EAST SIDE - NORTH WING
SCALE:
" = 1'-0"
T100
LEVEL 2
EL. = 52-0"
LEVEL 3
66'-0"
EXISTING TYPE L WINDOW
±20'-4" EXISTING "TYPE L" WINDOW TO BE TEMPORARILY REMOVED
& RE-INSTALLED AFTER CT EQUIPMENT IS INSTALLED
±14'-0" OF CMU BACKUP WALL
TO BE TEMP. REMOVED & REPLACED
20'-4" 20'-4"
REMOVE & RE-INSTALL
STONE AS REQ'D
±2'-8"
A
LEVEL 2
EL. = 52-0"
LEVEL 3
EL. = 66'-0"
1'-3
EXISTING 4" STONE
EXISTING 8" STONE
EXISTING SLAGBLOK
FLOOR SYSTEM
EXISTING WALL
FINISH ON
FURRING (V.I.F.)
EXISTING
SLATE SILL
EXISTING WINDOW UNIT
SECTION - TEMPORARY OPENING IN EXISTING EXTERIOR WALL
SCALE:
" = 1'-0"
T100
A
LEVEL 2
EL. = 52-0"
LEVEL 3
EL. = 66'-0"
1'-3
EXISTING SLAGBLOK
FLOOR SYSTEM
C
L E
A R
A N
C E
V
I F
A
LEVEL 2
EL. = 52-0"
LEVEL 3
EL. = 66'-0"
1'-3
RE-INSTALL
EXISTING
4" STONE
RE-INSTALL
EXISTING
8" STONE
EXISTING SLAGBLOK
FLOOR SYSTEM
EXISTING
SLATE SILL
RE-INSTALL
ORIGINAL WINDOW
REMOVE SECTION
OF WINDOW
REMOVE
VENEER STONE &
NON-BEARING
BACKUP WALL
FULLY GROUTED
6" CMU
FULLY GROUTED
10" CMU
FULLY GROUTED 10"
CMU BOND BEAM
W/ (2)-#4 CONT.
EXISTING SHELF
ANGLE (V.I.F.)
EXISTING SHELF
ANGLE (V.I.F.)
#5 A706 GRADE 60
(WELDABLE)
VERT. @ 16" O.C.
RE-INSTALL
ALL DOWELS TYP.
WALL TIES
(BY MASONRY
CONTRACTOR) TYP.
CAREFULLY CHIP OUT
CONCRETE AS REQ'D
TO WELD REBAR TO EXISTING
BEAM FLANGE. GROUT
CONCRETE OPENING SOLID
WHEN FINISHED. TYP.
EXISTING W16X40 (V.I.F.)
EXISTING CONDITION TEMPORARY WALL OPENING REPAIR OF TEMPORARY WALL OPENING
E80 WELD
ELECTRODE
EXISTING 8" CMU
EXISTING 4" CMU
FURRING
& GYPSUM BOARD
EXISTING W16X40 (V.I.F.)EXISTING W16X40 (V.I.F.)
EXISTING SHELF
ANGLE (V.I.F.)
NOTE:
FIELD VERIFY ALL
EXISTING
CONDITIONS TYP.
STEEL BEAM
(SEE PLAN)
CT EQUIPMENT
NEW
REINFORCED
TOPPING
CASTER
TEMP. CHANNEL
ON FLAT
(SEE PLAN)
CASTER
TEMP. CHANNEL
ON FLAT
(SEE PLAN)
SECTION - EQUIPMENT ON TEMPORARY CHANNELS
NOT TO SCALE
T100
MASONRY CONSTRUCTION
1. MASONRY WALLS SHOWN ON STRUCTURAL DRAWINGS HAVE BEEN DESIGNED IN ACCORDANCE WITH BUILDING
CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530 / ASCE 5 / TMS 402).
2. MASONRY WALLS SHOWN ON STRUCTURAL DRAWINGS SHALL BE CONSTRUCTED IN ACCORDANCE WITH
SPECIFICATIONS FOR MASONRY STRUCTURES (ACI 530.1 / ASCE 6 / TMS 602) AND THE PROJECT
SPECIFICATIONS. IF THERE ARE ANY CONFLICTS BETWEEN THE TWO, THE MORE RESTRICTIVE REQUIREMENT
SHALL BE APPLICABLE.
3. DETERMINE THE COMPRESSIVE STRENGTH OF MASONRY (F'M) BY THE UNIT STRENGTH METHOD (SECTION 1.4, B.2 OF ACI 530.1 / ASCE 6 / TMS 602).
3.1. MORTAR PROPERTIES SHALL BE DETERMINED BY TESTS PER ASTM C780 AND MORTAR SHALL BE
STRENGTH TESTED IN ACCORDANCE WITH ASTM C39 (3" DIAMETER X 6" LONG CYLINDERS).
3.2. THE STRENGTH OF GROUT SHALL BE DETERMINED BY TESTS IN ACCORDANCE WITH ASTM C1019.
4. INTERSECTING BEARING WALLS SHALL BE ANCHORED BY ONE OF THE FOLLOWING METHODS:
4.1. FIFTY PERCENT OF THE UNITS AT THE INTERSECTION SHALL BE LAID IN AN OVERLAPPING MASONRY
BONDING PATTERN, WITH ALTERNATE UNITS HAVING A BEARING OR NOT LESS THAT 3" ON THE UNIT
BELOW.
4.2. WALLS SHALL BE TIED BY GALVANIZED STEEL STRAPS 1
" X
" X 24" WITH 2" BEND AT 90° AT EACH END.
GROUT STRAPS SOLID INTO CORES OF BLOCK AT 24" MAXIMUM VERTICAL SPACING.
THE ABOVE DO NOT APPLY AT CONTROL JOINTS OR WHERE NON-LOAD-BEARING PARTITIONS ABUT
BEARING WALLS.
5. CORNERS OF BEARING WALLS SHALL BE BUILT IN RUNNING BOND.
6. PROVIDE A MINIMUM OF 24" DEPTH OF SOLID MASONRY UNDER THE BEARING ENDS OF ALL BEAMS, BEAM
LINTELS, AND LH AND DLH SERIES JOISTS; 16" DEPTH OF SOLID MASONRY UNDER THE BEARING ENDS OF ALL K
SERIES JOISTS AND SLABS; AND 8" OF SOLID MASONRY UNDER THE BEARING ENDS OF LOOSE LINTELS.
7. PROVIDE HORIZONTAL JOIST REINFORCEMENT PER ASTM A82, GALVANIZED, AT 16" ON CENTER VERTICALLY.
SEE SPECIFICATIONS. UNLESS OTHERWISE NOTED, PROVIDE A GALVANIZED LADDER TYPE JOINT
REINFORCEMENT.
8. WELDING REINFORCING BARS (INCLUDING TACK WELDING) IS NOT PERMITTED WITHOUT PERMISSION OF
ENGINEER IN WRITING.
9. PROVIDE SHOP DRAWINGS WHICH INDICATE SIZE, SPACING, BENDING DETAILS, AND TYPE OF ALL
REINFORCING BARS PLACED IN MASONRY WALLS.
10. PROVIDE DOWELS FROM SUPPORTING MEMBER (FOOTING, BEAM, OR SLAB) FOR ALL REINFORCED WALLS
SAME SIZE, LOCATION, AND SPACING AS WALL REINFORCING.
11. WALL REINFORCING SHALL BE HELD IN POSITION DURING GROUTING.
12. FOR BARS AT FACE OF WALL, MAINTAIN
" CLEARANCE FROM INSIDE FACE OF CMU TO REINFORCING.
13. SPLICES (GRADE 60 DEFORMED BARS):
13.1. ALL LAP SPLICES SHALL BE TYPE 2 (AS DEFINED IN THE TABLE BELOW), UNLESS OTHERWISE NOTED ON
THE DRAWINGS. TYPE 1 SPLICES SHALL BE USED THE FOLLOWING CONDITIONS:
13.1.1. DOWELS FROM FOUNDATIONS TO BASEMENT WALLS (THOSE WALLS BELOW GRADE, RESISTING
LATERAL EARTH PRESSURES FROM ONE SIDE, AND LATERALLY SUPPORTED AT THE TOP AND
BOTTOM OF THE WALL).
13.1.2. DOWELS FROM SUPPORTING ELEMENTS TO WIND WALLS (THOSE WALLS ABOVE GRADE RESISTING
LATERAL FORCES FROM ONE SIDE, AND LATERALLY SUPPORTED AT THE TOP AND BOTTOM OF THE
WALL).
13.1.3. ALL REINFORCING (DOWEL AND VERTICAL BARS) IN FOUNDATION WALLS (THOSE WALLS WITH EQUAL
LATERALS EARTH PRESSURES ON EACH SIDE FOR THE FULL HEIGHT OF THE WALL).
13.1.4. ALL REINFORCING (DOWEL AND VERTICAL BARS) IN COMPRESSION PIERS (THOSE PIERS SUBJECT
ONLY TO DOWNWARD VERTICAL LOADS, NOT THOSE SUBJECT TO UP-LIFT AND/OR MOMENT)
13.2. INCREASE SPLICE LENGTH BY 50% FOR EPOXY-COATED REINFORCING.
13.3. SPLICE LENGTHS GREATER THAN 60" REQUIRE HIGH LIFT GROUTING. THE CONTRACTOR, AT THEIR
OPTION, MAY USE OPEN-ENDED MASONRY UNITS OR MECHANICAL SPLICES FOR EASE OF CONSTRUCTION.
BAR MASONRY LAP SPLICE LENGTH
SIZE TYPE 1 (40DB) TYPE 2 (72DB)
#3 15" 27"
#4 20" 36"
#5 25" 45"
#6 30" 54"
#7 35" 63"
#8 40" 72"
DESIGN STRESSES
REINFORCING BARS (ASTM A615 OR ASTM A706, GRADE 60)-------------------------------- FY=60,000PSI
MC STEEL CAHNNELS (ASTM A36)---------------------------------------------------------------------- FY=36,000PSI
MASONRY---------------------------------------------------------------------------------------------------------F'M=1,500PSI
LOAD-BEARING CMU (ASTM C55 OR C90)
BRICK (ASTM C216 GRADE SW)
MORTAR-------------------------------------------------------------------------------------------------- TYPE M OR S
GROUT (ASTM C476)--------------------------------------------------------------------------------- 3,000PSI
DEMOLITION
1. THE CONTRACTOR IS TO OBTAIN AND PAY FOR ALL NECESSARY PERMITS FOR THE DEMOLITION
AND REMOVAL WORK.
2. NOTIFY ALL LOCAL AGENCIES HAVING JURISDICTION.
3. LOCATE EXISTING UNDERGROUND UTILITIES IN ALL AREAS OF CONSTRUCTION. COORDINATE
WITH UTILITY COMPANIES FOR ANY SHUT-OFF REQUIREMENTS OF STILL ACTIVE LINES. CALL THE
NY ONE-CALL CENTER.
4. DEMOLITION PROCEDURES, SHORING REQUIREMENTS, SEQUENCE TECHNIQUES, ETC., EITHER
GIVEN IN OR IMPLIED BY THESE DRAWINGS, ARE SUGGESTIONS ONLY. CONTRACTOR SHALL
RETAIN, AT HIS OWN EXPENSE, A PROFESSIONAL ENGINEER LICENSED IN THE JURISDICTION
WHERE THE PROJECT IS LOCATED TO DETERMINE ALL CONSTRUCTION PHASE REQUIREMENTS.
CONTRACTOR SHALL SUBMIT DRAWINGS , SIGNED AND SEALED BY HIS ENGINEER, TO THE
OWNER AND ENGINEER FOR CONCEPT REVIEW AND RECORD PURPOSES. CONTRACTOR SHALL
BE SOLELY RESPONSIBLE FOR THE PROTECTION, STABILITY, ETC., OF EXISTING AND NEW
STRUCTURES DURING EXECUTION OF THE WORK.
5. BEFORE UNDERTAKING ANY DEMOLITION WORK, ASCERTAIN THE EXISTING CONDITIONS OF THE
PROPERTIES AND BUILDINGS ADJOINING OR IN CLOSE PROXIMITY OF THE PREMISES BY SURVEY.
6. CONTRACTOR SHALL PERFORM ALL WORK IN SUCH A MANNER AS TO PROTECT EXISTING AND
ADJACENT STRUCTURES AND BE RESPONSIBLE TO PROPERLY REPAIR ANY DAMAGE THAT
OCCURS AS A RESULT OF HIS WORK. CONTRACTOR SHALL REPAIR ALL DAMAGES TO STREETS,
SIDEWALK, UTILITY LINES, OR ANY OTHER PUBLIC OR PRIVATE PROPERTIES RESULTING FROM
THE EXECUTION OF THE WORK AT NO COST TO THE OWNER OR ENGINEER.
7. CEASE OPERATIONS AND NOTIFY OWNER AND ENGINEER IMMEDIATELY IF SAFETY OR INTEGRITY
OF STRUCTURE APPEAR TO BE ENDANGERED. PROPERLY BRACE AND SUPPORT STRUCTURE
BEFORE RESUMING OPERATIONS.
8. NOTIFY OWNER AND ENGINEER IMMEDIATELY IF ANY PORTION OF EXISTING STRUCTURE WHICH
IS NOT TO BE DEMOLISHED IS DAMAGED. CONTRACTOR SHALL PAY FOR ALL REPAIR COSTS,
INCLUDING DESIGN AND INSPECTION EXPENSES.
9. DO NOT CUT OR ALTER ANY STRUCTURAL MEMBERS WITHOUT WRITTEN AUTHORIZATION OF THE
ENGINEER UNLESS INDICATED ON THE STRUCTURAL DRAWINGS.
10. DO NOT ALLOW RESULTING DEBRIS TO ACCUMULATE. DISPOSE OF THE MATERIAL IN A LEGAL
MANNER.
SUGGESTED SEQUENCE OF WORK:
1. FIELD-VERIFY ALL DIMENSIONS & EXISTING CONDITIONS. NOTIFY
ENGINEER IF EXISTING CONDITIONS ARE DIFFERENT THAN WHAT IS
SHOWN ON THESE DRAWINGS.
2. INSTALL ALL PERMANENT REINFORCEMENT BEAMS AND FRAMING,
PER CONSTRUCTION DOCUMENTS.
3. REMOVE EXISTING TOPPING, AND INSTALL STEEL REINFORCEMENT
PLATES AND REINFORCED TOPPING, PER CONSTRUCTION
DOCUMENTS. ALLOW TOPPING SLAB TO CURE TO ITS FULL 28-DAY
COMPRESSIVE STRENGTH.
4. CREATE TEMPORARY WALL OPENING. CAREFULLY REMOVE
VENEER STONE AND EXISTING WINDOWS FOR RE-INSTALLATION.
DO NOT STORE MASONRY OR HEAVY LOADS ON THE SLAGBLOK
FLOOR FRAMING.
5. PLACE TEMPORARY CHANNELS ON FLOOR, SPANNING OVER
UNDERSLAB STEEL BEAMS.
6. CRANE EQUIPMENT INTO LEVEL 2 ROOM, ONE PIECE AT A TIME.
PLACE EQUIPMENT CASTERS ON STEEL CHANNELS, AND MOVE
PIECE OF EQUIPMENT TO ITS PERMANENT LOCATION PRIOR TO
MOVING THE NEXT PIECE OF EQUIPMENT INTO THE LEVEL 2 SPACE.
7. ONCE ALL EQUIPMENT HAS BEEN MOVED TO THE PERMANENT
LOCATIONS, REPAIR THE TEMPORARY WALL OPENING.
NOTES:
1. THE CONTRACTOR SHALL MAINTAIN WEATHER TIGHTNESS OF THE FACILITY AND
EXTERIOR WALL DURING THE ENTIRE CONSTRUCTION AND CT EQUIPMENT DELIVERY
PROCESS.
2. THE CONTRACTOR SHALL REPLACE ALL FLASHING, DAMAGED OR REMOVED DURING THE
TEMPORARY…
This is the start of the file's text. The full file is on GovTribe.