S02 DRAWINGS.pdf
PDF 27 MB Posted
- Solicitation number
- 36C24221B0034
About this file
This document outlines the scope of work for a federal construction contract solicitation to replace condenser water piping at a Department of Veterans Affairs medical center. Key details include:
-
The solicitation number is 36C24221B0034 and is for project 630A4-13-403 to replace condenser water piping from the chiller plant to cooling towers on the east side of Building 4 at the VA Brooklyn Medical Center. Work includes replacing valves, installing electrical heat tracing and a centrifugal separator/cleaner package, as well as support piers for piping located on the roof.
-
The period of performance is 260 days from notice to proceed. The general contractor must submit preliminary schedules, bonds, insurance, and a schedule of values within 10 days of contract award. Off-hours and weekend work may be required.
-
The general contractor is responsible for safety compliance, hazardous materials reporting and inventory, environmental protection, daily cleanup, and taking precautions to prevent damage to facilities including elevators. A site superintendent must be present at all times and accessible by cell phone.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S05 RFI ANSWERS.pdf | ||
| 36C24221B0034 0001.docx | DOCX document | |
| S02 Safety or Environmental Violations and Experience Modification Rate.pdf | ||
| S02 Participation Goals for Minorities and Females.pdf | ||
| S02 SPECS.pdf | ||
| S02 ALL POSTERS.pdf | ||
| S02 VA ID PACKAGE 06-18-2019.pdf | ||
| 36C24221B0034_1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SITE
LOCATION
1 5
4A
8A
B
U
S
L
A
N
E
O
N
L
Y
T
A
X
I
M
B
U
L
E
T
T
E
T E
N A
N T
P A
R K
I N
G
4B
POLY PL.
SCALE: N.T.S.
N
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT:
Facilities
Management1
NUCLEAR MEDICINE
SPECT-CT SITE PREP
Services
4-27-21
FE PROJECT #
630A4-20-424
Revisions: Date
20-176
NEW YORK HARBOR
HEALTH CARE SYSTEM
BROOKLYN, NY
www.fellp.com
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704 fx 855-320-8735
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
ENGINEERING LLPLiscum
181 CHURCH STREET
POUGHKEEPSIE, NEW YORK 12601
PHONE 845-452-2268 FAX 845-452-3752
ARCHITECTURE
PLANNING INTERIORS
McCormack VanVoorhis LLP
100% CONSTRUCTION DOCUMENTS
GI-001
SHEET #: DRAWING #: DRAWING TITLE
1-MH-001
HVAC: SYMBOLS, ABBREVIATIONS & NOTES
1-ES-001 ELECTRICAL: SYMBOLS, ABBREVIATIONS & NOTES
1-FX-001
FIRE PROTECTION: SYMBOLS, ABBREVIATIONS & NOTES
HVAC:
ELECTRICAL:
FIRE PROTECTION SPRINKLER:
GENERAL:
1-ES-801 ELECTRICAL: SCHEDULES
1-MH-201 HVAC: DEMOLITION & NEW WORK
1-PL-001 PLUMBING: SYMBOLS, ABBREVIATIONS & NOTES
PLUMBING:
1-PL-101
1-ES-101 ELECTRICAL: POWER PLANS DEMOLITION & NEW WORK
1-FX-201 FIRE PROTECTION: RCP DEMOLITION & NEW WORK
1-ES-201 ELECTRICAL: LIGHTING PLANS DEMOLITION & NEW WORK
PLUMBING: MEDICAL GAS DEMOLITION & NEW WORK
1-AS-001
GENERAL INFORMATION: TITLE SHEET WITH INDEX OF DRAWINGS
ARCHITECTURAL:
1-LS-100 ARCHITECTURAL: LIFE SAFETY FLOOR PLAN
ARCHITECTURAL: SYMBOLS, ABBREVIATIONS & NOTES
1-PH-100
AS-D-100 ARCHITECTURAL: DEMOLITION FLOOR PLAN
ARCHITECTURAL: PHASING PLAN, SUMMARY, AND NOTES
1-AS-100
1-AS-101
1-AS-600
ARCHITECTURAL: PROPOSED PLAN OPTIONS 1 & 2
ARCHITECTURAL: ROOM FINISH SCHEDULE, FINISH SCHEDULE
ARCHITECTURAL: REFLECTED CEILING PLAN
C1-A2 COVER SHEET, DISCLAIMER - SITE READINESS, GENERAL NOTES & EQUIPMENT LAYOUT
GE DRAWINGS:
M1-E3
HVAC, ELECTRICAL NOTES, LAYOUT & ELEVATIONS
A3-A6 RADIATION PROTECTION, EQUIPMENT DETAILS & DELIVERY
S1-S4 STRUCTURAL NOTES, LAYOUT & DETAILS
E4-E5 POWER REQUIREMENTS & ELECTRICAL DETAILS - INTERCONNECTIONS
1-ES-102 ELECTRICAL: POWER PLANS, 3RD., 4TH, & 5TH FLOORS NEW WORK
1-S-100
1-S-200 STRUCTURAL: NOTES & SPECIAL INSPECTIONS
STRUCTURAL: SECOND FLOOR FRAMING REINFORCEMENT PLAN AND SECTIONS
STRUCTURAL:
1-AS-102
ARCHITECTURAL: EQUIPMENT PLAN AND SCHEDULE
1-T-200
STRUCTURAL: TEMPORARY SUPPORT FOR EQUIPMENT INSTALLATION
NEW WALL AND DOOR
EXISTING WALL AND
DOOR TO REMAIN
9-4-2b
W#
3-AS-000
3-AS-000
3-AS-000
NEW WINDOW/
STOREFRONT TAG
SEE SHEET A600
NEW DOOR TAG
NEW PARTITION TAG
FIRE/SMOKE RATING (SEE
3-AS-600 FOR PARTITION
LEGEND)
NOMINAL SIZE
SPECIFICATION CATEGORY
SEQUENCE NUMBER
DOOR NUMBER
DOOR SIZE (SEE 3-AS-600
FOR DOOR SIZE LEGEND)
NEW EXTERIOR
ELEVATION TAG
VIEW NUMBER
SHEET NUMBER
NEW WALL
SECTION TAG
VIEW NUMBER
SHEET NUMBER
NEW BUILDING
SECTION TAG
3-AS-000
VIEW
NUMBER
SHEET
NUMBER
# 3-AS-000 NEW INTERIOR
ELEVATION TAG
VIEW
NUMBER
SHEET
NUMBER
VIEW NUMBER
SHEET NUMBER
NEW DETAIL
CALLOUT TAG
GENERAL NOTES:
1. IN THE EVENT OF INCONSISTENCIES WITHIN OR BETWEEN PARTS OF THE CONTRACT DOCUMENTS, OR BETWEEN THE CONTRACT DOCUMENTS AND APPLICABLE STANDARDS, CODES AND ORDINANCES, THE CONTRACTOR SHALL:
(1) PROVIDE THE BETTER QUALITY OR GREATER QUANTITY OF WORK
OR
(2) COMPLY WITH THE MORE STRINGENT REQUIREMENT; EITHER OR BOTH IN ACCORDANCE WITH THE
ARCHITECT'S INTERPRETATION.
2. VERIFY ALL DIMENSIONS IN FIELD FOR FIT OF UNITS SPECIFIED. MODIFY DIMENSIONS ON SHOP DRAWING AS
REQUIRED, PRIOR TO SUBMITTAL OR RELEASE FOR PURCHASE OR FABRICATION.
3. ALL ARCHITECTURAL CASEWORK & WOODWORK IS TO BE INSTALLED ON TOP OF NEW FLOOR FINISHES. (CARPET, SHEET VINYL., ETC.)
4. THE DESIGN OF THE PROJECT IS IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE
5. CONTRACTORS SHALL VERIFY & ASSUME RESPONSIBILITY FOR VERIFYING ALL EXISTING OR AS-BUILT CONDITIONS
AND INCLUDE INFORMATION IN SHOP DRAWINGS PRIOR TO SUBMITTAL TO A & E.
6. EACH CONTRACTOR TO BE RESPONSIBLE FOR APPLIED FINISHES FOR THEIR WORK.
7. IN AREA OF WORK EACH CONTRACTOR TO BE RESPONSIBLE FOR ALL ADJACENT FINISHED WORK OF OTHER
TRADES. EACH CONTRACTOR IS TO PROTECT HIS OWN WORK.
8. ALL CONTRACTORS ARE TO COORDINATE THEIR WORK IN ACCORDANCE WITH DRAWINGS.
9. ALL PENETRATIONS THROUGH RATED WALLS & CORRIDOR WALLS ARE TO BE FIRE-STOPPED BY TRADE MAKING
PENETRATION, WITH APPROVED MATERIALS PER DRAWINGS AND SPECIFICATIONS.
10. ALL DIMENSIONS SHOWN ON DRAWINGS ARE SUBJECT TO VERIFICATION OF ACTUAL DIMENSIONS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL DIMENSIONS IN THE FIELD TO INSURE PROPER AND
ACCURATE FIT OF MATERIALS AND ITEMS TO BE INSTALLED.
11. THE CONTRACTOR SHALL CAREFULLY STUDY AND COMPARE THE CONTRACT DOCUMENTS WITH EACH OTHER AND THE INFORMATION FURNISHED BY THE OWNER, AND SHALL AT ONCE REPORT TO THE ARCHITECT ERRORS, INCONSISTENCIES OR OMISSIONS DISCOVERED. THE CONTRACTOR SHALL NOT BE LIABLE TO THE OWNER, OR ARCHITECT FOR DAMAGE RESULTING FROM ERRORS, INCONSISTENCIES OR OMISSIONS IN THE CONTRACT DOCUMENTS UNLESS THE CONTRACTOR RECOGNIZED SUCH ERROR, INCONSISTENCY OR OMISSION AND KNOWINGLY FAILED TO REPORT IT TO THE ARCHITECT. IF THE CONTRACTOR PERFORMS ANY CONSTRUCTION ACTIVITY KNOWING IT INVOLVES A RECOGNIZED ERROR, INCONSISTENCY OR OMISSION IN THE CONTRACT DOCUMENTS WITHOUT SUCH NOTICE TO THE ARCHITECT, THE CONTRACTOR SHALL ASSUME APPROPRIATE RESPONSIBILITY FOR SUCH PERFORMANCE AND SHALL BEAR AN APPROPRIATE AMOUNT OF THE ATTRIBUTABLE
COSTS FOR CORRECTION.
12. WHENEVER THE DRAWINGS SHOW EXISTING CONSTRUCTION, REQUIRED AS PART OF THE WORK OR NOT, IT IS UNDERSTOOD THAT IT IS SHOWN AS A MATTER OF INFORMATION TO BE SUBSTANTIALLY CORRECT. THE OWNER ASSUMES NO RESPONSIBILITY THEREFORE. THE CONTRACTOR SHALL MAKE ITSELF TOTALLY FAMILIAR WITH ALL EXISTING CONDITIONS AFFECTING THE NATURE AND MANNER OF CONDUCTING THEIR WORK. ANY ERRORS DUE TO THE CONTRACTOR'S FAILURE TO VERIFY ALL GRADES, ELEVATIONS, LOCATIONS, OR DIMENSIONS SHALL BE
PROMPTLY RECTIFIED BY THE CONTRACTOR WITHOUT ANY ADDITIONAL COST TO THE OWNER.
13. WHERE EQUIPMENT LINES OR PIPING AND/OR CONDUIT ARE SHOWN DIAGRAMMATICALLY, THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION AND ORDERLY ARRANGEMENT OF THE VARIOUS LINES OF PIPING AND CONDUIT INCLUDED IN THE WORK OF HIS CONTRACT. HE SHALL COORDINATE THE WORK OF SEVERAL CONTRACTORS AND PREVENT ALL INTERFERENCE'S BETWEEN EQUIPMENT, LINES OF PIPING, ARCHITECTURAL
FEATURES, AND AVOID ANY UNSIGHTLY ARRANGEMENTS IN THE EXPOSED AREAS.
14. ALL WORK SHALL BE EXECUTED IN A THOROUGH, SUBSTANTIAL, WORKMANLIKE MANNER, IN COMPLETE ACCORDANCE WITH THE MANUFACTURER'S MOST RECENT RECOMMENDATIONS UNLESS OTHERWISE SPECIFIED
OR PERMITTED BY THE ARCHITECT.
15. CONTRACTOR IS RESPONSIBLE FOR ALL I.T. TERMINATIONS, SEE ELECTRICAL DRAWINGS.
HEALTH & SAFETY GENERAL NOTES:
1. ALL EXISTING EXIT DOORS ARE REQUIRED TO BE KEPT CLEAR AT ALL TIMES.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CONTROL OF CHEMICAL FUMES, GASES, AND
OTHER CONTAMINATES PRODUCED BY WELDING, GASOLINE OR DIESEL ENGINES, ROOFING,
PAVING, PAINTING, ETC., TO ENSURE THEY DO NOT ENTER OCCUPIED PORTIONS OF THE BUILDING
OR AIR INTAKES.
3. THE CONTRACTOR SHALL BE RESPONSIBLE TO ENSURE THAT ACTIVITIES AND MATERIALS WHICH
RESULT IN "OFF-GASSING" OF VOLATILE ORGANIC COMPOUNDS SUCH AS GLUES, PAINTS,
FURNITURE, CARPETING, WALL COVERING, DRAPERY, ETC., ARE SCHEDULED, CURED OR
VENTILATED IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS BEFORE A SPACE CAN
BE OCCUPIED.
DOORS & FRAMES
1. CENTER LINE OF ALL PANIC DEVICES. PUSH BARS SHALL BE 38" (3'-2") ABOVE FINISHED FLOOR (MAX.
VERIFY WITH VA)
2. CLEAN AND CAULK THE FULL PERIMETER OF ALL GLASS, FRAMES, AND PANEL EDGES OF NEW
FRAMES AND LITES AS PER SPECIFICATIONS.
3. ALL NEW FRAMES IN GYPSUM BOARD PARTITIONS TO HAVE THREE (3) ANCHORS PER JAMB MINIMUM
INTO STUD AND FRAME.
4. ALL DOOR FRAMES SHALL BE PROVIDED WITH SILENCERS.
5. EXTERIOR METAL DOORS AND FRAMES ARE TO BE INSULATED.
6. ALL NEW FRAME IN MASONRY TO RECEIVE A MINIMUM OF 3 ANCHORS PER JAMB.
7. ALL GLASS IN EXTERIOR DOORS AND FRAMES TO BE INSULATED.
PLUMBING
1. PLUMBING CONTRACTOR TO PROVIDE AND INSTALL ALL NEW PLUMBING FIXTURES AS INDICATED (SEE PLANS, SPEC, AND SCHEDULE) WITH ALL REQUIRED PIPING, TRAPS, VENTING, CLEANOUTS, ETC., AS SHOWN OR AS REQUIRED PER CODE.
2. ALL EXPOSED PIPING BELOW NEW SINKS/LAVATORIES ARE TO BE INSULATED/PROTECTED TO MEET
ALL ADA REQUIREMENTS.
3. PLUMBING CONTRACTOR TO COORDINATE HIS WORK IN SPECIAL ROOMS WITH CASEWORK ROUGH-IN REQUIREMENTS OF THAT TRADE AND TO COORDINATE HIS WORK WITH ROUGH-IN REQUIREMENTS.
ARCHITECTURAL CASEWORK & EQUIPMENT
1. GENERAL CONTRACTOR IS TO PROVIDE ALL ROUGH-IN INFORMATION ON SHOPS (LOCATION & SIZE) SO AS NOT TO DELAY THE WORK OF OTHER TRADES. THE WORK OF OTHER TRADES IS BUILT INTO THE STRUCTURE, CASEWORK SHOPS MUST BE SUBMITTED AND APPROVED PRIOR TO ERECTION OF
STRUCTURE.
2. ALL CABINET DOORS AND DRAWERS TO HAVE LOCKS EXCEPT SINK CABINETS. CABINET LOCKS IN ALL
ROOMS TO BE KEYED ALIKE IN EACH ROOM AND DIFFERENTLY FROM OTHER ROOMS.
3. GENERAL CONTRACTOR SHALL INSTALL ALL ARCHITECTURAL CASEWORK FOR ALL ROOMS SHOWN
ON PLANS OR CALLED FOR IN SCHEDULES. INSTALL ALL TOPS, BACK SPLASHES, FILLERS,
BLOCKING, ETC.
4. GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONS PIPE CHASES OR OTHER OBSTRUCTIONS IN
FIELD FOR PROPER INSTALLATION OF CABINETWORK AND ALTER WORK AS NECESSARY FOR
PROPER FIT.
5. GENERAL CONTRACTOR SHALL PROVIDE AND INSTALL GROMMETS AS REQUIRED TO ALLOW ACCESS TO ALL POWER, DATA AND COMMUNICATION RECEPTACLES. ALL NEW COUNTERTOPS TO RECEIVE A
MINIMUM OF ONE GROMMET FOR EVERY 40" OF LINEAR LENGTH.
6. PROVIDE AND INSTALL NEW CONCEALED, FIRE RETARDANT BLOCKING AT ALL NEW
ACCESSORIES/CASEWORK AS REQUIRED.
CLIMATE ZONE: 4A KINGS COUNTY
REQUIRED PROVIDED
ROOF INSULATION: R-30 ci N/A
MASS WALL
ABOVE GRADE: R-9.5 ci N/A
METAL FRAMED WALL: R-13 & 7.5 c i N/A
BELOW GRADE WALL: R-7.5ci N/A
SLAB ON GRADE: R-10-24" N/A
FIXED GLAZING: 0.38EU N/A
0.36 SHGC N/A
SWING DOORS: 0.77U N/A
0.36 SHGC N/A
SKYLIGHTS: 0.50 U N/A
O.40 SHGC N/A
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT:
Facilities
Management1
NUCLEAR MEDICINE
SPECT-CT SITE PREP
Services
4-27-21
FE PROJECT #
630A4-20-424
Revisions: Date
20-176
NEW YORK HARBOR
HEALTH CARE SYSTEM
BROOKLYN, NY
www.fellp.com
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704 fx 855-320-8735
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
ENGINEERING LLPLiscum
181 CHURCH STREET
POUGHKEEPSIE, NEW YORK 12601
PHONE 845-452-2268 FAX 845-452-3752
ARCHITECTURE
PLANNING INTERIORS
McCormack VanVoorhis LLP
100% CONSTRUCTION DOCUMENTS
* BRICK
* EXISTING TO BE REMOVED
* NEW STUD WALLS
* EXISTING TO REMAIN
* EARTH
* POUROUS FILL
* METAL / STEEL
* INSULATION
* WOOD
* SPLIT FACE CONCRETE BLOCK
* CONCRETE
PARTITIONS (PLAN)
1.) THE CONTRACTOR IS TO VISIT THE SITE AND THOROUGHLY ACQUAINT HIMSELF WITH ALL EXIST. CONDITIONS TO CHECK AND VERIFY ALL CONDITIONS, DIMENSIONS, ETC. AND REPORT TO THE ARCHITECT ANY ERRORS, OMISSIONS OR VARIATION FROM INTENT OF THE PLANS PRIOR TO THE START OF WORK.
2.) NO DRAWINGS ARE TO BE SCALED: USE DIMENSIONS ONLY OR VERIFY ALL CONDITIONS IN FIELD.
3.) THOSE ITEMS NOT NOTED, BUT IMPLIED AS NECESSARY FOR THE PERFORMANCE OF THE CONTRACT ARE CONSIDERED PART OF THE WORK.
4.) ALL MATERIAL AND WORKMANSHIP IS TO BE GUARANTEED BY THE CONTRACTOR TO BE FREE OF DEFECTS FOR A PERIOD OF ONE YEAR, THE CONTRACTOR AGREES TO CORRECT WITHOUT CHARGE SUCH CONDITIONS AS MAY OCCUR DURING THE GUARANTEE PERIOD.
5.) ALL WORK IS TO BE EXECUTED BY MECHANICS SKILLED IN THEIR TRADES.
6.) ALL CHANGES AND OR SUBSTITUTIONS ARE TO BE APPROVED IN WRITING BEFORE BEING INCORPORATED INTO THE WORK.
7.) ALL TRADES TO COOPERATE WITH EACH OTHER TO FACILITATE THE PROGRESS OF THE ENTIRE JOB.
8.) CONTRACTOR IS TO PROTECT THE PUBLIC AND PREMISES DURING THE PERIOD OF CONSTRUCTION WITH ADEQUATE SHORING, BRACING, FENCING, LIGHTING, ETC. .
9.) CONTRACTOR IS TO REMOVE ALL RUBBISH FROM THE SITE ON A DAILY BASIS (AS PER ICRA AND VA GUIDELINES) RESULTING FROM HIS WORK DURING THE PROGRESS OF CONSTRUCTION AND SHALL LEAVE THE PREMISES IN A CONDITION SATISFACTORY TO THE OWNER PRIOR TO THE FINAL INSPECTION.
10.) ALL MATERIALS, ASSEMBLIES, CONSTRUCTION AND EQUIPMENT SHALL CONFORM TO THE REGULATIONS OF THE INTERNATIONAL BUILDING CODE AND SHALL
CONFORM TO GENERALLY ACCEPTED STANDARDS.
A.B. ANCHOR BOLT
AC ACOUSTICAL
ACT ACOUSTICAL CEILING TILE
ADJ ADJACENT
AFF ABOVE FINISH FLOOR
ALUM ALUMINUM
ANOD ANODIZED
A.P. ACCESS PANEL
ARCH ARCHITECT
ASPH ASPHALT
APPROX APPROXIMATE
@ AT
BLDG BUILDING
BLK BLOCK
BOT BOTTOM
B/O BOTTOM OF
BRK BRICK
CBL CONCRETE BLOCK
CLG CEILING
C.T. CERAMIC TILE
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
CONT CONTINUOUS
C.J. CONTROL JOINT
℄ CENTERLINE
CB CATCH BASIN
DIA./ Ø DIAMETER
DN DOWN
DR DRAIN
DWG DRAWING
ELEC ELECTRIC
EL/ELEV ELEVATION
EQUIP EQUIPMENT
EXIST EXISTING
EXP JT EXPANSION JOINT
EXT EXTERIOR
FIN FINISH
FIN FL FINISHED FLOOR
FD FLOOR DRAIN
FGL FIBERGLASS
FL FLOOR
GA GAGE/GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GL GLASS
GWB GYPSUM WALL BD
HC HUNG CEILING
HDW HARDWARE
HM HOLLOW METAL
HOR HORIZONTAL
HP HIGH POINT
H+V HEATING AND VENTILATION
INSUL INSULATION
JAN JANITOR
JT JOINT
LAM LAMINATE
MAS MASONRY
MATL MATERIAL
MECH MECHANICAL
MIN MIN
M.O. MASONRY OPENING
MAX MAXIMUM
MTL METAL
N.I.C. NOT IN CONTRACT
NTS NOT TO SCALE
NO. NUMBER
OPNG OPENING
O.C. ON CENTER
PARTN PARTITION
P+D PLUMBING AND DRAINAGE
POLY POLYURETHANE
⅊ PROPERTY LINE
PT PRESSURE TREATED
PTD PAINTED
R RISER OR RADIUS
RDL ROOF DRAIN LEADER
REINF REINFORCED
REQD REQUIRED
RM ROOM
SC SOLID CORE
SECT SECTION
SIM SIMILAR
SPEC SPECIFICATION
STL STEEL
SAD SADDLE
STOR STORAGE
T TREAD OR TOP
TEL TELEPHONE
T&G TONGUE AND GROOVE
THK THICK
T/O TOP OF
TW TOP OF WALL
TYP TYPICAL
VB VAPOR BARRIER
VERT VERTICAL
W WIDE
WH WEEP HOLE
WST WAINSCOT
WWF WELDED WIRE FABRIC
W/ WITH
WD WOOD
ABBREVIATIONS (U.N.O.)
GENERAL SPECIFICATION NOTESSYMBOLS LEGEND
ENERGY CODE NOTES MATERIALS GENERAL NOTES
AutoCAD SHX Text N#
AutoCAD SHX Text X
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Designed By:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text FE Project No.
AutoCAD SHX Text 20-176
AutoCAD SHX Text
SRB
AutoCAD SHX Text
DSS
AutoCAD SHX Text RAYMOND P. VanVOORHIS, RA
AutoCAD SHX Text
NY REGISTERED ARCHITECT
AutoCAD SHX Text
NO. 11032
AutoCAD SHX Text
ARCHITECTURAL:
AutoCAD SHX Text
SYMBOLS, ABBREVIATIONS,
AutoCAD SHX Text
AND NOTES
AutoCAD SHX Text
1-AS-001
AutoCAD SHX Text
CONTROL
AREA
510a
43 SF
CT
ROOM #2
420 SF
CT
ROOM #1
405 SF
CONTROL
AREA
508a
55 SF
HOUSEKEEPING
33 SF
(71') TOTAL MAX DISTANCE
(41')
(41')
(107')
(87')
DISTANCE TO NEAREST
STAIR DOOR IS (70')
(177')
(157')
AUTOMATIC
SLIDING DOOR
LEGEND
56'
2-HR RATED FIRE BARRIER
1-HR RATED FIRE BARRIER
30MIN RATED FIRE BARRIER
DISTANCE TO TWO MEANS OF
EGRESS
DISTANCE TO
EXIT
EXIT LOCATIONEXIT
56'
EXISTING FIRE
EXTINGUISHER
AREA OF ALTERATION
FE
NEW FULLY RECESSED
MOUNTED FIRE
EXTINGUISHER
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT:
Facilities
Management1
NUCLEAR MEDICINE
SPECT-CT SITE PREP
Services
4-27-21
FE PROJECT #
630A4-20-424
Revisions: Date
20-176
NEW YORK HARBOR
HEALTH CARE SYSTEM
BROOKLYN, NY
www.fellp.com
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704 fx 855-320-8735
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
ENGINEERING LLPLiscum
181 CHURCH STREET
POUGHKEEPSIE, NEW YORK 12601
PHONE 845-452-2268 FAX 845-452-3752
ARCHITECTURE
PLANNING INTERIORS
McCormack VanVoorhis LLP
100% CONSTRUCTION DOCUMENTS
ARCHITECTURAL: LIFE SAFETY PLAN1 NORTHKEY PLAN - BUILDING 1 - 2ND FLOOR - EAST
SMOKE COMPARTMENT
SECOND FLOOR: NORTHEAST
7.143 SF
EXISTING BUILDING INFORMATION
NFPA - TYPE 2 - (222)
AutoCAD SHX Text
STRETCHER/ EXAM ROOM
AutoCAD SHX Text
QUIET ROOM
AutoCAD SHX Text
QUIET ROOM
AutoCAD SHX Text
HOT LAB
AutoCAD SHX Text
CHANGE
AutoCAD SHX Text
CHANGE
AutoCAD SHX Text
THYROID
AutoCAD SHX Text
EXISTING LIBRARY
AutoCAD SHX Text
STRESS TEST
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
SOILED HOLDING
AutoCAD SHX Text
NURSES STATION
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
CONFERENCE
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
STAFF/COPY/WORK ROOM
AutoCAD SHX Text
BONE DENSITY
AutoCAD SHX Text
NURSE INTERVIEW IV STATION
AutoCAD SHX Text
RADIOLOGY READING
AutoCAD SHX Text
ADMINISTRATION
AutoCAD SHX Text
STAFF TOILET
AutoCAD SHX Text
WAITING
AutoCAD SHX Text
CLEAN HOLDING
AutoCAD SHX Text
EQUIPMENT AREA
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
HOT SOILED HOLDING
AutoCAD SHX Text
CLEAN LINEN
AutoCAD SHX Text E
AutoCAD SHX Text 6.5
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 11.8
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
QUIET ROOM
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 523A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CLOSET
AutoCAD SHX Text 519A
AutoCAD SHX Text
PET/CT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 526A
AutoCAD SHX Text
AutoCAD SHX Text
EFHC
AutoCAD SHX Text
FE
AutoCAD SHX Text
FE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CONTROL
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
STRETCHER/ EXAM ROOM
AutoCAD SHX Text
QUIET ROOM
AutoCAD SHX Text
QUIET ROOM
AutoCAD SHX Text
HOT LAB
AutoCAD SHX Text
CHANGE
AutoCAD SHX Text
CHANGE
AutoCAD SHX Text
THYROID
AutoCAD SHX Text
EXISTING LIBRARY
AutoCAD SHX Text
STRESS TEST
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
SOILED HOLDING
AutoCAD SHX Text
NURSES STATION
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
CONFERENCE
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
STAFF/COPY/WORK ROOM
AutoCAD SHX Text
BONE DENSITY
AutoCAD SHX Text
NURSE INTERVIEW IV STATION
AutoCAD SHX Text
RADIOLOGY READING
AutoCAD SHX Text
ADMINISTRATION
AutoCAD SHX Text
STAFF TOILET
AutoCAD SHX Text
WAITING
AutoCAD SHX Text
CLEAN HOLDING
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
HOT SOILED HOLDING
AutoCAD SHX Text
CLEAN LINEN
AutoCAD SHX Text
QUIET ROOM
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CLOSET
AutoCAD SHX Text
PET/CT
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 526A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
CONTROL
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
FE
AutoCAD SHX Text
FE
AutoCAD SHX Text
EXIT STAIR
AutoCAD SHX Text
FE
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Designed By:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text FE Project No.
AutoCAD SHX Text 20-176
AutoCAD SHX Text
SRB
AutoCAD SHX Text
DSS
AutoCAD SHX Text RAYMOND P. VanVOORHIS, RA
AutoCAD SHX Text
NY REGISTERED ARCHITECT
AutoCAD SHX Text
NO. 11032
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
AutoCAD SHX Text D
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
CLO.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
UPPER PART
AutoCAD SHX Text
OF
AutoCAD SHX Text
MAIN LOBBY
AutoCAD SHX Text
FOLDING PARTITION
AutoCAD SHX Text
FOLDING PARTITION
AutoCAD SHX Text
CLO
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
EFHC
AutoCAD SHX Text
FE
AutoCAD SHX Text
FE
AutoCAD SHX Text
ARCHITECTURAL:
AutoCAD SHX Text
LIFE SAFETY FLOOR PLAN
AutoCAD SHX Text
1-LS-100
510a
43 SF
CT
ROOM #2
420 SF
CT
ROOM #1
405 SF
CONTROL
AREA
508a
55 SF
HOUSEKEEPING
33 SF
EXIT ACCESS CORRIDOR
66 7
3 3
APPROXIMATE OUTLINE OF PHASE BOUNDARY LINES (PARTITION
LOCATION). COORDINATE WITH PROJECT DRAWING SET
LEGEND:
PHASING STAGE
1 HOUR RATED WEATHERPROOF TEMPORARY ENCLOSURE (INSULATED),
TYPICAL OF ALL EXISTING WINDOW AND DOOR OPENINGS. SEE
STRUCTURAL DRAWINGS FOR ALL EXTERIOR ENCLOSURE REQUIREMENTS.
EXISTING WALLS. INFILL AND FIREPROOF ALL OPENINGS FROM FLOOR TO
CONCRETE DECK ABOVE CEILING FOR A 1 HOUR FIRE RATED CONSTRUCTION
BARRIER. CONTRACTOR IS RESPONSIBLE FOR ALL REPAIRS/REPLACEMENT
OF FINISHES AS REQUIRED FOR INSTALLATION OF TEMPORARY BARRIERS.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT:
Facilities
Management1
NUCLEAR MEDICINE
SPECT-CT SITE PREP
Services
4-27-21
FE PROJECT #
630A4-20-424
Revisions: Date
20-176
NEW YORK HARBOR
HEALTH CARE SYSTEM
BROOKLYN, NY
www.fellp.com
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704 fx 855-320-8735
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
ENGINEERING LLPLiscum
181 CHURCH STREET
POUGHKEEPSIE, NEW YORK 12601
PHONE 845-452-2268 FAX 845-452-3752
ARCHITECTURE
PLANNING INTERIORS
McCormack VanVoorhis LLP
100% CONSTRUCTION DOCUMENTS
ARCHITECTURAL: PHASING PLAN1
NORTHKEY PLAN - BUILDING 1 - 2ND FLOOR - EAST
PARTITION WALL DETAIL
N.T.S.2
TEMPORARY CONSTRUCTION
KEYED NOTES:
1 CLOSE OFF EXISTING DOOR OPENING INSTALL TWO LAYERS OF ½" TYPE 'X' SHEETROCK
EITHER SIDE OF DOOR OPENING TO FORM A 1 HR. TEMPORARY CONSTRUCTION BARRIER.
ACCESS FOR UTILITY ISOLATION AND CHANGE-OVER ONLY.
PRIMARY ACCESS TO WORK SPACE THROUGHOUT CONSTRUCTION.
PROVIDE TEMPORARY SELF-CLOSING, U.L. LISTED ¾ HOUR FIRE RATED DOOR ASSEMBLY
WHERE INDICATED AND AS REQUIRED TO FACILITATE CONSTRUCTION AND PROJECT
PHASING.
CONTRACTOR TO PROVIDE AND OPERATE NEGATIVE PRESSURE MACHINES WITHIN THE
WORK AREA OF EACH PHASE AS REQ'D TO MAINTAIN THE CONSTRUCTION AREAS NEGATIVE
AIR PRESSURE RELATIONSHIP TO THE EXISTING ADJACENT FACILITIES. (QUANTITIES AND
SIZES OF NEG AIR MACHINES AS REQ'D). ALL NEGATIVE AIR MACHINES TO BE PROPERLY
VENTED TO THE EXTERIOR.
TEMPORARY CONSTRUCTION SEPARATION WITH SELF CLOSING DOOR. CONTRACTOR IS
RESPONSIBLE FOR REPAIRING ALL DAMAGES CAUSED BY INSTALLATION OF TEMPORARY
CONSTRUCTION BARRIERS.
CONTRACTOR TO PROVIDE AND INSTALL STEP AND PEEL OFF STICKY MATS (MIN 24"X30")
AT EVERY CONSTRUCTION ACCESS DOOR AND SHALL MAINTAIN AND REPLACE AS REQ'D.
CONTRACTOR TO INSTALL A MANOMETER AT EACH CONSTRUCTION ENTRANCE TO ALLOW
PROPER MONITORING OF AIR PRESSURE RELATIONSHIP BETWEEN THE CONSTRUCTION
AREA AND THE VA FACILITY
Description of Required Infection Control Precautions by Class During Construction Project Upon Completion of Project
1. Provide active means to prevent airborne dust from dispersing into atmosphere, which may include the use of a control cube.
2. Water mist work surfaces to control dust while cutting.
3. Seal unused doors with masking tape.
4. Block off and seal air vents.
7. Doors and windows within the work zone to remain closed at all times except during ingress/ergress.
8. Place adhesive mat at entrance and exit of work area as necessary.
9. Cover transport receptacles or carts.
1. Wipe work surfaces with disinfectant.
2. Contain construction waste before transport in tightly covered containers.
3. Wet mop and/or vacuum with HEPA filtered vacuum before leaving work area.
4. Remove isolation of HVAC system in areas where work is being performed.
C la ss
II
1. Isolate HVAC system in area where work is being done to prevent contamination of duct system.
2. Complete all critical barriers, i.e., sheetrock, plywood, plastic, to seal area from non-work area or implement control cube method (cart with plastic covering and sealed connection to work site with
HEPA vacuum for vacuuming prior to exit) before construction begins.
3. Maintain negative air pressure within work site utilizing HEPA equipped air filtration units.
4. Contain construction waste before transport in tightly covered containers.
5. Cover transport receptacles or carts. Tape covering unless solid lid.
6. All personnel entering work site are required to wear shoe covers. Shoe covers must be changed each time the worker exits the work area.
7. Do not remove barriers from work area until completed project is inspected by the owner's Safety
Section and Infection Control Department, and thoroughly cleaned by the owner's Environment
Services Department.
1. Remove barrier materials carefully to minimize spreading of dirt and debris associated with construction.
2. Contain construction waste before transportation in tightly covered containers.
3. Cover transport receptacles or carts. Tape covering unless solid lid.
4. Vacuum work area with HEPA filtered vacuums.
5. Wet mop area with disinfectant.
6. Remove isolation of HVAC system in areas where work is being performed.
C la ss
IV
C la ss
II
I
1. Isolate HVAC system in area where work is being done to prevent contamination of duct system.
5. Cover transport receptacles or carts. Tape covering unless solid lid.
6. All personnel entering work site are required to wear shoe covers. Shoe covers must be changed each time the worker exits the work area.
7. Do not remove barriers from work area until completed project is inspected by the owner's Safety
Section and Infection Control Department, and thoroughly cleaned by the owner's Environment
Services Department.
1. Do not remove barriers from work area until completed project is inspected by the owner’s Safety
Department and Infection Control Department, and thoroughly cleaned by the owner’s Environmental
Services Department.
2. Remove barrier materials carefully to minimize spreading of dirt and debris associated with construction.
3. Vacuum work area with HEPA filtered vacuums.
12. Wet mop and/or vacuum with HEPA filtered vacuum at end of day or end of work shift. Area to be free of dust and/or debris.
11. Use designated removal route/elevators for removal of debris.
10. Contain construction waste before transport in tightly covered containers.
6. Remove or isolate HVAC system in areas where work is being performed.
5. Place adhesive dust mat at entrance and exit of work area.
8. Designate entry and exit traffic pattern, unauthorized personnel are not permitted to enter work zone, traffic control signs placed.
9. The contractor shall maintain the construction zone in a clean manner
· The area will be HEPA-vacuumed or damped mopped daily or more often as necessary to minimize duct, as determined by the VA COR.
· Daily cleanup of debris, material and waste shall be completed.
· Adhesive mats monitored & changed on a regular basis so that they remain effective.
· Any dust or construction debris tracked outside of the work area shall be promptly cleaned.
10. Terminal cleaning will be performed following
VA protocol.
11. The terminal cleaning will be inspected by the
Owner prior to the authorization for the barrier removal.
12. Air samples may be performed following
IC/Safety protocol as deemed necessary by the COR.
2. Complete all critical barriers, i.e., sheetrock, plywood, plastic, to seal area from non-work area or implement control cube method (cart with plastic covering and sealed connection to work site with
HEPA vacuum for vacuuming prior to exit) before construction begins will stay in place until IC or PM authorizes removal.
3. Maintain negative air pressure within work site utilizing HEPA equipped air filtration units. Both will be maintained until project terminal cleaning is completed and IC authorizes removal. Air pressure to be monitored & documented at least daily. Adhesive mats placed at all entrances & exists of work area.
4. Contain construction waste before transport in tightly covered containers.
5. Remove isolation of HVAC system in areas where work is being performed.
4. Wet mop area with disinfectant.
6. Barriers will be removed carefully to minimize spreading of construction dust & debris.
8. Seal all holes, pipes and conduits penetrations in work area.
9. Construct anteroom for staging of equipment & donning of coveralls.
10. Workers will were coveralls in work area. Upon completion of major dust generation activities, coverall requirement is removed
11. Coveralls are removed in work zone before entering anteroom.
12. Any residual dust left on workers shall be removed by vacuum.
13. All renovation, construction, maintenance & tool carts leaving area must be covered & the wheels wiped down with a disinfectant solution.
14. Environmental Management Services (EMS) or a contract cleaner will vacuum or damp mop the area outside the work zone and adjacent areas.
UL U465 (1 HOUR RATED) FIRECODE 'C' OR 'X' GYPSUM BD PANELS
APPLIED VERTICALLY OR HORIZONTALLY. HORIZONTAL JOINTS NEED NOT
BE STAGGERED. FACE LAYER JOINTS TO BE FINISHED. FIRE CAULK ALL
PENETRATIONS.TAPE & SPACKLE OCCUPIED SIDE, LEVEL 4 FINISH.
FRAMING TO DECK
CONTINUOUS BOTTOM
RUNNER TRACK
SEALANT - BOTH SIDES3 5/8" x 25 GAUGE
MTL STUDS
5/8" FIRECODE 'C'
OR 'X' GYPSUM
WALL BD. (1) LAYER
EACH SIDE
LINE OF RATED FLOOR
STRUCTURE ABOVE
CONTINUOUS TO TOP RUNNER
TRACK. CEILING DECK IS CONCRETE
IN HONEY COMB ASSEMBLY, I.E. IT IS
NOT CONTINUOUS ON ONE PLANE,
THE DECK BOTTOM JOGS UP AND
DOWN. PARTITION MUST FOLLOW
THE CONTOUR OF THE CEILING AND
BE CONTINUOUS FROM FLOOR TO
CEILING DECK.
U.L. LISTED FIRE CAULK
COMPLETE, BOTH SIDES
3" MINERAL WOOL SOUND
ATTENUATION BATT. INSULATION
GENERAL CONSTRUCTION ACTIVITY
NOTES:
NOTES:
PATIENT RISK GROUP FOR "TYPE D" CONSTRUCTION
LOW RISK GROUP
MEDIUM RISK GROUP
HIGH RISK GROUP
HIGHEST RISK GROUP Class IV
Class III / IV
Class IV Class IV
PATIENT RISK GROUP FOR "TYPE C" CONSTRUCTION
LOW RISK GROUP
MEDIUM RISK GROUP
HIGH RISK GROUP
HIGHEST RISK GROUP
CLASS II
CLASS III
Class III / IV Class III / IV
PATIENT RISK GROUP FOR "TYPE B" CONSTRUCTION
LOW RISK GROUP
MEDIUM RISK GROUP
HIGH RISK GROUP
HIGHEST RISK GROUP
CLASS II
CLASS II
CLASS II
Class III / IV
VA BROOKLYN Phasing Summary
(Approximate 6 month duration)
1. Contractor to submit all required pre-construction documentation and proposed contract schedule for review and approval.
2. Contractor to submit Critical Path Submittals within 45 days of award.
3. Contractor to document existing conditions prior to the start of any work (including utility mark-up).
4. Contractor to undertake and complete construction and prepare work area for new CT equipment manufacturer's installation of new equipment.
5. Contractor to allow manufacturer to install their equipment within the work area and install the equipment that is provided for them from the equipment manufacturer and/or VA as per the equipment schedules and GE drawings attached.
6. Contractor to complete construction after installation of manufacturer's equipment as required.
CONTRACTOR TO REPAIR ALL FINISHES
DAMAGED BY TEMP BARRIER
INSTALLATION/REMOVAL
NOTE:
CONTRACTOR TO PROVIDE AND BE RESPONSIBLE FOR TWO CRANE MOBILIZATIONS. (1) MOBILIZATION FOR THE REMOVAL OF THE EXISTING CT EQUIPMENT AT THE BEGINNING OF THE PROJECT. ONE MOBILIZATION FOR THE DELIVERY AND INSTALLATION OF THE NEW CT EQUIPMENT. CONTRACTOR SHALL COORDINATE AS REQUIRED FOR THE REMOVAL & INSTALLATION WITH THE CT EQUIPMENT MANUFACTURER.
THE EXIST WALL BETWEEN THE TWO CT ROOMS WILL NEED TO BE REMOVED PRIOR TO THE CT. EQUIPMENT REMOVAL AND THE NEW CT'S ARE INSTALLED. A NEW SOFFIT WILL BE PROVIDED AT THE NEW WALL LOCATION TO FACILITATE THE CEILING CONSTRUCTION PRIOR TO THE NEW
EQUIPMENT INSTALLATION.
SEE STRUCTURAL DRAWINGS FOR EXTERIOR WALL DECONSTRUCTION/RECONSTRUCTION FOR CRANE MOBILIZATIONS.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FE
AutoCAD SHX Text
FE
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Designed By:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text FE Project No.
AutoCAD SHX Text 20-176
AutoCAD SHX Text
SRB
AutoCAD SHX Text
DSS
AutoCAD SHX Text RAYMOND P. VanVOORHIS, RA
AutoCAD SHX Text
NY REGISTERED ARCHITECT
AutoCAD SHX Text
NO. 11032
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
AutoCAD SHX Text D
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
CLO.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
UPPER PART
AutoCAD SHX Text
OF
AutoCAD SHX Text
MAIN LOBBY
AutoCAD SHX Text
FOLDING PARTITION
AutoCAD SHX Text
FOLDING PARTITION
AutoCAD SHX Text
CLO
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
EFHC
AutoCAD SHX Text
FE
AutoCAD SHX Text
FE
AutoCAD SHX Text
ARCHITECTURAL:
AutoCAD SHX Text
PHASING PLAN, SUMMARY,
AutoCAD SHX Text
AND NOTES
AutoCAD SHX Text
1-PH-100
AutoCAD SHX Text
AutoCAD SHX Text
1. ALL AREAS OF CONSTRUCTION SHALL ALL AREAS OF CONSTRUCTION SHALL BE SECURED BY USE OF TEMPORARY CONSTRUCTION FENCING DURING ALL DEMOLITION AND CONSTRUCTION ACTIVITIES. 2. ALL CONSTRUCTION AREAS SHALL BE ALL CONSTRUCTION AREAS SHALL BE SECURELY LOCKED WHEN CONTRACTOR IS NOT PRESENT WORKING IN AREA. 3. MAINTAIN EMERGENCY EGRESS PATHS MAINTAIN EMERGENCY EGRESS PATHS AT ALL TIMES DURING CONSTRUCTION. 4. PROTECTION OF EXISTING GROUNDS, PROTECTION OF EXISTING GROUNDS, SIDEWALKS AND CURBS IS THE RESPONSIBILITY OF THE CONTRACTOR AND DAMAGED AREAS SHALL BE REPAIRED IMMEDIATELY AFTER DISTURBANCE HAS DECEASED.
AutoCAD SHX Text
1. HARD WALL BARRIERS SHALL BE CONSTRUCTED HARD WALL BARRIERS SHALL BE CONSTRUCTED WITHIN THE MAIN CORRIDORS AS PART OF THIS CONTRACT WORK. REFER TO "PARTITION BARRIER DETAIL" ON 1-PH-100. 2. CONTRACTOR SHALL PROVIDE REQUIRED CONTRACTOR SHALL PROVIDE REQUIRED INFECTION CONTROL PRECAUTIONS AS SHOWN IN CHART FOR ALL WORK PERFORMED UNDER THIS PROJECT.
AutoCAD SHX Text MAJOR DEMOLITION AND CONSTRUCTION PROJECTS ACTIVITIES THAT REQUIRE CONSECUTIVE WORK SHIFTS REQUIRES HEAVY DEMOLITION OR REMOVAL OF COMPLETE CABLING SYSTEMS NEW CONSTRUCTION
AutoCAD SHX Text WORK THAT GENERATES A MODERATE TO HIGH LEVEL OF DUST OR REQUIRES DEMOLITION OR REMOVAL OF ANY FIXED BUILDING COMPONENTS OR ASSEMBLIES. SANDING OF WALLS FOR PAINTING OR WALL COVERING REMOVAL OF FLOOR COVERINGS, CEILING TILES AND CASEWORK NEW WALL CONSTRUCTION MINOR DUCTWORK OR ELECTRICAL WORK ABOVE CEILINGS MAJOR CABLING ACTIVITIES ANY ACTIVITIES THAT CANNOT BE COMPLETED WITHIN A SINGLE WORK SHIFT.
SMALL SCALE, SHORT DURATION ACTIVITIES THAT CREATE MINIMAL DUST. INSTALLATION OF TELEPHONE AND COMPUTER CABLING. ACCESS TO CHASE SPACES CUTTING OF WALLS OR CEILINGS WHERE DUST MIGRATION CAN BE CONTROLLED.
3 10
12 12
DEMOLITION PLAN LEGEND
EXISTING PARTITION
TO BE DEMOLISHED
EXISTING DOOR TO
BE DEMOLISHED
EXISTING PARTITION
TO REMAIN
EXISTING DOOR
TO REMAIN
TEMPORARY BARRIER, SEE GENERAL
DEMOLITION NOTE #4
1. DRAWING SHOWS GENERAL EXTENT OF DEMOLITION AND
REMOVALS. THE CONTRACTOR SHALL MAKE ALL REMOVAL
AS REQUIRED TO PROPERLY INSTALL ALL NEW WORK. SEE
PHASING/ICRA.
2.DEMOLITION AND REMOVALS SHALL BE PERFORMED SO
THAT EXISTING FINISHES, EQUIPMENT, AND SYSTEMS THAT
ARE TO RE`MAIN ARE NOT DAMAGED. PROVIDE
PROTECTION AS NEEDED TO ENSURE THAT THESE ITEMS
ARE NOT DAMAGED.
3.SEE MEP DRAWINGS FOR THOSE REMOVALS. ALL
ABANDONED WIRING, PIPING AND EQUIPMENT SHALL BE
REMOVED EXCEPT THOSE IN EXISTING WALL AND SLABS
THAT ARE TO REMAIN. PROPERLY CAP AND/OR TERMINATE
ABANDONED PIPING AND WIRING THAT REMAINS.
4.ERECT NEW TEMPORARY CONSTRUCTION BARRIER UP TO
DECK ABOVE AS REQUIRED BY NFPA 241, SECTION 8.6.2.1
WITH A MINIMUM OF 1-HOUR RATING AND SMOKE TIGHT.
COMPLY WITH THE JOINT COMMISSIONS STANDARDS AND
AS REQUIRED TO PROTECT ADJACENT SPACES FROM
DUST MIGRATION. PROVIDE AND INSTALL RATED (45MIN)
AND SEALED ACCESS DOORS AS REQUIRED FOR STAGING
AND PHASING, COMPLETE WITH ALL REQUIRED HARDWARE
AND CLOSURES. ALL EXISTING PENETRATIONS TO BE
SEALED AND TEMPORARY FIRE/SMOKE DAMPERS
INSTALLED AT ALL DUCT PENETRATIONS AT LINE OF NEW
TEMPORARY WALL. CUT AND PATCH AS REQUIRED ALL
EXISTING FINISHES TO INSTALL NEW TEMPORARY
CONSTRUCTION BARRIER WALLS. CONTRACTOR TO PATCH
AND REPAIR ALL EXISTING
SURFACES/FINISHES/CONSTRUCTION AS REQUIRED WHEN
TEMPORARY WALLS ARE REMOVED AT COMPLETION OF
PROJECT. COORDINATE WITH PHASING/ICRA DRAWINGS.
5.GENERAL CONTRACTOR IS TO NOTIFY THE ARCHITECT/VA
IMMEDIATELY FOLLOWING FINDING PIPING, CHASES,
DUCTWORK, ETC. WITHIN THE WALLS TO BE DEMOLISHED
THAT WILL CAUSE CHANGE IN DESIGN.
6. ALL CONSTRUCTION DEBRIS TO BE REMOVED DURING
W.H.E.N. ALL DEBRIS SHALL BE
REMOVED IN A COVERED BUGGY. COORDINATE WITH C.O.R.
AND REFER TO PHASING/ICRA DRAWING FOR ADDITIONAL
INFORMATION.
7.USE OF A JACK HAMMER IS NOT PERMITTED.
8.COORDINATE WITH VA C.O.R. FOR AFTER HOURS WORK
FOR ALL NOISY (HIGH DECIBEL) WORK.
9.COORDINATE WITH VA C.O.R. FOR AFTER HOURS WORK TO
REMOVE EXISTING MATERIALS; USE OF A JACK HAMMER IS
NOT PERMITTED.
11. ALL WALL MOUNTED POSTERS, POSTER BOARDS,
ARTWORK, PHOTOGRAPHS AND SIGNAGE TO BE
CAREFULLY REMOVED AND RETURNED TO THE VA C.O.R.
FOR RE-USE.
GENERAL DEMOLITION NOTES
12. ALL REMOVALS TO BE COORDINATED WITH MEP &
STRUCTURAL DRAWINGS AS REQ'D.
10. REMOVE ALL EXISTING CEILINGS/SOFFITS/FASCIA IN
AREA OF WORK.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT:
Facilities
Management1
NUCLEAR MEDICINE
SPECT-CT SITE PREP
Services
4-27-21
FE PROJECT #
630A4-20-424
Revisions: Date
20-176
NEW YORK HARBOR
HEALTH CARE SYSTEM
BROOKLYN, NY
www.fellp.com
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704 fx 855-320-8735
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
ENGINEERING LLPLiscum
181 CHURCH STREET
POUGHKEEPSIE, NEW YORK 12601
PHONE 845-452-2268 FAX 845-452-3752
ARCHITECTURE
PLANNING INTERIORS
McCormack VanVoorhis LLP
100% CONSTRUCTION DOCUMENTS
ARCHITECTURAL: DEMOLITION FLOOR PLAN1
NORTHKEY PLAN - BUILDING 1 - 2ND FLOOR - EAST
DEMOLITION KEYNOTES
Number Note
1 TEMPORARY CONSTRUCTION BARRIERS, SEE GENERAL
DEMOLITION NOTE #4.
REMOVE EXISTING INTERIOR PARTITION COMPLETE. CUT, PATCH
AND REPAIR ADJACENT FINISHES TO REMAIN AS REQUIRED FOR
SURFACES TO BE FLUSH & MATCH EXISTING.
REMOVE ANY EXISTING FLOORING AND CLEAN AND PREP FOR
NEW FLOORING.
CUT, PATCH AND REPAIR ADJACENT FINISHES TO REMAIN AS
REQUIRED.
REMOVE EXISTING CEILING SYSTEM COMPLETELY. CUT, PATCH
AND REPAIR ADJACENT FINISHES TO REMAIN AS REQUIRED.
REMOVE EXISTING COUNTER/WALL CASEWORK COMPLETE. PATCH
AND REPAIR ADJACENT FINISHES AS REQUIRED.
REMOVE EXISTING CEILING SYSTEM AND INSTALL NEW CEILING
SYSTEM AS REQUIRED TO INSTALL NEW MEP WORK. CUT, PATCH
AND REPAIR ADJACENT FINISHES TO REMAIN AS REQUIRED.
REMOVE EXISTING GYPSUM BOARD/PLASTER CEILING SYSTEM
ABOVE ACT CEILING COMPLETE. CUT, PATCH AND REPAIR
ADJACENT FINISHES TO REMAIN AS REQUIRED.
REMOVE EXISTING WALL AS REQUIRED FOR NEW DOOR, PATCH
AND REPAIR AS REQ'D.
KEYNOTE SYMBOL #
REMOVE EXISTING DOOR & FRAME COMPLETELY, CUT & PATCH
WALLS & FLOOR AS REQ'D.
REMOVE EXISTING SOFFIT AT THIS LOCATION COMPLETELY, CUT
AND PATCH CEILING AS REQUIRED.
CUT AND PATCH EXISTING CRASH/HAND RAIL AS REQUIRED FOR
NEW DOOR CONSTRUCTION. PROVIDE AND INSTALL NEW
MATCHING END CAP AND RE-SUPPORT AS REQUIRED.
REMOVE AND REINSTALL EXISTING CASEWORK (BASE WALL
CABINETS, WALL CABINETS, COUNTERTOPS, SUPPORTS, SINKS,
ETC) AS REQUIRED AFTER INSTALLATION OF NEW LEAD GYPSUM
BOARD ON EXISTING WALLS. CUT, PATCH AND MODIFY EXISTING
CASEWORK/COUNTER AS REQUIRED TO FIT IN THE NEW SMALLER
LOCATION.
COORDINATE AS REQUIRED FOR NEW LEAD GYPSUM BOARD
INSTALLATION (REINFORCE EXISTING FRAMING AS REQUIRED,
REMOVE AND REINSTALL EXISTING GRILLES, RECEPTACLES TO
REMAIN, ETC.) CUT AND PATCH AS REQUIRED.
NOTE:
SEE STRUCTURAL DRAWINGS FOR
DECONSTRUCTION/RECONSTRUCTION OF
EXTERIOR WALL FOR CRANE MOBILIZATIONS
AutoCAD SHX Text
BONE DENSITY
AutoCAD SHX Text
NURSE INTERVIEW IV STATION
AutoCAD SHX Text
EQUIPMENT AREA
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
CLEAN LINEN
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FE
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
BONE DENSITY
AutoCAD SHX Text
NURSE INTERVIEW IV STATION
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
CLEAN LINEN
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PATIENT
AutoCAD SHX Text
FE
AutoCAD SHX Text
HOUSEKEEPING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HAWKEYE GAMMA CAMERA
AutoCAD SHX Text
SMV GAMMA CAMERA
AutoCAD SHX Text
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Designed By:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text FE Project No.
AutoCAD SHX Text 20-176
AutoCAD SHX Text
SRB
AutoCAD SHX Text
DSS
AutoCAD SHX Text RAYMOND P. VanVOORHIS, RA
AutoCAD SHX Text
NY REGISTERED ARCHITECT
AutoCAD SHX Text
NO. 11032
AutoCAD SHX Text
SCALE: 1/4"=1'-0"
AutoCAD SHX Text D
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
CLO.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
DUCT
AutoCAD SHX Text
UPPER PART
AutoCAD SHX Text
OF
AutoCAD SHX Text
MAIN LOBBY
AutoCAD SHX Text
FOLDING PARTITION
AutoCAD SHX Text
FOLDING PARTITION
AutoCAD SHX Text
CLO
AutoCAD SHX Text
STORAGE
AutoCAD SHX Text
EFHC
AutoCAD SHX Text
FE
AutoCAD SHX Text
FE
AutoCAD SHX Text
ARCHITECTURAL:
AutoCAD SHX Text
DEMOLITION FLOOR PLAN
AutoCAD SHX Text
1-ASD-100
510a
43 SF
CT
ROOM #2
420 SF
CT
ROOM #1
405 SF
6'-7 1/2"
7'- 5"
CONTROL
AREA
508a
55 SF
6'-7 1/2"
2'-6 1/2
CLE
AR
CT MFR ISOCENTERCT MFR ISOCENTER
W1
AS100
AS100
2'-1 1/2"
27'-6 1/2"23'-1 1/2"
'-9
"M
IN
C
LE
AR3'-7 1/2" 9'-0"
9'-8" 8'-8 1/2" 10'-11" +/-
9'- 4 1
/2" 6'-
8 1 /2"
3'- 0"
C
LE
AR
W2
NEW SHIELDED DOOR
NEW SHIELDED
SLIDING DOOR
HOUSEKEEPING
33 SF
CG-1
CG-1
CG-1CG-1
CG-1 CG-1CG-1 CG-1CG-1
CG-1
4'- 8"
1'-0 1/2" 4'-8"
6" 4'-8"
4'- 0"
5'-4 1/2"
6'- 4"
1'- 8"
7'- 7"
6'- 2"
3'- 6"
C
LE
AR
2'-4" CLEAR
9-4-3 9-4
-3
9- 4-
3 CG-1
9- 0-
9-0-1
9-0-1
9-0-1
9-0-1
9- 0-
9-0-1
9- 0-
9- 0-
CUT, PATCH AND REPLACE END CAP OF
EXISTING CHAIR/CRASH RAIL AS REQUIRED
AFTER NEW DOOR INSTALLATION
NEW 7" X 5" METAL STUD, GYPSUM BOARD WRAPPED POSTNEW 7" X 5" METAL STUD, GYPSUM
BOARD WRAPPED POST
SEE ALT. NOTE #4
NEW OVERHEAD BRACED
WALL/FLOOR SUPPORTED
PATIENT LIFT
SEE ALT. NOTE #4
KNEE
SPACE
4'- 0"
7'- 2"
W1
2'-
P
RB
SS
AS100
3'- 2 1
/2" A.
F.
F
8'-6"
CT EQUIPMENT; REFER TO
CT DRAWINGS FOR DETAILS
8'- 3 1
/2"
KNEE
SPACE
4'- 0"
7'- 2"
W1
2'-
P
RB
SS
AS100
3'- 2 1
/2" A.
F.
F
6'-0"
CT EQUIPMENT; REFER TO
CT DRAWINGS FOR DETAILS
8'- 3 1
/2"
8'-2"135° ANGLE WALL
LINE OF CEILING. SEE
REFLECTED CEILING
PLAN
VINYL BASE, SEE SCHEDULE
FINISH WALL SURFACE- PAINTED
GWB. SEE FINISH PLAN.
2'-1" COUNTERTOP
1 1 /2"
9'- 2"
V.
I.F
4"
2'-
SOLID SURFACE COUNTER AND
4" BACKSPLASH (SS-1)
RAKKS COUNTER SUPPORT
BRACKET; EH-1824
PROVIDE FIRE RATED,
CONCEALED, WOOD BLOCKING
SOLID BLOCKING
NOTE:
MAINTAIN MINIMUM OF 27" CLEAR
BENEATH COUNTER
3" GROMMET WITH POWER AND
DATA PORTS INSIDE CABINETRY
EVERY 36" O.C.
5"
4'- 0"
SEE PLAN FOR PARTITION TYPE
COUNTER IN CONTROL ROOM
510A TO BE 20" DEEP
NEW WALL AND DOOR
EXISTING WALL AND
DOOR TO REMAIN
9-4-2b
W#
NEW WINDOW/
STOREFRONT TAG
SEE SHEET A600
NEW DOOR TAG
NEW PARTITION TAG
FIRE/SMOKE RATING (SEE
3-AS-600 FOR PARTITION
LEGEND)
NOMINAL SIZE
SPECIFICATION CATEGORY
SEQUENCE NUMBER
DOOR NUMBER
DOOR SIZE (SEE 3-AS-600
FOR DOOR SIZE LEGEND)
# 3-AS-000 NEW INTERIOR
ELEVATION TAG
VIEW
NUMBER
SHEET
NUMBER
FLOOR PLAN LEGEND
DIMS
DIMENSIONS ARE TYPICALLY
TO FACE OF GYP BD.
FEC
FIRE EXTINGUISHER
SRFE
SEMI RECESSED MOUNTED
FIRE EXTINGUISHER
CORNER GUARDS, SEE
A600 FOR TYPE
CG-1
AREA OF ALTERATION
ALTERATION NOTES:
1. NEW PRIVACY CURTAIN BY VA. TRACK PROVIDED & INSTALLED BY
CONTRACTOR.
2. CONTRACTOR TO PROVIDE AND INSTALL ALL REQUIRED STRUCTURAL
STEEL, BOLTS, SECONDARY SUPPORTS, FASTENERS, UNISTRUT,
STABILIZERS, ETC... AS REQ'D TO PROPERLY SUPPORT, SECURE &
STABILIZE NEW LEAD SHIELDING AT WALLS AND CEILING/STRUCTURE
ABOVE.
3. FLOOR TO RECIEVE NEW CEMENTITIOUS LEVELING COMPOUND AS
REQ'D TO MATCH CT EQUIPMENT REQUIREMENTS.
4. AT NEW PATIENT LIFT WALL BRACED SUPPORTS CUT & PATCH EXIST
WALL TO CONCEAL NEW WALL BRACE AND PROVIDE NEW ADDITIONAL
FRAMING UP TO DECK (SEE STRUCTURAL DETAIL) CUT & PATCH WALL
CONSTRUCTION AS REQ'D.
5. ENTIRE FLOOR OF CT ROOMS (508 & 510) TO RECEIVE A NEW LAYER OF
32" THK LEAD SHIELDING BELOW NEW CONCRETE FLOOR TOPPING.
(SEE STRUCTURAL DRAWINGS)
6. CONTRACTOR TO PROVIDE NEW 2HR RATED SPRAY FIRE PROOFING
OVER ALL NEW STEEL STRUCTURE AT ANY LOCATIONS WHERE
EXISTING STEEL HAS BEEN EXPOSED. COORDINATE AS REQ'D W/ NEW
LEAD SHIELDING.
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg. of
CONSULTANTS: ARCHITECT:
Facilities
Management1
NUCLEAR MEDICINE
SPECT-CT SITE PREP
Services
4-27-21
FE PROJECT #
630A4-20-424
Revisions: Date
20-176
NEW YORK HARBOR
HEALTH CARE SYSTEM
BROOKLYN, NY
www.fellp.com
181 Church St., Suite 100, Poughkeepsie, NY 12601 t 845-454-9704 fx 855-320-8735
22 Mulberry St., Suite 2A, Middletown, NY 10940 t 845-343-1481 fx 845-343-4986
ENGINEERING LLPLiscum
181 CHURCH STREET
POUGHKEEPSIE, NEW YORK 12601
PHONE 845-452-2268 FAX 845-452-3752
ARCHITECTURE
PLANNING INTERIORS
McCormack VanVoorhis LLP
100% CONSTRUCTION DOCUMENTS
NORTHKEY PLAN - BUILDING 1 - 2ND FLOOR - EAST
ARCHITECTURAL: FLOOR PLAN1
ARCHITECTURAL: MILLWORK DETAIL2
ARCHITECTURAL: MILLWORK DETAIL3
ARCHITECTURAL: MILLWORK DETAIL4
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FE
AutoCAD SHX Text
FE
AutoCAD SHX Text N#
AutoCAD SHX Text X
AutoCAD SHX Text one eighth inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text one and one half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three quarters inch = one foot
AutoCAD SHX Text one half inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one quarter inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Designed By:
AutoCAD SHX Text Drawn By:
AutoCAD SHX Text FE Project No.
AutoCAD SHX Text 20-176
AutoCAD SHX Text
SRB
AutoCAD SHX Text
DSS
AutoCAD SHX Text RAYMOND P. VanVOORHIS, RA
AutoCAD SHX Text
NY REGISTERED ARCHITECT
AutoCAD SHX Text
NO. 11032
AutoCAD SHX Text D
AutoCAD SHX Text
DUCT
AutoCAD SHX…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .