S02. Final CD Drawings E-T.pdf
PDF 11 MB Posted
- Attached to
- Y1DA--RENOVATE & RECONFIGURE CLINICAL SERVICES Federal contract opportunity
- Solicitation number
- Am0001
About this file
This document provides details for a federal contract opportunity to renovate and reconfigure clinical services areas. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 is soliciting bids for the Renovate and Reconfigure Clinical Services project through solicitation number Am0001. An amendment was issued to add the latest drawings and ICRA requirements from TIL. The bid opening date remains May 7, 2021 at 12:00PM EST. The purpose of the project is to renovate and reconfigure clinical services areas to update the spaces.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| S06. 36C25021B0004 0001.pdf | ||
| S02. Final CD Drawings G-Q.pdf | ||
| S02. Final CD Drawings F-M.pdf | ||
| S02. VARRCS Bid Addendum No 1 2021 04-15.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABBREVIATIONS
DEDICATED NEUTRAL CONDUCTORS
AC ABOVE COUNTER AT 9" UNLESS OTHERWISE NOTED
AF AMP FRAME
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AT AMP TRIP
BC BELOW COUNTER AT 18"AFF UNLESS OTHERWISE NOTED
BFC BELOW FINISHED CEILING
CM CEILING MOUNTED
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
IG ISOLATED GROUND
ITD INFORMATION TECHNOLOGY DEPARTMENT
PROVIDE DEFINITION: FURNISH, INSTALL AND CONNECT COMPLETE.
X EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, CONDUIT, ETC. - TO REMAIN
XB INDICATES EXISTING OUTLET, LIGHTING FIXTURE, CONDUIT, ETC - TO BE REMOVED.
PROVIDE BLANK COVER FOR OUTLET AND MAINTAIN CIRCUIT CONTINUITY.
XL NEW LOCATION OF EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC.
XN EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC. - TO BE REPLACED WITH NEW OF
SPECIFIED TYPE
XR EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, CONDUIT, ETC. - TO BE REMOVED COMPLETE-
MAINTAIN CIRCUIT CONTINUITY TO ADJACENT OUTLETS, EXTEND CONDUIT AND WIRING AS
REQUIRED.
XRR EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC. - TO BE REMOVED AND REINSTALLED
AT NEW LOCATION - EXTEND CONDUIT AND WIRING AS REQUIRED
MC MECHANICAL CONTRACTOR
MLO MAIN LUGS ONLY
NEC NATIONAL ELECTRICAL CODE
NF NOT FUSED
OFE OWNER FURNISHED EQUIPMENT
TC TELECOMMUNICATIONS CONTRACTOR
TCC TEMPERATURE CONTROLS CONTRACTOR
TV TELEVISION
VDC VOICE/DATA CONTRACTOR
VFD VARIABLE FREQUENCY DRIVE
WM WIREMOLD
WP WEATHERPROOF ENCLOSURE - NEMA 4
DEDICATED NEUTRAL CONDUCTORS ARE REQUIRED FOR ALL 120V AND 277V BRANCH CIRCUITS. MULTIWIRE BRANCH
CIRCUITS WITH SHARED NEUTRAL CONDUCTORS ARE NOT PERMITTED.
ROUTE NO MORE THAN (3) BRANCH CIRCUIT HOMERUNS PER EACH CONDUIT RUN.
GENERAL ELECTRICAL INSTALLATION NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
ALL MOUNTING HEIGHTS ARE TO CENTER OF DEVICE UNLESS OTHERWISE NOTED.
ALL NEW WALL MOUNTED ELECTRICAL DEVICES ARE TO BE INSTALLED FLUSH IN WALL UNLESS
OTHERWISE NOTED. ALL ELECTRICAL CONDUIT SHALL BE CONCEALED BEHIND FINISHED WALLS AND ABOVE FINISHED CEILING UNLESS OTHERWISE NOTED. THE COST TO CUT AND PATCH WALLS SHALL BE
THE RESPONSIBILITY OF THE TRADE REQUIRING THE CUTTING.
CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS REQUIRED FOR
ELECTRICAL WORK. CONTRACTOR SHALL REPLACE ANY DAMAGED CEILING TILES.
PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW OR RELOCATED WALL OR CEILING
MOUNTED DEVICES WITH ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS.
COORDINATE ALL SHUT-DOWNS OF EXISTING ELECTRICAL SYSTEMS WITH OWNER A MINIMUM OF
FOURTEEN (14) WORKING DAYS IN ADVANCE. ALL SHUT-DOWNS SHALL OCCUR DURING WEEKENDS OR BETWEEN 8:00PM AND 7:00AM ON WEEKDAYS ("OFF-HOURS"). INCLUDE ALL PREMIUM TIME CHARGES IN
BID.
ALL NOISE GENERATING OPERATIONS, INCLUDING CUTTING OF CEILINGS, WALLS AND FLOORS, CORING, DRILLING, ETC. SHALL BE SCHEDULED DURING WEEKENDS OR BETWEEN 8:00PM AND 7:00AM ON
WEEKDAYS ("OFF-HOURS"). INCLUDING ALL PREMIUM TIME CHARGES IN BID.
CONTRACTOR SHALL CONNECT ALL MECHANICAL EQUIPMENT COMPLETE PER MANUFACTURER'S WIRING DIAGRAMS AND INSTRUCTIONS. COORDINATE WITH MECHANICAL CONTRACTOR AND VERIFY LOCATION, VOLTAGE, AMPS, NO. OF WIRES, AND PROTECTION REQUIREMENTS PRIOR TO ROUGH-IN. CONTACT
ENGINEER WITH ANY DISCREPANCIES FROM DESIGN DRAWINGS.
PROVIDE LIQUID-TIGHT FLEXIBLE METAL CONDUIT FOR FINAL CONNECTION TO MECHANICAL EQUIPMENT
OR OTHER EQUIPMENT WHICH MAY PROPAGATE VIBRATION.
ALL FLUORESCENT LAMPS THAT WILL NOT BE REUSED SHALL BE DISPOSED OF IN ACCORDANCE WITH EPA STANDARDS, AND WRITTEN EVIDENCE OF PROPER DISPOSAL SHALL BE FURNISHED TO THE OWNER.
ALL WORK SHALL BE PERFORMED IN STRICT CONFORMANCE WITH THE PHASING REQUIREMENTS OF THE PROJECT. ALL COSTS ASSOCIATED WITH THESE REQUIREMENTS SHALL BE INCLUDED IN THE BID
SUBMITTAL.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING TEMPORARY LIGHTING TO ADEQUATELY LIGHT ALL CONSTRUCTION AREAS, TEMPORARILY PARTITIONED AREAS, AND EXIT CORRIDORS MAINTAINED DURING
CONSTRUCTION.
DEFINITION: "PROVIDE" - FURNISH, INSTALL AND CONNECT COMPLETE.
PROJECT AND PHASING SCOPE LINES INDICATE WHERE GENERAL CONSTRUCTION BOUNDARIES OCCUR.
ELECTRICAL WORK AND UTILITY TIE-INS MAY OCCUR OUTSIDE OF SCOPE LINES.
COUPLING AND JUNCTION BOX COLOR CODE
COUPLING AND JUNCTION BOX COLOR CODE AS INDICATED:
HOSPITAL SYSTEM
EMERGENCY "LIFE SAFETY" POWER
COLOR CODE
PURPLE
EMERGENCY "CRITICAL" POWER YELLOW
NORMAL POWER GREEN
TELECOMMUNICATIONS BLUE
LOW-VOLTAGE POWER BLACK
FIRE ALARM RED
NURSE CALL WHITE
GENERATOR POWER BROWN
EQUIPMENT EMERGENCY (ESSENTIAL) POWER ORANGE
FIRE ALARM SYSTEM LEGEND
F
F
F
CM
MM
TS
WF
NOTE F1: PROVIDE A 2-GANG MINIMUM SIZE BACKBOX FOR ALL OF THE ABOVE FIRE ALARM DEVICES. ALL FIRE ALARM SYSTEM CONDUCTORS SHALL BE INSTALLED IN 3/4" MINIMUM SIZE COMPLETE CONDUIT SYSTEM WITH COLOR CODED WIRING AS INDICATED ON SHOP DRAWINGS PREPARED BY NOTIFIER - MAINTAIN VA COLOR CODING. ALL NETWORK AND IDNET CABLES SHALL BE "COMMUNICATION GRADE" TYPE CABLE. FURNISH, INSTALL AND CONNECT ALL FIRE ALARM DEVICES IN
ACCORDANCE WITH WIRING DIAGRAMS AS PREPARED BY NOTIFIER.
FIRE ALARM PANELS - MOUNTING INDICATED FOR EACH TYPE.
FANE - FIRE ALARM NODE EQUIPMENT - CONSISTING OF FIRE ALARM CONTROL PANEL AND DIGITAL VOICE
CONTROLLER. REFER TO FIRE ALARM PANEL DETAIL.
FAZE - FIRE ALARM ZONE EQUIPMENT - CONSISTING OF FIRE ALARM EXTENDER PANEL AND DIGITAL AMPLIFIER. REFER
TO FIRE ALARM PANEL DETAIL.
ADDRESSABLE MANUAL PULL STATION - DOUBLE ACTION PUSH-PULL, SEMI-RECESSED, MOUNTED AT 48"AFF.
SPEAKER/STROBE (ADA TYPE) - RED HOUSING WITH WHITE "FIRE" LETTERING. MOUNTED AT 80".
STROBE ONLY DEVICE (ADA TYPE) - RED HOUSING WITH WHITE "FIRE" LETTERING. MOUNTED AT 80" AFF.
SMOKE DETECTOR - ADDRESSABLE INTELLIGENT PHOTOELECTRIC TYPE WITH STANDARD BASE - CEILING MOUNTED.
DUCT DETECTOR - ADDRESSABLE INTELLIGENT PHOTOELECTRIC DETECTOR, SAMPLING TUBES AND PROGRAMMABLE
RELAY BASE. PROVIDE DUCT DETECTOR TEST/RESET SWITCH
REMOTE TEST/RESET SWITCH - TEST/RESET SWITCH WITH REMOTE INDICATOR LAMP FOR DUCT DETECTOR. WALL
MOUNTED AT 6" BELOW THE CEILING.
CONTROL MODULE - RELAY FOR CONTROL OF SMOKE DAMPERS, ELEVATOR RECALL, MAGNETIC DOOR HOLDERS, AUTOMATIC DOORS, LATCH RETRACTION, ETC.
MONITOR MODULE - SUPERVISED RELAY FOR MONITORING TAMPER SWITCH, FLOW SWITCH, DAMPER POSITION ETC.
TAMPER SWITCH - MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL TAMPER SWITCH. ELECTRICAL
CONTRACTOR SHALL PROVIDE MONITOR MODULE AND TEST SWITCH.
WATER FLOW SWITCH - MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL FLOW SWITCH. ELECTRICAL CONTRACTOR SHALL PROVIDE MONITOR MODULE AND TEST SWITCH. PROVIDE LOCAL ALARM BELL.
24V MAGNETIC TYPE DOOR HOLDER.DH
GENERAL LEGEND:
CODED NOTE - "1" INDICATES NOTE NUMBER
REVISION REFERENCE NUMBER
MECHANICAL EQUIPMENT IDENTIFIER
DETAIL REFERENCE - "1" INDICATES DETAIL NUMBER, "E0.1" INDICATES DRAWING NUMBER
COLUMN REFERENCE GRID
INDICATES EXISTING CONSTRUCTION WALL TYPE
INDICATES DEMOLITION WALL TYPE
INDICATES NEW CONSTRUCTION WALL TYPE
AC
GB13
E0.1
A
LIGHTING FIXTURES LEGEND
LED LIGHTING FIXTURE CONNECTED TO NORMAL CIRCUIT AS INDICATED - TYPE AS SPECIFIED IN SCHEDULE.
REFER TO LIGHTING CIRCUITING GUIDE FOR ADDITIONAL INFORMATION.
LED LIGHTING FIXTURE CONNECTED TO EMERGENCY LIFE SAFETY CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE.
CONNECT TO UNSWITCHED EMERGENCY CIRCUIT. REFER TO LIGHTING CIRCUITING GUIDE FOR ADDITIONAL
INFORMATION.
LED LIGHTING FIXTURE - CONNECTED TO EMERGENCY CRITICAL LIGHTING CIRCUIT - TYPE AS SPECIFIED IN
SCHEDULE. REFER TO LIGHTING CIRCUITING GUIDE FOR ADDITIONAL INFORMATION.
LED LIGHTING FIXTURE CONNECTED TO NORMAL CIRCUIT AS INDICATED - TYPE AS SPECIFIED IN SCHEDULE.
REFER TO LIGHTING CIRCUITING GUIDE FOR ADDITIONAL INFORMATION.
LED LIGHTING FIXTURE - CONNECTED TO EMERGENCY LIFE SAFETY LIGHTING CIRCUIT - TYPE AS SPECIFIED IN SCHEDULE. CONNECT TO UNSWITCHED EMERGENCY LIFE SAFETY CIRCUIT. REFER TO LIGHTING CIRCUITING
GUIDE FOR ADDITIONAL INFORMATION.
LED LIGHTING FIXTURE CONNECTED TO NORMAL CIRCUIT AS INDICATED - TYPE AS SPECIFIED IN SCHEDULE.
REFER TO LIGHTING CIRCUITING GUIDE FOR ADDITIONAL INFORMATION.
LED LIGHTING FIXTURE - CONNECTED TO EMERGENCY CRITICAL OR LIFE SAFETY LIGHTING CIRCUIT AS INDICATED CONNECT LIFE SAFETY TO UNSWITCHED EMERGENCY CIRCUIT. - TYPE AS SPECIFIED IN SCHEDULE.
EXIT SIGN - CEILING OR WALL MOUNTED - TYPE AS SPECIFIED IN SCHEDULE OR AS INDICATED ON PLANS.
CONNECT TO NONSWITCHED EMERGENCY CIRCUIT.
A
A
C C
C C
3,a
A
3,a
A
A
OS
D
O
LIGHTING CONTROLS
20A-1P-120/277V WALL SWITCH - MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED.
20A-3WAY-120/277V WALL SWITCH MOUNTED AT 48" UNLESS OTHERWISE NOTED.
20A-4WAY-120/277V WALL SWITCH MOUNTED AT 48" UNLESS OTHERWISE NOTED.
120/277V SINGLE POLE, LARGE PADDLE SWITCH WITH SMALL DIMMER SLIDER FOR 0-10V DIMMING CONTROL, AUTOMATICALLY RETURNS TO PRESET LEVEL - ENGRAVING LABEL - MOUNTED AT 48" AFF UNLESS OTHERWISE
NOTED. VERIFY ALL SWITCHES ARE COMPATIBLE WITH FIXTURE TYPE.
120/277V WALL SWITCH WITH PASSIVE INFRARED OCCUPANCY SENSOR MOUNTED AT 48" UNLESS OTHERWISE NOTED,CONFIGURED FOR AUTO-OFF/MANUAL-ON OPERATION. MOUNTED AT 48" UNLESS OTHERWISE NOTED.
LIGHTING ROOM CONTROLLER - INTEGRATES LOW-VOLTAGE DIMMING SWITCH AND OCCUPANCY SENSOR (WHERE SHOWN). PROVIDES DIMMING AND CONTROL OUTPUT TO LIGHTING FIXTURES. CABLING (CAT6A) TO CONNECT TO SWITCHING AND OCCUPANCY AND UTILIZES STANDARD LOW-VOLTAGE CABLING TO CONNECT TO FIXTURE'S DIMMING DRIVER. REFER TO OCCUPANCY SENSOR DIAGRAM FOR ADDITIONAL INFORMATION. ROOM CONTROLLER, OCCUPANCY SENSOR, AND OVER-RIDE SWITCH SHALL BE A COMPLETE SYSTEM FROM A SINGLE
MANUFACTURER.
LOW VOLTAGE SINGLE POLE LARGE PADDLE SWITCH. MOUNT AT 48" AFF UNLESS OTHERWISE NOTED.
VERIFY ALL SWITCHES ARE COMPATIBLE WITH FIXTURE TYPE.
LOW VOLTAGE SINGLE POLE 0-10VDC LARGE PADDLE SWITCH WITH SMALL DIMMER SLIDER,
AUTOMATICALLY RETURNS TO PRESET LEVEL - MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED. VERIFY
ALL SWITCHES ARE COMPATIBLE WITH FIXTURE TYPE.
DUAL TECHNOLOGY OCCUPANCY SENSOR - CONNECTS TO ROOM CONTROLLER. PROVIDE FORM C RELAY IN RELAY UNIT IN ALL OCCUPANCY SENSORS FOR HVAC SWITCHING. COORDINATE MOUNTING WITH
MANUFACTURER'S RECOMMENDATIONS.
OTHER DESIGNATIONS
L - "LINEAR COVERAGE", TWO SIDED, 90 LINEAR FT. COVERAGE
NOTE: REFER TO "DEVICE AND WALL PLATE DETAIL" FOR ADDITIONAL INFORMATION.
S
S
S
S
S
DLVS
RC
LIGHTING CIRCUITING DESIGNATION
X: REFER TO PANEL SCHEDULE ABBREVIATION KEY, PER DRAWING
1: CIRCUIT NUMBER
a,b: SWITCHING SCHEME z#: LIGHTING CONTROL ZONE NUMBER r#: LIGHTING CONTROL RELAY NUMBER
X1
SYMBOL DESCRIPTION
LIGHTING CIRCUITING GUIDE
LIGHTING DESIGNATION REFER TO LUMINAIRE SCHEDULE
B
MOTOR AND MOTOR CONTROLLERS (FLOOR PLAN VIEW)
COMBINATION FUSED MAGNETIC MOTOR STARTER COMPLETE WHITE "HAND-OFF-AUTO" SELECTOR SWITCH AND RED "RUN" PILOT LIGHT IN COVER. NEMA SIZE 0 CONTACTS AND NEMA 1 ENCLOSURE MINIMUM UNLESS OTHERWISE
NOTED.
VARIABLE SPEED DRIVE MOTOR CONTROLLER - (REFER TO SPECIFICATIONS SECTION 262911).
120V -1ø OR 277V -1ø (AS REQUIRED) MANUAL MOTOR STARTER WITH INTEGRAL OVERLOAD PROTECTION.
120V -1ø OR 277V -1ø (AS REQUIRED) MANUAL MOTOR STARTER WITH INTEGRAL OVERLOAD PROTECTION AND
"HANDS-OFF-AUTO"
120V -1ø OR 277V -1ø (AS REQUIRED) LOCKABLE MANUAL SWITCH (NO THERMAL OVERLOADS).
CONTROLLER FURNISHED WITH EQUIPMENT
VSD
ST
STHOA
SML
POWER DISTRIBUTION EQUIPMENT
208/120V-3PH-4W-SN PANELBOARD UNLESS OTHERWISE NOTED
480/277V-3PH-4W-SN PANELBOARD UNLESS OTHERWISE NOTED
SPECIAL PANEL OR PULLBOX - SIZE AND TYPE AS NOTED
NON-FUSED DISCONNECT SWITCH - SIZE AND TYPE AS NOTED
FUSED DISCONNECT SWITCH - SIZE AND TYPE AS NOTED, WITH TYPE RK1 FUSES
ELECTRICAL GROUNDING BUS BAR
EGB
POWER CIRCUITING GUIDE
POWER CIRCUITING DESIGNATION
X: REFER TO PANEL SCHEDULE ABBREVIATION KEY, PER DRAWINGS
1: CIRCUIT NUMBER
X1
SYMBOL DESCRIPTION
DEVICE, JUNCTION BOX, FLOOR BOX, ETC.
XXX
EQUIPMENT ABBREVIATION, REFER TO EQUIPMENT ABBREVIATION SCHEDULE FOR ADDITIONAL INFORMATION
PT
WIRING DEVICES
TV
20A-125V, HOSPITAL GRADE, GROUNDED DUPLEX RECEPTACLE, MOUNTED IN (1) GANG BACKBOX AT 18" UNLESS
OTHERWISE NOTED. CONNECTED TO NORMAL POWER
DOUBLE 20A-125V, HOSPITAL GRADE, GROUNDED DUPLEX RECEPTACLES, MOUNTED IN (2) GANG BACKBOX AT 18"
UNLESS OTHERWISE NOTED. CONNECTED TO NORMAL POWER.
20A-125V, HOSPITAL GRADE, GROUND FAULT (GF) INTERRUPTER TYPE RECEPTACLE, MOUNTED IN A (2) GANG
BACKBOX AT 18" UNLESS OTHERWISE NOTED. CONNECTED TO NORMAL POWER
20A-125V, HOSPITAL GRADE, GROUNDED DUPLEX RECEPTACLE, MOUNTED IN (2) GANG BACKBOX. COORDINATE EXACT MOUNTING HEIGHT WITH ARCHITECT PRIOR TO ROUGH-IN. CONNECTED TO NORMAL POWER
20A-125V, HOSPITAL GRADE, TAMPER RESISTANT GROUNDED DUPLEX RECEPTACLE, MOUNTED IN (2) GANG
BACKBOX AT 18" UNLESS OTHERWISE NOTED. CONNECTED TO NORMAL POWER.
SAME DEVICE TYPES AS INDICATED ABOVE EXCEPT SHADING INDICATES DEVICE IS CONNECTED TO EMERGENCY
CIRCUIT
SPECIAL OUTLETS - TYPES AS NOTED ON PLANS
FLUSH STYLE FIRE-RATED POKE-THRU - MULTI-SERVICE POKE-THRU FOR CONNECTION TO POWERED FURNITURE. COORDINATE POWER AND DATA QUANTITIES AND REQUIREMENTS WITH FURNITURE VENDOR.
VERIFY FINISH ON COVER PLATE WITH ARCHITECT. PROVIDE CORE DRILL THRU FLOOR AS REQUIRED AND SEAL
FLOOR PENETRATIONS TO MAINTAIN FIRE RATING.
SURFACE MOUNTED METAL RACEWAY - INSERT DIMENSIONS, MOUNTED AT 3'-6" AFF UNLESS OTHERWISE NOTED.
PROVIDE OUTLETS AS DESIGNATED ON DRAWINGS. SURFACE MOUNTED RACEWAY SHALL BE FED FROM EMT CONDUIT CONCEALED IN WALL. PROVIDE ALL COMPONENTS (ELBOWS, COUPLINGS, ENDCAPS, ETC.) NECESSARY
FOR A COMPLETE INSTALLATION.
20A-125V, HOSPITAL GRADE, GROUND FAULT INTERRUPTER TYPE RECEPTACLE INSTALLED IN WEATHERPROOF ENCLOSURE THAT MAINTAINS WET LOCATION RATING WHILE IN-USE. CONNECT TO NORMAL CIRCUIT, SURFACE
MOUNT AT 30" ABOVE FINISHED ROOF SURFACE.
NOTE: REFER TO "DEVICE AND WALL PLATE DETAIL" FOR ADDITIONAL INFORMATION.
WP
SM
TR
WIRE TERMINATIONS
JJ JUNCTION BOX, CEILING OR WALL MOUNTED, 4" SQ. WITH GROUND LUG, UNLESS OTHERWISE NOTED:
SC - SINK CONTROLS. CONNECT PER MANUFACTURERS WIRING DIAGRAM
TC - TOILET CONTROLS. CONNECT PER MANUFACTURERS WIRING DIAGRAM
VAV - VARIABLE AIR VOLUME TERMINALS. SEE PLANS FOR ADDITIONAL INFORMATION AND WORK REQUIREMENTS.
PF - POWERED FURNITURE
AD - AUTOMATIC DOOR. JUNCTION BOX ABOVE CEILING. EC SHALL CONNECT AUTOMATIC DOOR INCLUDING PUSH PAD.
TF - DATA CONNECTION FOR POWERED FURNITURE
MOTOR - HORSEPOWER AND VOLTAGE AS NOTED
JUNCTION BOX MOUNTED AT 48" AFF FOR CONNECTION TO AUTOMATIC DOOR PUSH PAD DEVICE. PROVIDE 3/4"C TO DOOR
CONTROLLER WITH WIRING PER MANUFACTURER'S REQUIREMENTS.
3/4" MINIMUM SIZE CONCEALED CONDUIT WITH #12 AWG, THWN STRANDED COPPER CONDUCTORS PLUS SEPARATE #12 GROUND ( ), AND CONDUIT WIRE FILLS IN ACCORDANCE WITH N.E.C. - EMT MAY BE USED IN INTERIOR STUD WALLS, AND ABOVE FINISHED CEILINGS. DEDICATED NEUTRAL CONDUCTORS ARE REQUIRED FOR ALL 120V AND 277V BRANCH CIRCUITS.
MULTIWIRE BRANCH CIRCUITS WITH SHARED NEUTRAL CONDUCTORS ARE NOT PERMITTED. ROUTE NO MORE THAN (3)
BRANCH CIRCUIT HOMERUNS PER EACH CONDUIT RUN.
LVS
SECURITY SYSTEM LEGEND
SECURITY CONTROL PANEL - LENEL, MATCH FACILITY STANDARDS.
SECURITY CAMERA - FIXED DOME CAMERA CEILING MOUNTED. VARIFOCAL, 80º - 22º VIEWING ANGLE RANGE, NETWORK-ENABLED, 1280 X 800 (1MP) RESOLUTION, H.264 VIDEO COMPRESSION, 30 FRAMES PER SECOND, TAMPERING ALARM, POWER OVER ETHERNET, PROGRESSIVE SCAN, TAMPER RESISTANT CASING. PROVIDE DROP CEILING MOUNTING ACCESSORIES TO MOUNT DOME FLUSH WITH CEILING. DIRECTIONAL ARROW(S)
INDICATE GENERAL DIRECTION OF CAMERA'S FIELD OF VIEW.
PROXIMITY READER - PROVIDE CARD READER AT ALL ACCESS CONTROLLED DOORS. REFER TO DETAILS FOR TYPICAL INSTALLATION REQUIREMENTS. INSTALL CARDER AT LOCATION IN LIEU OF TYPICAL DETAILS WHEN
SHOWN ON PLANS.
PROXIMITY CARD READER WITH INTEGRAL KEY PAD FOR DUAL-AUTHENTICATION - PROVIDE READER AT ACCESS CONTROLLED DOORS AS INDICATED. REFER TO DETAILS FOR TYPICAL INSTALLATION REQUIREMENTS. INSTALL
READER AT LOCATION INDICATED IN LIEU OF TYPICAL DETAILS WHEN SHOWN ON PLANS.
ACCESS CONTROLLED DOOR TYPE # AS INDICATED. REFER TO ACCESS CONTROL DOOR DETAILS FOR
ADDITIONAL INFORMATION.
PUSH-TO-EXIT BUTTON - OPERATES MAGNETIC LOCKS, ELECTRIC STRIKES, AUTOMATIC DOORS, ETC. MOUNTED
AT 48" AFF.
REQUEST-TO-EXIT - MOTION SENSOR DEVICE OPERATES MAGNETIC LOCKS, ELECTRIC STRIKES, AUTOMATIC
DOOR, ETC. MOUNTED AT TOP OF DOOR PER MANUFACTURER'S REQUIREMENT.
PANIC ALARM PUSHBUTTON - MOUNTED TO UNDERSIDE OF DESK. PROVIDE PUSH BUTTON AND CONNECTION
PER HOSPITAL STANDARDS. REFER TO ELECTRICAL DETAILS FOR ADDITIONAL INFORMATION.
WM - WALL MOUNTED DEVICE WITH PROTECTIVE COVER.
D#
PROVIDE MINIMUM SIZE BACK BOX AS REQUIRED FOR ALL OF THE ABOVE SECURITY DEVICES AND INSTALL IN 3/4"C MINIMUM
COMPLETE CONDUIT SYSTEM TO JUNCTION BOX ABOVE FINISHED CEILING.
REFER TO SPECIFICATIONS DIVISION 28 FOR FURTHER DETAILS REGARDING THE SECURITY SYSTEM.
MOUNT DEVICES AT MOUNTING HEIGHTS LISTED ABOVE UNLESS OTHERWISE NOTED ON THE FLOOR PLANS. COORDINATE
EXACT MOUNTING LOCATION WITH ARCHITECTURAL ELEVATIONS.
ALL SECURITY SYSTEM ROUGH-INS, CONDUIT, WIRING AND EQUIPMENT/DEVICES SHALL BE PROVIDED BY CONTRACTOR.
FURNISH, INSTALL AND CONNECT ALL SECURITY DEVICES IN ACCORDANCE WITH SYSTEM PROVIDER. PROVIDE ALL ADDITIONAL COMPONENTS AS NECESSARY FOR A COMPLETE SYSTEM. SUBMIT ALL DEVICES WITH SHOP DRAWINGS SUBMITTAL.
PR
S1.
S2.
S3.
S4.
S5.
PR
C
PE
P
RE
PK
PK
GENERAL ELECTRICAL SPECIFICATION NOTES:
THE FOLLOWING ITEMS SUPERCEDE ITEMS WITHIN THE SPECIFICATIONS:
THE USE OF HOSPITAL GRADE HCF CABLE IS PERMITTED FOR CONNECTION TO FIXED EQUIPMENT (LIGHTING FIXTURES, SURGICAL BOOMS,ETC). THE LENGTH IS LIMITED TO 6 FEET.
THE FOLLOWING SYSTEM CABLING IS PERMITTED TO BE INSTALLED IN THE CABLE TRAY SYSTEM:
A. TEL/DATA CABLING
B. HOSPITAL PAGING SYSTEM
ALL OTHER SPECIAL SYSTEMS CABLING (FIRE ALARM, ACCESS CONTROL) SHALL BE INSTALLED IN A COMPLETE
CONDUIT SYSTEM
C. NURSE CALL CABLING
D. CATV
COR CONTRACTING OFFICER'S REPRESENTATIVE
3,a
RS
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID ISSUE
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
CLEVELAND, OHIO
DESIGN AND CONSTRUCTION DOCUMENTS AS INSTRUMENTS OF
SERVICE ARE GIVEN IN CONFIDENCE AND REMAIN THE PROPERTY
OF PERSPECTUS ARCHITECTURE. THE USE OF THIS DESIGN AND
THESE CONSTRUCTION DOCUMENTS FOR PURPOSES OTHER
THAN THE SPECIFIC PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN CONSENT OF
PERSPECTUS ARCHITECTURE.
COPYRIGHT © 2021.
1300 East 9th St. Suite 910 Cleveland, Ohio 44114 P. 216.752.1800 F. 216.752.3833 19072
C R e v it L o c a l F ile s \1
F F
H C
F R
S o n n y .T
.N g u y e n L
Q L
.r v t
/8
/2
:1
:0
A
M
E-001
ELECTRICAL LEGEND AND
GENERAL NOTES
RENOVATE AND RECONFIGURE
CLINICAL SERVICES
541‐20‐101
04/09/2021 MPL JRD
REVISIONS: DATE:
BID ISSUE 04/09/2021
DN
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007 T ectonic Cop yright 2007
T ectonic Cop yright 2007
J J
J
J
J
26 27 29 30 32 33 34 35 36
N
P
Q
R
T
W
Y
Z
AA
BB
CC
U
39 4228 31 4140
M
36a
DD
CC.2
BB.5
AA.5
26.5 CC.10
LE13
LE14
LE15
LE16
EQLG12 EQRG13
LF14 LF13
RAD1LNL1
RAD1LNH1
LF12
LF12-CR
X
X X X
X
X
XX
X
X
X X
EQRG14
EQRG11
EQLG11
EQDLG11
X
X
X
X
X X
X
X
X X
X
X X
X
X X X X
X X X
X X
X X X
X
XX
LF16
LF14-CR
LF15
NEW
X
X
PHASE 1
PHASE 1 AREA
PHASE 2 AREA
PHASE 3 AREA
PHASE 4 AREA
PHASE 5
AREA
X
Multipurpose Room
1B430
Processing
1B465
Tlt.
1B464
Alcove
1B463
CWT Work Area-1
1B508-1
MRI Scan
1B532
MRI Equip
1B531
Office
1B525
Soiled
1B524
Clean
1B523
Storage
1B521
Pat Toilet
1B522
Staff Toilet
1B520 Staff Lounge
1B519
Reception
1B517
Waiting
1B511
Corridor
1B513
Office
1B501D
Office
1B501C
Pre Op Office
1B501B
Pre Op Office
1B501A
Lockers
1B453B
Office
1B515
Read Consult
1B516
Public Toilet
1B512
EMS
1B514
Armory
1B452
Waiting
1B510
Interview Room
1B449
K-9 Officer Office
1B448
Cap't of Patrol Div./Ops Office
1B447
Lt. & Sg. Office
1B446
Passage
1B445C
Dispatch & Fire
1B456
Sec'y
1B457
Chief Of Police
1B459
Files/Copy
1B458
Interview Room
1B441
Vestibule
1B440
Cubicle Area
1B442
Holding Room
1B444
Work Rm.
1B450
Toilet
1B451
Evidence Room
1B443
Criminal Inves. Office
1B455
Capt. of Phys Sec & Tra Office
1B454
Corridor
1B400G
Stair 11
1S11
Corridor
1A400H
VSO Office
1B418
VSO Office
1B419
VSO Office
1B416
VSO Office
1B417
Hall
1B412
VSO Office
1B415
Escort Services
1B411Patient Alcove
1B410
VSO Office
1B413
VSO Office
1B414
Tri-C Veterans Edu.
Connection Center
1B420
Mainstreet
1B400A
Mainstreet
1B400B
Pre Op Waiting
1B476 Blood Draw Waiting
1B460
Corridor
1C400
Servery
1C411
Dining
1C410
Service 1
1C412
Service 2
1C413
Food Prep.
1C414
Dry Storage
1C415 Cooler
1C414B
Cooler
1C414A
EMS
1C417
Office
1C416
Corridor
1C404
Corridor
1C470
Veg. Cooler
1C471
Milk & Bread
1C472
Office
1B571
Exam Room
1B573
Office
1B575
Group Therapy 2
1B570D
Group Therapy 1
1B570C Toilet
1B570A
Toilet
1B570B
Nurse Screening
1B581
Waiting
1B560
Office
1B572
Office
1B582
Office
1B584
Case Manager
1B586
TMS Storage
1B587
Office
1B588
Office
1B579
Office
1B577
Office
1B576
Office
1B574
Corridor
1C501
Reception Copy/Work Rm
1C513
Waiting
1C511 Office
1B578
MH Office
1B594 Office 6
1C517
Telecomm
1C519
Office 9
1C518
Office 11
1C516
Office 13
1C514
Office 15
1C512
Office 14
1C541
Office 12
1C543
Corridor
1C557
Office 7
1C520
Engineering Room
1C521
Office 10
1C545
Office 8
1C547
Staff M Toilet
1C553
Staff F Toilet
1C555
Office 2
1C535
Office 3
1C534
Office 4
1C533
Office 5
1C532
Office 6
1C531
MRI Scan
1B538
MRI Equip
1B539
Ante Room
1B540
Corridor
1B541
Stair 12
1S12Control
1B537
Dress
1B536
Dress
1B535
Gowned Waiting
1B534
Control
1B533
Corridor
1B530
MH Office
1B593 MH Office
1B592
MH Office
1B591
CWT Office
1B590
CWT Consult
1B505D
Tlt
1B505C
CWT Consult
1B505B
CWT Consult
1B505A EEG Clinic
1B503C
EEG Office
1B503B
EEG Office
1B503A
Waiting
1B504
Office
1B502B
Office
1B502A
CWT Group Rm.
1B506
Elec.
1B507
Office
1B585
Office
1B583
Office
1B562
Office
1B564
Tele-Health
1B566A
Office
1B568
Corridor
1B560B
Registration
1B560A
Workroom
1B563A
Workroom
1B563 Breakroom
1B567
Soil
1B493
TeleHealth
1B492
Exam 6
1B491
Exam 7
1B490
Exam 8
1B489
Corridor
1B486A
Control Station
1B486
Clean
1B494 Exam 4
1B487 Exam 5
1B488
Corridor
1B402
Blood Draw 3
1B474
Storage
1B475
Control Station
1B485
Storage
1B484
Exam 1
1B482
Tlt.
1B479
Tlt.
1B478
Sub Wait
1B483 Exam 3
1B481
Exam 2
1B480
Blood Draw 2
1B471
Blood Draw 1
1B468
Reception/ Discharge
1B477 Check-In
1B467
Blood Draw 6
1B473
Blood Draw 5
1B472
Blood Draw 4
1B470
EMS
1B469
E-002
E-002
E-002
E-002
PHASE 2 AREA
Data
1B159
32 33 34
Q 4 3
X X
X
X
NEW
FANE
NEW
FAZE
Eng Closet
1B495
F-14
F-14
33 34
R
S
R1 R1 R2 R3
LF13-CR
X
X X X
X
X X
X
X X
X X
X
X
IRM
1B496
28a
CC.2
28.9
CC.9
X
X X X
33 34
X X
TCP
X X
X
X
X
X
X
X
XX
RF11CP LF11LSHF11-LS
HF11-CRDPLF11CR DPLF11 HF11
X
TCP
X
TCP
XX
X
X X
X
LF11CR
DPLF11CR
X
X
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID ISSUE
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
CLEVELAND, OHIO
DESIGN AND CONSTRUCTION DOCUMENTS AS INSTRUMENTS OF
SERVICE ARE GIVEN IN CONFIDENCE AND REMAIN THE PROPERTY
OF PERSPECTUS ARCHITECTURE. THE USE OF THIS DESIGN AND
THESE CONSTRUCTION DOCUMENTS FOR PURPOSES OTHER
THAN THE SPECIFIC PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN CONSENT OF
PERSPECTUS ARCHITECTURE.
COPYRIGHT © 2021.
1300 East 9th St. Suite 910 Cleveland, Ohio 44114 P. 216.752.1800 F. 216.752.3833 19072
C R e v it L o c a l F ile s \1
F F
H C
F R
S o n n y .T
.N g u y e n L
Q L
.r v t
/8
/2
:1
:1
A
M
E-002
PARTIAL FIRST FLOOR
ELECTRICAL KEY PLAN
RENOVATE AND RECONFIGURE
CLINICAL SERVICES
541‐20‐101
04/09/2021 MPL JRD
0' 8' 16' 32' 64'0' 8' 16' 32' 64'0' 8' 16' 32' 64'0' 8' 16' 32' 64'0' 8' 16' 32' 64'
1/16" = 1'-0"
PARTIAL FIRST FLOOR ELECTRICAL KEY PLAN 1N
GENERAL ELECTRICAL INSTALLATION NOTES
G1 PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW OR RELOCATED WALL OR CEILING MOUNTED
DEVICES.
G2 COORDINATE ALL SHUT-DOWNS OF EXISTING ELECTRICAL SYSTEMS WITH OWNER A MINIMUM OF FOURTEEN
WORKING DAYS IN ADVANCE.
G3 ALL NOISE GENERATING OPERATIONS, INCLUDING CUTTING OF CEILINGS, WALLS AND FLOORS, CORING, DRILLING, ETC. SHALL BE SCHEDULED ON WEEKENDS OR BETWEEN 8:00PM AND 7:00AM ON WEEKDAYS. INCLUDE ALL
PREMIUM TIME CHARGES IN BID.
G4 ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS REQUIRED FOR ELECTRICAL WORK. ELECTRICAL CONTRACTOR SHALL REPLACE ANY DAMAGED CEILING MATERIAL.
G5 WHERE POSSIBLE ALL NEW WALL MOUNTED ELECTRICAL DEVICES ARE TO BE INSTALLED FLUSH IN WALL UNLESS OTHERWISE NOTED. ALSO WHERE POSSIBLE ALL ELECTRICAL CONDUIT SHALL BE CONCEALED BEHIND FINISHED WALLS AND ABOVE FINISHED CEILING UNLESS OTHERWISE NOTED. THE COST TO CUT AND PATCH WALLS SHALL
BE THE RESPONSIBILITY OF THE TRADE REQUIRING THE CUTTING.
G6 ALL FLUORESCENT LAMPS THAT WILL NOT BE REUSED SHALL BE DISPOSED OF IN ACCORDANCE WITH EPA STANDARDS, AND WRITTEN EVIDENCE OF PROPER DISPOSAL SHALL BE FURNISHED TO THE OWNER.
G7 ALL WORK SHALL BE PERFORMED IN STRICT CONFORMANCE WITH THE PHASING REQUIREMENTS OF THE PROJECT. ALL COSTS ASSOCIATED WITH THESE REQUIREMENTS SHALL BE INCLUDED IN THE BID SUBMITTAL.
PANELBOARD DESIGNATION SCHEDULE
PANEL
DESIGNATION
PANEL NAME
ESSENTIAL
SYSTEM
CLASSIFICATION VOLTAGE
A HF11 NORMAL 480/277V
B HF11-CR CRITICAL 480/277V
C HF11-LS LIFE SAFETY 480/277V
D LF15 NORMAL 208/120V
E LF11CR CRITICAL 208/120V
F LF11LS LIFE SAFETY 208/120V
G LF16 NORMAL 208/120V
H LF14-CR CRITICAL 208/120V
J LF13-CR CRITICAL 208/120V
K LME22-EQ EQUIPMENT 208/120V
# CODED NOTES:
PROVIDE NEW LENEL CONTROL PANEL IN EXISTING TR ROOM FOR NEW ACCESS CONTROLLED DOORS IN PHASE 3 - 5. REFER TO POWER AND FIRE ALARM/SECURITY PLANS FOR ADDITIONAL INFORMATION.
EXISTING LENEL PANEL (PANEL E) IN EXISTING TR ROOM FOR NEW ACCESS CONTROLLED DOORS IN
PHASE 3 - 5. REFER TO ACCESS CONTROL DETAILS FOR ADDITIONAL INFORMATION.
PROVIDE NEW FIRE ALARM ZONE EQUIPMENT DURING PHASE 1. CONNECT NEW FIRE ALARM PANEL COMPLETE TO 120V-1ø-20A LIFE SAFETY CIRCUIT INDICATED VIA 3/4"C - 2#12 AND 1#12EG. REFER TO FIRE
ALARM CONTROL PANEL DETAILS FOR ADDITIONAL INFORMATION.
PROVIDE NEW FIRE ALARM NODE EQUIPMENT DURING PHASE 1. CONNECT NEW FIRE ALARM PANEL COMPLETE TO 120V-1ø-20A LIFE SAFETY CIRCUIT INDICATED VIA 3/4"C - 2#12 AND 1#12EG. REFER TO FIRE
ALARM CONTROL PANEL DETAILS FOR ADDITIONAL INFORMATION.
PROVIDE NEW FIRE ALARM ZONE EQUIPMENT DURING PHASE 2. REFER TO FIRE ALARM CONTROL PANEL
DETAILS FOR ADDITIONAL INFORMATION.
LOCATION OF EXISTING FIBER TERMINATION BOX FOR FIRE ALARM SYSTEM. REFER TO FIRE ALARM RISER
FOR ADDITIONAL INFORMATION.
PROVIDE (2) LENEL CONTROL PANEL IN EXISTING TR ROOM FOR NEW ACCESS CONTROLLED DOORS IN PHASE 1 AND 2. REFER TO ACCESS CONTROL DETAILS FOR ADDITIONAL INFORMATION. PROVIDE 120V-1Ø-20A CIRCUIT FROM PANEL LF13-CR CIRCUIT #14 AND CONNECT COMPLETE TO LENEL PANELS VIA
3/4"C-2#12 AND 1#12 EG.
REFER TO ONE LINE DIAGRAM FOR CONDUIT SIZES AND ADDITIONAL INFORMATION.
CONDUIT ROUTING GENERAL NOTE
CONDUIT ROUTING INDICATED FOR REFERENCE ONLY. CONTRACTOR IS RESPONSIBLE FOR SUBMITTING CONDUIT ROUTING COORDINATION DRAWINGS WITH ELECTRICAL EQUIPMENT SUBMITTAL FOR APPROVAL. ROUTING DRAWINGS SHALL INCLUDE FIELD VERIFIED ROUTING, BENDS, PULLBOXES, CONDUIT BODIES, PENETRATIONS, ETC. CONTRACTOR SHALL INCLUDE EXISTING CONDITIONS WHERE NECESSARY TO CONVEY ROUTING INFORMATION. MAINTAIN NEC REUIRED ACCESSIBILITY TO ALL EXISTING PULLBOXES, JUNCTION BOXES, ETC. TO REMAIN. ELECTRICAL EQUIPMENT SUBMITTAL WILL NOT BE APPROVED WITHOUT CONDUIT ROUTING DRAWINGS.
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
ENLARGED FIRST FLOOR ENG. CLOSET 1B495 2N
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
ENLARGED FIRST FLOOR TELECOM ROOM 1B496 3N
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
ENLARGED FIRST FLOOR FMS ROOM 1C521 4N
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
ENLARGED FIRST FLOOR ELECTRICAL RM 1B499 5
N
O S
AA
BB
CC
39 414036a
BB.5
AA.5
35.6
RAD1LNL1
RAD1LNH1
X
X
P H
A S
E
PHASE 1
PHASE 1
D1
TYPXX
X
X
X
X
X
X
X
X
X X
X
X
X X
X X X X
X
X
XXX
X
XX
XX
X X
X
27 29 30 32 33 34 35 36
Z
AA
BB
CC
3928 31 4036a
CC.8
CC.2
BB.5
AA.5
34.6 35.6
CC.5
CC.10
RAD1LNL1
RAD1LNH1
X
X X
X X
D1
TYP
D1
TYP
D1
TYP
D1
TYP
D2
X X
Passage
1B500B
X
X
Office-1
1B588-1
Corridor-1
1B570-1
Group Therapy
1-1
1B570C-1
Workroom-1
1B563-1
Veg.
Cooler-1
1C471-1
Milk & Bread-1
1C472-1
Waiting-1
1B560-1
Registration-1
1B560A-1
Elect.-1
1B550A-1
Read Consult-1
1B516-1
Telecomm-1
1C519-1
Office 6-1
1C517-1
Engineering Room-1
1C521-1
MRI
Scan-1
1B532-1
MRI
Equip-1
1B531-1
Control-1
1B533-1
Dress-1
1B535-1
Elec.-1
1B526-1
Corridor-1
1B541-1
Dress-1
1B536-1
Gowned Waiting-1
1B534-1
Control-1
1B537-1
Staff Toilet-1
1B520-1
Pat Toilet-1
1B522-1
Corridor-1
1B513-1
Waiting-1
1C511-1
Reception Copy/Work
Rm-1
1C513-1
Corridor-1
1B530-1
Ante Room-1
1B540-1
MRI
Equip-1
1B539-1
Corridor-1
1C557-1
Public Toilet-1
1B512-1
Office-1
1B515-1
Corridor-1
1C404-1
Supplies-1
1C515-1
Group Therapy
1-1
1B570C-1
Workroom-1
1B563-1
Veg.
Cooler-1
1C471-1
W.H. Work Room
1B551
W.H. Office
1B553
Office
1B555
Office
1B556
W.H. Office
1B557 W.H. Soiled
1B558
Corridor
1B550
M.H. Office
1B590
W.H. Office
1B554
W.H. General Work Area/Conference
Room
1B589
W.H. Exam Room
1B549
W.H.
Conf/Stor/Break/Clean
1B552
W.H.
1B589A
W.H. Exam Room
1B543E
W.H. Exam Room
1B547 W.H. Office
1B543F
W.H. Waiting Room
1B543D
W.H. Office
1B544
W.H. Tlt.
1B545
W.H. Office
1B546
W.H. Office
1B548
M.H. Office
1B559
Office
1B579
Office
1B577 Corridor
1B570G
Office
1B578
Office
1B575
Exam Room
1B573
Office
1B571
Group Therapy 2
1B570D
Nurse Screening
1B581
Office
1B582
Office
1B584
Case Manager
1B586
TMS Storage
1B587
Office
1B572
Office
1B574
Office
1B576
Corridor
1B560B
Office
1B583
Office
1B585
EMS
1B561
Office
1B562
Office
1B564
Tele-Health
1B566A
Storage
1B566
Office
1B568
Toilet
1B567A
Toilet
1B567B
Corridor
1B567CWorkroom
1B563A
Corridor
1B580
W.H. Conference Room
1B543A
Lockers
1B453B
W.H. Office
1B543B
W.H. Office
1B543C
Corridor
1B543G
Corridor
1B543G
Office-1
1B518-1
Read Consult-1
1B516-1
Staff Lounge-1
1B519-1
Clean-1
1B523-1
Soiled-1
1B524-1
Storage-1
1B521-1
Reception-1
1B517-1
Staff Toilet-1
1B520-1
Pat Toilet-1
1B522-1
Corridor-1
1B513-1
Waiting-1
1B511-1
W.H. Office
1B543F
W.H. Office
1B544
W.H. Tlt.
1B545
W.H. Office
1B546
W.H. Exam Room
1B547
W.H. Exam Room
1B543E
Office
1B568
W.H. Office
1B543C
W.H. Waiting Room
1B543D
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID ISSUE
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
CLEVELAND, OHIO
DESIGN AND CONSTRUCTION DOCUMENTS AS INSTRUMENTS OF
SERVICE ARE GIVEN IN CONFIDENCE AND REMAIN THE PROPERTY
OF PERSPECTUS ARCHITECTURE. THE USE OF THIS DESIGN AND
THESE CONSTRUCTION DOCUMENTS FOR PURPOSES OTHER
THAN THE SPECIFIC PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN CONSENT OF
PERSPECTUS ARCHITECTURE.
COPYRIGHT © 2021.
1300 East 9th St. Suite 910 Cleveland, Ohio 44114 P. 216.752.1800 F. 216.752.3833 19072
C R e v it L o c a l F ile s \1
F F
H C
F R
S o n n y .T
.N g u y e n L
Q L
.r v t
/8
/2
:1
:1
A
M
ED-101
PARTIAL FIRST FLOOR LIGHTING
DEMO PLAN - PHASE 1 AND 2
RENOVATE AND RECONFIGURE
CLINICAL SERVICES
541‐20‐101
04/09/2021 MPL JRD
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL FIRST FLOOR LIGHTING DEMO PLAN -
PHASE 1 1N
ELECTRICAL DEMOLITION NOTES
D1 ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC. THAT WILL NOT BE REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION SHALL INCLUDE ALL ELECTRICAL ITEMS SHOWN ON THIS PLAN THAT ARE NOT DESIGNATED BY "X", "XN" OR "XRR" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE REMOVED IN ORDER TO
PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED ELECTRICAL SYSTEMS COMPONENTS - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL DEMOLITION
WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.
D2 ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER SHALL
BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.
D3 DASHED WALLS ON PLAN INDICATE EXISTING CONSTRUCTION TO BE REMOVED.
D4 REFER TO ELECTRICAL LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED XB, XRR OR XN, AND REMOVE/BLANK OFF, RELOCATE OR REPLACE
THESE COMPONENTS AS REQUIRED.
D5 MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY TO
ACHIEVE SAME.
D6 THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A TIMELY
MANNER.
# CODED NOTES:
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL FIRST FLOOR LIGHTING DEMO PLAN -
PHASE 2 2N
REMOVE ALL LIGHTING FIXTURES, LIGHTING CONTROLS, AND ETC. FROM PROJECT AREA UNLESS OTHERWISE NOTED. REMOVE ALL ASSOCIATED CONDUIT AND WIRING COMPLETE TO SOURCE. MAINTAIN
CONTINUITY TO LIGHTING CIRCUITS OUTSIDE OF THE PROJECT SCOPE AREA.
PROVIDE TEMPORARY LIGHTING IN PASSAGE DURING PHASE 1 AND PHASE 2 DEMO FOR INSTALLATION OF
DUCTWORK. REFER TO PHASE 2 LIGHTING PLANS FOR ADDITIONAL INFORMATION.
D1
D2
OS OS
OS
OS
OS
OS R1
32 33 34 35 36
W
Y
30a 36a34.6 35.6
LF14 LF13
X
X
X
X
X X
X
X
X X
PHASE 3
PHASE 3
D1
TYP
X
X X
X
X
X X
X X
X
X X X X
X
X
X
X
X
X
X
X
30 32 33 34 35 36
N
P
Q
R
T
W
Y
S
U
31 36a34.6 35.6
LF13-CR
LE16
LF14 LF13
X X
X X X
X
X
X
X X
X
X X
X
X
X
X
X
X
X
XXXXXX
X X X
XX
X
X
XX
X
X
X
X
BBBBB
X X X X X X
XX
D1
TYP
D1
TYP
D1
TYP
D1
TYP
D1
TYP
X
X
X
X
X
X X X X
X X
X
X X
X
X
X
OSHOSL
D2
Dry Storage-1
1C415-1
Closet-1
1C403B-1
Director's Suite Office
1B469
Mailroom / Breakroom
1B468A
Surgical Service Office
1B462
Eng Closet
1B495
Elec.
Room
1B499
Elect.-1
1C403A-1
Toilet-1
1B570A-1
E.C.
1B465
Corridor-1
1C403-1
Interview Room-1
1B441-1
Chief Of Police-1
1B459-1
Files/Copy-1
1B458-1
Vacant
1B477
PIV
1B467
Service 2-1
1C413-1
Cooler-1
1C414B-1
Food Prep.-1
1C414-1
Dispatch & Fire-1
1B456-1
IRM-1
1B496-1 Hall
1B400E
CWT Conf.
Rm
1B482A
Servery-1
1C411-1
Corridor-1
1C402-1
Corridor-1
1C400-1
Corridor-1
1B570-1
Group Therapy
1-1
1B570C-1
Vocera
1B481
Surgical Service Office
1B498
Vacant
1B479
Vacant
1B478
IRM
1B468
Tele-Health
1B472 EEG Office
1B461
Surgical Service Office
1B473
My Healthy
Vet
1B471
Vacant
1B474
Data-1
1B159-1
Workroom-1
1B563-1
Breakroom-1
1B567-1
EEG Office
1B463SCI Nurse
1B475
EEG Lab
1B466
Hall
1B400C
Waiting-1
1B560-1
Registration-1
1B560A-1
EMS
1B464
CWT
Office
1B480A
Corridor
1B400D
Vacant
1B476
Corridor
1B400F
CWT Open Office
1B236
Dry Storage-1
1C415-1
Closet-1
1C403B-1
Elect.-1
1C403A-1
Toilet-1
1B570A-1
Corridor-1
1C403-1
Chief Of Police-1
1B459-1
Dispatch & Fire-1
1B456-1 CWT Conf.
Rm
1B482A
Data-1
1B159-1
Workroom-1
1B563-1
Breakroom-1
1B567-1
Waiting-1
1B560-1
Registration-1
1B560A-1
CWT
Office
1B480A
Corridor
1B400F
CWT Open Office
1B236
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID ISSUE
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
CLEVELAND, OHIO
DESIGN AND CONSTRUCTION DOCUMENTS AS INSTRUMENTS OF
SERVICE ARE GIVEN IN CONFIDENCE AND REMAIN THE PROPERTY
OF PERSPECTUS ARCHITECTURE. THE USE OF THIS DESIGN AND
THESE CONSTRUCTION DOCUMENTS FOR PURPOSES OTHER
THAN THE SPECIFIC PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN CONSENT OF
PERSPECTUS ARCHITECTURE.
COPYRIGHT © 2021.
1300 East 9th St. Suite 910 Cleveland, Ohio 44114 P. 216.752.1800 F. 216.752.3833 19072
C R e v it L o c a l F ile s \1
F F
H C
F R
S o n n y .T
.N g u y e n L
Q L
.r v t
/8
/2
:1
:2
A
M
ED-102
PARTIAL FIRST FLOOR LIGHTING
DEMO PLAN - PHASE 3 AND 4
RENOVATE AND RECONFIGURE
CLINICAL SERVICES
541‐20‐101
04/09/2021 MPL JRD
# CODED NOTES:
ELECTRICAL DEMOLITION NOTES
D1 ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC. THAT WILL NOT BE REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION SHALL INCLUDE ALL ELECTRICAL ITEMS SHOWN ON THIS PLAN THAT ARE NOT DESIGNATED BY "X", "XN" OR "XRR" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE REMOVED IN ORDER TO
PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED ELECTRICAL SYSTEMS COMPONENTS - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL DEMOLITION
WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.
D2 ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER SHALL
BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.
D3 DASHED WALLS ON PLAN INDICATE EXISTING CONSTRUCTION TO BE REMOVED.
D4 REFER TO ELECTRICAL LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED XB, XRR OR XN, AND REMOVE/BLANK OFF, RELOCATE OR REPLACE
THESE COMPONENTS AS REQUIRED.
D5 MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY TO
ACHIEVE SAME.
D6 THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A TIMELY
MANNER.
N
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL FIRST FLOOR LIGHTING DEMO PLAN -
PHASE 3 1
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL FIRST FLOOR LIGHTING DEMO PLAN -
PHASE 4 2N
REMOVE ALL LIGHTING FIXTURES, LIGHTING CONTROLS, AND ETC. FROM PROJECT AREA UNLESS OTHERWISE NOTED. REMOVE ALL ASSOCIATED CONDUIT AND WIRING COMPLETE TO SOURCE. MAINTAIN
CONTINUITY TO LIGHTING CIRCUITS OUTSIDE OF THE PROJECT SCOPE AREA.
REFER TO DRAWING ED-112 FOR ADDITIONAL INFORMATION AND WORK REQUIREMENTS.
D1
D2
OS
OS
OS
OSR1
R1
R1
R1
N
P
Q
R
T
S
U
39 424140
M
36a
PHASE 5
D1
TYP
XN
XN
D1
TYP
D1
TYPX
DD
DD
B
B
B
D D
E
E
XX
X
X
X
X
X X
X
X X
X X X
X X
X
X X
X XX
X X
X X
X
X
XX
X
X
X X
X X
X
X
X
X
X
X
X
Blood Draw 6
1B473
Blood Draw 5
1B472
Blood Draw 4
1B470
EMS
1B469
Elec
1B462
Corridor
1B466
Blood Draw Waiting
1B460
Interview Room
1B441
Vestibule
1B440
Cubicle Area
1B442
Lt. & Sg. Office
1B446
Corridor
1A400H
X X X
X X X
XX
K
J
J
H
H
H H
H H H
H
H
LF16 LF14-CR
Blood Draw
1B431
Blood Draw
Waiting
1B430
VSO Office
1B418
Stair 11
1S11
VSO Office
1B419
VSO Office
1B417 VSO Office
1B416
VSO Office
1B415
VSO Office
1B414
VSO Office
1B413
Hall
1B412
Escort Services
1B411
Patient Alcove
1B410
Mainstreet
1B400A Mainstreet
1B400B
Tri-C Veterans Edu.
Connection Center
1B420
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID ISSUE
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
CLEVELAND, OHIO
DESIGN AND CONSTRUCTION DOCUMENTS AS INSTRUMENTS OF
SERVICE ARE GIVEN IN CONFIDENCE AND REMAIN THE PROPERTY
OF PERSPECTUS ARCHITECTURE. THE USE OF THIS DESIGN AND
THESE CONSTRUCTION DOCUMENTS FOR PURPOSES OTHER
THAN THE SPECIFIC PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN CONSENT OF
PERSPECTUS ARCHITECTURE.
COPYRIGHT © 2021.
1300 East 9th St. Suite 910 Cleveland, Ohio 44114 P. 216.752.1800 F. 216.752.3833 19072
C R e v it L o c a l F ile s \1
F F
H C
F R
S o n n y .T
.N g u y e n L
Q L
.r v t
/8
/2
:1
:3
A
M
ED-103
PARTIAL FIRST FLOOR LIGHTING
DEMO PLAN - PHASE 5
RENOVATE AND RECONFIGURE
CLINICAL SERVICES
541‐20‐101
04/09/2021 MPL JRD
# CODED NOTES:
ELECTRICAL DEMOLITION NOTES
D1 ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC. THAT WILL NOT BE REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION SHALL INCLUDE ALL ELECTRICAL ITEMS SHOWN ON THIS PLAN THAT ARE NOT DESIGNATED BY "X", "XN" OR "XRR" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE REMOVED IN ORDER TO
PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED ELECTRICAL SYSTEMS COMPONENTS - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL DEMOLITION
WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.
D2 ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER SHALL
BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.
D3 DASHED WALLS ON PLAN INDICATE EXISTING CONSTRUCTION TO BE REMOVED.
D4 REFER TO ELECTRICAL LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED XB, XRR OR XN, AND REMOVE/BLANK OFF, RELOCATE OR REPLACE
THESE COMPONENTS AS REQUIRED.
D5 MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY TO
ACHIEVE SAME.
D6 THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A TIMELY
MANNER.
N
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL FIRST FLOOR LIGHTING DEMO PLAN -
PHASE 5 1
REMOVE ALL LIGHTING FIXTURES, LIGHTING CONTROLS, AND ETC. FROM PROJECT AREA UNLESS OTHERWISE NOTED. REMOVE ALL ASSOCIATED CONDUIT AND WIRING COMPLETE TO SOURCE. MAINTAIN
CONTINUITY TO LIGHTING CIRCUITS OUTSIDE OF THE PROJECT SCOPE AREA.
D1
J
J
J
AA
BB
CC
39 414036a
BB.5
AA.5
35.6
RAD1LNL1
RAD1LNH1
P H
A S
E
PHASE 1
PHASE 1
X X
X
X
X
X X
X
X
X
X
X
X
X
X
X
X
X
X
XX
D1
TYP
XN
XN
27 29 30 32 33 34 35 36
Z
AA
BB
CC
3928a 31 4036a
CC.8
CC.2
BB.5
AA.5
34.6 35.6
CC.5
CC.10
RAD1LNL1
RAD1LNH1
PROJECT SCOPE
X
X
D2
D1
TYP
D1
TYP
D1
TYP
D1
TYP
D1
TYP
X
X
X
X
Passage
1B500B
Office-1
1B588-1
Corridor-1
1B570-1
Group Therapy
1-1
1B570C-1
Workroom-1
1B563-1
Veg.
Cooler-1
1C471-1
Milk & Bread-1
1C472-1
Waiting-1
1B560-1
Registration-1
1B560A-1
Elect.-1
1B550A-1
Read Consult-1
1B516-1
Telecomm-1
1C519-1
Office 6-1
1C517-1
Engineering Room-1
1C521-1
MRI
Scan-1
1B532-1
MRI
Equip-1
1B531-1
Control-1
1B533-1
Dress-1
1B535-1
Elec.-1
1B526-1
Corridor-1
1B541-1
Dress-1
1B536-1
Gowned Waiting-1
1B534-1
Control-1
1B537-1
Staff Toilet-1
1B520-1
Pat Toilet-1
1B522-1
Corridor-1
1B513-1
Waiting-1
1C511-1
Reception Copy/Work
Rm-1
1C513-1
Corridor-1
1B530-1
Ante Room-1
1B540-1
MRI
Equip-1
1B539-1
Corridor-1
1C557-1
Public Toilet-1
1B512-1
Office-1
1B515-1
Corridor-1
1C404-1
Supplies-1
1C515-1
Group Therapy
1-1
1B570C-1
Workroom-1
1B563-1
Veg.
Cooler-1
1C471-1
W.H. General Work Area/Conference
Room
1B589
W.H. Office
1B554 M.H. Office
1B590
W.H.
Conf/Stor/Break/Clean
1B552
W.H.
1B589A
W.H. Exam Room
1B543E
W.H. Exam Room
1B547 W.H. Exam Room
1B549
W.H. Office
1B548
W.H. Work Room
1B551
W.H. Office
1B546
W.H. Tlt.
1B545
W.H. Office
1B544
Corridor
1B543G
W.H. Office
1B543F
W.H. Waiting Room
1B543D
W.H. Office
1B543C
W.H. Office
1B543B
W.H. Conference Room
1B543A
Corridor
1B543G
Office
1B568
Storage
1B566
Tele-Health
1B566A
Toilet
1B567A
Toilet
1B567B
Corridor
1B567C Workroom
1B563A
Office
1B564
Office
1B562
EMS
1B561
Office
1B583
Office
1B585
Toilet
1B570B
Nurse Screening
1B581
Corridor
1B580
Office
1B582
Office
1B584
Case Manager
1B586
TMS Storage
1B587
Office
1B579
Office
1B577
Office
1B576
Office
1B574
Office
1B572
Corridor
1B560B
Corridor
1B570G
Office
1B578
Office
1B575
Exam Room
1B573
Office
1B571
Group Therapy 2
1B570D
W.H. Office
1B553
Office
1B555
Office
1B556
W.H. Office
1B557
W.H. Soiled
1B558
Corridor
1B550
M.H. Office
1B559
Office-1
1B518-1
Read Consult-1
1B516-1
Staff Lounge-1
1B519-1
Clean-1
1B523-1
Soiled-1
1B524-1
Storage-1
1B521-1
Reception-1
1B517-1
Staff Toilet-1
1B520-1
Pat Toilet-1
1B522-1
Corridor-1
1B513-1
Waiting-1
1B511-1
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID ISSUE
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
CLEVELAND, OHIO
DESIGN AND CONSTRUCTION DOCUMENTS AS INSTRUMENTS OF
SERVICE ARE GIVEN IN CONFIDENCE AND REMAIN THE PROPERTY
OF PERSPECTUS ARCHITECTURE. THE USE OF THIS DESIGN AND
THESE CONSTRUCTION DOCUMENTS FOR PURPOSES OTHER
THAN THE SPECIFIC PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN CONSENT OF
PERSPECTUS ARCHITECTURE.
COPYRIGHT © 2021.
1300 East 9th St. Suite 910 Cleveland, Ohio 44114 P. 216.752.1800 F. 216.752.3833 19072
C R e v it L o c a l F ile s \1
F F
H C
F R
S o n n y .T
.N g u y e n L
Q L
.r v t
/8
/2
:1
:4
A
M
ED-111
PARTIAL FIRST FLOOR POWER
DEMO PLAN - PHASE 1 AND 2
RENOVATE AND RECONFIGURE
CLINICAL SERVICES
541‐20‐101
04/09/2021 MPL JRD
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL FIRST FLOOR POWER DEMO PLAN -
PHASE 1 1N
# CODED NOTES:
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL FIRST FLOOR POWER DEMO PLAN -
PHASE 2 2
N
ELECTRICAL DEMOLITION NOTES
D1 ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC. THAT WILL NOT BE REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION SHALL INCLUDE ALL ELECTRICAL ITEMS SHOWN ON THIS PLAN THAT ARE NOT DESIGNATED BY "X", "XN" OR "XRR" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE REMOVED IN ORDER TO
PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED ELECTRICAL SYSTEMS COMPONENTS - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT OF ALL DEMOLITION
WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.
D2 ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER SHALL
BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.
D3 DASHED WALLS ON PLAN INDICATE EXISTING CONSTRUCTION TO BE REMOVED.
D4 REFER TO ELECTRICAL LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED XB, XRR OR XN, AND REMOVE/BLANK OFF, RELOCATE OR REPLACE
THESE COMPONENTS AS REQUIRED.
D5 MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY TO
ACHIEVE SAME.
D6 THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A TIMELY
MANNER.
REMOVE ALL RECEPTACLES, JUNCTION BOXES, AND ETC. FROM PROJECT AREA NOTED UNLESS
OTHERWISE NOTED. REMOVE ALL ASSOCIATED CONDUIT AND WIRING COMPLETE TO SOURCE. MAINTAIN
CONTINUITY TO RECEPTACLE CIRCUITS OUTSIDE OF THE PROJECT SCOPE AREA.
DISCONNECT AND REMOVE EXISTING PANEL AND ALL ASSOCIATED CONDUIT AND WIRING COMPLETE BACK
TO SOURCE. RELOCATE EXISTING ACTIVE LOADS TO PANEL LF13.
D1
D2
J
J
J
JJ
J
J
JJ
J
J
J
J J
J
J J
J
J J
32 33 34 35 36
W
Y
31 36a34.6 35.6
LF14 LF13
X X
X X
PHASE 3
PHASE 3
X X
X
XX X
PP
D1
TYPD1
TYP
X
X
30 32 33 34 35 36
N
P
Q
R
T
W
Y
S
U
31 36a34.6 35.6
D2
OSL OSH
D2
D3
D1
TYP
D1
TYP
D1
TYP
D1
TYP
X
X
X
X X
PP
D1
TYP
X
X
X
X
X X
XX
X
X
X X
X X
X X
X X
X
X
X X
T-DPLF11CR
T-DPLF11 T-LF11LS DPLF11CR
X
LF11CR
HF11-CR
LF11LS
DPLF11CR DPLF11 HF11
RF11CP
HF11-LS
LF13-CR
X X X X X XX
X
X
X
XX
X
XX
X
X
X
X
X
X
LF14 LF13
X X
LE16
Dry Storage-1
1C415-1
Closet-1
1C403B-1
Elect.-1
1C403A-1
Toilet-1
1B570A-1
Corridor-1
1C403-1
Chief Of Police-1
1B459-1
Dispatch & Fire-1
1B456-1
CWT Conf.
Rm
1B482A
Data-1
1B159-1
Workroom-1
1B563-1
Breakroom-1
1B567-1
Waiting-1
1B560-1 Registration-1
1B560A-1
CWT
Office
1B480A
Corridor
1B400F
CWT Open Office
1B236
Dry Storage-1
1C415-1
Closet-1
1C403B-1
Director's Suite Office
1B469
Mailroom / Breakroom
1B468A
Surgical Service Office
1B462
Eng Closet
1B495
Elec.
Room
1B499
Elect.-1
1C403A-1
Toilet-1
1B570A-1
E.C.
1B465
Corridor-1
1C403-1
Interview Room-1
1B441-1
Chief Of Police-1
1B459-1
Files/Copy-1
1B458-1
Vacant
1B477
PIV
1B467
Service 2-1
1C413-1
Cooler-1
1C414B-1
Food Prep.-1
1C414-1
Dispatch & Fire-1
1B456-1
IRM-1
1B496-1
Hall
1B400E
CWT Conf.
Rm
1B482A
Servery-1
1C411-1
Corridor-1
1C402-1
Corridor-1
1C400-1
Corridor-1
1B570-1
Group Therapy
1-1
1B570C-1
Vocera
1B481
Surgical Service Office
1B498
Vacant
1B479
Vacant
1B478 IRM
1B468
Tele-Health
1B472
EEG Office
1B461
Surgical Service Office
1B473
My Healthy
Vet
1B471
Vacant
1B474
Data-1
1B159-1
Workroom-1
1B563-1
Breakroom-1
1B567-1
EEG Office
1B463SCI Nurse
1B475
EEG Lab
1B466
Hall
1B400C
Waiting-1
1B560-1
Registration-1
1B560A-1
EMS
1B464
CWT
Office
1B480A
Corridor
1B400D
Vacant
1B476
Corridor
1B400F CWT Open
Office
1B236
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
FREDRICK, FREDRICK & HELLER
ENGINEERS, INC.
672 EAST ROYALTON ROAD
BROADVIEW HTS., OHIO 44147
TEL. (440) 546-9696
FAX: (440) 546-9699
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID ISSUE
FULLY SPRINKLERED
Louis Stokes Cleveland
VA Medical Center
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
CLEVELAND, OHIO
DESIGN AND CONSTRUCTION DOCUMENTS AS INSTRUMENTS OF
SERVICE ARE GIVEN IN CONFIDENCE AND REMAIN THE PROPERTY
OF PERSPECTUS ARCHITECTURE. THE USE OF THIS DESIGN AND
THESE CONSTRUCTION DOCUMENTS FOR PURPOSES OTHER
THAN THE SPECIFIC PROJECT NAMED HEREIN IS STRICTLY
PROHIBITED WITHOUT THE EXPRESSED WRITTEN CONSENT OF
PERSPECTUS ARCHITECTURE.
COPYRIGHT © 2021.
1300 East 9th St. Suite 910 Cleveland, Ohio 44114 P. 216.752.1800 F. 216.752.3833 19072
C R e v it L o c a l F ile s \1
F F
H C
F R
S o n n y .T
.N g u y e n L
Q L
.r v t
/8
/2
:1
:5
A
M
ED-112
PARTIAL FIRST FLOOR POWER
DEMO PLAN - PHASE 3 AND 4
RENOVATE AND RECONFIGURE
CLINICAL SERVICES
541‐20‐101
04/09/2021 MPL JRD
N
ELECTRICAL DEMOLITION NOTES
D1 ALL…