This document is a detailed set of irrigation system design drawings for the Bay Pines National Cemetery Gravesite Expansion Phase 2 project (Contract Number 830CM3019). The technical drawings, prepared by John Gallup & Associates, LLC for the National Cemetery Administration, provide comprehensive details for five key irrigation system components: (1) Isolation Gate Valve Assembly, (2) Quick Coupling Valve Assembly, (3) Controller Assembly, (4) Remote Control Valve Assembly, and (5) Controller Grounding Detail. The drawings include precise technical specifications for installation, including grounding requirements, valve configurations, wire connections, and recommended materials such as copper-clad grounding rods, concrete valve boxes, and specific wire types. The project is located at 10000 Bay Pines Blvd, St. Petersburg, Florida, with design documents dated April 29, 2024, and involve engineering input from multiple firms including Aqua Engineering Inc. and consultants like WSP.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NATIONAL CEMETERY

ADMINISTRATION

OFFICE OF DESIGN

AND CONSTRUCTION

John Gallup & Associates, LLC 3225 Shallowford Rd NE Marietta, GA 30062 770-321-4040

Atriax Pllc 703 Main Avenue, SW Hickory, NC 28602 (828)315-9962

Gravesite Expansion Phase 2

830CM3019

APRIL 29, 2024

Bay Pines National Cemetery 10000 Bay Pines Blvd, St Petersburg, FL 33708

Environment & Infrastructure Solutions, Inc.

1075 Big Shanty Road, NW Suite 100 Kennesaw, GA 30144

(770) 421-3400

BID DOCUMENTS

CCTJDLWWW.BCEI.US

2840 REMINGTON GREEEN CIR

TALLAHASSEE, FLORIDA 32308

OFFICE 850.297.0440

Aqua Engineering Inc.

375 E. Horsetooth Road, Building 2-202 Fort Collins, CO 80525-3196

LI502

IRRIGATION DETAILS

1 ISOLATION GATE VALVE

ASSEMBLY N.T.S. 2 QUICK COUPLING VALVE

ASSEMBLY N.T.S. 3 CONTROLLER

ASSEMBLY N.T.S.

5 CONTROLLER GROUNDING

DETAIL N.T.S.4 REMOTE CONTROL VALVE

ASSEMBLY N.T.S.

PLAN VIEW

A. IRRIGATION CONTROLLER ASSEMBLY

B. UL LISTED 5/8" X 10' COPPER-CLAD GROUNDING

ROD

C. UL LISTED 4" X 8' COPPER GROUNDING PLATE

D. CONCRETE 9" ROUND VALVE BOX WITH COVER

E. CADWELD CONNECTION: PAIGE ELECTRIC

F. 3" MINIMUM DEPTH OF 3/4" WASHED GRAVEL

G. BRICK (1 OF 4)

H. #6 AWG INSULATED SOLID COPPER WIRE. NO

SHARP BENDS.

I. SPHERE OF INFLUENCE

J. EARTH CONTACT MATERIAL, POWERSET© OR

POWERFILL© DEPENDING ON SOIL CONDITIONS

K. FINISH GRADE

A

C

B

8'

10'

11'

I

I

30" MINIMUM

12"

SECTION VIEW

H

H

H

B

C J

D

G

F

E

NOTES:

1. CONNECT ALL #6 AWG WIRES INSIDE THE

CONTROLLER. CONNECT ONE WIRE TO

THE CONTROLLER GROUND LUG AND

USE A #4 SPLIT BOLT TO CONNECT ALL

WIRES TOGETHER.

2. EARTH CONTACT MATERIAL MUST

COMPLETELY COVER THE WELD JOINT

ON THE GROUND PLATE.

K

053_830CM3019.LI502.0.20240429