S02 523-23-006 VISN 1 RCx Repairs JP MIL.xlsx

XLSX spreadsheet 360 KB Posted

Attached to
B543--523-23-006 RCx Repairs JP Federal contract opportunity
Solicitation number
36C24123B0007
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1

About this file

This document contains details from a retro-commissioning report of a Veterans Affairs medical center. It identifies various equipment and systems across multiple buildings that would benefit from repairs, replacements, control sequence updates or other corrective actions to improve energy efficiency. Issues were found with AHUs, chillers, boilers, pumps and other HVAC equipment. Recommended solutions include implementing nighttime setbacks, releasing local fan controls to the BAS, replacing dampers and valves, updating sequences to prevent simultaneous heating and cooling, and re-commissioning energy recovery systems. Estimated energy savings and project costs are provided for each issue along with simple payback periods generally under ten years.

View the file

Other files for this federal contract opportunity

Other files attached to B543--523-23-006 RCx Repairs JP, newest first.
File Type Posted
S05 - RFI Questions and Answers 523-23-006 RCx Repairs JP.docx DOCX document
36C24123B0007 0002.docx DOCX document
S06 - Bid Opening Conference Line 36C24123B0007.docx DOCX document
S06 - Site Visit Sign In Sheet JP RCx Repairs.pdf PDF
36C24123B0007 0001.docx DOCX document
S02 Shop Drawings Product Data Samples.pdf PDF
S02 Safety Requirements.pdf PDF
S02 SOW 523-23-006 RCx Repairs JP.docx DOCX document
S02 WD MA20230001 16JUNE2023.pdf PDF
S02 General Requirements.pdf PDF
36C24123B0007_1.docx DOCX document
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RCx MIL

Issue No.Survey
DateBuildingLocationArea ServedEquipment
TypeEquipment
NameComponentIssue
DescriptionIssue Type
(from CTS)ResolutionPriorityStatusO&M Comments
----------------------------
761/14/211 - Main HospitalC5-145th Floor Wing C-WingAHUAHU-5C-14-2Coil, HW ReheatTrend data shows supply air temperature consistently rises above 160 Deg F during unoccupied hours. (24-7 Operation)BAS/EMCSUpgrade BAS Schedule and Sequence of Operation. Heating should not be provided at all during unoccupied hours. Replace Sensor.3 - Energy ConservationOpen
791/14/211 - Main HospitalC5-35SPD - DirtyAHUAHU-5C-35Fan, ExhaustSupply and Exhaust fans have VFDs, but are set in-hand locally. EF running at 100% while SF is only running 55%. (VFD Issue)BAS/EMCSRelease in-hand control. Upgrade BAS Sequence of Operations to allow for automatic controls. Coordinate with AHU-1 SPD and AHU-3 (Sub-Basement) to satisfy SPD Requirements.3 - Energy ConservationOpen
8211/2/201 - Main Hospital6B-54B6-54 SuiteAHUAHU-6B-75AHUUnit is approaching the end of useful life. Ductwork insulation has been torn off and the floor is rusted, suggesting coil leaks have previously occurred. Pneuamatics are still used to operate dampers.HVACReplace AHU, ductwork, and provide upgraded BAS graphic.3 - Energy ConservationOpen
871/14/211 - Main HospitalB9-749th Floor B-WingBASAHU-9B-74ShutdownUnit does not turn off when in unocupied mode. According to SOO the unit should turn off when unoccupied. (24-7 Operation)BAS/EMCSUpdate Sequence of Operation to match schedule3 - Energy ConservationOpen
1011/15/211 - Main HospitalB11-65B11-48 SuiteAHUAHU-11-B-65Supply Fan VFDNo pressure or airflow setting for supply fan. SF set by VFD percent set point.BAS/EMCSUpgrade BAS Controls and Setpoint. SF should modulate to meet discharge pressure setpoint.3 - Energy ConservationOpen
1261/15/211 - Main Hospital15th Floor14th Floor B-WingAHUS-09Damper, RAEconomizer damper could not be visually inspected, but is likely stuck at minimum position. Measured OA CFM nearly matches DA CFM. (Failed Damper)HVACReplace Economizer Damper3 - Energy ConservationOpen
1311/11/211 - Main HospitalMech Room EB-95ProstheticsBASAHU-1E ProstheticsCoil, CHWCHW Valve is always open 50%+ unless commanded to close. DAT Setpoint is 65F, but typically hovera around 58-60. When OA Damper commanded to close (OA Temp is below 40F), CHW valve also closes. VAV Reheats maintain Room Setpoint Temperature. (Effective Leak)BAS/EMCSIncrease AHU DAT Setpoint OR Adjust Sequence of Operation so CHW valve is not linked directly to OA Damper.3 - Energy ConservationOpen
1321/18/211 - Main HospitalBD-101B (Above Ceiling)Basement PET Scan (Wing D)AHUAHU-BD-101BAHULobby area was confirmed in staff interview to always be cold, but the rooms with dedicated reheat are 10+ DEG above setpoint when 0% open. System is small, so cooling OA down before reheating is not efficient. (Heating and Cooling)HVACReplace FCUs with Small AHU (heat + cool) OR Adjust Sequence of Operation to prevent Cooling + Reheating.3 - Energy ConservationOpen
14511/2/201 - Main HospitalSub-BasementSPD (2nd Floor D-Wing)AHUAHU-3 SPDFan, ExhaustExhaust fan is sized to pull more air (11,000 CFM) than the supply fans (4000 CFM). Supply Fans running at 100% on BAS but could not povide 4000 CFM setpoint. In the field, Supply Fan VFD is only running at 50%. (VFD Issue)BAS/EMCSUpgrade BAS Sequence of Operations and Points to show VFD correctly. Re-TAB System and Coordinate with AHU-1 SPD and AHU-5C-35 to satisfy SPD Requirements.3 - Energy ConservationOpen
1531/15/217 - Brain StorageRoofBuilding 7AHUACU-1Isolation DamperSupply fan isolation dampers do not close when linked one of the fan wall's supply fans shuts down. This causes the system to short circuit. (Failed Damper)BAS/EMCSUpgrade Sequence of Operation. Isolation Dampers should close when a fan shuts down.3 - Energy ConservationOpen
1791/18/211D - Radiation Therapy2nd Floor PenthouseOfficesAHUAHU-Radiation TherapyScheduleSystem is running 24-7, even when space is not occupied.BAS/EMCSImplement Nighttime setback3 - Energy ConservationOpen
1851/18/211A - Research3rd Floor Mech RoomOffices + Animal roomsAHUAC-04Energy RecoveryMissing control sequence for Energy Recovery. Cannot see Exhaust side of energy recovery on graphic. Energy Recovery confirmed to not be used since 2016 RCx. Required for 100% OA Systems. (ERC Issue)BAS/EMCSRe-Implement Energy Recovery Sequence.3 - Energy ConservationOpen

O&M comments $ 170,500 6,819 $ 81,782

Issue No.Survey
DateBuildingLocationArea ServedEquipment
TypeEquipment
NameComponentIssue
DescriptionIssue Type
(from CTS)ResolutionPriorityStatusEstimated

Implementation Cost ($) Electric Demand Savings (Peak kW) Annual Electric Energy Savings (kWh/yr) Annual Fuel Savings (MMBTU/yr) Energy Savings MMBtu Annual Energy Savings ($) Return On Investment (%) Simple Payback

(years)Comments
--------------------------------------------
411/13/211 - Main HospitalB4-734th Floor B-WingAHUAHU-4B-73Unnocupied modeunit does not turn off when in unocupied mode. According to SOO the unit should turn off when unoccupied (24-7 Operation)BAS/EMCSUpdate Sequence of Operation to match schedule3 - Energy ConservationOpen$ 500.000%N/A6,354.00265.00286.68$ 1,264.56AEM in progress of implementing schedules
311/13/211 - Main HospitalB4-464th Floor B-WingAHUAHU-4B-46Unnocupied modeunit does not turn off when in unocupied mode. According to SOO the unit should turn off when unoccupied. (24-7 Operation)BAS/EMCSUpdate Sequence of Operation to match schedule3 - Energy ConservationOpen$ 500.000%N/A6,353.00706.00727.68$ 4,833.70AEM in progress of implementing schedules
1601/15/219 - Admin/ResearchBasementHallways and LobbyHeating SystemMAU-1ControlsBoilers, Pumps, HW system setup to provide full heating 24/7, even when the building is unoccupied. Applies to MAU, all Fan Coil Units and Radiators. Most of Building is unoccupied due to Pandemic.BAS/EMCSImplement Nighttime setback3 - Energy ConservationOpen$ 2,000.001%N/A2,739.00249.00258.35$ 5,727.00cannot shut off heat during off hours
2157/28/211F - Ambulatory Care AdditionChiller Plant ACAWing F ACAChilled Water SystemChillerBASCooling Tower 2 controller is broken, preventing low speed mode. Maintenance has re-wired the control panel to force CT-2 to operate at full speed, while the BAS still shows low speed operation. (Chiller Plant Upgrade)BAS/EMCSReplace Cooling Tower 2 controller3 - Energy ConservationOpen$ 2,000.001%N/A14,266.00- 048.68$ 1,412.00Controller has been replaced and is fully functional
1341/18/211 - Main HospitalBD-101G (Above Ceiling)Basement PET Scan (Wing D)BASAHU-BD-101GFan, ReturnBAS graphic shows two supply fans and one exhaust fan, and is missing an economizer damper. Incoporporate return fan into control.BAS/EMCSIf not replaced, Re-Commission system. Upgrade BAS Graphics and Control Points.3 - Energy ConservationOpen$ 10,000.006%N/A- 035.0035.00$ 261.38Dampers our in fixed position for air changes only close if freeze stat is activated
1651/18/211F - Ambulatory Care AdditionPenthouseOperating RoomsAHUAHU-1Energy RecoverySetpoint is 40F even though DAT is 55F, so it is underutilized (Glycol Temp is 70F, 100% Exhaust at 70-75F). AHU is large 100% OA (40,000 CFM). (ERC Issue)BAS/EMCSUpgrade Sequence of Operation or modify setpoint. ERC should be active most of the time that heating is required.3 - Energy ConservationOpen$ 2,000.001%N/A814.00354.60357.38$ 7,040.35Energy Recovery was fully functional, so only setpoint changes should be required
1631/18/211F - Ambulatory Care AdditionPenthouseOperating RoomsAHUAHU-1HumidifierHumidifier has a minor steam leak (Effective Leak)HVACRe-seal pipe or replace valve.3 - Energy ConservationOpen$ 500.000%N/A- 0327.00327.00$ 3,364.00Humidifier is suoopsed to let a little steam by so line does not crack when steam is fed into line operating correctly
1851/18/211A - Research3rd Floor Mech RoomOffices + Animal roomsAHUAC-04Energy RecoveryMissing control sequence for Energy Recovery. Cannot see Exhaust side of energy recovery on graphic. Energy Recovery confirmed to not be used since 2016 RCx. Required for 100% OA Systems. (ERC Issue)BAS/EMCSRe-Implement Energy Recovery Sequence.3 - Energy ConservationOpen$ 2,000.001%N/A7,089.001,335.001,359.19$ 13,520.33Issue from 2016
1121/20/211 - Main HospitalB12-6711th Floor B-WingAHUAHU-12B-67Schedule24-7 Operation, zone not occupied overnightBAS/EMCSImplement Nighttime setback3 - Energy ConservationOpen$ 500.000%N/A4,040.00350.00363.79$ 1,982.86night setback is functional no action needed
14411/2/201 - Main HospitalSub-BasementSPD (2nd Floor D-Wing)AHUAHU-3 SPDCoil, Steam Preheat1/5 Steam Valve is leaking. 4/5 Steam Valve is okay. (Effective Leak)CHW, HW, and
Steam Distribution SystemsReplace Steam Valve3 - Energy ConservationOpen$ 2,500.001%N/A- 017.0017.00$ 294.00Repaired in house
8111/2/201 - Main Hospital6B-54B6-54 SuiteBASAHU-6B-75Coil, HW ReheatTrend data shows supply air temperature consistently rises above 160 Deg F during unoccupied hours. CHW Valve open 100% during investigation, possible that HW Valve is stuck open and CHW counteracts it until after hours, when the CHW valves closes. (24-7 Operation)BAS/EMCSUpgrade BAS Schedule and Sequence of Operation. Heating should not be provided at all during unoccupied hours. Replace Sensor.3 - Energy ConservationOpen$ 2,000.001%N/A- 0302.00302.00$ 2,270.06steam cannot be shut off during off hours steam coil would freeze
2087/28/211A - ResearchChiller Plant 1Building 1Chilled Water SystemChiller Plant 1Heat ExchangerChiller Plant 1 Heat Exchanger has been abandoned for years. No capability for free cooling from the cooling tower condensing water. HX not visible on BAS. (Chiller Plant Upgrade)HVACReplace Heat Exchanger. Upgrade Chiller Plant sequence to include HX and add monitoring to BAS.3 - Energy ConservationOpen$ 30,000.0018%N/A132,175.00- 0451.00$ 12,504.00This calculation assumes Chiller plant 1 is operating when free cooling is available. May be inaccurate if CP-2 is used most of the time.
931/14/211 - Main HospitalCeiling/ D9-130(Oncology) 9th Floor D-WingAHUAHU-9D-130VFDNo VFD indicated on the BAS for the Supply Fan, but fan has a VFD in the field. (VFD Issue)BAS/EMCSUpgrade BAS Graphics and Control Sequence to modulate the fan. Povide Pressure Sensor and Setpoint for control.3 - Energy ConservationOpen$ 3,000.002%N/A8,702.002.0031.69$ 874.36Unit balanced by vav locally
291/19/211 - Main HospitalRoom 3E-1103rd Floor Wing DAHUU-10AHU24-7 Operation, zone not occupied overnightBAS/EMCSImplement Nighttime setback3 - Energy ConservationOpen$ 500.000%N/A9,647.00232.00264.92$ 1,788.57unit is in process of replacment
801/14/211 - Main HospitalC5-35SPD - DirtyAHUAHU-5C-35ScheduleArea is not occupied overnight, but DAT Setpoint is maintained. (24-7 Operation)BAS/EMCSImplement Nighttime setback3 - Energy ConservationOpen$ 500.000%N/A- 0115.00115.00$ 546.19Unit serves sterile storage temps and humidity must be maintained 24-7
1531/15/217 - Brain StorageRoofBuilding 7AHUACU-1Isolation DamperSupply fan isolation dampers do not close when linked one of the fan wall's supply fans shuts down. This causes the system to short circuit. (Failed Damper)BAS/EMCSUpgrade Sequence of Operation. Isolation Dampers should close when a fan shuts down.3 - Energy ConservationOpen$ 500.000%N/A4,131.0034.0048.10$ 759.00
871/14/211 - Main HospitalB9-749th Floor B-WingBASAHU-9B-74ShutdownUnit does not turn off when in unocupied mode. According to SOO the unit should turn off when unoccupied. (24-7 Operation)BAS/EMCSUpdate Sequence of Operation to match schedule3 - Energy ConservationOpen$ 500.000%N/A8,254.0062.0090.16$ 1,081.52
1311/11/211 - Main HospitalMech Room EB-95ProstheticsBASAHU-1E ProstheticsCoil, CHWCHW Valve is always open 50%+ unless commanded to close. DAT Setpoint is 65F, but typically hovera around 58-60. When OA Damper commanded to close (OA Temp is below 40F), CHW valve also closes. VAV Reheats maintain Room Setpoint Temperature. (Effective Leak)BAS/EMCSIncrease AHU DAT Setpoint OR Adjust Sequence of Operation so CHW valve is not linked directly to OA Damper.3 - Energy ConservationOpen$ 500.000%N/A- 0268.00268.00$ 2,011.11
1791/18/211D - Radiation Therapy2nd Floor PenthouseOfficesAHUAHU-Radiation TherapyScheduleSystem is running 24-7, even when space is not occupied.BAS/EMCSImplement Nighttime setback3 - Energy ConservationOpen$ 500.000%N/A5,239.00125.00142.88$ 1,088.16
1551/19/219 - Admin/ResearchBasementHallways and LobbyHeating SystemBoiler 1 & 2PumpsPump 1 is leaking (Effective Leak)HVACRepair Leak3 - Energy ConservationOpen$ 1,000.001%N/A- 057.0057.00$ 497.00
1011/15/211 - Main HospitalB11-65B11-48 SuiteAHUAHU-11-B-65Supply Fan VFDNo pressure or airflow setting for supply fan. SF set by VFD percent set point.BAS/EMCSUpgrade BAS Controls and Setpoint. SF should modulate to meet discharge pressure setpoint.3 - Energy ConservationOpen$ 2,000.001%N/A2,140.00- 07.30$ 211.85
761/14/211 - Main HospitalC5-145th Floor Wing C-WingAHUAHU-5C-14-2Coil, HW ReheatTrend data shows supply air temperature consistently rises above 160 Deg F during unoccupied hours. (24-7 Operation)BAS/EMCSUpgrade BAS Schedule and Sequence of Operation. Heating should not be provided at all during unoccupied hours. Replace Sensor.3 - Energy ConservationOpen$ 2,000.001%N/A- 0229.00229.00$ 1,722.00
791/14/211 - Main HospitalC5-35SPD - DirtyAHUAHU-5C-35Fan, ExhaustSupply and Exhaust fans have VFDs, but are set in-hand locally. EF running at 100% while SF is only running 55%. (VFD Issue)BAS/EMCSRelease in-hand control. Upgrade BAS Sequence of Operations to allow for automatic controls. Coordinate with AHU-1 SPD and AHU-3 (Sub-Basement) to satisfy SPD Requirements.3 - Energy ConservationOpen$ 5,000.003%N/A20,083.00- 068.53$ 2,346.00
14511/2/201 - Main HospitalSub-BasementSPD (2nd Floor D-Wing)AHUAHU-3 SPDFan, ExhaustExhaust fan is sized to pull more air (11,000 CFM) than the supply fans (4000 CFM). Supply Fans running at 100% on BAS but could not povide 4000 CFM setpoint. In the field, Supply Fan VFD is only running at 50%. (VFD Issue)BAS/EMCSUpgrade BAS Sequence of Operations and Points to show VFD correctly. Re-TAB System and Coordinate with AHU-1 SPD and AHU-5C-35 to satisfy SPD Requirements.3 - Energy ConservationOpen$ 10,000.006%N/A92,062.0032.80346.93$ 9,472.00
1261/15/211 - Main Hospital15th Floor14th Floor B-WingAHUS-09Damper, RAEconomizer damper could not be visually inspected, but is likely stuck at minimum position. Measured OA CFM nearly matches DA CFM. (Failed Damper)HVACReplace Economizer Damper3 - Energy ConservationOpen$ 10,000.006%N/A- 087.0087.00$ 654.12
1321/18/211 - Main HospitalBD-101B (Above Ceiling)Basement PET Scan (Wing D)AHUAHU-BD-101BAHULobby area was confirmed in staff interview to always be cold, but the rooms with dedicated reheat are 10+ DEG above setpoint when 0% open. System is small, so cooling OA down before reheating is not efficient. (Heating and Cooling)HVACReplace FCUs with Small AHU (heat + cool) OR Adjust Sequence of Operation to prevent Cooling + Reheating.3 - Energy ConservationOpen$ 30,000.0018%N/A- 0464.00464.00$ 3,480.00
8211/2/201 - Main Hospital6B-54B6-54 SuiteAHUAHU-6B-75AHUUnit is approaching the end of useful life. Ductwork insulation has been torn off and the floor is rusted, suggesting coil leaks have previously occurred. Pneuamatics are still used to operate dampers.HVACReplace AHU, ductwork, and provide upgraded BAS graphic.3 - Energy ConservationOpen$ 50,000.0029%N/A7,479.0039.0064.52$ 776.00

Energy Summary

Energy Savings Summary
Issue IdentifiedRecommended Corrective ActionElectric Demand Savings (Peak kW)Annual Electric Energy Savings (kWh/yr)Annual Fuel Savings (MMBTU/yr)Annual Energy Savings ($)Estimated Implementation Cost ($)Anticipated Project Life (Years)Return On Investment (%)Simple Payback (years)
AHU-SPD-1 and AHU-3 SPD serve the same space, but there is no indication that controls are operating together.Re-Commission AHU-SPD-1 together with AHU-3 (in sub-basement) and combine graphics.N/A0.00115.00$ 546.19$ 500.0010.001092.38%0.92
AHU/RTU lacks a nighttime setback schedule and would benefit from it.Program set back schedule at the BAS. Valve replacement may be required if schedule is implemented.N/A34648.002261.00$ 15,489.46$ 7,000.0010.002212.78%0.45
Supply and Return fans are equipped with VFDs, but are in hand or not visible through BAS.Release in-hand control. Upgrade BAS Sequence of Operations to allow for automatic controls.N/A120847.0034.80$ 12,692.36$ 18,000.005.00352.57%1.42
AHU is approaching the end of useful life.Replace AHU, supporting equipment, and provide upgraded BAS graphic.N/A7479.0039.00$ 776.00$ 50,000.0030.0046.56%64.43
Economizer or other damper has failed and no longer opens/closes.Replace Failed DampersN/A4131.00121.00$ 1,413.12$ 10,500.0010.00134.58%7.43
HW or CHW is either visibly leaking to the floor or leaking through to heat/cool air when valve is closed.Replace Failed Valves and repair leaksN/A0.00669.00$ 6,166.11$ 4,500.005.00685.12%0.73
Unit experiences Simultaneous heating and coolingUpdate the SOO to prevent simultaneous heating and cooling. Replace window AC units and radiators heating with a centralized system.N/A0.00464.00$ 3,480.00$ 30,000.0010.00116.00%8.62
Energy Recovery is not utilized or underutilized. Issues are tracked for large AHUs that require Energy RecoveryRe-Implement Energy Recovery Sequence. ERC should be active most of the time that heating is required.N/A7903.001689.60$ 20,560.68$ 4,000.0010.005140.17%0.19
Chiller Plant 1 Heat Exchanger has been abandoned for years. No capability for free cooling from the cooling tower condensing water. Cooling Tower 2 controller is broken, preventing low speed mode.Replace Controllers and provide new Heat Exchanger sized correctly for Chiller Plant 1N/A146441.000.00$ 13,916.00$ 32,000.0010.00434.88%2.30

Drop Lists

"Drop List" InstructionsBuildingsStatusRepairPriorityEquipment TypeComponentsSub-Components
Building List1 - Main HospitalOpenSimple Repair1 - Health & SafetyAHUEquipment TypeAHUBASChilled Water SystemHeating SystemExhaust FanEquipment TypeAHUBASChilled Water SystemHeating System
When starting a new project, add the building IDs to the Building list. The dropdown list should automatically adjust in size to encompass all the information.1A - ResearchResolvedMinor Repair2 - VA Guideline ConformanceBASComponentsAHUAHUChillerBoilerExhaust FanComponentAHUCoilDamperEnclosureFanFilterPerformanceSafetyScheduleSensor_AFMSSensor_HumiditySensor_PressureSensor_TemperatureUnclassifiedAHUChillerDamperEconomizerFanSafetySensorSetpointShutdownValveVAVUnclassifiedChillerCooling TowerPipingPumpValveUnclassifiedBoilerHeat ExchangerPipingPump, HWValve
1B - MRIOther, see commentsMajor Repair3 - Energy ConservationChilled Water SystemCoil, CHWChillerCooling TowerHeat ExchangerUnclassifedSub-ComponentsGeneralCoilDamperAccess DoorBeltPre FilterCoolingFreeze StatScheduleDischarge AirflowDischarge RHDownstream SPGeneralUnclassifiedSchedulingSchedulingGUIGUIGUIGUIGUIGUIGUIGUISpace TempUnclassifiedChillerCooling TowerPipingPumpValveUnclassifiedBoilerHeat ExchangerPipingInsulationValve
1D - Radiation TherapyN/AN/A4 - Facility ImprovementSteam SystemCoil, Energy RecoveryDamper, EAPipingPipingUnclassifiedControl PanelActuatorDrain PanBelt_GuardFinal FilterHeatingHigh StaticReturn AirflowOutside RHFan SPDATControl SystemUnclassifiedTrendingProgrammingProgrammingProgrammingTrendingProgrammingProgrammingProgrammingUnclassifiedBasinInsulationMotorActuatorCondensate Return PercentInsulationInsulationPumpActuator
1E - Cryogenics ResearchN/AHeat ExchangerCoil, HumidifierDamper, Face/BypassPump, CondensorPump, HWPipingControl PanelExhaust DuctInlet Guide VanesUnclassifiedPneumaticsUnclassifiedUnclassifiedReturn RHFilter DPMATUnclassifiedUnclassifiedTrendingTrendingTrendingUnclassifiedTrendingTrendingTrendingFanGate ValveVFDPipingCondensate Return TemperaturePipingGate ValveMotorPiping
1F - Ambulatory Care AdditionHeating SystemCoil, HW PreheatDamper, MAX OAPump, Primary CHWValvePneumatic LineLinkageFan HousingIsolator CanvasOutside AirflowUnclassifiedUnclassifiedOATUnclassifiedUnclassifiedUnclassifiedUnclassifiedUnclassifiedUnclassifiedMediaSteam TrapUnclassifiedUnclassifiedFlue Gas TemperatureValveSteam TrapVFDInsulation
Status, Repair, & Priority Lists2 - Huntington HouseExhaust FanCoil, HW ReheatDamper, MIN OAPump, Secondary CHWUnclassifiedValvePneumatic LineIsolator CanvasMotorReturn AirflowPHTMotorUnclassifiedO2 PercentageUnclassifiedUnclassifiedUnclassifiedUnclassified
These lists should not need to be updated, but if they are, they will automatically adjust in size to encompass all the information.4 - SAARPTCoil, Steam PreheatDamper, Mixed AirValve, BypassUnclassifiedUnclassifiedReturn DuctTABSupply AirflowRATVFDSteam Pressure
7 - Brain StorageCoil, Steam ReheatDamper, OAValve, IsolationSupply Air DuctVFDUnclassifiedUnclassifiedUnclassifiedUnclassified
9 - Admin/ResearchDamper, EADamper, RAValve, DrainUnclassifiedBAS
CHWP 2 - Chilled Water PlantDamper, Face/BypassDamper, SmokeUnclassifiedUnclassified
Equipment Type ListDamper, MAX OAEconomizer
The Equipment Type list should not need to be updated, but if it is then the size of the named list will need to be adjusted under List Manager to encompass all of the new information. The name in List Manager is "EquipmentType". Additionally, If an Equipment Type is added or removed, be sure to account for the change in the Component, Sub-Component, and Defect Lists.Damper, MIN OAFan, Exhaust
Damper, OAFan, Return
Damper, RAFan, Supply
Damper, SmokeSafety, Freeze-stat
EnclosureSafety, High Static
Fan, ExhaustSafety, Low Static
Fan, ReturnSensor, DAT
Fan, SupplySensor, Discharge Airflow
FilterSensor, Discharge RH
PerformanceSensor, Downstream SP
Component ListsSafety AlarmSensor, Enthalpy
If a component needs to be added to the Component List, be sure to adjust the size of the list in the List Manager. The Component lists are named after the first word of the Equipment Type they're associated with (e.g. The Chilled Water System components are in the named list "Chilled"). If a component is added or removed, be sure to account for the change in the Sub-Component and Defect Lists.ScheduleSensor, Filter DP
Sensor_AFMSSensor, MAT
Sensor_HumiditySensor, OAT
Sensor_PressureSensor, Outside Air RH
Sensor_TemperatureSensor, RAT
UnclassifiedSensor, Return Airflow
Sensor, Return RH
Sensor, Temperature
Setpoint, DAT
Setpoint, Discharge Airflow
Sub-Component ListsSetpoint, Discharge RH
If a sub-component needs to be added to the Sub-Component List, be sure to adjust the size of the list in the List Manager. The Sub-Component lists are named after the first word of the Equipment Type they're associated with, concatenated with the first word of the Component they're associated with (e.g. The Cooling Tower sub-components are in the named list "ChilledCooling"). If a sub-component is added or removed, be sure to account for the change in the Component and Defect Lists.Setpoint, Downstream SP
Setpoint, Filter DP
Setpoint, MAT
Setpoint, OAT
Setpoint, RAT
Setpoint, Return Airflow
Setpoint, Return RH
Setpoint, Temperature
Shutdown
Valve, CHW
Valve, Energy Recovery
Valve, Humidifier
Valve, HW Preheat
Defect ListsValve, HW Reheat
If a defect needs to be added to the Defect List, be sure to adjust the size of the list in the List Manager. The Defect lists are named after the first word of the Component Type they're associated with, concatenated with the whole Sub-Component they're associated with, substituting any spaces for undescores (e.g. The Access Door defects are in the named list "EnclosureAccess_Door").Valve, Steam Preheat
Valve, Steam Reheat
VAV
Unclassified

This is the start of the file's text. The full file is on GovTribe.