RTS-Conformed-Vol3-dwgs.pdf

PDF 25 MB Posted

Attached to
Solar Canopy for Employee Parking Lot
Solicitation number
RTSX-260018-DS
Issued by
Alachua County, Graceville City, Florida

About this file

This is a conformed drawing set for the RTS Bus Fleet Maintenance & Operations Facility in Gainesville, Florida, prepared by Moses & Associates architects and engineers for the City of Gainesville. The project encompasses comprehensive mechanical, plumbing, electrical, telecommunications, and fire protection systems across five buildings: a maintenance facility with multiple levels and specialized bays, a service building housing chiller equipment, a fueling station, a bus wash building, and an administrative/operations building. The drawings detail HVAC systems including air handling units, variable air volume (VAV) terminal units, boilers, chillers, and exhaust fans; plumbing systems for sanitary waste and water distribution; electrical power distribution, lighting, fire alarm, and audio/visual systems; telecommunications infrastructure including backbone cabling and device outlets; and fire protection sprinkler systems. The document set consists of three volumes of conformed (final) drawings dated March 29, 2013, organized by building subsection and system type, with detailed schedules for equipment specifications, control sequences, and installation requirements.

The technical specifications require all equipment and materials to meet "Buy America" requirements and compliance with the 2010 Florida Building Code and associated standards including NFPA, ASHRAE, and UL requirements. Key mechanical systems include redundant 1,500 MBH natural gas boilers with 120 GPM heating hot water pumps, a 100-ton air-cooled chiller with redundant chilled water pumps, multiple packaged heat pump units, and an extensive network of variable frequency drives and direct digital controls integrated through a Building Automation System (BAS) using BACnet/MSTP protocol. The administrative/operations building features two custom air handling units with variable speed drives, demand-based ventilation with CO2 sensors, and comprehensive measurement and verification capabilities for tracking energy consumption across HVAC, lighting, and process loads. Telecommunications infrastructure includes redundant backbone cabling, fiber optic and copper pathways, server room equipment racks with multiple carriers (GRUCOM, Public Works, Cox, AT&T), and extensive camera, wireless access point, and access control system provisions throughout the facility complex.

View the file

Other files

Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRAFTED BY:

ARCHITECT'S PROJECT NO.:

DATE:

REVISION DATES:

PLANS CHECKED BY:

DATE CHECKED:

PHONE: FAX:

(352) 372-1378 (352) 378-1281

GAINESVILLE FLORIDA

5700 SW 34TH STREET SUITE 1307

32608

AA 0002486

for

A R C H I T E C T S

GENERAL:

Gainesville, Florida

G0.13

RTS BUS

FLEET

MAINTENANCE

& OPERATIONS

FACILITY

City of Gainesville

CONFORMED

DOCUMENTS

JLR

11046

MA

COVER SHEET - VOLUME 2

CONTENTS OF SET, PROJECT LOCATION

MAP, & APPLICABLE CODES

29 March 2013

RTS Bus Fleet Maintenance &

Operations Facility

Gainesville, Florida for the City of Gainesville

MECHANICAL

PLUMBING

G0.13 COVER SHEET - VOLUME 3:

CONTENTS OF SET

CONTENTS OF SET

GENERAL

Drawing Volume 3 of 3

SUB-SET 0 - GENERAL

0P0.00 LEGEND, ABBREVIATIONS & SCHEDULES

0P1.00 PLUMBING SITE PLAN

SUB-SET 1 - MAINTENANCE BUILDING

1P1.10 MAINTENANCE FACILITY PLAN - LEVEL 1 UNDERFLOOR CORE

1P1.11 MAINTENANCE FACILITY PLAN - LEVEL 1 UNDERFLOOR SOUTH

BAYS

1P1.12 MAINTENANCE FACILITY PLAN - LEVEL 1 UNDERFLOOR NORTH

BAYS

1P1.13 MAINTENANCE FACILITY PLAN - LEVEL 1 CORE

1P1.14 MAINTENANCE FACILITY PLAN - LEVEL 1 SOUTH BAYS

1P1.15 MAINTENANCE FACILITY PLAN - LEVEL 1 NORTH BAYS

1P1.16 MAINTENANCE FACILITY SECOND FLOOR & ROOF PLAN

1P1.20 MAINTENANCE FACILITY ENLARGED PLAN & SANITARY VENT RISER

1P1.41 MAINTENANCE FACILITY DETAILS & SCHEDULES

1P1.42 MAINTENANCE FACILITY DETAILS & SCHEDULES

SUB-SET 2 - SERVICE BUILDING

2P1.11 SERVICE BUILDING PLAN

SUB-SET 3 - FUELING BUILDING

3P1.11 FUELING STATION PLAN

3P1.21 ENLARGED FUELING STATION PLAN, RISERS, AND DETAILS

SUB-SET 4 - BUS WASH BUILDING

4P1.11 BUS WASH PLANS

SUB-SET 5 - ADMINISTRATIVE/OPERATIONS BUILDING

5P1.10 UNDERFLOOR PLAN

5P1.11 FIRST FLOOR PLAN - SANITARY WASTE & VENT

5P1.12 SECOND FLOOR PLAN - SANITARY WASTE & VENT

5P1.13 ROOF PLAN

5P1.21 FIRST FLOOR PLAN - WATER

5P1.22 SECOND FLOOR PLAN - WATER

5P1.31 SANITARY, WASTE, AND VENT RISER DIAGRAM

TELECOMMUNICATIONS

ELECTRICAL

FIRE PROTECTION

SUB-SET 0 - GENERAL

0F0.00 LEGEND, NOTES, AND DETAILS

0F1.00 FIRE PROTECTION SITE PLAN

SUB-SET 1 - MAINTENANCE BUILDING

1F1.10 MAINTENANCE FACILITIES PLAN - LEVEL 1 CORE

1F1.11 MAINTENANCE FACILITIES PLAN - LEVEL 1 SOUTH BAYS

1F1.12 MAINTENANCE FACILITIES PLAN - LEVEL 1 NORTH BAYS

1F2.00 MAINTENANCE FACILITIES PLAN - LEVEL 2 OVERALL PLAN

SUB-SET 0 - GENERAL

0E0.00 ELECTRICAL LEGEND

0E1.00 ELECTRICAL SITE PLAN

0E1.01 ELECTRICAL SITE PLAN

0E1.02 ENLARGED SITE PLAN

0E2.01 SINGLE LINE DIAGRAM

0E3.01 DETAILS

0E3.02 DETAILS

0E3.03 DETAILS

0E3.04 DETAILS

0E3.05 DETAILS

0E3.06 DETAILS

0E3.07 AUDIO/VISUAL DIAGRAMS

0E3.08 AUDIO/VISUAL DIAGRAMS

0E3.09 AUDIO/VISUAL DIAGRAMS

0E3.10 AUDIO/VISUAL DIAGRAMS

0E3.11 AUDIO/VISUAL DIAGRAMS

0E4.01 LIGHTING FIXTURE SCHEDULES

0E4.02 SCHEDULES

0E4.03 SCHEDULES

0E4.04 MAINTENANCE BLDG PANELBOARD SCHEDULES

0E4.05 MAINTENANCE BLDG PANELBOARD SCHEDULES

0E4.06 MAINTENANCE BLDG PANELBOARD SCHEDULES

0E4.07 MAINTENANCE BLDG PANELBOARD SCHEDULES

0E4.08 MAINTENANCE BLDG PANELBOARD SCHEDULES

0E4.09 GENERATOR HOUSING PANELBOARD SCHEDULES

0E4.10 FUELING STATION PANELBOARD SCHEDULES

0E4.11 BUS WASH PANELBOARD SCHEDULES

0E4.12 ADMINISTRATIVE BLDG PANELBOARD SCHEDULES

0E4.13 ADMINISTRATIVE BLDG PANELBOARD SCHEDULES

0E4.14 ADMINISTRATIVE BLDG PANELBOARD SCHEDULES

SUB-SET 1 - MAINTENANCE BUILDING

1E1.10 POWER LEVEL 1 CORE

1E1.11 POWER LEVEL 1 SOUTH BAYS

1E1.12 POWER LEVEL 1 NORTH BAYS

1E1.13 POWER LEVEL 2 CORE

1E1.20 MECHANICAL POWER LEVEL 1 CORE

1E1.21 MECHANICAL POWER LEVEL 1 SOUTH BAYS

1E1.22 MECHANICAL POWER LEVEL 1 NORTH BAYS

1E1.23 MECHANICAL POWER LEVEL 2 CORE

1E1.24 MECHANICAL POWER - ROOF CORE

1E1.25 MECHANICAL POWER - ROOF SOUTH BAYS

1E1.26 MECHANICAL POWER - ROOF NORTH BAYS

1E1.30 LIGHTING LEVEL 1 CORE

1E1.31 LIGHTING LEVEL 1 SOUTH BAYS

1E1.32 LIGHTING LEVEL 1 NORTH BAYS

1E1.33 LIGHTING LEVEL 2 CORE

1E1.34 LIGHTING LEVEL 2 SOUTH BAYS

1E1.35 LIGHTING LEVEL 2 NORTH BAYS

1E1.40 FIRE ALARM LEVEL 1 CORE

1E1.41 FIRE ALARM LEVEL 1 SOUTH BAYS

1E1.42 FIRE ALARM LEVEL 1 NORTH BAYS

1E1.43 FIRE ALARM LEVEL 2 CORE

1E1.50 SYSTEMS LEVEL 1 CORE

1E1.51 SYSTEMS LEVEL 1 SOUTH BAYS

1E1.52 SYSTEMS LEVEL 1 NORTH BAYS

1E1.53 SYSTEMS LEVEL 2 CORE

1E1.61 LIGHTNING PROTECTION

SUB-SET 0 - GENERAL

0T0.00 TELECOMMUNICATIONS LEGEND

0T2.01 VOICE RISER DIAGRAM

0T2.02 VIDEO RISER DIAGRAM

0T3.01 DETAILS

0T3.02 DETAILS

SUB-SET 1 - MAINTENANCE BUILDING

1T1.10 TELECOMMUNICATIONS LEVEL 1 CORE

1T1.11 TELECOMMUNICATIONS LEVEL 1 SOUTH BAYS

1T1.12 TELECOMMUNICATIONS LEVEL 1 NORTH BAYS

1T1.13 TELECOMMUNICATIONS LEVEL 2 CORE

1T1.14 TELECOMMUNICATIONS LEVEL 2 SOUTH BAYS

1T1.15 TELECOMMUNICATIONS LEVEL 2 NORTH BAYS

SUB-SET 2 - SERVICE BUILDING

2T1.11 - SERVICE BUILDING PLAN

SUB-SET 3 - FUELING BUILDING

3T1.11 FUELING STATION PLAN

SUB-SET 4 - BUS WASH BUILDING

4T1.11 BUS WASH PLAN

SUB-SET 5 - ADMINISTRATIVE OPERATIONS BUILDING

5T1.11 FIRST FLOOR PLAN

5T1.12 SECOND FLOOR PLAN

SUB-SET 0 - GENERAL

0M0.11 MECHANICAL LEGEND & DETAILS

0M0.21 MECHANICAL SCHEDULES

0M0.31 MECHANICAL DETAILS

0M0.41 MECHANICAL CONTROLS

0M0.42 MECHANICAL CONTROLS

0M0.43 MECHANICAL CONTROLS

SUB-SET 1 - MAINTENANCE BUILDING

1M1.11 LEVEL 1 PLAN - CORE

1M1.12 LEVEL 1 PLAN - SOUTH BAYS

1M1.13 LEVEL 1 PLAN - NORTH BAYS

1M2.11 LEVEL 2 PLAN - CORE

1M2.12 LEVEL 2 PLAN - SOUTH BAYS

1M2.13 LEVEL 2 PLAN - NORTH BAYS

1M3.11 ROOF PLAN - CORE

1M3.12 ROOF PLAN - SOUTH BAYS

1M3.13 ROOF PLAN - NORTH BAYS

SUB-SET 2 - SERVICE BUILDING

2M1.11 FLOOR PLAN

SUB-SET 3 - FUELING BUILDING

3M1.11 FLOOR PLAN

SUB-SET 4 - BUS WASH BUILDING

4M1.11 FLOOR PLAN

SUB-SET 5 - ADMINISTRATIVE/OPERATIONS BUILDING

5M1.11 FIRST FLOOR PLAN

5M1.12 SECOND FLOOR PLAN

5M1.13 ROOF PLAN

SUB-SET 2 - SERVICE BUILDING

2E1.11 - SERVICE BUILDING PLAN

SUB-SET 3 - FUELING BUILDING

3E1.11 FUELING BUILDING PLAN - POWER

3E1.21 FUELING BUILDING PLAN - MECHANICAL POWER

3E1.31 FUELING BUILDING PLAN - LIGHTING

3E1.41 FUELING BUILDING PLAN - FIRE ALARM

3E1.51 FUELING BUILDING PLAN - LIGHTNING PROTECTION

3E1.61 FUELING BUILDING PLAN - SYSTEMS

3E1.71 FUELING MANAGEMENT SYSTEM CONDUIT SCHEMATIC

SUB-SET 4 - BUS WASH BUILDING

4E1.11 BUS WASH PLAN - POWER

4E1.21 BUS WASH PLAN - MECHANICAL POWER

4E1.31 BUS WASH PLAN - LIGHTING

4E1.41 BUS WASH PLAN - SYSTEMS

4E1.51 BUS WASH PLAN - LIGHTNING PROTECTION

SUB-SET 5 - ADMINISTRATIVE/OPERATIONS BUILDING

5E1.11 FIRST FLOOR PLAN - POWER

5E1.12 SECOND FLOOR PLAN - POWER

5E1.21 FIRST FLOOR PLAN - MECHANICAL POWER

5E1.22 SECOND FLOOR PLAN - MECHANICAL POWER

5E1.23 ROOF PLAN - MECHANICAL POWER

5E1.31 FIRST FLOOR PLAN - LIGHTING

5E1.32 SECOND FLOOR PLAN - LIGHTING

5E1.41 FIRST FLOOR PLAN - FIRE ALARM

5E1.42 SECOND FLOOR PLAN - FIRE ALARM

5E1.51 FIRST FLOOR PLAN - SYSTEMS

5E1.52 SECOND FLOOR PLAN - SYSTEMS

5E1.61 FIRST FLOOR PLAN - AUDIO/VISUAL

5E1.62 SECOND FLOOR PLAN - AUDIO/VISUAL

5E1.71 LIGHTNING PROTECTION ROOF PLAN

Moses & Associates, Inc.

2209 NW 40th Terrace, Ste A Gainesville, Florida 32605 FL License EB-0003097

P 352-372-1911 F 352-372-0186 moses-eng.com

M&A #11211

1F2.10 MAINTENANCE FACILITIES PLAN - LEVEL 2 CORE & SECTION

1F3.01 FIRE PUMP DETAILS

SUB-SET 2 - SERVICE BUILDING

SUB-SET 3 - FUELING BUILDING

SUB-SET 4 - BUS WASH BUILDING

SUB-SET 5 - ADMINISTRATIVE/OPERATIONS BUILDING

5F1.11 FIRST FLOOR PLAN

5F1.12 SECOND FLOOR PLAN

5F1.21 FIRE PROTECTION SECTIONS

5F1.22 FIRE PROTECTION SECTIONS

5F1.31 FIRE PROTECTION ENLARGED PLAN

No. Description Date

A AMPS; AREA

AAV AUTOMATIC AIR VENT

ABV CLG ABOVE FINISHED CEILING

AC AIR CONDITIONING UNIT

ACH AIR CHANGE PER HOUR

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

AM AIRFLOW MONITOR

AMS AIRFLOW MEASURING STATION

AL ALUMINUM

AP ACCESS PANEL

AH ATOMIZING HUMIDIFIER

BD BALANCING DAMPER

BFF BELOW FINISHED FLOOR

BFP BACKFLOW PREVENTER

BTU BRITISH THERMAL UNITS

BTUH BTU PER HOUR

B BOILER

C CONDENSATE

CAC CONTROL AIR COMPRESSOR

CD CEILING DIFFUSER

CF CUBIC FEET

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CH CHILLER

CHW CHILLED WATER

CHP CHILLED WATER PUMP

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CO CLEANOUT

CR CONDENSATE RETURN (STEAM)

CT COOLING TOWER

CU CONDENSING UNIT; COPPER

CV COEFFICIENT OF VALVE

DB DRY BULB

DC DUST COLLECTOR

DDC DIRECT DIGITAL CONTROLS

DEFL DEFLECTION

DG DOOR GRILLE

DIA DIAMETER

DS DUCT SILENCER

DTW DUAL TEMPER WATER

DTWR DUAL TEMPER WATER RETURN

DTWS DUAL TEMPER WATER SUPPLY

DS DUCT SILENCER

EA EACH

EAT ENTERING AIR TEMPERATURE

EDH ELECTRIC DUCT HEATER

EF EXHAUST FAN

EG EXHAUST GRILLE

EH EXHAUST HOOD

ENT ENTERING

ER EXHAUST REGISTER

ESP EXTERNAL STATIC PRESSURE

EV EXHAUST VALVE

EWT ENTERING WATER TEMPERATURE

EXST EXISTING

EXH EXHAUST

°F DEGREES FAHRENHEIT

FCU FAN COIL UNIT

FD FIRE DAMPER, FLOOR DRAIN

FG FILTER GRILLE

FH FUME HOOD

FMS FLOW MEASURING STATION

FO FLAT OVAL

FPM FEET PER MINUTE

FRP FIBERGLASS REINFORCED PLASTIC

FT FEET

FT WG FEET OF WATER, GAUGE

FTU FAN TERMINAL UNIT

GA GAUGE

GAL GALLONS

GALV GALVANIZED

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

HG HOT GAS

HHW HEATING HOT WATER

HWP HEATING HOT WATER PUMP

HHWR HEATING HOT WATER RETURN

HHWS HEATING HOT WATER SUPPLY

HP HEAT PUMP; HORSEPOWER

HR HOUR

HX HEAT EXCHANGER

ID INSIDE DIAMTER

IN. WG INCHES OF WATER, GAUGE

KW KILOWATTS

ABBREVIATIONS

KWH KILOWATT HOUR

LAT LEAVING AIR TEMPERATURE

LB POUND

LD LINEAR DIFFUSER

LVG LEAVING

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH THOUSANDS OF BTU'S

MCF THOUSANDS OF CUBIC FEET

MD MOTORIZED DAMPER

MIN MINUTE; MINIMUM

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN, NUMBER

NTS NOT TO SCALE

OA OUTDOOR AIR

OAL OUTDOOR AIR LOUVER

OC ON CENTER

OD OUTSIDE DIAMETER

P PUMP

PCW PROCESS COOLING WATER

PCP PROCESS COOLING WATER PUMP

PCWR PROCESS COOLING WATER RETURN

PCWS PROCESS COOLING WATER SUPPLY

PH PHASE

PRESS PRESSURE

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PVC POLYVINYL CHLORIDE

R RADIUS

RA RETURN AIR

RD ROUND DIFFUSER

RAG RETURN AIR GRILLE

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RL REFRIGERANT LIQUID

RP REDUCED PRESSURE

RPM REVOLUTIONS PER MINUTE

RAR RETURN AIR REGISTER

RS REFRIGERANT SUCTION

RV ROOF VENT

SA SUPPLY AIR

SAR, SR SUPPLY AIR REGISTER

SD SMOKE DAMPER

SF SQUARE FEET, SUPPLY FAN

SG SOFFIT GRILLE

SIM SIMILAR

SP STATIC PRESSURE

SPEC SPECIFICATION

SR SIDEWALL REGISTER

SS STAINLESS STEEL

STD STANDARD

STL STEEL

STM STEAM

SV SUPPLY VALVE

TEMP TEMPERATURE

TG TRANSFER GRILLE

TSP TOTAL STATIC PRESSURE

TYP TYPICAL

UC UNDERCUT DOOR - 3/4"

UG UNDERGROUND

UH UNIT HEATER

V VOLTS

VAV VARIABLE AIR VOLUME

VFD VARIABLE FREQUENCY DRIVE

VFM VENTURI FLOW METER

VLV VALVE

VVU VARIABLE VOLUME UNIT

WB WET BULB

WPD WATER PRESSURE DROP

XXX

BALL VALVE

GENERAL LEGEND

UNIT SYMBOL W/ UNIT NUMBER

GATE VALVE

CHECK VALVE

PLUG VALVE

BUTTERFLY VALVE

RELIEF VALVE

GAUGE CONNECTOR PLUG

IN-LINE STRAINER

THERMOMETER

THERMOMETER WELL

UNION

AUTOMATIC AIR VENT

GAUGE AND BALL VALVE

ECCENTRIC REDUCER

CONCENTRIC REDUCER

VENTURI FLOW METER

FLEXIBLE PIPE CONNECTION

CALIBRATED BALANCING VALVE

PIPE DOWN

PIPE UP

RADIUSED ELBOW (RADIUS = 1.5 X WIDTH)

DUCT/PIPE

MECHANICAL GENERAL NOTES

1. ALL EQUIPMENT & MATERIALS SHALL MEET "BUY AMERICA" REQUIREMENTS PER

SPECIFICATION 01000.

2. DUCT SIZES ARE SHEET METAL SIZES. NO DUCTWORK SHALL RUN PARALLEL

WITH AND OVER WALLS.

3. VERIFY COLLAR SIZES ON ALL AIR TERMINALS AND EQUIPMENT INLETS AND

OUTLETS. TRANSITION DUCTWORK AS NECESSARY.

4. CONTRACTOR SHALL VERIFY CLEARANCE SPACE AVAILABLE, OFFSETS

REQUIRED, STRUCTURAL OPENINGS, AND WORK BY OTHER TRADES PRIOR TO

FABRICATION OF DUCTWORK. PRESSURE TEST ALL REFRIGERANT PIPING PER

SPECIFICATION.

5. KEEP ALL REFRIGERANT PIPING CAPPED AND SEALED TO PREVENT

CONTAMINANTS FROM ENTERING PIPING DURING CONSTRUCTION. UNCAPPED

PIPING SHALL BE REMOVED AND REPLACED AT OWNERS' DISCRETION.

6. CONTRACTOR SHALL INSTALL ALL EQUIPMENT, PIPING, AND DUCTWORK SUCH

THAT MANUFACTURER'S RECOMMENDED CLEARANCES ARE MET FOR ALL

ACCESS PANELS, MOTORS, FANS, BELTS, FILTERS, AND AIR INTAKES.

7. ROUTE ALL PIPING CONCEALED ABOVE CEILING OR IN WALL. SUBMIT LOCATIONS

FOR ANY EXPOSED PIPING ROUTING TO ARCHITECT/ENGINEER FOR APPROVAL.

8. ALL PIPING PASSING THROUGH FIRE-RATED WALLS SHALL HAVE A FIRE RATED

SLEEVE AND SHALL BE PROTECTED PER SPECIFICATIONS.

9. PROVIDE ALL FITTINGS, ACCESSORIES, AND PIPING AS REQUIRED FOR A FULLY

FUNCTIONAL SYSTEM AND TO MEET THE DESIGN INTENT.

DIVISION 15 CODES & STANDARDS

1 GENERAL

1.1 THE WORK COVERED BY THIS DIVISION CONSISTS OF PROVIDING ALL LABOR,

EQUIPMENT AND MATERIALS AND PERFORMING ALL OPERATIONS NECESSARY FOR THE

INSTALLATION OF THE MECHANICAL WORK AS HEREIN CALLED FOR AND SHOWN ON THE

DRAWINGS.

2 CODES

2.1 ALL WORK UNDER DIVISION 15 SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE

CODES LISTED HEREIN. THE DESIGN HAS BEEN BASED ON THE REQUIREMENTS OF

THESE CODES; AND WHILE IT IS NOT THE RESPONSIBILITY OF THE CONTRACTOR TO

VERIFY THAT ALL WORK CALLED FOR COMPLIES WITH THESE CODES, HE SHALL BE

RESPONSIBLE FOR CALLING TO THE ARCHITECT/ENGINEER'S ATTENTION ANY

DRAWINGS OR SPECIFICATIONS THAT ARE NOT IN CONFORMANCE WITH THESE OR

OTHER CODES PRIOR TO ORDERING EQUIPMENT OR INSTALLING WORK.

2.2 COMPLY WITH REGULATIONS AND CODES OF UTILITY SUPPLIERS.

2.3 WHERE NO SPECIFIC METHOD OR FORM OF CONSTRUCTION IS CALLED FOR IN THE

CONTRACT DOCUMENTS, THE CONTRACTOR SHALL COMPLY WITH CODE

REQUIREMENTS WHEN CARRYING OUT SUCH WORK.

2.4 WHERE CODE CONFLICT EXISTS, GENERALLY THE MOST RESTRICTIVE REQUIREMENT

APPLIES. COMPLY WITH CURRENT CODE EDITION, UNLESS NOTED.

2.5 ADDITIONAL CODES OR STANDARDS APPLYING TO A SPECIFIC PART OF THE WORK AY

BE INCLUDED IN THAT SECTION.

2.6 THE FOLLOWING CODES GOVERN THE WORK:

2.6.1 FLORIDA BUILDING CODE - BUILDING - 2010.

2.6.2 FLORIDA BUILDING CODE - PLUMBING - 2010.

2.6.3 FLORIDA BUILDING CODE - MECHANICAL - 2010.

2.6.4 FLORIDA BUILDING CODE - FUEL GAS - 2010.

2.6.5 FLORIDA BUILDING CODE - TEST PROTOCOLS FOR HIGH VELOCITY

HURRICANE ZONES - 2010.

2.6.6 UNIFORM FIRE CODE (NFPA 1) - 2009 FLORIDA EDITION.

2.6.7 NATIONAL ELECTRIC CODE (NFPA 70) - 2008.

2.6.8 LIFE SAFETY CODE (NFPA 101) - 2009 FLORIDA EDITION.

2.6.9 INSTALLATION OF AIR CONDITIONING AND VENTILATION SYSTEMS

(NFPA 90A) - 2009.

2.6.10 INSTALLATION OF SPRINKLER SYSTEMS (NFPA 13) - 2007.

2.6.11 FAC 69A-60 FLORIDA FIRE PREVENTION CODE - 2010.

3 STANDARDS

3.1 ALL DIVISION 15 MATERIALS, INSTALLATION AND SYSTEMS SHALL MEET THE

REQUIREMENTS OF THE FOLLOWING STANDARDS, INCLUDING THE LATEST ADDENDA AND

AMMENDMENTS, TO THE EXTENTREFERENCED:

3.1.1 UNDERWRITERS' LABORATORIES (UL)

3.1.2 AMERICAN NATIONAL STANDARDS INSTITUTION (ANSI)

3.1.3 AMERICAN SOCIETY OF TESTING MATERIALS (ASTM)

3.1.4 NATIONAL FIRE PROTECTION (NFPA)

3.1.5 NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

3.1.6 AIR CONDITIONING AND REFRIGERATION INSTITUTE (ARI)

3.1.7 SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL

ASSOCIATION (SMACNA)

3.1.8 AMERICAN SOCIETY OF HEATING, REFRIGERATION, AND AIR CONDITIONING

ENGINEERS (ASHRAE)

3.1.9 AIR MOVEMENT AND CONTROL ASSOCIATION (AMCA)

3.1.10 STANDARDS OF THE HYDRONIC INSTITUTE (IBR)

ALL EQUIPMENT AND MATERIALS SHALL

MEET "BUY AMERICA" REQUIREMENTS

PER SPECIFICATION 01000.

FULL RADIUS ELBOW HALF RADIUS ELBOW

W

1.0 X W1.5 X W

W

B

A

MAINTAIN SAME

DIMENSIONS

SQUARE ELBOW WITH TURNING VANES

NOTES:

1. FULL RADIUS ELBOWS SHALL BE USED FOR ALL LOW PRESSURE

SYSTEMS. HALF RADIUS ELBOWS SHALL ONLY BE PERMITTED

WHERE FULL RADIUS ELBOWS WILL NOT FIT. MECHANICAL

CONTRACTOR SHALL OBTAIN WRITTEN APPROVAL FROM ENGINEER

PRIOR TO INSTALLATION OF HALF RADIUS ELBOWS.

2. FOR SQUARE ELBOWS, DIMENSIONS 'A' AND 'B' MUST BE EQUAL,

UNLESS OTHERWISE SHOWN ON DRAWINGS.

3. FOR LOW PRESSURE SYSTEMS, SQUARE OR RECTANGULAR ELBOWS

WITH TURNING VANES SHALL ONLY BE PROVIDED WHERE FULL

RADIUS OR HALF RADIUS ELBOW WILL NOT FIT, UNLESS OTHERWISE

SHOWN ON DRAWINGS. MECHANICAL CONTRACTOR SHALL OBTAIN

WRITTENAPPROVAL FROM ENGINEER PRIOR TO INSTALLATION OF

SQUARE OR RECTANGULAR ELBOWS.

MAIN DUCT

FINISHED CEILING

CONICAL SPIN-IN FITTING

SMACNA 45 DEGREE

RECTANGULAR WITH TRANSITION

TO ROUND MAY BE REQUIRED

ROUND SHEET METAL

DUCT AS REQUIRED

INSULATE AS MAIN DUCTADAPTOR AS REQUIRED

NOTE: PROVIDE ADAPTOR WITH

SIDE CONNECTION WHERE

OBSTRUCTIONS DO NOT ALLOW

CONNECTION TO TOP

INSULATE SUPPLY DIFFUSERS

BACK WITH 2" FIBERGLASS

AND SEAL EDGES FLEX DUCT 8'-0" MAX FOR

SUPPLY RIGID SHEET

METAL FOR EXHAUST

BALANCING DAMPER IN

ALL DUCT RUNOUTS

(MAY BE IN SPIN-IN)

NOTES:

1. DETAIL IS FOR CONCEALED DUCT.

WHERE EXPOSED, DUCT RUNOUTS TO

CDs SHALL BE DOUBLE WALL HARD

DUCT.

2. EXHAUST SIMILAR BUT DO NOT USE FLEX

DUCT AND DO NOT INSULATE BACK OF

GRILLE.

8 9

1/4" MINIMUM CLEARANCE

1" MINIMUM OVERLAP (4 SIDES)

1-1/2" x 1-1/2" x 14 GAUGE ANGLES MINIMUM WITH No.10 GALVANIZED SCREWS @ 12" OC (MIN. 2 PER

SCREW OR TACK WELD FIRE DAMPER TO SLEEVE.

SAME SPACING AS ANGLES

UL-555, 1-1/2 HOUR SPRING ACTUATED FIRE DAMPER.

SLEEVE SHALL BE AT LEAST DUCT GAUGE PER SMACNA

AND NFPA 90A

GALVANIZED STEEL DUCT

6" MAXIMUM

ACCESS PANEL

SIDE) DO NOT ATTACH TO WALL

HORIZONTAL INSTALLATION SIMILAR.

MOTOR HOUSING

1. SECURE FAN TO PREFABRICATED CURB.

2. SEE ARCHITECTURAL DRAWINGS FOR ROOF CURB INSTALLATION.

3. RUN ELECTRIC LINES THRU CLEARANCE HOLE PROVIDED IN GRAVITY

DAMPER, THEN THRU VENTILATOR ELECTRICAL CONDUIT GUIDE.

GRAVITY BACKDRAFT

OR MOTORIZED

DAMPER AS SPECIFIED

RIGID CONDUIT FOR

ELECTRICAL WIRING

SEE NOTE 2

PERFABRICATED

ROOF CURB.

SEE

SPECIFICATIONS.

ELECTRICAL

CONDUIT GUIDE

SEE NOTE 1

SEE NOTE 2

ROOF

TRANSITION DUCT TO

FULL SIZE OF DAMPER

SUPPLIED WITH ROOF

FAN

SEE PLANS FOR

DUCT SIZES AND

LOCATIONS

NOTES:

LENGTH OF

3D

NOTES:

1. EXTERNALLY INSULATED ROUND DUCT RUNOUT 2" LARGER THAN NECK UNLESS

OTHERWISE NOTED.

2. MINIMUM STRAIGHT LENGTH TO BOX SHALL BE 3 DUCT DIAMETERS OR

MANUFACTURER'S RECOMMENDATION, WHICHEVER IS GREATER.

3. D=DUCT DIAMETER

VAV BOX

MAIN SA DUCT

FULL SIZE OF OUTLET

OR HEATING COIL

D

D+2

OFFSETS/ELBOWS

AS REQ'D

CONICAL SPIN-IN

STRAIGHT

ACCESS PANELS

MIN

MAIN DUCT

W/4 45°

W

(4"MIN)

4W

PROVIDE STANDOFF

ON INSULATED DUCTS

DRAFTED BY:

ARCHITECT'S PROJECT NO.:

DATE:

REVISION DATES:

PLANS CHECKED BY:

DATE CHECKED:

PHONE: FAX:

(352) 372-1378 (352) 378-1281

GAINESVILLE FLORIDA

5700 SW 34TH STREET SUITE 1307

32608

AA 0002486

for

A R C H I T E C T S

Gainesville, Florida

0M0.11

RTS BUS

FLEET

MAINTENANCE

& OPERATIONS

FACILITY

City of Gainesville

CONFORMED

DOCUMENTS

TA /

EJD

11046

TA

MECHANICAL LEGEND AND NOTES

29 March 2013

MECHANICAL:

J. ANTHONY ANDRESS

PE - 0046536

Moses & Associates, Inc.

2209 NW 40th Terrace, Ste A Gainesville, Florida 32605 FL License EB-0003097

P 352-372-1911 F 352-372-0186 moses-eng.com

M&A #11211

DUCT RUNOUT TO AIR OUTLETS/ INLETS DETAIL

NTS

4 FIRE DAMPER DETAIL

NTS

ROOF EXHAUST FAN DETAIL

NTS

VAV BOX DUCT DETAIL

NTS

1DUCT DELBOW DETAIL

NTS

BLDG 1: ROOF VENT SCHEDULE

MARK RV-101 RV-102 RV-103 RV-104

MANUFACTURER COOK COOK COOK COOK

MODEL TR-16 TR-16 TR-12 TR-8

THROAT DIAMIETER 16.5 16.5 12.5 8.5

CURB CAP ID 28 28 20 18

SCHEDULE NOTES 1 1 1 1

SCHEDULE NOTES

(1) PROVIDE ROOF CURB

BLDG 1: COMPUTER ROOM AIR CONDITIONING UNIT SCHEDULE

MARK CRAC-11 CRAC-12

MANUFACTURER DATA AIRE DATA AIRE

MODEL GFAD028 GFAD028

SYSTEM TYPE DOWNFLOW - DUCTED DOWNFLOW - DUCTED

VOLT-PHASE 460-3 460-3

DESIGN CONDITIONS

INDOOR DESIGN TEMP DB/WB (°F) 72/60 72/60

FAN DATA

TOTAL AIR (CFM) (HIGH SPEED) 3,600 3,600

ESP (IN WG) 0.5 0.5

MOTOR SIZE (HP) 3.7 3.7

COOLING COIL DATA

TYPE DX DX

TOTAL CAPACITY (BTUH) 95,700 95,700

MAX FACE VELOCITY (FPM) 300 300

SUCTION TEMP (°F) - -

REFRIGERANT PIPE SIZE RL-RS (IN.) NOTE 2 NOTE 2

CONDENSING UNIT

MARK CM-11 CM-12

MODEL GHRC032 GHRC032

TOTAL CAPACITY (BTUH) 95,700 95,700

SENSIBLE CAPACITY (BTUH) 79,700 79,700

VOLT-PHASE 480-3 480-3

UNIT AMPACITY (FLA) 1.7 1.7

HEATING COIL DATA

TYPE ELECTRIC ELECTRIC

POWER (kW) 15 15

STAGES SCR SCR

TOTAL CAPACITY (BTUH) 51,225 51,225

EAT - LAT (°F) 50-70 50-70

HUMIDIFIER DATA

TYPE ELECTRIC STEAM ELECTRIC STEAM

CAPACITY (PPH) 10 10

POWER (kW) 3.3 3.3

FILTER SECTION

TYPE 4" - 30% 4" - 30%

DIRTY PD (IN WG) 1 1

SCHEDULE NOTES 1, 2, 3, 4 1, 2, 3, 4

SCHEDULE NOTES

(1) MERV-8 FILTERS.

(2) PROVIDE REFRIGERANT PIPING SIZED PER MANUFACTURER'S RECOMMENDATIONS.

(3) PROVIDE COMPRESSOR SOUND ATTENUATION BLANKETS

(4) PROVIDE DOWNFLOW PLENUM WITH REAR DISCHARGE DUCT CONNECTION

BLDG 1: BOILER SCHEDULE

MARK B-1 B-2

MANUFACTURER AERCO AERCO

MODEL BMK 1.5 LN GWB BMK 1.5 LN GWB

FUEL NAT GAS NAT GAS

GROSS INPUT (MBH) 1,500 1,500

NET OUTPUT (MBH) 1,290 1,290

MIN EFFICIENCY 86% 86%

TURNDOWN RATIO 20:1 20:1

BLOWER MOTOR VOLTS-PHASE 120-1 120-1

WATER SUPPLY TEMP (°F) 180 180

WATER RETURN TEMP (°F) 156 156

WATER FLOW (GPM) 62 62

SCHEDULE NOTES 1 1

SCHEDULE NOTES

1 PROVIDE BOILER CONTROL SYSTEM

BLDG 1: VAV DX A/C SPLIT SYSTEM UNIT SCHEDULE

UNIT TYPE SPLIT A/C SPLIT A/C

MANUFACTURER AAON AAON

CONDENSING UNIT MARK CU-11 CU-12

CONDENSING UNIT MODEL CCB-017-3-D CCB-017-3-D

AIR HANDLING UNIT MARK AHU-11 AHU-12

AIR HANDLING UNIT MODEL M2-H-014 M2-H-014

AIR HANDLING UNIT TYPE HORIZONTAL HORIZONTAL

DESIGN CONDITIONS

WINTER OUTDOOR (°F) 10 10

WINTER INDOOR (°F) 70 70

SUMMER OUTDOOR DB/WB (°F) 95/75 95/75

SUMMER INDOOR DB/WB (°F) 75/62 75/62

AHU FAN SECTION

SUPPLY AIR (CFM) 6,000 6,000

OUTDOOR AIR (CFM) 1,000 1,000

EXTERNAL STATIC PRESSURE (IN WG) 1.5 1.5

FAN MOTOR (HP) 10 10

VOLTS-PHASE 460-3 460-3

AHU EVAPORATOR SECTION

SENSIBLE COOLING CAPACITY (BTUH) 163,800 163,800

TOTAL COOLING CAPACITY (BTUH) 207,200 207,200

AIR ENTERING COOLING DB/WB (°F) 78.3/64.4 78.3/64.4

CONDENSING SECTION

VOLTS-PHASE 460-3 460-3

LEAD COMPRESSOR DIGITAL SCROLL DIGITAL SCROLL

LAG COMPRESSOR SCROLL W/ HOT GAS BYPASS SCROLL W/ HOT GAS BYPASS

EER 12.9 12.9

SUCTION LINE SIZE (IN) NOTE 2 NOTE 2

LIQUID LINE SIZE (IN) NOTE 2 NOTE 2

SCHEDULE NOTES 1, 2, 3, 4 1, 2, 3, 4

SCHEDULE NOTES

(1) SINGLE POINT ELECTRICAL CONNECTION

(2) REFRIGERANT PIPE SIZING PER MANUFACTURER'S RECOMMENDATIONS

(3) PROVIDE COMPRESSOR SOUND ATTENUATION BLANKET

(4) PROVIDE VIBRATIION ISOLATION CURB WITH INTERNAL SOUND ATTENUATION BARRIER.

BLDG 1: EXHAUST FAN SCHEDULE

MARK EF-101-112 EF-121-124 EF-125 EF-131 & 133 EF-132 EF-134 EF-136, & 137

LOCATION BLDG 1 - ROOF BLDG 1 - ROOF BLDG 1 - ROOF BLDG 1 - ROOF BLDG 1 - ROOF BLDG 1 - ROOF BLDG 1 - SUSPENDED

MANUFACTURER COOK CARMON CARMON COOK COOK COOK COOK

MODEL 60HXEL12B CMB-25 BXI-12A0 135ACEB 70ACEB 100ACEB 100SQNB

TYPE - - - DOWNBLAST CENTRIFUGAL DOWNBLAST CENTRIFUGAL DOWNBLAST CENTRIFUGAL CENTRIFUGAL

CLASS - I - - - - INLINE

DRIVE BELT BELT BELT BELT BELT BELT BELT

AIRFLOW (CFM) 40,000 3,600 400 1,000 200 500 600

TSP (IN WG) 0.15 3.5 3.5 0.5 0.5 0.5 0.5

MOTOR SECTION

VOLTS-PHASE 460-3 460-3 460-3 277-1 277-1 277-1 277-1

BHP/HP 6.64/7.5 3.38/5 0.33/1 0.164/0.25 0.129/0.167 0.100/0.167 0.152 w/0.25

DRIVE TYPE STD STD STD STD STD STD STD

SOUND DATA (DB)

63 HZ 88 79 77 66 78 65 70

125 HZ 89 82 75 68 73 68 67

250 HZ 85 86 84 67 76 72 69

500 HZ 82 87 76 60 62 64 68

1000 HZ 79 83 75 58 58 58 64

2000 HZ 77 79 71 54 52 55 61

4000 HZ 74 72 63 49 49 50 56

8000 HZ 67 64 56 45 45 46 51

SONES 23 - - 6.4 9.0 7.6 8.6

SCHEDULE NOTES 7,8,10 1, 2, 3, 4, 5 1, 2, 3, 4, 5 7,8,9,10 7,8,9,10 7,8,9,10 6 (EF-137), 8,9,11

SCHEDULE NOTES

(1) PROVIDE DECK PLATFORM (7) PROVIDE ROOF CURB

(2) PROVIDE INLET TEE (8) PROVIDE BACKDRAFT DAMPER

(3) PROVIDE INLET FLEX (9) PROVIDE DISCONNECT

(4) PROVIDE WEATHER COVER (10) PROVIDE BIRD SCREEN

(5) PROVIDE HOUSING DRAIN (11) EF-135 DELETED FROM LIST

(6) PROVIDE LINE VOLTAGE WALL T-STAT.

BLDG 1: HHW PUMP SCHEDULE

MARK HWP-1 HWP-2

DUTY HHW HHW

MANUFACTURER TACO TACO

MODEL KV2009 KV2009

SIZE - -

SPEED (RPM) 1760 1760

TYPE INLINE INLINE

CAPACITY (GPM) 120 120

TOTAL HEAD (FT HD) 50 50

MINIMUM EFFICIENCY (%) 53 53

IMPELLER DIAMETER (IN) 7.9 7.9

MOTOR (HP) 3 3

VOLTS-PHASE 480-3 480-3

DRIVE TYPE STD STD

SCHEDULE NOTES

SCHEDULE NOTES

BLDG 1: HU HHW COIL SCHEDULE

MARK HC1A HC1B

LOCATION HU-11 HU-12

TYPE HHW HHW

EWT (F) 180 180

LWT (F) 134 134

DUTY HEAT HEAT

DESIGN CONDITIONS

SUPPLY AIR CFM 25,000 25,000

OUTDOOR AIR CFM - -

EAT (F) 60 60

LAT (F) 108 108

MAX FACE VELOCITY (FPM) 695 695

TOTAL CAPACITY (BTUH) 1,326,000 1,326,000

HHW FLOW (GPM) 62 62

MAX WATER PD (FT HD) 4.5 4.5

MAX AIR PD (IN WG) 0.5 0.5

MIN ROW/MAX FPI 2/12 2/12

CONTROL

VALVE MARK 1-3 1-3

TYPE 3-WAY 3-WAY

SIZE (IN) 2 2

CV 25 25

SCHEDULE NOTES 1, 2, 3 1, 2, 3

SCHEDULE NOTES

(1) REFER TO HU SCHEDULE

(2) EACH COIL

(3) REFER TO AHU COIL PIPING DIAGRAMS

BLDG 1: HEATING UNIT SCHEDULE

MARK HU-11 HU-12

BASIS OF DESIGN AAON AAON

MODEL CUSTOM CUSTOM

TYPE SINGLE ZONE SINGLE ZONE

LOCATION INDOOR INDOOR

FAN SECTION

FAN TYPE - -

FAN QUANTITY 2 2

DRIVE TYPE DIRECT DIRECT

FAN CFM 2 @ 12,500 2 @ 12,500

TOTAL CFM 25,000 25,000

TSP (IN WG)

ESP (IN WG) 0.5 0.5

MOTOR SECTION

EACH MOTOR BHP 2 @ 10.57 2 @ 10.57

EACH MOTOR HP 2 @ 15 2 @ 15

VOLT-PHASE 460-3 460-3

DRIVE STD STD

PRE FILTER SECTION

TYPE 2" PANEL 2" PANEL

EFFICIENCY (%) 30 30

SIZE (INxIN) 24x24 24x24

QUANTITY - -

DIRTY PD (IN WG) 1.0 1.0

AFTER FILTER SECTION

TYPE 12" BAG 12" BAG

EFFICIENCY (%) 90 90

SIZE (INxIN) 24X24 24X24

QUANTITY - -

DIRTY PD (IN WG) 1.2 1.2

AHU EQUIPMENT

SA SMOKE DAMPER NO NO

RA SMOKE DAMPER NO NO

HEATING COIL YES YES

SCHEDULE NOTES 1, 2, 3, 4 1, 2, 3, 4

SCHEDULE NOTES

(1) SUPPLY DUCT SHALL BE SINGLE WALL, UNINSULATED GALVANIZED SPIRAL AND RECTANGULAR

(2) MERV 8

(3) SIZE SHOWN ON DRAWINGS

(4) REFER TO HU COIL SCHEDULE

BLDG 1: PACKAGED HEAT PUMP SCHEDULE

UNIT TYPE HEAT PUMP HEAT PUMP

MARK PHP-11 PHP-12

MANUFACTURER CARRIER CARRIER

MODEL 50EZ-A48-60 50EZ-A48-60

VOLT-PHASE 460-3 460-3

SEER 13.5 13.5

COP @ 47°F 3.6 3.6

HSPF 7.7 7.7

DESIGN CONDITIONS

WINTER OUTDOOR (°F) 25 25

WINTER INDOOR (°F) 70 70

SUMMER OUTDOOR DB/WB (°F) 96/80 96/80

SUMMER INDOOR DB/WB (°F) 75/63 75/63

FAN SECTION (1)

SUPPLY AIR (CFM) 1,600 1,600

OUTDOOR AIR (CFM) - -

EXTERNAL STATIC PRESSURE (IN WG) - -

FAN MOTOR (HP) 1.0 1.0

PERFORMANCE SECTION

SENSIBLE COOLING CAPACITY (BTUH) - -

TOTAL COOLING CAPACITY (BTUH) 47,000 47,000

AIR ENTERING COOLING DB/WB (°F) 96/80 96/80

AIR ENTERING HEATING (°F) 52/52 52/52

ELECTRIC HEAT SECTION (1)

CAPACITY (kW) 10 10

VOLTS-PHASE 460-3 460-3

STAGES - -

SCHEDULE NOTES 1, 2, 3 1, 2, 3

SCHEDULE NOTES

(1) SINGLE POINT ELECTRICAL CONNECTION

(2) PROVIDE ROOF CURB AND TIE DOWNS

(3) PROVIDE COMBINATION CONCENTRIC SUPPLY/RETURN DIFFUSER/GRILLE.

BLDG 1: VARIABLE VOLUME TERMINAL UNIT SCHEDULE

MINIMUM MINIMUM ELECTRIC REHEAT COIL

TAG SIZE NOMINAL COOLING INLET V-PH KW BTUH STAGES EAT LAT REMARKS

(1) (2) CFM CFM STATIC

VAV-1101 10 800 320 0.35 277-1 4 13,700 SCR 55 80

VAV-1102 6 340 140 0.35 277-1 2 6,800 SCR 55 80

VAV-1103 7 440 180 0.35 277-1 2 6,800 SCR 55 80

VAV-1104 8 560 220 0.35 277-1 3 10,200 SCR 55 85

VAV-1105 10 750 300 0.35 277-1 4 13,700 SCR 55 80

VAV-1106 6 300 120 0.35 277-1 2 6,800 SCR 55 80

VAV-1107 6 300 120 0.35 277-1 2 6,800 SCR 55 80

VAV-1108 7 490 200 0.35 277-1 2 6,800 SCR 55 85

VAV-1109 6 380 150 0.35 277-1 2 6,800 SCR 55 80

VAV-1110 10 900 360 0.35 277-1 5 17,100 SCR 55 85

VAV-1111 6 300 50 0.35 277-1 - - - 55 55 Cooling Only VAV-1112 6 300 50 0.35 277-1 - - - 55 55 Cooling Only

VAV-1201 8 650 260 0.35 277-1 4 13,700 SCR 55 85

VAV-1202 14 1700 680 0.35 480-3 8 27,300 SCR 55 80

VAV-1203 14 2000 800 0.35 480-3 10 34,100 SCR 55 80

VAV-1204 12 1260 500 0.35 480-3 7 23,900 SCR 55 85

SCHEDULE NOTES:

(1) TAG KEY: VAV-XXYY; WHERE XX=AHU YY=BOX

(2) BASIS OF DESIGN: PRICE SDV WITH ELECTRIC HEAT.

(3) PROVIDE UNIT MOUNTED CONTROLS TRANSFORMER ON ALL UNITS INCLUDING THOSE WITHOUT ELECTRIC HEAT.

BLDG 2: AIR COOLED CHILLER SCHEDULE

MARK CH-1

MANUFACTURER SMARDT

MODEL AC037

MINIMUM CAPACITY (TONS) 100

VOLTS-PHASE 460-3

IPLV/NPLV (kW/Ton) 0.662

EER 18.1

GLYCOL 20% PROPYLENE

EWT (F) 60

LWT (F) 44

OUTDOOR TEMP (F) 95

CHW FLOW (GPM) 155

MINIMUM % LOAD 15%

STAGES VARIABLE

SCHEDULE NOTES 1,2

SCHEDULE NOTES

(1) PROVIDE INTEGRAL DISCONNECT

(2) PROVIDE HOT GAS BYPASS

BLDG 2: PUMP SCHEDULE

MARK CHP-1 CHP-2

DUTY CHW CHW

MANUFACTURER TACO TACO

MODEL FI2009 FI2009

SIZE - -

SPEED (RPM) 1760 1760

TYPE END SUCTION END SUCTION

CAPACITY (GPM) 150 150

TOTAL HEAD (FT HD) 70 70

MINIMUM EFFICIENCY (%) 66 66

IMPELLER DIAMETER (IN) 8.5 8.5

MOTOR (HP) 5 5

VOLTS-PHASE 480-3 480-3

DRIVE TYPE STD STD

SCHEDULE NOTES

SCHEDULE NOTES

BLDG 3: SPLIT SYSTEM HEAT PUMP SCHEDULE

UNIT TYPE HEAT PUMP

MANUFACTURER CARRIER

CONDENSING UNIT MARK CU-31

CONDENSING UNIT MODEL 25HBA336

AIR HANDLING UNIT MARK AHU-31

AIR HANDLING UNIT MODEL FY4ANF024005

AIR HANDLING UNIT TYPE VERTICAL

SEER 13

COP @ 47F 3.54

HSPF 8.2

DESIGN CONDITIONS

WINTER OUTDOOR (°F) 25

WINTER INDOOR (°F) 70

SUMMER OUTDOOR DB/WB (°F) 96/80

SUMMER INDOOR DB/WB (°F) 75/63

FAN SECTION

SUPPLY AIR (CFM) 800

OUTDOOR AIR (CFM) 60

EXTERNAL STATIC PRESSURE (IN WG) 0.4

FAN MOTOR (HP) 1/4

VOLTS-PHASE 208-1

EVAPORATOR SECTION

SENSIBLE COOLING CAPACITY (BTUH) 18,000

TOTAL COOLING CAPACITY (BTUH) 24,000

AIR ENTERING COOLING DB/WB (°F) 80/67

AIR ENTERING HEATING (°F) 70.0

CONDENSING SECTION

VOLTS-PHASE 208-1

SUCTION LINE SIZE (IN) NOTE 2

LIQUID LINE SIZE (IN) NOTE 2

ELECTRIC HEAT SECTION

CAPACITY (kW) 5.0

VOLTS-PHASE 208-1

STAGES 1

SCHEDULE NOTES 1, 2

SCHEDULE NOTES

(1) SINGLE POINT ELECTRICAL CONNECTION

(2) REFRIGERANT PIPE SIZING PER MANUFACTURER'S RECOMMENDATIONS

(3) PROVIDE FULL SIZE AUX DRAIN PAN UNDER AHU WITH FLOAT SWITCH FOR SHUT DOWN.

BLDG 3: EXHAUST FAN SCHEDULE

MARK EF-301-303 EF-304

LOCATION BLDG 3- ABV CEILING BLDG 3 - ABV CEILING

MANUFACTURER COOK COOK

MODEL GC-144 GC-520

TYPE CEILING FAN CEILING BLOWER

CLASS - -

DRIVE DIRECT DIRECT

AIRFLOW (CFM) 120 320

TSP (IN WG) 0.25 0.35

MOTOR SECTION

VOLTS-PHASE 208-1 208-1

BHP/HP 89.5 w/~0 146 w/0.062

DRIVE TYPE STD STD

SOUND DATA (DB)

63 HZ 51 68

125 HZ 59 68

250 HZ 55 63

500 HZ 54 58

1000 HZ 50 50

2000 HZ 43 45

4000 HZ 38 45

8000 HZ 31 43

SONES 3 5

SCHEDULE NOTES 1,2,3 1,2,3,6

SCHEDULE NOTES

(1) PROVIDE DISCONNECT & THERMAL OVERLOAD

(2) PROVIDE DELUXE ALUMINUM GRILLE

(3) PROVIDE WALL CAP

(4) PROVIDE WEATHER COVER

(5) PROVIDE HOUSING DRAIN

(6) PROVIDE LINE VOLTAGE WALL T-STAT.

BLDG 5: CUSTOM AHU COOLING COIL SCHEDULE

MARK CC1A CC1B

LOCATION AHU-51 AHU-51

TYPE CHW CHW

EWT (°F) 44 44

LWT (°F) 60 60

SST (°F) N/A N/A

TRAP DEPTH (IN) 12 12

FACE DAMPER NO NO

DESIGN CONDITIONS

SUPPLY AIR CFM 15,000 12,000

OUTDOOR AIR CFM (MAX) 3,000 2,400

OUTDOOR AIR CFM (MIN) 2,000 1,700

EAT DB/WB (°F) 78.4/65.5 78.4/65.5

LAT DB/WB (°F) 52.7/52.4 53.2/53.0

FACE VELOCITY (FPM) 439 443

SENSIBLE CAPACITY (BTUH) 409,900 320,900

TOTAL CAPACITY (BTUH) 563,600 434,300

CHW FLOW (GPM) 70 54

MAX WATER PD (FT HD) 17 15

MAX AIR PD (IN WG) 0.64 0.64

ESP (IN WG) 2.5 2.5

TSP (IN WG) 6.0 6.0

MIN ROW/MAX FPI 6 - 10 6 - 10

CONTROL

VALVE MARK 1-1 1-2

TYPE 3-WAY 3-WAY

SIZE (IN) 1.5 1.5

CV 25 25

SEPARATE CIRCUIT N/A N/A

SCHEDULE NOTES 1, 2, 3, 4 1, 2, 3, 4

SCHEDULE NOTES

(1) REFER TO CUSTOM AHU SCHEDULE

(2) REFER TO CONDENSATE TRAP DETAIL

(3) REFER TO AHU COIL PIPING DIAGRAMS

(4) VALVE SELECTED FOR TOTAL FLOW OF ALL COILS SERVED

BLDG 5: CUSTOM AIR HANDLING UNIT SCHEDULE

MARK AHU-51 AHU-52

BASIS OF DESIGN TEMTROL TEMTROL

MODEL CUSTOM CUSTOM

TYPE CHW SINGLE ZONE CHW SINGLE ZONE

LOCATION INDOOR INDOOR

FAN SECTION

FAN TYPE PLENUM PLENUM

FAN QUANTITY 1 1

DRIVE TYPE BELT BELT

FAN CFM 15,000 12,000

TOTAL CFM 15,000 12,000

TSP (IN WG) 6.0 6.0

ESP (IN WG) 2.5 2.5

MOTOR SECTION

EACH MOTOR BHP 19.8 17.2

EACH MOTOR HP 25 20

VOLT-PHASE 180-3 180-3

DRIVE VFD VFD

PRE FILTER SECTION

TYPE 2" PANEL 2" PANEL

EFFICIENCY (%) 30 30

SIZE (INxIN) 24x24 24x24

QUANTITY - -

DIRTY PD (IN WG) 1 1

AFTER FILTER SECTION

TYPE 12" BAG 12" BAG

EFFICIENCY (%) 90 90

SIZE (INxIN) 24X24 24X24

DIRTY PD (IN WG) 1.2 1.2

SOUND DATA (DB)

63 HZ 102 100

125 HZ 100 99

250 HZ 103 101

AHU EQUIPMENT

COOLING COIL YES YES

SCHEDULE NOTES 1, 2, 3, 4, 5 1, 2, 3, 4, 5

SCHEDULE NOTES

(1) SINGLE PLENUM FAN IN EACH AHU.

(2) PROVIDE VFD.

(3) MERV 13

(4) SIZE SHOWN ON DRAWINGS

(5) REFER TO CUSTOM AHU COIL SCHEDULE

BLDG 5: EXHAUST FAN SCHEDULE

MARK EF-501 EF-502-503

LOCATION BLDG 5 - ROOF BLDG 5 - ROOF

MANUFACTURER COOK COOK

MODEL 120ACEB 100ACEB

TYPE DOWNBLAST CENTRIFUGAL DOWNBLAST CENTRIFUGAL

CLASS - -

DRIVE BELT BELT

AIRFLOW (CFM) 840 460

TSP (IN WG) 0.50 0.50

MOTOR SECTION

VOLTS-PHASE 277-1 277-1

BHP/HP 0.13/0.25 0.093/0.25

DRIVE TYPE STD STD

SOUND DATA (DB)

63 HZ 65 65

125 HZ 67 67

250 HZ 69 72

500 HZ 60 63

1000 HZ 58 58

2000 HZ 55 54

4000 HZ 49 49

8000 HZ 45 46

SONES 7 7

SCHEDULE NOTES 1,2,3,4 1,2,3,4

SCHEDULE NOTES

(1) PROVIDE DISCONNECT.

(2) PROVIDE BACKDRAFT DAMPER.

(3) PROVIDE BIRD SCREEN.

(4) PROVIDE ROOF CURB..

BLDG 5: VARIABLE VOLUME TERMINAL UNIT SCHEDULE

MINIMUM MINIMUM ELECTRIC REHEAT COIL

TAG SIZE NOMINAL COOLING INLET V-PH KW BTUH STAGES EAT LAT REMARKS

(1) (2) CFM CFM STATIC (5)

VAV-5101 6 320 100 0.35 277-1 2 6,800 SCR 55 85

VAV-5102 12 1340 540 0.35 277-1 6 20,500 SCR 55 80

VAV-5103 8 680 270 0.35 277-1 3 10,200 SCR 55 80

VAV-5104 7 400 120 0.35 277-1 3 10,200 SCR 55 85

VAV-5105 6 320 100 0.35 277-1 2 6,800 SCR 55 85

VAV-5106 6 320 100 0.35 277-1 2 6,800 SCR 55 85

VAV-5107 7 400 120 0.35 277-1 3 10,200 SCR 55 85

VAV-5108 6 340 100 0.35 277-1 2 6,800 SCR 55 85

VAV-5109 8 520 160 0.35 277-1 3 10,200 SCR 55 85

VAV-5110 6 270 80 0.35 277-1 2 6,800 SCR 55 85

VAV-5111 7 500 150 0.35 277-1 3 10,200 SCR 55 85

VAV-5112 14 1880 560 0.35 480-1 10 34,100 SCR 55 85

VAV-5113 6 300 50 0.35 277-1 - - 55 - 55 Cooling only. Provide Controls Power.

VAV-5114 12 1200 360 0.35 480-1 6 20,500 SCR 55 85

VAV-5115 10 800 240 0.35 277-1 4 13,700 SCR 55 85

VAV-5116 8 640 190 0.35 277-1 4 13,700 SCR 55 85

VAV-5117 6 320 130 0.35 277-1 2 6,800 SCR 55 80

VAV-5118 14 1800 540 0.35 480-1 10 34,100 SCR 55 85

VAV-5119 14 1800 540 0.35 480-1 10 34,100 SCR 55 85

VAV-5120 4 160 20 0.35 277-1 - - SCR 55 55 Cooling only. Provide Controls Power.

VAV-5201 6 340 100 0.35 277-1 2 6,800 SCR 55 85

VAV-5202 6 340 100 0.35 277-1 2 6,800 SCR 55 85

VAV-5203 6 340 100 0.35 277-1 2 6,800 SCR 55 85

VAV-5204 6 320 100 0.35 277-1 2 6,800 SCR 55 85

VAV-5205 8 520 160 0.35 277-1 3 10,200 SCR 55 85

VAV-5206 6 320 100 0.35 277-1 2 6,800 SCR 55 85

VAV-5207 6 320 100 0.35 277-1 2 6,800 SCR 55 85

VAV-5208 6 280 110 0.35 277-1 2 6,800 SCR 55 80

VAV-5209 7 440 180 0.35 277-1 3 10,200 SCR 55 80

VAV-5210 6 320 100 0.35 277-1 3 10,200 SCR 55 85

VAV-5211 4 130 40 0.35 277-1 1 3,400 SCR 55 85

VAV-5212 6 300 90 0.35 277-1 2 6,800 SCR 55 85

VAV-5213 4 160 20 0.35 277-1 - - 55 55 55 Cooling only. Provide Controls Power.

VAV-5214 5 240 70 0.35 277-1 2 6,800 SCR 55 85

VAV-5215 10 900 270 0.35 277-1 5 17,100 SCR 55 85

VAV-5216 10 1020 310 0.35 277-1 6 20,500 SCR 55 85

VAV-5217 7 480 140 0.35 277-1 3 10,200 SCR 55 85

VAV-5218 8 600 240 0.35 277-1 3 10,200 SCR 55 80

VAV-5219 8 600 180 0.35 277-1 4 13,700 SCR 55 85

VAV-5220 10 800 240 0.35 277-1 4 13,700 SCR 55 85

VAV-5221 7 480 140 0.35 277-1 3 10,200 SCR 55 85

VAV-5222 8 600 240 0.35 277-1 4 13,700 SCR 55 80

VAV-5223 6 280 80 0.35 277-1 2 6,800 SCR 55 85

VAV-5224 7 380 150 0.35 277-1 2 6,800 SCR 55 80

VAV-5225 5 240 70 0.35 277-1 2 6,800 SCR 55 85

VAV-5226 7 410 120 0.35 277-1 3 10,200 SCR 55 85

VAV-5227 5 220 70 0.35 277-1 2 6,800 SCR 55 85

SCHEDULE NOTES:

(1) TAG KEY: VAV-XYY; WHERE X=AHU YY=BOX

(2) BASIS OF DESIGN: PRICE MODEL SDV WITH SCR CONTROLLED ELECTRIC HEAT.

(3) PROVIDE UNIT MOUNTED INTEGRAL INTERLOCKING POWER DISCONNECT SWITCH.

(4) PROVIDE UNIT MOUNTED CONTROLS TRANSFORMER FOR ALL UNITS INCLUDING THOSE WITHOUT ELECTRIC HEAT.

(5) THIS IS DESIGN LAT.

BLDG 5: DUCT SILENCER SCHEDULE

MARK DS-51A DS-51B DS-51C DS-52A DS-52B

LOCATION SA DUCT SA DUCT SA DUCT SA DUCT SA DUCT

MANUFACTURER PRICE PRICE PRICE PRICE PRICE

TYPE ELBOW STRAIGHT STRAIGHT ELBOW STRAIGHT

LENGTH 5 FEET 5 FEET 5 FEET 5 FEET 5 FEET

SIZE 20X16 34X20 36X20 26X18 48X18

AIRFLOW (CFM) 3,000 6,500 5,500 4,000 8,000

MAX APD 0.30 0.30 0.30 0.30 0.30

SCHEDULE NOTES

SCHEDULE NOTES

BLDG 1: ROOF VENT SCHEDULE

MARK UH-1, 2, 3, 4

MANUFACTURER MARKEL

MODEL G1G5105N

CAPACITY (KW) 5

VOLTS-PHASE 277-1

CFM 400

SCHEDULE NOTES 1,2,3

SCHEDULE NOTES

(1) PROVIDE WALL BRACKET FOR VERTICAL MOUNT

(2) PROVIDE BUILT IN THERMOSTAT

(2) PROVIDE INTEGRAL DISCONNECT

BLDG 4: ROOF VENT SCHEDULE

MARK RV-401

MANUFACTURER COOK

MODEL TR-20

THROAT DIAMIETER 20.5

CURB CAP ID 28

SCHEDULE NOTES 1

SCHEDULE NOTES

(1) PROVIDE ROOF CURB

BLDG 5: ROOF VENT SCHEDULE

MARK RV-501

MANUFACTURER COOK

MODEL GI

THROAT SIZE 42X20

SCHEDULE NOTES 1

SCHEDULE NOTES

(1) PROVIDE ROOF CURB

ALL EQUIPMENT AND MATERIALS SHALL

MEET "BUY AMERICA" REQUIREMENTS

PER SPECIFICATION 01000.

DRAFTED BY:

ARCHITECT'S PROJECT NO.:

DATE:

REVISION DATES:

PLANS CHECKED BY:

DATE CHECKED:

PHONE: FAX:

(352) 372-1378 (352) 378-1281

GAINESVILLE FLORIDA

5700 SW 34TH STREET SUITE 1307

32608

AA 0002486

for

A R C H I T E C T S

Gainesville, Florida

0M0.21

RTS BUS

FLEET

MAINTENANCE

& OPERATIONS

FACILITY

City of Gainesville

CONFORMED

DOCUMENTS

TA /

EJD

11046

TA

MECHANICAL SCHEDULES

29 March 2013

MECHANICAL:

J. ANTHONY ANDRESS

PE - 0046536

Moses & Associates, Inc.

2209 NW 40th Terrace, Ste A Gainesville, Florida 32605 FL License EB-0003097

P 352-372-1911 F 352-372-0186 moses-eng.com

M&A #11211

MAINTAIN 6" ALONG

ALONG BOTTOM RUN

BOTTOM COIL

TOP COIL

SENSOR

TERMINATION

TYPICAL

TRANSMITTER

J-BOX. QUANTITY

VARIES WITH COIL

AREA

SUPPORT RAIL

SENSING ELEMENT

TUBING TO PROTECT SENSING ELEMENT

WIRE

NOTES:

1. PROVIDE 1 LINEAR FOOT OF

SENSING ELEMENT FOR EVERY

SQUARE FOOT OF COIL AREA

NON-METALIC

CAPILLARY 6" Ø

MOUNTING CLIP

COIL

RETURN

SUPPLY

AAV AT HIGH POINT

MANUAL VENT

AAV AT HIGH POINT

MANUAL DRAIN

M

INLET - 2 Ø STRAIGHT PIPE

OUTLET - 5 Ø STRAIGHT PIPE

*NO DEVICES IN STRAIGHT RUN*

NO

NOTES:

1. COIL PIPED TO FAIL OPEN TO COIL.

FLOOR DRAIN

W/FUNNEL

FLOOR

180° BEND

INSULATED

STAINLESS STEEL

DRAIN PAN

CLEANOUT PLUGS

"A"

"B"

"C"

AIR

GAP

PER

CODE

COORDINATE

MINIMUM WITH UNIT

SUPPORT

NOTES:

1. CONTRACTOR SHALL COORDINATE DRAIN DIMENSIONS AND PAD/RAIL HEIGHT TO ENSURE

PROPER COIL DRAINAGE AND CLEARANCE FOR TRAP.

2. WHERE UNIT HEIGHT DOES NOT ALLOW PROPER DRAIN HEIGHT, DRAIN PIPE TO DROP DOWN

THRU FLOOR AND INSTALL TRAP AT FLOOR BELOW. ROUTE PIPING TO NEAREST FLOOR DRAIN.

3. SEE SPECIFICATIONS FOR PIPE MATERIALS.

4. DRAW-THRU UNITS: BLOW-THRU UNITS:

A = SP + 1" A = 1/2"

B = 1/2 SP + 1/2" B = SP + 1/2"

C = 1-1/2 SP + 1-1/2" C = SP + 1"

SP TO BE MAXIMUM STATIC PRESSURE ON DRAIN PAN INCLUDING MAXIMUM FILTER

PRESSURE DROP AND PRESSURE DROP OF FUTURE COMPONENTS OF UNIT IF APPLICABLE.

1/2"

PIPE TO FLOOR DRAIN

PROVIDE AIR GAP FITTING

1"

1/2"

BFP

M

WATER METER

PRESSURE REDUCING VALVE

B&G NO. 12 OR EQUAL SET

@ 20 PSIG

WATTS 909QT, OR EQUAL

BACKFLOW PREVENTER

VENTURI FLOW METER

AIR CHARGING VALVE

PROVIDE AAV AT ALL HIGH

POINTS IN SYSTEM

MOGUL 5 GAL. CHEMICAL

SHOT FEEDER

BLADDER TYPE

COMPRESSION TANK.

ASME SAFETY RELIEF

VALVE-ROUTE DRAIN FULL

SIZE TO FD CUT PIPE

END AT 45 DEGREE

LOW WATER CUTOFF

CONNECT TO GAS PIPING

ELIMINATOR R-3

ROLAIRTROL AIR

DISTRIBUTION HHW PUMP

1 32

BALANCING COCK

G

15 CW MAKEUP

HI CAPACITY AAV PIPE TO FD16

17 NON-SLAM CHECK VALVE

AND SUPPORT PUMP WITH

WALL BRACKET OR STANDS

3" HHWR

3" HHWS

MINIMUM 30 GAL

ACCEPTANCE VOLUME

1/4"

3/4"

G

B

1/4"

B

HWP

18 ROTOMETER TO MEASURE GAS FLOW

3" HHWS

3" HHWS

3" HHWS3" HHWS

3" HHWR3" HHWR3" HHWR

3"

H H

W S

3" H

H W

R

1814 18

HWP3"

H

H W

S

AAV AT ALL HIGH POINTS IN

THE SYSTEM-TYPICAL

PIPE TO FLOOR DRAIN

1/4" TYP

4"

MINIMUM 20 GAL ACCEPTANCE VOLUME.

BLADDER STYLE COMPRESSION TANK

PROVIDE AIR GAP FITTING

AIR COOLED

CHILLER

AIR ELIMINATOR-ROLAIRTROL R-4

MOGUL 5 GALLONS-

CHEMICAL SHOT FEEDER

DOWNSTREAM OF VFM

PIPE DIAMETERS CLEAR

CLEAR UPSTREAM AND 2

PROVIDE 5 PIPE DIAMETERS

45 DEGREE ANGLE

6" OF GRADE, CUT END AT

DRAIN FULL SIZE TO WITHIN

VALVE SET @ 100 PSIG. PIPE

1" ASME PRESSURE RELIEF

BASE MOUNTED END SUCTION

SUPPORT PUMP WITH

AIR CHARGING VALVE

HIGH CAPACITY AAV

CW MAKEUP

NOT USED

WATTS-909QT OR EQUAL-

BACKFLOW PREVENTER

@ 20 PSIG

B&G NO. 12 OR EQUAL, SET

PRESSURE REDUCING VALVE

VIBRATION ISOLATION ON PAD

1"

BFP

3/4"

3/4"

4" CHWS

3/4"

OUTSIDE

OUTSIDE

4" CHWR

TO AHU'S

4" CHWS

FROM AHU'S

4" CHWR CHP

1/4" TYP

CHP

CHILLED WATER PUMP

4" CHWS4" CHWS

4" CHWR CH

M

FM

FM

TS

TS

17 14

16 "ONICON" INSERTION TYPE

FLOW/BTU METER. REFERENCE

MANUFACTURER'S INSTALL

REQUIREMENTS.

17 TEMPERATURE SENSOR WITH WELL

18 CHILLER FLOW SAFETY SWITCH

3" CHW

COIL

RETURN

SUPPLY

AAV AT HIGH POINT

MANUAL VENT

AAV AT HIGH POINT

MANUAL DRAIN

M

INLET - 2 Ø STRAIGHT PIPE

OUTLET - 5 Ø STRAIGHT PIPE

*NO DEVICES IN STRAIGHT RUN*

NO

NOTES:

1. COIL PIPED TO FAIL OPEN TO COIL.

C

DRAFTED BY:

ARCHITECT'S PROJECT NO.:

DATE:

REVISION DATES:

PLANS CHECKED BY:

DATE CHECKED:

PHONE: FAX:

(352) 372-1378 (352) 378-1281

GAINESVILLE FLORIDA

5700 SW 34TH STREET SUITE 1307

32608

AA 0002486

for

A R C H I T E C T S

Gainesville, Florida

0M0.31

RTS BUS

FLEET

MAINTENANCE

& OPERATIONS

FACILITY

City of Gainesville

CONFORMED

DOCUMENTS

TA

11046

CD

MECHANICAL DETAILS

29 March 2013

MECHANICAL:

AVERAGING COIL DISCHARGE TEMP

SENSOR ROUTING DIAGRAM NTS

2 WAY AHU COOLING COIL PIPING DIAGRAM

NTS

CONDENSATE P-TRAP DETAIL

NTS

14HEATING HOT WATER BOILER PIPING DIAGRAM

NTS

AIR COOLED CHILLER PIPING DIAGRAM

NTS

Moses & Associates, Inc.

2209 NW 40th Terrace, Ste A Gainesville, Florida 32605 FL License EB-0003097

P 352-372-1911 F 352-372-0186 moses-eng.com

M&A #11211

J. ANTHONY ANDRESS

PE - 0046536

3 WAY AHU HEATING COIL PIPING DIAGRAM

NTS

S

AIRFLOW MEASURING STATION

ANALOG IN

AMS

ANALOG OUT

DIGITAL IN

DIGITAL OUT

AI

AO

DI

DO

CURRENT SENSING RELAY

BAS COMMUNICATION LINK

DUCT SMOKE DETECTOR (BY DIV 16)

DIFFERENTIAL PRESSURE TRANSMITTER

ELECTRIC-PNEUMATIC SWITCH

ELECTRIC-PNEUMATIC TRANSDUCER

END SWITCH

FLOW SWITCH

RELAY

TEMPERATURE SENSOR (POINT)

OCCUPANCY SENSOR

SPACE THERMOSTAT

TEMPERATURE SENSOR (AVERAGING)

TIME DELAY RELAY

VARIABLE FREQUENCY DRIVE

TWO WAY CONTROL VALVE

THREE WAY CONTROL VALVE

VELOCITY PRESSURE SENSOR

FLOW METER

ACTUATOR FEEDBACK

FIRE OR HIGH TEMPERATURE STAT

FLOAT SWITCH

FREEZESTAT

SPACE HUMIDISTAT

HIGH STATIC PRESSURE SWITCH

HUMIDITY SENSOR

LOW STATIC PRESSURE SWITCH

MOTORIZED ACTUATOR (PNEUMATIC)

DIFFERENTIAL PRESSURE SWITCH

PRESSURE TRANSMITTER

ABOVE FINISHED FLOOR

CHILLED WATER RETURN

CHILLED WATER SUPPLY

EXHAUST AIR

FIRE ALARM CONTROL PANEL

MOTORIZED ACTUATOR (ELECTRIC)

FAIL TO LAST POSITION

FAIL OPEN

FAIL CLOSED

RETURN AIR

HARDWIRE INTERLOCK

HARWIRE INTERLOCK WIRING

STARTER

TEST PORT

EPT

COMM

DP

EP

EP

FS

R

T

OS

TS

VP

TDR

VFD

FM

FB

FR

FS

FZ

H

HI

HS

LL

M

PS

P

AFF

CHWR

EA

FACP

FTL

FO

FC

RA

CHWS

M

CSR

D

TS

I

CONTROLS LEGEND

SSEQUENCE OF OPERATION: CU-11/AHU-1 & CU-12/AHU-12 (STATIC PRESSURE CONTROL)

SAFETY CONTROL SEQUENCES: THE FOLLOWING SAFETY FUNCTIONS SHALL BE OPERATIONAL WHETHER THE

UNIT OPERATION IS IN "HAND" OR "AUTO".

1. SMOKE DETECTORS: SMOKE DETECTORS SHALL BE INSTALLED IN THE SUPPLY AIR DUCTS WHERE SHOWN

ON THE DRAWINGS TO STOP FAN AND SIGNAL THE FIRE ALARM.

START - STOP SEQUENCES: PROVIDE THE FOLLOWING OPERATIONAL AND INTERLOCK FUNCTIONS WHEN THE AIR CONDITIOING UNIT FAN IS STARTED AND STOPPED, UNLESS OTHERWISE NOTED. THESE SEQUENCES SHALL BE FUNCTIONAL FOR ANY REASON THE FAN STARTS-STOPS IN ANY MODE OF OPERATION (ALL H-O-A MODES, ALL

VFD MODES, ALL AUTOMATIC AND SAFETY FUNCTIONS, AND LOCAL MANUAL START-STOP).

1. OUTDOOR AIR SUPPLY AND RETURN DAMPERS: OPEN OA DAMPERS ON FAN START. IF FAN FAILS TO START WITHIN 60 SECONDS AFTER DAMPERS ARE OPEN, CLOSE OA DAMPER AND SIGNAL FAN FAILURE ALARM.

CLOSE OA DAMPER ON FAN STOP.

OCCUPIED/UNOCCUPIED CYCLE: UNIT SHALL RUN CONTINUOUSLY.

1. START: INITIATE THE START SEQUENCE DESCRIBED IN : "START-STOP SEQUENCES".

2. OUTDOOR AIR CONTROL: PROVIDE AIR MONITOR STATION IN OUTDOOR AIR DUCT. MODULATE THE OUTDOOR AIR DAMPER AND RETURN AIR DAMPER IN SEQUENCE TO MAINTAIN OUTDOOR AIRFLOW VOLUME LISTED IN THE AIR HANDLING UNIT SCHEDULE REGARDLESS OF FAN SPEED OR FILTER LOADING. ONCE OUTSIDE AIR DAMPER HAS REACHED 100% AND MORE OUTSIDE AIRFLOW IS NEEDED, MODULATE RETURN AIR DAMPER

CLOSED (NO LESS THAN 50%).

3. FAN SPEED CONTROL: PROVIDE STATIC PRESSURE SENSOR MOUNTED IN SUPPLY AIR DUCT TO MODULATE THE VARIABLE SPEED DRIVE TO MAINTAIN AN INITIAL SET POINT OF 1.0 IN W.G. (ADJUSTABLE). OPTIMIZED BY TAB

CONTRACTOR.

4. COOLING COIL CONTROL: PROVIDE TEMPERATURE SENSOR TO MODULATE THE COOLING CAPACITY AS REQUIRED TO MAINTAIN A CONSTANT SUPPLY AIR TEMPERATURE OF 55°F. RESET THE SUPPLY AIR TEMPERATURE IN RESPONSE TO THE FOLLOWING RESET SCHEDULE: OUTSIDE AIR TEMPERATURE 30°F-70°F (ADJUSTABLE) AND SUPPLY AIR TEMPERATURE RESET RANGE OF 60°F-55°F (ADJUSTABLE). CONTINUE MONITORING RETURN AIR HUMIDITY AND RESET SUPPLY AIR TO 55°F IN THE EVENT RETURN AIR HUMIDITY RISES

ABOVE 60% RH. REMAIN IN DEHUMIDIFICATION MODE FOR A MINIMUM OF 1 HOUR.

EQUENCE OF OPERATION: CU-11/AHU-1 & CU-12/AHU-12 (STATIC PRESSURE CONTROL)

SAFETY CONTROL SEQUENCES: THE FOLLOWING SAFETY FUNCTIONS SHALL BE OPERATIONAL WHETHER THE

UNIT OPERATION IS IN "HAND" OR "AUTO".

1. SMOKE DETECTORS: SMOKE DETECTORS SHALL BE INSTALLED IN THE SUPPLY AIR AND RETURN AIR

DUCTS WHERE SHOWN ON THE DRAWINGS TO STOP FAN AND SIGNAL THE FIRE ALARM.

2. HIGH STATIC PRESSURE LIMIT: PROVIDE SEPARATE HIGH STATIC PRESSURE SWITCH (ADJUSTABLE) UPSTREAM OF ALL DAMPERS TO STOP THE FAN WHEN STATIC PRESSURE RISES TO 4.0 IN W.G.. MANUAL RESET.

START - STOP SEQUENCES: PROVIDE THE FOLLOWING OPERATIONAL AND INTERLOCK FUNCTIONS WHEN THE AIR CONDITIOING UNIT FAN IS STARTED AND STOPPED, UNLESS OTHERWISE NOTED. THESE SEQUENCES SHALL BE FUNCTIONAL FOR ANY REASON THE FAN STARTS-STOPS IN ANY MODE OF OPERATION (ALL H-O-A MODES, ALL

VFD MODES, ALL AUTOMATIC AND SAFETY FUNCTIONS, AND LOCAL MANUAL START-STOP).

1. OUTDOOR AIR SUPPLY AND RETURN DAMPERS: OPEN ALL DAMPERS ON FAN START. IF FAN FAILS TO START WITHIN 60 SECONDS AFTER DAMPERS ARE OPEN, CLOSE DAMPERS AND SIGNAL FAN FAILURE ALARM.

CLOSE SUPPLY AIR, OUTSIDE AIR DAMPER AND RETURN AIR DAMPER ON FAN STOP.

OCCUPIED CYCLE: UNIT RUNS CONTINUOUSLY.

1. START: INITIATE THE START SEQUENCE DESCRIBED IN : "START-STOP SEQUENCES".

2. OUTDOOR AIR CONTROL: PROVIDE AIR MONITOR STATION IN OUTDOOR AIR DUCT. MODULATE THE OUTDOOR AIR DAMPER AND RETURN AIR DAMPER IN SEQUENCE TO MAINTAIN OUTDOOR AIRFLOW VOLUME LISTED IN THE AIR HANDLING UNIT SCHEDULE REGARDLESS OF FAN SPEED OR FILTER LOADING. ONCE OUTSIDE AIR DAMPER HAS REACHED 100% AND MORE OUTSIDE AIRFLOW IS NEEDED, MODULATE RETURN AIR DAMPER

CLOSED (NO LESS THAN 50%).

3. FAN SPEED CONTROL: PROVIDE STATIC PRESSURE SENSOR MOUNTED IN SUPPLY AIR DUCT TO MODULATE THE VARIABLE SPEED DRIVE TO MAINTAIN AN INITIAL SET POINT OF 1.0 IN W.G. (ADJUSTABLE). OPTIMIZED BY TAB

CONTRACTOR.

4. COOLING COIL CONTROL: PROVIDE TEMPERATURE SENSOR TO MODULATE THE COOLING CAPACITY AS REQUIRED TO MAINTAIN A CONSTANT SUPPLY AIR TEMPERATURE OF 55°F. RESET THE SUPPLY AIR TEMPERATURE IN RESPONSE TO THE FOLLOWING RESET SCHEDULE: OUTSIDE AIR TEMPERATURE 30°F-70°F (ADJUSTABLE) AND SUPPLY AIR TEMPERATURE RESET RANGE OF 65°F-55°F (ADJUSTABLE). CONTINUE MONITORING RETURN AIR HUMIDITY AND RESET SUPPLY AIR TO 55°F IN THE EVENT RETURN AIR HUMIDITY RISES

ABOVE 60% RH. REMAIN IN DEHUMIDIFICATION MODE FOR A MINIMUM OF 1 HOUR.

INDICATION: PROVIDE THE FOLLOWING INDICATION AT BAS.

1. FAN STATUS: CURRENT SENSING RELAY FOR AIR HANDLING UNIT FAN.

2. FILTER PRESSURE DROP: DIFFERENT PRESSURE (ANALOG).

3. SUPPLY AIR TEMPERATURE: AVERAGING SENSOR (ANALOG).

4. COOLING COIL LEAVING AIR TEMPERATURE: AVERAGING SENSOR (ANALOG).

5. RETURN AIR TEMPERATURE: POINT SENSOR (ANALOG).

6. RETURN AIR HUMIDITY: (ANALOG).

7. MIXED AIR TEMPERATURE: AVERAGING SENSOR (ANALOG).

8. OUTDOOR AIR DAMPER/COMMAND AND POSITION: PERCENT OPEN (ANALOG).

9. RETURN AIR DAMPER/COMMAND ANDPOSITION: PERCENT OPEN (ANALOG).

10. VARIABLE SPEED DRIVE: PERCENT FULL SPEED OR HERTZ (ANALOG).

11. FAN START/STOP COMMAND: (BINARY)

12. OUTDOOR AIR FLOW: CFM (ANALOG).

13. OUTDOOR AIR TEMPERATURE: (ANALOG).

14. STATIC PRESSURE: STATIC PRESSURE IN SUPPLY DUCT (ANALOG).

15. ALL SET POINTS.

ALARMS: PROVIDE THE FOLLOWING ALARMS.

1. FAN FAILURE: FAN FAILURE FOR ANY REASON AND IF FAN FAILURE IS DUE TO A MANUAL SHUTDOWN AT

THE VFD, BAS SHALL RESTART FAN WHEN VFD IS RETURNED TO NORMAL.

2. FILTER PRESSURE DROP HIGH: (PRE-FILTER OR FINAL FILTER)

3. HIGH STATIC PRESSURE SHUTDOWN: 4.0 IN W.G.

4. HIGH SUPPLY AIR TEMPERATURE: GREATER THAN 3°F ABOVE SETPOINT

5. STATIC PRESSURE: LESS THAN 0.5 IN. WG BELOW SETPOINT.

OA

FC

FO

RA

SA

TO FACP

P R

E -F

IL

TE

R

BOLD LINE INDICATES

LIMITS OF AHU

CABINET

C

C

DX VAV SPLIT SYSTEM CONTROL DIAGRAM

NOT TO SCALE

SUPPLY

FAN

F A

N S

P E

E D

C O

N

TR

O L

S

TA

R T/

S

TO

P

F/A SHUT DOWN

VFD

PS

TS

MAIAO

AI AI

TS TS

DI

CSR TS

AI

SP

AI

DM

AI

AO

AO DO

A

FT

E R

F

IL

TE

R

TS

AMS

AI

AI

LOCATE APPROXIMATELY

2/3 DOWN SA DUCT

AAON

CONTROLLER

T O

B A

S B

A C

N E

T /M

S

TP

C O

M M

FOR CU/AHU-11 AND CU/AHU-12

DIAI

TS

HS

AI

AI

AO

RSRL

AI

TS

HL

DI

ALL CONTROL DEVICES AND FUNCTIONS

WITHIN THIS DASHED LINE BOX ARE PROVIDED

BY THE A/C EQUIPMENT MANUFACTURER

SA

TO FACP

P R

E -F

IL

TE

R

BOLD LINE INDICATES

LIMITS OF AHU

CABINET

H

C

HHWR

HHWS

HHW HEATING AHU CONTROL DIAGRAM

NOT TO SCALE

SUPPLY

FAN

PS TS

AI

D

M

AI

AO

A

FT

E R

F

IL

TE

R

CSRDI

DO

RA

TS

AI

PS

DI DI

APPLICABLE FOR HU-11 AND HU-12

AI SPACE TEMP

SPACE SENSOR

T

HEATING HOT WATER AHU SEQUENCE OF OPERATION

SAFETY CONTROL SEQUENCES: PROVIDE THE FOLLOWING SAFETY FUNCTIONS:

1. SMOKE DETECTORS: PROVIDE SMOKE DETECTOR(S) IN THE SUPPLY AIR DUCT AND WHERE SHOWN ON THE

DRAWINGS TO SIGNAL THE FIRE ALRM AND STOP THE FAN.

START-STOP SEQUENCES: PROVIDE THE FOLLOWING OPERATIONAL AND INTERLOCK FUNCTIONS WHEN THE AHU IS STARTED AND STOPPED. UNLESS OTHERWISE NOTED THESE SEQUENCES SHALL BE FUNCTIONAL FOR ANY REASON THE FAN STARTS OR STOPS IN ANY MODE OF OPERATION (ALL AUTOMATIC AND SAFETY FUNCTIONS, AND LOCAL MANUAL START-STOP).

1. BOILER/HHW PUMPS START: PROVIDE SPACE THERMOSTAT SET AT 65°F (ADJUSTABLE) TO SIGNAL A CALL FOR BOILER/HHW PUMP SYSTEM TO START AND ENABLE HU-11 AND HU-12. SEE BOILER/HHW PUMPS SEQUENCE OF OPERATION. ONCE THIS SYSTEM IS CIRCULATING HHW AT THE DESIGN TEMPERATURE CONTINUE AHU START

AS FOLLOWS.

2. FAN START: SIGNAL FAN TO START.

3. HEATING HOT WATER VALVE: ENABLE CONTROLS ON FAN START. CLOSE VALVE TO COIL ON FAN STOP.

ON CYCLE:

1. START: INITITATE THE START SEQUENCE DESCRIBED IN "START-STOP SEQUENCES"

2. HEATING HOT WATER COIL CONTROL: PROVIDE A POINT TYPE TEMPERATURE SENSOR IN THE SUPPLY AIR DUCT LEAVING THE UNIT AND MODULATE THE HHW CONTROL VALVE TO MAINTAIN THE SCHEDULED LEAVING AIR

TEMPERATURE OF 85°F.

OFF CYCLE:

STOP: INTIATED THE STOP SEQUENCE DESCRIBED IN "START-STOP SEQUENCES"

INDICATIONS

1. FAN STATUS: CURRENT SENSING RELAY FOR FAN.

2. PRE-FILTER PRESSURE DROP: ADJUSTABLE DIFERENTIAL PRESSURE SWITCH.

3. AFTER-FILTER PRESSURE DROP: ADJUSTABLE DIFERENTIAL PRESSURE SWITCH.

4. RETURN AIR TEMPERATURE: POINT SENSOR (ANALOG).

5. SUPPLY AIR TEMPERATURE: POINT SENSOR (ANALOG).

6. HEATING HOT WATER VALVE POSITION: PERCENT OPEN (ANALOG).

7. SPACE TEMPERATURE

8. FAN COMMAND

ALARMS

1. FAN FAILURE: SIGNAL ALARM IF FAN IS OFF WHEN CALLED TO BE ON.

2. HIGH PRE-FILTER PRESSURE DROP: 1.0 IN. WG (ADJUSTABLE)

2. HIGH AFTER-FILTER PRESSURE DROP: 2.0 IN. WG (ADJUSTABLE)

3. LOW SUPPLY AIR TEMPERATURE: ALARM IF BELOW 80°F.

COMPUTER ROOM A/C UNIT CONTROL DIAGRAM

NTS

ROOM TEMPERATURE

AND RELATIVE

HUMIDITY SENSORS

FOR BAS MONITORING.

LOCATE ON "COLD

AISLE" SIDE OF RACKS.

UNIT CONTROL PANEL

WITH LARGE GRAPHICS

DISPLAY AND (BY CRAC

MANUFACTURER) LCD

SCREEN. PROVIDE

NETWORK INTERFACE

CARD FOR INTEGRATION

TO BAS VIA BACNET MSTP.

PUSH-BUTTON

UNIT DISCONNECT

(COORDINATE WITH DIV.

16 IN ACCORDANCE

WITH NEC 645.10.)

AI

SA

RA

AI

FILTER

DX COOLING COILS

SCR ELECTRIC REHEAT COIL

HUMIDFICATION SECTION

FIRE ALARM

SHUTDOWN

RELAY BY DIV 16

PLENUM FAN(S)

DOWN DISCHARGE PLENUM

SECTION WITH REAR DUCT

ATTACHMENT COLLAR

T

RH

TS

R

TS

COMMTO BAS

BACNET/MSTP

AI

RH

DI STATUS

CSR

AI

AI

REMOTE CONDENSER

MODULE

AI

TS

COMPUTER ROOM A/C CONTROL SEQUENCE (CRAC-11, CRAC-12)

FAN: UNIT FAN SHALL RUN CONTINUOUSLY.

TEMPERATURE CONTROL

COOLING SHALL BE ACTIVATED UPON A RISE IN ROOM TEMPERATURE ABOVE SETPOINT AND DEACTIVATED UPON A

DROP IN ROOM TEMPERATURE BELOW SETPOINT USING A 3°F DIFFERENTIAL.

HUMIDITY CONTROL

HUMIDIFIER SHALL BE ACTIVATED UPON A DROP IN ROOM HUMIDITY BELOW SETPOINT. UPON AN INCREASE IN ROOM HUMIDITY ABOVE SETPOINT OVERRIDE COOLING ON AND MAINTAIN ROOM TEMPERATUER USING REHEAT

COIL.

SETPOINTS

COOLING = 75°F (ADJUSTABLE)

HUMIDITY = 52%RH (ADJUSTABLE)

CONTROLS SYSTEM RISER DIAGRAM

NTS

BAS

SERVER

LOCATED IN BLDG 1

ROOM 1126

BACNET/IP

BACNET/IP

BACNET/MSTP

AHU-51

AAC

BLC

BLDG 1

BACNET/IP

AHU-51

VFD

VAV- 5201

THRU

VAV-5229

ASC

EF-501

THRU

EF-…