Text version

Erie VA

Erie, Pennsylvania ( DATE: January 7, 2021

Legend

Structure

Blank Tile

Airflow Supply (+ Supply)

Light

Airflow Return (- Exhaust)

Airflow Direction

(FAIL)

Airflow Direction (Pass)

Rest Room

Lobby

Break Room

Bio Med Office

Sterile Storage

Bio Med

Office Cart Washes

Maint Room

Sterilizer Room

Closet

Gowning Rest Room

.0003” W.C.

.0337” W.C.

.0071” W.C.

+86

+57

-120

.0493” W.C.

-46

.0055” W.C.

-73

.0077” W.C.

.0031” W.C.

-192

.0138” W.C.

+150

.0043” W.C.

.0197” W.C.

+208 .0079” W.C. -31

-403

.0371” W.C.

-0

+196

+232

+275

+92

+137 +208

-39

.0188” W.C.

-690

+96

+155

.0030” W.C.

.0047” W.C.

.0042” W.C.

-218

+137

.0012” W.C.

.0002” W.C.

-122

+75

.0021” W.C.

-234

+150

+143

+232

+170

+170

+243

+233 +209

-171

-633Steam Maintenance

Room

+201

-481

-413

.0010” W.C.

.0077” W.C.

Rest Room

-51

-120 +83

+84

-205

-117

+80

+82

.0001” W.C.

.0003” W.C.

-48

Prep & Pack

(SEE Next Drawing)

Decontamination

(SEE Next Drawing)

+274

Entrance

Clean Area

Erie VA, SPS Area

DATE: January 7, 2021

Overview

.0211” W.C.

Prep & Pack

-48 -32

-72

-81

-193

-80

+718

+305

+934

+752 +603

Decontamination

-836

-797

+244

+222

-84

-371

+98 +224

+80 -597

+246

-527

Erie VA, SPS Area

.0230” W.C.

+73

-263

+190

+218

+205

+192

+29

+74

+78

+55

+70

-48 -299

-128

+339

+190.0096” W.C.

.0147” W.C. .0022” W.C.

Endoscopy 1 Endoscopy 2

Erie VA, Endoscopy 1 & 2

+213

-99

+192

+193

+192

+211

+198

.0588” W.C.

+206

-679

+196

+202

+219

+184

+211

.0516” W.C.

OR 1

.0068” W.C.

+29

-618 .0208” W.C.

Erie VA, OR 1

OR 2

+202+187

+182

+197+177

+207

.0208” W.C.

+244

-503

+203

+193 +196

+223

+197

.0168” W.C.

-1072

.0068” W.C.

Sub Sterile

+129

-618

.0588” W.C.

Erie VA, OR 2

.0123” W.C.

.0113” W.C.

.0171” W.C.

.0100” W.C.

.0138” W.C.

+48

+115

+171

+192

+171

UCC Triage

UCC 3

UCC 4

UCC 5

UCC 6

-566

-548

-511

-603

-379

Erie VA, UCC

+92

-254

.0125” W.C.

PAUC 3

Erie VA, PACU 3

Histology

.0374” W.C.

-244

+67

+86

-556

+32

+84 *Speed control set to 250 CFM

Erie VA, Histology

.0106” W.C.

Morgue

.0069” W.C.

+205+207

-607

Erie VA, Morgue

.0249” W.C.

Ante Room

Cleanroom Chemo Room

Chemo Hood LFH

-266 +233

+712

-271

+213

.0114” W.C.

.0344” W.C.

Erie VA, Pharmacy Area

Room 533 Contact Isolation

Erie VA, Room 533 Contact Isolation

Erie, Pennsylvania DATE: January 7, 2021

Overview

.0066” W.C.

+135

-328

-52

.0004” W.C.

Executive Summary
Room Pressurization Test Summary
INSTRUMENTATION: Electronic Air Data Multimeter
Model: Shortridge, ADM-870
RESULTS:

File details come from the government source that posted it. Updated .