Text version
Erie VA
Erie, Pennsylvania ( DATE: January 7, 2021
Legend
Structure
Blank Tile
Airflow Supply (+ Supply)
Light
Airflow Return (- Exhaust)
Airflow Direction
(FAIL)
Airflow Direction (Pass)
Rest Room
Lobby
Break Room
Bio Med Office
Sterile Storage
Bio Med
Office Cart Washes
Maint Room
Sterilizer Room
Closet
Gowning Rest Room
.0003” W.C.
.0337” W.C.
.0071” W.C.
+86
+57
-120
.0493” W.C.
-46
.0055” W.C.
-73
.0077” W.C.
.0031” W.C.
-192
.0138” W.C.
+150
.0043” W.C.
.0197” W.C.
+208 .0079” W.C. -31
-403
.0371” W.C.
-0
+196
+232
+275
+92
+137 +208
-39
.0188” W.C.
-690
+96
+155
.0030” W.C.
.0047” W.C.
.0042” W.C.
-218
+137
.0012” W.C.
.0002” W.C.
-122
+75
.0021” W.C.
-234
+150
+143
+232
+170
+170
+243
+233 +209
-171
-633Steam Maintenance
Room
+201
-481
-413
.0010” W.C.
.0077” W.C.
Rest Room
-51
-120 +83
+84
-205
-117
+80
+82
.0001” W.C.
.0003” W.C.
-48
Prep & Pack
(SEE Next Drawing)
Decontamination
(SEE Next Drawing)
+274
Entrance
Clean Area
Erie VA, SPS Area
DATE: January 7, 2021
Overview
.0211” W.C.
Prep & Pack
-48 -32
-72
-81
-193
-80
+718
+305
+934
+752 +603
Decontamination
-836
-797
+244
+222
-84
-371
+98 +224
+80 -597
+246
-527
Erie VA, SPS Area
.0230” W.C.
+73
-263
+190
+218
+205
+192
+29
+74
+78
+55
+70
-48 -299
-128
+339
+190.0096” W.C.
.0147” W.C. .0022” W.C.
Endoscopy 1 Endoscopy 2
Erie VA, Endoscopy 1 & 2
+213
-99
+192
+193
+192
+211
+198
.0588” W.C.
+206
-679
+196
+202
+219
+184
+211
.0516” W.C.
OR 1
.0068” W.C.
+29
-618 .0208” W.C.
Erie VA, OR 1
OR 2
+202+187
+182
+197+177
+207
.0208” W.C.
+244
-503
+203
+193 +196
+223
+197
.0168” W.C.
-1072
.0068” W.C.
Sub Sterile
+129
-618
.0588” W.C.
Erie VA, OR 2
.0123” W.C.
.0113” W.C.
.0171” W.C.
.0100” W.C.
.0138” W.C.
+48
+115
+171
+192
+171
UCC Triage
UCC 3
UCC 4
UCC 5
UCC 6
-566
-548
-511
-603
-379
Erie VA, UCC
+92
-254
.0125” W.C.
PAUC 3
Erie VA, PACU 3
Histology
.0374” W.C.
-244
+67
+86
-556
+32
+84 *Speed control set to 250 CFM
Erie VA, Histology
.0106” W.C.
Morgue
.0069” W.C.
+205+207
-607
Erie VA, Morgue
.0249” W.C.
Ante Room
Cleanroom Chemo Room
Chemo Hood LFH
-266 +233
+712
-271
+213
.0114” W.C.
.0344” W.C.
Erie VA, Pharmacy Area
Room 533 Contact Isolation
Erie VA, Room 533 Contact Isolation
Erie, Pennsylvania DATE: January 7, 2021
Overview
.0066” W.C.
+135
-328
-52
.0004” W.C.
| Executive Summary |
| Room Pressurization Test Summary |
| INSTRUMENTATION: Electronic Air Data Multimeter |
| Model: Shortridge, ADM-870 |
| RESULTS: |
File details come from the government source that posted it. Updated .