RHS_Rehabilitation_of_The_Access_Ramp_of_Margaret_E._Morton_Government_Center_2-13-26.pdf
PDF 6 MB Posted
- Solicitation number
- MNB035263
- Issued by
- Fairfield County, Bridgeport City, Connecticut
About this file
This is a set of construction design drawings and specifications for the City of Bridgeport's rehabilitation project of the access ramp at Margaret E. Morton Government Center, located at 999 Broad Street in Bridgeport, Connecticut. The project involves comprehensive repairs to the existing ramp structure, including structural steel repairs at three distinct sites, concrete deck repairs, joint reconstruction, waterproofing installation, and bituminous overlay paving. Key work items include replacement of deteriorated structural steel members and connections at floor beam and stringer locations, installation of temporary support systems during repairs, partial depth concrete patching, installation of preformed expansion joints with impregnated foam glands, trench drain replacement and cleaning, masonry repointing, membrane waterproofing application, and final asphalt paving. The project has a bid number of MNB035263, with electronic submissions required through the City's OpenGov Procurement Portal with a deadline of 2:00 pm on Tuesday, March 24, 2026. The design was prepared by RHS Consulting, with drawings dated February 11-13, 2026. A pre-bid site visit and coordination with the City's designated building/facility manager are required prior to mobilization, and all contractors must comply with CTDOT Standard Specifications, OSHA regulations, and applicable City of Bridgeport requirements.
The specifications establish strict construction sequencing requiring surface preparation and structural steel repairs prior to any deck repairs, with temporary support brackets used solely for stability and jacking or lifting prohibited. Live load limits restrict construction equipment to an AASHTO H-5 maximum with gross vehicle weight of 10,000 pounds and maximum axle loading of 6,000 pounds, with vibratory compaction equipment explicitly prohibited on the deck structure. Concrete repair materials must achieve minimum compressive strength of 3,500 psi, and all reinforcing steel must be galvanized ASTM A615 Grade 60. The contractor bears full responsibility for water control, dewatering, dust containment during steel surface preparation, worker safety, temporary shoring and bracing, protection of existing utilities and building systems, and restoration of any damage caused by construction operations at no additional cost to the owner. All work must comply with lead and asbestos safety protocols, with no lead-based paint detected in laboratory samples but lead awareness training and monitoring required per OSHA standards. Material selections include spray-applied cold liquid elastomeric waterproofing membranes, preformed expansion joint systems, and specific concrete mix designs identified by class designation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DISTRICT 1 DISTRICT 2
DISTRICT 3
DISTRICT 4
LOCATION PLAN
NOT TO SCALE
WOODSTOCK
THOMPSON
ASHFORD EASTFORD
POMFRET
BROOKLYN
HAMPTONCHAPLIN
MANSFIELD
PUTNAM
STERLINGPLAINFIELD
CANTERBURY
SCOTLAND
WINDHAM
LEBANON
HEBRON
EAST
HAMPTON COLCHESTER
GRISWOLD
STONINGTON
STONINGTON
NORTH
LEDYARD
WATERFORD
MONTVILLE
BOZRAH
FRANKLIN
EAST
LYME
SALEM
SPRAGUE
LISBON
EAST HADDAM
LYMECHESTER
ESSEX
OLD
CLINTON
COLUMBIA
HADDAM
KILLINGWORTH
WESTBROOK
DEEP RIVER
LYME
M A R
LB
O R O
U G
H
VOLUNTOWN
PORTLAND
PRESTON
REDDING
NEW
FAIRFIELD
BETHEL
NEWTOWN
BROOKFIELD
ROXBURY
SOUTHBURY
OXFORD
WOODBURY
SHERMAN
NEW
MILFORD
KENT
SHARON GOSHEN
WARREN
WASHINGTON
BETHLEHEM
MORRIS
LITCHFIELD
HARWINTON
WATERTOWN
CANAAN
NORTH
NORFOLK
CORNWALL
COLEBROOK
WINCHESTER
HARTLAND
BARKHAMSTED
NEW
HARTFORD
CANTON
GRANBY
SUFFIELD
EAST
GRANBY
SIMSBURY
AVON
SEYMOUR
ANSONIA
DERBY
PROSPECT
PLYMOUTH
BURLINGTON
FARMINGTON
CANAAN
RIDGEFIELD
SALISBURY
WALLINGFORD
W O
O D
B R
ID
G E
BETHANY
HAMDEN
SHELTON
MONROE
EASTON
WESTON
WILTON
CANAAN
NEW
GREENWICH
DARIEN
WESTPORT
FAIRFIELD
TRUMBULL
ORANGE
MILFORD
S T R
A T F O
R
DBRIDGEPORT
E A S T
H
A V E N
BRANFORD
GUILFORD
NORTH
BRANFORD
HAVEN
NORTH
NAUGATUCK
MIDDLEBURY
MADISON
NORWALK
W E S T
H
A V E N
SAYBROOK
OLD
LONDON
NEW
WATER
BRIDGE-
FALLS
BEACON
MIDDLETOWN
MERIDEN
CHESHIRE
SOUTHINGTONWOLCOTT
BRISTOL PLAINVILLE
CROMWELLBERLIN
BOLTON
GLASTONBURY
ANDOVER
MANCHESTER
HARTFORD
BRITAIN
NEW
HARTFORD
WEST EAST
BLOOMFIELD
WINDSOR
SOUTH
WINDSOR
WINDSOR
EAST
ENFIELD SOMERS STAFFORD UNION
WILLINGTON
TOLLAND
ELLINGTON
VERNON
COVENTRY
DURHAM
N E
W
IN
G T
O N
LOCKS
WINDSOR
FIELD
MIDDLE-
WETHERSFIELD
STATE OF CONNECTICUT
N
D E
P A
R T
M E
N
T
OF TRAN
S
P O
R T
A T I
O N
C
ONNECTICU
T
M A S S A C H U S E T T S
R H
O D
E
I S
L A
N D
N
W
Y
O
R
K
DRAWING NO.
SHEET NO.
TORRINGTON KILLINGLY
GROTON
STAMFORD
DANBURY
WATERBURY
G-1
N
D E
P A
R T
M E
N T
OF TRAN
S
P O
R T
A T I
O N
C
O
NNECTICU
T
LIST OF DRAWINGS
SHEET NO. SHEET TITLE
JOSEPH P. GANIM
MAYOR
PROJECT LOCATION
DIRECTOR OF PUBLIC FACILITIES
LUIS BURGOS
MARGARET E. MORTON GOVERNMENT CENTER
REHABILITATION OF THE ACCESS RAMP OF
NOT TO SCALE
LOCATION MAP
BRIDGEPORT, CT
999 BROAD STREET
PROJECT AREA
SUBMITTED BY:
PROPOSED REPAIR DETAILS-RENDERS
STRUCTURAL SLAB REPAIR DETAILS
MISCELLANEOUS REPAIR DETAILS
JOINT REPAIR DETAILS-3
JOINT REPAIR DETAILS-2
JOINT REPAIR DETAILS-1
TRENCH DRAIN REPAIR DETAILS
MISCELLANEOUS DETAILS-2 AT C2 COLUMN
MISCELLANEOUS DETAILS-1 AT C2 COLUMN
MISCELLANEOUS DETAILS AT F2 COLUMN
FRAMING PLAN
DECK PLAN
EAST & SOUTH ELEVATIONS
GENERAL NOTES
GENERAL NOTES
TITLE SHEET
CITY OF BRIDGEPORT BID NO. MNB035263
RHS CONSULTING DESIGN
345 HIGHLAND AVE., SUITE 201, CHESHIRE, CT 06410
DESIGNED BY:
27A
L O
D G E 95
P e q u o n n o c k
R A I L
R O
A D
CO
ST.
ST.
GOLD
HIL
L
T E
R
GOLDEN
AVE.
M
ID
D L E
ST.
ST.
ST.
ST.
STA.
R.R.
R D
WALL
CANNON
ST.
S T
BANKB
R
O A
D
C O
U R
T
L A
N D
S T
B O
U L E
V A
R D
W A
R R
E N
AVE.
ST.
N O
F R O
N T
A G E
S T
MILNE
ST.
ST.S
T
CALHOUN
PL.
S T
S A N
FO
R D
P L
T
ER
.W
A S H
IN
G T O
N
W A S
H
IN
G T
O N
W E S T
W A Y
S T
FA
IR
F
IE
LD
W E S T
JO
HN
STATE
A V
E
LI
BERTY
ST.
W.
PROSPECT
A V E
SOUTH
M Y
R T
L E
ST.
ST.
ST
AVE
S T
CK
R D
B R
O A
D
FR
O
N T A
G E
ALLEN
ST.L
A F
A Y
A V
E
S T
R A T F
O R
D
Pt.
Steel
M A
R K
L E
C T
27A
WAY
CESAR
BATALLA
W A
T E
R
L A
F A
Y
E T
T E
S Q
W A
T E
R
A C C E S S
LAFAY-
ETTE
CHAPEL
ST.
S T
S T
ST.
ELM
ST.
#2
ELM
ST.
#1
#1
I C
R
L A
F A
Y E
T T
E
27C
27B
HAVEN
NEW
HARTFORD
NORWICH
THOMASTON
HILL
ROCKY
APPROVED BY THE ENGINEER.
REQUIRED MEASUREMENTS AND THE EXTENT OF THE PROPOSED WORK HAS BEEN
ORDER ANY MATERIAL OR COMMENCE ANY FABRICATION UNTIL HE HAS MADE THE
ASSUME FULL RESPONSIBILITY FOR THEIR ACCURACY. THE CONTRACTOR SHALL NOT
MEASUREMENTS NECESSARY TO ASSURE PROPER FIT OF THE FINISHED WORK AND SHALL
AND ARE NOT GUARANTEED. THE CONTRACTOR SHALL PERFORM ALL SURVEY AND FIELD
REFERENCE ONLY. THEY HAVE BEEN TAKEN FROM THE ORIGINAL DESIGN DRAWINGS
DIMENSIONS OF THE EXISTING STRUCTURE SHOWN ON THESE PLANS ARE FOR GENERAL 14.
CONSTRUCTION PERIOD.
OTHER THAN THOSE ON THE PLANS WHEREVER REQUIRED DURING THE ENTIRE
THE CONTRACTOR MUST PROVIDE ADEQUATE SHORING AND/OR TEMPORARY SUPPORT 13.
CONSTRUCTION DEBRIS IN THE VICINITY OF WORK.
THE CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL AND DISPOSAL OF ALL 12.
OWNER AT NO EXTRA COST TO THE OWNER.
DAMAGE TO SAME ELEMENTS OCCURS, IT SHALL BE RECTIFIED TO THE SATISFACTION OF
THE EXISTING STRUCTURAL AND ARCHITECTURAL ELEMENTS AND UTILITIES. IF ANY
TAKE ADEQUATE PRECAUTION TO PROTECT PUBLIC SAFETY AND PREVENT DAMAGE TO
STRUCTURE AND SHALL STRUCTURE DURING THE ENTIRE ALTERATION OF THE EXISTING
CONTRACTOR ALONE SHALL BE RESPONSIBLE FOR THE SAFETY OF THE EXISTING 11.
TO THE OWNER.
ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS WITHOUT ADDITIONAL COST
OR PERFORMING ANY WORK THAT MAY BE REQUIRED TO COMPLETE WORK IN
WILL IN NO WAY RELIEVE THE SUCCESSFUL BIDDER FROM FURNISHING ANY MATERIALS
THE SITE AND NOT BEING FAMILIAR WITH THE EXISTING CONDITIONS AND LIMITATIONS
CONDITIONS AND LIMITATIONS PRIOR TO SUBMITTING THEIR PROPOSAL. FAILURE TO VISIT
CAREFULLY, VISIT THE JOB SITE AND FULLY INFORM THEMSELVES TO ALL EXISTING
ALL CONTRACTORS ARE REQUIRED TO EXAMINE THE DRAWINGS AND SPECIFICATIONS 10.
FIELD PRIOR TO THE START OF WORK.
THE CONTRACTOR SHALL VERIFY ALL EXISTING OPENING SIZES AND LOCATIONS IN THE 9.
MEMBERS UNDER GENERAL COST OF PROJECT.
STRUCTURAL FRAMING TO VERIFY AND MEASURE THE EXISTING CONDITIONS AND
THE CONTRACTOR SHALL ALLOW FOR THE COST OF OPENING AND EXPOSING EXISTING 8.
RESOLUTION.
EXISTING CONDITIONS AND SUBMIT SAME TO THE ENGINEER FOR REVIEW AND
CONTRACTOR MUST MAKE NECESSARY AND ACCURATE SKETCHES SHOWING THE
VARY FROM THOSE SHOWN ON THE STRUCTURAL DRAWINGS AND DETAILS, THE
DRAWINGS. IN THE EVENT THAT EXISTING CONDITIONS OR DETAILS OF CONSTRUCTION
FIELD DIMENSIONS OF ALL EXISTING MEMBERS PRIOR TO THE PREPARATION OF SHOP
THE CONTRACTOR SHALL EXPOSE THE EXISTING STRUCTURE, VERIFY AND CHECK 7.
VERIFY THE DRAWINGS AND TO PERFORM HIS WORK PROPERLY.
AT THE JOB SITE AND SHALL TAKE ANY AND ALL OTHER MEASUREMENTS NECESSARY TO
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND ELEVATIONS BY MEASUREMENTS 6.
ORDERING AND/OR FABRICATING MATERIALS. DO NOT SCALE DRAWINGS.
MATERIALS. THE CONTRACTOR SHALL FIELD CHECK ALL DIMENSIONS PRIOR TO
INFORMATION AND SHALL NOT BE USED FOR ORDERING AND/OR FABRICATING
ALL DIMENSIONS INDICATED ON THE DRAWINGS ARE BASED UPON THE AVAILABLE 5.
WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER.
THE CONTRACTOR SHALL MAKE NO DEVIATION FROM DESIGN DRAWINGS WITHOUT 4.
SPECIFICATIONS, THE MOST RIGID REQUIREMENTS SHALL GOVERN.
IN ANY CASE OF CONFLICT BETWEEN THE DRAWINGS, NOTES, DETAILS AND 3.
SIMILAR TO THAT SHOWN AT CORRESPONDING PLACES SHALL BE REPEATED.
IMPLIED TO BE WORK NOT INDICATED ON A PART OF THE DRAWINGS BUT REASONABLY 2.
2015 INTERNATIONAL EXISTING BUILDING CODED.
2015 INTERNATIONAL BUILDING CODEC.
2018 CONNECTICUT STATE BUILDING CODEB.
CTDOT FORM 819 WITH JULY 2025 SUPPLEMENTAL SPECIFICATIONSA.
THE FOLLOWING CODES AND STANDARDS, UNLESS OTHERWISE NOTED.
CODES REFERENCED WITHIN THESE DOCUMENTS. THE PROJECT DOCUMENTS REFER TO
PERFORM ALL CONSTRUCTION IN CONFORMANCE WITH THE BUILDING AND DESIGN 1.
BRIDGEPORT. CONTRACTOR MUST COORDINATE WITH THE CITY'S PUBLIC FACILITIES DEPARTMENT.
THROUGH THE WORK SITE ARE EITHER RELOCATED OR TEMPORARILY DISCONNECTED BY THE CITY OF PRIOR TO ANY DEMOLITION WORK, THE CONTRACTOR SHALL ENSURE ANY ACTIVE UTILITIES PASSING 8.
DURING DEMOLITION. REPLACEMENT MATERIAL MUST MATCH EXISTING.
CONTRACTOR SHALL BE COMPLETELY RESPONSIBLE FOR THE REPAIRS OF ALL AFFECTED AREAS 7.
REMAIN IN PLACE.
CONTRACTOR SHALL PRESERVE AND PROTECT ALL EXISTING UTILITIES, DUCTS, AND EQUIPMENTS TO 6.
TEMPORARY SHORING AND BRACING OTHER THAN THOSE SHOWN ON THE PLANS.
CONSTRUCTION. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE DESIGN OF SUCH
THE CONTRACTOR SHALL PROVIDE TEMPORARY SHORING AND BRACING AS REQUIRED DURING 5.
CONDITION.
PERFORMED IN SUCH A MANNER AS TO ENSURE THAT THE REMAINING STRUCTURE IS IN STABLE
STRUCTURE SHALL BE REPAIRED WITH MATERIAL MATCHING EXISTING. DEMOLITION MUST BE
PROPERLY EXECUTE THE DETAILS SHOWN ON THE DRAWINGS. ANY DAMAGE TO THE REMAINING
THE CONTRACTOR SHALL NOT REMOVE MORE OF THE EXISTING STRUCTURE THAN NECESSARY TO 4.
SAFETY OF THE WORKERS, OCCUPANCE AND THE EXISTING STRUCTURE.
THE CONTRACTOR IS FULLY RESPONSIBLE FOR THE MEANS AND METHODS OF DEMOLITION AND THE 3.
PROPERTY AND THE SPREADING OF DUST.
CAREFUL, ORDERLY AND CONTROLLED MANNER TO AVOID HAZARDS TO PERSONS, DAMAGE TO
OPERATIONS. SELECTIVE REMOVAL AND DEMOLITION OPERATIONS SHALL BE PERFORMED IN A
SELECTIVE REMOVAL THE CONTRACTOR SHALL USE QUALIFIED, EXPERIENCED PERSONNEL FOR2.
ORDINANCES AND REGULATIONS.
AND SHALL BE REMOVED FROM THE SITE IN ACCORDANCE WITH ALL APPLICABLE LAWS, CITY
REMOVED MATERIALS, UNLESS OTHERWISE NOTED, BECOMES THE PROPERTY OF THE CONTRACTOR 1.
WITHOUT PRIOR CONSENT FROM THE ENGINEER.
CONSTRUCTION JOINTS, OTHER THAN THOSE SHOWN ON THE PLANS, SHALL NOT BE PERMITTED 8.
ALL REINFORCEMENT SHALL HAVE TWO INCHES COVER UNLESS DIMENSIONED OTHERWISE.7.
PROVIDED BY THE CONTRACTOR TO FURNISH SUPPORT FOR ALL BARS.
SUPPLEMENTAL REQUIREMENTS. IF REQUIRED, ADDITIONAL BARS, STIRRUPS AND CHAIRS SHALL BE
REINFORCEMENT SHALL CONFORM TO THE REQUIREMENTS OF ASTM A767, CLASS 1, INCLUDING
ALL REINFORCEMENT SHALL BE GALVANIZED AFTER FABRICATION UNLESS NOTED OTHERWISE. ALL 6.
COVER UNLESS DIMENSIONED OTHERWISE.
A615, GRADE 60, INCLUDING SUPPLEMENTAL REQUIREMENTS, AND SHALL HAVE TWO INCHES
ALL REINFORCING BARS SHALL BE GALVANIZED AND CONFORM TO THE REQUIREMENTS OF ASTM 5.
ALL EXPOSED EDGES SHALL HAVE A 1" X 1" BEVEL UNLESS OTHERWISE DIMENSIONED.4.
FOR DETAILS OF PARTIAL DEPTH PATCH, SEE SPECIAL PROVISIONS.3.
CLASS PCC04481 BASED ON f'c = 4,000 psi SHALL BE USED FOR THE SURFACE REPAIR CONCRETE.2.
CONCRETE RAMP AT TRENCH DRAIN.
CLASS PCC04462 BASED ON f'c = 4,000 psi SHALL BE USED FOR THE JOINT REPAIRS, AND 1.
OTHERWISE NOTED.
ALL BOLTS SHALL MEET THE REQUIREMENTS OF ASTM A325 H.S. BOLTS, TYPE 3 EXCEPT WHERE 11.
OTHERWISE.
CONDITIONS, UNLESS NOTED, PREPARED IN ACCORDANCE WITH AASHTO SPECIFICATIONS
ALL CONTACT SURFACES ON BOLTED CONNECTIONS SHALL BE FOR CLASS C SLIP CRITICAL10.
LENGTH DIMENSIONS ARE MEASURED ALONG THE CENTERLINE OF THE BEAM.9.
STRUCTURAL ELEMENTS UNTIL THE TOTAL STRUCTURE IS IN BEING.
THE CONTRACTOR SHALL TAKE THE PROPER PRECAUTIONS TO ENSURE THE STABILITY OF ALL 8.
CATEGORY BRIDGE FABRICATOR SIMPLE (SBR).
STRUCTURAL STEEL FABRICATORS SHALL BE CERTIFIED UNDER THE AISC CERTIFICATION PROGRAM 7.
NOT REDUCE THE THICKNESS OF THE BASE METAL BY MORE THAN 5% OF THE TOTAL THICKNESS.
MAY BE USED PROVIDED IT IS FOLLOWED BY SUCH GRINDING. THE GRINDING PROCESS SHALL
DIRECTION OF THE APPLIED STRESS LEAVING THE SURFACES FREE FROM DEPRESSIONS. CHIPPING
FINISHED SMOOTH AND FLUSH WITH BASE METAL ON ALL SURFACES BY GRINDING IN THE
ALL SHOP WELDS SHALL BE INSPECTED BY RADIOGRAPHIC OR ULTRASONIC TESTING AND 6.
DETERMINED BY THE ENGINEER,
LAYER INSPECTED AND ACCEPTED BEFORE PROCEEDING TO THE NEXT PASS OR LAYER, AS
MULTIPLE PASS WELDS, INSPECTED BY MAGNETIC PARTICLE METHOD SHALL HAVE EACH PASS OR 5.
INCLUDING THE COST OF DESIGN, SHALL BE AT NO EXTRA EXPENSE TO THE STATE.
BY THE CONTRACTOR AND APPROVED BY THE ENGINEER. THE COST OF THESE SPLICES,
PRIOR TO THE SUBMISSION OF SHOP DRAWINGS. IF ALLOWED, THESE SPLICES SHALL BE DESIGNED FIELD SPLICES WILL NOT BE ALLOWED EXCEPT WITH THE WRITTEN PERMISSION OF THE ENGINEER 4.
AASHTO/AWS D1.5-(2015)-BRIDGE WELDING CODE, UNLESS OTHERWISE NOTED ON THE PLANS.
WELDING DETAILS, PROCEDURES, AND TESTING METHODS SHALL CONFORM TO THE ANSI/ 3.
STEEL BUILDINGS", LATEST EDITION.
AISC "SPECIFICATIONS FOR THE DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL A.
ALL STRUCTURAL STEEL WORK SHALL CONFORM TO THE FOLLOWING GOVERNING STANDARDS:2.
MATERIAL TO BE INCLUDED UNDER THEIR RESPECTED ITEMS.
GRADE B (46 KSI). TEMPORARY SUPPORTS 1 AND 2 SHALL REMAIN IN PLACE. THE COST FOR THE
CONFORM TO GRADE 50, EXCEPT FOR STRUCTURAL TUBES SHALL CONFORM TO ASTM A500,
ALL STRUCTURAL STEEL USED FOR THE TEMPORARY SUPPORT SYSTEM INCLUDING PLATES SHALL
BE ZINC PRIME ONLY.
FABRICATION, EXCEPT FOR STRUCTURAL STEEL USED FOR TEMPORARY SUPPORTS 1, 2 AND 3 SHALL GRADE 50 KSI AND SHALL BE HOT-DIPPED GALVANIZED IN ACCORDANCE WITH ASTM A123 AFTER
OTHER MISCELANNEOUS STRUCTURAL STEEL HARDWARE SHALL CONFORM TO THE ASTM M270,
ALL PROPOSED STRUCTURAL STEEL REPAIRS (LOW ALLOY) ANGLES, PLATES, SUPPORT BRACKETS 1.
PROJECT DESCRIPTION:
BID NUMBER: DRAWING NO.
SHEET NO.
2/11/2026
BLOCK:
SIGNATURE/
DRAWING TITLE: GENERAL NOTES
G-2
TOWN(S):
DESIGNER/DRAFTER: S.R.K. CHECKED BY: R.H.S.
BRIDGEPORT
REHABILITATION OF THE ACCESS RAMP OF MARGARET E. MORTON GOVERNMENT CENTER
PLOTTED DATE:
Y:\Projects\R127-8 Condition Inspection of Bridgeport City Hall 999 Broad St\CAD\Ramp Repairs\General Notes Rev.dgn FILE NAME: rhsuser15 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
IO
GINA@CHEM-SCOPE.COM
DIRECT LINE: 203.764.2384
MAIN LINE: 203.865.5605
CHEMSCOPE, INC.
OBSERVATION AND AIR MONITORING:
CONTRACTOR CAN CONTACT THE LABORATORY LISTED BELOW, OR APPROVED EQUAL, FOR
IF DEMOLITION OR DISTURBANCE OF EXISTING PAINTED MATERIALS IS REQUIRED, THE 8.
CONTAINING MATERIALS SHALL BE PERMITTED WITHOUT PROPER CLEARANCE AND APPROVAL.
NO SAWING, GRINDING, DRILLING, OR UNCONTROLLED DISTURBANCE OF SUSPECT ASBESTOS-7.
IMPLEMENTED IF SUSPECT MATERIALS ARE DISTURBED.
AWARENESS, AND PROPER ENGINEERING CONTROLS, PPE, AND SAFE WORK PRACTICES SHALL BE APPLICABLE FEDERAL, STATE, AND LOCAL REGULATIONS. WORKERS SHALL BE TRAINED IN ASBESTOS ALL CONTRACTORS SHALL COMPLY WITH OSHA ASBESTOS STANDARDS (29 CFR 1926.1101) AND 6.
SAMPLED, THE CONTRACTOR SHALL STOP WORK IN THE AFFECTED AREA AND NOTIFY THE ENGINEER.
HOWEVER, IF SUSPECT MATERIALS ARE ENCOUNTERED DURING CONSTRUCTION THAT WERE NOT
BASED ON LABORATORY TESTING, NO ASBESTOS WAS DETECTED IN THE SAMPLES PROVIDED. 5.
SHALL BE USED AT ALL TIMES.
PERMITTED. DUST CONTROL MEASURES, INCLUDING WET METHODS AND HEPA VACUUMING,
NO DRY SANDING, DRY SCRAPING, OR UNCONTROLLED REMOVAL OF PAINTED MATERIALS SHALL BE 4.
EXISTING PAINTED SURFACES.
PROTECTIVE EQUIPMENT (PPE), AND SAFE WORK PRACTICES SHALL BE IMPLEMENTED WHEN DISTURBING FEDERAL, STATE, AND LOCAL LEAD REGULATIONS. PROPER ENGINEERING CONTROLS, PERSONAL ALL CONTRACTORS SHALL COMPLY WITH OSHA LEAD STANDARDS (29 CFR 1926.62) AND APPLICABLE 3.
CONSTRUCTION, DEMOLITION, OR RENOVATION ACTIVITIES.
TRAINING AND PERSONAL AIR MONITORING IF EMPLOYEES DISTURB THESE MATERIALS DURING
ALTHOUGH THE PAINT IS NOT CLASSIFIED AS LEAD BASED PAINT, OSHA STILL REQUIRES LEAD AWARENESS 2.
BASED PAINT.
DETECTED, AND THE OTHER CONTAINED 0.11% LEAD, WHICH DOES NOT MEET THE CRITERIA FOR LEAD MORE THAN 0.5% LEAD. BOTH SAMPLES TESTED WERE BELOW THIS THRESHOLD. ONE SAMPLE HAD NO LEAD
CONTAIN BASED ON LABORATORY TESTING, TO BE CONSIDERED LEAD BASED PAINT (LBP), A SAMPLE MUST 1.
MNB035263
GENERAL NOTES SELECTIVE DEMOLITION NOTES
CONCRETE NOTES
STRUCTURAL STEEL NOTES
LEAD-RELATED CONSTRUCTION SAFETY AND MONITORING NOTES
LIVE LOAD NOTES:
ROLLERS ONLY.
STRUCTURE. COMPACTION SHALL BE PERFORMED USING STATIC (NON-VIBRATORY)
VIBRATORY COMPACTION EQUIPMENT SHALL NOT BE PERMITTED ON THE DECK
SHALL EXCEED 4,000 POUNDS.
INCLUDING OPERATOR AND ALL FLUIDS. NO INDIVIDUAL AXLE OR DRUM LOAD
WEIGHT OF 6,000 POUNDS (NOMINAL 3-TON CLASS), MAXIMUM TOTAL OPERATING
COMPACTION EQUIPMENT SHALL BE LIMITED TO LIGHT-DUTY ROLLERS WITH A
NOT BE PERMITTED ON THE STRUCTURE.
MAXIMUM AXLE LOADING OF 6,000 LBS. EQUIPMENT EXCEEDING THIS LIMIT SHALL
EXCEED AN AASHTO H-5, WITH A GROSS VEHICLE WEIGHT OF 10,000 LBS, AND A
CONSTRUCTION EQUIPMENT OR MAINTENANCE VEHICLE LOADS SHALL NOT
UNIFORM LIVE LOAD OF 40 PSF AND OR
THE RAMP STRUCTURE IS RATED FOR:
EMAIL: JONATHAN.ZEBROSKI@BRIDGEPORTCT.GOV
CELL: (475) 344-7794
MR. JOHNATHAN ZEBROSKI
THE CITY OF BRIDGEPORT MANAGER POINT OF CONTACT:
UNDER THE CONTRACT DOCUMENTS.
ADDITIONAL COST TO THE OWNER, REMOVAL FROM THE SITE, OR OTHER REMEDIES AVAILABLE
REQUIREMENTS MAY RESULT IN SUSPENSION OF WORK, CORRECTIVE ACTIONS AT NO
CONSTRUCTION ACTIVITIES OR UNAUTHORIZED ACCESS. FAILURE TO COMPLY WITH THESE
REPAIRING OR RESTORING ANY DAMAGE CAUSED BY CONDITION, AND PROMPTLY
SITE IN A SAFE AND ORDERLY RESPONSIBLE FOR PROTECTING CITY PROPERTY, MAINTAINING THE
APPROVAL IS RECEIVED FROM THE ENGINEER OF RECORD. THE CONTRACTOR SHALL BE FULLY
NO STRUCTURAL STEEL SURFACE PREPARATION WORK SHALL COMMENCE UNTIL WRITTEN 5.
WASTE HANDLING AND DISPOSAL METHODS, INCLUDING DISPOSAL LOCATIONS
WORKER PROTECTION MEASURES IN ACCORDANCE WITH OSHA REQUIREMENTS
DUST AND DEBRIS CONTAINMENT MEASURES
PROPOSED METHODS AND EQUIPMENT FOR SURFACE PREPARATION
RECORD FOR REVIEW AND APPROVAL. SUBMITTALS SHALL INCLUDE, AT A MINIMUM:
CONTRACTOR SHALL SUBMIT DETAILED WORK PLANS AND PROCEDURES TO THE ENGINEER OF
PRIOR TO PERFORMING ANY STRUCTURAL STEEL SURFACE PREPARATION OR CLEANING, THE
REQUIREMENTS.
REGULATIONS (INCLUDING 29 CFR PARTS 1910 AND 1926) AND APPLICABLE ENVIRONMENTAL
TOOLS, FILTRATION, OR OTHER APPROVED METHODS AS REQUIRED TO COMPLY WITH OSHA
MEASURES SHALL INCLUDE CONTAINMENT SYSTEMS, WET METHODS, VACUUM-ASSISTED
DUST, RUST, PAINT RESIDUE, OR DEBRIS BEYOND THE IMMEDIATE WORK AREA. DUST CONTROL
CONTRACTOR SHALL PREVENT THE RELEASE AND MIGRATION OF POWER TOOL CLEANING. THE
ACTIVITIES INCLUDING, BUT NOT LIMITED TO, GRINDING, BLASTING, NEEDLE SCALING, OR
ENVIRONMENTAL CONTROLS AT ALL TIMES. DURING STRUCTURAL STEEL SURFACE PREPARATION
THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING PROPER DUST, DEBRIS, AND 4.
SEQUENCING SHALL REQUIRE ADVANCE APPROVAL FROM THE CITY.
APPROVED WORK HOURS, OR MODIFICATIONS TO APPROVED ACCESS, STAGING, OR
REQUIRING TEMPORARY SHUTDOWNS, AFTER-HOURS OPERATIONS, DEVIATIONS FROM
ACCORDANCE WITH CTDOT STANDARD SPECIFICATIONS SECTION 1.07. ANY WORK
BUILDING OPERATIONS, PUBLIC ACCESS, EMERGENCY SERVICES, OR MEANS OF EGRESS, IN
CONSTRUCTION OPERATIONS SHALL BE CONDUCTED SO AS NOT TO INTERFERE WITH NORMAL 3.
AUTHORIZATION IS OBTAINED FROM THE CITY.
OCCUPIED, OR NON-DESIGNATED AREAS IS PROHIBITED UNLESS PRIOR WRITTEN
LIMITED STRICTLY TO AREAS APPROVED BY THE CITY. ENTRY INTO RESTRICTED, SECURED,
FEDERAL, STATE, AND LOCAL LAWS. ACCESS TO THE GOVERNMENT CENTER BUILDING SHALL BE
CTDOT STANDARD SPECIFICATIONS, OSHA REGULATIONS, AND ALL OTHER APPLICABLE `
BRIDGEPORT REQUIREMENTS, THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE CITY OF 2.
ONGOING CITY OPERATIONS.
USE, NOISE AND VIBRATION LIMITATIONS, UTILITY IMPACTS, AND PROTECTION OF RESTROOM
MATERIAL STORAGE, DELIVERIES, WASTE HANDLING, HOURS, STAGING AND LAYDOWN AREAS,
NOT BE LIMITED TO, BUILDING ACCESS AND SECURITY PROCEDURES, APPROVED WORKING
STANDARD SPECIFICATIONS SECTIONS 1.04 AND 1.07. COORDINATION SHALL INCLUDE, BUT
WITH THE INTENT OF CTDOT THROUGHOUT THE DURATION OF THE PROJECT, IN ACCORDANCE
BRIDGEPORT’S DESIGNATED BUILDING/FACILITY MANAGER PRIOR TO MOBILIZATION AND
THE CONTRACTOR SHALL COORDINATE ALL CONSTRUCTION ACTIVITIES WITH THE CITY OF 1.
DEWATERING AND WATER INTRUSION PROTECTION NOTE
PAYMENT WILL BE MADE.
IN THE CONTRACTOR’S GENERAL CONDITIONS OR APPLICABLE BID ITEMS. NO SEPARATE
CONTAINMENTM, MONITORING, PROTECTION, AND RESTORATION SHALL BE INCLUDED
ADDITIONAL COST TO THE OWNER. ALL COSTS ASSOCIATED WITH WATER CONTROL,
THE WORK AREA. ALL REPAIRS AND RESTORATION SHALL BE PERFORMED AT NO
DAMAGE TO OFFICES, FINISHES, EQUIPMENT, FURNISHINGS, AND BUILDING SYSTEMS BELOW
INTRUSION OR SEEPAGE RESULTING FROM CONSTRUCTION OPERATIONS, INCLUDING
THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ANY DAMAGE CAUSED BY WATER 4.
INCLUDING DURING ADVERSE WEATHER AND OFF-HOURS.
AND CONTROL SURFACE WATER, RAINFALL, WASH WATER, AND CONSTRUCTION RUNOFF,
CONTRACTOR SHALL TAKE ALL NECESSARY AND EXTREME MEASURES TO DIVERT, CONTAIN,
IN ACCORDANCE WITH CTDOT STANDARD SPECIFICATIONS SECTIONS 1.04 AND 1.07, THE 3.
ACTIONS NO WORK SHALL BEGIN UNTIL WRITTEN APPROVAL IS RECEIVED.
DISCHARGE LOCATIONS, MONITORING PROCEDURES, AND WEATHER CONTINGENCY
AND CONTAINMENT METHODS, TEMPORARY WATERPROOFING MEASURES, DIVERSION
OF RECORD FOR REVIEW AND APPROVAL. THE PLAN SHALL INCLUDE PROPOSED
SUBMIT A TEMPORARY WATER MANAGEMENT AND DEWATERING PLAN TO THE ENGINEER
PRIOR TO COMMENCEMENT OF DECK OR ROOF-LEVEL REPAIRS, THE CONTRACTOR SHALL 2.
INTO THE BUILDING SHALL NOT BE PERMITTED AT ANY TIME.
STRUCTURAL ELEMENTS, OR INTERIOR SPACES DURING CONSTRUCTION. WATER INTRUSION
WATER INFILTRATION, LEAKAGE, SEEPAGE, OR RUNOFF INTO THE RAMP DECK, ROOF DECK,
DRAINAGE, DIVERSION, AND CONTAINMENT MEASURES NECESSARY TO PREVENT ANY
THE CONTRACTOR SHALL PROVIDE AND MAINTAIN ALL TEMPORARY DEWATERING, 1.
NOTICE TO CONTRACTOR
CONTRACTOR COORDINATION, ACCESS, AND WORK CONTROL NOTE
"LOCALIZED PAINT REMOVAL AND FIELD PAINTING OF EXISTING STEEL".
PAINTING THE EXISTING STEEL AFTER REPAIRS SHALL BE PAID UNDER THE ITEM NO. 0603729A REMOVAL OF EXISTING PAINT, DISPOSAL OF DEBRIS AT THE PROPOSED STEEL REPAIRS AND 23.
NO. 0603431 "STEEL (MISCELLANEOUS)"
STEEL PLATE AT EACH JOINT REPAIR AS PROPOSED IN THE PLANS SHALL BE PAID UNDER THE ITEM 22.
ITEM NO. 0603081A "STRUCTURAL STEEL REPAIRS (SITE NO. 2")
REPAIR OF STRUCTURAL STEEL AS MENTIONED IN PLANS AT SITE NO. 2 SHALL BE PAID UNDER THE 21.
ITEM NO. 0603081A "STRUCTURAL STEEL REPAIRS (SITE NO. 1)"
REPAIR OF STRUCTURAL STEEL AS MENTIONED IN PLANS AT SITE NO. 1 SHALL BE PAID UNDER THE 20.
"WELDED WIRE FABRIC - GALVANIZED"
WELDED WIRE FABRIC USED IN THE RAMP LANDING SHALL BE PAID UNDER ITEM NO. 0602054 19.
" PREFORMED EXPANSION JOINT FILLER".2
ITEM NO. 0601502 "
PREFORMED EXPANSION JOINT AT THE END OF THE RAMP LANDING SHALL BE PAID UNDER THE 18.
STEEL".REINFORCEMENT
AND SHALL BE PAID UNDER THE ITEM NO. 0602980A "CLEAN AND COAT EXPOSED
EXPOSED REBARS WHILE REPAIR OF CONCRETE DECK RAMP SHALL BE CLEANED AND COATED 17.
PLACING THE CONCRETE SHALL BE PAID UNDER THE ITEM NO. 0601318A "PARTIAL DEPTH PATCH".
EQUIPMENT, REMOVAL OF DETERIORATED CONCRETE AND SURFACE PREPARATION AND
TO INSPECTION OF THE DECK, HAMMER DEMOLITION, HYDRO-DEMOLITION WATER AND
REPAIR OF UNSOUND AND DETERIORATED CONCRETE RAMP WHICH INCLUDES BUT NOT LIMITED 16.
"NON-TRACKING ASPHALT TACK COAT".
TACK COAT USED UNDER THE BITUMINOUS OVERLAY SHALL BE PAID UNDER ITEM NO. 0406238 15.
ITEM NO. 0601072 "SURFACE REPAIR CONCRETE".
REPAIR SPALLED CONCRETE BEAM BETWEEN COLUMN LINE G1 AND F1 SHALL BE PAID UNDER 14.
BE MADE UNDER ITEM NO. 0912518, “REMOVE AND RESET METAL BEAM RAIL.”
REMOVAL AND REPLACEMENT OF THE METAL BEAM RAIL SHALL BE INCLUDED. PAYMENT SHALL
ALLOW FOR JOINT REPAIR OF THE RAMP. ALL HARDWARE OR ACCESSORIES REQUIRED FOR
EXISTING METAL BEAM RAIL SHALL BE REMOVED AND REPLACED IN ITS EXISTING LOCATION TO 13.
WEBSITE: GCPAT.COM
E-MAIL: ANNETTE.AITKEN@GCPAT.COM
TELEPHONE: 678-575-1927
PRODUCT CONTACT: GCP
PRODUCT BRAND NAME: ELIMINATOR*
ADDITIONAL INFORMATION:
APPROVED EQUAL, AND THE CONTRACTOR MAY CONTACT THE MANUFACTURER FOR
WATERPROOFING SYSTEM. THE SYSTEM SHALL BE ONE OF THE PRODUCT LISTED BELOW OR
DEPARTMENT’S CURRENT QUALIFIED PRODUCT LIST (QPL) FOR SPRAY-APPLIED MEMBRANE
THE CONTRACTOR SHALL SELECT A WATERPROOFING MEMBRANE SYSTEM FROM THE
0707009A "MEMBRANE WATERPROOFING (COLD LIQUID ELASTOMERIC)".
WATERPROOFING MEMBRANE FOR RAMP AND TOP OF CURB SHALL BE PAID UNDER ITEM NO. 12.
STEEL BARS – GALVANIZED.”
DETERIORATED OR UNSOUND CONCRETE SHALL BE PAID UNDER ITEM NO. 0602030, “DEFORMED
ALL REINFORCEMENT USED FOR JOINT REPAIRS, CONCRETE LANDINGS, AND REPAIR OF 11.
"CLEAN EXISTING DRAINAGE STRUCTURE.”
CLEANING OF THE EXISTING DRAINAGE SYSTEM SHALL BE INCLUDED UNDER ITEM NO. 0653630, DISPOSAL OF SLUDGE, DIRT, SAND, GRAVEL, ROOTS, GREASE, AND OTHER DEBRIS, AND FLUSH
SHALL BE PAID UNDER ITEM NO. 0507900A, “TRENCH DRAIN.”
PROPOSED PRECAST TRENCH DRAIN, IRON EDGE CHANNELS, AND ALL REQUIRED HARDWARE 10.
PAID UNDER “REMOVAL OF EXISTING WEARING SURFACE” AND “HMA S0.375”.
REMOVAL OF EXISTING PAVEMENT SURFACE AND PROPOSED BITUMINOUS OVERLAY SHALL BE 9.
FIRE-RESISTANT PAINT.”
LIMITS, AS SHOWN ON THE PLANS, SHALL BE PAID UNDER ITEM NO. 0000001A, “INTUMESCENT EXISTING STRUCTURAL STEEL AND PROPOSED REPAIRED STRUCTURAL STEEL FIREPROOFING PAINT 8.
SPECIFICATIONS. PAYMENT SHALL BE MADE UNDER ITEM NO. 0609001A, “REPOINTED MASONRY.”
AND FILLED WITH MORTAR CONFORMING TO ASTM C1714 AND ASTM C387 STANDARD
LOOSE MORTAR, DIRT, OR OTHER FOREIGN MATERIAL TO A DEPTH OF APPROXIMATELY 2 INCHES, CRACKS IN THE EXISTING CMU WALL SHALL BE THOROUGHLY RAKED OUT AND CLEANED OF ALL 7.
BACKER ROD SHALL BE PAID UNDER ITEM NO. 0520041A "PREFORMED JOINT SEAL".
REMOVAL OF EXISTING JOINT MATERIAL, INSTALLATION OF IMPREGNATED FOAM GLAND AND 6.
BE PAID UNDER ITEM NO. 0213100 “GRANULAR FILL.”
GRANULAR FILL USED BENEATH THE PROPOSED TRENCH DRAIN AND CONCRETE LANDING SHALL 5.
ITEM "DRILLING HOLES AND BONDING DOWELS".
THE DRILLING AND BONDING OF ALL REINFORCING BAR DOWELS SHALL BE PAID FOR UNDER THE 4.
REPAIRS, SHALL BE PAID FOR UNDER THE ITEM " REMOVAL OF EXISTING MASONRY".
TO REMOVE THE CMU BLOCKS FROM THE WALLS AT THE LOCATIONS OF STRUCTURAL STEEL
IF REQUIRED ENCASING EXISTING STRINGERS AND FLOOR BEAMS AS SHOWN ON THE PLANS, AND
REMOVAL OF EXISTING CONCRETE WITHIN JOINT REPAIR LIMITS, REMOVAL OF CONCRETE 3.
LANDING AT TRENCH DRAIN SHALL BE PAID FOR UNDER ITEM "CLASS PCC04462".
THE PROPOSED CONCRETE FOR THE JOINT REPAIRS, CURBS, RAISED ISLANDS AND CONCRETE 2.
UNDER THE ITEM "STRUCTURE EXCAVATION - EARTH (COMPLETE)".
EXCAVATION UNDER EXISTING TRENCH DRAIN AND BITUMINOUS LANDING SHALL BE PAID FOR 1.
PROJECT DESCRIPTION:
BID NUMBER: DRAWING NO.
SHEET NO.
2/11/2026
BLOCK:
SIGNATURE/
DRAWING TITLE: GENERAL NOTES
G-2.1
TOWN(S):
DESIGNER/DRAFTER: S.R.K. CHECKED BY: R.H.S.
BRIDGEPORT
REHABILITATION OF THE ACCESS RAMP OF MARGARET E. MORTON GOVERNMENT CENTER
PLOTTED DATE:
Y:\Projects\R127-8 Condition Inspection of Bridgeport City Hall 999 Broad St\CAD\Ramp Repairs\General Notes Rev.dgn FILE NAME: rhsuser15 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
MNB035263
PAY ITEM NOTES
REPAIRS, DECK REPAIRS, WATERPROOFING MEMBRANE, AND PAVING.
WITH THE ENGINEER FOR FINAL INSPECTION AND ACCEPTANCE OF STRUCTURAL STEEL
FINAL INSPECTION AND ACCEPTANCE: UPON COMPLETION OF ALL WORK, COORDINATE 9.
STRUCTURAL LOAD LIMITS.
LOADS, AND OTHER INFORMATION NECESSARY TO VERIFY COMPLIANCE WITH
APPROVAL. SUBMITTALS SHALL INCLUDE OPERATING WEIGHTS, AXLE AND/OR DRUM
FOR ALL PAVING AND COMPACTION EQUIPMENT FOR ENGINEER REVIEW AND
SPECIFICATIONS. PRIOR TO PAVING, SUBMIT MANUFACTURER DATASHEETS OR CUT SHEETS
ASPHALT PAVING: PLACE ASPHALT PAVING IN ACCORDANCE WITH THE PLANS AND 8.
ACCORDANCE WITH THE PLANS AND SPECIFICATIONS.
WATERPROOFING MEMBRANE: INSTALL THE WATERPROOFING MEMBRANE IN 7.
EXPENSE, AS DIRECTED BY THE ENGINEER.
SUBSEQUENT OPERATIONS SHALL BE REPAIRED OR REPLACED AT THE CONTRACTOR’S
DURING REMAINING CONSTRUCTION OPERATIONS. ANY PATCHES DAMAGED BY
PROTECTION OF DECK PATCHES: THE CONTRACTOR SHALL PROTECT ALL DECK PATCHES 6.
NON-STRUCTURAL DECK REPAIRS, AFTER COMPLETION OF STRUCTURAL STEEL REPAIRS.
NOT LIMITED TO TRENCH GRADE RECONSTRUCTION, MASONRY REPOINTING, AND OTHER
OTHER DECK WORK: PERFORM OTHER MISCELLANEOUS DECK WORK, INCLUDING BUT 5.
WITH SUBSEQUENT WORK.
AS VERIFIED BY TEST RESULTS OR MANUFACTURER CERTIFICATION, PRIOR TO PROCEEDING
PSI OR 90 PERCENT OF THE SPECIFIED DESIGN STRENGTH, WHICHEVER IS GREATER, 3,500
PATCH REPAIR MATERIAL SHALL ACHIEVE A MINIMUM COMPRESSIVE STRENGTH OF
REPAIRS, PERFORM DECK PATCH REPAIRS AND RECONSTRUCTION OF DECK JOINTS.
DECK PATCH REPAIRS AND DECK JOINTS: UPON COMPLETION OF STRUCTURAL STEEL 4.
METHODS ONLY.
COMPACTION AND CONSTRUCTION OPERATIONS SHALL UTILIZE STATIC, NON-VIBRATORY
KIND ON THE DECK STRUCTURE IS PROHIBITED FOR THE DURATION OF THE PROJECT. ALL
PROHIBITION OF VIBRATORY EQUIPMENT: THE USE OF VIBRATORY EQUIPMENT OF ANY 3.
CONSTRUCTABILITY DURING STEEL REPAIR OPERATIONS.
TEMPORARY SUPPORTS SHALL BE USED SOLELY FOR STABILITY AND
PROHIBITED.
JACKING, LIFTING, OR ANY INTENTIONAL LOAD REDISTRIBUTION IS STRICTLY
BEAM ENDS AS TIGHT-FIT SUPPORTS ONLY.
TEMPORARY SUPPORT BRACKETS: TEMPORARY SUPPORT BRACKETS SHALL BE INSTALLED AT 2.
PLANS OR AS DIRECTED BY THE ENGINEER.
BOLTED CONNECTIONS, FLANGE PLATING, AND ALL OTHER STEEL REPAIRS SHOWN ON THE
STRUCTURAL STEEL REPAIRS SHALL INCLUDE, BUT NOT BE LIMITED TO, REPLACEMENT OF
SURFACE PREPARATION AND STRUCTURAL STEEL REPAIRS PRIOR TO ANY DECK REPAIRS.
SURFACE PREPARATION AND STRUCTURAL STEEL REPAIRS: PERFORM ALL REQUIRED 1.
SUGGESTED SEQUENCE OF CONSTRUCTION
PROJECT DESCRIPTION:
BID NUMBER: DRAWING NO.
SHEET NO.
2/11/2026
BLOCK:
SIGNATURE/
DRAWING TITLE: EAST & SOUTH ELEVATIONS
S-1
TOWN(S):
DESIGNER/DRAFTER: S.R.K. CHECKED BY: R.H.S.
MNB035263
BRIDGEPORT
REHABILITATION OF THE ACCESS RAMP OF MARGARET E. MORTON GOVERNMENT CENTER
PLOTTED DATE:
Y:\Projects\R127-8 Condition Inspection of Bridgeport City Hall 999 Broad St\CAD\Ramp Repairs\Framing Plan.dgn FILE NAME: rhsuser15 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
SCALE: 1"=10'
EAST ELEVATION
SCALE: 1"=10'
SOUTH ELEVATION
RAMP ENTRANCE
MARGARET E. MORTON GOVERNMENT CENTER
2'-2"
25'-0" 27'-0" 27'-0" 27'-0" 27'-0" 27'-0" 27'-0" 27'-0" 16'-0" 11'-0" 25'-0"
4'-0" 4'-0" 4'-0"4'-0" 4'-0" 4'-0" 4'-0"
PROJECT DESCRIPTION:
BID NUMBER: DRAWING NO.
SHEET NO.
2/11/2026
BLOCK:
SIGNATURE/
DRAWING TITLE: DECK PLAN
S-2
TOWN(S):
DESIGNER/DRAFTER: S.R.K. CHECKED BY: R.H.S.
MNB035263
BRIDGEPORT
REHABILITATION OF THE ACCESS RAMP OF MARGARET E. MORTON GOVERNMENT CENTER
PLOTTED DATE:
Z:\Projects\R127-8 Condition Inspection of Bridgeport City Hall 999 Broad St\CAD\Ramp Repairs\Deck Plan.dgn FILE NAME: Rhsuser20 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
4'-0"
LIMITS OF RAMP CONSTRUCTION
SCALE: 1"=10'
PROPOSED REPAIRS
L K J H G F E D C B A
L K J H G F E D C B A
Bs
BITUMINOUS PAVEMENT
LIMITS OF REMOVAL OF EXISTING
CURB LINE
CURB LINE
L OF RAMPC
L OF RAMPC
sB
CURB LINE
L OF RAMPC
L OF RAMPC
100+00 125+00 150+00 175+00 200+00 225+00 250+00 275+00 300+00 325+00 350+00 366+00
SCALE: 1"=10'
RAMP ELEVATION
C U
R B
L
IN
E
C U
R B
L
IN
E
L K J H G F E D C B ABs L OF RAMPC
PRESENT ROOF
EL. 54'-0"'
FLOOR
ND
FLOOR
ST
EL. 19'-0"'
REMAIN
SIGNAL POST TO
EXISTING TRAFFIC
REMAIN
SIGNAL POST TO
EXISTING TRAFFIC
REMAIN
SIGNAL POST TO
EXISTING TRAFFIC
RAILING TO REMAIN
EXISTING RAMP
REMAIN
SIGNAL POST TO
EXISTING TRAFFIC
REMAIN (TYP.)
EXISTING TRENCH DRAIN, TO
DRAIN (TYP.)
CLEAN EXISTING TRENCH
EL. 36'-6"
TRENCH DRAIN
REMOVE EXISTING
CURB LINE
SEE DWG NO. S-7
DRAIN FOR DETAILS,
INSTALL NEW TRENCH
DRAINAGE SYSTEM &
CLEAN EXISTING
JOINT (TYP.)
EXISTING CURB
S-8 (TYP.)DWG NO.
LOCATIONS, FOR DETAILS SEE
AT JOINTS A FLOORBEAM
RECONSTRUCT CONCRETE DECK
CONSTRUCTION
BEGIN OF
CONSTRUCTION
END OF
RAISED ISLAND
LIQUID ELASTOMERIC)
WATERPROOFING (COLD
TACK COAT AND MEMBRANE
NON-TRACKING ASPHALT
OVER OVERLAY HMA S0.375
" BITUMINIOUS 2
LIMITS OF 1
LEGEND:
REMOVAL OF EXISTING BITUMINIOUS PAVEMENT
LIMITS OF PARTIAL DEPTH PATCH REPAIRS
WATERPROOFING (COLD LIQUID ELASTOMERIC)/
TRACKING ASPHALT TACK COAT AND MEMBRANE
PROPOSED BITUMINIOUS OVERLAY HMA S0.375 OVER NON-
(TYP.)
EXISTING CURB JOINT
CONCRETE DECK AT JOINTS
OF RECONSTRUCTION OF
SECTION RAIL WITHIN LIMITS
POST AND REMOVE ONE
REMOVE AND RESET RAIL
NO. S-12 (TYP.)
WATERPROOFING SEE DETAILS IN DWG
TO PLACEMENT OF MEMBRANE
DEPTH PATCH REPAIR DETAILS, PRIOR
PROJECT LIMITS RAMP AS PER PARTIAL
CONCRETE THROUGHOUT THE
REPAIR DETERIORATED OR UNSOUND
SIGNAL POST TO REMAIN
EXISTING TRAFFIC
ENTRANCE GATE TO REMAIN
TO REMAIN
ENTRANCE GATE
TO REMAIN
SIGNAL POST
EXISTING TRAFFIC
S-7DWG NO. IN
LANDING, SEE DETAILS
RECONSTRUCT
S-10NO.
DWG SEE
REPAIR DETAILS
FOR JOINT
FOR DETAILS, SEE DWG NO. S-11
BEAM WITH EXPOSED REBAR
LIMITS OF SPALLED CONCRETE
REPAIR SPALLED CONCRETE BEAM
LIMITS OF SPALLED CONCRETE BEAM WITH EXPOSED REBAR/
NO. S-11
BEAM FOR DETAILS, SEE DWG
REPAIR SPALLED CONCRETE
DETERIORATED JOINT SEAL
WATER LEAKAGE DUE TO
E
S-11
E
S-11
DWG NO. S-11
OF RAMP,FOR DETAILS SEE
RAMP, FULL LENGTH X EACH SIDE
C.M.U WALL THROUGHOUT THE
BETWEEN CONCRETE CURB AND
INSTALL IMPREGNATED FOAM GLAND
SYSTEM.
BOTH TRENCH DRAINS SHALL BE CLEANED USING A FLUSH-CLEANING METHOD OF DRAINAGE 3.
JOINT REPAIR DETAILS.
SEE SECTION-E IN DRAWING NO. S-11 FOR LIMITS OF MEMBRANE WATERPROOFING AND 2.
SEE REPAIR DETAILS ON DWG. NO. S-11.
APPLICABLE. WORK SHALL BE PAID FOR UNDER ITEM NO. 0609001A “REPOINTED MASONRY.”
CONTRACTOR SHALL REPOINT C.M.U. WALL CRACKS ALONG BOTH SIDES OF RAMP, WHERE 1.
NOTE:
FOR DETAILS, SEE DWG NO. S-11
INSTALL IMPREGNATED FOAM GLAND AT FB6
STATIONS
BASE LINE
SHEET NO.
2/11/2026
BLOCK:
SIGNATURE/
DRAWING TITLE: FRAMING PLAN
S-3
TOWN(S):
DESIGNER/DRAFTER: S.R.K. CHECKED BY: R.H.S.
MNB035263
BRIDGEPORT
REHABILITATION OF THE ACCESS RAMP OF MARGARET E. MORTON GOVERNMENT CENTER
PLOTTED DATE:
Y:\Projects\R127-8 Condition Inspection of Bridgeport City Hall 999 Broad St\CAD\Ramp Repairs\Framing Plan.dgn FILE NAME: rhsuser15 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
EXISTING FRAMING PLAN
SCALE: 1"=10'
PROPOSED FRAMING PLAN
L K J H G F E D C B A
L K J H G F E D C B A
Bs
100+00 125+00 150+00 175+00 200+00 225+00 250+00 275+00 300+00 325+00 350+00 366+00
25'-0"
25'-0" 27'-0" 27'-0" 27'-0" 27'-0" 27'-0" 27'-0" 27'-0" 16'-0" 11'-0" 25'-0"
S1
S2
S3
W 24X
W 18X40
W
X
FB1
W21X50)FB2 ( DO)FB3 ( DO)FB4 ( DO)FB5 ( DO)FB6 ( DO)FB7 ( DO)FB8 (
W21X50)FB9 (
F B
FB11
FB12
- STRINGERS#
-FLOOR BEAMFB#
LEGEND:
Bs
S1
S2
S3
FB11
FB12
ELSEWHERE NEAR COLUMN F2
” THICKNESS REMAINING 8
1L4"X4" ANGLE WITH
THERE IS 4” X 2” HOLE AT BOTTOM LEG OF
FLOORBEAM TO COLUMN
AT BETWEEN BOTH SIDES OF
HEAVILY RUSTED CONNECTION
WITH ¼” REMAINING AT BOTTOM FLANGE OF FLOOR BEAM
COLUMN AT WEB OF FLOOR BEAM, 6’ LONG X FULL WIDTH
X 10” HIGH X ¼” DEEP SECTION LOSS AT WEB END NEAR
” DEEP SECTION LOSS, 8” LONG 8
16’ LONG X 4” HIGH X
FB
FB1 (W21X44)
ANGLE (TYP.)
" 8
3EXISTING L4X4X
ANGLE (TYP.)
" 8
3EXISTING L4X4X
AT STRINGER S3 AT NORTH SIDE OF COLUMN C2
HEAVILY RUSTED CONNECTION BOLTS AND ANGLE
AISC STEEL CONSTRUCTION MANUAL.
ON THE DRAWINGS ARE IN ACCORDANCE WITH THE LATEST
EXISTING FLOORBEAM AND STRINGER DESIGNATIONS SHOWN 2.
AND LOCALIZED AREAS ON STRUCTURAL STEEL. DO NOTHING.
" AT BEAM END16
1THERE ARE INSIGNIFICANT SECTION LOSSES ± 1.
NOTES:
SEE DETAILS IN DRAWING S-4,
THE COLUMN AT SITE NO. 1,
FLOORBEAM CONNECTIONS TO
BRACKET & REPLACE EXISTING
INSTALL TEMPORARY SUPPORT
SEE DETAILS IN DRAWING S-5
NORTH SIDE ONLY (SITE NO. 2)
CONNECTIONS TO THE COLUMN
REPLACE EXISTING FLOORBEAM
(SITE NO. 3), SEE DETAILS IN DRAWING S-6
STRINGER TO FB-9 NORTH SIDE ONLY
REPLACE CONNECTION OF EXISTING
FLANGE OF FLOORBEAM
LONG COVER PLATE TO BOTTOM
" THICK X 8" WIDE X 14'-9" ±2
1ADD
L OF RAMPC
1 2
TOP OF PAVEMENT
EDGE OF C.M.U. WALL
TOP OF CURB
FLOOR BEAM
STRINGER (TYP.)
"=1'2
1SCALE:
TYPICAL EXISTING CROSS SECTION
2'-0"2'-0"
CURB TO CURB
14'-3"
STRINGER
ENCASEMENT OF EXISTING
LIMITS OF REMOVAL CONCRETE
2'-0"2'-0"
CITY OF BRIDGEPORT
ENCASEMENT REMOVED BY
EXISTING STRINGER CONCRETE
DETERIORATED SURFACES FOLLOWING REPAIR.
REMOVAL OF EXISTING ENCASED CONCRETE OR WHERE STEEL IS EXPOSED AS A RESULT OF RUSTED OR INTUMESCENT FIRE-RESISTANT PAINT SHALL BE APPLIED ONLY WHERE EXISTING STEEL IS EXPOSED DUE TO
PAINTING OF EXISTING STEEL” SHALL BE APPLICABLE ONLY TO AREAS OF STRUCTURAL STEEL REPAIRS.
PAY LIMITS FOR “INTUMESCENT FIRE-RESISTANT PAINT” AND “LOCALIZED PAINT REMOVAL AND FIELD
NOTE:
FIRE-RESISTANT PAINT
& APPLICATION OF INTUMESCENT
LIMITS OF SURFACE PREPARATION
FIRE-RESISTANT PAINT
& APPLICATION OF INTUMESCENT
LIMITS OF SURFACE PREPARATION
W18X35
W18X35
DO DO
W18X35
W18X35
DO
W18X35
W18X35
DO
W18X35
W18X35
DO
W18X35
W18X35
DO
W18X35
W18X35
DO
W18X35
W18X35
DO
W18X35
W18X35
W16X31
W18X35
W16X26
W18X35
W18X35
DO DO
W18X35
W18X35
DO
W18X35
W18X35
DO
W18X35
W18X35
DO
W18X35
W18X35
DO
W18X35
W18X35
DO
W18X35
W18X35
DO
W18X35
W18X35
W16X31
W18X35
W16X26
W 18X35
W X
W X
W 24X68
W 18X40W
18X35
W X
W X
W X
" 7
15'-3"
STATIONS
BASELINE
FB1 (W21X44) W21X50)FB2 ( DO)FB3 ( DO)FB4 ( DO)FB5 ( DO)FB6 ( DO)FB7 ( DO)FB8 (
W21X50)FB9 (
W
X
W36X135
W36X135
W
X
1" 10"
S
P A
C E
S
"2
1"
5"
1"
" 2
21'-6"
1"10"
1'-6"
" ±2
1'-7 ±" 2
1'-7
3'-0" ± 3'-0"
1"6"
±" 2
1'-7
±1'-1"
1" 6"
±" 2
1'-7
±1'-1"
PROJECT DESCRIPTION:
BID NUMBER: DRAWING NO.
SHEET NO.
2/11/2026
BLOCK:
SIGNATURE/
DRAWING TITLE: MISCELLANEOUS DETAILS AT F2 COLUMN
S-4
TOWN(S):
DESIGNER/DRAFTER: S.R.K. CHECKED BY: R.H.S.
MNB035263
BRIDGEPORT
REHABILITATION OF THE ACCESS RAMP OF MARGARET E. MORTON GOVERNMENT CENTER
PLOTTED DATE:
Y:\Projects\R127-8 Condition Inspection of Bridgeport City Hall 999 Broad St\CAD\Ramp Repairs\F2 Details.dgn FILE NAME: rhsuser15 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
1'-6"
T Y
P
CL
FB-6 TO REMAIN
(FLOORBEAM)
W21X50
FORM
OVER STAY-IN-PLACE
EXISTING DECK SLAB
TOP & BOTTOM PLATE
8" X 8" X 1" THICK
HSS6.000X0.250
ANGLE TO REMAIN
EXISTING C.M.U. WITH
AT FLOORBEAM AT COLUMN LINE F2 (SITE NO. 1)
PROPOSED STRUCTURAL STEEL REPAIR DETAILS
"=1'2
SCALE: 1
NORTH SIDE AT COLUMN LINE F2
"=1'2
SCALE: 1
SOUTH SIDE AT COLUMN LINE F2
"=1'2
SCALE: 1
SECTION B
CL
(COLUMN LINE F2)
W12X106 CL
W18X35
STRINGER (S3)
1" DIA. A325 BOLTS (TYP.)
BIGGER TO ACCOMODATE (5)
"16
AND REAM BOLT HOLE TO 1
REPLACE EXISTING BOLTS
(S3) TO REMAIN
EXISTING STRINGER
HSS6.000X0.250
PLATE
TOP AND BOTTOM
8" X 8" X 1" THICK
SUPPORT BRACKET
SUPPORT TO REMAIN
EXISTING COLUMN AND
EXISTING PAVEMENT
ANGLE TO REMAIN
EXISTING C.M.U. WITH
ANGLE TO REMAIN
EXISTING C.M.U. WITH
B
S-4
B
S-4
CL
W18X35
STRINGER (S3)
(COLUMN LINE F2)
W12X106 CL
CL
W21X50 (FLOORBEAM)
W12X106 (COLUMN LINE F2)&
"=1'2
SCALE: 1
NORTH SIDE AT COLUMN LINE F2
"=1'2
SCALE: 1
SOUTH SIDE AT COLUMN LINE F2
EXISTING DETAILS AT COLUMN LINE F2
"=1'2
SCALE: 1
SECTION A
FORM
OVER STAY-IN-PLACE
EXISTING DECK SLAB
CL
FB-6 TO REMAIN
(FLOORBEAM)
W21X50
A
S-4
CL
(COLUMN LINE F2)
W12X106 CL
W18X35
STRINGER (S3)
EXISTING PAVEMENT
TO REMAIN
STRINGER (S3)
EXISTING
BOLTS AND ANGLE
REMOVE EXISTING
ANGLE
EXISTING C.M.U. WITH
WITH ANGLE
EXISTING C.M.U.
CL
W18X35
STRINGER (S3)
(COLUMN LINE F2)
W12X106 CL W21X50 (FLOORBEAM)
W12X106 (COLUMN LINE F2)ANDCL
(TYP.)
STRINGER (S3)
EXISTING
ANGLES
BOLTS AND
REMOVE EXISTING
16'' LONG
" THICK X2
WITH L5X5X
REPLACE EXISTING ANGLE
16" LONG
" THICK X2
WITH L5X5X
REPLACE EXISTING ANGLE
NOT SHOWN FOR CLARITY.
EXISTING DECK & STRINGERS
NOTE:
ANGLE TO REMAIN
EXISTING C.M.U. WITH
EXISTING DECK NOT SHOWN FOR CLARITY.
NOTE:
H.S. BOLTS (TYP.)
" DIA. A325 8
H.S. BOLTS (TYP.)
" DIA. A325 8
4 SPACES @ 3" = 12"
1" DIA. A325 H.S. BOLTS(TYP.)
WEST FLANGE
ON COLUMN F2
FULL WIDTH X 2' ±
” SECTION LOSS16
OF ANGLE
AT BOTTOM FLANGE
" THICK REMAINING8
FLANGE OF ANGLE
4" X 2" HOLE AT BOTTOM
" THICK REMAINING AND 8
WEST FLANGE
ON COLUMN F2
FULL WIDTH X 2' ±
” SECTION LOSS16
ANGLE
BOTTOM FLANGE OF
& 4" X 2" HOLE AT
" THICK REMAINING8
ANGLE
EXISTING C.M.U. WITH
FLOORBEAM
BOTTOM FLANGE OF
FULL WIDTH X 3' ±
ECTION LOSS S
TO COVER HOLE
UNDER EXISTING ANGLE
" THICK PLATE 8
3LONG X
INSTALL 3" WIDE X18"
PLATE TO EXISTIN ANGLE
C.M.U. TO WELD NEW
TRIM EDGE OF EXISTING
UNDER EXISTING ANGLE
3" WIDE PLATE
" THICK X8
3INSTALL
OF ANGLE
STING BOTTOM FLANGE EXI
A
S-4
EXISTING PAVEMENT
BOLTS & ANGLE
REMOVE EXISTING
STRINGER (S3)
EXISTING
WITH ANGLE
EXISTING C.M.U.
WEST FLANGE
ON COLUMN LINE F2
FULL WIDTH X 2' ±
” SECTION LOSS 16
OF ANGLE
AT BOTTOM FLANGE
" THICK REMAINING 8
FLOORBEAM
BOTTOM FLANGE OF
FULL WIDTH X 3' ±
ECTION LOSS S FLOORBEAM
BOTTOM FLANGE OF
" LOSS FULL WIDTH X 3' ±4
ANGLE
BOTTOM FLANGE OF
" THICK REMAINING AT 8
WITH ANGLE
EXISTING C.M.U.
1" DIA. A325 BOLT (TYP.)
BIGGER TO ACCOMODATE (5)
"16
1 AND REAM BOLT HOLE TO 1
REPLACE EXISTING BOLTS
(S3) TO REMAIN
EXISTING STRINGER
PLATE
TOP AND BOTTOM
8" X 8" X 1" THICK
SUPPORT BRACKET
SUPPORT TO REMAIN
EXISTING COLUMN AND
PAVEMENT
EXISTING
ANGLE TO REMAIN
EXISTING C.M.U. WITH
16" LONG
" THICK X2
1 WITH L5X5X
REPLACE EXISTING ANGLE
H.S. BOLTS (TYP.)
" DIA. A325 8
SEE LIMITS IN S-3
ENCASEMENT,
REMOVE CONCRETE
PROPOSED SUPPORT BRACKETS FOR GOOD FIT
EXISTING STRUCTURAL STEEL PRIOR TO THE FABRICATIONS OF
CONTRACTOR TO FIELD VERIFY DIMENSIONS AND SIZES OF
NOTE:
SEE LIMITS IN S-3
ENCASEMENT,
REMOVE CONCRETE
SUPPORT SYSTEM NO. 1 SHALL REMAIN IN PLACE.
PAID UNDER ITEM NO. 0603779A "TEMPORARY SUPPORT SYSTEM NO. 1". TEMPORARY
SUPPORT BRACKET, HSS6.000X0.250, STEEL PLATES AND CONNECTION BOLTS SHALL BE
NOTE:
(TYP.)
HSS6.000X0.250
3 - SIDES
TIGHT FIT
TIGHT FIT
1" CLIP IN PLATE
1" CLIP IN PLATE
2-2
1"10"
1'-6"
1" 6"
1'-0"1'-0"
PROJECT DESCRIPTION:
BID NUMBER: DRAWING NO.
SHEET NO.
2/13/2026
BLOCK:
SIGNATURE/
DRAWING TITLE: MISCELLANEOUS DETAILS-1 AT C2 COLUMN
S-5
TOWN(S):
DESIGNER/DRAFTER: S.R.K. CHECKED BY: R.H.S.
MNB035263
BRIDGEPORT
REHABILITATION OF THE ACCESS RAMP OF MARGARET E. MORTON GOVERNMENT CENTER
PLOTTED DATE:
Z:\Projects\R127-8 Condition Inspection of Bridgeport City Hall 999 Broad St\CAD\Ramp Repairs\Column C2 Details.dgn FILE NAME: Rhsuser20 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
SCALE: 1"=1'
PLAN
SCALE: 1"=1'
PLAN
(COLUMN LINE C2)
W14X120 CL
(COLUMN LINE C2)
W14X120 CL
S3 S2
S3 S2
(FB9)
EXISTING FLOORBEAM
AT FLOOR BEAM AT COLUMN LINE C2 (SITE NO. 2)
PROPOSED STRUCTURAL STEEL REPAIR DETAILS
EXISTING DETAILS AT COLUMN LINE C2 "=1'2
SCALE: 1
NORTH SIDE AT COLUMN LINE C2
"=1'2
SCALE: 1
NORTH SIDE AT COLUMN LINE C2
CL
(COLUMN LINE C2)
W14X120 CL W18X35 (S3)
CL W18X35 (S2)
CL
(FLOORBEAM FB9)
W21X50
TO REMAIN
EXISTING FLOORBEAM
BOLTS AND ANGLE
REMOVE EXISTING
EXISTING PAVEMENT
FORM
OVER STAY-IN-PLACE
EXISTING DECK SLAB
PLATE NORTHSIDE ONLY
BOLTS AND ANGLE /
REMOVE EXISTING
RUST
WEB DUE TO HEAVY LAMINATED
SECTION LOSS ALONG BOTTOM
" DEEP 8
6' LONG X 4" HIGH X
REMAINING ON BOTTOM FLANGE
" THICKNESS4
LAMINATED RUST,
SECTION LOSS DUE TO HEAVY
6' LONG X FULL WIDTH FLANGE
TOP FLANGE. DO NOTHING.
TO HEAVY LAMINATED RUST ON
" SECTION LOSS DUE8
" TO 16
X
6' LONG X FULL WIDTH FLANGE
OF STRINGER (S3)
REMAINING ON BOTTOM FLANGE
" THICKNESS4
LAMINATED RUST,
SECTION LOSS DUE TO HEAVY
2' LONG X FULL WIDTH FLANGE
AT NORTH SIDE ONLY
ALONG WEB OF FLOORBEAM FB9
" THICK8
INSTALL 6" HIGH PLATE X
AND GRIND OFF WELD SMOOTH
REMOVE EXISTING PLATE / ANGLE
PROPOSED SUPPORT BRACKET
" DIA. A325 H.S. BOLTS (TYP.)10# 1
1/2" THICK X 16" L ANGLE 5"X5"X
OFF WELD SMOOTH & INSTALL
REMOVE EXISTING ANGLE, GRIND
ACCOMODATE (5) 1" DIA A325 BOLTS
" DIA TO16
HOLE SIZE TO 1
REMOVE EXISTING BOLTS & REAM
SEE LIMITS IN S-3
FROM STRINGER (S3)
CONCRETE AND FIRE-PROOFING
REMOVE EXISTING IN-CASED
TO REMAIN
EXISTING FIRE-PROOFING
TO REMAIN
FIRE-PROOFING
EXISTING
CL
(FLOORBEAM FB9)
W21X50
CL W18X35 (S2)
CL W18X35 (S3)
CL
LINE C2)
(COLUMN
W14X120
PROPOSED PAVEMENT
FORM
OVER STAY-IN-PLACE
EXISTING DECK SLAB
BRACKET
PROPOSED SUPPORT
EXISTING STRINGER (TYP.)
S2 S3
S3 S2
(FB9)
EXISTING FLOORBEAM
PLATE IN S-6
SEE DETAIL FOR COVER
A
S-6
EXISTING C.M.U. TO REMAIN
EXISTING C.M.U. TO REMAIN
OF BRIDGEPORT TO REMAIN
" INSTALLED BY CITY1 L6X6X
COVER PLATE
1/2" THICK X 8" WIDE
BRIDGEPORT TO REMAIN
" INSTALLED BY CITY OF1 L6X6X
(TYP.)
3" MIN. (TYP.)
3" (TYP.)
(TYP.)
BENT PLATE
" THICK 2
NSTALL I
16"L ANGLE NORTHSIDE ONLY
" THICK X2
5"X5"X PLATE WITH
REPLACE EXISTING ANGLE /
NORTH SIDE ONLY
OF FLOORBEAM FB9 OF
6" HIGH PLATE ALONG WEB
" THICK X 8
INSTALL
"TEMPORARY SUPPORT SYSTEM NO. 2". TEMPORARY SUPPORT SYSTEM NO. 2 SHALL REMAIN IN PLACE.
PROPOSED SUPPORT BRACKET AND CONNECTION BOLTS SHALL BE PAID UNDER ITEM NO. 0603780A 2.
TO THE FABRICATIONS OF PROPOSED SUPPORT BRACKETS FOR GOOD FIT.
CONTRACTOR TO FIELD VERIFY DIMENSIONS AND SIZES OF EXISTING STRUCTURAL STEEL MEMBERS PRIOR 1.
NOTE:
1" DIA A325 BOLT
" DIA HOLE TO ACCOMODATE16
BOLTS AND REAM HOLE SIZE TO 1
REMOVE EXISTING ANGLE &
ACCOMODATE (4) 1" DIA A325 BOLTS
" DIA TO 16
HOLE SIZE TO 1
REMOVE EXISTING BOLTS & REAM
" THICK BENT PLATE2
INSTALL D
S-6
2-2
1" CLIP IN PLATE
EXISTING C.M.U. TO REMAIN
SHEET NO.
2/13/2026
BLOCK:
SIGNATURE/
DRAWING TITLE: MISCELLANEOUS DETAILS-2 AT C2 COLUMN
S-6
TOWN(S):
DESIGNER/DRAFTER: S.R.K. CHECKED BY: R.H.S.
MNB035263
BRIDGEPORT
REHABILITATION OF THE ACCESS RAMP OF MARGARET E. MORTON GOVERNMENT CENTER
PLOTTED DATE:
Z:\Projects\R127-8 Condition Inspection of Bridgeport City Hall 999 Broad St\CAD\Ramp Repairs\Column C2 Details.dgn FILE NAME: Rhsuser20 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
2'-6"
(6) 6" BLOCKS
3'-0"
" AT4
(COLUMN LINE C2)
W14X120 CL
(COLUMN LINE C2)
W14X120 CL
VERTICAL POST
.250 HSS6.000X0
"=1'4
SCALE:
PROPOSED STRINGER REPAIRS AT TEMPORARY SUPPORT AT NORTH SIDE C2 (SITE NO. 3)
CONCRETE PAD
RAISED
W16X26 (S3)
EXISTING STRINGER
X16" L ANGLE
" THICK2
& INSTALL 5"X5"X
GRIND OFF WELD SMOOTH
REMOVE EXISTING ANGLE,
A325 BOLT
ACCOMODATE (5) 1" DIA.
" BIGGER TO16
AND REAM BOLT HOLE TO
REPLACE EXISTING BOLTS
"=1'2
SCALE: 1
SECTION A
"2
1"
5"
1"
"2
1'-0"
S
P A
C E
S
SCALE: 3"=1'
SECTION B
B
S-6
CL
FLOORBEAM FB9
W21X50
"=1'4
SCALE:
COVER PLATE UNDER FLOORBEAM FB9 AT COLUMN LINE-C
(TYP.)
EXISTING STRINGER
WELDED COVER PLATE
" THICK X 8" WIDE2
COVER PLATE
" THICK X 8" WIDE2
IN THIS SHEET
SEE DETAIL C
SCALE: 3"=1'
DETAIL C
PLAN
FB9
FLOORBEAM
W21X50CL
COVER PLATE
" THICK2
8" WIDE X
3" 1'-0"
FLOORBEAM
BOTTOM FLANGE OF
END OF COVER PLATE AT
FLOORBEAM FB9
W21X50CL
SIDE ONLY
FLOORBEAM OF NORTH
THICK ALONG WEB OF
"8
INSTALL 6" HIGH PLATE X
1'-0" 1'-0"
(FLOORBEAM)
W21X50
"TEMPORARY SUPPORT SYSTEM NO. 3".
TO SUPPORT THE STRINGER SHALL BE PAID FOR UNDER ITEM NO. 0603781A
STEEL PLATES, BEVELED STEEL PLATE, TIMBER BLOCKS, AND HSS6.000X0.250 2.
SUPPORT BRACKETS FOR GOOD FIT.
TO THE FABRICATIONS OF PROPOSED STRUCTURAL STEEL MEMBERS PRIOR
CONTRACTOR TO FIELD VERIFY DIMENSIONS AND SIZES OF EXISTING 1.
NOTE:
COVER PLATE
" THICK X 8" WIDE2
TO REMAIN
EXISTING ANGLE / PLATE
TOP OF 2ND FLOOR
LONG TIMBER BLOCKS
2 LAYERS OF (6) 6"X6"X3'-0"
SIDE ONLY
FLOORBEAM OF NORTH
PLATE ALONG WEB OF
THICK X 6" HIGH"8
INSTALL
"=1'2
SCALE: 1
SECTION D
(COLUMN LINE C2)
W14X120 CL
SIDE ONLY
WEB OF STRINGER INSIDE
" THICK ALONG8
PLATE X
INSTALL 2'-0" LONG 6" HIGH
SIDE ONLY
WEB OF STRINGER INSIDE
" THICK ALONG8
PLATE X
INSTALL 2'-0" LONG 6" HIGH
W18X35
EXISTING STRINGER
X 1'-0" LONG BENT PLATE
" THICK2
INSTALL 8"X5"X
1" DIA A325 BOLTS
" DIA TO ACCOMODATE (8)16
SIZE TO 1
REMOVE EXISTING BOLTS & REAM HOLE
S3 W16X26
EXISTING STRINGERCL
S2 W16X31
EXISTING STRINGERCL
S1 W18X35
EXISTING STRINGERCL
1'-0"
2-2
"4
PLATE SECURED TO BOTTOM FLANGE
" THICK AT BEVELED4
10"X10"X
SECURED TO WOODEN BLOCKS
" THICK PLATE4
10"X10"X
"16
WIDTH
EXISTING FLANGE
S1 W18X35
EXISTING STRINGERCL
SECURE TO CONCRETE FLOOR
4'-0"X4'-0"X1" STEEL PLATE
X 1'-0" LONG BENT PLATE
" THICK2
INSTALL 8"X5"X
CL
CL
"16
FACE OF THE COLUMN
3-SIDES
SHEET NO.
2/11/2026
BLOCK:
SIGNATURE/
DRAWING TITLE: TRENCH DRAIN REPAIR DETAILS
S-7
TOWN(S):
DESIGNER/DRAFTER: S.R.K. CHECKED BY: R.H.S.
MNB035263
BRIDGEPORT
REHABILITATION OF THE ACCESS RAMP OF MARGARET E. MORTON GOVERNMENT CENTER
PLOTTED DATE:
Y:\Projects\R127-8 Condition Inspection of Bridgeport City Hall 999 Broad St\CAD\Ramp Repairs\Framing Plan.dgn FILE NAME: rhsuser15 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
L
1 2
B
S-7
L OF RAMPC
CURB LINE CURB LINE
SIDEWALK
LANDING UPTO EXISTING
PROPOSED CONCRETE
TRENCH DRAIN
PROPOSED PRECAST
WALL
FOUNDATION
EXISITNG
OF EXISTING CURB
REMOVAL LIMITS
SIDEWALK
UPTO EXISTING
EXCAVATION LIMITS
L
1 2
L OF RAMPC
CURB LINE
CURB LINE
TRENCH DRAIN
REMOVE AND REPLACE
2% MIN. SLOPE
JOINT SEALER
" 2
" X 2
JOINT FILLER WITH
" PREFORMED EXPANSION2
EXISTING SIDEWALK
GRANULAR FILL
12" THICK
GRANULAR FILL
LANDING
6" THICK CONCRETE
6"6"
1'-2"
FOUNDATION WALL
EXTERIOR FACE OF
6" MIN. EMBEDMENT
DRILL & BOND 2 #4 @12"
OVERLAY
" PROPOSED BITUMINOUS2
EXISTING RAMP
CHANNELS OR APPROVED EQUAL
POWERDRAIN-S300K IRON EDGED
PROPOSED PRECAST TRENCH DRAIN
WALL
FOUNDATION
EXISITNG
OVERLAY
TOP OF BITUMINOUS
EXISTING SIDEWALK
FOUNDATION WALL
EXTERIOR FACE OF
EXISTING RAMP
TRENCH DRAIN
REMOVE & REPLACE
EXISTING TRENCH DRAIN AT COLUMN LINE-L1 & L2
"=1'2
SCALE:
PLAN
"=1'2
SCALE:
PLAN
"=1'4
SCALE:
SECTION-A
A
S-7
"=1'4
SCALE:
SECTION-B
PROPOSED TRENCH DRAIN AT COLUMN LINE-L1 & L2
L
IM
IT
S
O F
E X
C A
V A
T
IO
N
EDGE OF EXISTING SIDEWALK
LIMITS OF EXCAVATION TO
6" MIN EMBEDMENT
DRILL & BOND #4 @ 12" MIDWAY
FABRIC MIDWAY(TYP.)
6 X 6 W4 XW4 WELDED WIRE
BITUMINOUS/CONCRETE LANDING
REMOVE EXISTING
NOTE:
SHOWN IN PLAN SHALL BE PAID FOR UNDER THE ITEM "STRUCTURE EXCAVATION - EARTH (COMPLETE)".
REMOVAL OF BITUMINOUS/ CONCRETE LANDING AND THE LIMITS OF STRUCTURAL EXCAVATION AS
PROJECT DESCRIPTION:
BID NUMBER: DRAWING NO.
SHEET NO.
2/11/2026
BLOCK:
SIGNATURE/
DRAWING TITLE: JOINT REPAIR DETAILS-1
S-8
TOWN(S):
DESIGNER/DRAFTER: S.R.K. CHECKED BY: R.H.S.
MNB035263
BRIDGEPORT
REHABILITATION OF THE ACCESS RAMP OF MARGARET E. MORTON GOVERNMENT CENTER
PLOTTED DATE:
Y:\Projects\R127-8 Condition Inspection of Bridgeport City Hall 999 Broad St\CAD\Ramp Repairs\Joint Repair Details.dgn FILE NAME: rhsuser15 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
" JOINT SEALER (TYP.)2
" X 2
WITH
" PREFORMED EXPANSION JOINT2
L FLOORBEAMC
L FLOORBEAMC
(TYP.)
L FLOORBEAMC
L FLOORBEAMC
L FLOORBEAMC
(TYP.)
L FLOORBEAMC
A
S-8
"=1'4
SCALE:
PLAN
"=1'4
SCALE:
PLAN
"=1'1SCALE:
SECTION-A
"=1'1SCALE:
SECTION-B
TYPICAL EXISTING JOINT DETAIL AT RAMP FLOORBEAM
TYPICAL PROPOSED REPAIR AT RAMP FLOORBEAM
TOP & BOTTOM (TYP.)
DRILL & BOND 2#6
IN SLAB 6" MIN EMBEDMENT (TYP.)
DRILL & BOND #6 @ 12" MIDWAY CURB LINE
OVERLAY AND CURB
EXISTING RAMP CONCRETE
LIMITS OF REMOVAL
MEMBRANE WATERPROOFING
" BITUMINOUS OVERLAY WITH2
RECONSTRUCT DECK & CURB
4'-0"
TO TOP OF EXISTING DECK
MATCH TOP OF PROPOSED DECK
BITUMINOUS OVERLAY
REMOVE 1" +/- TOP OF
LIMITS OF REMOVAL DECK & CURB
4'-0"
CONCRETE OVERLAY
1" SAW CUT EXISTING
#6 @ 6"
@ 6" MIDWAY (TYP.)
DRILL & BOND #6
OVERLAY
6" ± CONCRETE
DECK TO REMAIN
EXISTING STRUCTURAL
CURB LINE
CURB LINE
#6 @ 6"
SECTION AT JOINT IN S-9
SEE DETAIL TYPICAL CROSS
CURB LINE
1 2
1 2
1'-6" SPLICE
IN SLAB 6" MIN. EMBEDMENT (TYP.)
DRILL & BOND #6 @ 12" MIDWAY
INTO SLAB
1" SAW CUT
INTO SLAB
1" SAW CUT
#4 @ 12"
LEGEND:
LIMITS OF REMOVAL
B
S-8
6" 14'-3" 6"6"
6" 14'-3" 6" 6"
OF RAMP, SEE DETAILS IN S-11.
AND BACKER ROD X FULL LENGTH
IMPREGNATED FOAM GLAND
MATERIAL AND INSTALL NEW
REMOVE EXISTING JOINT
OF RAMP, SEE DETAILS IN S-11.
AND BACKER ROD X FULL LENGTH
IMPREGNATED FOAM GLAND
MATERIAL AND INSTALL NEW
REMOVE EXISTING JOINT
LIMITS OF REMOVAL EXISTING RAMP CONCRETE OVERLAY & CURB
15'-3"
2 SPACES @ 7'-6" = 15'-0"
2 SPACES @ 7'-6" = 15'-0"
6" ±
6"6" 6"
"2
1'-4 "2
1'-7
"2
1'-7"2
1'-4
" JOINT SEALER2
" X 2
WITH
" PREFORMED EXPANSION JOINT2
2'-0" SPLICE
PROJECT DESCRIPTION:
BID NUMBER: DRAWING NO.
SHEET NO.
2/11/2026
BLOCK:
SIGNATURE/
DRAWING TITLE: JOINT REPAIR DETAILS-2
S-9
TOWN(S):
DESIGNER/DRAFTER: S.R.K. CHECKED BY: R.H.S.
MNB035263
BRIDGEPORT
REHABILITATION OF THE ACCESS RAMP OF MARGARET E. MORTON GOVERNMENT CENTER
PLOTTED DATE:
Y:\Projects\R127-8 Condition Inspection of Bridgeport City Hall 999 Broad St\CAD\Ramp Repairs\Joint Repair Details.dgn FILE NAME: rhsuser15 LASTED SAVED BY:
R E
V
D A
T E
R E
V
IS
IO
N
D E
S C
R
IP
T
1" COVER
RECONSTRUCT CONCRETE OVERLAY & CURB
15'-3"
6"
6"
LINE (TYP.)
L COLUMN C
LINE (TYP.)
L COLUMN C
LINE (TYP.)
L COLUMN C
LINE (TYP.)
L COLUMN C
"=1'4
SCALE:
EXISTING CROSS SECTION
"=1'4
SCALE:
PROPOSED CROSS SECTION
STRINGER (TYP.)
(TYP.)
FLOORBEAM
TO REMAIN
EXISTING REINFORCEMENT
FLOOR BEAM
STRINGER (TYP.)
TO REMAIN
EXISTING REINFORCEMENT
MEMBRANE WATERPROOFING
" BITUMINOUS OVERLAY WITH2
"STEEL (MISCELLANEOUS)"
STEEL PLATE AT JOINT SHALL BE PAID UNDER THE ITEM NO. 0603431 2.
" THICK X 6" WIDE STEEL PLATE SECURED TO DECK.4
SEALER &
TYPICAL WHERE APPLICABLE BACKER ROD TOPPED WITH JOINT 1.
NOTE:
SCALE: 3"=1'
TYP. CROSS SECTION AT JOINT
FIELD VERIFY EXISTING CONCRETE OVERLAY THICKNESS
NOTE:
#6 @ 6"#4 @ 12"
LIMITS OF REMOVAL
SCALE: 3"=1'
TYP. CURB REINFORCEMENT CROSS SECTION AT JOINT
#4 @ 12"
"4
#6 @ 6"
BACKER ROD
JOINT SEALER OVER
BE FIELD VERIFIED
BACKER ROD SIZE TO
SECURED TO DECK SLAB
" THICK X 6" WIDE STEEL PLATE 4
MEMBRANE WATERPROOFING
" BITUMINOUS OVERLAY WITH2
MEMBRANE WATERPROOFING
" BITUMINOUS OVERLAY WITH2
TO REMAIN
EXISTING CURB
OF RAMP, SEE DETAILS IN S-11.
AND BACKER ROD X FULL LENGTH
IMPREGNATED FOAM GLAND
MATERIAL AND INSTALL NEW
REMOVE EXISTING JOINT
OF RAMP, SEE DETAILS IN S-11.
AND BACKER ROD X FULL LENGTH
IMPREGNATED FOAM GLAND
MATERIAL AND INSTALL NEW
REMOVE EXISTING JOINT
CHAMFER (TYP.)
3/4" X 3/4"
PLAN
BID NUMBER: DRAWING NO.
SHEET NO.
2/11/2026
BLOCK:
SIGNATURE/
DR…