Regarding RFQP06021700014 for a new Uninterrupted Power Supply System (UPS) in Dublin, CA:
Question: Is there a specific runtime required for the UPS batteries at full load or some other load?
Answer: 30minutes minimum run time on full load.
Additional information: This system is merely a system to sustain power until the main backup generator is active.
Question: Are the dimensions noted on the specifications required for installation, maximum dimensions, or just general dimensions of the existing UPS?
Answer: The generators dimensions listed, is the maximum allowable space provided for the new generator to be installed.
Question: How much runtime does the unit need?
Answer: 30 minutes Question: I see there is a battery cabinet requested, but can you state the runtime needed please?
Answer: 30 minute runtime for the back-up battery