Regarding RFQP06021700014 for a new Uninterrupted Power Supply System (UPS) in Dublin, CA:
Question: Is there a specific runtime required for the UPS batteries at full load or some other load?
Answer: We are requesting a 30 minute minimum run time on full load.
Additional information: This system is merely a system to sustain power until the main backup generator is active.
Question: Are the dimensions noted on the specifications required for installation, maximum dimensions, or just general dimensions of the existing UPS?
Answer: The generator dimensions listed, is the maximum allowable space provided for the new generator to be installed.
Question: How much runtime does the unit need?
Answer: Run time is 30 minutes.
Question: I see there is a battery cabinet requested, but can you state the runtime needed please?
Answer: The run time is 30 minutes for the back-up battery
Question: I have a question on item 0003 on RFQP06021700014, How many years would you like the extended warranty to be for?/ How many years would you like the extended warranty to be for?
Answer: We would like you quote 2 years of extended warranty, in addition to the initial 1 year manufacturer warranty.