RFQ905101-01 - Exhibit G - Installation Instructions.pdf

PDF 3 MB Posted

Attached to
Iowa Law Enforcement Academy Office Cement Siding Replacement
Solicitation number
RFQ905101-01
Issued by
Warren County, Iowa

About this file

This document is a set of installation instructions for the Fiber Cement Ventilated Rainscreen System with One Layer Steel Attachment System using rivets, provided by American Fiber Cement (AFC) and dated June 7, 2023. The instructions support the Iowa Law Enforcement Academy Office Cement Siding Replacement project (RFQ905101-01) at Building 4640 located at 7105 NW 70th Ave in Johnston, Iowa on the Camp Dodge campus. The detailed technical specifications are designed to guide contractors in the proper installation of 5/16-inch fiber cement panels measuring 21 inches wide, utilizing 1-inch vertical Z-channels with G90 or black powder coat finishes and rivet fastening systems. The installation manual includes 28 detailed pages of architectural drawings and specifications covering panel configurations at various building locations, including coping, soffits, windows, corners, and base conditions, with standard panel vertical and horizontal joint spacing of 3/8 inch. The document specifies that rivets must be painted to match the panels and establishes maximum fastener spacing for soffit panels at 16 inches on center. Delta Fassade S membrane underlayment is required for all installations, and the system accommodates both continuous and break-in substrate conditions with specific offsetting requirements for Z-channel breaks relative to horizontal panel joints to maintain a minimum 3/4-inch gap between members.

The installation instructions establish that work requiring vendor designation as "BY AFC" includes supplying and installing fiber cement panels, Delta Fassade S membrane, painted rivets, Z-channels, and foam tape, while items designated "BY OTHERS" remain the responsibility of the general contractor or project stakeholders, including plywood sheathing, flashing, blocking, windows, soffits, and profile-to-sheathing fasteners. The specifications provide multiple detail options for various conditions, such as alternate configurations for soffit terminations and window head installations, offering flexibility in construction approaches while maintaining performance standards. Drilling requirements are specified with fixed points at 8.3 millimeters and gliding points at 12 millimeters, with drill bits sourced from American Fiber Cement. The document does not contain pricing information, set-aside provisions, or contract award details, serving solely as a technical reference guide to ensure compliant installation of the rainscreen siding system on the state facility project.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fiber Cem ent Ventilated Rainscreen System

One Layer Steel Attachment System with Rivets

6901 South Pierce Street, Suite 180, LiƩleton, CO 80128

303-972-5107 • FAX: 303-978-0308

AmericanFiberCement.com

Typical Details Page 3: Top Panel @ Coping Page 4: Top Panel @ Soffit Page 5: Top of Panel @ F.C.P Soffit Page 6: Horizontal Joint @ ConƟnuous Substrate Page 7: Horizontal Joint @ Break In Substrate Page 8: Not PermiƩed @ Break in Substrate Page 9: BoƩom of Panel @ Wall Base Page 10: BoƩom of Panel @ Open TerminaƟon Page 11: BoƩom of Panel @ Low Roof Flashing Page 12: BoƩom of Panel @ Soffit Page 13: BoƩom of Panel @ Soffit (Alternate) Page 14: BoƩom of Panel @Soffit Page 15: BoƩom of Panel @ F.C.P Soffit Page 16: BoƩom of Panel @ F.C.P Soffit (Alternate) Page 17: Soffit TerminaƟon @ Adjacent Material Page 18: BoƩom of Panel @ Window Head Page 19: BoƩom of Panel @ Window Head (Alternate) Page 20: Top of Panel @ Window Sill Page 21: Panel Edge @ Window Jamb Page 22: Panel Edge @ Window Jamb (Alternate) Page 23: VerƟcal Panel Joint OpƟon 1 Page 24: VerƟcal Panel Joint OpƟon 2 Page 25: Panel Edge @ BuƩ Joint Page 26: Panels @ Outside Corner Page 27: Panels @ Inside Corner Page 28: Typical Fastener Layout

NOTES:

1. PANEL VERTICAL AND HORIZONTAL JOINT

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Top of Panel @ Coping

One Layer Steel Attach System

AutoCAD SHX Text

5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHERS)

AutoCAD SHX Text

VENTILATION

AutoCAD SHX Text

MIN

AutoCAD SHX Text

MIN

AutoCAD SHX Text

BLOCKING (BY OTHERS)

AutoCAD SHX Text

COPING (BY OTHERS)

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Top of Panel@ Soffit

One Layer Steel Attach System-Rivets

AutoCAD SHX Text

MIN

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHERS)

AutoCAD SHX Text

5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)

AutoCAD SHX Text

VENTILATION

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

SOFFIT (BY OTHERS)

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Top of Panel @ F.C.P Soffit

One Layer Steel Attach System

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)

AutoCAD SHX Text

VENTILATION

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHERS)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL SOFFIT (BY AFC)

AutoCAD SHX Text

MIN

NOTE: : THE MAXIMUM FASTENER SPACING FOR SOFFIT PANELS IS 16" O.C.

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Horizontal Joint @ Continuous Substrate

One Layer Steel Attach System

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHERS)

AutoCAD SHX Text

5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)

VENTILATION

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Horizontal Joint @ Break in Substrate

One Layer Steel Attach System

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

AutoCAD SHX Text OFFSET BREAK IN Z-CHANNEL FROM EACH HORIZ PANEL JOINT. MINIMUM 3/4" GAP BETWEEN MEMBERS

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHERS)

AutoCAD SHX Text

5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Not Permitted @ Break in Substrate

One Layer Steel Attach System

NOT PERMITTED!

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Bottom of Panel @ Wall Base

One Layer Steel Attach System

AutoCAD SHX Text

5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)

AutoCAD SHX Text

FINISH BASE (BY OTHERS)

AutoCAD SHX Text

VENTILATION

AutoCAD SHX Text

METAL FLASHING W/ DRIP (BY OTHERS)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

PROFILE TO SHEATHING FASTENER (BY OTHERS)

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Bottom of Panel @ Open Termination

One Layer Steel Attach System-Rivets

AutoCAD SHX Text

5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)

AutoCAD SHX Text

VENTILATION

AutoCAD SHX Text

METAL BASE FLASHING (BY OTHERS)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHERS)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

NOTE: : HOLD BASE OF FIBER CEMENT PANEL 6"-12" OFF GRADE BASED ON EXPECTED SNOW BUILDUP

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Bottom of Panel @ Low Roof Flashing

One Layer Steel Attach System-Rivets

AutoCAD SHX Text

FLASHING (BY OTHERS)

AutoCAD SHX Text

METAL FLASHING WITH DRIP (BY OTHERS)

AutoCAD SHX Text

ROOFING MEMBRANE (BY OTHERS)

AutoCAD SHX Text

TERMINATION BAR (BY OTHERS)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHERS)

AutoCAD SHX Text

5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)

AutoCAD SHX Text

VENTILATION

MIN

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Bottom of Panel @ Soffit

One Layer Steel Attach System

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

VENTILATION

AutoCAD SHX Text

SOFFIT (BY OTHERS)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHHERS)

AutoCAD SHX Text

MIN

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

AutoCAD SHX Text

5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)

FLASHING WITH DRIP (BY OTHERS)

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Bottom of Panel @ Soffit(Alternate)

One Layer Steel Attach System

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

VENTILATION

AutoCAD SHX Text

SOFFIT (BY OTHERS)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

MIN

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY OTHERS)

AutoCAD SHX Text

METAL FLASHING WITH DRIP (BY OTHERS)

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHHERS)

5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Bottom of Panel @ Soffit

One Layer Steel Attach System

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

VENTILATION

AutoCAD SHX Text

SOFFIT (BY OTHERS)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHERS)

AutoCAD SHX Text

MIN

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Bottom of Panel @ F.C.P Soffit

One Layer Steel Attach System

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL SOFFIT (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)

AutoCAD SHX Text

VENTILATION

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHERS)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

MIN

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Bottom of Panel @ F.C.P Soffit(Alternate)

One Layer Steel Attach System

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL SOFFIT (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY OTHERS)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

VENTILATION

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

SHEATHING (BY OTHERS)

AutoCAD SHX Text

MIN

AutoCAD SHX Text

METAL FLASHING WITH DRIP (BY OTHERS)

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHERS)

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Soffit Termination @ Adjacent Material

One Layer Steel Attach System

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL SOFFIT (BY AFC)

AutoCAD SHX Text

SHEATHING (BY OTHERS)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY OTHERS)

AutoCAD SHX Text

ADJACENT MATERIAL (BY OTHERS)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHERS)

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Bottom of Panel @ Window Head

One Layer Steel Attach System-Rivets

AutoCAD SHX Text

5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)

AutoCAD SHX Text

BLOCKING (BY OTHERS)

AutoCAD SHX Text

WINDOW (BY OTHERS)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHERS)

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Bottom of Panel @ Window Head (Alternate)

One Layer Steel Attach System

AutoCAD SHX Text

SHEATHING (BY OTHERS)

AutoCAD SHX Text

BLOCKING (BY OTHERS)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY OTHERS)

AutoCAD SHX Text

VENTILATION

AutoCAD SHX Text

METAL FLASHING WITH DRIP (BY AFC)

AutoCAD SHX Text

MIN

AutoCAD SHX Text

WINDOW (BY OTHERS)

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Top of Panel @ Window Sill

One Layer Steel Attach System

AutoCAD SHX Text

5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)

AutoCAD SHX Text

SILL FLASHING (BY OTHERS)

AutoCAD SHX Text

BLOCKING (BY OTHERS)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHERS)

AutoCAD SHX Text

VENTILATION

AutoCAD SHX Text

MIN

AutoCAD SHX Text

MIN

AutoCAD SHX Text

WINDOW (BY OTHERS)

1" RECOMMENDED

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Panel Edge @ Window Jamb

One Layer Steel Attach System

AutoCAD SHX Text

FOAM TAPE (BY AFC)

AutoCAD SHX Text

PREFINISHED .032" ALUMINUM CLOSURE PROFILE (BY OTHERS)

AutoCAD SHX Text

5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)

AutoCAD SHX Text

BLOCKING (BY OTHERS)

AutoCAD SHX Text

WINDOW (BY OTHERS)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Vertical Panel Joint Option 1

One Layer Steel Attach System

AutoCAD SHX Text

5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)

AutoCAD SHX Text

FOAM TAPE (BY AFC)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHERS)

NOTE: : THIS DETAIL IS RECOMMENDED AT VERTICAL PANEL JOINTS.

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Vertical Panel Joint Option-2

One Layer Steel Attach System

AutoCAD SHX Text

5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)

AutoCAD SHX Text

FOAM TAPE (BY AFC)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text 1" VERT HAT-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY OTHERS)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

PROFILE TO SHEATHING FASTENER (BY OTHERS)

NOTE: : OPTION 1 DETAIL IS RECOMMENDED FOR VERTICAL PANEL JOINTS.

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Panel Edge @ Window Jamb Alternate

One Layer Steel Attach System

AutoCAD SHX Text

FOAM TAPE (BY AFC)

AutoCAD SHX Text

BLOCKING (BY OTHERS)

AutoCAD SHX Text

WINDOW (BY OTHERS)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

SHEATHING (BY OTHERS)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

JAMB CLOSURE FLASHING (BY OTHERS)

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Panel Edge @ Butt Joint

One Layer Steel Attach System

AutoCAD SHX Text

5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)

AutoCAD SHX Text

FOAM TAPE (BY AFC)

AutoCAD SHX Text

ADJACENT MATERIAL (BY OTHERS)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Panels @ Outside Corner

One Layer Steel Attach System

AutoCAD SHX Text

5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)

AutoCAD SHX Text

FOAM TAPE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

SPACING SHOULD BE 3/8" TYPICAL.

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180 Littleton, CO 80128

Panel @ Inside Corner

One Layer Steel Attach System

AutoCAD SHX Text

FOAM TAPE (BY AFC)

AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR VERT Z-CHANNEL W/ G90 OR VERT Z-CHANNEL W/ G90 OR Z-CHANNEL W/ G90 OR Z-CHANNEL W/ G90 OR W/ G90 OR W/ G90 OR G90 OR G90 OR OR OR BLACK POWDER COAT FINISH, POWDER COAT FINISH, POWDER COAT FINISH, COAT FINISH, COAT FINISH, FINISH, FINISH, SPACING PER PANEL FASTENERS (BY AFC)

AutoCAD SHX Text

5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)

AutoCAD SHX Text

RIVET PAINTED TO MATCH PANEL (BY AFC)

AutoCAD SHX Text

5/16" (8MM) FIBER CEMENT PANEL (BY AFC)

AutoCAD SHX Text

DELTA FASSADE S MEMBRANE (BY AFC)

Ref.:

Date: 06/07/2023

(303) 972-5107 www.americanfibercement.com

6901 S Pierce St #180

Littleton, CO 80128

Typical Fastner layout

Typical Steel And Aluminum Attachment System

Typical Edge Fastners

Scale 3"=1'

NOTES:

1. PANEL VERTICAL AND HORIZONTAL JOINT

SPACING SHOULD BE 3/8" TYPICAL.

AutoCAD SHX Text 21.00"

AutoCAD SHX Text 21.00"

AutoCAD SHX Text DRILLING KEY : : Metal (Steel and Aluminum) - Fixed Points 8.3 mm (Drill Bit Sourced from AFCC), Gliding Points 12mm (Drill Bit Sourced from AFCC)

AutoCAD SHX Text F

AutoCAD SHX Text F

SCALE 3/4"=1'-0"

ef1e5f3a8cb03b4a01a0dcf84bdc94fe1698311d27c9aed8e8c70c3f89100f99.pdf
c974612994bd7c4c581253cd10ea85491f7ebabb8d554e1ecf3f9d6c433b493c.pdf
fb5a5ec93ce0130103594780e38b277b5dba0f9f79e5bbbc36f94763917f6f7f.pdf
Microsoft Word - Cover Page

Microsoft Word - Table of Contents

01
Sheets and Views
AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-14
AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-11
AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-25
AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-24
AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-12
AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-13
AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-10
c974612994bd7c4c581253cd10ea85491f7ebabb8d554e1ecf3f9d6c433b493c.pdf
fb5a5ec93ce0130103594780e38b277b5dba0f9f79e5bbbc36f94763917f6f7f.pdf
88af5c4421d5d8bed3f05067a7b0a5b2d6810293256723b6e952d3123e0d6713.pdf
Sheets and Views
TYPICAL LAYOUTS-01
04
Sheets and Views
AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-04

ef1e5f3a8cb03b4a01a0dcf84bdc94fe1698311d27c9aed8e8c70c3f89100f99.pdf