This document is a set of installation instructions for the Fiber Cement Ventilated Rainscreen System with One Layer Steel Attachment System using rivets, provided by American Fiber Cement (AFC) and dated June 7, 2023. The instructions support the Iowa Law Enforcement Academy Office Cement Siding Replacement project (RFQ905101-01) at Building 4640 located at 7105 NW 70th Ave in Johnston, Iowa on the Camp Dodge campus. The detailed technical specifications are designed to guide contractors in the proper installation of 5/16-inch fiber cement panels measuring 21 inches wide, utilizing 1-inch vertical Z-channels with G90 or black powder coat finishes and rivet fastening systems. The installation manual includes 28 detailed pages of architectural drawings and specifications covering panel configurations at various building locations, including coping, soffits, windows, corners, and base conditions, with standard panel vertical and horizontal joint spacing of 3/8 inch. The document specifies that rivets must be painted to match the panels and establishes maximum fastener spacing for soffit panels at 16 inches on center. Delta Fassade S membrane underlayment is required for all installations, and the system accommodates both continuous and break-in substrate conditions with specific offsetting requirements for Z-channel breaks relative to horizontal panel joints to maintain a minimum 3/4-inch gap between members.
The installation instructions establish that work requiring vendor designation as "BY AFC" includes supplying and installing fiber cement panels, Delta Fassade S membrane, painted rivets, Z-channels, and foam tape, while items designated "BY OTHERS" remain the responsibility of the general contractor or project stakeholders, including plywood sheathing, flashing, blocking, windows, soffits, and profile-to-sheathing fasteners. The specifications provide multiple detail options for various conditions, such as alternate configurations for soffit terminations and window head installations, offering flexibility in construction approaches while maintaining performance standards. Drilling requirements are specified with fixed points at 8.3 millimeters and gliding points at 12 millimeters, with drill bits sourced from American Fiber Cement. The document does not contain pricing information, set-aside provisions, or contract award details, serving solely as a technical reference guide to ensure compliant installation of the rainscreen siding system on the state facility project.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fiber Cem ent Ventilated Rainscreen System
One Layer Steel Attachment System with Rivets
6901 South Pierce Street, Suite 180, LiƩleton, CO 80128
303-972-5107 • FAX: 303-978-0308
AmericanFiberCement.com
Typical Details Page 3: Top Panel @ Coping Page 4: Top Panel @ Soffit Page 5: Top of Panel @ F.C.P Soffit Page 6: Horizontal Joint @ ConƟnuous Substrate Page 7: Horizontal Joint @ Break In Substrate Page 8: Not PermiƩed @ Break in Substrate Page 9: BoƩom of Panel @ Wall Base Page 10: BoƩom of Panel @ Open TerminaƟon Page 11: BoƩom of Panel @ Low Roof Flashing Page 12: BoƩom of Panel @ Soffit Page 13: BoƩom of Panel @ Soffit (Alternate) Page 14: BoƩom of Panel @Soffit Page 15: BoƩom of Panel @ F.C.P Soffit Page 16: BoƩom of Panel @ F.C.P Soffit (Alternate) Page 17: Soffit TerminaƟon @ Adjacent Material Page 18: BoƩom of Panel @ Window Head Page 19: BoƩom of Panel @ Window Head (Alternate) Page 20: Top of Panel @ Window Sill Page 21: Panel Edge @ Window Jamb Page 22: Panel Edge @ Window Jamb (Alternate) Page 23: VerƟcal Panel Joint OpƟon 1 Page 24: VerƟcal Panel Joint OpƟon 2 Page 25: Panel Edge @ BuƩ Joint Page 26: Panels @ Outside Corner Page 27: Panels @ Inside Corner Page 28: Typical Fastener Layout
NOTES:
1. PANEL VERTICAL AND HORIZONTAL JOINT
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Top of Panel @ Coping
One Layer Steel Attach System
AutoCAD SHX Text
5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHERS)
AutoCAD SHX Text
VENTILATION
AutoCAD SHX Text
MIN
AutoCAD SHX Text
MIN
AutoCAD SHX Text
BLOCKING (BY OTHERS)
AutoCAD SHX Text
COPING (BY OTHERS)
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Top of Panel@ Soffit
One Layer Steel Attach System-Rivets
AutoCAD SHX Text
MIN
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHERS)
AutoCAD SHX Text
5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)
AutoCAD SHX Text
VENTILATION
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
SOFFIT (BY OTHERS)
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Top of Panel @ F.C.P Soffit
One Layer Steel Attach System
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)
AutoCAD SHX Text
VENTILATION
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHERS)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL SOFFIT (BY AFC)
AutoCAD SHX Text
MIN
NOTE: : THE MAXIMUM FASTENER SPACING FOR SOFFIT PANELS IS 16" O.C.
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Horizontal Joint @ Continuous Substrate
One Layer Steel Attach System
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHERS)
AutoCAD SHX Text
5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)
VENTILATION
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Horizontal Joint @ Break in Substrate
One Layer Steel Attach System
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
AutoCAD SHX Text OFFSET BREAK IN Z-CHANNEL FROM EACH HORIZ PANEL JOINT. MINIMUM 3/4" GAP BETWEEN MEMBERS
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHERS)
AutoCAD SHX Text
5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Not Permitted @ Break in Substrate
One Layer Steel Attach System
NOT PERMITTED!
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Bottom of Panel @ Wall Base
One Layer Steel Attach System
AutoCAD SHX Text
5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)
AutoCAD SHX Text
FINISH BASE (BY OTHERS)
AutoCAD SHX Text
VENTILATION
AutoCAD SHX Text
METAL FLASHING W/ DRIP (BY OTHERS)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
PROFILE TO SHEATHING FASTENER (BY OTHERS)
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Bottom of Panel @ Open Termination
One Layer Steel Attach System-Rivets
AutoCAD SHX Text
5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)
AutoCAD SHX Text
VENTILATION
AutoCAD SHX Text
METAL BASE FLASHING (BY OTHERS)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHERS)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
NOTE: : HOLD BASE OF FIBER CEMENT PANEL 6"-12" OFF GRADE BASED ON EXPECTED SNOW BUILDUP
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Bottom of Panel @ Low Roof Flashing
One Layer Steel Attach System-Rivets
AutoCAD SHX Text
FLASHING (BY OTHERS)
AutoCAD SHX Text
METAL FLASHING WITH DRIP (BY OTHERS)
AutoCAD SHX Text
ROOFING MEMBRANE (BY OTHERS)
AutoCAD SHX Text
TERMINATION BAR (BY OTHERS)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHERS)
AutoCAD SHX Text
5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)
AutoCAD SHX Text
VENTILATION
MIN
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Bottom of Panel @ Soffit
One Layer Steel Attach System
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
VENTILATION
AutoCAD SHX Text
SOFFIT (BY OTHERS)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHHERS)
AutoCAD SHX Text
MIN
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
AutoCAD SHX Text
5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)
FLASHING WITH DRIP (BY OTHERS)
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Bottom of Panel @ Soffit(Alternate)
One Layer Steel Attach System
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
VENTILATION
AutoCAD SHX Text
SOFFIT (BY OTHERS)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
MIN
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY OTHERS)
AutoCAD SHX Text
METAL FLASHING WITH DRIP (BY OTHERS)
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHHERS)
5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Bottom of Panel @ Soffit
One Layer Steel Attach System
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
VENTILATION
AutoCAD SHX Text
SOFFIT (BY OTHERS)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHERS)
AutoCAD SHX Text
MIN
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Bottom of Panel @ F.C.P Soffit
One Layer Steel Attach System
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL SOFFIT (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
5/8" 0R 3/4" PLYWOOD SHEATHING (BY OTHERS)
AutoCAD SHX Text
VENTILATION
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHERS)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
MIN
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Bottom of Panel @ F.C.P Soffit(Alternate)
One Layer Steel Attach System
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL SOFFIT (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY OTHERS)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
VENTILATION
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
SHEATHING (BY OTHERS)
AutoCAD SHX Text
MIN
AutoCAD SHX Text
METAL FLASHING WITH DRIP (BY OTHERS)
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHERS)
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Soffit Termination @ Adjacent Material
One Layer Steel Attach System
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL SOFFIT (BY AFC)
AutoCAD SHX Text
SHEATHING (BY OTHERS)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY OTHERS)
AutoCAD SHX Text
ADJACENT MATERIAL (BY OTHERS)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHERS)
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Bottom of Panel @ Window Head
One Layer Steel Attach System-Rivets
AutoCAD SHX Text
5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)
AutoCAD SHX Text
BLOCKING (BY OTHERS)
AutoCAD SHX Text
WINDOW (BY OTHERS)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHERS)
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Bottom of Panel @ Window Head (Alternate)
One Layer Steel Attach System
AutoCAD SHX Text
SHEATHING (BY OTHERS)
AutoCAD SHX Text
BLOCKING (BY OTHERS)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY OTHERS)
AutoCAD SHX Text
VENTILATION
AutoCAD SHX Text
METAL FLASHING WITH DRIP (BY AFC)
AutoCAD SHX Text
MIN
AutoCAD SHX Text
WINDOW (BY OTHERS)
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Top of Panel @ Window Sill
One Layer Steel Attach System
AutoCAD SHX Text
5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)
AutoCAD SHX Text
SILL FLASHING (BY OTHERS)
AutoCAD SHX Text
BLOCKING (BY OTHERS)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHERS)
AutoCAD SHX Text
VENTILATION
AutoCAD SHX Text
MIN
AutoCAD SHX Text
MIN
AutoCAD SHX Text
WINDOW (BY OTHERS)
1" RECOMMENDED
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Panel Edge @ Window Jamb
One Layer Steel Attach System
AutoCAD SHX Text
FOAM TAPE (BY AFC)
AutoCAD SHX Text
PREFINISHED .032" ALUMINUM CLOSURE PROFILE (BY OTHERS)
AutoCAD SHX Text
5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)
AutoCAD SHX Text
BLOCKING (BY OTHERS)
AutoCAD SHX Text
WINDOW (BY OTHERS)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Vertical Panel Joint Option 1
One Layer Steel Attach System
AutoCAD SHX Text
5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)
AutoCAD SHX Text
FOAM TAPE (BY AFC)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHERS)
NOTE: : THIS DETAIL IS RECOMMENDED AT VERTICAL PANEL JOINTS.
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Vertical Panel Joint Option-2
One Layer Steel Attach System
AutoCAD SHX Text
5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)
AutoCAD SHX Text
FOAM TAPE (BY AFC)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text 1" VERT HAT-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY OTHERS)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
PROFILE TO SHEATHING FASTENER (BY OTHERS)
NOTE: : OPTION 1 DETAIL IS RECOMMENDED FOR VERTICAL PANEL JOINTS.
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Panel Edge @ Window Jamb Alternate
One Layer Steel Attach System
AutoCAD SHX Text
FOAM TAPE (BY AFC)
AutoCAD SHX Text
BLOCKING (BY OTHERS)
AutoCAD SHX Text
WINDOW (BY OTHERS)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
SHEATHING (BY OTHERS)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
JAMB CLOSURE FLASHING (BY OTHERS)
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Panel Edge @ Butt Joint
One Layer Steel Attach System
AutoCAD SHX Text
5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)
AutoCAD SHX Text
FOAM TAPE (BY AFC)
AutoCAD SHX Text
ADJACENT MATERIAL (BY OTHERS)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Panels @ Outside Corner
One Layer Steel Attach System
AutoCAD SHX Text
5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)
AutoCAD SHX Text
FOAM TAPE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR BLACK POWDER COAT FINISH, SPACING PER PANEL FASTENERS (BY AFC)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
SPACING SHOULD BE 3/8" TYPICAL.
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180 Littleton, CO 80128
Panel @ Inside Corner
One Layer Steel Attach System
AutoCAD SHX Text
FOAM TAPE (BY AFC)
AutoCAD SHX Text 1" VERT Z-CHANNEL W/ G90 OR VERT Z-CHANNEL W/ G90 OR VERT Z-CHANNEL W/ G90 OR Z-CHANNEL W/ G90 OR Z-CHANNEL W/ G90 OR W/ G90 OR W/ G90 OR G90 OR G90 OR OR OR BLACK POWDER COAT FINISH, POWDER COAT FINISH, POWDER COAT FINISH, COAT FINISH, COAT FINISH, FINISH, FINISH, SPACING PER PANEL FASTENERS (BY AFC)
AutoCAD SHX Text
5/8" OR 3/4" PLYWOOD SHEATHING (BY OTHERS)
AutoCAD SHX Text
RIVET PAINTED TO MATCH PANEL (BY AFC)
AutoCAD SHX Text
5/16" (8MM) FIBER CEMENT PANEL (BY AFC)
AutoCAD SHX Text
DELTA FASSADE S MEMBRANE (BY AFC)
Ref.:
Date: 06/07/2023
(303) 972-5107 www.americanfibercement.com
6901 S Pierce St #180
Littleton, CO 80128
Typical Fastner layout
Typical Steel And Aluminum Attachment System
Typical Edge Fastners
Scale 3"=1'
NOTES:
1. PANEL VERTICAL AND HORIZONTAL JOINT
SPACING SHOULD BE 3/8" TYPICAL.
AutoCAD SHX Text 21.00"
AutoCAD SHX Text 21.00"
AutoCAD SHX Text DRILLING KEY : : Metal (Steel and Aluminum) - Fixed Points 8.3 mm (Drill Bit Sourced from AFCC), Gliding Points 12mm (Drill Bit Sourced from AFCC)
AutoCAD SHX Text F
AutoCAD SHX Text F
SCALE 3/4"=1'-0"
| ef1e5f3a8cb03b4a01a0dcf84bdc94fe1698311d27c9aed8e8c70c3f89100f99.pdf |
| c974612994bd7c4c581253cd10ea85491f7ebabb8d554e1ecf3f9d6c433b493c.pdf |
| fb5a5ec93ce0130103594780e38b277b5dba0f9f79e5bbbc36f94763917f6f7f.pdf |
| Microsoft Word - Cover Page |
Microsoft Word - Table of Contents
| 01 |
| Sheets and Views |
| AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-14 |
| AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-11 |
| AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-25 |
| AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-24 |
| AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-12 |
| AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-13 |
| AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-10 |
| c974612994bd7c4c581253cd10ea85491f7ebabb8d554e1ecf3f9d6c433b493c.pdf |
| fb5a5ec93ce0130103594780e38b277b5dba0f9f79e5bbbc36f94763917f6f7f.pdf |
| 88af5c4421d5d8bed3f05067a7b0a5b2d6810293256723b6e952d3123e0d6713.pdf |
| Sheets and Views |
| TYPICAL LAYOUTS-01 |
| 04 |
| Sheets and Views |
| AFCC-OLSA-One-Layer-Steel-Attach-System-RIVETS-04 |
ef1e5f3a8cb03b4a01a0dcf84bdc94fe1698311d27c9aed8e8c70c3f89100f99.pdf
File details come from the government source that posted it. Updated .