RFQ 27-005 Attachment 1 Electrical Modifications Drawing Set v2.pdf
PDF 1 MB Posted
- Attached to
- RFQ 27 005 Springfield Union Station Bus Berth Display Replacement Electrical Modifications
- Solicitation number
- BD-26-2263-PTA01-PTVA1-135613
- Issued by
- Hampden County, Massachusetts
About this file
This document is an electrical modifications drawing set for the Springfield Union Station Bus Berth Display Replacement Project managed by the Pioneer Valley Transit Authority (PVTA). The project encompasses the replacement of thirty-four (34) bus berth passenger information displays at Springfield Union Station, requiring structural modifications to existing display mounts, changes to the bus berth electrical system, and installation of new displays. The scope includes upgrading the shelter and canopy bus stop electrical wiring to current Massachusetts Electrical Code standards. The project involves modifications to two bus shelter breaker panels and one canopy breaker panel, with specific recommendations including correction of a tripped breaker on Bus Shelter Breaker Panel 2 (Breaker 7 serving Berth 10) and rewiring of the last bus berth in the chain on Bus Shelter Breaker Panel 1 (Breaker 5 serving Berths 1, 2, and 3) to a new 20-ampere breaker to prevent exceeding amperage requirements for the new displays.
The document provides detailed electrical specifications, junction box layouts, wiring diagrams, and dimensional drawings for both shelter and canopy bus stop configurations. Key modifications include replacing Mini-Con-X connectors and direct display wiring with new IEC C14 inlet connections, removing female power cord ends from new 10-foot outdoor-rated power cords and directly terminating wire leads to junction boxes, and replacing existing bus berth number sign three-conductor cables with extended lengths terminating through pass-thru cable glands. The canopy junction box may require replacement due to anticipated increased conductor terminations and the inclusion of a circuit switch. No pricing, set-asides, funding sources, or contract award information is provided in this technical drawing and specification document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFQ 27-005 Union Station Electrical Modifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Springfield Union Station Bus Berth Display Replacement Project
Electrical Modifications
PVTA is planning to replace thirty-four (34) Bus Berth Passenger Information Displays at the Springfield Union Station Facility.
The overall project encompasses structural modifications to the existing display mounts, changes to the bus berth electrical system, and the installation of new displays.
The following drawings outline the electrical changes needed to support the new displays.
Project Scope:
• Upgrade the Shelter and Canopy Bus Stop electrical wiring as outlined in the following pages.
• Recommend any changes needed to comply with current version of MA Electrical Code.
Springfield Union Station
(Project Overview)
(Electrical Equipment Specifications)
(Braker Panel Utilization)
Bus Shelter Breaker Panel 2Bus Shelter Breaker Panel 1
Braker 7 (Berth 10) tripped during testing.
The cause of the issue needs to be corrected.
Braker 5 (Berths 1, 2, & 3) will exceed the new Display required amperage as wired. PVTA recommends the last bus berth in the chain be rewired and moved to a new 20A braker.
Canopy Breaker Panel
Bus Shelter 11 Bus Shelter 10 Bus Shelter 9 Bus Shelter 8
Bus Shelter 15
Bus Shelter 16
Bus Shelter 17
Bus Shelter 14
Bus Shelter 13
Bus Shelter 12
Canopy Berth 1Canopy Berth 2
Canopy Berth 5 Canopy Berth 6 Canopy Berth 7Canopy Berth 4
Each Island Canopy Stop has 2 back-to-back Displays
Canopy Berth 3
Each Bus Shelter has 2 Displays, one on each side of the shelter.
Springfield Union Station Bus Berth Display Replacement Project
(Bus Berth Locations)
42.09”
25.55”
77.81” (6’ 5”)
Springfield Union Station
(Bus Stop Shelter Dimensions)
Figure 1 Figure 2 Figure 3
Springfield Union Station Bus Berth Display Replacement Project
(Existing Bus Stop Shelter Electrical Wiring)
Each bus shelter has an electrical Junction Box, a Bus Stop Display, and a lighted Berth Number on opposite ends of the shelter. (As shown on Dia. 1)
• The electrical junction boxes are located inside, on opposite ends of the shelter, affixed to the framing. (As shown on Fig. 1)
• The displays are wired directly to the junction box using 18 AWG, 3-conductor cable, and Mini-Con-X 3-pin bulkhead connectors. (As shown on Dia. 2 & Fig. 3)
• The berth number signs are wired to the displays using 3-conductor cable and waterproof pass thru cable glands. (As shown on Dia. 2)
Existing - Shelter Bus Stop Wiring Diagram
Junction Box 1
Shelter Display 1 Stop Number 1
Breaker Box
Junction Box 2
Shelter Display 2 Stop Number 2
Mini-Con-X (3-Pin)
Mini-Con-X (3-Pin)
Pass-Thru Cable Glands
Pass-Thru Cable Glands
Diagram 2
Existing – Shelter Bus Stop Layout
Display 2
Berth No 2
Bus Shelter
Berth No 1
Display 1
Diagram 1
The new displays have an IEC C14 inlet located on the back panel. (As shown on Fig. 4)
• The new displays come with a 10’, outdoor rated, power cord.
PVTA would like to have the female end of the power cord removed and its individual wire leads attached to the complementary leads in the junction box.
PVTA would like to have the existing Bus Berth Number Signs’ 3-conductor cable replaced due to the need extend its length.
• The new 3-conductor cable will terminate in the junction box, route to and through the berth number cable glands (As shown on Diag. 3 & Fig. 5) and connect to the complementary leads in the Berth Number Sign. (As shown on Fig. 6).
Springfield Union Station Bus Berth Display Replacement Project
(New Bus Stop Shelter Electrical Wiring)
Figure 6Figure 5Figure 4
New - Shelter Bus Stop Wiring Diagram
Junction Box 1
Display 1 Stop Number 1
Breaker Box
IEC C14 inlet Pass-Thru Cable Gland
Junction Box 2
Display 2 Stop Number 2
IEC C14 inlet Pass-Thru Cable Gland
Diagram 3
108.31” (9’ 0”)
42.09”
25.55”
Springfield Union Station
(Canopy Bus Stop Dimensions)
The Canopy Bus Stop Displays and Number Signs are mounted back-to-back (As shown on Fig. 7 & Dia. 4)
• The electrical junction box is located on top of the display mount. (As shown on Fig. 9)
• The electrical junction box is connected to Shelter Display using 18 AWG 3-conductor cable and Mini-Con-X 3-pin bulkhead connectors. (As shown on Dia. 4)
• The bus berth signs obtain power from the Display using 3-conductor wire and pass-thru cable glands. (As shown on Dia. 4)
• Atop the Canopy Junction Boxes is a circuit on/off switch (As shown in Figure 10)
• This Junction Box may need to be due to the anticipated increased number of conductors, terminations, and the inclusion of a circuit switch.
Springfield Union Station Bus Berth Display Replacement Project
(Canopy Bus Stop Electrical Upgrade)
Figure 9Figure 8Figure 7
Diagram 4
Existing - Canopy Bus Stop Wiring Diagram
Canopy Display 1
Canopy Display 2
Berth Sign 1
Berth Sign 2
Mini-Con-X (3-Pin) Connectors
Pass-Thru Cable Glands Breaker
Box
Junction Box
Figure 10
Bus Berth Display Replacement Project
(Canopy Bus Stop Electrical Upgrade)
The new displays have an IEC C14 inlet located on the back panel. (As shown on Fig. 11)
• The new displays come with a 10’, outdoor rated, power cord.
PVTA would like to have the female end of the power cord removed and its individual wire leads attached to the complementary leads in the junction box.
PVTA would like to have the existing Bus Berth Number Signs’ 3-conductor power cable replaced.
• The new 3-conductor cable will terminate in the junction box, route to and through the stop number cable glands (As shown on Diag. 5 & Fig. 12), and connect to the complementary leads in the Berth Number Sign. (As shown on Fig. 13), Figure 13Figure 12Figure 11
Diagram 5
New - Canopy Bus Stop Wiring Diagram
Canopy Display 1
Canopy Display 2
Berth Sign 1
Berth Sign 2
IEC C14 inlets
Pass-Thru Cable Glands Breaker
Box
Junction Box