RFQ_16-530-CV_Final.pdf

PDF 346 KB Posted

Attached to
BVL Substation Wall Mount A/C Units
Solicitation number
RFQ #16-530-CV
Issued by
Florida

About this file

This Request for Quotation (RFQ #16-530-CV) is issued by the Kissimmee Utility Authority (KUA), a Florida local government agency, for the procurement of two wall-mounted air conditioning units. The specific equipment required is the Bard model BARW24A2A10 with heater option package EHWA 02A-A10B, or an equivalent that meets exact specifications for direct replacement of existing units. The units must feature single-phase 230/208V, 60Hz AC voltage, 23,600 BTUH cooling capacity, 9.00 Energy Efficiency Ratio (EER), R-410A green refrigerant, standard 1-inch filters, standard beige color, and a 10kW heater package with FLA ratings of 41.6/36.2. Quotations were due by Friday, September 9, 2016, at 10:00 AM local time, to be submitted via fax or email to the KUA Finance & Administration Department. The delivery location is 2850 N. John Young Parkway, Kissimmee, Florida 34741, and all delivery costs must be included in the quoted price with FOB destination terms.

Award selection will be based on quoted pricing including both units and delivery fees, warranty period and optional extended warranty availability, lead time, and if equivalent units are proposed, current user references and fitment specification evaluation. All prices must exclude Florida State Sales and Use Taxes as KUA is tax-exempt. Quoters must provide both unit price and extended total pricing, with each item priced separately. The supplier bears all responsibility for compliance with OSHA, EPA, and Florida regulations, hazardous material provisions, Jessica Lunsford Act requirements for school board property access, I-9 verification compliance, and all indemnification obligations. No modifications to the RFQ terms and conditions are permitted, and any failure to deliver according to specifications or within the quoted timeframe may result in cancellation and procurement from alternative sources at the quoter's expense.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Title: BVL Substation Wall Mount A/C Units Request for Quotation RFQ #16-530-CV

REQUEST FOR QUOTATION

RFQ #16-530-CV

BVL Substation Wall Mount A/C Units

THIS IS NOT AN ORDER

QUOTER INFORMATION

Company______________________________

Name ________________________________

Address __________________________________

Address __________________________________

City/State/Zip ______________________________

Contact Person ____________________________

Phone Number ____________________________

Fax Number _______________________________

FEIN ____________________________________

DUE DATE: FRIDAY, SEPTEMBER 9, 2016 AT

10:00 AM LOCAL TIME

KISSIMMEE UTILITY AUTHORITY

Finance & Administration Department, Accounting/Purchasing Division Contact Person: Coraly Vazquez, CPPB, FCCM Address: 1701 W Carroll Street, Kissimmee, FL 34741 Phone Number: 407-933-9802 Fax Number: 407-932-3286 E-Mail Address: purchasing@kua.com

FOB – Destination. The articles to be furnished shall be deliver with all transportation charges paid by the Supplier to Kissimmee Utility Authority, Kissimmee, Florida.

INSTRUCTIONS: Provide your best selling price in the unit price column for the item(s) being quoted. If not quoting, please indicate “NO QUOTE” and return this form.

BVL SUBSTATION WALL MOUNT A/C UNITS

The pricing for two wall mounted AC units shall be for Bard model # BARW24A2A10, with heater option package EHWA 02A-A10B, or equivalent. These units are direct replacements for existing units and therefore must meet exact dimensions for mounting, intake and exhaust ducts, and power requirements for the current installations.

Care must be taken to ensure that the quoted units meet all of these requirements and specifications.

TECHNICAL REQUIREMENTS

The air conditioning units proposed shall meet the following requirements:

-Reference attached Bard specification sheet for additional details-

Wall-Mount Air Conditioning Unit

Single phase 230/208, 60hz AC voltage

23,600 BTUH cooling capacity

9.00 Energy Efficiency Ratio (EER)

R-410A green refrigerant

Use of 1” standard filter

Standard Beige color

Heater Package EHWA 02A-A10B

FLA 41.6/36.2

10kw

OPTIONAL ACCESSORIES

Extended warranties options.

BASIS OF AWARD

Quoted pricing, to include both units and delivery fees.

Warranty period, to include optional quoted extended warranties available.

Lead time.

If equivalent is quoted, then:

References for current users will be required and evaluated.

Fitment and specifications will be evaluated.

PRICING

BVL Substation Wall Mount AC Units

The following prices are all inclusive, delivered to 2850 N. John Young Parkway, Kissimmee, Florida, 34741.

Qty Description

Unit Price

Extended Price

2 Bard model #BARW24A2A10 AC Unit with Heater Package EHWA 02A-A10B

Total

Included Warranty Labor

Included Warranty Parts

Included Warranty Compressor

Delivery Lead Time

Extended Warranty Each Unit $

Details of proposed optional extended warranty

SIGNATURE___________________________________ ANY PURCHASE ORDER RESULTING FROM THIS

Print Name ____________________________________ QUOTATION WILL BE SUBJECT TO THE TERMS

Title__________________________________________ AND CONDITIONS CONTAINED HEREIN.

Date of Quote__________________________________

Payment Terms ________________________________

Will Deliver By _________________________________

RETURN BY DUE DATE ABOVE VIA FAX (407) 932-3286 or E-MAIL PURCHASING@KUA.COM

Kissimmee Utility Authority Page 3 of 7

GENERAL TERMS AND CONDITIONS

General

The terms and conditions of this order must not be changed by quoter. If order is not acceptable, return to Kissimmee Utility Authority. Failure of an awarded quoter to deliver according to the Purchase Order or to comply with any of the terms and conditions therein may disqualify him/her from receiving future orders.

KUA reserves the right to cancel this order if not filled within the quoted time, if specified.

The conditions of this order are not to be modified by any verbal understanding.

Acceptance of this order includes all terms, prices, delivery instructions, specifications and conditions stated.

No payment will be made for materials ordered without proper purchase order authorization.

Invoices and packages must bear this Purchase Order number.

Please forward all invoices to Accounts Payable.

Quality

KUA reserves the right to reject any or all materials/services if, in its judgment, the item/service reflects unsatisfactory workmanship or manufacturing or shipping damages. If any product/service delivered does not meet applicable specifications or if the product/service will not produce the effect that the quoter represents to KUA, the quoter shall remove the product or stop the service at no expense to KUA. Also, the quoter shall refund to KUA any money which has been paid for same. The quoter will be responsible for attorney fees in the event that he/she defaults and court action is required.

Pricing

Give both unit price and extended total. Prices must be stated in units of quantity specified. All prices for materials to include F.O.B. destination, freight prepaid unless otherwise stated. Each item must be priced separately and no attempt is to be made to tie any item or items in with any other item or items.

No quoter will be allowed to offer more than one price on each item/service even though he/she may feel that he/she has two or more types or styles/services that will meet specifications. Quoter must determine for themselves which to offer.

Prices bid shall be used for payment and these prices shall be deemed to include payment in full for all transportation in delivering all supplies to the point of delivery. All items to be provided under this contract shall be new (not used or reconditioned, and not of such age or so deteriorated as to impair their usefulness or safety), of current production and of the most suitable grade for the purpose intended.

This purchase by Kissimmee Utility Authority is tax exempt. Exemption Certificate Number is 85- 8012665901C-9. The price stated in this bid should exclude Florida State Sales and Use Taxes.

Kissimmee Utility Authority Page 4 of 7

Indemnity

The successful contractor(s) covenants and agrees to indemnify and save harmless KUA and to defend from all cost, expenses, damages, attorney's fees, injury or loss to which KUA and/or its board members, officials, directors, partners, consultants, agents, or employees may be subjected by any person, firm, corporation, or organization by reason of any wrongdoing, misconduct, want, or need of care or skill, negligence or default or breach of contract, guaranty, or warranty, by the successful contractor(s), his subcontractor, sub-supplier, any person or organization directly or indirectly employed by any of them to perform or furnish any of the work or anyone for whose acts any of them may be liable.

Packing & Delivery

Packages must be plainly marked with shipper’s name and Purchase Order Number; charges are not allowed for boxing or crating unless previously agreed upon in writing. All materials must be shipped F.O.B.

Destination. KUA will not pay freight or expense charges, except by previous agreement. The delivery must actually be affected within the time stated on Purchase Order. KUA reserves the right to cancel this order and purchase elsewhere if the quoter fails to meet the delivery date specified on Purchase Order. Deliveries shall be made between 9:00 a.m. and 3:00 p.m. on regular working days unless otherwise stated. Transport deliveries must be unloaded and ready for inspection prior to 3:00 pm. In case of default by the quoter, KUA may procure the articles or services covered by this order from other sources and hold the quoter responsible for any additional cost occasioned thereby.

Hazardous Material Provision

Where applicable, the quoter agrees to furnish KUA with a current Material Safety Data Sheet (MSDS) on or before delivery of each and every hazardous chemical or substance purchased which is classified as toxic under Chapter 422, Florida Statutes. Appropriate labels and MSDS’s shall be provided for all shipments.

Send MSDS’s and other pertinent data to Kissimmee Utility Authority (KUA) at the “Ship to” address.

Regulations

It shall be the responsibility of each quoter to assure compliance with all OSHA, EPA and/or Federal or State of Florida rules, regulations or other requirements, as each may apply.

Appeals & Remedies

Any person adversely affected by the decision or intended decision of award must file a written notice of protest to the Manager of Accounting within seventy-two (72) hours (excluding Saturday, Sundays, and legal holidays) after the posting of the KUA’s decision or intended decision. KUA Purchasing Division personnel should be contacted to obtain comprehensive written protest procedures prior to filing a written notice of protest.

Kissimmee Utility Authority Page 5 of 7

Compliance with Laws and Regulations

By its signature on the Contract Agreement, Contractor hereby certifies that it is aware of any and all applicable federal, state and local laws, regulations, orders of courts and/or governmental agencies, ordinances and permitting requirements and further certifies that it has taken or will take all actions necessary to ensure full compliance with such requirements, including full compliance by any subcontractors and/or materialmen employed by Contractor to perform on this Contract. Contractor agrees to indemnify and hold KUA harmless for any and all claims, losses, penalties, fines and expenses (including, without limitation, any and all reasonable attorney’s and expert’s fees) related to Contractor’s failure, and/or the failure of its subcontractors and materialmen, to abide by the terms of this Section.

Jessica Lunsford Act Compliance

In the event Contractor performs services for KUA on the premises of any Osceola County School Board property, Contractor hereby certifies that it complies with the Jessica Lunsford Act (Florida Statutes, 2005) and that all employees of Contractor, including the employees of subcontractors, materialmen, agents or anyone else hired by Contractor to perform work under this Contract, accessing such property in the performance of KUA-related work have cleared sexual predator/offender and U.S. Department of Justice criminal databases. Contractor agrees to furnish written proof of such compliance and a list of names of all of persons cleared before accessing any public school property on KUA-related work. Contractor also agrees not to permit any of its employees, or the employees of any subcontractors, materialmen, agents or anyone else hired by Contractor to perform KUA-related work, to access Osceola County School Board property if they have not been checked or cleared on the databases described herein. In the event Contractor fails to comply with this section, Contractor shall indemnify and hold KUA harmless for any and all claims, suits, actions, causes of actions, damages, losses, liability, expenses, or costs, in accordance with the terms and provisions of this Contract governing Contractor’s obligation to indemnify KUA.

KUA Sovereign Immunity

No provision in this award, resulting agreement, contract, or purchase order is intended, nor shall be construed, to be a waiver for any purpose by KUA of its sovereign immunity, and any accompanying limitations on KUA’s liability pursuant to same, as set forth in Florida Statutes, Chapter 768, Section 768.28.

No Third Party Beneficiaries

No provisions of this contract shall be construed to benefit in any way any party not a signatory hereto.

Disposal of Hazardous Waste and Used Materials

All hazardous waste and used materials, such as containers, liquids, rags, filters, and solvents, etc. must be disposed of in accordance with all Federal, State and Local regulations. Contractor agrees to indemnify and hold KUA harmless for any and all claims, losses, penalties, fines and expenses (including, without limitation, any and all reasonable attorney’s and expert’s fees) related to Contractor’s failure, and/or the failure of its subcontractors and materialmen, to abide by the terms of this Section.

Kissimmee Utility Authority Page 6 of 7

Certification of OSHA and Indemnification

By its signature on the Contract Agreement, Contractor hereby certifies that it is aware of any and all applicable federal and state requirements, including those imposed by rules and regulations of relevant governmental authorities, of the Occupational Safety and Health Act, and further certifies that it has taken and will take all actions necessary to ensure full compliance with such requirements, including compliance by its employees, subcontractors and materialmen (and any person employed by either) for the duration of this Contract. Contractor agrees to indemnify and hold KUA harmless for any and all claims, losses, penalties, fines and expenses (including, without limitation, any and all reasonable attorney’s and expert’s fees) related to Contractor’s failure, and/or the failure of its subcontractors and materialmen, to abide by the terms of this Section.

I-9 Verification Compliance and Indemnification

By its signature on the Contract Agreement, Contractor hereby certifies that it is aware of any and all applicable federal immigration law requirements, including, without limitation, Contractor’s obligation to properly verify the legal work status of each of its employees by the filing of a complete and accurate Form I-

9. Contractor also acknowledges the importance of ensuring that all personnel accessing any of KUA’s property have been properly verified through the I-9 documentation process. Accordingly, Contractor further certifies that it has taken and will take all actions necessary to ensure full compliance with the Form I-9 requirements, and any other applicable immigration law requirements, and shall also ensure the compliance with such requirements by any subcontractors and materialmen employed by Contractor on this Contract.

Contractor agrees to indemnify and hold KUA harmless for any and all claims, losses, penalties, fines and expenses (including, without limitation, any and all reasonable attorney’s and expert’s fees) related to Contractor’s failure, and/or the failure of its subcontractors and materialmen, to abide by the terms of this Section.

Florida Sunshine Law Requirements

Contractor acknowledges that KUA, as a local government agency, is subject to public records disclosure requirements contained in Florida Statutes, §119.07, et seq. Contractor further understands that to the extent it should act on behalf of KUA in carrying out the terms and conditions of this Contract, it would be subject to the public records retention and other requirements set forth in Florida Statutes, §119.0701.

Contractor acknowledges that it has read and is fully aware of the requirements set forth in Florida Statutes, §119.0701 and agrees to fully comply with the requirements therein to the extent it acts on behalf of KUA.

Governing Law, Jurisdiction and Venue

This Agreement, and all matters arising directly or indirectly from this Agreement, will be governed by and construed in accordance with the law of the State of Florida without giving effect to the conflicts of laws, provisions or principles thereof. For any legal action, suit, claim, or other proceeding arising out of or in any way connected with this Agreement, each of the parties to this Agreement consents to the exclusive jurisdiction and venue of the state and federal courts sitting in, or having principal jurisdiction over, Osceola County, Florida.

****END OF SECTION****

Kissimmee Utility Authority Page 7 of 7

ACCEPTANCE OF TERMS & CONDITIONS

I the undersigned accept in total all the terms and conditions stipulated and referenced in this Request for Quotation document and agree that if a contract is offered or negotiated it will abide by the terms and conditions presented in this Request for Quotation document or as negotiated pursuant thereto. The signature below is an acknowledgment of my full understanding and acceptance of all terms and conditions set forth in the Request for Quotation document or as otherwise agreed to between the parties in writing.

COMPANY NAME

SIGNATURE

NAME, TITLE, TYPED OR PRINTED

MAILING ADDRESS

CITY, STATE, ZIP CODE

FAX NUMBER

E-MAIL ADDRESS

FED ID

Form No. S3461-216 Supersedes S3461-915

Aluminum Finned Copper Coils:

Grooved tubing and enhanced louvered fin for maximum heat transfer and energy efficiency.

Twin Blowers:

Move air quietly. Most models feature multispeed blower motors providing airflow adjustment for high and low static operation. Motor overload protection is standard on all models.

Air Conditioner Compressor:

Scroll Compressors eliminate need for crankcase heater. Standard on all models.

R-410A Refrigerant:

Designed with R-410A (HFC) non-ozone depleting refrigerant in compliance with the Montreal protocol and 2010 EPA requirements.

Phase Rotation Monitor:

Standard on all 3 phase scroll compressors. Protects against reverse rotation if power supply is not properly connected.

Galvanized 20 Gauge Zinc Coated Steel Cabinet:

Cleaned, rinsed, sealed and dried before the polyurethane primer is applied. The cabinet is handsomely finished with a baked on textured enamel, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03.

Foil Faced Insulation:

Standard on all units.

Full Length Mounting Brackets:

Built into cabinet for improved appearance and easy installation.

NOTE: Bottom mounting bracket included to assist in installation.

Electrical Components:

Are easily accessible for routine inspection and maintenance through a right side, service panel opening. Features a lockable, hinged access cover to the circuit breaker or toggle disconnect switch.

Electric Heat Strips:

Features an automatic limit and thermal cut-off safety control. Heater packages can be factory or field installed.

Filter Service Door:

Separate service door provides easy access for filter change.

One Inch, Disposable Air Filters:

Are standard equipment. Optional one inch washable filters available and filter racks permit the addition of 2" pleated filter. Factory or field installed.

Condenser Fan and Motor Shroud Assembly:

Slides out for easy access.

Barometric Fresh Air Damper:

Standard on all units. Allows up to 25% outside fresh air. Optional ventilation packages available.

Built-in Circuit Breakers:

Standard on all electric heat versions of single (230/208 volt) and three phase

(230/208 volt) equipment. Toggle disconnects are standard on all electric heat versions of three phase (460 volt) equipment.

Slope Top:

Standard feature for water run-off.

Top Rain Flashing:

Standard feature on all models.

Liquid Line Filter Drier:

Standard on all units. Protects system against moisture.

The Bard Wall-Mount Air Conditioner is a self contained energy efficient system, which is designed to offer maximum indoor comfort at a minimal cost without using valuable indoor floor space or outside ground space. This unit is the ideal product for versatile applications such as: new construction, modular offices, school modernization, telecommunication structures, portable structures or correctional facilities. Factory or field installed accessories are available to meet specific job requirements.

THE WALL-MOUNT™ AIR CONDITIONERS - 9.0 EER, (60HZ)

Compressor Control Module:

Standard on all units. Built-in off-delay timer adjustable from 30 seconds to 5 minutes. 2-minute on-delay if power interrupt. 120-second bypass for low pressure control, and both soft and manual lockouts for high and low pressure controls. Alarm output for alarm relay.

High & Low Pressure Switches are Auto-Reset:

Standard on all units. Built-in lockout circuit resets from the room thermostat.

Provides commercial quality protection to the compressor.

Models W17A to W60A Right-Side Control Panel Models W17L to W60L Left-Side Control Panel

1.5 to 5 Ton (16,400 to 55,000 Btuh)

Engineered Features

GREEN REFRIGERANT

R-410A

• Complies with efficiency requirements of ASHRAE/IESNA 90.1-2010.

• Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units).

• Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL

1995/CSA 22.2 No. 236-05, Fourth Edition.

• Commercial Product - Not intended for Residential application.

Capacity is certified in accordance with ANSI/ARI Standard 390-2003.

EER = Energy Efficiency Ratio and is certified in accordance with ANSI/ARI Standard 390-2003.

All ratings based on fresh air intake being 100% closed (no outside air introduction).

Capacity and Efficiency Ratings

Specifications 1-1/2 Ton through 3 Ton

Specifications 3-1/2 Ton through 5 Ton

Models W17A2 / W18A2 W17L2 / W18L2

W24A2 W24L2

W30A2 W30L2

W36A2 W36L2

W42A2 W42L2

W48A2 W48L2

W60A2 W60L2

Cooling Capacity BTUH 16,400 23,600 29,400 35,000 40,000 48,500 55,000

EER 9.00 9.00 9.00 9.00 9.50 9.00 9.00

MODELS W17A2-A

W17L2-A

W18A2-A W18L2-A

W24A2-A W24L2-A

W24A2-B W24L2-B W24A2-C W30A2-A

W30L2-A W30A2-B W30L2-B

W30A2-C W30L2-C

W36A2-A W36L2-A

W36A2-B W36L2-B

W36A2-C W36L2-C

Electrical Rating – 60 Hz 230/208-1 230/208-1 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3

Operating Voltage Range 197-253 197-253 197-253 197-253 414-506 197-253 197-253 414-506 197-253 197-253 414-506

Compressor--Circuit A

Voltage 230/208 230/208 230/208 230/208 460 230/208 230/208 460 230/208 230/208 460

Rated Load Amps 6.5/7.4 6.3/7.2 9.6/11.2 6.3/7.3 4.5 12.2/13.9 7.8/8.9 5.6 15.3/17.2 11.3/12.7 5.8

Branch Circuit

Selection Current

9.0 9.0 12.9 8.4 5.2 14.2 9.0 5.7 18 13.3 6.0

Lock Rotor Amps 48/48 48/48 64/64 58/58 28 77/77 71/71 38 112/112 88/88 44

Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll

Fan Motor & Condenser

Fan Motor--HP--RPM 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075

Fan Motor--Amps 1.2 1.2 1.2 1.2 0.8 1.5 1.5 0.8 1.5 1.5 0.8

Fan--DIA/CFM 18" - 1700 18" - 1700 18" - 1700 18" - 1700 18" - 1700 20" - 2200 20" - 2200 20" - 2200 20" - 2000 20" - 2000 20" - 2000

Blower Motor & Evap.

Blower Motor--HP-RPM-SPD 1/6-1100-2 1/6-1100-2 1/6-1100-1 1/6-1100-1 1/6-1100-1 1/3-1100-2 1/3-1100-2 1/3-1100-2 1/3-1100-2 1/3-1100-2 1/3-1100-2

Blower Motor--Amps 1.0 1.0 0.8 0.8 .45 2.1 2.1 1.0 2.1 2.1 1.0

CFM Cooling & E.S.P.

w/Filter (Rated-Wet Coil) 600 - .40 550 - .45 800 - .30 800 - .30 800 - .30 1000 - .3 1000 - .3 1000 - .3 1100 - .2 1100 - .2 1100 - .2

Filter Sizes (inches) STD. 16x25x1 16x25x1 16x25x1 16x25x1 16x25x1 16x30x1 16x30x1 16x30x1 16x30x1 16x30x1 16x30x1

Shipping Weight --LBS. 295 295 295 295 295 320 320 320 340 340 340

MODELS W42A2-A

W42L2-A

W42A2-B W42L2-B

W42A2-C W42L2-C

W48A2-A W48L2-A

W48A2-B W48L2-B

W48A2-C W48L2-C

W60A2-A W60L2-A

W60A2-B W60L2-B

W60A2-C W60L2-C

Electrical Rating – 60 Hz 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3

Operating Voltage Range 197-253 197-253 414-506 197-253 197-253 414-506 197-253 197-253 414-506

Compressor--Circuit A

Voltage 230/208 230/208 460 230/208 230/208 460 230/208 230/208 460

Rated Load Amps 15.9/17.8 10.5/11.8 5.5 21/23.5 13.4/15 6.7 21.9/24.9 13/14.8 7.4

Branch Circuit

Selection Current

19.9 13.2 6.1 25 15.9 7.1 26.3 15.7 7.8

Lock Rotor Amps 109/109 83.1/83.1 41 134/134 110/110 52 134/134 110/110 52

Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll

Fan Motor & Condenser

Fan Motor--HP--RPM-SPD 1/3-825-2 1/3-825-2 1/3-825-1 1/3-825-2 1/3-825-2 1/3-825-1 1/3-825-2 1/3-825-2 1/3-825-1

Fan Motor--Amps 2.5 2.5 1.3 2.5 2.5 1.3 2.5 2.5 1.3

Fan--DIA/CFM 24" - 2700 24" - 2700 24" - 2700 24" - 2700 24" - 2700 24" - 2700 24" - 2500 24" - 2500 24" - 2500

Blower Motor & Evap.

Blower Motor--HP-RPM-SPD 1/3-985-2 1/3-985-2 1/3-985-2 1/3-985-2 1/3-985-2 1/3-985-2 1/2-1070-2 1/2-1070-2 1/2-1070-2

Blower Motor--Amps 2.3 2.3 1.2 2.3 2.3 1.2 3.5 3.5 1.9

CFM Cooling & E.S.P.

w/Filter (Rated-Wet Coil) 1400 - .45 1400 - .45 1400 - .45 1550 - .3 1550 - .3 1550 - .3 1700 - .4 1700 - .4 1700 - .4

Filter Sizes (inches) STD. 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1

Shipping Weight --LBS. 460 460 460 465 465 465 485 485 485

W24A2

W24A2-A

Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the factory or field-installed at a later date.

Ventilation System Packages

Barometric Fresh Air Damper

Motorized Fresh Air Damper

Commercial Room Ventilator

Energy Recovery Ventilator

BAROMETRIC FRESH AIR DAMPER - BFAD STANDARD

The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into the building and can be easily locked closed if required.

BLANK OFF PLATE - BOP OPTIONAL

A blank off plate is installed on the inside of the service door. It covers the air inlet openings, which restricts any outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not required to be mixed with the conditioned air.

MOTORIZED FRESH AIR DAMPER - MFAD OPTIONAL

The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower operation or can be field connected to be managed based on building occupancy.

COMMERCIAL ROOM VENTILATOR - CRV OPTIONAL

The built-in commercial room ventilator is internally mounted behind the service door and allows outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings.

It includes a built-in exhaust air damper.

The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled based on room occupancy. Two versions available (except on 1.5 and 2-Ton models). The CRV and CRVS are power open - spring return on power loss, and CRVP is power open and power close. Complies with ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality”.

ECONOMIZER – ECONWM-Series OPTIONAL The built-in economizer system is internally mounted behind the service door and allows outdoor air to be introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide

“free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running the compressor. This in turn provides lower operating costs, while extending the life of the compressor.

• ECONWMT Equipment Building versions have extended 11" air intake hood to deliver up to 100% of cooling rated airflow.

• ECONWMS Standard versions have 3" air intake hood to deliver up to 75% of cooling rated airflow.

Standard Features:

• Fully modulating

• Honeywell Direct Drive Hi-Torque Actuator

• No linkage required

• Simple single blade design

• Positive shut-off with non-stick gaskets

• Electronic DB and/or Enthalpy sensors depending upon version

• Honeywell JADE electronic economizer module with precision settings and diagnostics

• DB or Enthalpy economizer versions available

WALL-MOUNT ENERGY RECOVERY VENTILATOR - ERVF OPTIONAL

The wall-mount energy recovery ventilator (ERV) is a highly innovative approach to meeting indoor air quality ventilation requirements as established by ANSI/ASHRAE Standard 62.1. The ERV allows from 200 to 450 CFM

(depending upon model) of fresh air and exhaust through the unit while maintaining superior indoor comfort and humidity levels. In most cases this can be accomplished without increasing equipment sizing or operating costs.

Heat transfer efficiency is up to 67% during summer and 75% during winter conditions.

The ERV consists of a unique “rotary energy recovery cassette” that provides effective sensible and latent heat transfer capabilities during summer and winter conditions. Various control schemes are addressed including limiting ventilation during building occupancy only.

The ERV is designed to be internally mounted behind the service door in the W**A or W**L model wall-mount units. It can be built-in at the factory (W**A only) or field installed as an option. ERVF-*3 and ERVF-*5 can be independently adjusted for intake and exhaust rates.

NOTE: The above vent systems are intake only without built-in exhaust capability. Building will likely require separate field installed barometric relief or mechanical exhaust elsewhere within the conditioned space.

Balancing dampers in the return air grille may be required to achieve specified amount of outdoor air intake.

Economizer

W

W H

IG

H

S P

E E

D T

O

TA

L A

N D

V E

N T

IL

A

T

IO

N A

IR

F

L O

W W

W L

O W

S P

E E

D T

O

TA

L A

N D

V E

N T

IL

A

T

IO

N A

IR

F

L O

W

W /W

W T

O

TA

L A

N D

V E

N T

IL

A

T

IO

N A

IR

F

L O

W

C o m m er ci a l

R o o m

V en ti la to r

P er fo rm a n ce D a ta

C

R V

-2

C o m m er ci a l

R o o m

V en ti la to r

P er fo rm a n ce D a ta

C

R V

S -3 a n d C

R V

P -3

A B

C D

E F

Airflow (cfm)

V e n t P o s it io n

T o ta l A ir

E S

P

T o ta l A ir

E

S P

T o ta l A ir

E S

P

V e n t

A ir

E

S P

V e n t

A ir

E

S P

V e n t

A ir

E S

P

A B

C D

E F

Airflow (cfm)

V e n t P o s it io n

T o ta l A ir

E

S P

T o ta l A ir

E

S P

T o ta l A ir

E S

P

V e n t

A ir

E

S P

V e n t

A ir

E

S P

V e n t

A ir

E S

P

A B

C D

E F

Airflow (cfm)

V e n t P o s it io n

T o ta l A ir

E

S P

T o ta l A ir

E

S P

T o ta l A ir

E S

P

V e n t

A ir

E

S P

V e n t

A ir

E

S P

V e n t

A ir

E S

P

W

Caution

* Top outlet supply option is available only factory installed and only on the selected models.

IMPORTANT:

Electrical Code and all local codes.

MODEL

Rated Volts & Phase

No.

Field Power

Circuits

Single Circuit Dual Circuit

Minimum Circuit

Ampacity

Maximum External Fuse or

Ckt. Brkr.

Field Power

Wire Size

Ground Wire

Minimum Circuit

Ampacity

Maximum External Fuse or

Ckt. Breaker Field Power Wire Size

Ground Wire Size

Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B

W17, 18A2-A00,A0Z

A05

A08

A10

230/208-1

W24A2-A00, A0Z

A04

A05

A08

A10

230/208-1

W24A2-B00, B0Z

B06 230/208-3

W24A2-C00, C0Z

C06 460-3

W30A2-A00*, A0Z*

A05*

A08

A10*

A15

230/208-1

1 or 2

8 58 26 60 30 6 10 10 10

W30A2-B00*, B0Z*

B06

B09*

B15

230/208-3

W30A2-C00*, C0Z*

C06

C09*

C15

460-3

W36A2-A00*, A0Z*

A05*

A08

A10*

A15

230/208-1

1 or 2

8 58 26 60 30 6 10 10 10

W36A2-B00*, B0Z*

B06*

B09*

B15

230/208-3

W36A2-C00*, C0Z*

C06*

C09*

C15

460-3

W42A2-A00, A0Z

A05

A10

A15

A20

230/208-1

1 or 2

1 or 2

W42A2-B00, B0Z

B09

B15

B18

230/208-3

W42A2-C00, C0Z

C09

C15

460-3

W48A2-A00, A0Z

A05

A10

A15

A20

230/208-1

1 or 2

1 or 2

W48A2-B00, B0Z

B09

B15

B18

230/208-3

W48A2-C00, C0Z

C09

C15

460-3

W60A2-A00, A0Z

A05

A10

A15

A20

230/208-1

1 or 2

1 or 2

W60A2-B00, B0Z

B09

B15

B18

230/208-3

N/A

N/A

N/A

N/A 35 28 40 30 8 10 10 10

W60A2-C00, C0Z

C09

C15

460-3

Electrical Specifications — W**A Series

W24A2-A00, A10

230/208-1

1 56 60 6 10

Above data is with 1" standard throwaway filter and 1" washable filter.

For optional 2" pleated filter - reduce ESP by .15 in.

See installation instructions for maximum ESP information on various KW application.

Speed W17/W18 W24 W30 W36 W42/W48 W60

High Low Single High Low High Low High Low High Low

ESP

(Inch H20)

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

Dry

Coil

Wet

Coil

0.0 1045 1025 760 745 990 970 1370 1285 910 885 1415 1275 955 925 1850 1800 1605 1555 2080 2015 1505 1460

0.1 1010 970 730 715 945 925 1305 1225 885 860 1350 1215 945 915 1775 1725 1545 1500 2020 1960 1450 1405

0.2 940 905 700 685 890 870 1225 1135 850 815 1265 1125 925 900 1685 1640 1460 1415 1925 1865 1395 1355

0.3 860 830 670 655 820 800 1115 1020 790 755 1190 1060 875 850 1590 1550 1390 1345 1870 1815 1340 1300

0.4 780 750 610 595 735 720 1005 910 695 660 1085 975 780 755 1495 1460 1310 1270 1755 1705 1225 1185

0.5 665 640 485 455 605 590 865 775 590 560 970 865 640 615 1400 1365 1225 1185 1660 1610 1125 1085

Nominal

KW

At 240V (1) At 208V (1) At 480V (2) At 460V (2)

Kw 1-Ph Amps

3-Ph Amps Btuh Kw 1-Ph

Amps 3-Ph Amps Btuh Kw 3-Ph

Amps Btuh Kw 3-Ph Amps Btuh

5.0 5.0 20.8 17,065 3.75 18.0 12,799

6.0 6.0 14.4 20,478 4.50 12.5 15,359 6.0 7.2 20,478 5.52 6.9 18,840

8.0 8.0 33.3 27,304 6.00 28.8 20,478

9.0 9.0 21.7 30,717 6.75 18.7 23,038 9.0 10.8 30,717 8.28 10.4 28,260

10.0 10.0 41.7 34,130 7.50 36.1 25,598

15.0 15.0 62.5 36.1 51,195 11.25 54.1 31.2 38,396 15.0 18.0 51,195 13.80 17.3 47,099

18.0 18.0 43.3 61,434 13.50 37.5 46,076 18.0 21.7 61,434 16.56 20.8 56,519

20.0 20.0 83.3 68,260 15.00 72.1 51,195

(1) These electric heaters are available in 230/208V units only.

(2) These electric heaters are available in 480V units only.

Indoor Blower Performance (60 Hz) - CFM at Rated Volts

Electric Heat Table - Refer to Electrical Specifications for Availability by Unit Model

Factory Connected Speed.

W24

NOTE: Field installed Heater Packages are not approved for use with top supply opening models.

Field installed Heater Package not available for W70L models.

These heater packages approved for use in dehumidification versions with hot gas reheat.

Heater Packages - Field Installed "A" Series Right-Hand Units

• Designed for adding Electric Heat to 0 KW Units • ETL US & Canada Listed

• Circuit Breaker Standard on 230/208V Models • Toggle Disconnect Standard on 460V Models

Air Conditioner

Models

-A00 Models 230/208-1

-B00 Models 230/208-3

-C00 Models 460-3

Heater Model # KW Heater Model # KW Heater Model # KW

W17A2 W18A2

EHWA02-A05B

EHW02A-A08B

EHWA02A-A10B

N/A N/A

W24A2

EHWA24A-A04B

EHWA02-A05B

EHW02A-A08B

EHWA02A-A10B

EHWA24-B06B 6 EHWH24B-C06 6

W30A2

EHWA03-A05B

EHWA03-A08B

EHWA03-A10B

EHWA03-A15B

EHWA03-B06B

EHWA03-B09B

EHWA37-B15B

EHWC03A-C06

EHWC03A-C09

EHWA03A-C12

EHWA03A-C15

W36A2

EHWA03-A05B

EHWA03-A08B

EHWA03-A10B

EHWA03-A15B

EHW36A-B06B

EHWA03-B09B

EHWA37-B15B

EHWC03A-C06

EHWC03A-C09

EHWA03A-C12

EHWA03A-C15

W42A2 W48A2

EHWA05-A05B

EHWA05-A10B

EHWA05-A15B

EHWA05-A20B

EHWA05-B09B

EHWA05-B15B

EHWA05-B18B

EHWA05A-C09

EHWA05A-C15

W60A2

EHWA60-A05B

EHWA05-A10B

EHWA05-A15B

EHWA05-A20B

EHW60A-B09B

EHWA05-B15B

EHW05A-B18B

EHWA05A-C09

EHWA05A-C15

Air Conditioner

Models

-A00 Models 230/208-1

-B00 Models 230/208-3

-C00 Models 460-3

Heater Model # KW Heater Model # KW Heater Model # KW

W17L2 W18L2

EHWA02A-A05LB

EHW02A-A08LB

EHWA02-A10LB

N/A N/A

W24L2

EHWA02A-A05LB

EHW02A-A08LB

EHWA02-A10LB

EHWA24-B06LB 6 N/A

W30L2

EHWA03-A05LB

EHWA03-A08LB

EHWA03-A10LB

EHWA03-A15LB

EHWA03-B09LB

EHWA37-B15LB

EHWC03-C09L

EHWA03-C15L

W36L2

EHWA03-A05LB

EHWA03-A10LB

EHWA03-A15LB

EHWA03-B09LB

EHWA37-B15LB

EHWC03-C09L

EHWA03-C15L

W42L2 W48L2

EHWA05-A05LB

EHWA05-A10LB

EHWA05-A15LB

EHWA05-B09LB

EHWA05-B15LB

EHWA05A-C09L

EHWA05A-C15L

W60L2

EHWA05-A05LB

EHWA05-A10LB

EHWA05-A15LB

EHWA60-B09LB

EHWA05-B15LB

EHWA05A-C09L

EHWA05A-C15L

Heater Packages - Field Installed "L" Series Left-Hand Units

EHWA02A-A10B 10

3"

7.88 1.00

11"

31.88

Filter Access Panel

Air Outlet

Front View

Condenser

Standard flush vent door for non-ERV/ Econ.

models

Ventilation Air

W

5.88

F

G

Heat models.

Electric

Hood for

ECONWMT

MIS-2487 H

(Lockable)

Built In Rain Hood

4° Pitch

Entrance

High Voltage Entrance

Access Panel

Low Voltage

Disconnect

Heater

Panel Access

Air Inlet

Drain

Cond.

Electrical

Side View

Electrical

C. Breaker/

Hood for ERV and ECONWMS models only

1.250

H

A

I

D

J

2.13

C

K

Electrical

Side Wall

Entrances

Mounting

Optional

Supply Air Opening

(Built In)

Shipping Location

Brackets

Return Air Opening

Top Rain Flashing

Bottom Installation BracketBack View

T

B

M

O E

R

S

S

S

S

S P

.44

N Q

L

Dimensions of W17-60A Basic Unit for Architectural & Installation Requirements (Nominal)

MODEL WIDTH

(W)

DEPTH

(D)

HEIGHT

(H)

SUPPLY RETURN

A B C B E F G I J K L M N O P Q R S T

W17A2 W18A2 W24A2

33.300 17.125 70.563 7.88 19.88 11.88 19.88 35.00 10.88 25.75 20.56 26.75 28.06 29.25 27.00 2.63 34.13 22.06 10.55 4.19 12.00 5.00

W30A2 W36A2 38.200 17.125 70.563 7.88 27.88 13.88 27.88 40.00 10.88 25.75 17.93 26.75 28.75 29.25 27.00 2.75 39.13 22.75 9.14 4.19 12.00 5.00

W42A2 W48A2 W60A2

42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 1.88

Clearances Required for Service Access and Adequate Condenser Inlet Airflow

MODELS LEFT SIDE RIGHT SIDE

W17A, W18A, W24A, W30A, W36A 15" 20"

W42A, W48A, W60A 20" 20"

NOTE: For side-by-side installation of two (2) WA models, there must be 20" between units. This can be reduced to 15" by using a WL model (left side compressor and controls) for the left unit and WA (right side compressor and controls) for right unit.

Minimum Clearances Required to Combustible Materials

MODELS

SUPPLY AIR DUCT

FIRST THREE FEET CABINET

W17A, W18A, W24A 0" 0"

W30A, W36A 1/4" 0"

W42A, W48A, W60A 1/4" 0"

Refer to the Installation Manual for more detailed information.

Not used when ECONWMT Economizers installed. Filter access is through the ECONWMT hood.

Optional top outlet (factory installed only) in place of standard front supply air opening for W30A and W36A models only.

W24A, 15" 20"

W24A 0" 0"

33.300 17.125 70.563 7.88 19.88 11.88 19.88 35.00 10.88 25.75 20.56 26.75 28.06 29.25 27.00 2.63 34.13 22.06 10.55 4.19 12.00 5.00

Model Return Air (DB/WB) Cooling Capacity 75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F 120°F

W17A2 W17L2

75/62 Total Cooling

Sensible Cooling

17200

13900

16500

13600

15700

13400

15000

13000

14300

12700

13700

12400

13100

12000

12500

11700

11900

11400

11300

11000

80/67 Total Cooling

Sensible Cooling

18300

13400

17900

13300

17400

13200

16900

13000

16400

12800

15900

12600

15400

12300

14900

12100

14300

11800

13700

11500

85/72 Total Cooling

Sensible Cooling

21800

13800

21000

13500

20000

13300

19100

13000

18300

12600

17400

12200

16600

11800

15900

11400

15100

10900

14300

10400

W18A2 W18L2

75/62 Total Cooling

Sensible Cooling

17700

14200

16800

13800

16000

13400

15200

13000

14300

12600

13600

12300

12900

11900

12200

11600

11600

11300

10900

10900

80/67 Total Cooling

Sensible Cooling

18900

13700

18300

13500

17700

13200

17100

13000

16400

12700

15800

12500

15200

12200

14500

11900

13900

11700

13200

11400

85/72 Total Cooling

Sensible Cooling

22600

14100

21400

13700

20400

13300

19300

13000

18300

12500

17300

12100

16400

11700

15500

11200

14600

10800

13800

10300

W24A2 W24L2

75/62 Total Cooling

Sensible Cooling

25000

19800

23800

19300

22700

18800

21600

18300

20600

17900

19600

17300

18700

16900

17600

16400

16700

15900

15800

15400

80/67 Total Cooling

Sensible Cooling

26600

19200

25900

18900

25200

18600

24400

18300

23600

18000

22800

17600

22000

17300

21000

16900

20100

16500

19100

16100

85/72 Total Cooling

Sensible Cooling

31700

19700

30300

19200

29000

18700

27600

18200

26200

17700

25000

17100

23800

16500

22400

15900

21200

15200

19900

14600

W30A2 W30L2

75/62 Total Cooling

Sensible Cooling

30200

23500

29000

23400

27900

23200

26800

22700

25600

22300

24500

21700

23300

21100

22200

20300

21000

19500

19700

18600

80/67 Total Cooling

Sensible Cooling

32200

22800

31600

22900

31000

22900

30300

22700

29400

22500

28500

22100

27500

21600

26400

21000

25200

20300

23800

19400

85/72 Total Cooling

Sensible Cooling

38400

23400

37000

23300

35600

23000

34200

22600

32700

22100

31200

21400

29700

20600

28100

19700

26500

18700

24800

17600

W36A2 W36L2

75/62 Total Cooling

Sensible Cooling

37100

27700

35400

27100

33700

26400

32100

25700

30500

25100

29000

24300

27700

23600

26300

22800

25000

21900

23700

21100

80/67 Total Cooling

Sensible Cooling

39600

26800

38500

26500

37400

26100

36200

25700

35000

25300

33800

24700

32600

24200

31300

23500

30100

22800

28700

22100

85/72 Total Cooling

Sensible Cooling

47200

27500

45000

26900

43000

26200

40900

25600

38900

24800

37000

23900

35200

23100

33300

22100

31700

21000

29800

20000

W42A2 W42L2

75/62 Total Cooling

Sensible Cooling

42500

32800

40300

32600

38400

32100

36600

31500

34800

30800

33400

30100

32000

29200

30700

28200

29600

27000

28600

25800

80/67 Total Cooling

Sensible Cooling

45300

31800

43900

31900

42600

31800

41300

31500

40000

31100

38900

30600

37700

29900

36600

29100

35600

28100

34600

27000

85/72 Total Cooling

Sensible Cooling

54000

32600

51300

32400

48900

32000

46600

31300

44500

30500

42600

29600

40700

28500

39000

27300

37400

25900

36000

24400

W48A2 W48L2

75/62 Total Cooling

Sensible Cooling

53400

39900

50200

38800

47300

37700

44700

36600

42200

35500

40200

34500

38200

33400

36600

32400

35100

31400

33800

30500

80/67 Total Cooling

Sensible Cooling

57000

38700

54700

38000

52500

37300

50500

36600

48500

35800

46800

35100

45100

34300

43600

33500

42200

32700

40900

31900

85/72 Total Cooling

Sensible Cooling

67900

39600

64000

38600

60300

37500

57000

36400

53900

35100

51200

34000

48600

32700

46400

31400

44400

30100

42500

28800

W60A2 W60L2

75/62 Total Cooling

Sensible Cooling

57000

43700

54700

42800

52400

41700

50200

40700

47900

39600

45800

38600

43500

37500

41300

36500

39100

35400

36800

34200

80/67 Total Cooling

Sensible Cooling

60800

42400

59600

41900

58200

41300

56700

40700

55000

40000

53300

39300

51300

38500

49200

37700

47000

36800

44600

35800

85/72 Total Cooling

Sensible Cooling

72400

43400

69700

42500

66800

41500

64000

40400

61100

39200

58300

38000

55300

36700

52400

35400

49400

33900

46400

32400

Capacity Multiplier Factors % of Rated Airflow -10 Rated +10

Total BTUH Sensible BTUH

0.975

0.950

1.0

1.0

1.02

1.05

Below 65°F (18.3C), unit requires a factory or field installed low ambient control.

Return air temperature.

Cooling Application Data - Outdoor Temperature

Intake and exhaust can be independently adjusted.

Insert color to match unit ("X" = Beige; "4" = Buckeye Gray; etc.)

WMDK Door Kit must be ordered in addition to ERVF Assembly & color matched to unit ("X" = Beige; "4" = Buckeye Gray; etc.)

Partial Full Flow (75% of Rated Cooling CFM). All ECONWMS versions have 3" deep intake hood.

Full Flow (100% of Rated Cooling CFM). All ECONWMT versions have 11" deep intake hood.

Model W24A2-C & W24L2-C only.

Energy Recovery Ventilator must be field-installed on W**L models. Also see Note .

Ventilation Options Models W17A2, W18A2, W24A2

W17L2, W18L2, W24L2 W30A2, W36A2 W30L2, W36L2

W42A2, W48A2, W60A2 W42L2, W48L2, W60L2

Description Factory Installed

Code No.

Field Installed

Part No.

Factory Installed

Code No.

Field Installed

Part No.

Factory Installed

Code No.

Field Installed

Part No.

Barometric Fresh Air Damper - Standard X BFAD-2 X BFAD-3 X BFAD-5

Blank-Off Plate B BOP-2 B BOP-3 B BOP-5

Motorized Fresh Air Damper M MFAD-2 M MFAD-3 M MFAD-5

Commercial Ventilator - Spring Return w/Exhaust V CRV-2 V CRVS-3 V CRVS-5

Commercial Ventilator - Power Return w/Exhaust --- --- P CRVP-3 P CRVP-5

Economizer - Standard Versions, Enthalpy S ECONWMS-E2B S ECONWMS-E3B S ECONWMS-E5B

Economizer - Equipment Bldg., Enthalpy W ECONWMT-E2B W ECONWMT-E3B W ECONWMT-E5B

Economizer - Equipment Bldg., DB Temp T ECONWMT-T2B T ECONWMT-T3B T ECONWMT-T5B

Energy Recovery Ventilator - 230 Volt R ERVF-A2 R ERVF-A3 R ERVF-A5

Energy Recovery Ventilator - 460 Volt N/A ERVF-C2 R ERVF-C3 R ERVF-C5

Door Kit for ERVF (Required) N/A WMDK2- N/A WMDK3- N/A WMDK5-

Air Conditioning Control Modules All Models Except As Noted W17A2 W17L2

Factory OnlyHPC LPC CCM LAC ALR SK SK ODT DDC Factory Installed Code Field Installed Part

STD STD STD X N/A N/A

STD STD STD E CMA-28 N/A

STD STD STD J Factory Only J

STD STD STD K CMC-15 and CMA-28 N/A

STD STD STD M Factory Only M

STD STD STD N, W18A Only N/A N/A

STD STD STD Field Installed Only CMC-15 CMC-15

STD STD STD Field Installed Only CMA-14 N/A

STD STD STD V Factory Only N/A

STD STD STD Field Installed Only CMA-23 for W17-36

CMA-24 for W42-70 N/A

STD STD STD Field Installed Only SK111 Except W70

SK121 W70 Only

SK111

SERIES | | CONTROL MODULES

(See Chart Below)

REVISION

VOLTS & PHASE

A - 230/208/60/1

B - 230/208/60/3

C - 460/60/3

KW

COLOR OPTIONS

X - Beige (Standard)

1 - White

4 - Buckeye Gray

5 - Desert Brown

8 - Dark Bronze

A - Aluminum

S - Stainless Steel

FILTER OPTIONS

X - 1-inch Throwaway (Standard)

W - 1-inch Washable

P - 2-inch Pleated (MERV 8)

| COIL OPTIONS

X - Standard

1 - Phenolic Coated Evaporator

2 - Phenolic Coated Condenser

3 - Phenolic Coated Evaporator and Condenser

| SUPPLY AIR OUTLET

X - Front (Standard)

T - Top (on W30A and

W36A Models)

NOMINAL

CAPACITY |

17 - 1½ Ton

18 - 1½ Ton

24 - 2 Ton

30 - 2½ Ton

36 - 3 Ton

42 - 3½ Ton

48 - 4 Ton

60 - 5 Ton

W 36 A 2 A 10 X X X X X X

VENTILATION OPTIONS

(See Table Below)

Air Conditioning Wall-Mount Model Nomenclature

For 0KW and circuit breakers (230/208 Volt) or toggle disconnects (460 Volt) applications, insert 0Z in the KW field of the model number.

See Pages 8 & 9 for available Factory Installed KW options and Page 11 for Field Installed Heater Packages.

A = Compressor & Controls - Right Side

L = Compressor & Controls - Left Side

STD = Standard equipment for these specified models.

HPC. High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note .

LPC. Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note .

CCM. Compressor control module has adjustable 30-second to 5-minute delay-on-break timer. On initial power-up, or any time the power is interrupted, the delay-on-make will be 2-minutes plus 10% of the delay-on-break setting. There is no delay-on-make during routine operation of the unit. The module also provides the lockout feature (with 1 retry) for high and/or low pressure controls, and a 2-minute timed bypass for low-pressure control.

LAC. Low ambient control permits cooling operation down to 0°F. LAC is fan-cycling control for outdoor fan motor on all models except W48/W60 Dehum. units, which have modulating control.

ALR. The alarm relay has a set of normally open and normally closed dry contacts to provide the ability to signal a condition of shutdown on either high or low pressure controls.

SK. PTCR start kit can be used with all -A single phase models. Increases starting torque 2-3x. Not used for -B or -C three phase models. Do not use if SK111 or SK121 is used.

SK. Start capacitor & potential relay start kit can be used with all -A single phase models. Increases starting torque 9x. Not used for -B or -C three phase models. Do not use if CMC-15 is used.

ODT. Outdoor thermostat is adjustable from 0 to 50°F. It is suitable for use as a compressor cut-off thermostat.

DDC. Incorporates 4 additional sensors: discharge air temperature, indoor blower airflow, compressor current, and dirty filter. These sensing devices function to input analog data such as temperature, as well as digital data such as airflow, compressor status or filter status. Special economizer required; consult factory.

“V” control module should be ordered in conjunction with direct digital controller (DDC) model TCS24. Refer to DDC specification sheet S3280 for more information.

Option not available for Model W18A.

Use option N for Alarm Relay on Model W18A only.

LAC consists of special heat transfer device suitable for operation down to 0°F. Fan-cycling control is not used.

D = DEHUMIDIFICATION OPTION

Models W30A2, W36A2, W42A2, W48A2 & W60A2 only.

Insert D in place of dash (-).

24 - 2 Ton

SERIES

A = Compressor &A Compressor & Controls - Right Side pp

REVISION

A - 230/208/60/1

KW

X - Beige (Standard)

X - 1-inch Throwaway (Standard)

(See Table Below)

X - Front (Standard)

(See Chart Below)

File details come from the government source that posted it. Updated .