RFQ_16-530-CV_Final.pdf
PDF 346 KB Posted
- Attached to
- BVL Substation Wall Mount A/C Units
- Solicitation number
- RFQ #16-530-CV
- Issued by
- Florida
About this file
This Request for Quotation (RFQ #16-530-CV) is issued by the Kissimmee Utility Authority (KUA), a Florida local government agency, for the procurement of two wall-mounted air conditioning units. The specific equipment required is the Bard model BARW24A2A10 with heater option package EHWA 02A-A10B, or an equivalent that meets exact specifications for direct replacement of existing units. The units must feature single-phase 230/208V, 60Hz AC voltage, 23,600 BTUH cooling capacity, 9.00 Energy Efficiency Ratio (EER), R-410A green refrigerant, standard 1-inch filters, standard beige color, and a 10kW heater package with FLA ratings of 41.6/36.2. Quotations were due by Friday, September 9, 2016, at 10:00 AM local time, to be submitted via fax or email to the KUA Finance & Administration Department. The delivery location is 2850 N. John Young Parkway, Kissimmee, Florida 34741, and all delivery costs must be included in the quoted price with FOB destination terms.
Award selection will be based on quoted pricing including both units and delivery fees, warranty period and optional extended warranty availability, lead time, and if equivalent units are proposed, current user references and fitment specification evaluation. All prices must exclude Florida State Sales and Use Taxes as KUA is tax-exempt. Quoters must provide both unit price and extended total pricing, with each item priced separately. The supplier bears all responsibility for compliance with OSHA, EPA, and Florida regulations, hazardous material provisions, Jessica Lunsford Act requirements for school board property access, I-9 verification compliance, and all indemnification obligations. No modifications to the RFQ terms and conditions are permitted, and any failure to deliver according to specifications or within the quoted timeframe may result in cancellation and procurement from alternative sources at the quoter's expense.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Title: BVL Substation Wall Mount A/C Units Request for Quotation RFQ #16-530-CV
REQUEST FOR QUOTATION
RFQ #16-530-CV
BVL Substation Wall Mount A/C Units
THIS IS NOT AN ORDER
QUOTER INFORMATION
Company______________________________
Name ________________________________
Address __________________________________
Address __________________________________
City/State/Zip ______________________________
Contact Person ____________________________
Phone Number ____________________________
Fax Number _______________________________
FEIN ____________________________________
DUE DATE: FRIDAY, SEPTEMBER 9, 2016 AT
10:00 AM LOCAL TIME
KISSIMMEE UTILITY AUTHORITY
Finance & Administration Department, Accounting/Purchasing Division Contact Person: Coraly Vazquez, CPPB, FCCM Address: 1701 W Carroll Street, Kissimmee, FL 34741 Phone Number: 407-933-9802 Fax Number: 407-932-3286 E-Mail Address: purchasing@kua.com
FOB – Destination. The articles to be furnished shall be deliver with all transportation charges paid by the Supplier to Kissimmee Utility Authority, Kissimmee, Florida.
INSTRUCTIONS: Provide your best selling price in the unit price column for the item(s) being quoted. If not quoting, please indicate “NO QUOTE” and return this form.
BVL SUBSTATION WALL MOUNT A/C UNITS
The pricing for two wall mounted AC units shall be for Bard model # BARW24A2A10, with heater option package EHWA 02A-A10B, or equivalent. These units are direct replacements for existing units and therefore must meet exact dimensions for mounting, intake and exhaust ducts, and power requirements for the current installations.
Care must be taken to ensure that the quoted units meet all of these requirements and specifications.
TECHNICAL REQUIREMENTS
The air conditioning units proposed shall meet the following requirements:
-Reference attached Bard specification sheet for additional details-
Wall-Mount Air Conditioning Unit
Single phase 230/208, 60hz AC voltage
23,600 BTUH cooling capacity
9.00 Energy Efficiency Ratio (EER)
R-410A green refrigerant
Use of 1” standard filter
Standard Beige color
Heater Package EHWA 02A-A10B
FLA 41.6/36.2
10kw
OPTIONAL ACCESSORIES
Extended warranties options.
BASIS OF AWARD
Quoted pricing, to include both units and delivery fees.
Warranty period, to include optional quoted extended warranties available.
Lead time.
If equivalent is quoted, then:
References for current users will be required and evaluated.
Fitment and specifications will be evaluated.
PRICING
BVL Substation Wall Mount AC Units
The following prices are all inclusive, delivered to 2850 N. John Young Parkway, Kissimmee, Florida, 34741.
Qty Description
Unit Price
Extended Price
2 Bard model #BARW24A2A10 AC Unit with Heater Package EHWA 02A-A10B
Total
Included Warranty Labor
Included Warranty Parts
Included Warranty Compressor
Delivery Lead Time
Extended Warranty Each Unit $
Details of proposed optional extended warranty
SIGNATURE___________________________________ ANY PURCHASE ORDER RESULTING FROM THIS
Print Name ____________________________________ QUOTATION WILL BE SUBJECT TO THE TERMS
Title__________________________________________ AND CONDITIONS CONTAINED HEREIN.
Date of Quote__________________________________
Payment Terms ________________________________
Will Deliver By _________________________________
RETURN BY DUE DATE ABOVE VIA FAX (407) 932-3286 or E-MAIL PURCHASING@KUA.COM
Kissimmee Utility Authority Page 3 of 7
GENERAL TERMS AND CONDITIONS
General
The terms and conditions of this order must not be changed by quoter. If order is not acceptable, return to Kissimmee Utility Authority. Failure of an awarded quoter to deliver according to the Purchase Order or to comply with any of the terms and conditions therein may disqualify him/her from receiving future orders.
KUA reserves the right to cancel this order if not filled within the quoted time, if specified.
The conditions of this order are not to be modified by any verbal understanding.
Acceptance of this order includes all terms, prices, delivery instructions, specifications and conditions stated.
No payment will be made for materials ordered without proper purchase order authorization.
Invoices and packages must bear this Purchase Order number.
Please forward all invoices to Accounts Payable.
Quality
KUA reserves the right to reject any or all materials/services if, in its judgment, the item/service reflects unsatisfactory workmanship or manufacturing or shipping damages. If any product/service delivered does not meet applicable specifications or if the product/service will not produce the effect that the quoter represents to KUA, the quoter shall remove the product or stop the service at no expense to KUA. Also, the quoter shall refund to KUA any money which has been paid for same. The quoter will be responsible for attorney fees in the event that he/she defaults and court action is required.
Pricing
Give both unit price and extended total. Prices must be stated in units of quantity specified. All prices for materials to include F.O.B. destination, freight prepaid unless otherwise stated. Each item must be priced separately and no attempt is to be made to tie any item or items in with any other item or items.
No quoter will be allowed to offer more than one price on each item/service even though he/she may feel that he/she has two or more types or styles/services that will meet specifications. Quoter must determine for themselves which to offer.
Prices bid shall be used for payment and these prices shall be deemed to include payment in full for all transportation in delivering all supplies to the point of delivery. All items to be provided under this contract shall be new (not used or reconditioned, and not of such age or so deteriorated as to impair their usefulness or safety), of current production and of the most suitable grade for the purpose intended.
This purchase by Kissimmee Utility Authority is tax exempt. Exemption Certificate Number is 85- 8012665901C-9. The price stated in this bid should exclude Florida State Sales and Use Taxes.
Kissimmee Utility Authority Page 4 of 7
Indemnity
The successful contractor(s) covenants and agrees to indemnify and save harmless KUA and to defend from all cost, expenses, damages, attorney's fees, injury or loss to which KUA and/or its board members, officials, directors, partners, consultants, agents, or employees may be subjected by any person, firm, corporation, or organization by reason of any wrongdoing, misconduct, want, or need of care or skill, negligence or default or breach of contract, guaranty, or warranty, by the successful contractor(s), his subcontractor, sub-supplier, any person or organization directly or indirectly employed by any of them to perform or furnish any of the work or anyone for whose acts any of them may be liable.
Packing & Delivery
Packages must be plainly marked with shipper’s name and Purchase Order Number; charges are not allowed for boxing or crating unless previously agreed upon in writing. All materials must be shipped F.O.B.
Destination. KUA will not pay freight or expense charges, except by previous agreement. The delivery must actually be affected within the time stated on Purchase Order. KUA reserves the right to cancel this order and purchase elsewhere if the quoter fails to meet the delivery date specified on Purchase Order. Deliveries shall be made between 9:00 a.m. and 3:00 p.m. on regular working days unless otherwise stated. Transport deliveries must be unloaded and ready for inspection prior to 3:00 pm. In case of default by the quoter, KUA may procure the articles or services covered by this order from other sources and hold the quoter responsible for any additional cost occasioned thereby.
Hazardous Material Provision
Where applicable, the quoter agrees to furnish KUA with a current Material Safety Data Sheet (MSDS) on or before delivery of each and every hazardous chemical or substance purchased which is classified as toxic under Chapter 422, Florida Statutes. Appropriate labels and MSDS’s shall be provided for all shipments.
Send MSDS’s and other pertinent data to Kissimmee Utility Authority (KUA) at the “Ship to” address.
Regulations
It shall be the responsibility of each quoter to assure compliance with all OSHA, EPA and/or Federal or State of Florida rules, regulations or other requirements, as each may apply.
Appeals & Remedies
Any person adversely affected by the decision or intended decision of award must file a written notice of protest to the Manager of Accounting within seventy-two (72) hours (excluding Saturday, Sundays, and legal holidays) after the posting of the KUA’s decision or intended decision. KUA Purchasing Division personnel should be contacted to obtain comprehensive written protest procedures prior to filing a written notice of protest.
Kissimmee Utility Authority Page 5 of 7
Compliance with Laws and Regulations
By its signature on the Contract Agreement, Contractor hereby certifies that it is aware of any and all applicable federal, state and local laws, regulations, orders of courts and/or governmental agencies, ordinances and permitting requirements and further certifies that it has taken or will take all actions necessary to ensure full compliance with such requirements, including full compliance by any subcontractors and/or materialmen employed by Contractor to perform on this Contract. Contractor agrees to indemnify and hold KUA harmless for any and all claims, losses, penalties, fines and expenses (including, without limitation, any and all reasonable attorney’s and expert’s fees) related to Contractor’s failure, and/or the failure of its subcontractors and materialmen, to abide by the terms of this Section.
Jessica Lunsford Act Compliance
In the event Contractor performs services for KUA on the premises of any Osceola County School Board property, Contractor hereby certifies that it complies with the Jessica Lunsford Act (Florida Statutes, 2005) and that all employees of Contractor, including the employees of subcontractors, materialmen, agents or anyone else hired by Contractor to perform work under this Contract, accessing such property in the performance of KUA-related work have cleared sexual predator/offender and U.S. Department of Justice criminal databases. Contractor agrees to furnish written proof of such compliance and a list of names of all of persons cleared before accessing any public school property on KUA-related work. Contractor also agrees not to permit any of its employees, or the employees of any subcontractors, materialmen, agents or anyone else hired by Contractor to perform KUA-related work, to access Osceola County School Board property if they have not been checked or cleared on the databases described herein. In the event Contractor fails to comply with this section, Contractor shall indemnify and hold KUA harmless for any and all claims, suits, actions, causes of actions, damages, losses, liability, expenses, or costs, in accordance with the terms and provisions of this Contract governing Contractor’s obligation to indemnify KUA.
KUA Sovereign Immunity
No provision in this award, resulting agreement, contract, or purchase order is intended, nor shall be construed, to be a waiver for any purpose by KUA of its sovereign immunity, and any accompanying limitations on KUA’s liability pursuant to same, as set forth in Florida Statutes, Chapter 768, Section 768.28.
No Third Party Beneficiaries
No provisions of this contract shall be construed to benefit in any way any party not a signatory hereto.
Disposal of Hazardous Waste and Used Materials
All hazardous waste and used materials, such as containers, liquids, rags, filters, and solvents, etc. must be disposed of in accordance with all Federal, State and Local regulations. Contractor agrees to indemnify and hold KUA harmless for any and all claims, losses, penalties, fines and expenses (including, without limitation, any and all reasonable attorney’s and expert’s fees) related to Contractor’s failure, and/or the failure of its subcontractors and materialmen, to abide by the terms of this Section.
Kissimmee Utility Authority Page 6 of 7
Certification of OSHA and Indemnification
By its signature on the Contract Agreement, Contractor hereby certifies that it is aware of any and all applicable federal and state requirements, including those imposed by rules and regulations of relevant governmental authorities, of the Occupational Safety and Health Act, and further certifies that it has taken and will take all actions necessary to ensure full compliance with such requirements, including compliance by its employees, subcontractors and materialmen (and any person employed by either) for the duration of this Contract. Contractor agrees to indemnify and hold KUA harmless for any and all claims, losses, penalties, fines and expenses (including, without limitation, any and all reasonable attorney’s and expert’s fees) related to Contractor’s failure, and/or the failure of its subcontractors and materialmen, to abide by the terms of this Section.
I-9 Verification Compliance and Indemnification
By its signature on the Contract Agreement, Contractor hereby certifies that it is aware of any and all applicable federal immigration law requirements, including, without limitation, Contractor’s obligation to properly verify the legal work status of each of its employees by the filing of a complete and accurate Form I-
9. Contractor also acknowledges the importance of ensuring that all personnel accessing any of KUA’s property have been properly verified through the I-9 documentation process. Accordingly, Contractor further certifies that it has taken and will take all actions necessary to ensure full compliance with the Form I-9 requirements, and any other applicable immigration law requirements, and shall also ensure the compliance with such requirements by any subcontractors and materialmen employed by Contractor on this Contract.
Contractor agrees to indemnify and hold KUA harmless for any and all claims, losses, penalties, fines and expenses (including, without limitation, any and all reasonable attorney’s and expert’s fees) related to Contractor’s failure, and/or the failure of its subcontractors and materialmen, to abide by the terms of this Section.
Florida Sunshine Law Requirements
Contractor acknowledges that KUA, as a local government agency, is subject to public records disclosure requirements contained in Florida Statutes, §119.07, et seq. Contractor further understands that to the extent it should act on behalf of KUA in carrying out the terms and conditions of this Contract, it would be subject to the public records retention and other requirements set forth in Florida Statutes, §119.0701.
Contractor acknowledges that it has read and is fully aware of the requirements set forth in Florida Statutes, §119.0701 and agrees to fully comply with the requirements therein to the extent it acts on behalf of KUA.
Governing Law, Jurisdiction and Venue
This Agreement, and all matters arising directly or indirectly from this Agreement, will be governed by and construed in accordance with the law of the State of Florida without giving effect to the conflicts of laws, provisions or principles thereof. For any legal action, suit, claim, or other proceeding arising out of or in any way connected with this Agreement, each of the parties to this Agreement consents to the exclusive jurisdiction and venue of the state and federal courts sitting in, or having principal jurisdiction over, Osceola County, Florida.
****END OF SECTION****
Kissimmee Utility Authority Page 7 of 7
ACCEPTANCE OF TERMS & CONDITIONS
I the undersigned accept in total all the terms and conditions stipulated and referenced in this Request for Quotation document and agree that if a contract is offered or negotiated it will abide by the terms and conditions presented in this Request for Quotation document or as negotiated pursuant thereto. The signature below is an acknowledgment of my full understanding and acceptance of all terms and conditions set forth in the Request for Quotation document or as otherwise agreed to between the parties in writing.
COMPANY NAME
SIGNATURE
NAME, TITLE, TYPED OR PRINTED
MAILING ADDRESS
CITY, STATE, ZIP CODE
FAX NUMBER
E-MAIL ADDRESS
FED ID
Form No. S3461-216 Supersedes S3461-915
Aluminum Finned Copper Coils:
Grooved tubing and enhanced louvered fin for maximum heat transfer and energy efficiency.
Twin Blowers:
Move air quietly. Most models feature multispeed blower motors providing airflow adjustment for high and low static operation. Motor overload protection is standard on all models.
Air Conditioner Compressor:
Scroll Compressors eliminate need for crankcase heater. Standard on all models.
R-410A Refrigerant:
Designed with R-410A (HFC) non-ozone depleting refrigerant in compliance with the Montreal protocol and 2010 EPA requirements.
Phase Rotation Monitor:
Standard on all 3 phase scroll compressors. Protects against reverse rotation if power supply is not properly connected.
Galvanized 20 Gauge Zinc Coated Steel Cabinet:
Cleaned, rinsed, sealed and dried before the polyurethane primer is applied. The cabinet is handsomely finished with a baked on textured enamel, which allows it to withstand 1000 hours of salt spray tests per ASTM B117-03.
Foil Faced Insulation:
Standard on all units.
Full Length Mounting Brackets:
Built into cabinet for improved appearance and easy installation.
NOTE: Bottom mounting bracket included to assist in installation.
Electrical Components:
Are easily accessible for routine inspection and maintenance through a right side, service panel opening. Features a lockable, hinged access cover to the circuit breaker or toggle disconnect switch.
Electric Heat Strips:
Features an automatic limit and thermal cut-off safety control. Heater packages can be factory or field installed.
Filter Service Door:
Separate service door provides easy access for filter change.
One Inch, Disposable Air Filters:
Are standard equipment. Optional one inch washable filters available and filter racks permit the addition of 2" pleated filter. Factory or field installed.
Condenser Fan and Motor Shroud Assembly:
Slides out for easy access.
Barometric Fresh Air Damper:
Standard on all units. Allows up to 25% outside fresh air. Optional ventilation packages available.
Built-in Circuit Breakers:
Standard on all electric heat versions of single (230/208 volt) and three phase
(230/208 volt) equipment. Toggle disconnects are standard on all electric heat versions of three phase (460 volt) equipment.
Slope Top:
Standard feature for water run-off.
Top Rain Flashing:
Standard feature on all models.
Liquid Line Filter Drier:
Standard on all units. Protects system against moisture.
The Bard Wall-Mount Air Conditioner is a self contained energy efficient system, which is designed to offer maximum indoor comfort at a minimal cost without using valuable indoor floor space or outside ground space. This unit is the ideal product for versatile applications such as: new construction, modular offices, school modernization, telecommunication structures, portable structures or correctional facilities. Factory or field installed accessories are available to meet specific job requirements.
THE WALL-MOUNT™ AIR CONDITIONERS - 9.0 EER, (60HZ)
Compressor Control Module:
Standard on all units. Built-in off-delay timer adjustable from 30 seconds to 5 minutes. 2-minute on-delay if power interrupt. 120-second bypass for low pressure control, and both soft and manual lockouts for high and low pressure controls. Alarm output for alarm relay.
High & Low Pressure Switches are Auto-Reset:
Standard on all units. Built-in lockout circuit resets from the room thermostat.
Provides commercial quality protection to the compressor.
Models W17A to W60A Right-Side Control Panel Models W17L to W60L Left-Side Control Panel
1.5 to 5 Ton (16,400 to 55,000 Btuh)
Engineered Features
GREEN REFRIGERANT
R-410A
• Complies with efficiency requirements of ASHRAE/IESNA 90.1-2010.
• Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units).
• Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL
1995/CSA 22.2 No. 236-05, Fourth Edition.
• Commercial Product - Not intended for Residential application.
Capacity is certified in accordance with ANSI/ARI Standard 390-2003.
EER = Energy Efficiency Ratio and is certified in accordance with ANSI/ARI Standard 390-2003.
All ratings based on fresh air intake being 100% closed (no outside air introduction).
Capacity and Efficiency Ratings
Specifications 1-1/2 Ton through 3 Ton
Specifications 3-1/2 Ton through 5 Ton
Models W17A2 / W18A2 W17L2 / W18L2
W24A2 W24L2
W30A2 W30L2
W36A2 W36L2
W42A2 W42L2
W48A2 W48L2
W60A2 W60L2
Cooling Capacity BTUH 16,400 23,600 29,400 35,000 40,000 48,500 55,000
EER 9.00 9.00 9.00 9.00 9.50 9.00 9.00
MODELS W17A2-A
W17L2-A
W18A2-A W18L2-A
W24A2-A W24L2-A
W24A2-B W24L2-B W24A2-C W30A2-A
W30L2-A W30A2-B W30L2-B
W30A2-C W30L2-C
W36A2-A W36L2-A
W36A2-B W36L2-B
W36A2-C W36L2-C
Electrical Rating – 60 Hz 230/208-1 230/208-1 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3
Operating Voltage Range 197-253 197-253 197-253 197-253 414-506 197-253 197-253 414-506 197-253 197-253 414-506
Compressor--Circuit A
Voltage 230/208 230/208 230/208 230/208 460 230/208 230/208 460 230/208 230/208 460
Rated Load Amps 6.5/7.4 6.3/7.2 9.6/11.2 6.3/7.3 4.5 12.2/13.9 7.8/8.9 5.6 15.3/17.2 11.3/12.7 5.8
Branch Circuit
Selection Current
9.0 9.0 12.9 8.4 5.2 14.2 9.0 5.7 18 13.3 6.0
Lock Rotor Amps 48/48 48/48 64/64 58/58 28 77/77 71/71 38 112/112 88/88 44
Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Fan Motor & Condenser
Fan Motor--HP--RPM 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075 1/5 - 1075
Fan Motor--Amps 1.2 1.2 1.2 1.2 0.8 1.5 1.5 0.8 1.5 1.5 0.8
Fan--DIA/CFM 18" - 1700 18" - 1700 18" - 1700 18" - 1700 18" - 1700 20" - 2200 20" - 2200 20" - 2200 20" - 2000 20" - 2000 20" - 2000
Blower Motor & Evap.
Blower Motor--HP-RPM-SPD 1/6-1100-2 1/6-1100-2 1/6-1100-1 1/6-1100-1 1/6-1100-1 1/3-1100-2 1/3-1100-2 1/3-1100-2 1/3-1100-2 1/3-1100-2 1/3-1100-2
Blower Motor--Amps 1.0 1.0 0.8 0.8 .45 2.1 2.1 1.0 2.1 2.1 1.0
CFM Cooling & E.S.P.
w/Filter (Rated-Wet Coil) 600 - .40 550 - .45 800 - .30 800 - .30 800 - .30 1000 - .3 1000 - .3 1000 - .3 1100 - .2 1100 - .2 1100 - .2
Filter Sizes (inches) STD. 16x25x1 16x25x1 16x25x1 16x25x1 16x25x1 16x30x1 16x30x1 16x30x1 16x30x1 16x30x1 16x30x1
Shipping Weight --LBS. 295 295 295 295 295 320 320 320 340 340 340
MODELS W42A2-A
W42L2-A
W42A2-B W42L2-B
W42A2-C W42L2-C
W48A2-A W48L2-A
W48A2-B W48L2-B
W48A2-C W48L2-C
W60A2-A W60L2-A
W60A2-B W60L2-B
W60A2-C W60L2-C
Electrical Rating – 60 Hz 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3
Operating Voltage Range 197-253 197-253 414-506 197-253 197-253 414-506 197-253 197-253 414-506
Compressor--Circuit A
Voltage 230/208 230/208 460 230/208 230/208 460 230/208 230/208 460
Rated Load Amps 15.9/17.8 10.5/11.8 5.5 21/23.5 13.4/15 6.7 21.9/24.9 13/14.8 7.4
Branch Circuit
Selection Current
19.9 13.2 6.1 25 15.9 7.1 26.3 15.7 7.8
Lock Rotor Amps 109/109 83.1/83.1 41 134/134 110/110 52 134/134 110/110 52
Compressor Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll
Fan Motor & Condenser
Fan Motor--HP--RPM-SPD 1/3-825-2 1/3-825-2 1/3-825-1 1/3-825-2 1/3-825-2 1/3-825-1 1/3-825-2 1/3-825-2 1/3-825-1
Fan Motor--Amps 2.5 2.5 1.3 2.5 2.5 1.3 2.5 2.5 1.3
Fan--DIA/CFM 24" - 2700 24" - 2700 24" - 2700 24" - 2700 24" - 2700 24" - 2700 24" - 2500 24" - 2500 24" - 2500
Blower Motor & Evap.
Blower Motor--HP-RPM-SPD 1/3-985-2 1/3-985-2 1/3-985-2 1/3-985-2 1/3-985-2 1/3-985-2 1/2-1070-2 1/2-1070-2 1/2-1070-2
Blower Motor--Amps 2.3 2.3 1.2 2.3 2.3 1.2 3.5 3.5 1.9
CFM Cooling & E.S.P.
w/Filter (Rated-Wet Coil) 1400 - .45 1400 - .45 1400 - .45 1550 - .3 1550 - .3 1550 - .3 1700 - .4 1700 - .4 1700 - .4
Filter Sizes (inches) STD. 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1 20x30x1
Shipping Weight --LBS. 460 460 460 465 465 465 485 485 485
W24A2
W24A2-A
Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements. All units are equipped with a barometric fresh air damper as the standard ventilation package. All ventilation packages can be built-in at the factory or field-installed at a later date.
Ventilation System Packages
Barometric Fresh Air Damper
Motorized Fresh Air Damper
Commercial Room Ventilator
Energy Recovery Ventilator
BAROMETRIC FRESH AIR DAMPER - BFAD STANDARD
The barometric fresh air damper is a standard feature on all models. It is installed on the inside of the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The damper opens during blower operation and closes when the blower is off. Adjustable blade stops allow different amounts of outside air to be introduced into the building and can be easily locked closed if required.
BLANK OFF PLATE - BOP OPTIONAL
A blank off plate is installed on the inside of the service door. It covers the air inlet openings, which restricts any outside air from entering the unit. The blank off plate should be utilized in applications where outside air is not required to be mixed with the conditioned air.
MOTORIZED FRESH AIR DAMPER - MFAD OPTIONAL
The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air, up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed with the conditioned air. The two position damper can be fully open or closed. The damper blade is powered open by a 24VAC motor with spring return on power loss. The damper can be controlled by indoor blower operation or can be field connected to be managed based on building occupancy.
COMMERCIAL ROOM VENTILATOR - CRV OPTIONAL
The built-in commercial room ventilator is internally mounted behind the service door and allows outside ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings.
It includes a built-in exhaust air damper.
The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by providing fresh air intake and exhaust capability through the CRV. The damper can be easily adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled based on room occupancy. Two versions available (except on 1.5 and 2-Ton models). The CRV and CRVS are power open - spring return on power loss, and CRVP is power open and power close. Complies with ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality”.
ECONOMIZER – ECONWM-Series OPTIONAL The built-in economizer system is internally mounted behind the service door and allows outdoor air to be introduced through the air inlet openings. The amount of outdoor air varies in response to the system controls and settings defined by the end user. It includes a built-in exhaust air damper. The economizer is designed to provide
“free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running the compressor. This in turn provides lower operating costs, while extending the life of the compressor.
• ECONWMT Equipment Building versions have extended 11" air intake hood to deliver up to 100% of cooling rated airflow.
• ECONWMS Standard versions have 3" air intake hood to deliver up to 75% of cooling rated airflow.
Standard Features:
• Fully modulating
• Honeywell Direct Drive Hi-Torque Actuator
• No linkage required
• Simple single blade design
• Positive shut-off with non-stick gaskets
• Electronic DB and/or Enthalpy sensors depending upon version
• Honeywell JADE electronic economizer module with precision settings and diagnostics
• DB or Enthalpy economizer versions available
WALL-MOUNT ENERGY RECOVERY VENTILATOR - ERVF OPTIONAL
The wall-mount energy recovery ventilator (ERV) is a highly innovative approach to meeting indoor air quality ventilation requirements as established by ANSI/ASHRAE Standard 62.1. The ERV allows from 200 to 450 CFM
(depending upon model) of fresh air and exhaust through the unit while maintaining superior indoor comfort and humidity levels. In most cases this can be accomplished without increasing equipment sizing or operating costs.
Heat transfer efficiency is up to 67% during summer and 75% during winter conditions.
The ERV consists of a unique “rotary energy recovery cassette” that provides effective sensible and latent heat transfer capabilities during summer and winter conditions. Various control schemes are addressed including limiting ventilation during building occupancy only.
The ERV is designed to be internally mounted behind the service door in the W**A or W**L model wall-mount units. It can be built-in at the factory (W**A only) or field installed as an option. ERVF-*3 and ERVF-*5 can be independently adjusted for intake and exhaust rates.
NOTE: The above vent systems are intake only without built-in exhaust capability. Building will likely require separate field installed barometric relief or mechanical exhaust elsewhere within the conditioned space.
Balancing dampers in the return air grille may be required to achieve specified amount of outdoor air intake.
Economizer
W
W H
IG
H
S P
E E
D T
O
TA
L A
N D
V E
N T
IL
A
T
IO
N A
IR
F
L O
W W
W L
O W
S P
E E
D T
O
TA
L A
N D
V E
N T
IL
A
T
IO
N A
IR
F
L O
W
W /W
W T
O
TA
L A
N D
V E
N T
IL
A
T
IO
N A
IR
F
L O
W
C o m m er ci a l
R o o m
V en ti la to r
P er fo rm a n ce D a ta
C
R V
-2
C o m m er ci a l
R o o m
V en ti la to r
P er fo rm a n ce D a ta
C
R V
S -3 a n d C
R V
P -3
A B
C D
E F
Airflow (cfm)
V e n t P o s it io n
T o ta l A ir
E S
P
T o ta l A ir
E
S P
T o ta l A ir
E S
P
V e n t
A ir
E
S P
V e n t
A ir
E
S P
V e n t
A ir
E S
P
A B
C D
E F
Airflow (cfm)
V e n t P o s it io n
T o ta l A ir
E
S P
T o ta l A ir
E
S P
T o ta l A ir
E S
P
V e n t
A ir
E
S P
V e n t
A ir
E
S P
V e n t
A ir
E S
P
A B
C D
E F
Airflow (cfm)
V e n t P o s it io n
T o ta l A ir
E
S P
T o ta l A ir
E
S P
T o ta l A ir
E S
P
V e n t
A ir
E
S P
V e n t
A ir
E
S P
V e n t
A ir
E S
P
W
Caution
* Top outlet supply option is available only factory installed and only on the selected models.
IMPORTANT:
Electrical Code and all local codes.
MODEL
Rated Volts & Phase
No.
Field Power
Circuits
Single Circuit Dual Circuit
Minimum Circuit
Ampacity
Maximum External Fuse or
Ckt. Brkr.
Field Power
Wire Size
Ground Wire
Minimum Circuit
Ampacity
Maximum External Fuse or
Ckt. Breaker Field Power Wire Size
Ground Wire Size
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
W17, 18A2-A00,A0Z
A05
A08
A10
230/208-1
W24A2-A00, A0Z
A04
A05
A08
A10
230/208-1
W24A2-B00, B0Z
B06 230/208-3
W24A2-C00, C0Z
C06 460-3
W30A2-A00*, A0Z*
A05*
A08
A10*
A15
230/208-1
1 or 2
8 58 26 60 30 6 10 10 10
W30A2-B00*, B0Z*
B06
B09*
B15
230/208-3
W30A2-C00*, C0Z*
C06
C09*
C15
460-3
W36A2-A00*, A0Z*
A05*
A08
A10*
A15
230/208-1
1 or 2
8 58 26 60 30 6 10 10 10
W36A2-B00*, B0Z*
B06*
B09*
B15
230/208-3
W36A2-C00*, C0Z*
C06*
C09*
C15
460-3
W42A2-A00, A0Z
A05
A10
A15
A20
230/208-1
1 or 2
1 or 2
W42A2-B00, B0Z
B09
B15
B18
230/208-3
W42A2-C00, C0Z
C09
C15
460-3
W48A2-A00, A0Z
A05
A10
A15
A20
230/208-1
1 or 2
1 or 2
W48A2-B00, B0Z
B09
B15
B18
230/208-3
W48A2-C00, C0Z
C09
C15
460-3
W60A2-A00, A0Z
A05
A10
A15
A20
230/208-1
1 or 2
1 or 2
W60A2-B00, B0Z
B09
B15
B18
230/208-3
N/A
N/A
N/A
N/A 35 28 40 30 8 10 10 10
W60A2-C00, C0Z
C09
C15
460-3
Electrical Specifications — W**A Series
W24A2-A00, A10
230/208-1
1 56 60 6 10
Above data is with 1" standard throwaway filter and 1" washable filter.
For optional 2" pleated filter - reduce ESP by .15 in.
See installation instructions for maximum ESP information on various KW application.
Speed W17/W18 W24 W30 W36 W42/W48 W60
High Low Single High Low High Low High Low High Low
ESP
(Inch H20)
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
0.0 1045 1025 760 745 990 970 1370 1285 910 885 1415 1275 955 925 1850 1800 1605 1555 2080 2015 1505 1460
0.1 1010 970 730 715 945 925 1305 1225 885 860 1350 1215 945 915 1775 1725 1545 1500 2020 1960 1450 1405
0.2 940 905 700 685 890 870 1225 1135 850 815 1265 1125 925 900 1685 1640 1460 1415 1925 1865 1395 1355
0.3 860 830 670 655 820 800 1115 1020 790 755 1190 1060 875 850 1590 1550 1390 1345 1870 1815 1340 1300
0.4 780 750 610 595 735 720 1005 910 695 660 1085 975 780 755 1495 1460 1310 1270 1755 1705 1225 1185
0.5 665 640 485 455 605 590 865 775 590 560 970 865 640 615 1400 1365 1225 1185 1660 1610 1125 1085
Nominal
KW
At 240V (1) At 208V (1) At 480V (2) At 460V (2)
Kw 1-Ph Amps
3-Ph Amps Btuh Kw 1-Ph
Amps 3-Ph Amps Btuh Kw 3-Ph
Amps Btuh Kw 3-Ph Amps Btuh
5.0 5.0 20.8 17,065 3.75 18.0 12,799
6.0 6.0 14.4 20,478 4.50 12.5 15,359 6.0 7.2 20,478 5.52 6.9 18,840
8.0 8.0 33.3 27,304 6.00 28.8 20,478
9.0 9.0 21.7 30,717 6.75 18.7 23,038 9.0 10.8 30,717 8.28 10.4 28,260
10.0 10.0 41.7 34,130 7.50 36.1 25,598
15.0 15.0 62.5 36.1 51,195 11.25 54.1 31.2 38,396 15.0 18.0 51,195 13.80 17.3 47,099
18.0 18.0 43.3 61,434 13.50 37.5 46,076 18.0 21.7 61,434 16.56 20.8 56,519
20.0 20.0 83.3 68,260 15.00 72.1 51,195
(1) These electric heaters are available in 230/208V units only.
(2) These electric heaters are available in 480V units only.
Indoor Blower Performance (60 Hz) - CFM at Rated Volts
Electric Heat Table - Refer to Electrical Specifications for Availability by Unit Model
Factory Connected Speed.
W24
NOTE: Field installed Heater Packages are not approved for use with top supply opening models.
Field installed Heater Package not available for W70L models.
These heater packages approved for use in dehumidification versions with hot gas reheat.
Heater Packages - Field Installed "A" Series Right-Hand Units
• Designed for adding Electric Heat to 0 KW Units • ETL US & Canada Listed
• Circuit Breaker Standard on 230/208V Models • Toggle Disconnect Standard on 460V Models
Air Conditioner
Models
-A00 Models 230/208-1
-B00 Models 230/208-3
-C00 Models 460-3
Heater Model # KW Heater Model # KW Heater Model # KW
W17A2 W18A2
EHWA02-A05B
EHW02A-A08B
EHWA02A-A10B
N/A N/A
W24A2
EHWA24A-A04B
EHWA02-A05B
EHW02A-A08B
EHWA02A-A10B
EHWA24-B06B 6 EHWH24B-C06 6
W30A2
EHWA03-A05B
EHWA03-A08B
EHWA03-A10B
EHWA03-A15B
EHWA03-B06B
EHWA03-B09B
EHWA37-B15B
EHWC03A-C06
EHWC03A-C09
EHWA03A-C12
EHWA03A-C15
W36A2
EHWA03-A05B
EHWA03-A08B
EHWA03-A10B
EHWA03-A15B
EHW36A-B06B
EHWA03-B09B
EHWA37-B15B
EHWC03A-C06
EHWC03A-C09
EHWA03A-C12
EHWA03A-C15
W42A2 W48A2
EHWA05-A05B
EHWA05-A10B
EHWA05-A15B
EHWA05-A20B
EHWA05-B09B
EHWA05-B15B
EHWA05-B18B
EHWA05A-C09
EHWA05A-C15
W60A2
EHWA60-A05B
EHWA05-A10B
EHWA05-A15B
EHWA05-A20B
EHW60A-B09B
EHWA05-B15B
EHW05A-B18B
EHWA05A-C09
EHWA05A-C15
Air Conditioner
Models
-A00 Models 230/208-1
-B00 Models 230/208-3
-C00 Models 460-3
Heater Model # KW Heater Model # KW Heater Model # KW
W17L2 W18L2
EHWA02A-A05LB
EHW02A-A08LB
EHWA02-A10LB
N/A N/A
W24L2
EHWA02A-A05LB
EHW02A-A08LB
EHWA02-A10LB
EHWA24-B06LB 6 N/A
W30L2
EHWA03-A05LB
EHWA03-A08LB
EHWA03-A10LB
EHWA03-A15LB
EHWA03-B09LB
EHWA37-B15LB
EHWC03-C09L
EHWA03-C15L
W36L2
EHWA03-A05LB
EHWA03-A10LB
EHWA03-A15LB
EHWA03-B09LB
EHWA37-B15LB
EHWC03-C09L
EHWA03-C15L
W42L2 W48L2
EHWA05-A05LB
EHWA05-A10LB
EHWA05-A15LB
EHWA05-B09LB
EHWA05-B15LB
EHWA05A-C09L
EHWA05A-C15L
W60L2
EHWA05-A05LB
EHWA05-A10LB
EHWA05-A15LB
EHWA60-B09LB
EHWA05-B15LB
EHWA05A-C09L
EHWA05A-C15L
Heater Packages - Field Installed "L" Series Left-Hand Units
EHWA02A-A10B 10
3"
7.88 1.00
11"
31.88
Filter Access Panel
Air Outlet
Front View
Condenser
Standard flush vent door for non-ERV/ Econ.
models
Ventilation Air
W
5.88
F
G
Heat models.
Electric
Hood for
ECONWMT
MIS-2487 H
(Lockable)
Built In Rain Hood
4° Pitch
Entrance
High Voltage Entrance
Access Panel
Low Voltage
Disconnect
Heater
Panel Access
Air Inlet
Drain
Cond.
Electrical
Side View
Electrical
C. Breaker/
Hood for ERV and ECONWMS models only
1.250
H
A
I
D
J
2.13
C
K
Electrical
Side Wall
Entrances
Mounting
Optional
Supply Air Opening
(Built In)
Shipping Location
Brackets
Return Air Opening
Top Rain Flashing
Bottom Installation BracketBack View
T
B
M
O E
R
S
S
S
S
S P
.44
N Q
L
Dimensions of W17-60A Basic Unit for Architectural & Installation Requirements (Nominal)
MODEL WIDTH
(W)
DEPTH
(D)
HEIGHT
(H)
SUPPLY RETURN
A B C B E F G I J K L M N O P Q R S T
W17A2 W18A2 W24A2
33.300 17.125 70.563 7.88 19.88 11.88 19.88 35.00 10.88 25.75 20.56 26.75 28.06 29.25 27.00 2.63 34.13 22.06 10.55 4.19 12.00 5.00
W30A2 W36A2 38.200 17.125 70.563 7.88 27.88 13.88 27.88 40.00 10.88 25.75 17.93 26.75 28.75 29.25 27.00 2.75 39.13 22.75 9.14 4.19 12.00 5.00
W42A2 W48A2 W60A2
42.075 22.432 84.875 9.88 29.88 15.88 29.88 43.88 13.56 31.66 30.00 32.68 26.94 34.69 32.43 3.37 43.00 23.88 10.00 1.44 16.00 1.88
Clearances Required for Service Access and Adequate Condenser Inlet Airflow
MODELS LEFT SIDE RIGHT SIDE
W17A, W18A, W24A, W30A, W36A 15" 20"
W42A, W48A, W60A 20" 20"
NOTE: For side-by-side installation of two (2) WA models, there must be 20" between units. This can be reduced to 15" by using a WL model (left side compressor and controls) for the left unit and WA (right side compressor and controls) for right unit.
Minimum Clearances Required to Combustible Materials
MODELS
SUPPLY AIR DUCT
FIRST THREE FEET CABINET
W17A, W18A, W24A 0" 0"
W30A, W36A 1/4" 0"
W42A, W48A, W60A 1/4" 0"
Refer to the Installation Manual for more detailed information.
Not used when ECONWMT Economizers installed. Filter access is through the ECONWMT hood.
Optional top outlet (factory installed only) in place of standard front supply air opening for W30A and W36A models only.
W24A, 15" 20"
W24A 0" 0"
33.300 17.125 70.563 7.88 19.88 11.88 19.88 35.00 10.88 25.75 20.56 26.75 28.06 29.25 27.00 2.63 34.13 22.06 10.55 4.19 12.00 5.00
Model Return Air (DB/WB) Cooling Capacity 75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F 120°F
W17A2 W17L2
75/62 Total Cooling
Sensible Cooling
17200
13900
16500
13600
15700
13400
15000
13000
14300
12700
13700
12400
13100
12000
12500
11700
11900
11400
11300
11000
80/67 Total Cooling
Sensible Cooling
18300
13400
17900
13300
17400
13200
16900
13000
16400
12800
15900
12600
15400
12300
14900
12100
14300
11800
13700
11500
85/72 Total Cooling
Sensible Cooling
21800
13800
21000
13500
20000
13300
19100
13000
18300
12600
17400
12200
16600
11800
15900
11400
15100
10900
14300
10400
W18A2 W18L2
75/62 Total Cooling
Sensible Cooling
17700
14200
16800
13800
16000
13400
15200
13000
14300
12600
13600
12300
12900
11900
12200
11600
11600
11300
10900
10900
80/67 Total Cooling
Sensible Cooling
18900
13700
18300
13500
17700
13200
17100
13000
16400
12700
15800
12500
15200
12200
14500
11900
13900
11700
13200
11400
85/72 Total Cooling
Sensible Cooling
22600
14100
21400
13700
20400
13300
19300
13000
18300
12500
17300
12100
16400
11700
15500
11200
14600
10800
13800
10300
W24A2 W24L2
75/62 Total Cooling
Sensible Cooling
25000
19800
23800
19300
22700
18800
21600
18300
20600
17900
19600
17300
18700
16900
17600
16400
16700
15900
15800
15400
80/67 Total Cooling
Sensible Cooling
26600
19200
25900
18900
25200
18600
24400
18300
23600
18000
22800
17600
22000
17300
21000
16900
20100
16500
19100
16100
85/72 Total Cooling
Sensible Cooling
31700
19700
30300
19200
29000
18700
27600
18200
26200
17700
25000
17100
23800
16500
22400
15900
21200
15200
19900
14600
W30A2 W30L2
75/62 Total Cooling
Sensible Cooling
30200
23500
29000
23400
27900
23200
26800
22700
25600
22300
24500
21700
23300
21100
22200
20300
21000
19500
19700
18600
80/67 Total Cooling
Sensible Cooling
32200
22800
31600
22900
31000
22900
30300
22700
29400
22500
28500
22100
27500
21600
26400
21000
25200
20300
23800
19400
85/72 Total Cooling
Sensible Cooling
38400
23400
37000
23300
35600
23000
34200
22600
32700
22100
31200
21400
29700
20600
28100
19700
26500
18700
24800
17600
W36A2 W36L2
75/62 Total Cooling
Sensible Cooling
37100
27700
35400
27100
33700
26400
32100
25700
30500
25100
29000
24300
27700
23600
26300
22800
25000
21900
23700
21100
80/67 Total Cooling
Sensible Cooling
39600
26800
38500
26500
37400
26100
36200
25700
35000
25300
33800
24700
32600
24200
31300
23500
30100
22800
28700
22100
85/72 Total Cooling
Sensible Cooling
47200
27500
45000
26900
43000
26200
40900
25600
38900
24800
37000
23900
35200
23100
33300
22100
31700
21000
29800
20000
W42A2 W42L2
75/62 Total Cooling
Sensible Cooling
42500
32800
40300
32600
38400
32100
36600
31500
34800
30800
33400
30100
32000
29200
30700
28200
29600
27000
28600
25800
80/67 Total Cooling
Sensible Cooling
45300
31800
43900
31900
42600
31800
41300
31500
40000
31100
38900
30600
37700
29900
36600
29100
35600
28100
34600
27000
85/72 Total Cooling
Sensible Cooling
54000
32600
51300
32400
48900
32000
46600
31300
44500
30500
42600
29600
40700
28500
39000
27300
37400
25900
36000
24400
W48A2 W48L2
75/62 Total Cooling
Sensible Cooling
53400
39900
50200
38800
47300
37700
44700
36600
42200
35500
40200
34500
38200
33400
36600
32400
35100
31400
33800
30500
80/67 Total Cooling
Sensible Cooling
57000
38700
54700
38000
52500
37300
50500
36600
48500
35800
46800
35100
45100
34300
43600
33500
42200
32700
40900
31900
85/72 Total Cooling
Sensible Cooling
67900
39600
64000
38600
60300
37500
57000
36400
53900
35100
51200
34000
48600
32700
46400
31400
44400
30100
42500
28800
W60A2 W60L2
75/62 Total Cooling
Sensible Cooling
57000
43700
54700
42800
52400
41700
50200
40700
47900
39600
45800
38600
43500
37500
41300
36500
39100
35400
36800
34200
80/67 Total Cooling
Sensible Cooling
60800
42400
59600
41900
58200
41300
56700
40700
55000
40000
53300
39300
51300
38500
49200
37700
47000
36800
44600
35800
85/72 Total Cooling
Sensible Cooling
72400
43400
69700
42500
66800
41500
64000
40400
61100
39200
58300
38000
55300
36700
52400
35400
49400
33900
46400
32400
Capacity Multiplier Factors % of Rated Airflow -10 Rated +10
Total BTUH Sensible BTUH
0.975
0.950
1.0
1.0
1.02
1.05
Below 65°F (18.3C), unit requires a factory or field installed low ambient control.
Return air temperature.
Cooling Application Data - Outdoor Temperature
Intake and exhaust can be independently adjusted.
Insert color to match unit ("X" = Beige; "4" = Buckeye Gray; etc.)
WMDK Door Kit must be ordered in addition to ERVF Assembly & color matched to unit ("X" = Beige; "4" = Buckeye Gray; etc.)
Partial Full Flow (75% of Rated Cooling CFM). All ECONWMS versions have 3" deep intake hood.
Full Flow (100% of Rated Cooling CFM). All ECONWMT versions have 11" deep intake hood.
Model W24A2-C & W24L2-C only.
Energy Recovery Ventilator must be field-installed on W**L models. Also see Note .
Ventilation Options Models W17A2, W18A2, W24A2
W17L2, W18L2, W24L2 W30A2, W36A2 W30L2, W36L2
W42A2, W48A2, W60A2 W42L2, W48L2, W60L2
Description Factory Installed
Code No.
Field Installed
Part No.
Factory Installed
Code No.
Field Installed
Part No.
Factory Installed
Code No.
Field Installed
Part No.
Barometric Fresh Air Damper - Standard X BFAD-2 X BFAD-3 X BFAD-5
Blank-Off Plate B BOP-2 B BOP-3 B BOP-5
Motorized Fresh Air Damper M MFAD-2 M MFAD-3 M MFAD-5
Commercial Ventilator - Spring Return w/Exhaust V CRV-2 V CRVS-3 V CRVS-5
Commercial Ventilator - Power Return w/Exhaust --- --- P CRVP-3 P CRVP-5
Economizer - Standard Versions, Enthalpy S ECONWMS-E2B S ECONWMS-E3B S ECONWMS-E5B
Economizer - Equipment Bldg., Enthalpy W ECONWMT-E2B W ECONWMT-E3B W ECONWMT-E5B
Economizer - Equipment Bldg., DB Temp T ECONWMT-T2B T ECONWMT-T3B T ECONWMT-T5B
Energy Recovery Ventilator - 230 Volt R ERVF-A2 R ERVF-A3 R ERVF-A5
Energy Recovery Ventilator - 460 Volt N/A ERVF-C2 R ERVF-C3 R ERVF-C5
Door Kit for ERVF (Required) N/A WMDK2- N/A WMDK3- N/A WMDK5-
Air Conditioning Control Modules All Models Except As Noted W17A2 W17L2
Factory OnlyHPC LPC CCM LAC ALR SK SK ODT DDC Factory Installed Code Field Installed Part
STD STD STD X N/A N/A
STD STD STD E CMA-28 N/A
STD STD STD J Factory Only J
STD STD STD K CMC-15 and CMA-28 N/A
STD STD STD M Factory Only M
STD STD STD N, W18A Only N/A N/A
STD STD STD Field Installed Only CMC-15 CMC-15
STD STD STD Field Installed Only CMA-14 N/A
STD STD STD V Factory Only N/A
STD STD STD Field Installed Only CMA-23 for W17-36
CMA-24 for W42-70 N/A
STD STD STD Field Installed Only SK111 Except W70
SK121 W70 Only
SK111
SERIES | | CONTROL MODULES
(See Chart Below)
REVISION
VOLTS & PHASE
A - 230/208/60/1
B - 230/208/60/3
C - 460/60/3
KW
COLOR OPTIONS
X - Beige (Standard)
1 - White
4 - Buckeye Gray
5 - Desert Brown
8 - Dark Bronze
A - Aluminum
S - Stainless Steel
FILTER OPTIONS
X - 1-inch Throwaway (Standard)
W - 1-inch Washable
P - 2-inch Pleated (MERV 8)
| COIL OPTIONS
X - Standard
1 - Phenolic Coated Evaporator
2 - Phenolic Coated Condenser
3 - Phenolic Coated Evaporator and Condenser
| SUPPLY AIR OUTLET
X - Front (Standard)
T - Top (on W30A and
W36A Models)
NOMINAL
CAPACITY |
17 - 1½ Ton
18 - 1½ Ton
24 - 2 Ton
30 - 2½ Ton
36 - 3 Ton
42 - 3½ Ton
48 - 4 Ton
60 - 5 Ton
W 36 A 2 A 10 X X X X X X
VENTILATION OPTIONS
(See Table Below)
Air Conditioning Wall-Mount Model Nomenclature
For 0KW and circuit breakers (230/208 Volt) or toggle disconnects (460 Volt) applications, insert 0Z in the KW field of the model number.
See Pages 8 & 9 for available Factory Installed KW options and Page 11 for Field Installed Heater Packages.
A = Compressor & Controls - Right Side
L = Compressor & Controls - Left Side
STD = Standard equipment for these specified models.
HPC. High pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note .
LPC. Low pressure control is auto reset. Always used with compressor control module (CCM) which is included. See note .
CCM. Compressor control module has adjustable 30-second to 5-minute delay-on-break timer. On initial power-up, or any time the power is interrupted, the delay-on-make will be 2-minutes plus 10% of the delay-on-break setting. There is no delay-on-make during routine operation of the unit. The module also provides the lockout feature (with 1 retry) for high and/or low pressure controls, and a 2-minute timed bypass for low-pressure control.
LAC. Low ambient control permits cooling operation down to 0°F. LAC is fan-cycling control for outdoor fan motor on all models except W48/W60 Dehum. units, which have modulating control.
ALR. The alarm relay has a set of normally open and normally closed dry contacts to provide the ability to signal a condition of shutdown on either high or low pressure controls.
SK. PTCR start kit can be used with all -A single phase models. Increases starting torque 2-3x. Not used for -B or -C three phase models. Do not use if SK111 or SK121 is used.
SK. Start capacitor & potential relay start kit can be used with all -A single phase models. Increases starting torque 9x. Not used for -B or -C three phase models. Do not use if CMC-15 is used.
ODT. Outdoor thermostat is adjustable from 0 to 50°F. It is suitable for use as a compressor cut-off thermostat.
DDC. Incorporates 4 additional sensors: discharge air temperature, indoor blower airflow, compressor current, and dirty filter. These sensing devices function to input analog data such as temperature, as well as digital data such as airflow, compressor status or filter status. Special economizer required; consult factory.
“V” control module should be ordered in conjunction with direct digital controller (DDC) model TCS24. Refer to DDC specification sheet S3280 for more information.
Option not available for Model W18A.
Use option N for Alarm Relay on Model W18A only.
LAC consists of special heat transfer device suitable for operation down to 0°F. Fan-cycling control is not used.
D = DEHUMIDIFICATION OPTION
Models W30A2, W36A2, W42A2, W48A2 & W60A2 only.
Insert D in place of dash (-).
24 - 2 Ton
SERIES
A = Compressor &A Compressor & Controls - Right Side pp
REVISION
A - 230/208/60/1
KW
X - Beige (Standard)
X - 1-inch Throwaway (Standard)
(See Table Below)
X - Front (Standard)
(See Chart Below)