Ames Laboratory RFP SC-23-586 ADDENDUM NUMBER 3
ADDENDUM NUMBER 3
ADDENDUM DATE: 6/1/2023
PROJECT: RFP SC-23-586 Magnet Test Bed Remodel
PROPOSAL DUE DATE: 6/9/2023 at 4:00 p.m. CST
ADDENDUM ISSUED DATE: 6/1/2023
The information contained in this Addendum modifies, supplements, or replaces information contained in the Bidding Documents dated 5/5/2023 and is hereby made a part of the Contract Documents.
Acknowledge receipt of this Addendum with your proposal submission
Addendum consists of 6 pages and 10 pages of attachments.
ADDENDUM INDEX
GENERAL ITEMS: None.
APPLICABLE TO THE PROJECT SPECIFICATIONS: Items 1 thru 11.
APPLICABLE TO THE DRAWINGS: Items 12 thru 19.
ADDITIONAL ACCEPTABLE PRODUCTS AND SYSTEMS None.
ATTACHMENTS:
Specification Section 00 74 13 – Project Requirements 2 pages.
Drawing Sheets:
G-001 – Architectural Legend and Details.
A-101 – Level 1 – Architecture PL101 – Level 1 – Plumbing Plan MD101 – Level 1 – Mechanical Demolition Plan MH101 – Level 1 and Roof – HVAC Plans E-101 – Level 1 – Power and Fire Alarm Floor Plan E-501 – One Line Diagram T-101 – Level 1 – Telecom and Security Floor Plan
APPLICABLE TO THE PROJECT SPECIFICATIONS
1. 00 74 13 – PROJECT REQUIREMENTS
1.1 Add Section.
2. 01 10 00 – SUMMARY
2.1. Section 1.3.B – Change to: “Refer to Section 00 74 13 – PROJECT REQUIREMENTS.”
3. 09 06 00 – SCHEDULE OF FINISHES
3.1. Section 3.2.B – Add: “RESIN = RESINOUS FLOORING (09 67 23).”
3.2. Section 3.3.A – Change to: “RB-1 = RESILIENT BASE – RESILIENT BASE (09 65 00).”
4. 09 60 01 – FLOOR PATCHING AND LEVELING
4.1. Add Section 1.2:
“1.2 WORK BY OWNER
a All work included in this section will be performed by Owner. Refer to Section 00 74 13
– Project Requirements.”
4.2. Revise subsequent section numbering accordingly.
5. 09 67 23 – RESINOUS FLOORING
5.1. Add Section 1.2:
A. All work included in this section will be performed by Owner. Refer to Section 00 74 13 – Project Requirements.”
5.2. Revise subsequent section numbering accordingly.
6. 23 07 19 – HVAC PIPING INSULATION
6.1. Add Article 1.2:
A. All work included in this section will be performed by owner. Refer to Section 00 74 13 –
6.2. Revise subsequent section numbering accordingly.
7. 23 09 23 – INSTRUMENTATION AND CONTROLS FOR HVAC
7.1. Add Article 1.2:
7.2. Revise subsequent section numbering accordingly.
8. 23 21 13 – HYDRONIC PIPING
8.1. Add Article 1.2:
B. All work included in this section will be performed by owner. Refer to Section 00 74 13 –
8.2. Revise subsequent section numbering accordingly.
9. 23 21 16 – HYDRONIC PIPING SPECIALTIES
9.1. Add Article 1.2:
9.2. Revise subsequent section numbering accordingly.
10. 23 36 00 – AIR TERMINAL UNITS
10.1. Add Article 1.2:
10.2. Revise subsequent section numbering accordingly.
11. 23 09 23 – INSTRUMENTATION AND CONTROLS FOR HVAC
11.1. Add Section 1.2:
All work included in this section will be performed by Owner. Refer to Section 00 74 13 – Project Requirements.”
11.2. Revise subsequent section numbering accordingly.
APPLICABLE TO THE DRAWINGS
12. DRAWING SHEET G-001 – ARCHITECTURAL LEGEND AND DETAILS
12.1. Revise Sheet title:
“ARCHITECTURAL LEGEND AND DETAILS”
12.2. Detail A6:
12.2.1. Add Detail: : FLOOR – RESINOUS TO VCT
12.2.2. SHEET NOTE LEGEND, ADD
12.3. Detail B6:
12.3.1. Add Detail: FLOOR – RESINOUS TO CONC
12.3.2. Add KEYNOTE LEGEND.
13. DRAWING SHEET A-101 – LEVEL 1 – ARCHITECTURE
13.1. DOOR SCHEDULE, Revise:
13.1.1. DR 160A.1 DOOR MATL: “IP”
13.2. ROOM FINISH SCHEDULE, Revise:
13.2.1. RM 160A FLOOR FINISH: “RESIN”.
13.2.2. NOTE 3:
“3. PAINT ALL UNPAINTED DUCTWORK, PIPING, CONDUIT, ETC. TO MATCH THE WALL,
CEILING, OR RAILING THEY RUN PARALLEL TO. DO NOT PAINT BRICK.”
13.2.3. NOTE 11:
“11. FILL THEN PREPARE CONCRETE FLOOR FOR FINISH FLOORING.”
13.3. DOOR, PANEL TYPES, Revise:
13.3.1. Type C:
13.3.1.1. “08 11 13.B2”
13.3.1.2. “IP = INSULATED METAL PANEL”
13.4. SHEET NOTE LEGEND, Revise NOTE N2:
“N2 ALL CASEWORK (12 35 53.B-G): OFOI – GC COORDINATE”
13.5. DETAIL A4: LEVEL 1 – ARCHITECTURE, Add DETAIL CALLOUTS:
13.5.1. “A6 / G-101”
13.5.2. “B6 / G-101”
14. DRAWING SHEET PL101 – LEVEL 1 – PLUMBING PLAN
14.1. Change Keyed Note 2 symbol to Keyed Note 3 symbol at Arc Cast Machine (vicinity
Column Line La-14).
14.2. Add Keyed Note 3:
“3. REMOVE TEMPORARY CONNECTIONS AND ROUTE NEW ½” COMPRESSED AIR PIPING
AND 1/2" FLEXIBLE PLASTIC COMPRESSED AIR PIPING TO EQUIPMENT.”
15. DRAWING SHEET MD101 – LEVEL 1 – MECHANICAL DEMOLITION PLAN
15.1. Add Note: “ALL WORK ON THIS SHEET BY OWNER”
16. DRAWING SHEET MH101 – LEVEL 1 AND ROOF – HVAC PLANS
16.1. Detail A1, Add Note: “VERTICAL SUPPORT BY OWNER.”
16.2. Revise Detail A2: Extent of exhaust ductwork by owner indicated by halftone ductwork.
16.3. Revise Detail A3: Extent of exhaust ductwork by owner indicated by halftone ductwork.
16.4. Revise Variable Volume General Exhaust Terminal Unit Schedule, Remark 1. See attached.
16.5. Revised Keyed Notes:
16.5.1. Keyed Note 2: See attached.
16.5.2. Keyed Note 5: See attached.
16.5.3. Keyed Note 8: See attached.
17. DRAWING SHEET E-101 – LEVEL 1 POWER AND FIRE ALARM FLOOR PLAN
17.1. Add Keyed Note 7 symbol near Arc Cast equipment (vicinity Column Line Lb-14).
17.2. Add Keyed Note 7:
“7. Three (3) three-phase circuits to panel PF23 and one (1) one-phase circuit to panel LF-39 for Arc Cast equipment are Owner Furnished, Owner Installed. Reconnect circuit to new panel LF-39.”
18. DRAWING SHEET E-501 – ONE-LINE DIAGRAM
18.1. Panel PD480:
18.1.1. Breaker O2 – Change feeder note to: “4-500 MCM & #3G IN EXISTING 3” C.”
18.1.2. Breaker O2 – Change panel note to: “OWNER FURNISHED/OWNER
INSTALLED PANEL.”
19. DRAWING SHEET T-101 – LEVEL 1 – TELECOM AND SECURITY FLOOR PLAN
19.1.1. Change General Note C:
“C FURNISH (2) CABLES TO EACH DATA OUTLET UNLESS OTHERWISE INIDCATED
ON DRAWINGS. OWNER TO INSTALL, TEST, AND TERMINATE ALL CABLES.”
19.1.2. Keyed Note 1.
“1 DATA CABLES FROM ROOOM 160A WILL TERMINATE AT OWNER’S RACK IN THIS
LOCATION.”
19.1.3. Change Keyed Note 3.
“3 OWNER TO INSTALL, TERMINATE, AND TEST CABLES FURNISHED BY
CONTRACTOR. (TYP)”
Issued 6/1/2023
BBS 22066 PROJECT REQUIREMENTS
Ames Laboratory 00 74 13-1 MD Magnet Testbed Addendum 3
SECTION 00 74 13
PROJECT REQUIREMENTS
1. DEFINITIONS
a. Long Lead Items: Laboratory Casework.
b. Critical Laboratory Equipment: Arc Cast equipment.
2. SUMMARY OF WORK
a. General Description of Work:
1) Project consists of renovations and new work in Metals Development Rooms 160 and 160A to facilitate the installation of new laboratory equipment and support infrastructure.
2) Alternates: None.
3) Allowances: None.
4) Unit Prices: None.
b. Work by Owner: Owner will self-perform work or contract directly with others (outside the requirements of these Contract Documents) to facilitate the early procurement of long-lead products and installation of critical laboratory equipment in Room 160A. Refer to Drawings and Specifications listed. Inclusion of a Drawing or Specification Section in this list does not infer that all work on that Sheet or Section is by Owner. In some cases, work depicted is required by both Owner and Contractor. Contractor will work around, protect, and facilitate continued operation of critical laboratory equipment during the project and protect Owner installed finishes during construction.
1) Flooring:
a. Drawing Sheet G-001:
a) Detail A6: FLOOR – RESINOUS TO VCT
b) Detail B6: FLOOR – RESINOUS TO CONC
b. Drawing Sheet A-101:
a) Room Finish Schedule Note 11.
c. Specification Sections:
a) 09 60 01 – Floor Patching and Leveling.
b) 09 67 23 – Resinous Flooring.
2) Painting:
a. Drawing Sheet A-101:
a) Room Finish Schedule Notes 12, 13, and 14.
b. Specification Section:
a) 09 90 00 – Painting and Coating.
b) 09 01 90.52 – Maintenance Repainting.
3) Mechanical:
a. Drawing Sheet MD101:
a) All work shown on this sheet - exhaust duct demolition.
b. Drawing Sheet MP100:
a) All work shown on this sheet – process chilled water piping.
c. Drawing Sheet MP101:
a) All work shown on this sheet – process chilled water piping.
d. Drawing Sheet MH101:
a) 10” exhaust ductwork and accessories from Arc Cast equipment to tie-in to exhaust ductwork on roof. This includes tee fittings and caps in ductwork for connections to ductwork installed under this contract.
b) 4” Schedule 40 relief pipe from Arc Cast equipment, through roof.
c) Work shown in Detail A2, connecting to new ductwork to existing ductwork penetrating roof. Work includes Exhaust Terminal Unit and controls.
d) Slotted Steel Strut shown mounted to wall in Detail A1 to support exhaust ductwork at wall. (Cable tray and conduit work under this Contract).
e. Specification Section:
a) 23 07 19 – HVAC Piping Insulation.
b) 23 09 23 – Instrumentation and Controls for HVAC
BBS 22066 PROJECT REQUIREMENTS
Ames Laboratory 00 74 13-2 MD Magnet Testbed Addendum 3
c) 23 21 13 – Hydronic Piping
d) 23 21 16 – Hydronic Piping Specialties
e) 23 36 00 – Air Terminal Units
4) Electrical:
a. Drawing Sheet ED101:
a) Demolition of existing panels PF23A & PF23B, including feeders.
b. Drawing Sheet ED501:
a) Demolition of existing panels PF23A & PF23B, including feeders.
c. Drawing Sheet E-101:
a) Installation of new panel PF23, reconnection of existing circuits to AHU, Exhaust Fan, and Elevator, and connection of three new circuits to Arc Cast equipment.
d. Drawing Sheet T-101:
a) Installation, termination and testing of data circuits. (Data cabling product furnished under this Contract.)
c. Constructor Supervision and Coordination:
1) Laboratory Casework:
a. Products and Installation by Owner’s vendor, including blocking.
b. Contractor to coordinate equipment delivery and installation by Owner’s vendor to coordinate with overall construction schedule and adjacent construction.
i. Contractor to supervise installation in order to avoid damage to space and
Contractor’s new work.
ii. Contractor scheduling shall not unnecessarily delay project or installation of new laboratory casework.
END OF SECTION
ALIGNALIGN
AB
AC
ACI
ACT
AD-#
ADJ
AE-#
AF-#
AFF
AFG
AGG
AHU
AHU-#
AIC
ALT
ALUM
AMP
ANCH
ANSI
APPROX
ARCH
AS REQ'D
ASD
ASHRAE
ASTM
ATS
ATTEN
ANCHOR BOLT
ALTERNATING CURRENT
AMERICAN CONCRETE INSTITUTE
ACOUSTICAL CEILING TILE
AREA DRAIN - (MECH)
ADJACENT
AIR ELIMINATION DEVICE
AIR FITTING
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AGGREGATE
AIR HANDLING UNIT - (ARCH)
AIR HANDLING UNIT - (MECH)
AMPS INTERRUPTING CAPACITY
ALTERNATE
ALUMINUM
AMPERE
ANCHOR
AMERICAN NATIONAL STANDARDS
INSTITUTE
APPROXIMATE
ARCHITECTURAL
AS REQUIRED
ALLOWABLE STRESS DESIGN
AMERICAN SOCIETY OF
HEATING, REFRIGERATING, &
AIR CONDITIONING ENGINEERS
AMERICAN SOCIETY FOR
TESTING & MATERIALS
AUTOMATIC TRANSFER SWITCH
ATTENUATION
B-#
BB
BD
BFA-#
BFU-#
BLDG
BLK
BLKG
BM
BM
BOC
BOT
BRG
BTU
BTUH
BUR
BOILER
BALLED AND BURLAPPED
BOARD
BACKFLOW ASSEMBLY
BOILER FEED UNIT
BUILDING
BLOCK
BLOCKING
BENCH MARK (ARCH, CIVIL)
BEAM (STRUC)
BOTTOM OF CURB
BOTTOM
BEARING
BRITISH THERMAL UNIT
BRITISH THERMAL UNIT PER HOUR
BUILT-UP ROOFING
STANDARD ABBREVIATIONS
A
B
C C-#
CAB
CB
CB-#
CCTV
CCW-#
CDX-#
CF-#
CFM
CFOI
CG
CH-#
CHC
CHKBD
CI
CIP
CJ
CKT
C/B
CLG
CLR
CMT
CMU
CNTR
CO
COL
COMM
CON-#
CONC
CONST
CONT
COORD
CORR
CPH-#
CPT
CR
CR-#
CRE-#
CRH-#
CRI-#
CRP-#
CRU-#
CSK
CT
CT
CT-#
CTR
CU-#
CUH
CUH-#
CW
CONDUIT (ELEC)
CONDENSER (MECH)
CABINET
CATCH BASIN (ARCH)
CATCH BASIN (MECH)
CLOSED CIRCUIT TELEVISION
CHILLED WATER COIL
COIL, DX
CARBON DIOXIDE FITTING
CUBIC FEET PER MINUTE
CONTRACTOR FURNISHED, OWNER
INSTALLED
CORNER GUARD
CHILLER
COIL, HEATING
CHALK BOARD
CAST IRON
CAST IN PLACE
CONTROL JOINT
CIRCUIT
CIRCUIT BREAKER
CEILING
CLEAR
CERAMIC MOSAIC TILE
CONCRETE MASONRY UNITY
COUNTER
CLEAN OUT
COLUMN
COMMUNICATION
CONVECTOR
CONCRETE
CONSTRUCTION
CONTINUOUS
COORDINATE, COORDINATED
CORRIDOR
COIL, PREHEAT
CARPET
COLD ROLLED (STRUC)
CARD READER (ELEC)
COIL, EXHAUST RECLAIM
COIL, REHEAT
COIL, INTAKE RECLAIM
CONDENSATE RETURN PUMP
COMPUTER ROOM UNITY
COUNTERSINK
CERAMIC TILE (ARCH)
CURRENT TRANSFORMER (ELEC)
COOLING TOWER (MECH)
CENTER, CENTERED
CONDENSING UNIT
CABINET UNIT HEATER (ARCH)
CABINET UNIT HEATER (MECH)
COLD WATER, DOMESTIC
C
DA-#
DBL
DC
DC-#
DD-#
DDC
DEMO
DEPT
DF
DF-#
DIA
DIAG
DIM
DISP
DN
DWG
DS
DTL
DWC-#
DWH-#
DEAERATOR
DOUBLE
DIRECT CURRENT (ELEC)
DRY COOLER (MECH)
DECK DRAIN
DIRECT DIGITAL CONTROL
DEMOLITION
DEPARTMENT
DRINKING FOUNTAIN (ARCH)
DRINKING FOUNTAIN (MECH)
DIAMETER
DIAGONAL
DIMENSION
DISPENSER
DOWN
DRAWING
DOWNSPOUT
DETAIL
DRINKING WATER CHILLER (MECH)
DOMESTIC WATER CHILLER (MECH)
D
E
EA
EC-#
ECB
ED-#
EEW-#
EF
EF-#
EFC-#
EIFS
EJ
ELEV
EMERG
ENAM
ENCL
EP
EQ
EQUIP
ES-#
ET-#
EVC-#
EW
EW-#
EWC
EWC-#
EWS-#
EXH
EXIST
EXP
EXPS
EXT
ELECTRICAL
EACH
EXHAUST, CEILING MOUNTED
ENCLOSED CIRCUIT BREAKER (ELEC)
EXHAUST, DUCT MOUNTED
EMERGENCY EYE WASH
EACH FACE
EXHAUST, FLOOR MOUNTED
EVAPORATIVE FLUID COOLER
EXTERIOR INSULATION & FINISH SYSTEM
EXPANSION JOINT
ELEVATION
EMERGENCY
ENAMEL
ENCLOSURE
ELECTRICAL PANELBOARD
EQUAL
EQUIPMENT
EMERGENCY SHOWER
EXPANSION TANK
EVAPORATIVE CONDENSER
EACH WAY (STRUC)
EXHAUST, WALL MOUNTED (MECH)
ELECTRIC WATER COOLER (ARCH)
ELECTRIC WATER COOLER (ELEC)
EMERGENCY WASH STATION
EXHAUST
EXISTING
EXPANSION
EXPOSED
EXTERIOR
E
F-#
FA
FACP
FB-#
FC-#
FCU
FCU-#
FD
FD-#
FDN
FE
FE-#
FEC
FH
FH
FHC
FIN
FIXT
FL
FLASH
FLEX
FLG
FLOUR
FLR
FO
FPC-#
FPS
FPT-#
FR-#
FS-#
FSK-#
FT
FTG
FTR-#
FURR
FURNACE
FUSED AT
FIRE ALARM CONTROL PANEL
FILTER/FILTER BANK
FAN, CEILING MOUNTED
FAN COIL UNIT (ARCH)
FAN COIL UNIT (MECH)
FLOOR DRAIN (ARCH)
FLOOR DRAIN (MECH)
FOUNDATION
FIRE EXTINGUISHER
FAN, EXHAUST (MECH)
FIRE EXTINGUISHER CABINET
FIRE HYDRANT (CIVIL)
FLAT HEAD (STRUC)
FIRE HOSE CABINET
FINISH FLOOR
FIXTURE
FLOW LINE
FLASHING
FLEXIBLE
FLANGE (STRUC)
FLUORESCENT
FLOOR
FIBER OPTIC
FIRE PROTECTION CABINET
FEET PER SECOND
FAN POWERED TERMINAL
FAN, RELIEF
FAN, SUPPLY
FLOOR SINK
FEET/FOOT
FOOTING
FINNED TUBE RADIATOR
FURRING
F
G
G, GND
GA
GALV
GB
GC
GF-#
GFI
GL
GPM
GYP
GYP BD
GAS
GROUND
GAGE
GALVANIZED
GRADE BEAM
GENERAL CONTRACTOR
GAS FITTING
GROUND FAULT INTERRUPTER
GLASS
GALLONS PER MINUTE
GYPSUM
GYPSUM WALLBOARD
G
H-#
HB
HB-#
HC
HDWD
HDWR
HEX-#
HM
HOA
HORIZ
HP
HP
HP-#
HSS
HT
HTG
HTR
HW
HY
HZ
HUMIDIFIER
HOSE BIB (ARCH)
HOSE BIB (MECH)
HOLLOW CORE
HARDWOOD
HARDWARE
HEAT EXCHANGER
HOLLOW METAL
HAND OFF AUTOMATIC
HORIZONTAL
HIGH POINT (CIVIL, STRUCT)
HORSEPOWER (MECH)
HOUR
HOLLOW STRUCTURAL SHAPE
HEIGHT
HEATING
HEATER
HOT WATER, DOMESTIC
HYDRANT
HERTZ
H
IBC
ID
IG
IN
INSUL
INV
INTERNATIONAL BUILDING CODE
INSIDE DIAMETER
ISOLATED GROUND
INCH
INSULATION, INSULATED
INVERT
I
JAN
JB
JST
JT
JANITOR
JUNCTION BOX
JOIST
JOINT
J
KCMIL
KO
KVA
KW
THOUSAND CIRCULAR MILL
KNOCK OUT
KILOVOLT AMPERES
KILOWATTS
K
L-#
LAM
LAV
LCP
LDC
LGMF
LLH
LLV
LP
LP
LRFD
LT WT CON
LT-#
LVR
LVT
LAVATORY (MECH)
LAMINATE
LAVATORY (ARCH)
LIGHTING CONTROL PANEL
LOAD DISTRIBUTION CABINET
LIGHT GAGE METAL FRAMING
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LOW POINT (CIVIL, STRUCT)
LIQUID PETROLEUM GAS (MECH)
LOAD & RESISTANCE FACTOR DESIGN
LIGHT WEIGHT CONCRETE
LAVATORY TRIM
LOUVER
LUXURY VINYL TILE
L
MACH
MAN
MAU-#
MAX
MB
MB-#
MCC-#
MDF
MDO
MECH
MEMB
MEZZ
MFG
MH
MH-#
MIN
MISC
MO
MPH
MS
MTC
MTD
MTL
MTR
MUL
MACHINE
MANUAL
MAKE-UP AIR UNIT
MAXIMUM
MOP BASIN (ARCH)
MOP BASIN (MECH)
MOTOR CONTROL CENTER
MEDIUM DENSITY FIBERBOARD
MEDIUM DENSITY OVERLAY
MECHANICAL
MEMBRANE
MEZZANINE
MANUFACTURER
MANHOLE (ARCH)
MANHOLE (MECH)
MINIMUM
MISCELLANEOUS
MASONRY OPENING
MILES PER HOUR
MOTOR STARTER
EMPTY CONDUIT
MOUNTED
METAL
MOTOR
MULLION
M
N, NEUT
N/A
NC
NEC
NF
NFPA
NIC
NO
NO
NOM
NTS
NEUTRAL
NOT APPLICABLE
NORMALLY CLOSED
NATIONAL ELECTRIC CODE
NON FUSED
NATIONAL FIRE PROTECTION
ASSOCIATION
NOT IN CONTRACT
NORMALLY OPEN (ELEC)
NUMBER (GENERAL)
NOMINAL
NOT TO SCALE
N
OA
OC
OD
OD-#
OFCI
OFOI
OH
OPNG
OPP
OSB
OVER ALL
ON CENTER
OUTSIDE DIAMETER
OVERFLOW DRAIN (MECH)
OWNER FURNISHED,
CONTRACTOR INSTALLED
OWNER FURNISHED,
OWNER INSTALLED
OVERHEAD
OPENING
OPPOSITE
ORIENTED STRAND BOARD
O
PCD-#
PCH-#
PCI
PCW-#
PDI-#
PDR-#
PDU-#
PF
PF-#
PFO-#
PHP-#
PHR-#
PHW-#
PIR-#
PL
PL
PLAM
PLYWD
PNL
PPB-#
PR
PRA-#
PRC-#
PRI
PRO-#
PRV-#
PSE-#
PSF
PSI
PST-#
PT
PT
PTN
PVC
PWR
PUMP, CONDENSATE DRAIN
PUMP, CHILLED WATER
PRECAST CONCRETE INSTITUTE
PUMP, CONDENSER WATER
PUMP, DEIONIZED WATER
PUMP, DRINKING WATER - DOMESTIC
POWER DISTRIBUTION UNIT
POWER FACTOR
FIRE PUMP
PUMP, FUEL OIL SYSTEM
PUMP, HEAT PUMP SYSTEM
PUMP, DOMESTIC WATER RECIRCULATING
PUMP, HEATING WATER
PUMP, IRRIGATION
PILOT LIGHT (ELEC)
PLATE (STRUC, ARCH)
PLASTIC LAMINATE
PLYWOOD
PANEL
PUMP, DOMESTIC PRESSURE BOOSTER
PAIR
PRESSURE REDUCING ASSEMBLY
PUMP, RECLAIM SYSTEM
PRIMARY
PUMP, REVERSE OSMOSIS
PRESSURE RELEASE VALVE
PUMP, SANITARY SEWAGE EJECTOR
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
PUMP, STORM AND FOOTING DRAIN SUMP
POTENTIAL TRANSFORMER (ELEC)
POINT
PARTITION
POLYVINYL CHLORIDE
POWER
P
QT QUARRY TILE
Q
R R
RA
RB
RC
RC-#
RCP
RCP
RD
RD-#
RDR-#
REBAR
REF
REQ'D
RESIL
RF-#
RHW
RND
RO
RTU
RTU-#
RADIUS
RISER(S)
RETURN AIR
RESILIENT BASE
RESILIENT COVE BASE
RETURN, CEILING MOUNTED
REINFORCED CONCRETE PIPE (MECH)
REFLECTED CEILING PLAN (ARCH)
ROOF DRAIN (ARCH)
RETURN, DUCT MOUNTED
ROOF DRAIN RECEIVER
REINFORCING BAR
REFERENCE, REFER
REQUIRED
RESILIENT
RETURN, FLOOR MOUNTED
RECIRCULATING HOT WATER, DOMESTIC
ROUND
ROUGH OPENING
ROOF TOP UNIT (ARCH)
ROOF TOP UNIT (MECH)
R
S-#
SA
SA-#
SC-#
SCHED
SD-#
SECT
SF-#
SG-#
SH-#
SHT
SHT-#
SHTG
SIM
SPEC
SQ
SS
SS-#
ST-#
STD
STL
STRUC
SURF
SUSP
SW-#
SWBD
SWGR
SINK (MECH)
SUPPLY AIR
SOUND ATTENUATOR
SUPPLY, CEILING MOUNTED
SCHEDULE
SUPPLY, DUCT MOUNTED
SECTION
SUPPLY, FLOOR MOUNTED
STEAM GUN
SHOWER
SHEET (ARCH, STRUC)
SHOWER TRIM (MECH)
SHEATHING
SIMILAR
SPECIFICATION(S)
SQUARE
STAINLESS STEEL (ARCH) OR SANITARY
SEWER
SERVICE SINK (MECH)
SINK TRIM
STANDARD
STEEL
STRUCTURAL
SURFACE
SUSPENDED
SUPPLY, WALL MOUNTED
SWITCHBOARD
SWITCHGEAR
S
T T & G
TC-#
TD-#
TEL
TELECOM
TERR
TF
TF-#
THRU
TKBD
TOB
TOC
TOS
TS
T'STAT
TW-#
TYP
TREAD(S)
TONGUE AND GROOVE
TRANSFER GRILLE, CEILING MOUNTED
TRENCH DRAIN
TELEPHONE
TELECOMMUNICATIONS
TERRAZZO
TOP FLANGE (STRUC)
TRANSFER GRILLE, FLOOR MOUNTED
THROUGH
TACKBOARD
TOP OF BEAM
TOP OF CURB, TOP OF CONCRETE
TOP OF FOOTING
TOP OF STEEL
THERMOSTAT
TRANSFER GRILLE, WALL MOUNTED
TYPICAL
T
UH-#
UMC
UNO
UPC
UPS
UR-#
UNIT HEATER
UNIFORM MECHANICAL CODE
UNLESS NOTED OTHERWISE
UNIFORM PLUMBING CODE
UNINTERRUPTIBLE POWER SUPPLY
URINAL
U
V V
VA
VAE-#
VAR-#
VAS-#
VAV
VB
VCP
VCT
VDT
VER
VERT
VEST
VF-#
VFD-#
VSF
VTR
VWC
VOLT(S) (ELEC)
VENT (MECH)
VOLT AMPERE
VARIABLE AIR EXHAUST TERMINAL UNIT
VARIABLE AIR RETURN TERMINAL UNIT
VARIABLE AIR SUPPLY TERMINAL UNIT
VARIABLE AIR VOLUME
VINYL BASE
VITRIFIED CLAY PIPE
VINYL COMPOSITION TILE
VIDEO DISPLAY TERMINAL
VERIFY
VERTICAL
VESTIBULE
VACUUM FITTING
VARIABLE FREQUENCY DRIVE
VINYL SHEET FLOORING
VENT THRU ROOF
VINYL WALL COVERING
V
W W W/ W/O
WC-#
WD
WH
WH-#
WR
WT
WWF
WASTE (MECH)
WATTS (ELEC)
WITH
WITHOUT
WATER CLOSET
WOOD
WATER HEATER (ARCH)
WALL HYDRANT (MECH)
WATER RESISTANT
WEIGHT
WELDED WIRE FABRIC
W
STANDARD SYMBOLS
STANDARD MATERIALS LEGEND
12.22
12.22
12.22
12.22
1A
12.22
12.22
1A
2A
3A
4A
DETAIL
1/8" = 1'-0"
0' 2' 4' 8' 16'
SECTION MARK - SEE
SECTION 1 ON
SHEET 12.22
SECTION MARK - SEE
SECTION 1 ON
SHEET 12.22 -
DIRECTIONAL
DETAIL MARK - SEE
DETAIL 1 ON
SHEET 12.22
DETAIL MARK
WITH BUBBLE - SEE
DETAIL 1 ON
SHEET 12.22
ELEVATION MARK - SEE
ELEVATION 1 ON
SHEET 12.22
ELEVATION MARK - SEE
ELEVATION 1A, 2A, ETC. ON
SHEET 12.22
DRAWING TITLE -
NUMBER, NAME, AND
SCALE
GRAPHICAL SCALE
BREAK LINES
DATUM POINTSECOND LEVEL
12' - 5 1/2"
REVISION BUBBLE AND
REVISION TAG
SHEET NOTE MARK
WITH LEADER
A1
WOOD
INSULATION
FINISHES
PARTITION INDICATIONS
ELEVATION INDICATIONS
FINISHED WOOD
BATT OR LOOSE FILL
METAL STUD
CERAMIC TILE
CERAMIC TILE
RIGID INSULATION
WOOD BLOCKING -
CONTINUOUS
WOOD BLOCKING -
DISCONTINUOUS
MEDIUM DENSITY
FIBERBOARD
THIS IS A MASTER LIST. ALL ITEMS LISTED MAY NOT BE APPLICABLE TO THIS PARTICULAR PROJECT.
1B
WINDOW TAG
DOOR TAG
OFFICE
ROOM TAG -
ROOM NAME AND
ROOM NUMBER
BRICK
PLYWOOD
KEY NOTE MARK
WITH LEADER
XXXXX.X
WALL TYPE TAG
ACOUSTIC
CEILING TILE
GYPSUM BOARD
FOAMED IN PLACE
INSULATION
TROFFER LIGHT FIXTURE
RECESSED LIGHT FIXTURE
SUPPLY AIR DIFFUSER
RETURN AIR DIFFUSER
EXHAUST FAN
EXIT LIGHT
OCCUPANCY SENSOR
SMOKE DETECTOR
FIRE ALARM STROBE
SPRINKLER HEAD
S
OS
SECURITY CAMERA
PAGING SPEAKERS
WIRELESS ACCESS POINT
MD MOTION DETECTOR
WAP
ARCHITECTURAL LEGEND
EARTHWORKS
CONCRETE
MASONRY
METAL
EARTH /
COMPACT FILL
CONCRETE
FACE BRICK
STEEL /
OTHER METALS
CONCRETE
MASONRY UNIT
ALUMINUM
SAND
PRECAST CONCRETE
A1
SPOT ELEVATION12' - 5 1/2"
09 65 00.A2
09 67 23.A
09 65 00.B13
09 67 23.A1
09 67 23.A
09 67 23.A1
1" MIN
WHERE PRESENT
LOCATION OF
NEW WALL,
SHEET NUMBER
SHEET TITLE
REVISION DATE
CONSULTANT
LOCATION
PHONE
WEBSITE
219 EIGHTH STREET
DES MOINES, IOWA 50309
515-244-7167
WWW.BBSAE.COM
ISSUE DATE
PROJECT NUMBER
SUBMISSION
/8
/4
/2
/4
A
/2
24x36
2 3 4 5 6 7
C
D
E
F
B
1 2 3 4 5 6 7 8
/2
/2
:2
:4
A
M
C
U s e rs
\M G a u l\ D o c u m e n ts
\R e v it
L o c a l F ile s \2
A m e s L a b M
D M a g n e t
T e s tb e d
A R
C H m a tt h e w g a u l.
rv t
22066
ISSUE FOR BID
M D
M A
G N
E T
T E
S T
B E
D
ARCHITECTURAL
LEGEND AND
DETAILS
M E
T A
L S
D E
V E
L O
P M
E N
T B
L D
G
P
A M
M E
L D
R A
M E
S
IA
A M
E S
L A
B R
A T
O R
Y
G-001
05.05.2023
3 ADD-03 05.30.2023
3" = 1'-0"A6 FLOOR - RESINOUS TO VCT
SHEET NOTE LEGEND
D1 DEMO DOOR AND FRAME
D2 DEMO, SEE MECHANICAL
D3 DEMO, SEE ELECTRICAL
N1 STOP RESILIENT BASE AT EXISTING CORNER GUARDS
N2 ALL CASEWORK (12 35 53.B-G): OFOI - GC COORDINATE
KEYNOTE LEGEND
09 65 00.A2 EXIST VINYL COMPOSITION TILE
09 65 00.B13 DIVIDER STRIP, MANUFACTURER
RECOMMENDED, STAINLESS
09 67 23.A EPOXY RESINOUS FLOORING
09 67 23.A1 KEY FLOORING INTO EXISTING CONCRETE
AS RECOMMENDED BY MANUFACTURER
3" = 1'-0"B6 FLOOR - RESINOUS TO CONC
A L
IG
NA
L
IG
N
9 12 14
N
M
L
MAGNET
TESTBED
160A
CORRIDOR
005-S16
La
Lb
160A
VTI GLOVE BOX
& Ai TUBE
FURNACE
VTI GLOVE BOX
& Ai TUBE
FURNACE
PULSED
MAGNETIZER
ARC 500
LABPILOT
M-JET 10
CIP ASSY
03 54 00.A
12 35 53.A
12 35 53.E
12 35 53.E
12 35 53.D1
12 35 53.D1
12 35 53.D2
A-101
D4
12 35 53.A
13' - 2" 13' - 2"
12 35 53.F
.0
12' - 0" 4' - 0"
MACHINE
SHOP
2' - 6"
F V
F V
A-101
D3
A-101
B
A-101
B
TYP
ARC 500ARC 500
26 24 1626 24 1626 24 1626 24 16
10 44 16.A1
N1N1
12 35 53.G2
06 10 00.A2
/2
160A.1
A-101
A3
6' - 6" FV
F
V
26 24 16
A-101
C3
A-101
C3
A-101
B3
A-101
B3
N2
N2
N2
N2
B6
G-001
B6
G-001
TYP
B6
G-001
A6
G-001
9 14
N
M
L
La
Lb
DEMO CEILING
GRID AND TILE
AS NECESSARY
TO BUILD NEW
WALL AND
MOUNT NEW
WALL TRACK
TO NEW WALL.
REUSE CEILING
TILES.
MACHINE
SHOP
D3D3D3D3D3
D1
D2
D3
EXISTING
FLOOR
DEPRESSION
DEMOLITION GENERAL NOTES
A. PERFORM DEMOLITION WITHOUT DAMAGE TO
ADJACENT RETAINED CONSTRUCTION. WHERE SUCH
DAMAGE OCCURS, PATCH, REPAIR, OR OTHERWISE
RESTORE TO ITS ORIGINAL CONDITION.
B. PATCH AND REPAIR ALL SURFACES ADJACENT TO
DEMOLISHED ITEMS AS REQUIRED TO MATCH FINISHED
ADJACENT CONSTRUCTION.
C. PATCH AND REPAIR ALL OPENINGS AND VOIDS LEFT BY
REMOVAL OF EXISTING CONSTRUCTION, EQUIPMENT,
PIPING, DUCTS, CONDUIT, ETC. AS REQUIRED TO
MATCH FINISHED ADJACENT.
D. PROVIDE TEMPORARY SHORING AS REQUIRED FOR
SELECTIVE DEMOLITION.
E. UNLESS SPECIFICALLY INDICATED OTHERWISE,
REMOVE ALL DEMOLISHED MATERIALS FROM THE SITE
AND FOLLOW IOWA DNR AND LANDFILL PROCEDURES
TO PROPERLY SEPARATE AND DISPOSE OF MATERIALS
REMOVED FROM THE SITE.
F. PROVIDE ALL DEMOLITION AND DISPOSAL AS
REQUIRED FOR INSTALLATION OF NEW WORK AS
INDICATED, OR AS REASONBLY IMPLIED BY THESE
CONSTRUCTION DOCUMENTS.
G. STORE AND PROTECT ALL SALVAGED ITEMS NOTED OR
REQUESTED TO BE RETURNED TO OWNER.
COORDINATE WITH OWNER FOR THE LOCATION OF
STORAGE FOR SALVAGED ITEMS.
GENERAL NOTES
A. SCREENED (GRAY-TONE) LINES INDICATE EXISTING
CONSTRUCTION TO REMAIN.
B. BOLD SOLID LINES INDICATE NEW CONSTRUCTION.
C. FIELD VERIFY EXISTING BUILDING CONDITIONS,
ELEVATIONS, AND DIMENSIONS PRIOR TO START OF
WORK. NOTIFY ARCHITECT OF ANY DISCREPANCIES
FOUND IN RELATION TO THE CONTRACT DOCUMENTS.
D. GENERAL CONTRACTOR SHALL COORDINATE WORK
OF ALL TRADES PRIOR TO STARTING ANY
DEMOLITION/CONSTRUCTION.
E. DO NOT SCALE DRAWINGS TO DETERMINE
DIMENSIONS. VERIFY ALL DIMENSIONS. IMMEDIATELY
REPORT ANY DISCREPANCIES TO THE ARCHITECT.
F. ALL DIMENSIONS ARE GIVEN TO THE FACE OF FINISHED
SURFACE, UNLESS NOTED OTHERWISE. ± DIMENSIONS
ALLOW FOR VARIATION DUE TO EXISTING CONDITIONS.
G. ALL DIMENSIONS TO EXISTING STRUCTURE/WALLS ARE
APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY.
H. PROTECT FROM DAMAGE ALL EXISTING
CONSTRUCTION TO REMAIN.
I. MAINTAIN THE BUILDING IN A WEATHER TIGHT
CONDITION AT ALL TIMES.
J. MAINTAIN OPERATION OF ALL EXISTING SERVICES AND
UTILITIES TO THE BUILDING. COORDINATE ANY
DISRUPTIONS OR DISCONTINUATIONS WITH THE
OWNER'S REPRESENTATIVE IN ADVANCE.
K. REFER TO AND COORDINATE WITH MECHANICAL,
PLUMBING, AND ELECTRICAL DRAWINGS FOR EXTENT
OF ASSOCIATED DEMOLITION AND NEW WORK.
L. CONSULT ARCHITECT/STRUCTURAL ENGINEER FOR
ANY AND ALL LOCATIONS WHERE UNFORESEEN OR
UNUSUAL STRUCTURAL CONDITIONS EXIST.
M. PROVIDE BLOCKING AS REQUIRED IN WALLS FOR ALL
BASE AND WALL CABINETS, WALL-HUNG EQUIPMENT,
WALL-APPLIED DOOR HARDWARE, AND OWNER-
PROVIDED EQUIPMENT.
12 35 53.B2
12 35 53.B3
12 35 53.B1
12 35 53.B5
12 35 53.B6
12 35 53.B4
"4
12 35 53.C112 35 53.C1
12 35 53.C2
12 35 53.C112 35 53.C1
A-101
D3
12 35 53.B3
12 35 53.B2
12 35 53.B6
12 35 53.B5
12 35 53.G1 12 35 53.G1
12 35 53.G1
12 35 53.G3 12 35 53.G3
1" TYP
06 10 00.A2
12 35 53.G2
07 92 00.A107 92 00.A1
12 35 53.A 12 35 53.A
N2N2N2N2
N2
N2
ROOM FINISH NOTES:
1. WALL BASE ON NEW EAST WALL ONLY.
2. WALL BASE ON CASEWORK TOE-KICK AND VISIBLE SIDES.
3. PAINT ALL UNPAINTED DUCTWORK, PIPING, CONDUIT, ETC. TO MATCH THE WALL, CEILING, OR RAILING
THEY RUN PARALLEL TO. DO NOT PAINT BRICK. SEE ALSO NOTES 13 AND 14 BELOW FOR PAINTING TO BE
COMPLETED BY OWNER PRIOR TO WORK.
4. PROTECT FLOORING FROM DAMAGE WITH PLASTIC SHEETING TOPPED WITH RIGID HARDBOARD. TAPE
SEAMS. (MINIMUM PROTECTION REQUIRED).
WORK BY OWNER PRIOR TO BID ACCORDING TO DRAWINGS AND SPECIFICATIONS;
CONTRACTOR TO PROTECT FROM DAMAGE :
11. FILL THEN PREPARE CONCRETE FLOOR FOR FINISH FLOORING. APPLY FINISH FLOORING.
12. REMOVE PAINT FROM BRICKWORK THIS ROOM, INCLUDING INSIDE FACE OF OPENING IN WALL.
PAINT CORNER GUARDS AND LINTEL TO MATCH DOOR 160. DO NOT PAINT BRICKWORK.
13. RE-PAINT EXISTING CONSTRUCTION INCLUDING: WALLS, COLUMNS, CEILING, CRANE RAILS, DUCTWORK, PIPING, CONDUIT, ETC., BUT NOT LIGHT FIXTURES OR CRANE.
14. RE-PAINT INTERIOR OF OPENING TO LOADING DOCK, CRANE RAILS AND SUPPORTS, BALCONY, RAILINGS, LADDER, AND WEST FACE OF MEZZANINE DOOR AND DOOR FRAME TO MATCH DOOR 160.
A B
SEE SCHED
S E
E S
C H
E D
SEE SCHED
4" 4"
S E
E S
C H
E D
4" 4"
C
IP = INSULATED
METAL PANEL
SEE SCHED
S E
E S
C H
E D
08 11 13.B2
AL-1 HM-1
S E
E S
C H
E D
" 2"
SEE SCHED
2"
S E
E S
C H
E D
" 2"
SEE SCHED
2" 09 65 00.B5
07 92 00.A1
09 21 16.A
09 21 16.B
09 21 16.C09 21 16.C
09 65 00.B5
07 92 00.A1
CEILING AS SCHEDULED
08 11 13.B1
WALL TYPE, SEE PLAN
07 92 00.A107 92 00.A1
08 11 13.E3
WALL TYPE, SEE PLAN
07 92 00.A1
09 65 00.B509 65 00.B5
FLOOR ABOVE (SECTION)
COLUMN (PLAN)
(PLAN)
07 92 00.A1
08 11 13.E3
08 11 13.B2
WALL TYPE, SEE PLAN
07 92 00.A107 92 00.A1
07 91 00.A107 91 00.A1
08 11 13.H1
DOOR NOTES:
1. PROVIDE DOOR AND OR FRAME READY FOR FUTURE ELECTRIFIED HARDWARE.
05 50 00.A2
08 11 13.B2
07 91 00.A1
1/8" MIN
/2
08 11 13.B2
COUNTERSUNK
SCREWS, TYP
07 91 00.A1
05 50 00.A2
08 11 13.B2
07 91 00.A1
1/8" MIN
/2
07 91 00.A1
COUNTERSUNK
SCREWS, TYP
07 91 00.A2
WALL TYPE, EXISTING
07 92 00.A107 92 00.A1
08 43 00.A5
08 43 00.A13
08 43 00.A14
1/4"1/4"
/4
/4
SHEET NUMBER
SHEET TITLE
REVISION DATE
CONSULTANT
LOCATION
PHONE
WEBSITE
219 EIGHTH STREET
DES MOINES, IOWA 50309
515-244-7167
WWW.BBSAE.COM
ISSUE DATE
PROJECT NUMBER
SUBMISSION
/8
/4
/2
/4
A
/2
24x36
2 3 4 5 6 7
C
D
E
F
B
1 2 3 4 5 6 7 8
/2
/2
:2
:3
A
M
C
U s e rs
\M G a u l\ D o c u m e n ts
\R e v it
L o c a l F ile s \2
A m e s L a b M
D M a g n e t
T e s tb e d
A R
C H m a tt h e w g a u l.
rv t
22066
ISSUE FOR BID
M D
M A
G N
E T
T E
S T
B E
D
LEVEL 1 -
ARCHITECTURE
M E
T A
L S
D E
V E
L O
P M
E N
T B
L D
G
P
A M
M E
L D
R A
M E
S
IA
A M
E S
L A
B R
A T
O R
Y
A-101
05.05.2023
1/4" = 1'-0"A4 LEVEL 1 - ARCHITECTURE N
N
9 17 35
L
C
A
KEY PLAN
DOOR SCHEDULE
DOOR NO ROOM KEY SIDE
DOOR FRAME
RATING
HARDWARE
DESCRIPTION COMMENTSWIDTH HEIGHT TYPE MATL QTY TYPE
160 160A 6' - 0" 7' - 0" B HM 2 HM-1 - 1 1, PNT-3
160A 005-S16 6' - 0" 7' - 0" A ALUM 2 AL-1 - 2 1
160A.1 160 8' - 0" 10' - 0" C IP 2 HM-1 - 1, PNT-3
1/4" = 1'-0"A1 LEVEL 1 - ARCHITECTURE DEMOLITION
ROOM FINISH SCHEDULE
ROOM NO. ROOM NAME FLOOR BASE
WALLS
CEILING REMARKS (KEYED NOTES)NORTH EAST SOUTH WEST
160 MACHINE SHOP EXIST RB-1 EXIST EXIST EXIST PT-1 EXIST 1, 3
160A MAGNET TESTBED RESIN RB-1 PT-1 PT-1 PT-1 PT-1 PT-2 2, 3, 11, 12, 13, 14
1/4" = 1'-0"D4 ROOM 160A - ELEVATION NORTH
1/4" = 1'-0"
DOOR, PANEL TYPES
1/4" = 1'-0"
FRAME TYPES
3/4" = 1'-0"E4 WALL TYPE 1
1 1/2" = 1'-0"B3 HM DOOR HEAD / JAMB
1 1/2" = 1'-0"D3 GYP TO EXISTING
1 1/2" = 1'-0"B PANEL HEAD / JAMB
3 ADD-03 05.30.2023
1 1/2" = 1'-0"A3 PANEL MEETING
1 1/2" = 1'-0"A PANEL SILL
SHEET NOTE LEGEND
D1 DEMO DOOR AND FRAME
D2 DEMO, SEE MECHANICAL
D3 DEMO, SEE ELECTRICAL
N1 STOP RESILIENT BASE AT EXISTING CORNER GUARDS
N2 ALL CASEWORK (12 35 53.B-G): OFOI - GC COORDINATE
1 1/2" = 1'-0"C3 AL DOOR HEAD / JAMB
KEYNOTE LEGEND
03 54 00.A SELF LEVELING CONCRETE TOPPING
05 50 00.A2 STEEL CHANNEL
06 10 00.A2 2X BLOCKING FOR UPPER CABINETS,
COORDINATE WITH NEW SURFACE MOUNTED
CONDUIT ROUTED BEHIND CABINETS
07 91 00.A1 SINGLE SIDED COMPRESSIBLE FOAM TAPE
07 91 00.A2 DOUBLE SIDED COMPRESSIBLE FOAM TAPE
07 92 00.A1 SEALANT
08 11 13.B1 1 3/4" METAL DOOR
08 11 13.B2 1" INSULATED METAL PANEL
08 11 13.E3 5 3/4" DOUBLE RABBET HM DOOR FRAME
08 11 13.H1 REMOVEABLE GLAZING STOP METAL PANEL
08 43 00.A5 STOREFRONT DOOR FRAME
08 43 00.A13 STOREFRONT ALUMINUM TRIM
08 43 00.A14 ALUMINUM TRIM ANGLE
09 21 16.A 3-5/8" METAL STUDS
09 21 16.B BATT INSULATION
09 21 16.C 5/8" GYPSUM BOARD
09 65 00.B5 4" RESILIENT TOPSET BASE
10 44 16.A1 FIRE EXTINGUISHER, REMOVE AND REINSTALL
12 35 53.A EPOXY COUNTER WITH BACKSPLASH
12 35 53.B1 22" X 36", 31-3/4" HT FULL DOOR BASE CAB
12 35 53.B2 22" X 30", 31-3/4" HT FULL DOOR BASE CAB
12 35 53.B3 22" X 30", 31-3/4" HT 3 EQ DRAWER BASE CAB
12 35 53.B4 22" X 36", 34-3/4" HT FULL DOOR BASE CAB
12 35 53.B5 22" X 30", 34-3/4" HT FULL DOOR BASE CAB
12 35 53.B6 22" X 30", 34-3/4" HT 4 EQ DRAWER BASE CAB
12 35 53.C1 18" X 30", 30" HT HINGED FRAME WALL CAB
12 35 53.C2 18" X 30", 36" HT HINGED FRAME WALL CAB
12 35 53.D1 22" X 48", 84" HT HINGED DOOR FLOOR CAB
12 35 53.D2 22" X 48", 65" HT INSULATED SOLVENT CAB -
FOR FLAMMABLE SOLIDS
12 35 53.E 30" X 40" CART
12 35 53.F 6 CYLINDER GAS RACK
12 35 53.G1 FILLER PANEL, ALIGN WITH FACE OF COLUMN
12 35 53.G2 FILLER PANEL
12 35 53.G3 FILLER PANEL, SIDE OF BASE CABINET
26 24 16 ELECTRICAL PANEL, SEE ELECTRICAL
PLUMBING GENERAL NOTES:
A. PLUMBING ENTITIES DRAWN WITH THIS LINETYPE
( ) INIDICATES NEW WORK, UNLESS NOTED
OTHERWISE.
B. PLUMBING ENTITIES DRAWN WITH THIS LINETYPE
( ) INDICATES EXISTING TO REMAIN, UNLESS
NOTED OTHERWISE.
C. DRAWINGS SHOWING LOCATIONS OF FIXTURES,
EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT
ACTUAL INSTALLATION CONDITIONS. DRAWINGS
SHOW THE GENERAL ARRANGEMENT OF ALL
PIPING, DUCTWORK, EQUIPMENT, ETC. AND MAY
NOT INCLUDE ALL OFFSETS AND FITTINGS, AS
REQUIRED. THE DRAWINGS SHALL BE FOLLOWED
AS CLOSELY AS ACTUAL BUILDING
CONSTRUCTION AND THE WORK OF OTHERS WILL
PERMIT.
D. PLUMBING CONTRACTOR SHALL COORDINATE ALL
PLUMBING PIPING WITH ALL DUCTWORK AND
OTHER TRADES PRIOR TO COMMENCEMENT OF
WORK.
E. FURNISH AND INSTALL PLUMBING PRODUCTS IN
COMPLIANCE WITH LOCAL BUILDING CODES AND
THE AUTHORITY HAVING JURISDICTION, AND IN
ACCORDANCE WITH GENERALLY ACCEPTED
INDUSTRY STANDARDS AND PRACTICES AND
MANUFACTURER'S RECOMMENDATIONS.
F. VERIFY ACTUAL LOCATIONS OF FIXTURES AND
DRAINS.
G. SEQUENCE DOMESTIC WATER, GAS, AND
SANITARY PIPING WORK TO MINIMIZE DISRUPTION
TO EXISTING BUILDING.
9 12 14 17
N
M
Lb
La
L
MAGNET TESTBED
160A
CORRIDOR
005-S16
1/2" A
EX 1/2" A
EX 4" ST
EX 1/2" A
EX 1/2" A
EX 4" ST UP
TO RD
TUBE
FURNACE
GLOVE BOX
TUBE
FURNACE
GLOVE BOX
PULSE
MAGNETIZER
JET MILL
ARC
CAST
EX 1/2 A CONNECTION
EX 1/2" A CONNECTION
AND VALVE
1/2" A
RM 160
SHEET NUMBER
SHEET TITLE
REVISION DATE
CONSULTANT
LOCATION
PHONE
WEBSITE
219 EIGHTH STREET
DES MOINES, IOWA 50309
515-244-7167
WWW.BBSAE.COM
ISSUE DATE
PROJECT NUMBER
SUBMISSION
/8
/4
/2
/4
A
/2
24x36
2 3 4 5 6 7
C
D
E
F
B
1 2 3 4 5 6 7 8
/2
/2
:5 :4
A
M
C
U se rs \E
K o n ra d \D o c u m e n ts
\R e v it
L o ca l F ile s\
A m e s
L a b M
D M a g n e t
T e s tb e d
M E
C H e ko n ra d M
C L T
(R e c o ve ry rv t
22066
ISSUE FOR BID
M D
M A
G N
E T
T E
S T
B E
D
P
A M
M E
L D
R A
M E
S
IA
LEVEL 1 -
PLUMBING
PLAN
M E
T A
L D
E V
E L
O P
M E
N T
B L
D G
A M
E S
L A
B O
R A
T O
R Y
PL101
05.05.2023
KEYED NOTES
1 ROUTE 1/2" COMPRESSED AIR PIPING DOWN TIGHT TO
WALL TO APPROXIMATELY 36" AFF. PROVIDE SHUTOFF
VALVE AT FLEXIBLE PIPING CONNECTION.
2 ROUTE 1/2" FLEXIBLE PLASTIC COMPRESSED AIR
PIPING FROM THIS POINT TO EQUIPMENT.
3 DISCONNECT TEMPORARY FLEXIBLE PLASTIC
COMPRESSED AIR PIPING AND INSTALL AS SHOWN.
1/4" = 1'-0"A3 LEVEL 1 - PLUMBING PLAN KEY PLAN
N
1 ADD#03 05.30.2023
TUBE FURNACE - - - -
GLOVE BOX (3) 1" @ 36" AFF - - -
JET MILL (1) 4" @ 24" AFF - (1) 1/4" @ 24" AFF -
ARCAST (1) 4" @ 120"... (1) 4" @ 120" AFF (1) 1/4" @ 96" AFF 1-1/4" @ 82" AFF
NAME EXHAUST AIR RELIEF AIR COMPRESSED AIR PROCESS WATER
LABORATORY EQUIPMENT CONNECTION SCHEDULE
9 12 14 17
N
M
Lb
La
L
MAGNET TESTBED
160A
CORRIDOR
005-S16
EX 48"x8" SA UP EX 48"x8" SA UP EX 48"x8" SA UP
EX 10"Ø EAEX 48"x16" OA
EX 42"x20" SA EX 42"x16" SA EX 32"x16" SA
ER 10"x10" EA
EX 10"Ø EA
2 EX RETURN GRILLE
EX 10" EA
THROUGH ROOF
EX 10"Ø EA
EX 10"Ø EA
EX 4"Ø EA
MECHANICAL DEMOLITION GENERAL NOTES:
A. MECHANICAL ENTITIES DRAWN WITH THIS LINETYPE
( ) INIDICATES EXISTING TO BE DEMOLISHED,
UNLESS NOTED OTHERWISE.
B. MECHANICAL ENTITIES DRAWN WITH THIS LINETYPE
( ) INDICATES EXISTING TO REMAIN, UNLESS
NOTED OTHERWISE.
C. DRAWINGS SHOWING LOCATIONS OF FIXTURES,
EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT
ACTUAL INSTALLATION CONDITIONS. DRAWINGS
SHOW THE GENERAL ARRANGEMENT OF ALL
PIPING, DUCTWORK EQUIPMENT, ETC. AND MAY
NOT INCLUDE ALL OFFSETS AND FITTINGS AS
REQUIRED. THE DRAWINGS SHALL BE FOLLOWED
AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION
AND THE WORK OF OTHERS WILL PERMIT.
D. REMOVE HANGERS, SUPPORTS AND FASTENERS
FOR EXISTING PIPING INDICATED ON DRAWINGS TO
BE REMOVED.
E. MECHANICAL CONTRACTOR SHALL COORDINATE
ALL PIPING WITH ALL OTHER TRADES, PRIOR TO
COMMENCEMENT OF WORK.
RM 160
SHEET NUMBER
SHEET TITLE
REVISION DATE
CONSULTANT
LOCATION
PHONE
WEBSITE
219 EIGHTH STREET
DES MOINES, IOWA 50309
515-244-7167
WWW.BBSAE.COM
ISSUE DATE
PROJECT NUMBER
SUBMISSION
/8
/4
/2
/4
A
/2
24x36
2 3 4 5 6 7
C
D
E
F
B
1 2 3 4 5 6 7 8
/2
/2
:5 :4
A
M
C
U se rs \E
K o n ra d \D o c u m e n ts
\R e v it
L o ca l F ile s\
A m e s
L a b M
D M a g n e t
T e s tb e d
M E
C H e ko n ra d M
C L T
(R e c o ve ry rv t
22066
ISSUE FOR BID
M D
M A
G N
E T
T E
S T
B E
D
P
A M
M E
L D
R A
M E
S
IA
LEVEL 1 -
MECHANICAL
DEMOLITION
PLAN
M E
T A
L D
E V
E L
O P
M E
N T
B L
D G
A M
E S
L A
B O
R A
T O
R Y
MD101
05.05.2023
1/4" = 1'-0"A3 LEVEL 1 - HVAC DEMOLITION PLAN
KEYED NOTES
1 REMOVE DUCTWORK TO THIS POINT AND CAP BY
OWNER.
2 REMOVE DUCTWORK TO ROOF PENETRATION.
PREPARE FOR NEW CONNECTION.
KEY PLAN
N
1 ADD#03 05.30.2023
ALL WORK ON THIS
SHEET BY OWNER
9 12 14 17
M
Lb
La
L
MAGNET TESTBED
160A
CORRIDOR
005-S16
EX 32"x16" SAEX 42"x20" SA EX 42"x16" SA
EX 48"x16" OA EX 48"x24" OA
EX 24"x24" OA
EX 10"Ø EA
EX 10"Ø EA
EX 10"Ø EA
EX. 48"x8" SA UP EX. 48"x8" SA UP EX. 48"x8" SA UP
EX 46"x36" OA
4"Ø EA
EX 36"x8" RA
14"x10" RW-1
(@ 12" AFF)
14"x10" RW-1
(@ 96" AFF)
EX RETURN GRILLE
EX 10" EA
THROUGH
ROOF
CIP
EX 28"x28" EA
TUBE
FURNACE
GLOVE BOX
TUBE
FURNACE
GLOVE BOX
4"Ø EA
10"Ø EA
PULSE
MAGNETIZER
JET MILL
ARC
CAST
EX DUST
COLLECTOR
A2
MH101 EX 46"x36" OA
3 2
CAP AT WALL
BALANCE TO 30 CFM
BALANCE TO 490 CFM
BALANCE TO 10 CFM
BALANCE TO
10 CFM
4"Ø EA
1' - 4"
1' - 6"
4"Ø EA
4"Ø EA
GEV-1
(BY OWNER)
MECHANICAL GENERAL NOTES:
A. MECHANICAL ENTITIES DRAWN WITH THIS LINETYPE
( ) INIDICATES NEW WORK, UNLESS NOTED
OTHERWISE.
B. MECHANICAL ENTITIES DRAWN WITH THIS LINETYPE
( ) INDICATES EXISTING TO REMAIN, UNLESS
NOTED OTHERWISE.
C. DRAWINGS SHOWING LOCATIONS OF FIXTURES,
EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT
ACTUAL INSTALLATION CONDITIONS. DRAWINGS
SHOW THE GENERAL ARRANGEMENT OF ALL
PIPING, DUCTWORK EQUIPMENT, ETC. AND MAY
NOT INCLUDE ALL OFFSETS AND FITTINGS AS
REQUIRED. THE DRAWINGS SHALL BE FOLLOWED
AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION
AND THE WORK OF OTHERS WILL PERMIT.
D. VERIFY SIZE AND LOCATION OF EXISTING PIPING,
APPURTENANCES, FIXTURES AND EQUIPMENT AS IT
RELATES TO NEW WORK.
E. CAREFULLY CAULK ALL PIPE AND DUCT
PENETRATIONS OF FULL HEIGHT WALLS,
PARTITIONS, FLOOR AND ROOF ASSEMBLIES. THIS
IS ESSENTIAL TO PREVENT NOISE FROM GOING
FROM ONE ROOM TO ANOTHER AND TO PROVIDE
THE DESIRED NC LEVELS WITHIN THE ROOMS.
F. MECHANICAL CONTRACTOR SHALL COORDINATE
ALL PIPING & DUCTWORK WITH ALL OTHER TRADES,
PRIOR TO COMMENCEMENT OF WORK.
G. SUPPORT ALL UTILITIES IN ROOM 160A FROM WALL,
FLOOR, OR COLUMNS UNLESS OTHERWISE NOTED.
NO UTITILIES SHALL BE SUPPORTED FROM THE
CEILING TO MAINTAIN OPERATION OF EXISTING
CRANE HOIST.
RM 160
9 12 14 17
N
M
Lb La
L
EX 10"Ø EA
EX 10"Ø EA
EX EF
EX 10"Ø EA
EX ROOF SUPPORT
METAL FRAMING
SYSTEM SUPPORT
WALL/COLUMN
DUCT
CONDUIT
(COORDINATE
WITH ELECTRICAL)
CABLE TRAY
COORDINATE
WITH ELECTRICAL
FLOOR LEVEL
'0
A F
F
(C O
O R
D
IN
A T
E E
X A
C T
H E
IG
H
T
W
IT
H E
X
IS
T
IN
G C
O N
D
IT
IO
S
D O
T H
E R
T R
A D
E S
VERTICAL SUPPORT
BY OWNER APPROX. 3'0" TALL
WALL/COLUMN
CONDUIT, COORD W ELEC
C O
O R
D
IN
A T
E E
X A
C T
H E
IG
W
IT
H E
X
IS
T
IN
G C
O N
D
IT
IO
D O
T H
E R
T R
A D
E S
M
A
IN
T A
IN
S
A M
E H
E
IG
R
O U
G H
O U
T R
O O
M
A
F F
M
A X
CRANE RAIL BEAM
AND BRACKET
DUCT
METAL FRAMING
SYSTEM SUPPORT
CABLE TRAY, COORD W ELEC
STEEL SUPPORT CABLE
SPLAY CABLES EAST AND WEST
FOR LATERAL STABILITY
DUCT, CONDUIT, ETC.
ON CANTILEVER NOT
SHOWN FOR CLARITY
N
12' - 5 3/8"
SECOND FLOOR
24' - 0"
HIGH ROOF
26' - 8"
TOP OF PARAPET
10"Ø EA
10"Ø SA
8"Ø EA
EX 32"x16" SAEX 10"x10" EA
GEV-1
10"Ø EA
4"Ø EA
MH101
C1
EX CRANE
RAIL
(BY OWNER)
SHEET NUMBER
SHEET TITLE
REVISION DATE
CONSULTANT
LOCATION
PHONE
WEBSITE
219 EIGHTH STREET
DES MOINES, IOWA 50309
515-244-7167
WWW.BBSAE.COM
ISSUE DATE
PROJECT NUMBER
SUBMISSION
/8
/4
/2
/4
A
/2
24x36
2 3 4 5 6 7
C
D
E
F
B
1 2 3 4 5 6 7 8
/2
/2
:5 :5
A
M
C
U se rs \E
K o n ra d \D o c u m e n ts
\R e v it
L o ca l F ile s\
A m e s
L a b M
D M a g n e t
T e s tb e d
M E
C H e ko n ra d M
C L T
(R e c o ve ry rv t
22066
ISSUE FOR BID
M D
M A
G N
E T
T E
S T
B E
D
P
A M
M E
L D
R A
M E
S
IA
LEVEL 1 AND
ROOF - HVAC
PLANS
M E
T A
L D
E V
E L
O P
M E
N T
B L
D G
A M
E S
L A
B O
R A
T O
R Y
MH101
05.05.2023
1/4" = 1'-0"A3 LEVEL 1 - HVAC PLAN
DIFFUSER, REGISTER & GRILLE SCHEDULE
DESIGNATION MANUFACTURER MODEL DESCRIPTION MATERIAL
FRAME
BORDER FINISH REMARKS
RW-1 PRICE 535L SINGLE DEFLECTION GRILLE WITH 1/2" BLADE SPACING STEEL FLUSH WHITE -
KEYED NOTES
1 CONNECT NEW 10" EXHAUST AIR AT EXISTING 12"X12"
EXHAUST AIR THROUGH ROOF.
2 ROUTE DUCTWORK STACKED ON WALL AT
APPROXIMATELY 13'6" WITH PIPING AND CONDUIT.
COORDINATE WITH OTHER TRADES.
3 ROUTE NEW EXHAUST DUCTWORK ON WALL BEHIND
EXISTING. COORDINATE WITH OTHER TRADES.
4 CONTRACTOR SHALL PROVIDE WALL SUPPORTED
CABLE TRAY STRUCTURE BOLTED TO EXISTING
HOLLOW CMU WALL. HATCHED REGION INDICATES
APPROXIMATE DIMENSIONS OF TRAY. COORDINATE
DIMENSIONS WITH OTHER TRADES. TRAY SHALL BE
ABLE TO SUPPORT 250 LBS OF CABLING AND DUCT.
CONTRACTOR SHALL DESIGN ALL STRUCTURE
ASSOCIATED WITH TRAY AND WALL SUPPORT AND
PROVIDE SEALED ENGINEERING CALCULATIONS FOR
THE DESIGNED ELEMENTS.
5 BY OWNER: ROUTE 4" SCHEDULE 40 STEEL RELIEF
PIPE THROUGH ROOF. MAXIMUM LENGTH OF PIPE
SHALL BE THIRTY (30) FEET WITH MAXIMUM OF TWO
(2) 90 DEGREE ELBOWS. TERMINATE PIPE WITH A 45
DEGREE ELBOW AND BIRD SCREEN APPROXIMATELY
36" ABOVE ROOF. PROVIDE WARNING SIGN READING
"BURST DISK RELIEF. MAINTAIN MINIMUM 10'0"
DISTANCE FROM DISCHARGE."
6 OFFSET DOWN TO EQUIPMENT CONNECTION.
7 OFFSET DOWN TO OWNER PROVIDED SUPPORT
ABOVE EQUIPMENT.
8 BY OWNER: CONNECT TO EXISTING DUCT CURB
THROUGH ROOF. ROUTE DUCTWORK AS SHOWN AND
CONNECT TO DUCT AT EXISTING ENDCAP. SUPPORT
DUCT FROM ROOF AS REQUIRED VIA SUPPORT
MATCHING EXISTING ROOF SUPPORT WITH 4X4 (FIELD
VERIFY) CONCRETE BASE.
KEY PLAN
N
REMARKS
1. -
1/8" = 1'-0"E5 HIGH ROOF - HVAC PLAN
A1
WALL UTILITY
SUPPORT DETAIL
1 ADD#03 05.30.2023
VARIABLE VOLUME GENERAL EXHAUST TERMINAL UNIT SCHEDULE
DESIGNATION MANUFACTURER MODEL
INLET SIZE
(IN.)
MAXIMUM
AIRFLOW
(CFM)
MINIMUM
AIRFLOW
(CFM) REMARKS
GEV-1 PRICE RDV 8 800 125 1
REMARKS
1. BAS SUB-CONTRACTOR (BY OWNER) SHALL CONTROL GEV-1 TO A CONSTANT AIRFLOW. FINAL AIRFLOW
SHALL BE SET AT BALANCING. PROVIDE AIRFLOW READOUT ON BAS SYSTEM FRONT-END. ALARM WHEN AIRFLOW IS LESS THAN 20% (adj.) OF BALANCED AIRFLOW.
TUBE FURNACE - - - -
GLOVE BOX (3) 1" @ 36" AFF - - -
JET MILL (1) 4" @ 24" AFF - (1) 1/4" @ 24" AFF -
ARCAST (1) 4" @ 120"... (1) 4" @ 120" AFF (1) 1/4" @ 96" AFF 1-1/4" @ 82" AFF
NAME EXHAUST AIR RELIEF AIR COMPRESSED AIR PROCESS WATER
LABORATORY EQUIPMENT CONNECTION SCHEDULE
1/4" = 1'-0"C1
CANTILEVERED UTILITY
SUPPORT DETAIL
1/4" = 1'-0"A2
EXHAUST AIR
TRANSITION TO ROOF
J J J J J J
GENERAL NOTES:
A. ELECTRICAL ENTITIES DRAWN WITH THIS LINETYPE
( ) INDICATES NEW WORK, UNLESS
NOTED OTHERWISE.
B. ELECTRICAL ENTITIES DRAWN WITH THIS LINETYPE
( ) INDICATES EXISTING TO REMAIN,
UNLESS NOTED OTHERWISE.
C. COORDINATE FINAL LOCATIONS OF EQUIPMENT-
MOUNTED CONVENIENCE RECEPTACLES WITH
OWNER AT ROUGH-IN.
D. INTERCEPT ALL EXISTING 120V CIRCUITS
SPECIFICALLY NOTED (CONVENIENCE RECEPTS &
GENERAL USE DEVICES) LOCATED IN MACHINE
SHOP 160 AND RETERMINATE EXISTING
CONDUCTORS ON NEW 1P-20A BREAKER IN PANEL
LF-43. NOTE CIRCUITS ON NEW PANEL SCHEDULES
AT PROJECT CLOSEOUT.
2 4 7 9 12 14 17
N
M
Lb
La
L
PF-23LF-39LF-43
JET MILL
ARC MELTER
PF-24
DC POWER
SUPPLY 1
DC POWER
SUPPLY 2
INDUCTION POWER
CONTROL POWER
PF-23- 1,3,5
PF-23- 2,4,6
PF-23- 7,9,11
LF-39- 1
LF-39- 27
LF-39- 2
LF-39- 3
LF-39- 4
LF-39- 5
LF-39- 6
LF-39- 7
LF-39- 8
LF-39- 9
PF-23- 8,10,12
PF-23- 13,15,17
LF-39- 12
PULSED
MAGNETIZER
PF-23- 14,16,18
MACHINE SHOP
MAGNET TESTBED
160A
162 162A
LF-43- 1,3,5
PF-24- 1,3,5
PF-24- 2,4,6
LF-43- 7,9,11
LF-43- 8,10,12
LF-43- 2,4,6
LF-43- 14,16,18
LF-43- 13,15,17
LF-39- 16,18,20
LF-39- 17,19,21
PF-23- 19,21,23
+48" +48" +48"
+48"
+48"
+48"
+48"
LF-39- 24
159E-101
E1
WATER FOUNTAIN
OWNER FURNISHED
OWNER INSTALLED
PANEL PF-23
LF-39- 15
LF-39- 10
LF-39- 11,13
NEMA L5-20C
NEMA L6-20C
LF-39- 26,28
NEMA L5-20C
NEMA L6-20C
LF-39- 25
LF-39- 14
VACUUM PUMP
TUBE FURNACE
VACUUM PUMP
TUBE FURNACE
4 4
MD 160AMD 160
SHEET NUMBER
SHEET TITLE
REVISION DATE
CONSULTANT
LOCATION
PHONE
WEBSITE
219 EIGHTH STREET
DES MOINES, IOWA 50309
515-244-7167
WWW.BBSAE.COM
ISSUE DATE
PROJECT NUMBER
SUBMISSION
/8
/4
/2
/4
A
/2
24x36
2 3 4 5 6 7
C
D
E
F
B
1 2 3 4 5 6 7 8
/4
/2
:2 :0
P
M
C
U s e rs
\B R h o d e s \D o c u m e n ts
\R e v it
L o c a l F ile s \2
A m e s L a b M
D M a g n e t
T e s tb e d
E L E
C b rh o d e s V
G U
Y B
.r v t
22066
ISSUE FOR BID
M D
M A
G N
E T
T E
S T
B E
D
05.05.2023
LEVEL 1 -
POWER AND
FIRE ALARM
FLOOR PLAN
M E
T A
L S
D E
V E
L O
P M
E N
T B
L D
G
P
A M
M E
L D
R A
M E
S
IA
A M
E S
L A
B R
A T
O R
Y
E-101
VACUUM PUMP 1200 1 120 10.0 20A LF-39
GLOVE BOX 2
TUBE FURNACE 5500 1 208 26.4 35A LF-39
PULSED MAGNETIZER 1 SINGLE POINT CONNECTION 20785 3 480 25.0 40A PF-23
NETZCH JET MILL 1 SINGLE POINT CONNECTION 13302 3 480 16.0 20A PF-23
CONTROL POWER 3600 1 120 30.0 30A LF-39
INDUCTION POWER 17000 3 480 20.4 25A PF-23
DC POWER SUPPLY 2 73000 3 480 87.8 110A PF-23
ARCCAST ARC 500 1
DC POWER SUPPLY 1 73000 3 480 87.8 110A PF-23
EQUIPMENT QUANTITY CONNECTION LOAD (VA) PHASE VOLTAGE (V) AMPS BREAKER SIZE PANEL
LAB EQUIPMENT - ELECTRICAL REQUIREMENTS
1/4" = 1'-0"A1 LEVEL 1 - POWER & FIRE ALARM PLAN
1/2" = 1'-0"E1 ENLARGED PLAN - GLOVE BOX CIRCUITING
KEYED NOTES
1 INTERCEPT EXISTING CRANE CIRCUIT AND
RETERMINATE ON NEW PANEL LF-39 VIA NEW
DISCONNECT AS SHOWN. PROVIDE 3-#12, #12G, 3/4"
C. AS REQUIRED.
2 INTERCEPT EXISTING DUST COLLECTOR CIRCUIT
AND RETERMINATE ON NEW PANEL PF-23 VIA NEW
STARTER DISCONNECT AS SHOWN. PROVIDE 3-#12,
#12G, 3/4" C. AS REQUIRED.
3 DISCONNECT MOUNTED ON EAST WALL OF MD 159,
APPROXIMATELY 15' EAST OF THIS LOCATION.
4 ROUTE ALL CIRCUITS ON GLOVE BOX TO SINGLE
LOCATION AT UTILITY SUPPORT LADDER AS SHOWN.
PROVIDE 24" OF SEO CABLE WITH
MATCHING NEMA PLUG FOR EACH CIRCUIT SHOWN
FROM JUNCTION BOX. COORDINATE WITH
MECHANICAL FOR ROUTING ON UTILITY LADDER.
5 SUSPEND SEOW CORDS FROM JUNCTION BOXES AT
OVERHEAD MOUNTING FOR CONDUIT AND
DUCTWORK TO GLOVEBOX. PROVIDE PROPER
STRAIN RELIEF AT TOP.
6 PROVIDE ONE #10 AWG GROUND WIRE FROM
ARCAST SYSTEM FRAME TO GROUND BUS OF
PANEL PF-23. BOND TO 1/2" CONDUIT WITH
GROUNDING BUSHING AND ROUTE WITH OTHER
CONDUITS FROM MACHINE TO PANEL.
KEY PLAN
7 THREE (3) THREE-PHASE CIRCUITS TO PANEL
PF23 AND ONE (1) ONE-PHASE CIRCUIT TO PANEL
LF-39 FOR ARC CAST EQUIPMENT ARE OWNER
FURNISHED, OWNER INSTALLED. RECONNECT
CIRCUIT TO NEW PANEL LF-39.
1 ADD #03 05/30/2023
LF-39
RM 160A
PF-24
RM 160A
NEW 4-4/0 & 1-#4G IN
NEW 2-1/2" C.
NEW 4-4/0 & 1-#4G IN
NEW 2-1/2" C.
NEW 4-4/0 & 1-#4G IN
EXISTING 3-1/2" C.
AM
AM
800A/3P-225A800A/3P-225A
800A/3P-400A800A/3P-225A
800A/3P-225A800A/3P-200A
800A/3P-225A800A/3P-200A
1200A/3P-600A800A/3P-250A
800A/3P-250A800A/3P-225A
800A/3P-250A [240A (.4)]800A/3P-225A
800A/3P-250A800A/3P-250A
800A/3P-250A800A/3P-250A
1600A/3P-1000A800A/3P-225A [250A (.9)]
800A/3P-225A [250A (.9)] 800A/3P-400A
800A/3P-200A [250A (.8)] 800A/3P-480A [600A (.8)]
800A/3P-225A [250A (.9)] 800A/3P-250A
800A/3P-200A [250A (.8)] 800A/3P-200A [250A (.8)]
800A/3P-200A [250A (.8)] 800A/3P-250A
4000A/3P-2400A [4000A (.6)]
800A/3P-225A [250A (.8)]
800A/3P-250A
800A/3P-250A
800A/3P-125A [250A (.5)]
800A/3P-225A [400A (.56)]
800A/3P-200A [250A (.8)]
800A/3P-125A
800A/3P-370A [600A (.63)]
800A/3P-360A [400A (.9)]
800A/3P-250A
800A/3P-250A
800A/3P-250A
800A/3P-250A
800A/3P-250A
800A/3P-250A
800A/3P-375A [600A (.63)]
800A/3P-125A [250A (.5)]
800A/3P-250A
800A/3P-250A
800A/3P-250A
800A/3P-600A
800A/3P-250A
1600A/3P-1250A [1600A (.8)]
AM
AM
P.T.FUSE
C.T.
P.T.FUSE
(T2)
EF-2 VFD
EF-1 VFD
163 DISC. (2)
164 DISC. (2)
(T7)
(T1)
(T3)
(T1)
(T3)
160 DISC. (7)
160 DISC. (6)
282 DISC. (1)
160 DISC. (17)
164 DISC. (1)
159 DISC. (2)
160 DISC. (2)
160 DISC. (8)
160 DISC. (9)
160 DISC. (15)
160 DISC. (13)
160 DISC. (14)
160 DISC. (11)
160 DISC. (12)
GROUND
LF-40
RM 187
LF-17
RM 148 4#3/0
2-1/2"C
4#250MCM
2-1/2"C
LF-16
RM 131 4#3/0
2-1/2"C
4#3/0 2-1/2"C
LF-38
RM 190
4#3/0 2-1/2"C
4#4/0 3"C
LF-15
CORR.
LF-37
RM 177
BUSDUCT RM 187
LF-30
LF-11
RM C28 4#250MCM (2) 4#300 MCM
3"C
BUSDUCT RM 187
LF-29
LF-10
RM 150 4#3/0
2-1/2"C
4#4/0 3"C
LF-9
CORR. 4#3/0
2-1/2"C
4#4/0 3"C
BUSDUCT RM 167C
LF-27
4#4/0 3"C
LF-26
RM 1804#4/0
3"C
BUSDUCT RM 244
LF-25
LF-6
RM 199 4#3/0
2-1/2"C
1000A BUS
BUSDUCT RM 244
LF-24
LF-5
RM 244 4#3/0
2-1/2"C
LF-24
CORR. C27
BUSDUCT RM 244
LF-23
LF-4
RM 290
LF-23
CORR. C27(2) 4#4/0
2-1/2"C
LF-4B
RM 290 4#3/0 2-1/2"C
4#3/0 (RH)
2-1/2"C
BUSDUCT RM 244
LF-22
4#3/0 2-1/2"C
4#3/0
2-1/2"CLF-22
CORR. C274#4/0
3"C
LF-3
RM 296
4#3/0 2-1/2"C
(2) 4#2/0
LF-2
4#3/0 2-1/2"C
LF-1
RM C23RM. 202 CORR.
N E
U T
R A
L
A
B U
S
30'
4160V
DELTA
1000KVA
208Y/120V 3P, 4W
T
8 SETS #750MCM
A
A
4160V FROM RM B5
HVS
RM 244
GROUND
REMOVABLE LINK
REMOVABLE LINK
SPARE
PF-21
RM 150B3#400MCM
PF-19
RM 2443#3/0
1-1/4"C
PF-18
RM 150A3#1
1-1/4"C
PF-17
RM 1483#1
1-1/4"C
PF-16
RM 131(2) 4#3/0
BUSDUCT RM 135
PF-14
BUSDUCT RM 150
PF-13
BUSDUCT RM 150
PF-12
BUSDUCT RM 187
PF-11
BUSDUCT RM 199
PF-10
3#4/0 2-1/2"C
(2) 4#3/0 2-1/2"C
PF-8
RM 131
PF-6 MCC-AC
RM 2403#2
1-1/4"C
3#4/0 (RH)
2-1/2"C
BUSDUCT RM 244
PF-1
N E
U T
R A
L
A
B U
S
C.T.
4160V DELTA
750KVA
480Y/277V 3P, 4W
80°C RISE
5.4%IMPEDANCE
AT 100%
A
A
4160V FROM RM B5
120/208V 3PH, 4W277/480V 3PH, 4W
3#2
3#2
M1
Q1
P2
3#350MCM
PF-8 MCC
RM 131
M3 PF-9
RM 177
P3
3#4/0 2-1/2"C
P4
3#4/0 2-1/2"C
N3
3#4/0 2-1/2"C
3#4/0 2-1/2"C
N4
3#4/0 2-1/2"C
PF-14 MCC
RM 135
3#3/0
M2
O2
N2
Q4
O1
M4
P1
Q2
R3
3#2
3#2
F4B1
RM. 102CORR.
H1B3
L1E1
K2D2
H3E2
(2) 4#3/0 2-1/2"C
A1E4
I4D1
J4E3
LF-27 #1
RM 180
LF-27 #2
RM 180
LF-28
RM 161
J3F3
J1F2
A2F1
LF-30 #2
RM 190
LF-30 #3
RM 190
K3D3
I3D4
4#4/0 3"C
LF-15A
CORR.
I2G3
H2G2
LF-25A
RM 290
LF-25B
CORR. C27
4#3/0
PD
T
HVS
RM 244
PD
4#3/0 2-1/2"C
4#3/0 2-1/2"C
4-#4
3#6
3#6
3#6 3#122#123#10
3#12
2#6
3#10
3#12
3#12
3#12
N1
Q3
R1
R2
SPARE
LF-21
RM. 224
EM-PD
SPARE
800A/3P-225A [250A (.9)]800A/3P-225A [250A (.9)]
LF-41
RM 187
LF-18
RM 156 4#3/0
2-1/2"C
K4G1
800A/3P-225A [250A (.9)]800A/3P-225A [250A (.9)]
LF-42
RM 157
LF-19
RM b-4 4#3/0
2-1/2"C
I1B4
BUSDUCT RM 131
PF-15
O4
800A/3P-250A
PF-20
RM B-1
ELEVATOR
SPARE
SPARE
SPARE
SPARE
800A/3P-400A800A/3P-200A
BUSDUCT RM 187
LF-31
LF-12A
RM 203
H4C1
800A/3P-250A800A/3P-200A [250A (.8)]
BUSDUCT RM 150
LF-32
LF-13
RM 229
L2C2
800A/3P-250A800A/3P-200A [250A (.8)]
BUSDUCT RM 150
LF-33
LF-13A
RM 229
L4B2
800A/3P-250A800A/3P-200A [250A (.8)]
BUSDUCT RM 135
LF-34
LF-14
RM 103
L3C4
800A/3P-240A [600A (.4)]800A/3P-200A [250A (.8)]
BUSDUCT RM 131
LF-35
LF-14A
RM 103
K1C3
800A/3P-250A
BUSDUCT RM 131
LF-36
J2
LF-43
RM 160
160 DISC. (16)
800A/3P-250A
G4
SPARE
PF-23
RM 160
4- 500 MCM & #3G IN 3" C.
257A EXHAUST
DISC.
257A AHU-15
DISC.
160 DISC. (10)
3#12
3#10
3#12
159 DISC. (1)
OWNER FURNISHED / OWNER INSTALLED
PANEL. CONTRACTOR TO REMOVE TEMP
CIRCUITS AND COMPLETE CONNECTION OF
CIRCUITS RELOCATED FROM OLD PANEL AT
THIS LOCATION.
GENERAL NOTES:
A. ELECTRICAL ENTITIES DRAWN WITH THIS LINETYPE
( ) INDICATES NEW WORK, UNLESS
NOTED OTHERWISE.
B. ELECTRICAL ENTITIES DRAWN WITH THIS LINETYPE
( ) INDICATES EXISTING TO REMAIN,
UNLESS NOTED OTHERWISE.
SHEET NUMBER
SHEET TITLE
REVISION DATE
CONSULTANT
LOCATION
PHONE
WEBSITE
219 EIGHTH STREET
DES MOINES, IOWA 50309
515-244-7167
WWW.BBSAE.COM
ISSUE DATE
PROJECT NUMBER
SUBMISSION
/8
/4
/2
/4
A
/2
24x36
2 3 4 5 6 7
C
D
E
F
B
1 2 3 4 5 6 7 8
/4
/2
:2 :0
P
M
C
U s e rs
\B R h o d e s \D o c u m e n ts
\R e v it
L o c a l F ile s \2
A m e s L a b M
D M a g n e t
T e s tb e d
E L E
C b rh o d e s V
G U
Y B
.r v t
22066
ISSUE FOR BID
M D
M A
G N
E T
T E
S T
B E
D
05.05.2023
ONE-LINE
DIAGRAM
M E
T A
L S
D E
V E
L O
P M
E N
T B
L D
G
P
A M
M E
L D
R A
M E
S
IA
A M
E S
L A
B R
A T
O R
Y
E-501
EXTEND AND RECONNECT
EXISTING CIRCUITS
EXTEND AND RECONNECT EXISTING
CIRCUITS
EXTEND AND RECONNECT
EXISTING CIRCUITS
1 ADD #03 05/30/2023
4-500 MCM & #3G IN EXISTING 3” C.
DP
DP
C R
ML
ML
R X
9 12 14 17
N
M
Lb La
L
K
J
H
G
F
E
D
C
6"x2" CT
3" C.
D-RINGS
BOTH SIDES.
4" C. TO B3
MAGNET TESTBED
160A
D
C
B3
4" C. FROM LEVEL 1
MD 160A
MD B3
GENERAL NOTES:
A. ELECTRICAL ENTITIES DRAWN WITH THIS LINETYPE
( ) INDICATES NEW WORK, UNLESS
NOTED OTHERWISE.
B. ELECTRICAL ENTITIES DRAWN WITH THIS LINETYPE
( ) INDICATES EXISTING TO REMAIN,
UNLESS NOTED OTHERWISE.
C. PROVIDE (2) CABLES TO EACH DATA OUTLET
UNLESS OTHERWISE INDICATED ON DRAWINGS.
D. PROVIDE CONDUIT FROM ALL DATA OUTLETS
SHOWN TO CABLE TRAY. ROUTE ALL NEW CABLES
TO MD B3 TELECOM RACK.
SHEET NUMBER
SHEET TITLE
REVISION DATE
CONSULTANT
LOCATION
PHONE
WEBSITE
219 EIGHTH STREET
DES MOINES, IOWA 50309
515-244-7167
WWW.BBSAE.COM
ISSUE DATE
PROJECT NUMBER
SUBMISSION
/8
/4
/2
/4
A
/2
24x36
2 3 4 5 6 7
C
D
E
F
B
1 2 3 4 5 6 7 8
/4
/2
:2 :1
P
M
C
U s e rs
\B R h o d e s \D o c u m e n ts
\R e v it
L o c a l F ile s \2
A m e s L a b M
D M a g n e t
T e s tb e d
E L E
C b rh o d e s V
G U
Y B
.r v t
22066
ISSUE FOR BID
M D
M A
G N
E T
T E
S T
B E
D
05.05.2023
LEVEL 1 -
TELECOM
AND
SECURITY
FLOOR PLAN
M E
T A
L S
D E
V E
L O
P M
E N
T B
L D
G
P
A M
M E
L D
R A
M E
S
IA
A M
E S
L A
B R
A T
O R
Y
T-1011/8" = 1'-0"1 LEVEL 1
1/4" = 1'-0"2 BASEMENT KEY PLAN
KEYED NOTES
1 TERMINATE NEW DATA OUTLETS SHOWN IN
160A TO RJ45 PANELS IN THIS LOCATION.
COORDINATE WITH OWNER FOR JACK
LABELING REQUIREMENTS.
2 OWNER PROVIDED CORE DRILL AND CONDUIT
SLEEVE WITH GROUNDING BUSHING AT +100"
AFF (MINIMUM) AND BELOW 140" AFF.
3 OWNER INSTALLED DATA CABLING.
CONTRACTOR TO TERMINATE AND TEST (TYP).
4 6" X 2" WIRE BASKET CABLE TRAY MOUNTED
AT BOTTOM OF SUPPORTS PROVIDED FOR
MECHANICAL PIPING AND CONDUITS IN THIS
AREA. APPROX 12'0" AFF. COORDINATE WITH
OTHER TRADES. AVOID CONFLICTS WITH
EXISTING OVERHEAD CRANE AND OTHER
EXISTING UTILITIES.
5 LOCKS, CARD READER, DOOR POSITION
SWITCHES, AND REQUEST TO EXIT DEVICE
WIRING TO SPARE PORT ON EXISTING DOOR
CONTROLLER IN ROOM 157. PROVIDE POWER
SUPPLIES AS REQUIRED. CARD READER TO
BE SOFTWARE HOUSE MODEL SWH-5100.
VERIFY PART NUMBERS AND COORDINATE
PROGRAMMING AND STARTUP WITH OWNER'S
SECURITY VENDOR (PER MAR SECURITY).
SYSTEM JUNCTION BOXES TO BE LOCATED IN
ROOM 160A (SECURE) SIDE, NOT LOCATED IN
CORRIDOR.
1 ADD #03 05/30/2023
DATA CABLES FROM ROOOM 160A WILL
TERMINATE AT OWNER’S RACK IN THIS
LOCATION.
FURNISH (2) CABLES TO EACH DATA OUTLET UNLESS
OTHERWISE INIDCATED ON DRAWINGS. OWNER TO
INSTALL, TEST, AND TERMINATE ALL CABLES.
OWNER TO INSTALL, TERMINATE, AND TEST
CABLES FURNISHED BY CONTRACTOR. (TYP)
| 1. 00 74 13 – PROJECT REQUIREMENTS |
| 1.1 Add Section. |
| 2. 01 10 00 – SUMMARY |
| “1.2 WORK BY OWNER |
| a All work included in this section will be performed by Owner. Refer to Section 00 74 13 – Project Requirements.” |