RFP950600-02 - DOC MPCF Perimeter Fence & Wagon Replacement.pdf
PDF 2 MB Posted
- Solicitation number
- RFP950600-02
- Issued by
- Harrison County, Iowa
About this file
This is a Request for Proposals (RFP) issued by the Iowa Department of Administrative Services (DAS) seeking professional design services for the replacement of the perimeter fence and wagon gate at the Mt. Pleasant Correctional Facility in Mt. Pleasant, Iowa. The scope of work encompasses design of a new secure perimeter fence system, associated vehicle and pedestrian gates, replacement of inner fence security wire, security enhancements, site grading, utilities evaluation, structural assessment, and removal and replacement of existing rocks between inner and outer security fences with concrete. The design must maintain continuous secure perimeter operations throughout construction, with minimum requirements including one barrier (fence) at all times and two operational barriers for the wagon gate. The RFP was issued January 28, 2026, with a non-mandatory pre-proposal conference scheduled for February 4, 2026, at 9:00 AM at the facility or via Microsoft Teams. Questions and requests for clarification were due February 13, 2026, at 3:00 PM, and proposals were due February 27, 2026, at 2:00 PM via the Iowa IMPACS electronic procurement system. The selected firm must commence work the week of March 2, 2026, with design kick-off the week of March 9, 2026, and deliver 100% design development documents, 50% construction documents, 95% construction documents, and final 100% construction documents by June 1, 2026. The contract includes a minimum of ten required site visits spanning design kick-off, design review meetings at 100%, 50%, and 95% design stages, pre-bid meeting, pre-construction meeting, two construction field observations, substantial completion and punch list development, final completion approval, and one-year warranty correction period visit. Construction bidding is anticipated June to July 2026, with contractor contract execution in July 2026 and construction execution from July 2026 through August 2027, followed by closeout April to May 2027.
The State requests lump sum pricing inclusive of all reimbursables such as printing, mileage, and travel expenses, with fees broken down into four categories for schedule of values billing: Design Development Documents, Construction Documents, Bidding or Negotiation Assistance, and Construction Phase services. Additionally, proposers must provide a unit price per construction inspection visit that will be additive or deductive based on actual visits exceeding the required ten. No specific budget amount is disclosed in the RFP. The selected design firm must be registered with the Iowa Secretary of State, maintain professional liability insurance of $2 million, and employ at least one licensed engineer, architect, or landscape architect in compliance with Iowa Code Chapter 26. The design must integrate with existing security systems including SafeGuard Technologies fence and taut wire system, Genetec camera system, and Creative Technologies door control system currently operational at the facility. A critical restriction prohibits the selected design firm or any of its consultants from being eligible to receive an award for the subsequent construction services contract, ensuring separation of design and construction contracts. No set-aside designations for disadvantaged enterprises, no incumbent contractors, and no current contractors are identified. The firm must demonstrate staff qualifications and experience with similar projects completed within the last five years, organizational stability, financial strength, and proposed approach alignment with the State's schedule and budget constraints.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFP950600-02 - Addendum 01.pdf | ||
| RFP950600-02 - DOC MPCF Perimeter Fence & Wagon Replacement.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFP COVER SHEET
Administrative Information
STATE OF IOWA
REQUEST FOR PROPOSALS
PROFESSIONAL DESIGN SERVICES
RFP Number RFP950600-02 Title of RFP DOC MPCF Perimeter Fence and Wagon Gate
Replacement
Agency Iowa Department of Administrative Services (DAS)
Project
Description
The State of Iowa Department of Administrative Services (DAS) is seeking professional design services for the creation of construction documents for the replacement of the perimeter fence & wagon gate at the Mt. Pleasant Correctional Facility.
State Issuing Officer:
Michael Bradbury
Issuing Officer
Iowa Department of Administrative Services
Hoover State Office Building, Level 3
1305 East Walnut, Des Moines, IA 50319-0105 Phone: 515-823-9327
Email: construction.procurement@iowa.gov
PROCUREMENT TIMETABLE—Event or Action Date/Time (Central Time)
State Posts Notice of RFP on TSB website 1/26/2026
State Issues RFP 1/28/2026
Pre-Proposal Conference Location and Address:
Is Pre-Proposal Conference mandatory? No
If a map is needed, contact the Issuing Officer.
2/4/26 @ 9:00 AM at MPCF at 1200 E Washington Street, Mt.
Pleasant, IA 52641 or on Microsoft Teams below..
MEETING LINK
Meeting ID: 268 550 901 672 20
Passcode: mL6wq7Wj
Questions, requests for clarification, and suggested changes from Respondents due to Construction Procurement
2/13/26 @ 3:00 PM
Proposals Due 2/27/26 @ 2:00 PM
Relevant Websites
Website where Addenda to this RFP will be posted http://bidopportunities.iowa.gov
Website where contract terms and conditions are posted https://das.iowa.gov/sites/default/files/procurement/pdf/ConsensusDoc803.pdf
Number of Copies of Proposals Required to be Submitted: 1 Digital
Firm Proposal Terms
The minimum number of days following the deadline for submitting Proposals that the firm guarantees all proposal terms, including price, will remain firm is 120 Days.
mailto:construction.procurement@iowa.gov https://teams.microsoft.com/l/meetup-join/19%3ameeting_MThiZDA3OTYtMDg0Ni00YWVlLWIwZjMtZDQ3MTE5M2E2NTJl%40thread.v2/0?context=%7b%22Tid%22%3a%22c6c429d4-d18c-4ab8-a9a8-f0c82d33f945%22%2c%22Oid%22%3a%22f2a0c006-1634-486a-9b85-1de9fc05f08e%22%7d http://bidopportunities.iowa.gov/ https://das.iowa.gov/sites/default/files/procurement/pdf/ConsensusDoc803.pdf
1.1 INTRODUCTION
The Iowa Department of Administrative Services (DAS) is seeking proposals from qualified and available Design companies for services, per RFP cover page, and as outlined in the following
(Sections 1.2 - 1.3). The successful proposal must:
● For the staff that will be assigned, identify and describe qualifications, experience, and expertise in providing services for similar, or relevant, projects.
● For the staff that will be assigned, provide a list of past similar or relevant projects completed in the last 5 years, and include brief descriptions of what the projects entailed and a contact name and phone number (reference). In addition provide estimated project cost, final project cost at acceptance, and whether it was completed on time.
● Describe the composition of your team. Identify staff to be assigned. Provide resumes of key individual(s) including education, relevant experience, and certifications/licensing.
NOTE: Any responding company and/or consultant that is part of the project design services cannot receive an award from the resulting request for bid of construction services.
● Describe the cost estimating, status reporting, and cost reporting procedures you utilize.
● Describe computer program/software capabilities and expertise you utilize. Please describe your experience.
● Provide a copy of your organizational chart.
● Describe your experience, if any, on designing similar or relevant projects for the State of
Iowa.
● Provide the hourly rates, and anticipated hours by position, for all persons (including sub-consultants) that will be assigned to the project. Also provide an estimated fee total.
● Identify desired reimbursable charges (the State has limitations, per State of Iowa Accounting
Policies and Procedures 210.245), and all other charges.
1.2 SCHEDULE
DAS is seeking a firm that can commence work upon execution of a contract. Time is of the essence.
Execution of Designer’s Contract Week of March 2nd, 2026
Tentative Design Kick-Off Meeting Week of March 9th, 2026
100% Design Development Documents and Cost Opinion By Design professional to propose in RFP schedule
50% Construction Documents and Cost Opinion By Design professional to propose in RFP schedule
95% Construction Documents and Cost Opinion By Design professional to propose in RFP schedule
100% Construction Documents and Cost Opinion By June 1st, 2026
Contractor Bidding June to July 2026
Execution of Contractor’s Contract(s) July 2026
Submittals, Procurement and Construction July 2026 to August 2027
Closeout April 2027 to May 2027
1.3 PROJECT DESCRIPTION
Construction Manager (McGough Construction) has been engaged for this Project to serve as advisor to DAS and to provide assistance in administrating the Contract for Design between DAS and the Designer according to separate contract between DAS and Construction Manager. DAS is currently seeking design services from qualified firms for a project consisting of the designing the replacement of the secure perimeter fence system, associated vehicle and pedestrian gates, any required security enhancements.
Design services shall include:
1.3.1 The contract for this work will be a modified ConsensusDoc 803. See link on cover page for a sample contract.
1.3.2 All design disciplines necessary to complete the scope of work.
1.3.3 Attend design kick-off meeting onsite to discuss desired outcome of the project with the
Owner, Construction Manager, and Owner’s maintenance staff.
1.3.4 Use of the State of Iowa‘s construction management software program for uploading all documents, submitting and approving pay apps, and construction administration. The cost for the use of the software is paid by the Owner.
1.3.5 The following design services will be needed:
1.3.5.1 This project will include the design of a new secure perimeter fence system, associated vehicle and pedestrian gates, replacement of the inner fence security wire, and any required security enhancements. The design will also address site grading, utilities, and structural needs associated with the fence replacement. The design would also include removing existing rocks in between the inner & outer security fences and replacing with concrete. Design to also include operational considerations for maintaining a continuous secure perimeter throughout construction.
1.3.5.1.1 The minimum requirements for maintaining a continuous secure perimeter include one barrier (fence) required at all times, and the wagon gate to have two operational barriers at all times. These requirements will be coordinated with the owner.
1.3.5.2 The selected design team will be responsible for evaluating existing conditions, recommending appropriate fence and security technologies, developing phased construction strategies compatible with facility operations, and preparing complete construction documents suitable for public bidding. Coordination with
Iowa DOC security and MPCF staff is a critical project component, and all design activities must comply with applicable state, departmental, and correctional security standards.
1.3.5.3 The existing security fence and taut wire was designed by SafeGuard
Technologies which integrates with the facilities camera system of Genetec. The door control system at the facility is Creative Technologies. The expectation is to have all new systems integrate with existing systems.
1.3.5.4 Existing PDF drawings will be provided to the successful design firm. Accuracy of drawings shall be verified by the design firm.
1.3.6 Field examination of the existing buildings.
1.3.7 Design for scope of work. Provide material recommendations based on experience, quality, and price. Recommendations for replacements and upgrades shall include non-proprietary equipment and systems.
1.3.8 Designer shall include any and all survey work required for completion of project.
1.3.9 Coordinate with State agencies to confirm utilities that may be abandoned as well as shut down requirements where required.
1.3.10 Provide detailed input of design schedule to Construction Manager for overall incorporation into master schedule.
1.3.11 Designer shall assist Construction Manager in the evaluation of long lead times.
1.3.12 Quality control during Design, Preconstruction and Construction.
1.3.13 Compliance with all Federal, State, and applicable AHJ codes.
1.3.14 Completion of State building and energy code documents, as required.
1.3.15 Design review will be conducted at 100% design development documents, 50% construction documents, and 95% construction documents. Dates for design review meetings to be coordinated with the design and project team and set no later than the design kickoff meeting. Review will be conducted with DAS Owner Representative, Construction Manager, and Facility Representative, at a minimum. Drawings, specifications and cost opinions (if applicable) shall be provided at least five days prior to each review meeting. An additional review meeting may be required at the end if there are discrepancies in cost opinions or constructability review questions.
1.3.16 Review with the Department of Inspections, Appeals, and Licensing’s Building Code
Bureau for approval of plans or exemption from review. All fees associated with the
Bureau are the responsibility of the designer.
1.3.17 Develop and distribute agendas and meeting minutes for all meetings during the design phase.
1.3.18 Construction cost opinions provided by the Design Professional team during Design (at
100% design development documents, 50% construction documents, and 95% construction documents) with a Final Estimate for construction included with bid documents, per Iowa Code.
1.3.19 Construction drawings, specifications (the Construction Manager will produce Divisions
00 and 01), and addenda.
1.3.20 Provide bid alternates as determined during the course of design and bid package development.
1.3.21 Assist Owner and Construction Manager in obtaining bids from qualified contractors.
1.3.22 Construction administration, including creation of the submittal and closeout items log, review of and responses to submittals and closeout documentation, RFIs, proposal requests, change orders, pay applications, periodic site visits, attendance at project meetings as required, participation / development of contractor punch list, closeout documentation review and approval, certificates of substantial completion, and certificates of final completion, as well as development of Architectural Supplemental
Instructions for design revisions, and punch lists within the construction management software program.
1.3.23 Participation with project team during construction progress meetings as required.
Designer shall participate in bi-weekly conference calls during the construction period.
1.3.24 Field Observation reports, with photos, submitted for each site inspection within five (5) days of the site visit.
1.3.25 Acknowledgement that all documents are copyright to the State of Iowa and shall be turned over to the State of Iowa in their native computer format. Any ASIs/RFIs/PRs and addendums will be expected to be incorporated before final posting. Both the native computer format and PDF versions shall be uploaded to the construction management software program at the end of the project.
1.3.26 The Department requests lump sum pricing from the respondents to this RFP, with the lump sum base scope price being inclusive of all reimbursables, such as printing, mileage and travel expenses. The Department requests the fee proposal from the respondents to this RFP be broken down as follows. These breakdown prices will be used as the schedule of values for billing purposes.
1.3.26.1 Design Development Documents
1.3.26.2 Construction Documents
1.3.26.3 Bidding or Negotiation Assistance
1.3.26.4 Construction Phase
Include at a minimum, ten (10) site visits. Design kick off/Building evaluation, 100% design development document review meeting, 50% document review, Pre-bid meeting, Pre-construction kickoff, Construction Field Observation (2), Substantial completion/punch list development, Punch list/Final Completion approval, and one year warranty correction period visit. Design Review at 95% construction document development will be conducted via conference call. Beyond these site visits, each proposing firm shall provide additional visits as they see fit to complete the work of design. In addition to the lump sum pricing, the Department requests a unit price per construction inspection visit. This unit price will be additive or deductive based on the number of actual visits made.
1.4 ATTACHMENTS
1.4.1 Exhibit A for photos of existing security fence.
1.4.2 Exhibit B for existing drawings of the security fence
Exhibit A
State of Iowa - Department of Administrative Services
Printed on Fri Dec 5, 2025 at 10:54 am CST
Job #: 9506.00 DOC MPCF Perimeter Fence and Wagon Gate Replacement
1200 East Washington
Mount Pleasant, Iowa 52641
Photos From Daily Log
Description
Taken Date
12/12/2024 at 11:29 am
Upload Date
12/05/2025 at 10:46 am
Uploaded By
Brandon Adams
File Name
IMG_1187.JPG
Exhibit A
Job #: 9506.00 DOC MPCF Perimeter Fence and Wagon Gate Replacement
07/10/2024 at 12:20 pm
12/05/2025 at 10:50 am
IMG_1065.JPG
Job #: 9506.00 DOC MPCF Perimeter Fence and Wagon Gate Replacement
07/10/2024 at 12:20 pm
IMG_1064.JPG
Job #: 9506.00 DOC MPCF Perimeter Fence and Wagon Gate Replacement
07/10/2024 at 12:05 pm
IMG_1058.JPG
MA[N DU[LDING
\./EST \./ING
SEE
I , 1 --------------- t--t p
Exhibit B
NE\./ 6 5/8'
END ANCHOR
POST
-----=ZON320-'17 -------------------------------------------------- ,
1- -
CABLE
(SEE DETA[L3, D\./G 02)
(SEE DETA1L3,
D\./G 02>
TEMPORARY
S\./INGING GATE
TO BE CLOSED
\./ITH TAUTE \./IRE
TEMPORARY
EXISTING
f-ENCE l -' - - --+--Z □1N5E2- ' 2 ---------------------- , (SEE DETAfL3, D\./G 02)
NOTES:
!. VER[FY MEASUREMENTS IN THE FIELD.
2. CHECK FDR EXISTING UTILIT[ES IN THE FIELD.
3. REMOVE EX[STING GATE. REPLACE \./!TH CHA[N L[NK
TD MATCH EXISTING. REPLACE AND MODIFY EXISTING END
POST TD ACCOMMODATE THE TAUT \./IRE SYSTEM.
4. PROVIDE ANCHOR POSTS TD ACCOMMODATE CHANGE OF flEIGHT
AT EXISTING CONCRETE PLATFORM.
5. INSTALL RAZOR TAPE 30' ABOVE THE TAUT \./IRE SYSTEM.
120'
SP17-2
2 3/8' OD
EXISTING
4' OD
SP! 7-3
SPIB-1
130'
Z□NE- 18
260'
SEE NOTES 6
SEE NOTE 3
140'
3DD
SP2-l
6. EXTEND FENCE TD MATCH EX[STING. INSTALL TAUT \./IRE ON NE\./
FENCE SECTION.
7. MODIFY PER D\./G 2, DETAIL !A. PROVIDE MATERIAL AS REQUIRED.
8. REMOVE THE EXISTING BOTTOM RAZOR TAPE ON THE INNER FENCE
TD THE TOP OF THE INNER FENCE. INSTALL PER INDUSTRY STANDARDS.
ADD NE\./ RAZOR TAPE IF REQUIRED.
112'
L ----- EXISTING
LONG CABLE
TO VERY CORNER
OF OUTER FENCE
<SEE DETA[L3, D\./G 02)
SP16-3
SP18-2
CONTROL
ROOM
127'
ZONE-I
26 7'
ZONE-3
168'
9. THE LASER GUARD SENSOR AT Z□NE- 19 SHALL COVER THE ENTIRE ROOF
\./ITH EMPHASIS TD\./ARDS THE MAIN/ADMINISTRATION BUILDING.
10. INTEGRATE EXISTING PTZ CCTV CAMERA \./ITH THE PSS FDR
AUTOMATIC CALL UP.
DOUBLE S\./ING GATE
NOTE 7
SEE NOTE 10
DOUBLE S\./ING GATE
SEE NOTE 7
LEGEND:
Z□NE- 2 2
48'
MAfN BU[LD[NG
EAST UNITS
CABLE <SEE DETA[L3,
- END ANCHOR POST
o- INLJNE ANCHOR POST
0 - SENSOR POST
24' D\./G 02> ◄---► _ [NF RA RED/MICRO\./ AVE SYSTEM
ZONE -16
352'
SP16-2
Z□NE- 19
<SEE NOTE 9)
"--1---ZONE-2
TRANSMITTER
AND ANTENA
\./ILL BE MOUNTED
ZONE-21
SEE D\./G 03
DETAIL 1
SP4-l 131'
ZONE-4
251'
BIi - CORNER ANCHOR POST \./ITH
OVERLAPPING OUTRIGGER
@ - □Ul R JGGER END ANCHOR POST
© - OUTRIGGER INL!NE ANCHOR POST
®) - □UT R[ GGER SENSOR POST
(@- OUl RIGGER ROLLER POST
SP16-1
SP15-2
4 FT HIGH NUISANCE FENCE/BARRIER
EXISTING LIGHT
POST \./!LL BE
REMOVED
(BY OTHER>
ON THE BLDG
ZONE -10----j,I --- I
IR/M\./
MOTORIZED
SLIDING
GATE
SENSOR COIL
SEt D\./G 2, DETAIL 2
THIS 2 3/8' POST
NEED TO BE CHANGED
FOR 4' OD POST
DOUBLE S\./ING
GATE
SP4-2
SP5-l
!2U'
Z□NE- 5
205'
<J---!l> - INFRA RED/ MJCR□'w'A VE SYSlEM
COLUMN \./ITH DOPPLER
- 4 FT HIGH NUISANCE FENCE/BARRIER
- EXISTING CHAIN LINK FENCE
- EXISTING CHAINLINK FENCE \./ITH
THE TAUT \./IRE SYSTEM.
mtttt1tt+tttt- - \./ALL MOUNTED OUTRIGGER TAUT
\./IRE FE_NCE
NVv'N./\ - SENSOR COIL 030'
EXISTING PTZ CCTV CAMERA
EXISTING STATIONARY CCTV CAMERA
- LASER GUARD SENSOR DUAL BEAM
\./ITH PTZ CCTV CAMERA
ZONE-15
190'
3" OD
3' OD
INSTALL RAZOR
MESH FENCE
MAN
GATE Z□NE- 8
34'
SPB-1
ZONE-9
IR/M\./
4 FT HIGH NUISANCE FENCE/BARRIER
4' DD
EXISTING, ------
SP5-2
SP!5-l POST
SP14-2 SP14-1
ZONE -11
80'
SP6-2 SP6-1
70' lf.-----120' -----1------ 140' --------- f--I
CD
----._1 CABLE
<SEE DETAIL3, D\./G 02)
(SEE DETAIL3, D\./G 02) , ZONE -14 -+ ----- I , ZONE-7 ZONE-6
NE\./ 6 5/8'
END ANCHOR
POST
260'
SEE NOTE
_ZONE-13
I
80'
EXISTING MAN
4, 150'
THIS POST NEED TD BE
REPLASED BY 6 5/8 POST
320'
SEE DETAIL 2 D\./G.03
-- ------------. --------------------- DE-SIG-NED-BY-•
r
-- ---- --------------------,-----------------,----------18 This ciocuMent canto.ins JOB\SQ NO :::,;::
SCALE
l--l---f--------------1-+---I inforrio.tion to So.feguo.rds Technology Inc. Any disclosures
DRA\JN BY,
MOUNT PLEASANT CORRECTIONAL
FACILITY, IOWA
PERIMETER SECURITY
DRA\JING NO O1 p orus of this inforMo. tion or o.ny f---=-f. M-Y_S_H_A_N_-l ------- , <----= ----- l U'\
O' 25' 50 75' 100' 4 8-26-02 ADDED CABLE OP. IM reproduction of this ciocur1ent CHECKED BY, f--------, -------------------- 1 3 8-10-02 CHANGED ZDNE-21, ADDED z□NE- 22 O.P. I.M. for other tho,n the specific M. FEINSTEIN _A, SYSTEM (PSS) REV SHEET NO. ::, f----+--+-------------1-----+--, purposes for which it is intended 1-------->--------<,,. . , f-2---+ 4_- _2,_-0_2+- _ c H_A_N_GE oz_□_NE_ -_2_1_,A_□DE_ □_ _z _□N_ E - 22_ -l-1-.-M-.-+- -, is expressly prohibited except os APPROVED BY•
SAFEGUARDS TECHNOLOGY, INC.
75 Atlantic Street LAYOUT f-----'--------1
I 12-24-01 CHANGED LOCATION !RIM\./ D,P. BK SoJeguo.rds Technology Inc. MOY 1-------1-----...j otherwise o.gree in writing. DATE• Tel
REV DATE DESCRIPTION BY APP. 12-02-01
Hockensock, New Jersey 07601
(201) 488-1022 Fox (201) 488-1244
SCALE, <
C
BASl<ETBALL
COURT
s
- - 105 ' ----1- ---95' ----1
VEHICLE
GATE
OPPER CONDUCTOR
#tt8-26-14C
COPP£!! CONOIJCTOR
TO POST fH8-20-14C
G!<OVNO 1100
CONNECIOR
#UB-2<H;C
GROUND RO□ &. CONtiECDON
EXISTING FfNCE POST
BONDING LUG
fH8-58XL -
COPPER
CONDUCTOR
IHB-28-14C
GRADE
SENSOR POST
2'-0" MIN
BY-PASS 1/(K'"-.J_
CONN[ClO _ 2·- • MIN fH8-206C
BONDING LUG EOR SEtlSOR F'OST
COPPER GROUND LOOP
fHB-28-14C
-3/4"d0'-Q" COPPER WELD
GROUND ROD IHB-107GR
SENSOR POST GROUNDING DETAIL
FENCE GROUNDING DETAILS
This docur1ent contains inforr10.tion to So.feguo.rds
DESIGNED BY,
JOB\SQ NO
DRA\JING NO
r n
--l 7J
Technology Inc. Any disclosures DRA'w'N BY, 1--+---j-----------------,-,--,or softhis inf'orr10.tion or ony 1-==;,I.:,-M::,Y.,..:.S_H_A.N..
reproduction of this docur1ent CHECKED BY·
+-------- FACILITY IOWA DETAILS
p"' p '"
3 08/26/02
2 08/10/02
REMOVED DETAIL 1
CHANCHED DETAIL IA
for other tho.n the specific OP, l M, purposes for which it is intended □.P. J.M. Is expressty prohibited except o.s
M. FEINSTEIN
APPROVED BY,
SAFEGUARDS TECHNOLOGY, INC.
75 Atlantic Street
SHEET 1
REV
SHEET NO ::;
l> / to l- - t- - - -t - - - - - - - - - - - - - - - - - -r- M- , - - 7 So. f' eguo.rds Technology Inc. r10. y
REV
04/24/02
DATE
CHANCHED DETAIL I AND ADDED DETAIL IA 1
DESCRI PTI□N BY
APP.
otherwise ogree in writing. DATE, 12-02-01
Hackensack, New Jersey 07601
(201) 4B8-1022 Fa, (201) 488-1244
SCALE•
NTS 0""
CD
l
CIFl'.t:11 POST
J!
[)(JSfM;
UH< POU
--f-s 314'
7FT.- RAZOR MESH
200nr1xi00MM
CHAIN LINK
c□Nl ROL FENCE
EXISTING
3' OD
----20 rv----
, n
FENCE POST
TAUT \./IRE SYSTEM
NE\./ 30' RAZOR TAPE
EXISTING
RAZOR TAP[
NfRARED
CLUS"'
D i ----------------------
'" CLUS TEe INfRA s· I"'-i_i
'"-C 1:itl
D F.=
LEAST 4 INCHES
DISTANCE BET'w'EEN TAUT \./IRES
AND THE CHAIN LJNK SHOULD BE AT
LJNK FENCE AS MUCH AS POSSIBLE
3.
0111...-.
cmrncn:
/m,"""
MAINTAIN INTEGRITY or THE CHAIN
MANUFACTURERS RECOMMENDATIONS
AND ATTACHMENT.
rtlC!I""
THE FENCE POSTS ACCORDING TD
ATTACH TAUT 'w'IRE
ON ALL DRA'w'INGS.
2 SYSTEM TO
' l ' L
<!YPIC'-.>
"' !kif"""'"'
.., UIU!ER ANCHOR P□ST
StNS!I! P□SI t STlllG
C II[ 1[
r TJ G
SENSOR COIL WALL MOUNTED BRACKET
.30" SENSOR COIL
S>----BARBED WIRE
BUILDING
NOT[,
I. INSTALL SENSOR COIL BRACKETS EVERY IO FT.
DETAIL 2 DETAIL 1A
NOTES
I. VERIFY MEASUREMENTS AND LOCATION
IN THE FIELD.
2. MODIFY EXISTING CONTROL FENCE
3. RELOCATE END CONTROL FENCE
POST SO THAT IT IS INSTALLED 4
INCHES FROM THE TAUT \./IRE SYSTEM.
4. NE\./ RAZOR TAPE (30') ON BOTH SIDES.
"ABSOLUTE"
DUAL TECHNOLOGY OUTDOOR BARRIER
(I.R./M,V.)
NOTE,
* - ZONES -9,10 - \./ITH DOPPLER,
ZONE-12 - \./IT H□UT DOPPLER
-- 10 1/4' 1---i-10 1/4'
,.DOPPLER
HICROYAV[
MI
INrRARED
CLUSTER
s·
SECTl□N A-A
D
17"f
D
D
D
[!j
L OGIC
BOARD
IMfRARED
CLUST[R
RX TX
4 THE INSTALLER IS RESPONSIBLE TO
VERIFY FOUNDATION SIZE FOR NE\J
POSTS AND INSTALL ACCDRDINGL Y.
S. THE EXISTING RAZOR TAPE IS NOT SHD\JN.
REMOVE THE EXISTING RAZOR TAP[ FROM
THE INNER FENCE AND REPLACE \JITH
NE\J 30' COIL
SENSCR POST
TAUT IRE SYSTEM DETAILS
FDR 'EXISTING FENCE' ZONES
SLIOCR POST
l
IWIOTl<>ll '1.txlkt l<CTA<.- Cll<OUIT
I. EXISTING CHAINLlNK NOT SHO'w'N l l t
[Xllf!Nj
C""l"'--H.«:t: ,l,X.,1!l,l.l_N1G,-, rrncc nmJ1tG _rtNCc ""'" tXIS11NG -r[>tC[ l'OIT
I • !ki ]OU<<H ,,u.r,c•
SCCIJ[)f C-C
1€11 .. AC[
DETAIL 3
1,t'.V '!)[AO' BIIACt
SUOCII
SLIOCII
POST 7'-6'
<21 ROPC
CLIP
THIHDL[
1,t'.V OOTIIIGGt:IIS J!
HE BIJLT
r<
FENCE GROUNDING LEGEND
COPPER GROUND LOOP CONDUCTOR
,H8-28-!4C
CORROSION RESISTANT BONDING COG
fHB- BXC
BY-PASS CQNN(CTOR )GROUND
LOOP TO GROUND ROD i!IH8-206C
::!,/-4's10'-0" COPPER WELD GROUND ROO !l'HB-107GR
NOTE
INST/I.LL COPPER GROUND LOOP CONDUCTOR
AROUND ENTIRE TAUT WIRE FENCE PERlt.AElER
'SENSOR POST TO THE ALUMINUM CHANNEL
CONUECT GROUND ROO MIO CABLE AT CH
HOUSINC
CONNECT CROUNO ROO ANO CABLE " CH
MICROWAVE POST
• CONNECT GROUND ROD ANO CABLE CH
CORNER POST OF THE TAUT WIRE FENCE "
INSTALL PER rEDERAL ANO LOCAL CODE
• CROUNOINC CABLE LOOP TO BE MlOV£ GROUtlO FOIi EmX,ISTING f[NCE SECTIONS ANO BELOW C/IOUtlO
-STANO ALONE" SECTIONS
- ,::,a -
PTZ
..j..□:::::.-:P.·+ '::·:.":·:_ -J is expressly prohibited except 05 APPROVED BYi I ' l
BUILDING
'w!ND□'w
OUTRIGGER ANCHOR POST
CLOCK LGS SYSTEM
CONTROL MON1TOR
\./ALL MOUNTED
SITE MAP
8'
ANCH□R-J
19" RACK
CCC ACCESSORIES.
TYPICAL TAUT VIRE SENSOR
VIRE ATTACHMENT DETAIL
COMPUTERIZED
CONTROL
CENTER CCCCl
ANTO,INA
120V
60 Hz
PO'w'ER
SUPPLY
TRANS-
MITTER
L-1
CCC
EYBOARD
:R[NT[:
FROM SENSORS
LASER GUARD
CAMERAS 1 " " " N s
VIOCO
MONITOR
VlllEO MOtHTOR
CCTV
NOTES,
1. THE VIDEO MONITORS ARE EXISTING.
2. THE SYSTEM SHALL HAVE A CAPABILITY TO UTILIZE EXISTING PTZ CAMERAS FOR ALARM RECALL.
PERIMETER SECURITY SYSTEM CPSS) CONNECTION DIAGRAM
N.T.S.
r-r--T----------------,--,---,-----------------..:;::::
D
E
SIG
NE
D
B Y• :;::::-:-::----,------,,--------------------------r--------------------,_JO
B\
SQ
N O -------...,:sl: This docuMent canto.ins intorMo.tion to So.teguords Technology Inc. Any disclosures
DRA'wN BY•
MOUNT PLEASANT FACILITY, CORRECTIONAL IOWA DRA \./ING NO. 03
:::C:
p"' or se tthis intor Mo. tion or ony 1---'l_. ..:M_Yc_S.:.:...HA'-N'--11 ------------ 1 DETAILS 1 ------------- 1"p' l- -'3'- IO-'B- /..2: :.:6.=:.i/-.:-.0- A.:D: ..:::ED::D..cM...:.N:...G:..:.A:.T:E:._T..:□:...D:::E.:.TAc.I::L:...:
PSS SYSTEM
KEYBOARD
ZONE 13-1 ZONE 14-1
, TYPICAL TENSIDN
BOTTOM \./IRE
120 lbs. +/- lllb. '
TELEPHONE
WINDOW
OR
I EXTENDED SENSOR COIL DD\./N TD THE TAUT \./IRE
SYSl EM □N THE FENCE AND OVERLAP.
NOTE,
TRANS-
MITTER
INTER
rACE
NOTES,
I. THE UPS \./ILL BE LOCATED IN THE CORNER UNDER
THE CLOCK, (NOT SHD\./N).
2. MOUNT THE LGS SYSl EM MONITOR TD THE CEILING
ABOVE THE CCC MONITOR.
3. LOCATE PRINTER ADJACENT TD THE UPS. (NOT SHO\./N).
CONTROL ROOM
N.T.S
DETAIL 2
NOTE,
A - TD BE VERIFY ON SITE
2 A ff ACH FENCE POSTS TD THE \./ALLS.
"G'A"lE
DETAIL 1
NE>
ANCHOR POST
(SEE NOTE 6 D\JGOI)
------- ZONE 18-2
OUTRIGGER SLIDER POST
- DUTPIGGER ROLLER POST
OUTRIGGER SENSOR POST
SP22 1
OUTRIGGER ANCHOR POST
OUTRIGGER SLIDER POST
1-2=-fO..:B..:/l::0..:/0..:2+ ..:A..:D:.:D..:E..:D.....::DE::.T..:A.::1.:.L..:2::...
I 6
SENSOR
MOUSE
□"J
□w
LGS
COHROL
l--l ---+ -----------------1-- 1- --1 l
7 ' 7 I /
I 7 I /
7 7· I /
I ' ' / 'l " .
; I
I
75 Atlantic Street /
1----' ------- lto
-l .□::.:.-P1 ..:'.:."-.:.· reproduction ot this docuMent purfporoseosthfeorr thwohnich thite isspienctiefnicded
CHECKED BY,
M. FEINSTEIN
.,A
SAFEGUARDS
TECHNOLOGY, INC.
SHEET 2
REV
SHEET NO.
12/24/02 ADDED CONTROL ROOM OP. BK. Sofeguords Technology Inc. no.y otherwise o.gree in writing
REV DATE DESCRIPTION BY APP.
1----------1-------1
DATE=
01-14-02 Tel
Hackensack, New Jersey 07601
(201) 488-1022 Fox (201) 488-1244
SCALE• cJ ru
I , I
POST
SLIDER
3.5'
T YPICAL
s PACING
---LGS KEYBOARD
L-------1 ---- KEYBOARO SHELF
LGS MOUSE
WINDOW
EXISTING CONTROL
CONSOLE
8'
'- ,I
'I
V
SUDER _/
POST
SPOSTIDE
POSTLI+A 7
TAUT
\./IRE\
OUTRIGGER
ANCHOR
POST+ A
OUTRIGGER
TAUT \.I IRE
SENSOR
TYPICAL TENSIDN
TOP \./IRE
77 lbs. +/- 11 lb.
-SENSOR LEADS
i\rrn, l-
-26
-0 c
A
D
DE
D
D
IS
T
A
NC
E
P
EIV
E
E tl
.IIR
E
S
P
M
..----1 Is expressly prohibited exc<2pt OS APPROVED BY, # ,, 75 AHonhc Slr e!
I I
GALVANIZED ANGLE IRON
l- l/2'*1-l/2':.:3/16'
\JALL
I,---
OD. SCH40 PIPE 3' OD. SCH40 PIPE
8'
END CAP
4• 5/8' HOLE
GALVANIZED PLATE
-- l/4' 5/8' HOLE
CSET 3/4' FROM
ALL EDGES)
, G ALVANIZED PLATE
12'*10':«l/4'
I I I I I I
OUTRIGGER END ANCHOR POST. CARRYING STRUCTURE
I I " I I ) " )J,, )
\JALL
1--r---, 3' OD. SCH40 PIPE
ND CAP
ROLLER OUTRIGGER 0
3'0Dx67' GALV. PIPE
\./ITH DOME CAP
'"-.L.-' -- CAAIRBCLERAFT
A 4 8'
68'
- - 1/4'
GAL VAN!ZED ANGLE IRON
1- l/2'*1-1/2':.:J/16'
4,8'
6.8' 0
4 8'
6.8'
3' OD. SCH40 PIPE
8'
4• 5/8' HOLE
0 0
BRACES NOT SHDVN
4,8'
6 8'
4.8'
LASER GUARD
10'*8'*1/4'
5/8' HOLE
(SET 3/4" FROM
ALL EDGES)
12'*10'*1/4'
OUTRIGGER ROLLER POST. CARRYING STRUCTURE
GALVANIZED ANGLE !RON
1- 1/2'*1-1/2'*3/16'
POST BRACING
I l/2'•1 1/2'•1/8'
ANGLE IRON (TYP) -
<FINISH• PRIMED
3' OD I 1/2'•1 1/2'•1/8'
@.PAINTED)
DUlRIGGER ANGLE IRON (TYP) r
-END ANCHOR (FINISH PRIMED
POST BRACING
(GALVANIZED
ANGLE IRON
I I /2'xl l/2'x3/16')
3' DD
/OUT
I R
NL
IG
IN
G E
E A R
NCHOR POST
I 1/2'•1 1/2'•1/8'
ANGLE IRON (TYPl
<r!NlSH PRJM[D
8-PA!Nl[D)
2 3/8' DD
OUTRIGGER
2 3/8' DD. SCH40 PIPE
2 3/8' DD. SCH40 PIPE
I I I I I I I I I I
I I I I
I I\ I I I
I I I I N I I
/ I I II II
8' I I I I I I \ I I I I I I I I II I I
4• I I I I I I I I YI I I
0 I I I I ' I I I I I I ; J I
1-
ND CAP
TAUT
\./IRE
I I In
I I
I I I I I I I I I
I I I I I I \ I I
I I I II I
I I V I I V I I I I
TAUT VIRE SYSTEM
®ll!
1---1·---1
I I I
I I
I I
I
I I
> f V I
-"\. ,r I
I ,,... /-
I. VELD SENSOR POST
BRACKETS TO THE
- -3/16' i.ti3/W
HOLE <TYPl (SET 3/4' FROM
I I I I I I I I I I I I I
I I I I
48'
SENSOR POST CARRYJNG
STRUCTURE
ALL EDGES) I I I I
I I I I I I I I I I I I I I I I I
2. rn SENSOR POST
BRACKET TD THE SENSOR
OUTRIGGER SENSOR POST. CARRYING STRUCTURE
1 1/2'*1 l/2'*1/B'
ANGLE IRON (TYP)
I I I I I I I I I I
I I I I I
J -1 I I I I I I I
I I I
I I I/ I I I I
<FINISH• PRIMED
8.PAINTED>
IOrT (TYP)
!OFT (TYP.)
JOrT OYP)
-4•-o
3'
38'
33•
3•[XENDER
END A CHOR POST !NL!NE ANCHOR POST SENSOR POST
N T.S.
M.T.S. M.T.S.
M.T.S.
I. EXTENDER ARE PRE
\.l[LDED TO THE ANGEL
IRON.
l'
HOLE
<SET 3/4' FROM
ALL EDGES)
OUTRIGGER TAUT w!RE SYSTEM C□N F IGUR!'\ T ION.
N.T.S.
OUTRIGGER SLIDER POST. CARRYING STRUCTURE
This docuMent contains fnforr1otlon to Sofeguords
Technology Inc Any disclosures 1-+--+-----------j----j! --- j
FILE LDC., MTPLEASANTJA/BIDl
DRAVN BY•
FACILITY IOWA
DETAILS
JOB\SO NO 1827B
DP/IVJNG NO 04
TAUT wIRE SYSTEM OUTRIGGER INFRASTRUCTURE DETAILS. or useof -this inforr,o tlon or ony i-==I "-'.c.SH_A N+ ----------- 1 reproduction of this docunent CHECKED BY, 1 ----------------------- J Foorther thon the specific _,. SHEET NO.
purposes for which It Is Intended 1--= --1------ll'...T. SAFEGUARDS TECHNOLOGY, INC.
Sl-lEET 3
I--/--'-"--"-f----'--------+-11-----1 o-tlwrwlse o.gree In writing DATE• T@I (701) 411/1-1022 fa, (201) 488-12H REV DATE DESCR1Pl l N BY APP, 04/30/02 NTS
Sofeguords lechnology Inc. Moy Hock,nsock. N w J ,, y 07601 l 00-10-02 CHNJl'.,[D DESIGN VALL ur "
O
C
V
90' a
/_J_
DTR-200O SENSOR
NTS
TOP WIRE OF THE
SENSOR
4 POINT TENSIONERS
BOTTOM WIRE OF
SENSOR
l---+-+---------18' ---------- I'--
SUBS ECTOR
ODS
ARB WIRE
TENSIONER
BREAKAWAY
STRIP
-- !orusf:' of this lnforMOtlon or ,my □. PLOTNl l<□V A reproduction of this docuMent CHECKED BY•
This docunent contains F"ILE LDC.• MTPleosontlA/:SM08 lnfornotlon to Sofeguords
Ly
TYPICAL TENSION
TOP WIRE
77 lbs. +/- 11 lb.
GROUND WIRE
CONNECTOR
NUT
WIRE
CLAMP
RUBBER
SLEEVE
SENSOR PIN
SEAL RING
PIN
CONTACT
POINT
SIGNAL
WIRE
CUP
SPECIAL
DAMPING
COMPOUND
NORMALLY OPEN
CONTACTS
E
'J
'-I--
CD
92.7'
3.4'
4.5•
3.4•
4.5'
3 4•
4.s·
3.4'
6.s· 59.0'
3.4'
3.4•
3.4'
3.4'
83.6'
75.9'
67.8'
9 57.9'
51.1'
44.3'
37.5'
SPRU
MICRO SVITCH
TYPICAL TENSION
LEXAN ENCLOSURE
EMBEDED NUT
3.4•
3.4•
3.4•
3.4'
3.4•
3.4•
30.7'
23.9'
I. SENSORS 111,2,3,4,5,6 WITH LIMITER
2. ANCHOR POST WILL ACCOMMODATE THE SAME
NUMBER OF BARBWIRES AS SENSOR POST.
NOTES•
I. ANCHOR POST WILL ACCOMMODATE THE SAME
NUMBER OF BARBWIRES AS SENSOR POST.
BOTTOM WIRE 3.4' ·-----l-- 17.L!I'QUIDTIGHT
121 lbs.+/- 111b. · j•J[[ FLEXIBLE METAL
3.4•
L --31.4Z' :.==:--rj' ·
,t--1""0. 3• CONDUIT
COVER HOLDER
3 5•--"="'
DATUM
OUTRIGGER SENSOR
Pos1· (5 SENSORS)@
-:-E_N_SO_R P_O_S_T (1_3 +5 SENSORS)@
ANCHOR POST
U-CHANNEL
THE
ANCHOR
TENSIONER
TENSIONERS ATTACHMENT TO THE ANCf-lOR POST
JOB\$0 N□, 1827 B
DRA',/ING NO
for other than 1:he spf:'clflc I. HYSHAN _J.
purposes for whfch It rs Intended f-=cc'-c...,..:...=-..-1------1;r... ,- SAf'EGUARDS TECHNOLOGY, INC.
l--l---+---------11--11---l lsexpressly prohibited except os APP□R V[ D llY• I ' 75 A\lont,c Street
Safeguards Techno!o9y Inc MOY Hoden1ack, ii ,. Jersey 07601 l-t---f---------1-11---l
MOB
$H[[l NO
SCALE• NT[
REV DATE D[ $CRI PT! □N JlY APP.
other...lse ogree In 'll'rltlng. DAT[, 08-26-02 1e1 (201) 488-1022 ro, (201) 488-1244
Techno!ogy Inc. Any disclosures A\IN BY•
,, _. Ill 6' r----1-,----, ---------- SPRU
3•
!CR□ S\JITCH
DATUM
DTR-3OOO TENSIONER INSTALLATION
NTS
RlV
-- +---------11--11 l--- 1--
DETAILS
FACILlTY IOWA
C7 4
L
+12 VDC
Technology Inc. Any cllsctosures DRAYN BY• reproduction of thls docur,ent I CH[Cl<:ED DY•
I L
J3 CONNECTOR J2 CONNECTOR
Jl
1 IN 1
3.9k/5%
2 RETURN 1
GPRU-49
ND 1
output ND 1 23
RELAYS \./ITH DPST CONTACTS
03/4" FLEX.
CONDUIT
TD PRIMARY
CDMMUN J C A Tl N
LINE
SUPPLY PO\./ER
TO 12 VDC
3 9k/5%
•-4
IN 2 RETURN 2
#8 C122
{N ND 2 21
I + + I I +
. '.,_ IN 3 output □ 2 20 -a -a Ai Al
RETURN 3
IN 4
RETURN 4
IN S
RETURN 5
IN 6
RETURN 6
IN 7
RETURN 7
tt? C2l9
ND 3 18
o ut p ut { N JI?
ll 6 CJ LT6
N04 15 output< N□414 1!5 C413
NOS ,_l_i'_ output< NDSJ.L
01" GAL V .C □N DU I T
4PR CABLE BELDEN 1049A i 7
I"'w
Ul
X X X
, D u u :0 T T
16' l,,J rul ltn
X < < c+
.,,. w Iru L.,,.
Reel
.J '.J_
IN 8
RETURN 8
+ 24 VDC
!14 cs 10 N06e-'3._ output ND 6 8
#3 C67
ND?
\JHT
PRl BLK -24V DC
\JHT -Rx PR2 BLK <Rx
PR! BLK
\JHT
PR2 BLK
Fi SYNOPTIC
MAP
C□MMUNI CATI□N
CABLE +
PD\.JER SUPPLY
._2 _l
- 24
- RX
+ RX
VDC output<
#2 f------
7 5 f------
COMMUNICATION LINE
PR3 BU<
PR4 BLK
>Tx
-24V DC
PR3 BLK
PR4 BLK
COMMUNICATION LINE \
23 - TX
24 + TX
N08 3 output< NOB2 ttl cs' 1
-J3
FAIL -NC ND9c.2
ND9 2
1--=-
FAIL -ND C9 , 1_
o u t put
#9
FROM SENSOR POST N-1
JUNCTION BOX
TYPE JR _J
SENSOR POST N+l
To LEDS
Cei,t,-ol Mop
Display
GENERAL POST REPORTING UNIT SENSOR POST JUNCTION BOX SYNOPTIC MAP WIRING DIAGRAM
NTS NTS
DETECTOR
(DTR-3000)
\./HT -RX
TD CCC
ELK +RX
PRIMARY
DLP-05
) PR2
TD SENSOR POST 1-1
+12 VDC
VOLTAGE
ADJUST
I/
MANUAL
/ TRANSMIT
/ PUSH-BOTTON
1,,,,.- VOLT AGE
ADJUST
C□MMUNI CATI DN LINE
SECONDARY
CDMMUNICA TI N LINE
\./HT -TX
ELK +TX
DLP-05
PLP-'12S
) PR3
) PR2
) PR3
TD SENSOR POST 22-1
0 Jl 1
POLARITY
NOT
I BR 11
1 2
C$ll
Tl
IC 0IJ2Q
OBSERVE
POLARITY CABLE
COMMUNICATION
CIIT • i'ZOOQ22
GROUND \.'IRE or SENSORS SHOULD BE
CONNECTED TO GROUND SCRE\.' IN POST,
SENSOR=GROUP
ALARM CONDITION AT COMPUTER
SENSOR I - SENSORS l,2
SENSOR 2 - SENSORS 3,4
SENSOR 3 - SENSORS 5,6
SENSOR 4 - SENSORS 7,8,9
SENSOR 5 - SENSORS I0,ll,12,13
SENSOR 6 - SENSORS 14,15,16,17,18
C MMUNI CA TIDN LINE <
+24V
-24V
+24V
\./HT +24V
BLK -24V
\./HT +24V
) PR1+PR4
COMMUNICATION LINE
TD SENSOR POST 1-1
IMPORTANT
BACK UP
BATTERY
12 VDC
--SHIELD NOT
CONNECTED
' --- \./HT
1---BLK------
SENSOR 7 - SP TAMPER $\.'ITCH SECONDARY C MMUNI CA TIDN LINE
-24V BLK -24V
SECONDARY ) PR1+PR4 CDMMUNICA TION LINE
TD SENSOR POST 22-1
\./ALL MOUNTED
PLUG-IN
TRANSFORMER
CABLE TD
REMOTE
ENCODER UNIT
DTR-3OOO OUTRIGGER SENSOR POST ( 13+5 SENSORS) WIRING DIAGRAM(,,\ LIGHTNING PROTECTION UNIT WIRING DIAGRAM TRANSMITTER UNIT POWER AND OUTPUT WIRING
NTS NTS NTS
This docul"lent contains FILE LDC., MTPleo.so.ntJA/SEOI lnforrio.tlon to Safeguards MOUNT PLEASANT CORRECTIONAL
1--1---1-----------1- --1orusofthis lnforr,a-Uon or any s;mi',·t,"Y S:.:HA N t-----j --F A C l:'.LI T_'.Y IO W".:A: _j for other thon tile specific M. FEINSTEJN ,)
ELEC1'RICAL
DIAGRAMS
JOD\SO NO 1827B
JIRMIJNG NO
EOl Sfl[£l NO
1--1---1-----------1- -...,1J purposes
J for which
J It Is Intended f=:;:;:" ,==+----jsr SAFEGUARDS TECHNOLOGY, JNC.
SIIEET 1
0--+---+ ---------- 1--<--J
Sexpress Y pro h lb ted except ns 75 A\lont,c Strut Sofeguo.rds Technology Inc Moy Hocken oc . New Jer.iey 07601 otherwise agree !n writing DAT[, Tel ,,001 488-1022 fox ''") ,4.88-!2H
SCAL[,
REV DATE DESCRIPTION DY APP 08-26-02
APPROV[D DY•
f--
I-
GND
'i'
Brn Blu Grn \.Jh-t Bl1-<
•-7
I-
I-f--f------f------f------
.--1.i
•-16
,1Z ru
Ul
N□
COM >
Q9 LI LI Q9
\./HT -RX
Q9 L2 L2 Q9
BLK +RX
1-- GND f---
Q9 L3 L3 Q9 "IT -TX
I- I-
® L4 L4 Q9 Pl + TX
Q9 LI
ELK +RX BLK +RX
\./HT -TX
Q9 L2 L2 Q9
. GND
Q9 L3 'j' L3 Q9 I-
Q9 L4 L4 Q9
\./HT -TX
BLK +lX
BLK +TX
12V AC
I
I I
TRANSMITTER
INTERFACE
BOARD
outpui NO
'"' m•
I
'-' ' M3 C6 ' m
7. ' \
DY•
lr r)
MOUNTED
f!ES J ill
R!T""N < !7-2l '" ' ouipu•{ ,_,. .".
• •£111RH 2 68-69 ...,,..,, IC2) ''
zoc "
O(!UON ) "
I
"•-.OCT,UON • 9-16 ""'""'{
ll ""'""'{ HIJ
6 •
--'' ." Ml ca r•IL-NCmNO, r-·
EXTERNAL MAP
24 voe
ENCODER
R
IIRN l (,€,-67 " , ""'""'{ I I) '
" R
(IU '
•s c•
Tronsriltter lJ IN 1
C5 •"
• 2< IIPC
..........{ 111·11 •
- 14· VP(
•2 C> •
Transforrier
At UPS Rec:epto.cle
F•ll-te "°'
.,.,put{ NO -
B ll co t (-) tTx (-)
T CCTV
TD CCTV/VMD
NOTE:
RELAY OUTPUT IN GPRU
il.. :
LASER GUARD
PTZ
SHOULD HAVE DPST CONTACTS ')j
• Gf'RU-◄ 9 ·1-'E'-' • ' ' 7
' '•"nu' •N, °" \ I>"
'{0 N O l J
, ., ADORES$ MS Cl
R'"C'IIIRN l 70-71 □□
°""'""' {m'
"-', R □□F R M MMP MONIT□Rt======== ::::-7 RCT,..,N ] z NO 2 {Ml zcn: 22 I _,, I/ ANTENNA ROOF ALARM I ""'-'
'"'TURN ft6 CJ I I I ENCODER Rt:11.lRN 6 MS u
I 'l>"l:'IU>H T " ""'""'{ tffl
TD CCTV l11!1s 19 20!21!22! I I "-I/ 1 ---=-- 7 ,,,
• 2< IIPC
"J C6
TO CCTV
INPUTS ZONES 17-22
ZONE
ANTENNA c , I H KE Y B□ARD co
- " .-.".' l2
C> • .., INPUTS
COAX CABLE1 RADIO
TRANSMITTER I '""'"" "" .-.". wll)UI N08
TD CCTV I I I
12VDC
GPRU
MOXA COHH BOARD RS-422 j
COH.2 T CD>ll I C ) I
MOUSE
.,._ ,J_._
R(ll-"'N I
'-•ll·NC HOS
CDH NO,
F ll--Kl C9 I
Gf'RU-<9 • ""'""'{Ml I " r
TD CCTV
I 9 I10 12l13I1411sl16l
INPUTS ZONES 9-16
ADDRESS
M8
ICJ I
---r l '4f '-- ••
ZONtS ' "'
12VDC "
'. .R'"-(l,'!PN' ""•'°s"' { HcJ•• ",. "
Z[J,C II'
10 CCTV INPUTS ZONES 1-8
UPS OPTICAL L_ \JALL "' ' ""'°"'{ = "
PD\./ER
>-- h ISOLATORS MAP ... "'
14 C5 ,'"
ZDNC II
60 Hz SUPPLY PROTECTION u,.;;- .. M3 (6 ION[ 10
CONDUJ"f -
CABLEfl2
UNIT
CABLE fl I
/ CONDUIT - "°"'
f ------ """'"
• · voc
• 2, I/PC
""M'"2"'{ "c1°' •
.,..1..,1 HD
,_, TD CCTV
T□ CCTV
- MOBILE
CON NO' 2
f IL -ICJ C1 l
INPUT
SIGNAL'
BLK
\,,/HITE
SP U SP ll8·1
ZOI< 118
SPRU SENSOR
UJIL
" ,,'=1 Gf'RU- '.l
' •• ADDRESS
i8 ICJ I " ·,-_'. TD CCTV
" " " ' " " " ' •' •• ,_, ""\nu•<00'1 ' ,-' T□ CCTV INPUT INPUT
" " '" " " ,,7 " " " ' " II II II II II I II II II II I I II II II II II II I "
l![T""1! l M7 C<
ZONES
•6 CJ
12 VAC 12 VAC
' " SENSORS " SENSORS " SENSORS
SENSORS SENSORS SENSORS SENSORS SENSORS SENSORS
RCTUOH •
1>£1<-"'" 5
• >H '
""'""'{..,·. ",. ,_. Ta CCTV I I I [ iE '--..r' To
COMMUNICATION LOOP
,_, ? To wo.ll riount
T□ CCC '
El •
""'""' H09
- ' Ml ca '
PPll
" SPPl/ n
CDH HD,
T'"''''
JR/H\J
ZONE 12
W11-1 IR/H\J
ZUNE 10
IR/H\J
ZONE 9 ,S-P
7-l
SP 6-l rAlL·Ml C9 I "
LJ "
7, ,.:='J,11 l r
SENSORS SENSORS SENSORS SENSORS SENSORS SENSORS SENSORS SENSORS SENSORS
CONNECTION OF
ENCODER ANO
FIELD
RELAY
GP R LI , MOBI LE
OUl-PUTS FOR
MAP,
CCTV
SYSTEM CONFIGURATION
COM. BUS TD MOBILE MAP AND CCTV
GPRU(S)
COMPUTERIZED
CENTER
MOXA COM.I
COMM. CDM.2
DB 9
COM.1
DB 9
COM.2
, ,-,), 4850P Tx
B (+) " B <+I
A (-'} Tx Rxt <-> B (+) D (+)
I-
PROTECT GND PROTECT GND
,- 12 V DC I- "'
RS 22/RS ◄ 85
OPTICAL ISOLATOR
, ,-,) 4850P - B <+> Rx B (+)
A (-'}lx Rxt (-) D U) D (+)
I-
I- PROTECT GND PROTECT GND
, 12 V DC I-
TO LIGHTNING PROTECTION
PRIMARY FIELD CABLE
TD LIGHTNING PROTECTION
SECONDARY FIELD CABLE
BOARD
RS-422 C□M.3
CDM.4 -
TD 12 V DC PDVER SUPPLY
VALLMOUNTED
ALARM
ANNUNCIATOR
OPTICAL JSDLATDR
This ciocunent contains
!nf'ornotlon to Sof'eguords
FILE LDC.• MTPleosontJA/SE02
MOUNT PLEASANT CORRECTIONAL ELECTRICAL
JOB\SO ND 1827B
DRI\VING ND E02
Technology Inc Any disclosures DRAVN J--+--+-------------1--+--I or useof' this inf'ornotlon or any 1,-,:D,c,:..PL"De;Te,N:.,.lK::;D'-V:CA.:_I ----- I FACILITY IOWA , DIAGRAMS reproduction of' this docur1ent CHECKED BY• 1-----,----------------f'or other thon the speclf'lc y ZHUl<OVSKIY
1!-£Ef ND purposes f'or which It Is Intended 1-,,,:,,,:::,:;:;:,::c.::::.:_:_1 ------ 1
APPROVED BY•
SIIEE'f 2 l---+--+-------------1-..J..---+ Safeguards Technology Inc. Moy 1-------1 ------ 1 Hac nsoc f.,,w J • ey 0760 I ◄ SCALE• NTC
REV DATE DESCRIPTION
other'<!lse ogree In "<¥rltlng, DAT[, 08-26-02 T.t (201) <Bll-1022 fo• {201) <88- 124
75 AUontte s1, t prohibtted except os
TABLE
NTS
OF SENSOR POST ANO MOBILE MAP GPRU ADDRESSES
LGS
CONTROL
TO CCTV
'R"(I'U,,N l .,.,1..,1{ 00 l " 22-1
- - PRlMIIRY
TD CCTV
01.0' GAL V 01.0' GAL V
•6 CJ I
E1-'S24l2
DC-DC
CONVERTER
TD CCTV - 2• IIPC ""'""'{ HOT ts- Ubj
NTS
COMMUNICATION
NTS
LINE CONNECTION DIAGRAM
24VDC
VALLMOUNTED
ALARM
ANNUNCIATOR MAP
COMPUTERIZED
CENTER
PRINTER
24V DC
Ffl'wER
SUPPLY
S-150-24
GPRU
t
J
NEAR •,' TO CCTV
TO CCTV
h---- II1
TD CCTV I I I
ll TT I 1 12 4151617181
120V AC LIGHTNING
SECONDARY
n'
ZONE 20
TD CCTV
slgnol In put
M◄ IOHC J COMfUNICAT!04
10 CCTV
BLK
,_' RED
J--+--+ ------------ 1--+-- sI expressyI
2 VEHICLE
MOUNTED
MOBILE MAPS
l2VDC 1 AMP <Plug in cor lighter)
ADDRESS LOCATION ADDRESS LOCATION ADDRESS LOCATION
1 1-1 15 13-1 29
2 1-2 16 14-1
ZONE -20,21
SENSOR
COIL
GPRU 3 2-1 17 14-2 31
4 3-1 18 15-1 32 ZONE -9,10
IR/Ml,/
GPRU 5 3-2 1CJ 15-2 33
6 4-1 20 16-1 34 ZONE -12
lR/MV
GPRU
7 4-2 21 16-2 35
8 5-1 22 16-3 36 MOB. MAP
ZUNEl-8
GPRU CJ 5-2 23 17-1 37
10 6-1 24 17-2 38 MOB. MAP
ZONE 9-16
GPRU 11 6-2 25 17-3 ]CJ
12 7-1 26 18-1 40 MOB. MAP
ZONEl?-22
GPRU 13 8-1 27 18-2 41
14 11-1 28 22-l sr)
INPUTS
Rx t
ZONE 9
7- X
INTERf ACE
Tx
I NJERf ACE
C□MMUNICAT IDN LINE
INTERfAC[
BOARD
12V DC
INTERFACE
C□MMUNICAT IDN LINE
BACKUP
BATTERY
12V DC
BATlERY
I2V DC
BATTERY I-
PD\JER
SUPPLY
PO\JER
24V
HEATER
24V
\HEAlERJ
120V AC
PD\JER
SUPPLY
24V --IHlA TE
XFRMRI
t
PO\JER
SUPPLY
24V HEAlER
IXFRMRI
XFRMRI
-t t t
IXFRMRI
I20V AC
I. 24 V AC FDR l.R. LENS HEATERS.
BOARD
ZONE 10
2. 12V DC FDR I.R./M.\J. CKT BOARD PO\JER + GPRU.
BACKUP
BATTERY
BACKUP
BATTERY I. 24V AC FDR I.R. LENS HEATERS.
2. 12V DC FOR I.R./M,\J, CKT BOARD PD\JER + GPRU.
1- I
-- -121/- U& ···· ·-
POWER AND CONTROL CONNECTIONS BETWEEN
I.R./M.W.
UNITS FOR ZONE 12 1
SEOJ
PD\JER
24V "iHEATER
XFRMR
PO\JER
24V -IHEA IEPI
IXFRMR I
I20V AC
POWER AND CONTROL CONNECTIONS BETWEEN I.R./M.W. UNITS FOR ZONES 9,10 3
NTS SEOJ
ZONE A
N/C '-
Tx TAMPER
COMMON
.9K vvv
Rx . ·'?K
ZONE A Tx TAMPER
COMMON
ZONE A Rx TAMPER
COMMON
ZONE A IR/Ml,/ ALARM
COMMON
J_ IN I
2 RETURN I
:L IN 2
4 RETURN 2
I-
5 IN 3
RETURN 3
NIC f.
3.9K
ZONE A Tx TAMPER
ZONE A Rx TAMPER
COMMON
ZONE A IR/Ml,/ ALARM l IN I
L RETURN l
- 3 IN 2
4 RETURN 2
l IN 3
DOPPLER
MASTER 'V
'V V cl_
I-
I-
I-
I-lN 4
RETURN 4
lN 5 GPRU
RETURN 5
IN 6
RETURN 6
lN 7
RETURN 7
DOPPLER
Rx
MASTER
BOARD
3.9K
-?K
J.l_
I- eli
RElURN 3
IN 4
RETURN 4
IN 5 GPRU
RETURN 5
IN 6
RETURN 6
lN 7
RETURN 7
Reel
.l'.5. lN 8
- 16 RETURN 8
- 17
.lll_
ZONE B
Tx Rx
3.9k/5%
.J2. 18
IN 8
RElURN 8
Blk
\Jht
Grn
19 12 - 24 voe 20 12 - 24 voe
- 21 - RX
22 + RX
N/C
ZONE B Tx TAMPER
Reel
Blk
\Jht Grn
19 12 - 24 voe 20 12 - 24 voe
21 - RX
I-
Blu
Brn
23 - TX
24 + TX
COM. LINE TO CCC
- COMMON
DOPPLER
MASTER
BOARD
_3.' lK
3.9K V
ZONE B Rx TAMPER
COMMON
ZONE B IR/Ml,/ ALARM
Blu
Brn
22 + RX
23 - TX
24 + TX
COMMON COMMON COM. LINE TD CCC
DUAL TECHNOLOGY I.R./M.W. WIRING WITH GPRU INTERFACE FOR ZONE 12/ '
I. ONE GPRU FOR 2 ZONES/2 SETS O, IR/Ml,/
1 DUAL TECHNOLOGY I.R./M.W. WIRING WITH GPRU INTERFACE FOR ZONES 9,1 0 /
NTS SEOJ
NTS SEOJ
This docuMent contains FILE LDC., MTPleo.sontlA/SE02
JOS\$0 NO
ORA'-'ING J-,10
l827B
Technology Inc Any disclosures DRAYN BY• ELECTRICAL E03 or use of this lnforno.tlon or o.ny for other tho.n the specific
0 PLOTNIKOVA
L MYSHAN
FACILITY IOWA DIAGRAMS
e,v
DAT£
DESCRIPTION
reproclvctlon of this docurient CfCCK[D RY• purposes for which It Is Intended
Is expressly prohibited except o.s
Sofeguords Technology Inc. MOY otherwise ogree ln writing DAU•
08-26-02
SAFEGUARDS TECHNOLOGY, INC.
7S Atlontic Slre !
Hockensock, New Jecsey 07601 r (201) 488-1022 Fo• (201) 488-1244
SIIEE'f 3 scv SH[[T NO
SCALE•
lnforMo.tlon to Sofeguords
BATTERY
R
APPROV(IJ IIY,
I-
-I
X u
----1 X
;1)
X
I Al X < <
I +
- u C
'1l
(0
":y c+
Ul
ADDRESS 0
t:J
- 3 reproduction of this docur,ent I CHE(YED BY• l-='-c':-c-"-'--1------ll.,, z ' z' z ' z y z I' Z z z z z ' z ZI' z> 21' z ZY - z ZI'- Z, z z y l'l cor1r1unicG tion t:J BoQrcl T
----1 ----1 ;1) A)
- - -'- - - - - -t - -a t - 7 - a': a re a I';: - ,: - e: z> I' Z D 0
I' Z I' Z D D D D
L E E E E E E E E E L E ' L E E C E E E
'E" E E'" "E E E E E E E E"
7 I
I t c c l'l t:J
J3 P3
SINOPTIC MAP WIRING DIAGRAM
G N D
D-TYPE
7 P I
" 9 p
-+-V y y y y y y R R
(FROM TERMINAL BLOCK IN RACK)
12VDC
L L L L E E w w w w D D
R R R R R R R R E E E E E E E E D D D D D D D D
R R R R R R E E E E E E D D D D D D +
RED J I
D-TYPE - "- t - "- "- "- le - - - - - - a - a le a a - le - -" z- , "- - ' - '
SECURE ""
37S 37P D D D D D D D D N N N N N N N N E E E E E E E E u
,s
" " " ' 2
D D D 0 D D D D D D D D D D N N N N N N N N N N N N N N E E E E E E E E E E E E E E 3 ' 5 6 7 8 9 ,0 " " " " " '"
ACCESS ,,,' '" SINDPTIC MAP
CAT. No: 10100314 {
To 9 Pin connector COMMUnicQ tion
To 9 Pin
BUZZER
BoQrcl ttJ ;1) ' -connector ttJ ;1) '
I I +
RM3
u u (0 :-; C )
":y
'1l :-; c+
COMMUNICATION
RMS
J4
J2 P2 37S 37P
R R G G G G G G G G G G G G G G G G
G G y y
--+V y y y y y y y y y y
+V RED - -
_LJ. i ' E E R R D D N N
R R R N N N
R R R R R N N N N N
R R R N N N
R R R N N N R R L L
N N w w
L L
L L L L L L
',; ',; ',; ',; w n SINOPTIC
-V RO ' 2 z y z
- y z z ' z z "- z z z ' z
- "y z
,z,' z "- "r-z z'' - z z"- "- "-z'- z
' z \ z' z z ' z z' z
N " ' N N N N N N N
0 □
D N N N N N D 0 D
0 D D D D D D N
BOARD
PD\JER
SUPPLY
12 VDC DR
24 VDC
-4
JS
I
-3 -4
J
RMB •
RMlO
" " ' 2 3 ' 5 6 7 '
,s
" " 18 ' 2 3 ' s 6 7 8 9 w " "
ZONES 1-18
-3
-4
-J7
K!/N,C.
Kl/NO
KI/COH.
K2/N.C.
RM7
p CentrQl
,JJisplQ y
Mop
I K2/NO
2 K2/CDH
VCC <5V)
37S 37P
NOTES• 1. IN EACH SYNOPTIC MAP \JIRE THE LEDS TD BE USED IN THAT PARTICULAR MAP ONLY.
2. +V - PD\JER SUPPLY VOLTAGE TD THE MAP.
This docur-.ent contolns mt LOC,MTP\eoso.nt1A/SE04
JOB\S() NU 1827B
Jnfornotlon to Sofeguords MOUNT PLEASANT CORRECTIONAL Technology Inc Any disclosures DRAVN BY• ELECTRICAL DPAVlNG J-0 E04 or use of this lnfor....otlon or o.ny "'"O P□iL'f;T';,N□"I"KV" _A1 i ----- F'._.'.:A:,'.C'..'.l'._'.L'.'.l T'.,_Y'._.'.l::O W::_A'.'.._ j DIAGRAMS
SHEET NU
l--t---+-------------1-+---t forother thon the specific y ZHUKOVSK]Y ,)
>--+--+-------------<-+----! purposes for which It Is Intended l--t---+-------------1-+---t IsPxprE.>ssly prohibited except os
APPROVED BY•
Sofeguords Technology Inc noy 1- -----l ----- l
75 Allont,c Slr et
Hoden ock, Ne" J , y 07601
SI-IEET 4
$CALE, NTC
REV DATE DESCRIPTION BY APP
otherwise agree In writing DAT[, 08-26-02 Tel (201) 488-1022 Fa, (201) 488-120
R, - \/HT
□ D N N N N
0 0
I
X
I +
- T
9 S ALARM
SINOPTIC
MAP BLOCK DIAGRAM
SHIELD
N T,- BRO
T,+ BLUE
R, + GRN
y -
RM9
' J2 P2
RM6
X X X z ' D D D D D D D D y C y y '
RS422 ""---
E
N N N N N
-----vv-
{ N {--'y "'' V
Ul t:J n
ADDRESS 1
SINOPTIC
MAP
ZONES 19-22
JJ
CONNECTOR
J2 CONNECTOR
CentrQl MQp DisplQ y
JJ CONNECTOR
J2 CONNECTOR
CentrQl MQp DisplQy
CentrQl MQ DisplQy
2 – ADMINISTRATIVE ISSUES
2.1 GENERAL INFORMATION
2.1.1 DAS will evaluate the qualifications, experience, and other relevant information from companies interested in contracting with the State of Iowa to provide the necessary services to complete the project described in this RFP.
2.1.2 Companies certified as Targeted Small Businesses are encouraged to submit Proposals. The
Iowa Department of Economic Development administer the Targeted Small Business (TSB) Program. Businesses meeting the requirements of the program are approved and registered with the Department of Economic Development and are considered Targeted Small Businesses for purposes of this RFP and most other solicitations issued by DAS. Questions concerning the TSB Program and for identification of companies certified as Targeted Small Businesses, contact the TSB Certification office in the Department of Economic Development at (515) 348- 6159.
2.2 INQUIRIES
2.2.1 All inquiries concerning this RFP shall reference the RFP number and shall be provided (via email) to the issuing officer email address identified on the cover page of this RFP. Addenda type questions must be submitted per Schedule, Section 1.2.
2.2.2 Any information provided by prospective companies orally shall not be considered part of the companies Proposal.
2.2.3 DAS assumes no responsibility for representations concerning conditions made by its officers or employees prior to the execution of a contract. Oral discussions pertaining to modifications or clarifications of this RFP shall not be considered part of this RFP and are not binding.
2.3 PREPARATION OF THE PROPOSAL
2.3.1 Proposals must be submitted on the Iowa IMPACS Electronic Procurement System.
Prospective companies are solely responsible for timely submission.
2.4 DATE, TIME AND PLACE TO SUBMIT PROPOSALS
2.4.1 As stated above the proposal must be submitted on the Iowa IMPACS Electronic
Procurement System
2.4.2 The Proposal must be submitted into IMPACS, on or before 2:00 pm, central time on the
Proposal due date.
2.5 ECONOMY OF PRESENTATION
Proposals shall address the specific RFP requirements. All questions posed by the RFP shall be answered clearly and concisely.
2.6 RFP CHANGES AND ADDENDA
Written Addenda will serve to amend the RFP documents accordingly.
2.7 CERTIFICATION OF INDEPENDENT PRICE DETERMINATION
By submission of a response to this Proposal, the Company certifies, and in the case of a joint
Proposal, each party thereto certifies as to its own organization, that in connection with this procurement:
2.7.1 Any prices or hourly rates in this Proposal have been arrived at independently, without consultation, communication, or agreement, for the purpose of restricting competition, as to any matter relating to such prices with any competitor.
2.7.2 Unless otherwise required by law, any prices or hourly rates which have been provided in this
Proposal shall not knowingly be disclosed by the Firm, directly or indirectly, to any competitor prior to the notice of intent to award a contract for services.
2.7.3 No attempt has been made or shall be made by the Company to induce any other person or
Company to submit or not to submit a Proposal for the purpose of restricting competition.
2.7.4 Each person signing this Proposal certifies that:
2.7.4.1 He/she is the person in the Firm’s organization responsible within that organization for the decision as to any prices being offered herein, or
2.7.4.2 He/she is not the person in the Firm’s organization responsible within that organization for the decision as to any prices being offered herein, but that he/she has been authorized in writing to act as agent for the persons responsible for such decision, and
2.7.4.3 Any offer made by the submitted Proposal and any clarifications to that Proposal shall be signed by an officer of the offering Company or a designated agent empowered to bind the Company in a contract.
2.8 NOTICE OF INTENT TO AWARD
After the successful Company has been selected, a copy of the Notice of Intent to Award will be issued to all Companies who submitted Proposals in response to this RFP.
2.9 WITHDRAWAL OF PROPOSALS
Prospective Companies may withdraw, modify, and/or resubmit at any time prior to the date and time set for the receipt of Proposals. Once the time set for receipt of Proposals has passed, a
Company shall not withdraw a Proposal for a period of sixty (60) days following the issuance of the
Notice of Intent to Award a contract. Proposals shall remain open and valid for consideration by DAS throughout this period of sixty days, and until such time thereafter that written request to withdraw a Proposal is received by DAS.
2.10 DISPOSITION OF PROPOSALS
All Proposals become the property of DAS and disposition of the Proposals shall be at the sole discretion of DAS.
2.11 DISCLOSURE OF PROPOSAL CONTENT
Proposals will be placed in the public domain and be available for examination by interested parties.
No Proposals shall be disclosed until after a Notice of Intent to Award has been issued. DAS reserves the right to destroy all Proposals if the RFP is withdrawn or otherwise in the normal course of business. Trade secrets or proprietary information legally recognized as such and protected by law may be withheld if they are clearly and conspicuously labeled “Proprietary” in the margin of each individual page where they appear in the Proposal. Pricing information is not normally considered proprietary.
Public Records and Requests for Confidential Treatment.
The Agency’s release of public records is governed by Iowa Code chapter 22. Contractors are encouraged to familiarize themselves with Chapter 22 before submitting a Proposal. The Agency will copy and produce public records upon request as required to comply with Chapter 22 and will treat all information submitted by a Contractor as non-confidential records unless Contractor requests specific parts of the Proposal be treated as confidential at the time of the submission as set forth herein AND the information is confidential under Iowa or other applicable law.
Failure to request information be treated as confidential as specified herein shall relieve Agency and State personnel from any responsibility for maintaining the information in confidence. Contractors may not request confidential treatment with respect to pricing information and transmittal letters. A contractor’s request for confidentiality that does not comply with this section or a contractor’s request for confidentiality on information or material that cannot be held in confidence as set forth herein are grounds for rejecting contractor’s Proposal as non-responsive. Requests to maintain an entire Proposal as confidential will be rejected as non-responsive.