This addendum is issued by the City of Sanford, Florida Finance Department Purchasing Division to provide clarification and answers to bidder questions regarding RFP 25/26-14 for Elevated & Storage Tank Maintenance and Asset Management. The scope of work encompasses full-service maintenance and asset management services for potable water storage tanks, including professional inspection, rehabilitation, repair, washouts, visual inspections, and repainting. The specific assets consist of eleven ground storage tanks (two 1-million-gallon tanks, two 700,000-gallon tanks, one 500,000-gallon tank, and six additional tanks), two 250,000-gallon elevated storage tanks, one 27,000-gallon ozone contact chamber, and one 50,000-gallon backwash waste storage tank. The solicitation due date remains Thursday, July 2, 2026 at 2:00 PM local time, with no mandatory pre-bid meeting scheduled. Bidders must acknowledge receipt of this addendum prior to submission or include it with their proposal to avoid disqualification.

Key contractual requirements identified in the addendum include the contractor's responsibility for hiring an independent third-party quality control inspector, annual pricing structure that must encompass all repairs necessary to maintain structural integrity and function rather than hourly rates, and adherence to Florida Administrative Code requirements for professional structural evaluations of potable ground storage tanks at least once every five years. Historically, sediment removed during tank cleaning has been released on nearby grounds with minimal volume. Exterior renovation specifications require Tnemec or comparable paint with appropriate safety data sheets, and no existing mixer systems are installed on the drinking water assets. The contractor must develop pricing based on the specified tank inventory and maintenance schedule, with the understanding that all repair costs and deficiencies discovered during inspections should be incorporated into the annual pricing proposal.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

City of Sanford | Finance Department | Purchasing Division 300 N. Park Avenue Suite 236, Sanford, Florida 32771

Phone: 407-688-5030 or 5191 | Fax: 407-688-5021 | Email: purchasing@sanfordfl.gov ADDENDUM

#3 RFP 25/26-14

Elevated & Storage Tank Maintenance and Asset Management

DATE: June 18, 2026

TO: All Bidders/Proposers

FROM: Frank Mascola, Purchasing Coordinator

City of Sanford Purchasing Division

SUBJECT: RFP 25/26-14 Elevated & Storage Tank Maintenance and Asset Management | ADDENDUM #3

This addendum is issued to provide additional information, clarification, corrections, additions, deletions and/or answers to questions concerning the above referenced solicitation. All information provided in this addendum is incorporated into the solicitation document as set forth therein. All other parts of the solicitation have been maintained as originally distributed. This addendum supersedes any verbal and/or other instructions given to any bidder/proposer qualified to respond pursuant to the requirements set forth in the solicitation document.

I. DUE DATE

This Addendum changes the solicitation due date. The solicitation due date has NOT changed from Thursday, July 2nd, 2026 at 2:00PM Local Time.

II. NON-MANDATORY MEETING

N/A

III. QUESTIONS AND ANSWERS (Q&A)

The City has received the following question(s) concerning the solicitation:

Q1. The bid documents indicate that the project includes services for both ground storage tanks and seven

(7) elevated water storage tanks. However, Exhibit A appears to identify only two (2) elevated water tanks with a total of 9 tanks. Please clarify the tank list in Exhibit A.

A1. (11) Ground Storage Tanks, (2) For the Drinking Water Facilities there are (2) 1 million gallon ground storage tanks (one at the Aux Plant and one at French Ave Booster), (2) 700,000 gallon ground storage tanks (with aerators at the Main Water Plant), (1) 500,000-gallon storage tank (at Aux Plant), and (2) 250,000-gallon elevated storage tanks. All answers below will be specific to the Drinking Water Facilities. In addition to the potable water storage tanks there is (1) 27000-gal ozone contact chamber and (1) 50000-gal backwash waste storage tank at the Auxiliary Water plant.

In addition to the potable water storage tanks there is (1) 27000-gal ozone contact chamber and (1) 50000-gal backwash waste storage tank at the Auxiliary Water plant. Unsure if these are to be included.

Q2. Can the sediment be released on the nearby grounds when cleaning? If Not, how should the sediment be disposed of?

mailto:purchasing@sanfordfl.gov

Phone: 407-688-5030 or 5191 | Fax: 407-688-5021 | Email: purchasing@sanfordfl.gov ADDENDUM

#3 RFP 25/26-14

Elevated & Storage Tank Maintenance and Asset Management

A2. Historically the removed sediment has been released on the nearby grounds from potable water storage tanks.

Q3. How much sediment is normally in the tanks when they were cleaned last?

A3. No exact quantity is known, however, during previous cleanings when the sediment has been left on the grounds it was not a noticeable amount for potable water storage tanks.

Q4. Do you know what type of sediment is in the water tanks?

A4. Sand and other small particulate matter transported through raw water lines from the production wells for potable water storage tanks.

Q5. Does the city have a schedule of interior and exterior inspections, cleaning, repairs, coating, and or repainting of all the tanks for us to use for pricing?

A5. Currently the dry surfaces of the elevated storage tanks are inspected yearly. Potable ground storage tanks are cleaned and professional structural evaluation inspections performed at least once every 5 years in accordance with F.A.C 62-555.350.

Q6. Can the city provide previous inspection / and or drawings of the water tanks?

A6. Previous inspection records are available for all tanks. Video is available for some. Some drawings are available.

Q7. Does the city intend for the tank rehabilitation and major repair cost to be included in the annual pricing schedule for each tank?

A7. Yes, any repairs should be included in the annual pricing.

Q8. Does the city just want us to provide cost for cleaning and inspection and then an hourly rate for any type of repair work that would be needed?

A8. No hourly rate just annual pricing.

Q9. In the RFP, page 5, section 2.01 A---Is the Contractor or the Owner responsible for hiring the independent third-party QC inspector?

A9. The contractor is responsible.

Q10. On page 6, section 2.02, A iv. A. part of this spec in section A refers to interior surfaces. Please clarify the surface prep for the exterior renovation.

A10. Tnemec or comparable paint; safety data sheets for any chemical used.

Phone: 407-688-5030 or 5191 | Fax: 407-688-5021 | Email: purchasing@sanfordfl.gov ADDENDUM

#3 RFP 25/26-14

Elevated & Storage Tank Maintenance and Asset

Q11. On page 8, Section 2.02, J.V----Do any of the tanks have existing mixer systems installed?

A11. No, Drinking Water assets do not have mixers.

Q12. In the RFP, there is a scope for the elevated steel tank renovation, but what is the specification for the concrete tank renovations?

A12. Tnemec or comparable paint

Q13. In Section 2.02, Item C, it mentions numerous repair items but isn't quite definitive on exactly which repairs are being requested. Can we get some clarification on this?

A13. Repairs are for deficiencies found during the inspection that would require repair to maintain the structural integrity and function of the tank and its components.

Q14. Is the 5-year schedule up to the contractor to determine? Or is there a set schedule the client wants to follow for each asset?

A14. 5yr schedule is per Florida Administrative Code. See Answer 5 above.

Q15. The RFP document lists seven tanks but the provided excel spreadsheet has eleven tanks in total.

Can you clarify how many tanks are included for the RFP?

A15. Please see Answer 1.

IV. CHANGES, ADDITIONS AND/OR CLARIFICATIONS

V. SIGN-IN SHEET

N/A

VI. ATTACHMENTS

Phone: 407-688-5030 or 5191 | Fax: 407-688-5021 | Email: purchasing@sanfordfl.gov ADDENDUM

#3 RFP 25/26-14

Elevated & Storage Tank Maintenance and Asset

Respondents must acknowledge receipt of this Addendum by signing this form below and returning it to the Procurement Division prior to the hour and date specified for receipt of bids/proposals or by including this Addendum with your submittal. Failure to comply may result in disqualification of your response.

Acknowledgment is hereby made of Addendum #3 to RFP 25/26-14 Elevated & Storage Tank Maintenance and Asset Management

Name of Firm/Company Contact Email

Street Address City, State, Zip Code

Telephone Number Fax Number

Authorized Person Printed Name Authorized Person Title

Authorized Person Signature Date of Signature

File details come from the government source that posted it. Updated .