Variable Environmental Control Unit (VECU)
Solicitation number
M67854-25-I-5327
Issued by

About this file

This Request for Information (RFI) is issued by the Marine Corps Systems Command (MCSC) to conduct market research on a Variable Environmental Control Unit (VECU) for the United States Marine Corps. The VECU is intended to improve upon existing 3-Ton and 5-Ton Environmental Control Units (ECUs) by focusing on enhanced British Thermal Unit (BTU) tonnage output with reduced power consumption. Key requirements include using a Hydrofluoroolefin (HFO) refrigerant with a Low Global Warming Potential (LGWP) rated at 750 or less, compatibility with existing USMC mobile electric power systems, and optimization for soft/rigid wall shelters.

The RFI seeks detailed vendor responses covering development cost estimates, production timelines, monthly production capacity, and technical capabilities. Specific design criteria include weight limits (560 lbs max), dimensional constraints (47.6 x 37 x 47.4 inches), operational temperature range (-25°F to 125°F), variable cooling capacity up to 6 tons, multiple airflow rates, electromagnetic interference compliance, and reliability standards (Mean Time Between Failure of 2,100 hours). Vendors are requested to submit responses by November 3, 2025, addressing a comprehensive set of technical, performance, and operational specifications for the proposed VECU system.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Request for Information M67854-25-I-5327 Variable Environmental Control Unit (VECU)

General Information

Document Type Request for Information (RFI) Request for Information Number M67854-25-I-5327 Posted Date 30 September 2025 Response Date 03 November 2025 Product Service Code 4120 (Air-Conditioning Equipment)

NAICS Code 333415 (Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing)

Introduction

This Request for Information (RFI) initiates market research under Federal Acquisition Regulation Part 10.002(b)(2)(iii). This is NOT a Request for Proposals. NO FINAL SOLICITATION DOCUMENTS EXIST AT THIS TIME. This RFI does not constitute a commitment, implied or otherwise, that the Marine Corps Systems Command (MCSC) will take procurement action in this matter. The Government will not be responsible for any cost incurred in furnishing this information.

In support of USMC Environmental Control Equipment (ECE) requirements, MCSC is interested in understanding industry's capability to design and produce a Variable Environmental Control Unit (VECU) with a capability that focuses on improving British Thermal Unit (BTU) Tonnage output with a reduced power consumption and are optimized to be powered by existing United States Marine Corps (USMC) mobile electric power, the Advanced Medium Mobile Power Systems (AMMPS) and USMC electric distribution systems, the Mobile Electric Power Distribution System – Replacement (MEPDIS-R). The VECU will need to use a Hydrofluoroolefin (HFO), a Low Global Warming Potential (LGWP) refrigerant rated at 750 or less and non-polyfluoroalkyl substances (PFAS). Information is requested in Microsoft Word or Adobe PDF format document.

General Background

The USMC 3-Ton ECU and 5-Ton ECU, listed in attachments/links, are the currently fielded Program of Record systems. These units primarily support Soft/Rigid Wall shelters. Both units cool, dehumidify, ventilate, filter, and heat. The VECUs are intended to satisfy most Marine Corps requirements. The current ECUs are designed for minimum size and weight, standardization of components, minimum power requirement, a tolerance of variations in power supply, and maximum reliability and maintainability consistent with their relatively small interior volume. Their features include:

• Rugged construction and able to withstand shock and vibration

• Automatically controlled heating as well as cooling

• Fresh air ventilation with or without cooling or heating

• Self-protection against storage temperatures

• Self-protection against restriction of condenser air flow

• Electromagnetic Interference compliant

The current refrigerant used by these systems have a high LGWP and contain PFAS, which do not comply with new policies such as the American Innovation and Manufacturing Act and Environmental Protection Agency’s Final Rules. This drives a Marine Corps’ need for a VECU that uses modernized refrigerants as an enduring solution. The VECU needs to be optimized to encompass a range of BTU/hr. outputs and consume less power/fuel resources.

This RFI includes a list of VECU design criteria that are also applicable to individual 36K & 60K BTU systems.

Request for Written Responses

No industry day is planned. Interested vendors shall submit their document as an attachment via email to jamie.fullinwider@usmc.mil and luis.larios@usmc.mil no later than 03 Nov 2025, 1300 Eastern Time Zone, for consideration.

Cover Page of RFI response should include the following:

1. Business Name

2. Business Size

3. Point of Contact Name

4. Business Address

5. Phone Number

6. Email Address

MCSC is requesting respondents answer the following Vendor Survey questions:

Vendor Survey for Variable Output Environmental Control Units

1. Provide a cost estimate for development and production of the items described in the "Design Criteria" section of this RFI. For estimating purposes, assume a total of 20 VECU Test Articles, 6 Low-Rate Initial Production (LRIP) systems, and 2,685 Production VECUs (or 1,904 36K and 781 60K systems). List the cost separately for the test articles, LRIP systems, production units, and non-recurring engineering costs.

2. Estimate the length of development time from contract award to delivery of test articles.

3. Estimate the monthly production rate/capacity.

mailto:jamie.fullinwider@usmc.mil

4. State whether your organization qualifies as a Small Business Administration (SBA) 8(a) Program, Historically Underutilized Business Zones (HUBZone) program, Service- Disabled Veteran- Owned Businesses, Small Disadvantaged Businesses, Small Business, or participant of the government Ability One Program as defined by the Small Business Administration.

5. Describe your personnel, facility, and infrastructure to support research and development, testing, and production efforts.

6. Provide examples of past performance related to subject of this RFI, including demonstrated capability to deliver products while managing Cost, Schedule, and Performance.

7. Identify design criteria you cannot meet at this time.

8. Describe how much cooling/heating can be produced using a three-phase 120/208VAC 30 ampere input and three phase 120/208VAC 60 ampere input using 2-stage compressor and Variable Frequency Drive compressor. Please provide a graph to show the estimations.

9. What are the typical harmonic profiles generated by variable speed compressors, and how can these harmonics be mitigated to minimize their impact on the generator's power quality and other connected equipment?

10. Describe any variable systems available at this time, that meet the design criteria outlined below, that are or will be commercially available within the next year. If none are available, then provide information on existing 36K & 60K BTU systems.

NOTE: This RFI is issued for the purpose of determining market capability of sources and does not constitute an Invitation for Bid (IFB), a Request for Proposal (RFP), a Request for Quote (RFQ) or an indication that the Government will contract for any of the items or services contained in this notice. No final solicitation document exists. Responses shall not include classified or proprietary material. Information with classified, “Proprietary," "Confidential," or other markings limiting distribution will not be reviewed. Responses to this notice will not be returned. No reimbursement will be made for any costs to provide information in response to this announcement or any follow-up information requests.

Information or statements contained herein are not binding upon the Government. All submissions become Government property and will not be returned.

Applicable Documents. The following documents may be applicable.

1. Government Documents

MIL-HDBK-454C General Guidelines for Electronic Equipment

MIL-STD-130 N(1)

NOT 1 Identification Marking of U.S. Military Property MIL-STD-209K Lifting and Tiedown Provisions

MIL-STD-461G Requirements for the Control of Electromagnetic Interference Characteristics of Subsystems and Equipment

SAE-AMS-STD-595 Colors Used in Government Procurement

MIL-STD-810H(1) Environmental Engineering Considerations and Laboratory Test

MIL-STD-1472H Human Engineering

MIL-STD-882E(1) NOT

1 System Safety

2. Non-Government Documents

ANSI Z535.4-2023 American National Standard for Product Safety Signs and Labels

AHRI-210/240 Unitary Air-Conditioning and Air-Source Heat, Pump Equipment, Standard for

ANSI/ASHRAE

Standard 34-2024 Designation and Safety Classification of Refrigerants

ANSI/ASHRAE

Standard 37-2024

Methods of Testing for Rating Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment

NFPA 70 National Electric Code UL 969 Standard for Marking and Labeling Systems

UL 60950-1 Information Technology Equipment – Safety – Part 1:

General Requirements

Design Criteria

The government is interested in a system that can meet or is close to meeting the criteria that follows. The government welcomes recommendations for changing/modifying the criteria if improvements can be gained in performance.

1. Weight. The weight of each VECU with a full refrigerant charge and all ancillary parts, including power cords, digital remote, and ducts, shall not exceed 560 lbs.

2. Dimensions. The dimensions of the VECU shall not exceed Length 47.6 inches x Width 37 inches x Height 47.4 inches. Dimensions include the storage of all ancillary components, including ducts, remote, and power cord stowed in the VECU.

3. Handling Provisions: The VECU must be movable by organic means over short distances on dry ground. The VECU may use an integral skid. Weight distribution of VECU components shall provide a safe and stable configuration in all likely operating positions. This feature should not be included at the expense of efficiency, reliability, or the specified dimensional constraints in the stowed configuration.

4. Lift provisions: The VECU shall be skid mounted for handling by standard USMC forklifts.

Each VECU shall be equipped with lift and tie-down provisions IAW MIL-STD-209K. The VECU must be stackable at least two high, with a capability for locking together stacked units at no more than a 10° incline.

5. Efficiency: The cooling Coefficients of Performance (COP) of the VECU shall be no less than those specified in the attachments at the rating conditions specified therein. It is desired that the Heating COP shall be no less than that specified in the attachments. It is highly desired that the COPs be higher than specified in the attachments.

6. Cooling Capacity: The variable cooling capacity and sensible heat ratio shall be a maximum of 6-TON BTU/hr. The current minimum net total cooling capacity and the current minimum sensible heat ratio is stated in the Interface Specification for 60 Hz operation. The VECU variable cooling capacity shall be specified and determined using the ANSI/ASHRAE STANDARD 37-2024 Room Air Enthalpy method, while operating against an external static pressure differential between the inlet and discharge at the shelter interface. A variable capacity feature which permits operation at reduced capacity and power draw during part load conditions is desired; example of this could be the compressor does not run at max load which will reduce power consumption. Cooling and heating capacity and COP shall be determined at the tent interface such that distribution losses between the VECU and shelter are included in the testing.

7. Evaporator airflow: The evaporator fan must be capable of operation at multiple user-selected flow rates.

8. High temperature operation: The VECU shall start and provide continuous cooling in an ambient temperature of 125ºF, with 125ºF air entering the evaporator and condenser sections.

9. Heating capacity: The minimum heating capacity of each VECU as measured at the specified rating point using AHRI-210/240, shall be as specified in the Interface Specification. Power consumption shall not exceed either 30 ampere or 60 ampere three-phase 120/208VAC. The current maximum power consumption is specified in the Interface Specification. Use of a variable refrigerant flow without electrical resistive backup and defrosting capability is highly desired. Electric resistive heating is only acceptable if for operation at the lower temperatures.

10. Low temperature operation: After being subjected to minus 25ºF (-25ºF) for a period of not less than four hours, each VECU shall start, operate and provide heating, and restart in the heating mode with air at-25ºF entering into the evaporator inlet.

11. Inclined operation: Each VECU shall be capable of operating without malfunction when the base of the VECU is positioned 10 degrees from the horizontal in any plane. During inclined operation, draining condensate shall be disposed of through the condensate drain line.

12. Condensate Draining: There shall be no evidence of moisture “carryover” in the airflow leaving the conditioned air outlet or from leakage. There shall be an exterior opening of the condensate drain possess a connector to allow for a drainage line to be installed during operation to direct condensate away from VECU and a plugging mechanism to prevent insect and debris intrusion during storage.

13. Electrical performance: The VECU shall operate as specified when supplied with up to +10% and down to –5% of the voltage. The input power will be 3-phase 120/208VAC, 60 Hz.

14. Power connector: The connector for power input to the VECU shall be either three-phase 30 ampere IEC309 connector or 60 ampere IEC309 connector. The power wires shall include a label, sticker, or placard at the plug indicating which conductor and plug jack corresponds to which voltage phase/ground/neutral.

15. Power conductor color-coding: Conductor ends shall be colored in green, white, black, red, and blue. The USMC color coding standard is: Green – Ground; White – Neutral; Black – Phase A; Red – Phase B; and Blue (or other off color)-Phase C.

16. Power Cables: Each VECU shall include a 30A or 60A power cable with a minimum 50ft length.

17. Capacity Control: It is desired that the VECUs be capable of actively modulating cooling and heating capacity to more efficiently control interior temperature. It is desired that the VECU include features to maximize efficiency during non-peak thermal loading.

18. Conditioned-air thermostat: The remote digital thermostat shall allow operators to regulate the conditioned space temperature to within a 10ºF band of the selected temperature between 60ºFto 90ºF. Thermostat bulb and capillary tubing (if used) shall withstand storage and transport in a temperature range of -50°F to 160ºF. It is desired the remote thermostat display “mode,” “set temperature” and “current temperature.”

19. High pressure cutout: VECU shall have automatic controls that de-energize or otherwise protect the compressor from discharge pressures exceeding the compressor manufacturer’s specified maximum operating pressure.

20. Low pressure cutout: VECU shall have automatic controls that de-energize or otherwise protect the compressor from operation when the suction pressure falls below the compressor manufacturer’s specified minimum operating pressure.

21. Heater high limit cutout: If resistive heater elements must be used, a switch shall automatically de-energize the heater system in the HEAT mode when the interior of the evaporator compartment reaches between 180ºF and 250ºF. All materials used in the evaporator compartment shall be able to withstand the maximum operating temperature without charring, becoming brittle, or otherwise becoming damaged.

22. Control Box: The VECU shall have a control box with a room thermostat, which shall be capable of operating the VECU both remotely and when installed on the VECU. No conductors connected to the remote-control box shall exceed 30 volts. The minimum length of cable for the remote shall be 25 feet long. Labels and markings on Marine operated components (primary control box and remote control) shall be in accordance with MIL-STD- 1472H.

23. Refrigerant system: The refrigerant used in the VECU shall be EPA-approved, have an ozone depletion potential (ODP) of zero, a LGWP <= 750 and be a non-PFAS. The refrigerant shall have a safety classification of “A1” in accordance with ANSI/ASHRAE

STANDARD 34-2024.

24. Pressure relief: The VECU shall have a mechanism to relieve refrigerant pressure in a safe location and manner in the event of an unmitigated pressure spike.

25. Service Ports: Two service connection ports, with standard fittings for the refrigerant used, shall be provided on the condenser section, one for high side (discharge) and one for low side (suction). The service connections shall be mounted in a protected or recessed area such that they can be accessed with the unit running and without affecting unit operation. Clearance shall be provided so that manifold gage hoses can be connected and disconnected to these service ports by gloved hands.

26. Sight glass: A sight glass with moisture indicator, located in a protected location connected between the Condenser and Expansion Valve, shall be provided and be visible on the installed

VECU.

27. Evaporator compartment air leakage: It is desired that the air leakage from the evaporator compartment does not exceed 20 standard cubic feet per minute (scfm) when the evaporator compartment is subjected to an internal static pressure of 1.0-inch water gauge (in wg) at the

VECU.

28. Condenser and Evaporator covers: It is desired that the VECU units have protective covers for the condenser air inlet and outlet during storage. It is desired that the VECU condenser coil be equipped with shading from direct solar radiation.

29. Distribution: Each VECU shall come with all necessary air distribution equipment (e.g.

ducts) as specified in the Interface Specification. Ducts, if used, should be insulated to minimize heat loss to the surrounding.

30. Fresh-air airflow: A built-in fresh-air system with a damper shall be provided on each model VECU. This feature shall provide fresh, filtered air from the exterior of the VECU.

When the evaporator is operating, outside air shall flow into the evaporator compartment when the damper is opened. When the damper is closed it shall positively seal off airflow with no leakage. It is desired that the fresh air system provide a means for enthalpy recovery.

31. Vibration: When subjected to MIL-STD-810H(1), Procedure I, General Vibration Procedure, Restrained Cargo Category, Transportation scenario (non-operational during the test), using the composite wheeled vehicle profile (category 4), the VECU shall show no evidence of structural damage, misalignment or malfunction of components, leaks, fractures, abnormal vibration, or any other irregular operation.

32. Electromagnetic Interference (EMI): The VECU shall meet all test method requirements specified herein, paragraphs 9.2.1 – 9.2.3, per MIL-STD-461G. When specific application requirements are specified in MIL-STD-461G, “Ground” and “Navy” shall apply unless specified otherwise.

33. Radiated: The electromagnetic field emissions shall not be radiated from the VECU or any interconnecting cables in excess of those shown in Method RE102, electric field, 2 MHz to 1 GHz. It is desired that VECU not exceed the maximum levels specified for ARMY ground equipment within the range of 10kHz to 18GHz.

34. Conducted: The conducted emissions on power leads shall not exceed the applicable values shown in Method CE102, power leads, 10 kHz to 10 MHz.

35. Susceptibility: If the VECU contain any circuit cards or electronic controls, the unit shall not be susceptible to conducted or radiated EMI in accordance with the following tests:

• Method CS101, power leads, second harmonic to 150 kHz.

• Method CS114, bulk cable injection, 10 kHz to 200 MHz.

• Method RS103, electric field, 30 MHz to 18 GHz.

36. Noise: The acoustic noise levels produced by the VECUs shall not exceed the following limits:

• The emitted sound pressure level on the evaporator side less than 65 dB(A) re: 20 µPa at one meter from any point on the perimeter of the evaporator side of the housing

• The emitted sound pressure level on the condenser side less than 85 dB(A) re: 20 µPa at one meter from any point on the perimeter of the condenser side of the VECU.

37. Chemical Biological, Radiation and Nuclear: Each VECU air system shall be designed such that it inherently protects the conditioned air space from the contamination by CBRN agents located at the exterior of the shelter. Each VECU shall be cable of passing a Static Vapor Challenge test using a Methyl Salicylate (MeS) simulation agent when subjected to the challenge with a 0.5 inwg overpressure in the Toxin Free Area (indoor side).

38. Reliability: The Mean Time Between Failure (MTBF) shall be no less than 2100 hours demonstrated at 80% confidence. The expected service life of the VECU is 10 years without any major overhaul.

39. Maintainability: The maintenance ratio shall be no greater than 0.017 hours of maintenance for each hour of operation.

40. Maintenance Access: The VECU shall be maintainable through exterior access panels using only Marine Corps Standard tools. Equipment design and installation should provide the maintainer with complete visual and physical access and a favorable working level for all parts of a system on which maintenance is performed, including interfaces, support equipment interfaces, access openings, adjustment points, test points, servicing points, and connections.

41. Electrical Safety: The VECU shall be designed so that under all conditions of normal use (installation, operation, and maintenance) and under a likely fault condition (including human error), it protects against the risk of electric shock and other hazards (such as hot /cold thermal burns). Utilizing MIL-STD-882E(1) NOT 1terminology, “catastrophic” or “critical” hazards shall not rely solely on warnings, cautions, or procedures/training for control of risk.

All safety hazards not eliminated through design shall be addressed in the appropriate technical manuals. Information regarding hazard-avoiding procedures and safety warning labels on equipment shall be included in all manuals.

• Voltage: Operators shall not have access to components with voltages exceeding 30V. The operator will not be exposed to energy shock at the disconnecting means.

• Contact: Protection will be provided to personnel during maintenance and repair to prevent unintentional contact with voltages exceeding 30V. Capacitors shall be discharged to less than 30V and 20J energy prior to maintainer access.

• Lockout: The VECU units shall have the means to utilize lock out and tag out components to prevent unintended start up. The remote-control panel shall have the means of a quick disconnect so that remote operation during maintenance activities will not occur.

• Grounding: Equipment shall include a grounding in accordance with NFPA 70 Electrical Safety Code.

42. Identification plate: The identification plate shall be permanently attached to the housing in a location where it is visible. It is desired that a single identification plate includes the following information:

A Item Name B Manufacturer’s name C Table of Authorized Materiel Control Number (TAMCN) D Item Description (e.g., Variable Environmental Control Unit, #####

BTU/HR, 120/208VAC 3-PH, 60 HZ)

E Model Number F Serial number G Date of manufacture (e.g., MAR 2026) H Contract number I National Stock Number (NSN) J Type of refrigerant (e.g., R-XXXX) K The refrigerant charge amount (e.g., # LB # OZ) L Unit Weight (e.g., ### LB) M Notice of Warranty including duration N Item Unique Identification (IUID)

43. Safety markings and labels: Safety markings and labels, in accordance with ANSI Z535.4- 2023 and MIL-STD-1472H, shall be provided identifying any potential hazards to personnel.

Safety labels shall comply with the durability requirements of UL 60950-1, paragraph 1.7.15 and/or UL 969. Voltages in excess of 30V shall use the signal word “WARNING.”

Markings shall be readily visible.

44. Item Unique Identification: All VECUs delivered may be serialized and marked per the requirements for IUID specified in MIL-STD-130 N(1) NOT , construct 2.

45. Permanency and Legibility: The IUID marking and identification plates shall be as permanent as the normal life expectancy of the item and be capable of withstanding the environmental test and cleaning procedures specified for the item. Legibility shall be as required for ready readability per MIL-STD-130 N(1) NOT .

46. Material protection: The VECU shall be fabricated from compatible materials, inherently corrosion resistant or treated to provide protection against the various forms of corrosion and deterioration that may be encountered in any of the applicable operating and storage environments to which the VECU may be exposed. Dissimilar metals shall not be used in intimate contact with each other unless protected against galvanic corrosion. Considerations for material protection shall include to below IAW MIL-STD-810H(1):

• Sand

• Dust

• Rain Intrusion

• Humidity

• Salt Fog

47. Externally exposed surfaces: It is highly desired that all externally exposed surfaces of the VECU shall be cleaned and treated or painted unless otherwise specified herein. It is desired that surfaces which Marines will come in contact with not contain sharp edges. It is desired that the paint complies with SAE-AMS-STD-595 green 383, color number 34094 or tan 686A, color number 33446.

48. Interior surfaces: The interiors of the condenser, evaporator, and control box shall be treated for corrosion protection. All sheet metal interior to VECU, i.e., fan shrouds, ducts, brackets, etc. shall be cleaned and treated.

Acronyms

ACRONYM DEFINITION

ANSI American National Standards Institute ASHRAE American Society of Heating, Refrigeration, and Air

Conditioning Engineers BTU/h British Thermal Units per hour COP Coefficient Of Performance CPP Critical Performance Parameter dB(A) Decibels, A-weighted VECU Variable Environmental Control Unit ECU Environmental Control Unit (interchangeable with VECU) EMI Electromagnetic Interference EPA Environmental Protection Agency

FED-STD Federal Standard GHz Gigahertz Hz Hertz

IAW In accordance with IEC International Electrotechnical Commission IS Interface Standard

IUID Item Unique Identification kHz Kilohertz MHz Megahertz

MIL-STD Military Standard NEC National Electric Code

NFPA National Fire Protection Association NSN National Stock Number ODP Ozone Depletion Potential SOW Statement of Work THD Total Harmonic Distortion UL Underwriters Laboratories V Volt

Attachments/Links

Specifications, Environmental Control Unit, 3-TON, 36,000 BTU/hr.

OVERALL

Current 1 Maximum Dimensions (in) L x W x H L1 < 53.0, L2 < 42.0, H < 43.0 2 Maximum Gross Weight (lbs.) 472 3 Mounting Skid with integral forklift pockets 4 Refrigerant R-407C 5 Operating Temperature Range (°F) Heating: -25 to 80, Cooling: +50 to 125

PERFORMANCE

6a Cooling Capacity, minimum (BTU/h) 36,000 6b SEER 9.44 6c Coefficient of Performance 1.50 7 Power, Cooling Mode, Maximum (W) 7000 8 Current, Maximum, All Modes (A) 23.0 9 Heating Capacity (BTU/h) 31,000 10 Heating Seasonal Performance Factor per

ANSI/AHRI-210/240-2008

5.0

11 Rating Conditions (ºF)

IDDB/IDWB/ODDB

Cooling: 90/75/125 Heating: 47/43/70

12 Minimum Sensible Heat Ratio 0.73 13 Evaporator Airflow Static Pressure (inwg) Not Specified 14 Evaporator Airflow Rate (SCFM) 1,325 15 Noise Level, Tent Side, Installed (dBA) 65 16 Noise Level, Condenser Face (dBA) 85

INSTALLATION

17 Mounting Points Skid-mounted 18 Fresh Air Intake Location Filtered, on outdoor face, at least 24 inches from the ground plane 19 Condensate Drain Removable 10 ft hose with tethered plug 20 Max Incline Angle 10 degrees in any direction 21 Flexible Duct Length (ft) 10.0 22 Duct Diameter (in) 12.0

TRANSPORTABILITY

23 Forklift Pocket Dimensions (in) Minimum Tine Thickness: 2.63

Minimum Tine Width: 8.13 Minimum Spread, Inside to Inside: 18.0 Minimum Spread, Outside to Outside: 34.0

24 Tie Down Four tie-down provisions IAW MIL-STD-209K_ 25 Sling Lift Provisions Four crane lift provisions IAW MIL-STD-209K_ 26 Stackability 2-high 27 Transport Modes All USMC transportation assets, as secured cargo

AIRFLOW

28 Minimum Evaporator Airflow (SCFM) TBD by Design, Multi-speed blower desired 29 Fresh Air Flow (SCFM) Adjustable to 280 maximum 30 Static Pressure Rating Point (inwg), Ducts

Installed 0.0

Specifications, Environmental Control Unit, 5-TON, 60,000 BTU/hr.

Current 1 Maximum Dimensions (in) L x W x H L1 < 53.0, L2 < 42.0, H < 48.0 2 Maximum Gross Weight (lbs.) 560 3 Mounting Skid, with integral forklift pockets 4 Refrigerant R-407C 5 Operating Temperature

Range (°F) Heating: -25 to 80 Cooling: +50 to 125

6a Cooling Capacity, minimum (BTU/h) 60,000 6b SEER 9.44 6c Coefficient of Performance 1.70 7 Power, Cooling Mode, Maximum (W) 11,200 8 Current, Maximum, All Modes (A) 36.0 9 Heating Capacity (BTU/h) 54,200 10 Heating Seasonal Performance Factor per ANSI/AHRI-210/240-2008 6.0

11 Rating Conditions (ºF)

IDDB/IDWB/ODDB

Cooling: 90/75/125 Heating: 47/43/70

12 Minimum Sensible Heat Ratio 0.75 13 Evaporator Airflow Static Pressure

(inwg)

0.0 (ducts installed)

14 Evaporator Airflow Rate (SCFM) 2,000 15 Noise Level, Tent Side, Installed (dBA) 65 16 Noise Level, Condenser Face (dBA) 85 17 Mounting Points Skid-mounted 18 Fresh Air Intake Location Filtered, on outdoor face, at least 24 inches from the ground plane 19 Condensate Drain Removable 10 ft hose with tethered plug 20 Max Incline Angle 10 degrees in any direction 21 Flexible Duct Length (ft) 10.0 22 Duct Diameter, ID (in) 16.0 23 Forklift Pocket Dimensions (in) Minimum Tine Thickness: 2.63

Minimum Tine Width: 8.13 Minimum Spread, Inside to Inside: 18.0 Minimum Spread, Outside to Outside: 34.0

24 Tie Down Four tie-down provisions IAW MIL-STD-209K_ 25 Sling Lift Provisions Four crane lift provisions IAW MIL-STD-209K_ 26 Stackability 2-high 27 Transport Modes All USMC transportation assets, as secured cargo

General Background
Request for Written Responses
Vendor Survey for Variable Output Environmental Control Units
1. Government Documents
2. Non-Government Documents
1. Weight. The weight of each VECU with a full refrigerant charge and all ancillary parts, including power cords, digital remote, and ducts, shall not exceed 560 lbs.
2. Dimensions. The dimensions of the VECU shall not exceed Length 47.6 inches x Width 37 inches x Height 47.4 inches. Dimensions include the storage of all ancillary components, including ducts, remote, and power cord stowed in the VECU.
4. Lift provisions: The VECU shall be skid mounted for handling by standard USMC forklifts. Each VECU shall be equipped with lift and tie-down provisions IAW MIL-STD-209K. The VECU must be stackable at least two high, with a capability for locking ...
17. Capacity Control: It is desired that the VECUs be capable of actively modulating cooling and heating capacity to more efficiently control interior temperature. It is desired that the VECU include features to maximize efficiency during non-peak t...
35. Susceptibility: If the VECU contain any circuit cards or electronic controls, the unit shall not be susceptible to conducted or radiated EMI in accordance with the following tests:
Method CS101, power leads, second harmonic to 150 kHz.
Method CS114, bulk cable injection, 10 kHz to 200 MHz.
Method RS103, electric field, 30 MHz to 18 GHz.