RFB946600-01 DOC 3JD CBC New Backup Generator - Drawings.pdf

PDF 4 MB Posted

Attached to
DOC 3JD CBC New Backup Generator
Solicitation number
005-RFBCON-1971-2026
Issued by
Scott County, Iowa

About this file

Summary of RFB 946600-01 DOC 3JD CBC New Backup Generator - Drawings

This is a set of electrical construction drawings prepared by KCL Engineering for the Iowa Department of Administrative Services for the installation of a new backup generator system at the DOC 3JD Community-Based Corrections facility located at 515 Water Street in Sioux City, Iowa 51103. The project involves the procurement and installation of a 250 kilowatt diesel standby generator with a 24-hour base day fuel tank, automatic transfer switch (ATS), and associated electrical infrastructure to provide backup power for the entire building during utility outages. The generator system is designed to comply with NFPA 110 and NEC Section 702 standards and is classified as non-life-safety backup power only. Key project elements include relocating an existing 60-ton condensing unit to accommodate the new generator pad, downsizing the existing electrical service from 2000 amperes to 1100 amperes, installing new grounding electrode systems with dual 10-foot ground rods, and extending service conductors to the new automatic transfer switch. The project includes demolition of existing electrical facilities, installation of a new concrete generator pad with reinforced specifications, conduit routing along exterior walls, and integration with the existing Siemens building management system, which will be reprogrammed to delay the condensing unit start by five minutes when generator power is active. A pre-bid meeting is scheduled for July 30, 2025, with construction anticipated to begin June 15, 2026.

The electrical drawings specify that all work must comply with current state electrical codes and the Americans with Disabilities Act (ADAAG), with local officials verifying code compliance during permitting. The project requires two separate utility shutdowns coordinated with MidAmerican Energy: Shutdown #1 involves replacing service fuses and reconnecting existing service conductors to the ATS during a maximum four-hour outage between 9 AM and 3 PM, while Alternate #1 (Shutdown #2) provides an option to salvage existing conductors no longer in use during a maximum three-hour outage. The electrical contractor is responsible for providing arc flash calculations, labeling, and documentation for both the new main distribution panel (MDP) and existing MDP upon project completion. Additional contractor responsibilities include sealing all wall, floor, ceiling, and roof penetrations in accordance with fire-rated assembly standards, balancing panel loads during installation, providing typed panel directories for all modified circuits, and coordinating work timing and traffic control with the City of Sioux City. The project includes provisions for a battery heater, block heater with 120-volt circuits utilizing spare breakers in the existing panel, a generator annunciator panel at the reception desk, and an emergency power-off (EPO) button at the electrical room entrance.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

7/17/2025 8:36:11 AM

100% CD

07/18/2025

AG00

STATE OF IOWA DEPARTMENT OF ADMINISTRATIVE SERVICES

DOC 3JD CBC NEW BACKUP GENERATOR

PROJECT #: RFB 946600-01

SHEET LIST

Sheet Number Sheet Name

AG00 TITLE SHEET

E000 ELECTRICAL GENERAL NOTES & SYMBOLS

E001 ELECTRICAL SITE PLAN

ED101 ELECTRICAL DEMO

E101 ELECTRICAL POWER

E401 ELECTRICAL ONE-LINE DIAGRAM

E501 ELECTRICAL DETAILS

TITLE SHEETTITLE SHEET

OWNER

IOWA DEPARTMENT OF ADMINISTRATIVE SERVICES

109 SE 13TH STREET

DES MOINES, IA 50319

OWNER PROJECT NUMBER: 9466.00

OWNER REP: JENNIE ELLIOT

CONSTRUCTION MANAGER

ROB GREINER - PROJECT MANAGER

BOYD JONES CONSTRUCTION COMPANY

rgreiner@boydjones.biz 515-650-7777

CM PROJECT NUMBER: 015PC

ENGINEER

ERIC HEYNEN, PE

KCL ENGINEERING

eheynen@kclengineering.com 515-300-8092 ENGINEER PROJECT NUMBER: 25108.00 I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that i am a duly licensed Professional Engineer under the laws of the State of Iowa

(signature)

License Number :

Pages or sheets covered by this seal:

(date)

My license renewal date is December 31, E N

G N

E E

R I

AOFESSION

S E

D

PR

AI O W

L

IC

E N

L

ERIC HEYNEN, P.E.

ERIC

HEYNEN

E. Sheets

P24706P24706

07-18-2025

CONDUIT SLEEVE

CONDUIT UP, REFER TO TAG ON DRAWING FOR SIZE

CONDUIT DOWN, REFER TO TAG ON DRAWING FOR SIZE

CIRCUIT HOMERUN, CONCEALED CONDUIT OR CABLE

CIRCUIT HOMERUN, UNDER FLOOR CONDUIT OR CABLE

EQUIPMENT IDENTIFICATION TAG. REFER TO EQUIPMENT CONNECTION SCHEDULE

DETAIL DRAWING REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE

INTERIOR ELEVATION DRAWING REFERENCE TAG

GENERAL SYMBOLS

A101

SIM

A101 1

R e f

KEYNOTE#

XXX

X

SHEET REFERENCE

SECTION CUT REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE

SHEET REFERENCE

JUNCTION BOX, CEILING OR FLOOR MOUNTED.

JUNCTION BOX, WALL MOUNTED, ELEVATION AS NOTED.

J

J

A101

SIM

1 DRAWINGS REVISION. REFER TO TITLEBLOCK FOR REVISION NAME AND DATE

POWER SYMBOLS

DUPLEX RECEPTACLE, WALL MOUNTED, TAMPER-RESISTANT

EQUIPMENT CONNECTION,

REFER TO EQUIPMENT CONNECTION SCHEDULE FOR CONNECTION TYPE.

REFER TO PANEL SCHEDULES FOR GFCI PROTECTION WHERE REQUIRED

UTILITY TRANSFORMER

UTILITY METER

SURGE PROTECTIVE DEVICE

SAFETY DISCONNECT SWITCH

M

PANELBOARD - SURFACE MOUNTED

PANELBOARD - RECESSED IN WALL

J CORD REEL, CEILING MOUNTED - REFER TO DETAIL

DISTRIBUTION PANELBOARD/SWITCHBOARD - SURFACE MOUNTED AS NOTED.

T

SPD

GENERATOR

MULTI-GROUND ROD ELECTRODE SYSTEM

GEN

MOTOR CONNECTION,

REFER TO EQUIPMENT CONNECTION SCHEDULE FOR CONNECTION TYPE.

REFER TO PANEL SCHEDULES FOR GFCI PROTECTION WHERE REQUIRED

M

AUTOMATIC TRANSFER SWITCHATS

ELECTRICAL ABBREVIATIONS

A DEVICE MOUNTED +8" ABOVE

COUNTER TOP (VERIFY LOCATION)

AFF ABOVE FINISHED FLOOR

ATS AUTOMATIC TRANSFER SWITCH

C CEILING

CB CIRCUIT BREAKER

CT CURRENT TRANSFORMER

E EXISTING ITEM TO REMAIN

EC ELECTRICAL CONTRACTOR

EM EMERGENCY LIGHT FIXTURE

ER NEW LOCATION OF EXISTING ITEM

F ROUGH IN FOR FUTURE DEVICE

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FSD FIRE SMOKE DAMPER

G GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

KVA KILO-VOLT-AMPERES

KW KILOWATTS

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MDP MAIN DISTRIBUTION PANEL

MLO MAIN LUGS ONLY

N NEW DEVICE IN EXISTING LOCATION

NIC NOT IN CONTRACT

NM NONMETALLIC

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED

CONTRACTOR INSTALLED

OFOI OWNER FURNISHED,

OWNER INSTALLED

R EXISTING ITEM TO BE REMOVED

RR EXISTING ITEM TO BE REMOVED AND

RELOCATED

RN EXISTING ITEM TO BE REMOVED AND

REPLACED WITH NEW

SCCR SHORT CIRCUIT CURRENT RATING

T TAMPER PROOF DEVICE

TCC TEMPERATURE CONTROL CONTRACTOR

TV TELEVISION

TYP TYPICAL

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLTS

VA VOLT-AMPERES

WG WIREGUARD COVER

WP WEATHERPROOF DEVICE

WR WEATHER RESISTANT DEVICE

+24" INDICATES MOUNTING HEIGHT CENTER

LINE OF DEVICE TO FINISHED FLOOR

1. PROVIDE ELECTRICAL INSTALLATION IN ACCORDANCE WITH ALL STATE CODES.

2. THE CURRENT ADOPTED EDITION OF THE ELECTRICAL CODE IS THE STANDARD FOR THE

ELECTRICAL INSTALLATION. VERIFY WITH LOCAL OFFICIALS WHEN PERMITS ARE OBTAINED.

NOTIFY DESIGN TEAM OF ANY DISCREPANCIES BETWEEN THE PROJECT MANUAL OR

DRAWINGS AND THE GOVERNING CODE.

3. INSTALLATION SHALL FOLLOW REQUIREMENTS OF THE ADAAG –AMERICANS WITH

DISABILITIES ACT.

CODE NOTES - ELECTRICAL

1. INSTALL NEW STANDBY GENERATOR FOR THE ENTIRE BUILDING.

2. GENERATOR TO COMPLY WITH NFPA 110 AND NEC SECTION 702. THIS GENERATOR IS NOT

PROVIDED FOR LIFE SAFETY AND WILL ONLY BE UTILIZED FOR BACKUP POWER.

3. EXISTING LIFE SAFETY SYSTEM (EMERGENCY LIGHTING AND FIRE ALARM) TO REMAIN INTACT AND

OPERATIONAL DURING CONSTRUCTION.

4. EXISTING ELECTRICAL SERVICE IS BEING DOWNSIZED FROM 2000A TO 1100A.

5. RELOCATE CONDENSING UNIT TO MAKE WAY FOR NEW GENERATOR.

6. THE OWNER WILL REPROGRAM SIEMENS DDC SYSTEM TO LAPSE START OF 60 TON CONDENSING

UNIT WHEN ON GENERATOR POWER.

7. ALTERNATE #1: SALVAGE EXISTING SERVICE CONDUCTORS NO LONGER IN USE. REFER TO MORE

NOTES ON SHEET E401.

8. AT PROJECT COMPLETION, ELECTRICAL CONTRACTOR WILL BE RESPONSIBLE TO PROVIDE ARC FLASH CALCULATIONS, LABELING, AND DOCUMENTATION FOR THE "MDP" AND "EXISTING" MDP.

SCOPE

1. INCREASE CONDUCTOR SIZES ON 20A 120V-1 PHASE CIRCUITS EXCEEDING 100 FEET TO

CENTER OF LOAD TO ACCOUNT FOR VOLTAGE DROP.

2. RACEWAYS AND BOXES ARE SHOWN DIAGRAMMATICALLY ONLY AND INDICATE GENERAL

AND APPROXIMATE LOCATIONS. LAYOUTS DO NOT ALWAYS SHOW THE TOTAL NUMBER

OF RACEWAYS OR BOXES FOR THE CIRCUITS REQUIRED, NOR ARE THE LOCATIONS OF

INDICATED RUNS INTENDED TO SHOW THE ACTUAL ROUTING OF THE RACEWAYS.

3. LIGHT FIXTURES, SWITCHES, DEVICES, ETC. ARE SHOWN IN PREFERRED LOCATION.

MODIFY CONDUIT, HANGERS, CIRCUITING, ETC. TO PROVIDE A COMPLETE AND

OPERATIONAL SYSTEM.

4. PROVIDE A DEDICATED GREEN INSULATED GROUND CONDUCTOR TO ALL DEVICES. DO

NOT USE CONDUIT SYSTEM AS THE ONLY EQUIPMENT GROUNDING METHOD.

5. DO NOT INSTALL BOXES BACK-TO-BACK ON OPPOSITE SIDES OF THE SAME WALL.

MAINTAIN MINIMUM OF 8” DISTANCE BETWEEN BOXES WHEREVER APPLICABLE.

6. BALANCE PANEL LOADS DURING INSTALLATION. CIRCUIT NUMBERING SHOWN ON PLANS

MAY BE ADJUSTED TO ACCOMMODATE.

7. PROVIDE TYPED PANEL DIRECTORY AT PROJECT COMPLETION FOR NEW PANELS AND

EXISTING PANELS WITH CIRCUITS MODIFIED DURING PROJECT. USE OWNER’S CURRENT

ROOM NUMBERS AND EQUIPMENT NAMES. PROVIDE UNIQUE CIRCUIT IDENTIFICATION

PER NEC 408.4(A)

8. CONTRACTOR IS RESPONSIBLE FOR OPENINGS IN WALLS, FLOORS, CEILINGS, AND

ROOFS THAT ARE REQUIRED TO COMPLETE THEIR SCOPE OF WORK. SEAL

PENETRATIONS IN ACCORDANCE WITH THE RATING OF THE AFFECTED ASSEMBLY.

REFER TO ARCHITECTURAL CODE PLAN FOR RATED WALLS, FLOORS, AND CEILINGS.

INSTALLATION NOTES - ELECTRICAL

Drawing #:

Date:

Project No:

© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.

P lo t D a te

T im e

Drawing Name:

info@kclengineering.com

300 4th Street West Des Moines, Iowa 50265 515.724.7938

/1

/2

:3 :1

A

M

E000

100% CD

07/18/25

9466.00

IO

W

A D

A S

D O

C

J D

C B

C N

E W

B A

C K

U P

G E

N E

R A

T O

R

W a te r S t, S io u x C it y

IA

ELECTRICAL GENERAL

NOTES & SYMBOLS

# Revision Date

5TH STREET

W A

T E

R S

T

EXISTING TEST

WELL LOCATION

EXISTING

BUILDING

APPROXIMATE LOCATION OF

EXISTING FIBER OPTICS AND

COMMUNICATIONS. FIELD VERIFY

LOCATIONS

SITE GENERAL NOTES

A. UTILITIES SHOWN ARE FROM THE PREVIOUS CONSTRUCTION DOCUMENTS.

ALL LOCATIONS SHOULD BE CONSIDERED APPROXIMATE. AS-BUILT

DOCUMENTS WERE NOT PROVIDED. VERIFY ALL SITE CONDITIONS AND

DIMENSIONS ON SITE.

B. NEW WORK SCOPE IS UNDERLINED AND BOLD ON PLAN.

C. PROVIDE TRENCHING, PULL BOXES, BACKFILL, AND PATCHWORK AS

REQUIRED TO COMPLETE SITE ELECTRICAL INSTALLATION.

D. REPAIR ALL AFFECTED SURFACES AND RESTORE TO EXISTING CONDITIONS

AT COMPLETION OF PROJECT.

E. PROVIDE ALL SITE CONDUIT AS 1" MINIMUM, ALL CONDUCTORS AS #10 AWG

CU. MINIMUM.

F. WARNING - CALL BEFORE YOU DIG: LAW REQUIRES ANYONE DOING

EXCAVATION, FENCING, PLANTING OR DRILLING TO CALL 48 HOURS IN

ADVANCE. HAND DIG WITHIN 18 INCHES OF ANY LOCATE MARK OR FLAG.

ONE-CALL 811

GENERAL NOTE:

UNDERGROUND FACILITIES, STRUCTURES, AND UTILITIES HAVE BEEN SHOWN BASED UPON

INFORMATION OBTAINED FROM FIELD LOCATIONS BY UTILITY COMPANIES, AVAILABLE SURVEYS

AND RECORDS. THEIR LOCATIONS MUST BE CONSIDERED APPROXIMATE ONLY. IT IS ALSO

POSSIBLE THAT THERE MAY BE OTHER UNDERGROUND FACILITIES, STRUCTURES, AND UTILITIES IN

EXISTENCE THAT ARE NOT SHOWN. IT IS THE RESPONSIBILITY OF EACH INDIVIDUAL PARTY

REFERENCING THIS PLAN TO DETERMINE THE EXACT LOCATION AND TYPE OF UNDERGROUND

FACILITIES ON THE SITE. HAND EXCAVATE AT CRITICAL POINTS AS NECESSARY TO VERIFY

LOCATIONS, SIZES, ELEVATIONS, FLOW LINES, ETC. IF A PROBLEM OR INTERFERENCE EXISTS, NOTIFY ARCHITECT/ENGINEER BEFORE PROCEEDING.

IOWA

ONE CALL

1-800-292-8989

CALL - BEFORE - YOU - DIG

Drawing #:

Date:

Project No:

© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.

P lo t D a te

T im e

Drawing Name:

info@kclengineering.com

300 4th Street West Des Moines, Iowa 50265 515.724.7938

/1

/2

:3 :1

A

M

E001

100% CD

07/18/25

9466.00

IO

W

A D

A S

D O

C

J D

C B

C N

E W

B A

C K

U P

G E

N E

R A

T O

R

W a te r S t, S io u x C it y

IA

ELECTRICAL SITE

PLAN

NOT TO SCALE

EXISTING SITE PLAN

NEW LOCATION OF

DIESEL GENERATOR

EXISTING UTILITY

TRANSFORMER TO REMAIN

APPROXIMATE

LOCATION OF CRANE

AND FUEL TANK.

COORDINATE TRAFFIC

SIGNALING, TIMING,

AND REQUIREMENTS

WITH THE CITY OF

SIOUX CITY.

# Revision Date

PROTECT LAWN FROM

EQUIPMENT BEING

USED

A. DEMOLITION DRAWINGS PRESENT LAYOUT OF EXISTING

CONDITIONS AND MAJOR ELECTRICAL ITEMS. FIELD VERIFY

EXISTING CONDITIONS AND BECOME FAMILIAR WITH EXISTING

ELECTRICAL SYSTEM AND DEMOLITION SCOPE BEFORE WORK

BEGINS. CONTRACTOR SHALL NOTE EXISTING CONDITIONS AND

NOTE DAMAGE BEFORE STARTING WORK.

B. ADDITIONAL COMPONENTS MAY EXIST WHICH ARE NOT SHOWN.

HANDLE SUCH ITEMS IN A MANNER SIMILAR TO THOSE ITEMS

WHICH ARE SHOWN.

C. REMOVE ELECTRICAL FACILITIES AND CLEAR THE AREA TO

RECEIVE THE NEW WORK.

a. REMOVE AND REINSTALL CEILING TILES AS REQUIRED

TO REMOVE THE ELECTRICAL FACILITIES NOTED.

REPLACE CEILINGS TILES DAMAGED DURING

DEMOLITION.

b. KEEP EXISTING SYSTEMS OPERATIONAL DURING ALL

PHASES OF CONSTRUCTION UNLESS NECESSARY FOR

DEMOLITION.

c. OBTAIN OWNER AND CM PERMISSION TO SHUT OFF

SERVICES 2 WEEKS IN ADVANCE OR SYSTEMS WHICH

MAY AFFECT OTHER AREAS BEYOND DEMOLITION AREA.

INFORM OWNER AS TO THE REASON FOR AND THE

DURATION OF THE SHUTDOWN.

d. REPAIR AT CONTRACTORS EXPENSE ANY DAMAGED

CONDUIT OR WIRE NOT IDENTIFIED FOR DEMOLITION.

D. ALL WIRING FOR REMODELED AREAS SHALL BE NEW UNLESS

SPECIFICALLY NOTED OTHERWISE.

E. PROTECT EXISTING DEVICES IDENTIFIED TO REMAIN OR BE

RELOCATED. IF AN EXISTING DEVICE CANNOT BE REINSTALLED

NOTIFY DESIGN TEAM DURING DEMOLITION. REPLACE

FUNCTIONING ITEMS DAMAGED DURING DEMOLITION.

ELECTRICAL DEMOLITION NOTES

EXISTING ELECTRICAL

TRANSFORMER LOCATION

QUIET LOUNGE

101A

CHECK IN

VEST

STOR

MECH

MECH

EXISTING 60 TON ACCU

EXISTING LINES TO REMAIN

REMOVE REFRIGERANT LINES BACK TO APPROXIMATE

LOCATION AND READY FOR REINSTALLATION.

CUT EXISTING 6" PAD AS NECESSARY

TO READY AREA FOR NEW CONCRETE

PAD REQUIRED FOR GENERATOR

EXISTING MDP

OLD MDP

REMOVE/SALVAGE

EXISTING

CONDENSING UNIT

FOR RELOCATION

ISOLATE REFRIGERANT OR PROVIDE

ADDITIONAL REFRIGERANT AS REQUIRED

FOR CU RELOCATION. DRAIN AND REUSE

IF POSSIBLE.

REMOVE/SALVAGE

EXISTING

DISCONNECT AND

RELOCATE WITH

CONDENSING UNIT

5' - 4"

7' - 0"

EXISTING PANEL D

EXISTING PANEL 1A

APPROXIMATE

LOCATION OF EXISTING

SERVICE ENTRANCE

CONDUCTORS

Drawing #:

Date:

Project No:

© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.

P lo t D a te

T im e

Drawing Name:

info@kclengineering.com

300 4th Street West Des Moines, Iowa 50265 515.724.7938

/1

/2

:3 :1

A

M

ED101

100% CD

07/18/25

9466.00

IO

W

A D

A S

D O

C

J D

C B

C N

E W

B A

C K

U P

G E

N E

R A

T O

R

W a te r S t, S io u x C it y

IA

ELECTRICAL DEMO

1/4" = 1'-0"

DEMO PLAN

POWER GENERAL NOTES

A. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND ELECTRICAL

WORK WITH ALL OTHER TRADES. NO ASPECT OF A SYSTEM INSTALLATION

OR ITS ROUGH-IN SHALL COMMENCE UNTIL PROPER AND TIMELY

COORDINATION WITH ALL TRADES ASSOCIATED WITH THE INSTALLATION HAS

TRANSPIRED. ITEMS TO BE COORDINATED SHALL INCLUDE BUT NOT BE

LIMITED TO: BUILDING STRUCTURE, SHEET METAL, PIPING SYSTEMS, LIGHT

FIXTURES, CONDUITS, CABLE TRAYS, ETC. REFER TO ALL GENERAL,

MECHANICAL, AND ELECTRICAL DRAWINGS AND SPECIFICATIONS FOR THIS

PROJECT.

B. COORDINATE ELECTRICAL REQUIREMENTS FOR MECHANICAL UNITS WITH

MECHANICAL CONTRACTOR AND FINAL MECHANICAL SHOP DRAWINGS.

C. PROVIDE PENETRATIONS REQUIRED FOR ROUTING RACEWAYS THROUGH

THE BUILDING. COORDINATE FIRE RATED WALL PENETRATIONS AND

PROVIDE CONDUIT SLEEVES AND FIRE STOPPING TO MAINTAIN RATING.

EXISTING

ELECTRICAL

TRANSFORMER

LOCATION

OWNER TO REPROGRAM UNIT TO

DELAY 5 MINUTES AFTER UTILITY

LOSS OF POWER WITHIN DDC

SYSTEM. EXISTING SYSTEM IS

SIEMENS.

REPLACE EXISTING

FUSES. REFER TO ONE-LINE

FOR MORE INFORMATION

OLD MDP

MDP

EXISTING PANEL 1A

QUIET LOUNGE

VEST

101A

CHECK IN

STOR

MECH

OFFICE

MECHANICAL

MECH

LNDRY

197A

DINING

197B

KITCHEN

147A

CORRIDOR

RECREATION

149B

COMP

DORM

166A

RCP

166B

CONTROL

GENERATOR ANNUNCIATOR

PANEL INSTALLED AT RECEPTION

DESK WALL. INSTALL IN GYP WALL.

INSTALL AT 40" TO CENTER OF BOX.

INSTALL EPO BUTTON FOR

GENERATOR AT ENTRANCE

TO ELECTRICAL ROOM. ALL

OTHER LOCATIONS NEAR GENERATOR

ARE OPEN TO GENERAL PUBLIC.

120V BATTERY HEATER

H-39

CONFIRM POWER

REQUIREMENTS WITH

MANUFACTURER

120V BLOCK HEATER

H-41

ATS

INSTALL NEW ATS ABOVE EXISTING

PAD. INSTALL 6" ABOVE PAD ON

UNISTRUT WITH COVER FOR ACCESS

TO EXISTING HATCH. EXISTING PAD IS 30"

DEEP X 37" WIDE.

EXISTING 60 TON ACCU

INSTALL NEW CONCRETE

PAD TO MATCH HEIGHTS OF

EXISTING SO THAT EXISTING

ACCU CAN BE RELOCATED TO

THE NORTH TO MAKE WAY FOR

GENERATOR. INSTALL 6X6-6/6

WELDED WIRE FABRIC OR REBAR

EQUIVALENT IN PAD.

RELOCATE ACCU 4' TO THE

NORTH.

REUSE DISCONNECT.

INSTALL JUNCTION BOX AT END

OF STUBBED CONDUIT. EXTEND

CONDUIT/CONDUCTORS FROM

DISCONNECT TO UNIT AS

NECESSARY.

PROVIDE NEW/REVISE REFRIGERANT PIPING

AS REQUIRED TO TIE INTO EXISTING LINES. MATCH LINE

SIZE/INSULATION AND RECHARGE LINES AS REQUIRED.

OPERABLE WINDOWS ARE APPROXIMATELY 15'-6"

ABOVE GRADE. TOP OF GENERATOR ENCLOSURE SHALL

BE LESS THAN 9'-6" TALL SUCH THAT IT IS MORE THAN 6'

FROM THE WINDOW OPENINGS.

LAUNDRY

STOR

REC LOUNGE

101B

CORRIDOR

MECH

W DORM

13'

3'

3'

12'-6" LONG MAXIMUM

3' MINIMUM

3' MINIMUM

3' MINIMUM

REVISE AND EXTEND

CONTROL WIRING FOR

CU AS REQUIRED

DOWEL #5 EPOXY COATED BAR

4" INTO EXISTING PAD AT 12"

O.C. TIE DOWELS

INTO REINFORCING STEEL IN

NEW PAD.

EXISTING PANEL D

UTILIZE 20A 1P SPARE BREAKERS IN

SPACES 39 AND 41 FOR GENERATOR

HEATER AND CHARGER

INSTALL CONDUIT ON UNISTRUT

ABOVE GRADE FOR CONTROLS

AND 120V CIRCUITS BACK TO

MECHANICAL ROOM

5' - 4"

NEW GENERATOR ON PAD.

REFER TO DETAIL ON E501

1/4" = 1'-0"

POWER PLAN

Drawing #:

Date:

Project No:

© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.

P lo t D a te

T im e

Drawing Name:

info@kclengineering.com

300 4th Street West Des Moines, Iowa 50265 515.724.7938

/1

/2

:3 :1

A

M

E101

100% CD

07/18/25

9466.00

IO

W

A D

A S

D O

C

J D

C B

C N

E W

B A

C K

U P

G E

N E

R A

T O

R

W a te r S t, S io u x C it y

IA

ELECTRICAL POWER

FIELD VERIFY/MAINTAIN

EXISTING SERVICE

CLEARANCE FOR BOTH

ACCUs

METER

2000 A

MCB

MDP

B U

S

,0

A

/ 4W- 3ɸ120/208V

UTIL XFMR

208Y/120V

500kVA

EXISTING PRIMARY UTILITY

/3P100A

/3P200A

/3P200A

/3P200A

/3P60A

/3P200A

/3P200A

/3P200A

/3P800A PANEL

A

PANEL

D

PANEL

C

PANEL

B

TVSS

PANEL

F

PANEL

G

PANEL

H

SIEMENS SWITCHBOARD

800 A

MCB

EXISTING OLD MDP

B U

S

A

/ 4W- 3ɸ120/208V

A /3

P

(3) SETS OF 500 MCM

SIEMENS

SWITCHBOARD

G

STANDBY GENERATOR

250KW

208V

ATS

208V /

3 POLE

SCCR: 30,000 A

1200A

N

E

800A

/3P

SERVICE ENTRANCE

RATED WITH 1200A FUSES

REPLACE WITH 1100A

FUSES

INSTALL (2) 10' GROUND RODS

INSTALL 10' APART WITH #3/0 CU

FOR GROUNDING ELECTRODE SYSTEM.

COORDINATE EXACT LOCATION WITH EXISTING

UTILITIES AND GEOTHERMAL BORE FIELD.

COORDINATE SHUTDOWN AND INSTALLATION

WITH MIDAMERICAN. VERIFY TRIMECS

REQUIREMENTS ARE MET

(3) SETS OF 500 MCM

EXTEND EXISTING

GROUNDING ELECTRODE

SYSTEM TO NEW ATS VIA

#3/0 COPPER

CONDUCTOR

2000AS

1100AF(3)

A. DIAGRAM INDICATES OVERALL LAYOUT OF ELECTRICAL

DISTRIBUTION SYSTEM. REFER TO FLOOR PLANS FOR

EQUIPMENT LOCATIONS.

B. USE COPPER CONDUCTORS UNLESS OTHERWISE INDICATED.

C. MATCH NEUTRAL CONDUCTOR SIZE TO THE PHASE

CONDUCTORS UNLESS OTHERWISE NOTED.

D. ALL WIRING SHALL BE IN RACEWAY AS NOTED. REFER TO

SPECIFICATIONS FOR CONDUIT APPLICATION REQUIREMENTS.

E. INSTALL UTILITY TRANSFORMER PAD, METERING EQUIPMENT,

AND SERVICE ENTRANCE FEEDERS IN ACCORDANCE WITH

UTILITY COMPANY REQUIREMENTS.

RISER DIAGRAM GENERAL NOTES

RECOMMENDED PHASING

PREP WORK:

-REMOVE CONCRETE

-INSTALL NEW CONCRETE

-RELOCATE ACCU UNIT

1. INSTALL NEW GENERATOR AND ATS ON PADS

2. -INSTALL NEW CONDUCTORS FROM GENERATOR TO ATS.

-INSTALL NEW CONDUIT FROM GENERATOR TO ATS AND ATS TO MDP MAIN SERVICE

SECTION.

-INSTALL NEW GROUNDING CONDUCTORS AS SHOWN.

3. SHUTDOWN #1 -- MAXIMUM OF 4 HOUR DURATION

-COORDINATE UTILITY SHUTDOWN WITH MIDAMERICAN ENERGY

-REPLACE SERVICE FUSES IN MDP. INSTALL FUSE CLIPS AND ACCESSORIES AS

NECESSARY TO FIT NEW FUSES.

-REMOVE (3) CONDUCTOR SETS FROM TERMINALS.

-EXTEND (3) CONDUCTOR SETS TO ATS LOCATION.

-TURN UTILITY POWER BACK ON.

-GROUND CLUSTER THE (3) EXISTING CONDUCTORS NO LONGER IN USE AT THE

UTILITY TRANSFORMER AND AT THE MDP IF ALTERNATE #1 IS NOT SELECTED.

4. ALTERNATE #1:

SHUTDOWN #2 -- MAXIMUM OF 3 HOUR DURATION

-COORDINATE UTILITY SHUTDOWN WITH MIDAMERICAN ENERGY

-REMOVE (3) CONNECTED CONDUCTORS IN THE MDP THAT ARE NO LONGER IN USE.

-TERMINATE (3) ATS CONNECTED CONDUCTORS ONTO FUSES IN THE MDP.

-UTILIZE PERMANENT GENERATOR TO TURN POWER BACK ON.

-REMOVE (3) SETS OF CONDUCTORS FROM TRANSFORMER SIDE. CONTRACTOR TO

SALVAGE EXISTING COPPER.

NOTES:

SHUTDOWNS TO BE NO LONGER THAN MAXIMUM DURATIONS NOTED. SHUTDOWNS TO TAKE

PLACE DURING THE DAY. BETWEEN THE HOURS OF 9AM AND 3PM.

CONTRACTOR TO HAVE OAC MEETING TO COORDINATE SHUTDOWN. OBTAIN OWNER AND CM

PERMISSION TO SHUT OFF SERVICES 1 WEEK IN ADVANCE OF SHUTDOWN.

A. BASIS OF DESIGN IS 250KW DIESEL GENERATOR WITH A 24 HOUR BASE DAY TANK.

B. SOUND ATTENUATING TYPE 1 ENCLOSURE

GENERATOR NOTES

METER

2000 A

MCB

MDP

B U

S

,0

A

/ 4W- 3ɸ120/208V

UTIL XFMR

208Y/120V

500kVA

EXISTING PRIMARY UTILITY

/3P100A

/3P200A

/3P200A

/3P200A

/3P60A

/3P200A

/3P200A

/3P200A

/3P800A PANEL

A

PANEL

D

PANEL

C

PANEL

B

TVSS

PANEL

F

PANEL

G

PANEL

H

SIEMENS SWITCHBOARD

800 A

MCB

EXISTING OLD MDP

B U

S

A

/ 4W- 3ɸ120/208V

A /3

P

SIEMENS

SWITCHBOARD

G

STANDBY GENERATOR

250KW

208V

ATS

208V /

3 POLE

SCCR: 30,000 A

1200A

N

E

800A

/3P

SERVICE ENTRANCE

RATED WITH 1200A FUSES

(3) SETS OF 500 MCM

(3) SETS OF 500 MCM 4

2000AS

1100AF(3)

METER

2000 A

MCB

MDP

B U

S

,0

A

/ 4W- 3ɸ120/208V

UTIL XFMR

208Y/120V

500kVA

EXISTING PRIMARY UTILITY

/3P100A

/3P200A

/3P200A

/3P200A

/3P60A

/3P200A

/3P200A

/3P200A

/3P800A PANEL

A

PANEL

D

PANEL

C

PANEL

B

TVSS

PANEL

F

PANEL

G

PANEL

H

SIEMENS SWITCHBOARD

800 A

MCB

EXISTING OLD MDP

B U

S

A

/ 4W- 3ɸ120/208V

A /3

P

SIEMENS

SWITCHBOARD

#3/0 GNDG

STANDBY GENERATOR

250KW

208V

ATS

208V /

3 POLE

SCCR: 30,000 A

1200A

N

E

800A

/3P

(3) SETS OF 500 MCM - ABANDONED IN PLACE

ALTERNATE #1 TO REMOVE

2000AS

1100AF(3)

SERVICE ENTRANCE

RATED WITH 1200A FUSES

METER

2000 A

MCB

MDP

B U

S

,0

A

/ 4W- 3ɸ120/208V

UTIL XFMR

208Y/120V

500kVA

EXISTING PRIMARY UTILITY

/3P100A

/3P200A

/3P200A

/3P200A

/3P60A

/3P200A

/3P200A

/3P200A

/3P800A PANEL

A

PANEL

D

PANEL

C

PANEL

B

TVSS

PANEL

F

PANEL

G

PANEL

H

SIEMENS SWITCHBOARD

800 A

MCB

EXISTING OLD MDP

B U

S

A

/ 4W- 3ɸ120/208V

A /3

P

SIEMENS

SWITCHBOARD

(3) SETS OF 500 MCM

TOTAL OF (6) SETS IN PARALLEL.

SHOWN AS SUCH FOR PHASING PURPOSES

(3) SETS OF 500 MCM

2000AS

2000AF(3)

Drawing #:

Date:

Project No:

© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.

P lo t D a te

T im e

Drawing Name:

info@kclengineering.com

300 4th Street West Des Moines, Iowa 50265 515.724.7938

/1

/2

:3 :1

A

M

E401

100% CD

07/18/25

9466.00

IO

W

A D

A S

D O

C

J D

C B

C N

E W

B A

C K

U P

G E

N E

R A

T O

R

W a te r S t, S io u x C it y

IA

ELECTRICAL ONE-LINE

DIAGRAM

NOT TO SCALE

SHUTDOWN #1 - ONE-LINE DIAGRAM

FEEDER SCHEDULE

TAG PHASE GROUND

CONDUCTOR

MATERIAL CONDUIT

804 2- SETS (4) 500 MCM 1/0 COPPER (2) 4"

1204 3- SETS (3) 600 MCM 3/0 COPPER (3) 4"

NOT TO SCALE

ALTERNATE - SHUTDOWN #2 - ONE-LINE DIAGRAM

NOT TO SCALE

COMPLETE - ONE-LINE DIAGRAM

EXISTING SERVICE LOAD SUMMARY

(PER NEC 220.87)

EXISTING MAXIMUM DEMAND: 189kW PEAK DEMAND CALCULATION: 189kW x 125% (NEC 220.87) = 236 kW LOAD: 236kW / (208V/3P) = 656A

NOT TO SCALE

EXISTING ONE-LINE DIAGRAM

5'-6"

6" 6"

6"

6"

PLAN VIEW

SECTION A/A

5"

5"

18"

LENGTH OF

GENERATOR (VERIFY

WITH MANUFACTURER)

WIDTH OF GENERATOR

(VERIFY WITH

MANUFACTURER)

ANCHOR BOLTS AS

REQUIRED (TYP.)

#5 REINFORCING (TYP.)

GRADE

A

A

CAULK AROUND ENTIRE PAD AT

JOINT BETWEEN NEW PAD AND

EXISTING

RELOCATE APPROXIMATELY 4' TO THE NORTH.

FIELD VERIFY EXACT DIMENSIONS ONSITE.

EXTEND PAD FOR CONDENSING

UNIT TO MATCH FLOOR PLANS

CUT EXISTING PAD TO MAKE

WAY FOR NEW FOOTING OF

GENERATOR PAD. TIE EXISTING

PAD INTO NEW FOOTING.

INSTALL CONDUIT FOR CONTROL WIRING

AND SEPARATE CONDUIT FOR

120V CIRCUIT.CORE HOLES THROUGH EXTERIOR BRICK.

CAULK AND SEAL AROUND CONDUIT. TYPICAL FOR ALL.

COMBINE CONDUIT

ONTO VERTICAL STRAND

OF GALVANIZED UNISTRUT.

MOUNT UNISTRUT IN MORTAR

BED AND NOT IN BRICK.

RELOCATE EXISTING CU AS

SHOWN ON FLOOR PLANS

MODIFY REFRIGERANT

AS SHOWN ON FLOOR

PLANS

Drawing #:

Date:

Project No:

© 2022 KCL Engineering L.L.C. These documents have been prepared specifically for this project. they are not suitable for use on other projects or in other locations without the expressed written approval and participation of KCL Engineering L.L.C. A limited license is granted to the owner/contractor to reproduce these documents or portions thereof, but only for use in connection with this project. Unauthorized reproduction is prohibited.

P lo t D a te

T im e

Drawing Name:

info@kclengineering.com

300 4th Street West Des Moines, Iowa 50265 515.724.7938

/1

/2

:3 :1

A

M

E501

100% CD

07/18/25

9466.00

IO

W

A D

A S

D O

C

J D

C B

C N

E W

B A

C K

U P

G E

N E

R A

T O

R

W a te r S t, S io u x C it y

IA

ELECTRICAL DETAILS

NOT TO SCALE

GENERATOR PAD DETAIL

1/4" = 1'-0"

RELOCATE ACCU

1/4" = 1'-0"

CONDUIT ROUTING

(2) 4" CONDUIT INSTALLED ALONG

EXTERIOR WALL. INSTALL

ABOVE EXISTING FLUE AND DOOR

FRAME.

1/4" = 1'-0"

CONDENSING UNIT EXISTING LOCATION

Sheets
AG00 - TITLE SHEET
E000 - ELECTRICAL GENERAL NOTES & SYMBOLS
E001 - ELECTRICAL SITE PLAN
E101 - ELECTRICAL POWER
E401 - ELECTRICAL ONE-LINE DIAGRAM
E501 - ELECTRICAL DETAILS
ED101 - ELECTRICAL DEMO

File details come from the government source that posted it. Updated .