RFB945800-01 - Drawings.pdf
PDF 1013 KB Posted
- Attached to
- NCCF Powerhouse Water Heater Replacement
- Solicitation number
- RFB945800-01
- Issued by
- Warren County, Iowa
About this file
The provided document is a comprehensive set of architectural and engineering design drawings for the North Central Correctional Facility (NCCF) Powerhouse Water Heater Replacements project, prepared by Resource Consulting Engineers, LLC for the Iowa Department of Administrative Services. The project involves a phased replacement of existing domestic hot water heating systems in the facility's central plant located at 313 Lanedale in Rockwell City, Iowa. The design includes detailed mechanical and electrical plans for demolishing and replacing two hot water boilers (HWB-1 and HWB-2), two hot water generators (HWG-1 and HWG-2), associated pumps, and related infrastructure. The project is identified by DAS Project Number 9458.00 and RFB Number 945800-01, with design drawings dated March 14, 2025.
The project scope includes comprehensive system replacements with specific requirements such as maintaining operational continuity during installation, reusing existing equipment skids, and ensuring compliance with multiple Iowa administrative rules and building codes, including the 2015 International Building Code, 2015 International Fire Code, and 2020 National Electrical Code. The electrical designs specify precise connections for new equipment, including wiring the hot water boilers to integrate with existing emergency shutdown systems. The mechanical drawings detail piping configurations, insulation requirements, and installation specifications, with particular attention to phasing the replacement to minimize facility disruption. The project will be executed by McGough Construction, located in Des Moines, Iowa, and involves specialized equipment from manufacturers like Powerhouse Thermal Solutions, Taco, and Hubbell.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFB945800-01 - Notice to Bidders.pdf | ||
| 1303604-event.pdf | ||
| RFB945800-01 - Bid Form.pdf | ||
| RFB945800-01 - Project Manual.pdf | ||
| Project Manual.html | HTML file | |
| RFB945800-01 - Addendum 1.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPLICABLE CODES:
A. 2015 INTERNATIONAL BUILDING CODE AS ADOPTED BY IOWA
ADMINISTRATIVE RULES 661-201 AND 661-301
B. 2015 INTERNATIONAL FIRE CODE AS ADOPTED BY IOWA ADMINISTRATIVE
RULE 661-201
C. 2012 INTERNATIONAL ENERGY CONSERVATION CODE AS ADOPTED BY IOWA
ADMINISTRATIVE RULE 661-303
D. 2015 INTERNATIONAL EXISTING BUILDING CODE AS ADOPTED BY IOWA
ADMINISTRATIVE RULE 661-301 AND 661-350, AS APPLICABLE.
E. 2012 NFPA 101 LIFE SAFETY CODE AS ADOPTED BY IOWA ADMINISTRATIVE
RULE 661-205
F. 2010 AMERICANS WITH DISABILITIES ACT AS ADOPTED BY IOWA
ADMINISTRATIVE RULE 661-302
G. 2024 INTERNATIONAL MECHANICAL CODE AS ADOPTED BY THE IOWA
DEPARTMENT OF PUBLIC HEALTH, IOWA ADMINISTRATIVE RULE 641-61
H. 2021 UNIFORM PLUMBING CODE AS ADOPTED BY THE IOWA DEPARTMENT
OF PUBLIC HEALTH, IOWA ADMINISTRATIVE RULE 641-25
I. 2020 NATIONAL ELECTRICAL CODE AS ADOPTED BY THE IOWA ELECTRICAL
LICENSING BOARD, IOWA ADMINISTRATIVE RULE 661-504.
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERONSAL SUPERVISION
AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER
THE LAWS OF THE STATE OF IOWA.
DAVID MICHAEL REPAIR, PE
REG. NO. DATE:
MY LICENSE RENEWAL DATE IS DECEMBER 31, 2025
PAGES OR SHEETS COVERED BY THIS SEAL:
P29277
ALL ELECTRICAL SHEETS
L
IC
E N S E
D
PR
OFE
SSIONAL
E
N G I N E E R
O WI A
DAVID
MICHAEL
REPAIR
P29277
I HEREBY CERTIFY THAT THIS ENGINEERING DOCUMENT WAS
PREPARED BY ME OR UNDER MY DIRECT PERONSAL SUPERVISION
AND THAT I AM A DULY LICENSED PROFESSIONAL ENGINEER UNDER
THE LAWS OF THE STATE OF IOWA.
SCOTT JASPER, PE
REG. NO. DATE:
MY LICENSE RENEWAL DATE IS DECEMBER 31, 2026
PAGES OR SHEETS COVERED BY THIS SEAL:
12568
ALL MECHANICAL SHEETS
L
IC
E N S E
D
PR
OFE
SSIONAL
E
N G I N E E R
O WI A
SCOTT
JASPER
12568
MEP ENGINEER:
RESOURCE CONSULTING
ENGINEERS, LLC
301 ALEXANDER AVENUE
SUITE C
AMES, IA 50010
515-292-2500 www.resourcece.com
PROJECT NO:
ISSUED:
DATEMARK
©2025
RESOURCE CONSULTING
ENGINEERS, LLC
REVISION INFORMATION
KEY PLAN
DESCRIPTION
2024.029
N O
R T
H C
E N
T R
A L
C O
R R
E C
T
IO
N A
L
F A
C
IL
IT
Y
P
O W
E R
H O
U S
E
.0
D O
C N
C C
F P
O W
E R
H O
U S
E W
A T
E R
H E
A T
E R
R E
P L
A C
E M
E N
T S
C D
G0
COVER SHEET
L
A N
E D
A L
E
R O
C K
W E
L L
C
IT
Y
IA
3/14/2025
THESE DOCUMENTS HAVE BEEN PREPARED BY RESOURCE
CONSULTING ENGINEERS, LLC FOR THE 9458.00 - DOC NCCF
POWERHOUSE WATER HEATER REPLACEMENTS PROJECT. THE
DOCUMENTS SHALL REMAIN THE PROPERTY OF RESOURCE
CONSULTING ENGINEERS, LLC, AND SHALL NOT BE USED ON OTHER
PROJECTS, OR IN OTHER LOCATIONS WITHOUT THE EXPRESS
WRITTEN APPROVAL AND PARTICIPATION OF RESOURCE
CONSULTING ENGINEERS, LLC. RESOURCE CONSULTING ENGINEERS,
LLC SHALL RETAIN ALL COMMON LAW, STATUTORY, AND OTHER
RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
NORTH CENTRAL CORRECTIONAL FACILITY
POWERHOUSE WATER HEATER REPLACEMENTS
OWNER INFORMATION:
DEPARTMENT OF ADMINISTRATIVE SERVICES
109 SE 13TH STREET
DES MOINES, IA 50319
DRAWING INDEX:
PROJECT LOCATION
RCE PROJECT NUMBER: 2049.029.00
PROJECT LOCATION:
DAS PROJECT NUMBER: 9548
ELECTRICAL SHEET INDEX
SHEET DESCRIPTION
E000 ELECTRICAL SYMBOL LEGEND
E001 ELECTRICAL PROJECT NOTES AND ABBREVIATIONS
E002 ELECTRICAL PROJECT SCHEDULES
ED101 LEVEL 1 - ELECTRICAL PLAN - DEMOLITION
E201 LEVEL 1 - POWER PLAN - NEW WORK
E820 POWER SCHEDULES
MECHANICAL SHEET INDEX
M000 HVAC SYMBOLS AND ABBREVIATIONS
MD101 LEVEL 1 - MECHANICAL PLAN - DEMOLITION
M101 LEVEL 1 - MECHANICAL PLAN - NEW WORK
M500 BOILER AND HW GENERATOR PIPING DIAGRAMS - DEMO & NEW
M501 BOILER VENT DETAILS AND EXISTING SKID DIMENSIONS
M800 MECHANICAL SCHEDULES
NORTH CENTRAL CORRECTION FACILITY
CENTRAL PLANT
313 LANEDALE
ROCKWELL CITY, IA 50579
DAS PROJECT NUMBER: 9458.00 RFB: 945800-01
CONSTRUCTION MANAGER:
McGOUGH CONSTRUCTION
217 E 2ND STREET
SUITE 120
DES MOINES, IOWA 50309
CHS
CD
STC
CWR
CWS
HWR
HWS
NG
STM-L
-E
CHR CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSATE DRAIN
CONDENSATE RETURN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
HEATING WATER RETURN
HEATING WATER SUPPLY
NATURAL GAS
STEAM
RL
RS
REFRIGERANT-LIQUID
REFRIGERANT-SUCTION
2"
2"
4"
4"
RHG REFRIGERANT-HOT GAS
MECHANICAL PIPING SYMBOLS
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL MECHANICAL SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
EXISTING PIPE TAG
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
PIPING BEING DEMOLISHED
ABOVE GROUND PIPING
PIPE SIZE TAG (DIAMETER)
PIPE RISE
PIPE DROP
PIPE TEE
REDUCING 45
DEGREE TEE
45 DEGREE TEE
BELOW GROUND PIPING
PIPE INVERT ELEVATION TAG
PIPE SLOPE TAG
* NOTE *
ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN
THIS SET. THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE
USED IN THIS SET OF DRAWINGS.
LP PROPANE GAS
Room
INVERT: -105' - 1"
1/8" / 12" SLOPE
16"x8"
16"/8"
-E
F
S
M
B
D
C
16"Ø
EXHAUST AIR
OUTSIDE AIR
RELIEF AIR
RETURN AIR
SUPPLY AIR
TRANSFER AIR
GRILLES, REGISTERS & DIFFUSERS TAG
CFM
THROW-150FPM/ 100FPM/ 50FPM
NECK SIZE / MODULE SIZE
EXISTING DUCT TAG
OVAL DUCT SIZE TAG (WIDTH / HEIGHT)
SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)
HVAC SYMBOLS
RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE
RECTANGULAR RETURN/TRANSFER AIR DUCT RISE
MECHANICAL EQUIPMENT TAGS
ROUND DUCT SIZE TAG (DIAMETER)
LINEAR DIFFUSER TAG
CFM
TYPE (SEE SCHEDULE) NUMBER OF SLOTS /
ACTIVE SLOT LENGTH (PLENUM LENGTH) /
NECK SIZE
DUCT BEING DEMOLISHED
ELEVATION (CENTER OF FACE)
ROUND SUPPLY/OUTSIDE AIR DUCT RISE
ROUND RETURN/TRANSFER AIR DUCT RISE
RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE
ROUND EXHAUST/RELIEF AIR DUCT RISE
DROP
DROP
DROP
DROP
DROP
DROP
GREASE EXHAUST AIR
SMOKE EXHAUST AIR
EQUIPMENT BY OTHERS
(REFER TO OTHER DISCIPLINE
FOR ADDITIONAL INFORMATION)
EXISTING EQUIPMENT
TO REMAIN
EXHAUST GAS FLUE
COMBUSTION AIR
CONDITIONED OUTSIDE AIR
48"x2 1/2"
SLB3 400
10" / 24x24
SD3 300
12" / ---
SD9 400
LINEAR BAR GRILLE
LINEAR SLOT
DIFFUSER
PERFORATED
DIFFUSER WITH
DEFLECTORS
ROUND DIFFUSER
WITH ADJUSTABLE
PATTERNS
LOUVERED DOUBLE
DEFLECTION GRILLE 12"x10"
SG5 500
TYPE (SEE SCHEDULE)
10" / 24x24 H-5/7/1422
SD1 400
3-CONE DIFFUSER
THROW PATTERN
MAX NC RATING
1 / 4' - 0" / 8"
LSD1 200
8' - 0"AFF
1 / 4' - 0" / 8"
LSD1 200
6' - 0"
1 / 4' - 0" / 8"
LSD1 200
SECTION TOTAL TRACK LENGTH
12"x10" / 24x12
RG11 500
LOUVERED GRILLE
12"x10" / 24x24
RG2 500
EGGCRATE RETURN
GRILLE
BOTTOM OF EQUIPMENT
ELEVATION
HEATING
COIL FLOW
OPERATING WEIGHT
NOT INCLUDING CURB
FUEL INPUT
GAS PIPE FLOW
NOMINAL COOLING
CAPACITY
PIPE ACCESSORY TAGS
DOMESTIC WATER METER
BALANCING VALVE
SHUTOFF BALL VALVE
CHECK VALVE
3-WAY MIXING VALVE
MOTORIZED CONTROL VALVE
3 WAY MOTORIZED CONTROL
VALVE
PRESSURE REDUCING VALVE
REFRIGERANT SOLENOID VALVE
BUTTERFLY VALVE
DATA DEVICE TAGS
DAMPER TAGS
EQUIPMENT ID
SYMBOL
MANUAL BALANCING DAMPER
BACKDRAFT DAMPER
COMBINATION FIRE/SMOKE
DAMPER
FIRE DAMPER
SMOKE DAMPER
MOTORIZED DAMPER
CAP
PLUG
GWR
GWS
GEOTHERMAL WATER RETURN
GEOTHERMAL WATER SUPPLY
EXISTING RELOCATED
EQUIPMENT
EQUIPMENT ABBREVIATIONS
A AMPS
AAV AUTOMATIC AIR VENT
ABV ABOVE
AC AIR CONDITIONING
ADJ ADJUSTABLE
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
AL ALUMINUM
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
ASSY ASSEMBLY
BAS BUILDING AUTOMATION SYSTEM
BFF BELOW FINISHED FLOOR
BLW BELOW
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
°C DEGREES CELSIUS
CAP CAPACITY
CB CATCH BASIN
CC COOLING COIL
CEA COMBINED EXHAUST AIR (LAB/GENERAL)
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CL CENTERLINE
CLG CEILING
CO CLEAN OUT
COD CENTER OF DUCT
COND CONDENSATE/CONDENSER
COP CENTER OF PIPE
CS CARBON STEEL
CU COPPER
CV CONSTANT VOLUME
CW COLD WATER
D DEGREE
DB DRY BULB
DBA A-WEIGHTED DECIBELS
DDC DIRECT DIGITAL CONTROL
DIA DIAMETER
DP DIFFERENTIAL PRESSURE
DN DOWN
DT DIFFERENTIAL TEMPERATURE
DW DISTILLED WATER
EAT ENTERING AIR TEMPERATURE
EC ELECTRICAL CONTRACTOR
EDB ENTERING DRY BULB TEMPERATURE
EFT ENTERING FLUID TEMPERATURE
EG ETHYLENE GLYCOL
EL ELEVATION
ELEC ELECTRICAL
EQUIP EQUIPMENT
ERV ENERGY RECOVERY VENTILATION
ESP EXTERNAL STATIC PRESSURE
ETR EXISTING TO REMAIN
EWB ENTERING WET BULB TEMPERATURE
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATUR
EXH EXHAUST
EXST EXISTING
°F DEGREES FAHRENHEIT
FC FAIL CLOSED
FCO FLOOR CLEANOUT OUT
FD FLOOR DRAIN
FD FIRE DAMPER
FDV FIRE DEPARTMENT VALVE
FH FUME HOOD
FL FAIL LAST POSITION
FL FLOOR
FLA FULL LOAD AMPS
FO FAIL OPEN
FO FUEL OIL
FPI FINS PER INCH
FPM FEET PER MINUTE
FPS FEET PER SECOND
FS FLOOR SINK
FSD COMBINATION FIRE/SMOKE DAMPER
FT FOOT OR FEET
FTG FOOTING
GA GAGE
GAL GALLONS
GC GENERAL CONTRACTOR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
H ENTHALPY
HB HOSE BIBB
HD HUB DRAIN
HP HORSEPOWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
HZ HERTZ
ID INDIRECT
IN INCH OR INCHES
INV INVERT
KW KILOWATTDV
KWH KILOWATT-HOURS
LAT LEAVING AIR TEMPERATURE
LB POUND OR POUNDS
LB/HR POUND PER HOUR
LBS POUNDS
LDB LEAVING DRY BULB TEMPERATURE
LF LINEAL FOOT/LINEAL FEET
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LRA LOCKED ROTOR AMPS
LVR LOUVER
LWB LEAVING WET BULB TEMPERATURE
LWT LEAVING WATER TEMPERATURE
MAV MANUAL AIR VENT
MAX MAXIMUM
MBH THOUSANDS OF BTU PER HOUR
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPACITY
MCF ONE THOUSAND CUBIC FEET
MCP MAXIMUM OVERCURRENT
PROTECTION (ALSO MOCP)
MD MOTORIZED DAMPER
MECH MECHANICAL
MEP MECHANICAL, ELECTRICAL AND
PLUMBING
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANOUS
MTR MOTOR
NA NOT APPLICABLE (ALSO N/A)
NC NORMALLY CLOSED
NC NOISE CRITERIA
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO NUMBER
NPS NOMINAL PIPE SIZE
NPT NATIONAL PIPE THREAD
NTS NOT TO SCALE
O OXYGEN
OC ON CENTER
OED OPEN ENDED DUCT
OFCI OWNER FURNISHED, CONTRACTOR
INSTALLED
OFOI OWNER FURNISHED, OWNER
INSTALLED
OV OUTLET VELOCITY
PC PLUMBING CONTRACTOR
PCF POUNDS PER CUBIC FOOT
PD PRESSURE DROP
PG PROPYLENE GLYCOL
PH PHASE
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSF POUNDS PER SQUARE FOOT
PSI PONDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH
ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
QTY. QUANTITY
RCP REFLECTED CEILING PLAN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RM ROOM
RPM REVOLUTIONS PER MINUTE
SCH SCHEDULE
SD SMOKE DAMPER
SF SQUARE FEET
SM SURFACE MOUNT
SP STATIC PRESSURE
SRV SAFETY RELIEF VENT
STM STEAM
SS STAINLESS STEEL
TC TEMPERATURE CONTROL
TD TEMEPRATURE DROP
TEMP TEMPERATURE
TEMP TEMPORARY
TOD TOP OF DUCT
TOP TOP OF PIPE
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UG UNDERGROUND
V VENT
V VOLTS
VAC VACUUM
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VFD VARIABLE FREQUENCY DRIVE
VP VELOCITY PRESSURE
W WASTE
WB WET BULB
WC WATER COLUMN
WCO WALL CLEAN OUT
WG WATER GAUGE
WH WALL HYDRANT
W/ WITH
WMS WIRE MESH SCREEN
ABBREVIATIONS
SA
SOA
OA
RA
TA
EA
RLA
GEA
SEA
FLUE
CA
T.O.D. (5' - 6")
TOP TAKEOFF
BOTTOM TAKEOFF
FUEL OIL SUPPLY
FUEL OIL RETURN
FUEL OIL VENT
FOS
FOR
FOV
ELBOW
PLAQUE DIFFUSER
ELBOW-RADIUS
ELBOW-MITERED
BOTTOM TAKE-OFF
TOP TAKE-OFF
TAKE-OFF
DUCT TRANSITION
AC AIR-COOLED CHILLER
ACCU AIR COOLING CONDENSING UNIT
AFMS AIR FLOW MEASURING STATION
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
CB CHILLED BEAM
CCV COOLING CONTROL VALVE
CD CONTROL DAMPER
CH CHILLER
CO CARBON MONOXIDE
C02 CARBON DIOXIDE SENSOR
CT COOLING TOWER
CCT CLOSED CIRCUIT COOLING TOWER
CPF CHEMICAL POT FEEDER
CRU CONDENSATE RETURN UNIT
CU CONDENSING UNIT (ALSO COND)
CUH CABINET UNIT HEATER
CV CONTROL VALVE
CHWP CHILLED WATER PUMP
CPF CHEMICAL POT FEEDER
DBP DOMESTIC WATER BOOSTER PUMP
DC DRY COOLER
DF DUCT FILTER
DHU DEHUMIDFICATION UNIT
DOAS DEDICATED OUTDOOR AIR UNIT
DP DIFFERENTIAL PRESSURE SENSOR
DWH DOMESTIC WATER HEATER
ERF ENERGY RECOVERY FAN
ERM ENERGY RECOVERY MODULE
ERW ENERGY RECOVERY WHEEL
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
F FURNACE
FCU FAN COIL UNIT
FTR FIN TUBE RADIATOR
GFP GLYCOL FEED PUMP
GIH GRAVITY INTAKE HOOD
GRV GRAVITY ROOF VENTILATOR
H HUMIDITY SENSOR
HC HEATING COIL
HCV HEATING CONTROL VALVE
HP HEAT PUMP
HRU HEATING RECOVERY UNIT
HWP HEATING WATER PUMP
HRU HEAT RECOVERY UNIT
HU HUMDIFICATION UNIT
HX HEAT EXCHANGER
KEH KITCHEN EXAHUST HOOD
L LOUVER
MAU MAKEUP AIR UNIT
OAT OUTDOOR AIR TEMPERATURE
PFPB PARALLEL FAN POWERED BOX
PHC ELECTRICAL PREHEAT COIL
PR PANEL RADIATOR
PRV POWER ROOF VENTILATOR
RTU ROOFTOP UNIT
SFPB SERIES FAN POWER BOX
ST STEAM TRAP
T TEMPERATURE SENSOR
TH THERMOMETER
UH UNIT HEATER
VAV VARIABLE VOLUME AIR TERMINAL
VFD VARIABLE FREQUENCY DRIVE
VT VOLUME TANK
VRF VARIABLE REFRIGERANT FLOW
WWHP WATER-TO-WATER HEAT PUMP
NPCW NON-POTABLE COLD WATER
PROJECT MECHANICAL DESIGN NOTES:
A. MECHANICAL DESIGN TO PROVIDE SETBACK CONTROLS PER ASHRAE 90.1-2010 SECTION
6.4.3.3.2 AND BE SET TO THE FOLLOWING TEMPERATURE SETPOINTS DURING NORMAL BUILDING
OPERATION:
a. OCCUPIED COOLING SETPOINT: 75 F.
b. UNOCCUPIED COOLING SETPOINT: 80 F.
c. OCCUPIED HEATING SETPOINT: 68 F.
d. UNOCCUPIED HEATING SETPOINT: 65 F.
SECTION VIEW
ELEVATION VIEW
xF FANS (ALSO SF, EF, RF, KEF) xAS AIR SILENCER ( ALSO SAS, RAS, OAS, EAS) xABD AIR BALANCING DAMPER (ALSO SABD, EABD, RABD, OABD) xAT AIR TERMINAL (ALSO SAT, EAT, RAT, TAB, VAV) xP PUMP (ALSO CP, CBP, CHP, ERP, GSP, HWP) xC COIL (ALSO PHC, RHC, ERC, HC, CC) xCV CONTROL VALVE (ALSO CCV, HCV)
CHS
CWV
CA
CD
STC
CWR
CWS
DCW
F-DCW
H-DCW
S-DCW
DHW
DHWR
V-G
SAN-G
HWR
HWS
NG
OV
OW
PD
V
SAN
SHWR
SHWS
STM-L
ST
ST-O
CHR CHILLED WATER RETURN
CHILLED WATER SUPPLY
COMBINATION WASTE & VENT
COMPRESSED AIR
CONDENSATE DRAINAGE
CONDENSATE RETURN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
DOMESTIC COLD WATER
FILTERED COLD WATER
HARD COLD WATER
SOFT COLD WATER
HOT WATER
HOT WATER RECIRCULATION
GREASE VENT
GREASE WASTE
HEATING WATER RETURN
HEATING WATER SUPPLY
NATURAL GAS
OIL VENT
OIL WASTE
PUMP DISCHARGE
SANITARY VENT
SANITARY SEWER
SOLAR HOT WATER RETURN
SOLAR HOT WATER SUPPLY
STEAM - LOW PRESSURE
STORM DRAINAGE
OVERFLOW STORM DRAINAGE
RL
RS
REFRIGERANT-LIQUID
REFRIGERANT-SUCTION
2"
4"
4"
RHG REFRIGERANT-HOT GAS
PLUMBING AND PIPING SYMBOLS
DRAIN SIZE
PIPE RISE
PIPE DROP
PIPE TEE REDUCING 45
DEGREE TEE
45 DEGREE TEE
LP PROPANE GAS
TYPE (SEE SCHEDULE)
RO REVERSE OSMOSIS WATER
IW INDIRECT WASTE
4000 SF
6" SD-1
4" FD-1FLOOR DRAIN 4" AD-6 AREA DRAIN
4" FS-4FLOOR SINK
4" SD-29 DECK DRAIN4" FD-3PFLOOR DRAIN
8 WFU
4" FD-13
HUB DRAIN
DRAIN TAGS
"P" - INDICATES
PRIMER CONNECTION
FIXTURE UNITS
FLOW CONTROL
DRAIN
4" SD-12
COMBINATION
DRAINS
STORM DRAIN4" SD-15
ROOF AREA
SERVED BY DRAIN
WATER CLOSET -
WALL HUNG - ADA WC-1
U-1
1 WFU
LAV-1A
1.5 CWFU
1.5 HWFU
LAV-1A
FIXTURE UNITS
4" WCO
PIPE ACCESORY
TAG
PLUMBING FIXTURE TAGS
4" WCO
TYPE (SEE SCHEDULE)
WC-1A
CAP
PLUG
GWR
GWS
GEOTHERMAL WATER RETURN
GEOTHERMAL WATER SUPPLY
STM-M
STM-H
STEAM - MEDIUM PRESSURE
STEAM - HIGH PRESSURE
PIPE ACCESSORY TAGS
DOMESTIC WATER METER
BALANCING VALVE
SHUTOFF BALL VALVE
CHECK VALVE
3-WAY MIXING VALVE
MOTORIZED CONTROL VALVE
3 WAY MOTORIZED CONTROL
VALVE
PRESSURE REDUCING VALVE
REFRIGERANT SOLENOID VALVE
BUTTERFLY VALVE
S
BACKFLOW PREVENTER
REINSULATE EXISTING DHW (E) PIPINGDHW (E)
MEP ENGINEER:
RESOURCE CONSULTING
ENGINEERS, LLC
301 ALEXANDER AVENUE
SUITE C
AMES, IA 50010
515-292-2500 www.resourcece.com
PROJECT NO:
ISSUED:
DATEMARK
©2025
RESOURCE CONSULTING
ENGINEERS, LLC
REVISION INFORMATION
KEY PLAN
DESCRIPTION
2024.029
N O
R T
H C
E N
T R
A L
C O
R R
E C
T
IO
N A
L
F A
C
IL
IT
Y
P
O W
E R
H O
U S
E
.0
D O
C N
C C
F P
O W
E R
H O
U S
E W
A T
E R
H E
A T
E R
R E
P L
A C
E M
E N
T S
C D
M000
HVAC SYMBOLS AND
ABBREVIATIONS
L
A N
E D
A L
E
R O
C K
W E
L L
C
IT
Y
IA
3/14/2025
THESE DOCUMENTS HAVE BEEN PREPARED BY RESOURCE
CONSULTING ENGINEERS, LLC FOR THE 9458.00 - DOC NCCF
POWERHOUSE WATER HEATER REPLACEMENTS PROJECT. THE
DOCUMENTS SHALL REMAIN THE PROPERTY OF RESOURCE
CONSULTING ENGINEERS, LLC, AND SHALL NOT BE USED ON OTHER
PROJECTS, OR IN OTHER LOCATIONS WITHOUT THE EXPRESS
WRITTEN APPROVAL AND PARTICIPATION OF RESOURCE
CONSULTING ENGINEERS, LLC. RESOURCE CONSULTING ENGINEERS,
LLC SHALL RETAIN ALL COMMON LAW, STATUTORY, AND OTHER
RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
S
MECHANICAL SHEET INDEX
M000 HVAC SYMBOLS AND ABBREVIATIONS
MD101 LEVEL 1 - MECHANICAL PLAN - DEMOLITION
M101 LEVEL 1 - MECHANICAL PLAN - NEW WORK
M500 BOILER AND HW GENERATOR PIPING DIAGRAMS - DEMO & NEW
M501 BOILER VENT DETAILS AND EXISTING SKID DIMENSIONS
M800 MECHANICAL SCHEDULES
or GAS PRESSURE REGULATOR
3/4" DHWR 140° (E)
4" DCW (E)
3" DHW 140° (E)
6" NG (E)
3" DCW (E)
2" DCW (E)
1/2" DHWR 140° (E)
MECH/ELEC
CENTRAL PLANT
PHASE 1
DEMO EXISTING HWB-1 AND HWG-1
WHILE MAINTAINING OPERATION OF
EXISTING HWB-2 AND HWG-2.
SEE PIPING DIAGRAM 1/M500 AND
VENT DETAIL 1/M501 FOR DETAILED
DEMOLITION SCOPE.
EXISTING BOILER SKIDS TO REMAIN.
SEE 3/M501 FOR SKID DIMENSIONS.
PHASE 2
AFTER NEW HWB-1 AND HWG-1 ARE
OPERATIONAL AND COMMISSIONED,
DEMO EXISTING HWB-2, HWG-2 AND
HW BOOSTER.
SEE PIPING DIAGRAM 1/M500 AND
VENT DETAIL 1/M501 FOR DETAILED
DEMOLITION SCOPE.
EXISTING BOILER SKIDS TO REMAIN.
SEE 3/M501 FOR SKID DIMENSIONS.
3" DHW 140° (E)
3/4" DHWR 140° (E)
6" NG (E)
6" LPG (E)
2 1/2" NG (E)
3" NG (E)
3" DCW (E)
3/4" DHWR 140° (E)
3" DHW 140° (E)
3" S-DCW (E)
EXIST WATER SOFTENERS
3" DHW 140° (E)
EXIST STEAM
BOILER CATWALK
MEP ENGINEER:
RESOURCE CONSULTING
ENGINEERS, LLC
301 ALEXANDER AVENUE
SUITE C
AMES, IA 50010
515-292-2500 www.resourcece.com
PROJECT NO:
ISSUED:
DATEMARK
©2025
RESOURCE CONSULTING
ENGINEERS, LLC
REVISION INFORMATION
KEY PLAN
DESCRIPTION
2024.029
N O
R T
H C
E N
T R
A L
C O
R R
E C
T
IO
N A
L
F A
C
IL
IT
Y
P
O W
E R
H O
U S
E
.0
D O
C N
C C
F P
O W
E R
H O
U S
E W
A T
E R
H E
A T
E R
R E
P L
A C
E M
E N
T S
C D
MD101
LEVEL 1 - MECHANICAL
PLAN - DEMOLITION
L
A N
E D
A L
E
R O
C K
W E
L L
C
IT
Y
IA
3/14/2025
THESE DOCUMENTS HAVE BEEN PREPARED BY RESOURCE
CONSULTING ENGINEERS, LLC FOR THE 9458.00 - DOC NCCF
POWERHOUSE WATER HEATER REPLACEMENTS PROJECT. THE
DOCUMENTS SHALL REMAIN THE PROPERTY OF RESOURCE
CONSULTING ENGINEERS, LLC, AND SHALL NOT BE USED ON OTHER
PROJECTS, OR IN OTHER LOCATIONS WITHOUT THE EXPRESS
WRITTEN APPROVAL AND PARTICIPATION OF RESOURCE
CONSULTING ENGINEERS, LLC. RESOURCE CONSULTING ENGINEERS,
LLC SHALL RETAIN ALL COMMON LAW, STATUTORY, AND OTHER
RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
MECHANICAL DEMOLITION GENERAL NOTES
A ALL DUCT, PIPING, AND EQUIPMENT SHOWN DASHED OR HATCHED WITHIN THE
AREA OF DEMOLITION SHALL BE DEMOLISHED, UNLESS NOTED OTHERWISE.
B DEMOLITION DRAWINGS SHOWING CONDITIONS BASED ON FIELD OBSERVATION AND
EXISTING DRAWINGS. ADDITONAL COMPONENTS REQUIRING REMOVAL OR
MODIFICATIONS MAY NOT BE SHOWN. CONTRACTOR SHALL FAMILIARIZE THEMSELF
WITH EXISTING SYSTEM AND COMPONENTS, AND SHALL BE REPONSIBLE FOR
INCLUDING NECESSARY WORK TO PREPARE SYSTEMS FOR REQUIRED
MODIFICATIONS.
C FURNISH ALL LABOR, MATERIALS AND EQUIPMENT REQUIRED TO COMPLETE
DEMOLITION OF EXISTING MECHANICAL EQUIPMENT AS SPECIFIED OR INDICATED.
DISCONNECT, REMOVE AND RELOCATE ALL ITEMS REQUIRED TO FACILITATE THE
WORK.
D CONTRACTOR SHALL THOROUGHLY FAMILIARIZE THEMSELF WITH EXISTING
MECHANICAL SYSTEM(S), WHICH WILL BE AFFECTED BY THE DEMOLITION WORK.
E CONTRACTOR SHALL OBTAIN PERMISSION FROM OWNER PRIOR TO SHUT OFF OF
SERVICES WHICH MAY AFFECT OTHER AREAS BEYOND THE LIMITS OF THE
IMMEDIATE AREA.
F ALL WORK SHALL BE SCHEDULED WITH OWNER.
N
1/4" = 1'-0"
LEVEL 1 - MECHANICAL PLAN - DEMOLITION
KEYNOTE LEGEND
KEY VALUE KEYNOTE TEXT
1 DEMO DOMESTIC HOT WATER HEATING SYSTEM NO. 1, INCLUDING: BOILER,
PUMP, HOT WATER GENERATOR (TANK AND HEAT EXCHANGER) AND
EXPANSION TANK AND RELATED PIPING, VALVES, PIPING SPECIALTIES AND
BACKFLOW PREVENTER - SEE 1/M500
2 DEMO DOMESTIC HOT WATER HEATING SYSTEM NO. 2, INCLUDING: BOILER,
PUMP, HOT WATER GENERATOR (TANK AND HEAT EXCHANGER) AND
EXPANSION TANK AND RELATED PIPING, VALVES, PIPING SPECIALTIES AND HW
CIRC PUMP- SEE 1/M500
3 DEMO DHW BOOSTER PUMP ASSEMBLY AND RELATED PIPE DROPS - SEE
1/M500
HWB-2
HWB-1
PLUMB/ELEC SHOP
3" NG (E) 6" NG (E)
3/4" DHWR 140° (E)
4" DCW (E)
3" DHW 140° (E)
3" DCW (E)
6" NG (E)
2 1/2" NG (E)
2" DCW (E)
1/2" DHWR 140° (E)
HWG-1
HWG-2
B-2
B-1
STAGING AREA FOR BOILERS AND HOT WATER
GENERATOR TANKS - COORDINATE FINAL
LOCATION WITH NCCF OPERATIONS TEAM
PHASE 1
INSTALL NEW HWB-1 AND HWG-1
WHILE MAINTAINING OPERATION OF
EXISTING HWB-2 AND HWG-2.
SEE PIPING DIAGRAM 2/M500 AND
VENT DETAIL 2/M501 FOR DETAILED
SCOPE.
PHASE 2
AFTER NEW HWB-1 AND HWG-1 ARE
OPERATIONAL AND COMMISSIONED,
INSTALL NEW HWB-2 AND HWG-2.
SEE PIPING DIAGRAM 2/M500 AND
VENT DETAIL 2/M501 FOR DETAILED
SCOPE.
3" DCW (E)
3" S-DCW
RE-INSULATE 10'
OF 3" DHW (E) IN
TUNNEL BELOW
REINSULATE
15' OF 3" DHW
(E) RISER
REINSULATE 75'
OF 3" DHW (E)
@ 10'-6" AFF
3" DHW 140° (E)
MECH/ELEC
CENTRAL PLANT
HWG-2
HWG-1
3/4" DHWR 140° (E)
3" DHW 140° (E)
6" LPG (E)
3" S-DCW (E)
REINSULATE 75'
OF 3" DHW (E)
@ 10'-6" AFF
EXIST STEAM
BOILER CATWALK
HWP-2
HWCP-1
HWP-1
MEP ENGINEER:
RESOURCE CONSULTING
ENGINEERS, LLC
301 ALEXANDER AVENUE
SUITE C
AMES, IA 50010
515-292-2500 www.resourcece.com
PROJECT NO:
ISSUED:
DATEMARK
©2025
RESOURCE CONSULTING
ENGINEERS, LLC
REVISION INFORMATION
KEY PLAN
DESCRIPTION
2024.029
N O
R T
H C
E N
T R
A L
C O
R R
E C
T
IO
N A
L
F A
C
IL
IT
Y
P
O W
E R
H O
U S
E
.0
D O
C N
C C
F P
O W
E R
H O
U S
E W
A T
E R
H E
A T
E R
R E
P L
A C
E M
E N
T S
C D
M101
LEVEL 1 - MECHANICAL
PLAN - NEW WORK
L
A N
E D
A L
E
R O
C K
W E
L L
C
IT
Y
IA
3/14/2025
THESE DOCUMENTS HAVE BEEN PREPARED BY RESOURCE
CONSULTING ENGINEERS, LLC FOR THE 9458.00 - DOC NCCF
POWERHOUSE WATER HEATER REPLACEMENTS PROJECT. THE
DOCUMENTS SHALL REMAIN THE PROPERTY OF RESOURCE
CONSULTING ENGINEERS, LLC, AND SHALL NOT BE USED ON OTHER
PROJECTS, OR IN OTHER LOCATIONS WITHOUT THE EXPRESS
WRITTEN APPROVAL AND PARTICIPATION OF RESOURCE
CONSULTING ENGINEERS, LLC. RESOURCE CONSULTING ENGINEERS,
LLC SHALL RETAIN ALL COMMON LAW, STATUTORY, AND OTHER
RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
N
1/4" = 1'-0"
LEVEL 1 - MECHANICAL PLAN - NEW WORK
MECHANICAL PIPING GENERAL NOTES
A SUPPLY AND RETURN PIPING TO ALL TERMINAL EQUPMENT SHALL BE THE SAME SIZE.
B CONDENSATE DRAINS SHALL BE SUPPLIED FOR ALL COOLING EQUIPMENT. CONTRACTOR
SHALL ENSURE PROPER INSTALLATION AND DRAINAGE AS REQUIRED BY FEDERAL, STATE,
AND LOCAL CODES. CONDENSATE PIPING SHALL BE TYPE "L" COPPER.
C PROVIDE A 4" HOUSEKEEPING PAD FOR EACH PIECE OF MECHANICAL EQUIPMENT
MOUNTED ON THE FLOOR. COORDINATE SIZES WITH MECHANICAL EQUIPMENT SELECTED.
D CONTRACTOR SHALL SECURE AND PAY ALL FEES AND PERMITS PERTAINING TO WORK.
E CONTRACTOR IS RESPONSIBLE FOR ALL RIGGING, HANDLING, AND PROTECTION OF
MATERIALS.
F ALL EQUIPMENT SHALL BE INSTALLED IN STRICT COMPLIANCE WITH MANUFACTURER’S
WRITTEN INSTRUCTIONS. THE CONTRACTOR SHALL PROVIDE ALL HANGERS AND
SUPPORTS REQUIRED FOR A COMPLETE INSTALLATION.
G FOR CLARITY OF INFORMATION ON DRAWING, ALL CONDUIT, PIPING, DUCTWORK,
EQUIPMENT, DEVICES, ETC. ARE NOT SHOWN ON THIS DRAWING. CONTRACTOR SHALL BE
RESPONSIBLE FOR COORDINATING WORK WITH WORK OF OTHER TRADES AND BUILDING
ARCHITECTURAL.
H REQUIRED ACCESS AREA FOR MECHANICAL EQUIPMENT IS TYPICALLY INDICATED ON
DRAWINGS. CONTRACTOR SHALL COORDINATE FINAL EQUIPMENT LOCATIONS WITH WORK
OF OTHER TRADES TO ENSURE EQUIPMENT IS ACCESSIBLE FOR MAINTENANCE, FILTER
REPLACEMENTS, ETC.
I CONTRACTOR SHALL PROVIDE COORDINATION DRAWINGS FOR DUCT WORK, HVAC PIPING,
PLUMBING PIPING, FIRE SPRINKLER PIPING, STRUCTURE, ELECTRICAL PANELS AND
TRANSFORMERS, CONDUITS 2" DIAMETER AND LARGER, CABLE TRAYS. ETC.
J DRAWINGS ARE DIAGRAMMATIC IN NATURE AND SHOULD NOT BE USED TO DETERMINE
EXACT LOCATIONS OF EQUIPMENT, PIPING AND ACCESSORIES, ETC. REFER TO ALL
AVAILABLE INFORMATION WITHIN CONTRACT DOCUMENTS (INCLUDING, BUT NOT
NECESSARILY LIMITED TO, STRUCTURAL PLANS, FLOOR PLANS, REFLECTED CEILING
PLANS, ELECTRICAL LIGHTING, POWER AND SYSTEM PLANS, PLUMBING PLANS,
MECHANICAL PIPING PLANS, ETC.) TO COORDINATE EXACT LOCATIONS FOR INSTALLATION
OF WORK INDICATED ON THIS DRAWINGS.
K CONTRACTOR SHALL LOCATE THERMOSTATS AND TEMPERATURE SENSORS AT 4'-0" AFF, A
MINIMUM OF 8" FROM LIGHT SWITCH.
L CONDENSATE DRAINS SHALL BE SUPPLIED FOR ALL COOLING EQUIPMENT. CONTRACTOR
SHALL ENSURE PROPER INSTALLATION AND DRAINAGE AS REQUIRED BY FEDERAL, STATE,
AND LOCAL CODES. CONDENSATE PIPING SHALL BE TYPE "L" COPPER.
KEYNOTE LEGEND
KEY VALUE KEYNOTE TEXT
1 INSTALL NEW DOMESTIC HOT WATER HEATING SYSTEM NO. 1, INCLUDING:
BOILER, PUMP, HOT WATER GENERATOR, EXPANSION TANK AND RELATED
PIPING, VALVES, PIPING SPECIALTIES AND BACKFLOW PREVENTER - SEE
2/M500.
2 INSTALL NEW DOMESTIC HOT WATER HEATING SYSTEM NO. 2, INCLUDING:
BOILER, PUMP, HOT WATER GENERATOR (TANK AND HEAT EXCHANGER) AND
EXPANSION TANK AND RELATED PIPING, VALVES, PIPING SPECIALTIES AND HW
CIRC PUMP- SEE 2/M500.
3 MAINTAIN 36" OF CLEARANCE, MINIMUM, BETWEEN HWB-1 AND HWB-2
CONTROL PANELS.
4 MAINTAIN 36" OF CLEARANCE NEW HWB-1 PIPING AND EXISTING WATER
SOFTENER TANKS AND RELATED CONTROL PANELS.
5 INSTALL NEW HW BOILER AND HW GENERATOR TANK ON EXISTING SKID. FOR
SKID DIMENSIONS, SEE 3/501. IF NECESSARY, WELD NEW 6"X2" C-CHANNEL
MEMBERS TO EXISTING SKID TO SUPPORT NEW EQUIPMENT. PREP AND PAINT
(GREY EPOXY PAINT) BOTH NEW AND EXISTING CHANNELS BEFORE
INSTALLING NEW EQUIPMENT.
6 TO MOVE NEW HWG-1 INTO PLACE, TEMPORARILY SHORE-UP EXISTING
CATWALK AND REMOVE TWO CATWALK SUPPORT COLUMNS. NET FREE
HEIGHT BENEATH CATWALK WILL BE 100.5" (VERIFY).
EXIST 3" S-DCW
1-1/4" TANK DRAIN
(VERIFY) - EXTEND TO
NEAREST FLOOR DRAIN
HWS
HWR
FACTORY-SUPPLIED, FIELD-
INSTALLED FLOW SWITCH, RELIEF
VALVE AND PRESS/TEMP GAUGE
1" BOILER DRAIN - EXTEND TO
NEAREST FLOOR DRAIN
s
5 PIPE DIAMETERS, MINIMUM,
STRAIGHT HORIZONTAL PIPE
AFTER FLOW SWITCH
EXIST 3" NG
HWG-2HWG-1
HWB-1 HWB-2SEE 2/M501
FOR VENT
DETAILS
3/4" BOILER CONDENSATE DRAIN -
EXTEND TO NEAREST FLOOR DRAIN
EXIST 1" DHWR
FROM TUNNEL
EXIST 3" DHW
TO TUNNEL
NEW BACKFLOW
PREVENTER ASSY
FOR BOILER MAKEUP
3"
3/4" DCW HWS
HWR
s
1"
PHASE 1
INSTALL NEW DOMESTIC HW HEATING SYSTEM NO. 1.
NEW HWB-1 AND HWG-1 MUST BE 100% OPERATIONAL
AND COMMISSIONED BEFORE BEGINNING DEMO, AND
THEN INSTALLATION, ON SYSTEM NO. 2
3"
DHW (E)
S-DCW
DHWR (E)
NG (E)
HWP-1 HWP-2
HWCP-1
3/4"
3/4"
ET-1 ET-2
SRVSRV
1" 3"
3/4"
1" DRAIN FROM SRV
- EXTEND TO NEAREST
FLOOR DRAIN
REINSULATE 1/2" DHW (E) UP TO
SW WALL OF MECH/ELEC
CENTRAL PLANT, RM 101
REINSULATE APPROX 20'
OF 3" DHW (E) ABOVE
NEW HW SYSTEMS
REINSULATE 3" DHW (E)
SEE SHEET M101 FOR
LOCATION AND LENGTHS
NEW 3" DHW
3"
NEW 3" S-DCW AS
NEEDED TO REPLACE
HWG TANKS
MAV
3" 2-1/2" (VERIFY)
TEMP SENSOR FITTING
(BY TANK MFR)
TH
MAV
GPRGPR
EXISTING SKID
TO REMAIN
EXIST 3" SOFT CW
EXIST AIR GAP AND
INDIRECT DRAIN
EXIST 1" HW CIRC
FROM TUNNEL
HWS
HWR
DEMO PUMP AND PIPING
BETWEEN HWB-1 AND HWG-1
s HWS
HWR
EXIST 3" NG EXIST 3" HW
TO TUNNEL
HWG-2HWG-1
HWB-1 HWB-2
DEMO 1-1/2" GAS
LINE BACK TO
EXIST 2-1/2" LINE
DEMO HW CIRC PUMP
AND RELATED
COMPONENTS
s
DEMO STRAINER
AND BACKFLOW
PREVENTER
DEMO EXIST HOT
WATER GENERATOR
DEMO EXIST
BOILER
PHASE 1
DEMO DOMESTIC HW HEATING SYSTEM NO. 1 ONLY.
NEW HWB-1 AND HWG-1 MUST BE 100% OPERATIONAL AND
COMMISSIONED BEFORE BEGINNING DEMO ON SYSTEM NO. 2
SEE 1/M501
FOR VENT
DEMO
DEMO HW BOOSTER PUMP
ASSEMBLY AND DHW DROPS
EXIST HW CIRC, HW AND
SOFT CW BRANCHES
(TO SHOPS) TO REMAIN
DEMO 3" SOFT CW, AS
NEEDED, TO REPLACE
HWG TANKS
3"
3/4" DCW
3/4"
1"
3"
3/4"
2-1/2"
3"
3"
2-1/2" (VERIFY)
MEP ENGINEER:
RESOURCE CONSULTING
ENGINEERS, LLC
301 ALEXANDER AVENUE
SUITE C
AMES, IA 50010
515-292-2500 www.resourcece.com
PROJECT NO:
ISSUED:
DATEMARK
©2025
RESOURCE CONSULTING
ENGINEERS, LLC
REVISION INFORMATION
KEY PLAN
DESCRIPTION
2024.029
N O
R T
H C
E N
T R
A L
C O
R R
E C
T
IO
N A
L
F A
C
IL
IT
Y
P
O W
E R
H O
U S
E
.0
D O
C N
C C
F P
O W
E R
H O
U S
E W
A T
E R
H E
A T
E R
R E
P L
A C
E M
E N
T S
C D
M500
BOILER AND HW
GENERATOR PIPING
DIAGRAMS - DEMO & NEW
L
A N
E D
A L
E
R O
C K
W E
L L
C
IT
Y
IA
3/14/2025
THESE DOCUMENTS HAVE BEEN PREPARED BY RESOURCE
CONSULTING ENGINEERS, LLC FOR THE 9458.00 - DOC NCCF
POWERHOUSE WATER HEATER REPLACEMENTS PROJECT. THE
DOCUMENTS SHALL REMAIN THE PROPERTY OF RESOURCE
CONSULTING ENGINEERS, LLC, AND SHALL NOT BE USED ON OTHER
PROJECTS, OR IN OTHER LOCATIONS WITHOUT THE EXPRESS
WRITTEN APPROVAL AND PARTICIPATION OF RESOURCE
CONSULTING ENGINEERS, LLC. RESOURCE CONSULTING ENGINEERS,
LLC SHALL RETAIN ALL COMMON LAW, STATUTORY, AND OTHER
RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
NOT TO SCALE
BOILER / HOT WATER GENERATOR PIPING DIAGRAM - NEW WORK
NOT TO SCALE
BOILER / HOT WATER GENERATOR PIPING DIAGRAM - DEMO WORK
ITEM PIPING AND PIPE INSULATION - APPLICATIONS AND SPECIFICATION EXCERPTS (NOTE 1.)
[1] NATURAL GAS PIPING (1-1/2" AND 2"): SCREWED SCHEDULE 40 BLACK STEEL PIPE (ASTM A106, GRADE B) WITH SCREWED MALLEABLE FITTINGS (ANSI B16.3, 125 LB) AND MALLEABLE IRON GROUND-JOINT UNIONS WITH BRASS SEATS (250 LB)
[2] NATURAL GAS PIPING (2-1/2" AND 3"): WELDED AND FLANGED SCHEDULE 40 BLACK STEEL PIPE (ASTM A106, GRADE B) WITH BUTT WELD SCHEDULE 40 STEEL FITTINGS (ANSI B16.9, 125 LB) AND 150 PSIG FORGED STEEL SLIP-ON FLANGES (ANSI B16.5).
[3] BOILER HOT WATER PIPING (2-1/2" AND 3"): SCHEDULE 40 BLACK STEEL PIPE (ASTM A106, GRADE B) WITH TWO JOINING OPTIONS:
OPT 1: SCREWED MALLEABLE IRON FITTINGS (ANSI B16.3, 125 LB) AND MALLEABLE IRON GROUND-JOINT UNIONS WITH
BRASS SEATS (250 LB)
OPT 2: WELDED AND FLANGED SCHEDULE 40 BLACK STEEL PIPE (ASTM A106, GRADE B) WITH BUTT WELD SCHEDULE 40 STEEL FITTINGS (ANSI B16.9, 125 LB) AND 150 PSIG FORGED STEEL SLIP-ON FLANGES (ANSI B16.5).
[4] DOMESTIC COLD AND HOT WATER PIPING (3" AND SMALLER): TYPE L HARD TEMPER COPPER PIPE (ASTM B88) WITH WROUGHT
COPPER FITTINGS (ANSI B16.22) AND WITH TWO JOINING OPTIONS:
OPT 1: 95-5 SOLDER JOINTS
OPT 2: PRESS-TYPE JOINTS (ASTM B16-51, 200 PSI, 32 TO 250°F)
[5] PIPING INSULATION (DOMESTIC COLD AND SOFTENED DOMESTIC COLD WATER):
ARMACELL AP ARMAFLEX LAPSEAL OR EQUAL BY AEROFLEX OR K-FLEX
BLACK CLOSED-CELL ELASTOMERIC INSULATION WITH SELF-SEAL SYSTEM , 0.254 THERMAL CONDUCTIVITY @ 90°F.
INSTALL WITH FOLLOWING THICKNESS: 1-1/4" AND SMALLER PIPE SIZE = 1/2" THICKNESS; 1-1/2" AND LARGER PIPE SIZE = 1" THICKNESS.
[6] PIPING INSULATION (DOMESTIC HOT WATER AND HOT WATER CIRCULATION):
JOHNS MANVILLE MICRO-LOK OR EQUAL BY CERTAINTEED OR KNAUF
PREFORMED FIBERGLASS INSULATION WITH ASJ, 4 LB/FT3 DENSITY AND 0.24 THERMAL CONDUCTIVITY @ 100°F.
INSTALL WITH FOLLOWING THICKNESS: 1-1/4" AND SMALLER PIPE SIZE = 1" THICKNESS; 1-1/2" AND LARGER PIPE SIZE = 1.5" THICKNESS.
ITEM VALVES AND PIPING SPECIALTIES - APPLICATIONS AND SPECIFICATION EXCERPTS (NOTE 1.)
[7] BALL VALVES (NATURAL GAS): APOLLO 80-109-01 OR EQUAL BY MILWAUKEE, NIBCO OR WATTS 2-1/2" LARGE-PORT, TWO-PIECE, BRONZE BALL VALVE WITH NPT CONNECTIONS, REINFORCED TEFLON (RPTFE) SEATS AND SEALS, 250
PSIG RATING FOR LP-GAS. UL LISTED FOR LP-GAS AND NATURAL GAS.
[8] BALL VALVES (BOILER HOT WATER): APOLLO 94A OR EQUAL BY MILWAUKEE, NIBCO OR WATTS FULL PORT, 2-PIECE, BRASS BALL VALVE WITH NPT CONNECTIONS, TEFLON SEATS AND SEALS, 400 PSIG CWP AND -20 TO 400°F
TEMPERATURE RANGE.
[9] BALL VALVES (DOMESTIC COLD AND HOT WATER): APOLLO 94ALF OR EQUAL BY MILWAUKEE, NIBCO OR WATTS LEAD-FREE, FULL PORT, 2-PIECE, BRASS BALL VALVE WITH NPT CONNECTIONS, TEFLON SEATS AND SEALS, 400 PSIG CWP AND -20 TO
400°F TEMPERATURE RANGE.
[10] STRAINERS (BOILER HOT WATER AND DOMESTIC HOT WATER RECIRC): APOLLO 59-000, SPIRAX SARCO BT OR APPROVED EQUAL BRONZE, WYE-PATTERN STRAINER WITH NPT CONNECTIONS, STAINLESS STEEL 20 MESH SCREEN AND TAPPING ON POCKET CAP.
3" BOILER HOT WATER: INSTALL 1.25" OR 1.5" APOLLO 70-100 SERIES BALL VALVE ON POCKET CAP TAPPING FOR MANUAL BLOW DOWN.
1" DOMESTIC HOT WATER RECIRC: INSTALL 3/4" APOLLO 70-100 SERIES BALL VALVE ON POCKET CAP FOR MANUAL BLOW DOWN.
[11] BACKFLOW PREVENTER: WATTS 3/4" U009M2-QT-S OR EQUAL BY APOLLO OR ZURN
BRONZE BODY REDUCED PRESSURE ZONE, DOUBLE CHECK VALVE BACKFLOW PREVENTER WITH 3/4" CONNECTIONS, INTEGRAL UNIONS (U), QUARTER-TURN INLET AND OUTLET BALL VALVES (QT) AND BRONZE STRAINER (S). UNIT SHALL PASS 12 GPM @ 7.5 FPS AND 13 PSI
PRESSURE DROP.
[12] GAS PRESSURE REGULATOR (GPR): MAXITROL RV81 OR EQUAL BY AMERICAN METER OR FISHER CONTROLS STRAIGHTH-THRU-FLOW NATURAL GAS PRESSURE REGULATOR. 0.4 INCHES W.C. PRESSURE DROP AT 1500 CFH FLOW. 1/2 PSI (= 14 INCHES W.C.) INLET PRESSURE AND 7 TO 11 INCHES W.C. OUTLET PRESSURE. 1-1/2" NPT INLET/OUTLET CONNECTIONS AND 3/8" NPT
VENT CONNECTION.
[13] SAFETY RELIEF VALVE (SRV): WATTS 140X-9 OR EQUAL BY APOLLO OR ZURN
2-IN-1 TEMPERATURE AND PRESSURE (T&P) RELIEF VALVE WITH 1,670 MBH CAPACITY @ 75 PSI. BRONZE BODY WITH EXTENDED (9"
LENGTH) THERMOSTAT AND 1" NPT CONNECTIONS.
[14] THERMOMETER (TH): ASHCROFT 50CI60R040-0/200F OR EQUAL BY WEISS OR WINTERS
TAMPER RESISTANT, BIMETAL THERMOMETER WITH HERMETICALLY-SEALED 304 STAINLESS STEEL (SS) CASE WITH 1/4" DIAMETER SS STEM. THERMOMETER FACE SHALL HAVE ADJUSTABLE VIEWING ANGLE. 5" DIAL (50), 1/2" NPT CONNECTION (60), REAR CONNECTION (R), 4" STEM LENGTH (060) AND 0 TO 200°F SINGLE-SCALE TEMPERATURE RANGE (0/200F). INSTALL THERMOMETER IN BRASS
THERMOWELL FROM SAME MANUFACTURER - SEE BELOW.
[15] THERMOWELL: ASHCROFT 50W0250-H-T-260-AA OR EQUAL BY WEISS OR WINTERS
THREADED THERMOWELL WITH 1/2" PROCESS CONNECTION SIZE (50), 2-1/2" PROCESS INSERTION LENGTH (0250), TAPERED SHANK (H), NPT THREADED PROCESS CONNECTION (T) AND BRASS MATERIAL (AA). INSTALL THERMOWELL ON A 1/2" BRASS THREADOLET, OR
SIMILAR THREADED FITTING, SOLDERED TO TYPE L COPPER PIPE.
NOTE 1. SEE PROJECT SPECIFICATIONS BOOK FOR DETAILED "GENERAL", "PRODUCT" AND "EXECUTION" REQUIREMENTS.
DEMO 8" VENT PIPE
AND FITTINGS
HWB-2
PITCHED ROOF
SEE 1/M501 FOR
BOILER DEMO DETAILS
HWB-1
DEMO VENT CAP AND
PYRAMIDAL FLASHING
EXIST SHEET METAL "CURB" (ABOVE ROOF)
AND "CLEARANCE BOX" (BELOW ROOF)
TO REMAIN
PHASE 1
DEMO HWB-1 VENT SYSTEM ONLY.
NEW HWB-1 MUST BE 100% OPERATIONAL AND COMMISSIONED
BEFORE BEGINNING DEMO ON HWB-2 VENT SYSTEM.
BEFORE DEMO, DOCUMENT EXIST
VENT CAP EL ABOVE ROOF
NEW 6" VENT PIPE
AND FITTINGS
NOTE: VENT SIZE
TO MATCH BOILER
FLUE OUTLET
HWB-2
CONNECT NEW 6"
VENT PIPE TO BOILER
FLUE OUTLET
HWB-1
NEW 6" VENT CAP AND PYRAMIDAL
(OR SIMILAR) FLASHING
PITCHED ROOF
PHASE 1
INSTALL NEW HWB-1 VENT SYSTEM ONLY.
NEW HWB-1 MUST BE 100% OPERATIONAL AND COMMISSIONED BEFORE
BEGINNING DEMO AND INSTALL OF HWB-2 VENT SYSTEM
INSTALL NEW VENT CAP AT SAME EL
AS FORMER VENT CAP
EXIST SHEET METAL "CURB"
AND "CLEARANCE BOX"
PITCH DOWN AT
1/4" PER FOOT
2' - 0 1/2"2' - 6"3' - 10"1' - 2 1/2"
1'
/2
3'
1'
/2
0' - 3" 0' - 3"
UNLESS NOTED OTHERWISE, STRUCTURAL MEMBERS HAVE A WIDTH OF 2"
NOTE: SKIDS FOR HWB-1 / HWG-1 AND HWB-2 / HWG-2 ARE IDENTICAL
NOT TO SCALE
BOILER DEMO VENT DETAIL
NOT TO SCALE
BOILER NEW VENT DETAIL
MEP ENGINEER:
RESOURCE CONSULTING
ENGINEERS, LLC
301 ALEXANDER AVENUE
SUITE C
AMES, IA 50010
515-292-2500 www.resourcece.com
PROJECT NO:
ISSUED:
DATEMARK
©2025
RESOURCE CONSULTING
ENGINEERS, LLC
REVISION INFORMATION
KEY PLAN
DESCRIPTION
2024.029
N O
R T
H C
E N
T R
A L
C O
R R
E C
T
IO
N A
L
F A
C
IL
IT
Y
P
O W
E R
H O
U S
E
.0
D O
C N
C C
F P
O W
E R
H O
U S
E W
A T
E R
H E
A T
E R
R E
P L
A C
E M
E N
T S
C D
M501
BOILER VENT DETAILS
AND EXISTING SKID
DIMENSIONS
L
A N
E D
A L
E
R O
C K
W E
L L
C
IT
Y
IA
3/14/2025
THESE DOCUMENTS HAVE BEEN PREPARED BY RESOURCE
CONSULTING ENGINEERS, LLC FOR THE 9458.00 - DOC NCCF
POWERHOUSE WATER HEATER REPLACEMENTS PROJECT. THE
DOCUMENTS SHALL REMAIN THE PROPERTY OF RESOURCE
CONSULTING ENGINEERS, LLC, AND SHALL NOT BE USED ON OTHER
PROJECTS, OR IN OTHER LOCATIONS WITHOUT THE EXPRESS
WRITTEN APPROVAL AND PARTICIPATION OF RESOURCE
CONSULTING ENGINEERS, LLC. RESOURCE CONSULTING ENGINEERS,
LLC SHALL RETAIN ALL COMMON LAW, STATUTORY, AND OTHER
RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.N
NOT TO SCALE
EXISTING BOILER SKID DIMENSIONS
MEP ENGINEER:
RESOURCE CONSULTING
ENGINEERS, LLC
301 ALEXANDER AVENUE
SUITE C
AMES, IA 50010
515-292-2500 www.resourcece.com
PROJECT NO:
ISSUED:
DATEMARK
©2025
RESOURCE CONSULTING
ENGINEERS, LLC
REVISION INFORMATION
KEY PLAN
DESCRIPTION
2024.029
N O
R T
H C
E N
T R
A L
C O
R R
E C
T
IO
N A
L
F A
C
IL
IT
Y
P
O W
E R
H O
U S
E
.0
D O
C N
C C
F P
O W
E R
H O
U S
E W
A T
E R
H E
A T
E R
R E
P L
A C
E M
E N
T S
C D
M800
MECHANICAL
SCHEDULES
L
A N
E D
A L
E
R O
C K
W E
L L
C
IT
Y
IA
3/14/2025
THESE DOCUMENTS HAVE BEEN PREPARED BY RESOURCE
CONSULTING ENGINEERS, LLC FOR THE 9458.00 - DOC NCCF
POWERHOUSE WATER HEATER REPLACEMENTS PROJECT. THE
DOCUMENTS SHALL REMAIN THE PROPERTY OF RESOURCE
CONSULTING ENGINEERS, LLC, AND SHALL NOT BE USED ON OTHER
PROJECTS, OR IN OTHER LOCATIONS WITHOUT THE EXPRESS
WRITTEN APPROVAL AND PARTICIPATION OF RESOURCE
CONSULTING ENGINEERS, LLC. RESOURCE CONSULTING ENGINEERS,
LLC SHALL RETAIN ALL COMMON LAW, STATUTORY, AND OTHER
RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
3. FURNISH BOILER WITH OPTIONAL SUPPLY SYSTEM TEMPERATURE SENSOR
2. BOILER SHALL BE PROVIDED WITH ALL ACCESSORIES NECESSARY FOR COMPLIANCE WITH ASME CSD-1. CONTRACTOR SHALL SUBMIT REQUIRED CSD-1 FORMS AND OTHER REQUIRED DOCUMENTATION TO AUTHORITY HAVING JURISDICTION UPON BOILER START-UP.
1. SEE PROJECT SPECIFICATIONS BOOK FOR DETAILED "GENERAL", "PRODUCT" AND "EXECUTION" REQUIREMENTS.
NOTES:
HWB-2 POWERHOUSE THERMAL SOLUTIONS EVS-1500 DOMESTIC HW WATER-TUBE HX ROOM AIR 1,500 1,251 83 3:1 WATER 120 160 180 NG 4-14 120 1 7.5 20 1,2,3
HWB-1 POWERHOUSE THERMAL SOLUTIONS EVS-1500 DOMESTIC HW WATER-TUBE HX ROOM AIR 1,500 1,251 83 3:1 WATER 120 160 180 NG 4-14 120 1 7.5 20 1,2,3
MANUFACTURER MODEL VOLTAGE PHASE FLA MOCP
DESIGNATION LOCATION
BASIS OF DESIGN
SERVICE TYPE
COMBUSTION
TYPE
PEAK INPUT
(MBH)
PEAK OUTPUT
(MBH)
PEAK EFFICIENCY
MIN TURNDOWN
RATIO
FLUID TYPE
FLOW
(GPM)
ENT. FLUID
TEMP. (°F)
LVG. FLUID
TEMP. (°F)
FUEL TYPE
GAS INLET PRESS.
RANGE (IN. W.C.)
ELECTRICAL DATA
NOTES
HOT WATER BOILER SCHEDULE
5. PUMP HAS A REPLACEABLE CARTRIDGE AND COMES WITH 3 SPEED SWITCH AND MATING FLANGES FOR SUCTION AND DISCHARGE PIPE.
4. CONSTRUCTION, INCLUDING STAINLESS STEEL CASING, TO BE SUITABLE FOR POTABLE WATER APPLICATIONS.
3. IN-LINE PUMP SHALL BE SUITABLE FOR INSTALLATION WITH MOTOR IN EITHER HORIZONTAL OR VERTICAL (MOTOR ABOVE PIPING) ORIENTATIONS.
2. SUCTION AND DISCHARGE FLANGES SHALL HAVE 1/4" NPT PRESSURE TAPPINGS.
1. PUMP TO BE PROVIDED WITH PREMIUM EFFICIENCY, NON-OVERLOADING MOTOR.
NOTES:
HWCP-1 POWERHOUSE TACO 0013-MSSF2-IFC DHW CIRCULATION CARTRIDGE CIRCULATOR 10 22.5 WATER 140 N/A N/A 1 1 N/A N/A 1/8 3250 120 1 NO 3, 4, 5
HWP-2 POWERHOUSE TACO 1941 2x2 HW BOILER #2 CLOSE-COUPLED IN-LINE 125 30 WATER 170 7.5 62 2 2 6.2 1.6 2 1760 480 3 NO 1, 2, 3
HWP-1 POWERHOUSE TACO 1941 2x2 HW BOILER #1 CLOSE-COUPLED IN-LINE 125 30 WATER 170 7.5 62 2 2 6.2 1.6 2 1760 480 3 NO 1, 2, 3
RPM VOLTAGE PHASE VFD?
MANUFACTURER MODEL
BRAKE
HP
MOTOR
HP
DESIGNATION LOCATION
BASIS OF DESIGN
SERVICE TYPE
CAPACITY
(GPM)
HEAD
(FT W.C.)
FLUID
TYPE
AVG. FLUID
TEMP.
(°F)
MAX
NPSHR
(FT W.C.)
MIN
EFFICIENCY
SUCTION
SIZE
(INCH)
DISCHARGE
SIZE
(INCH)
IMPELLER
SIZE
(INCH)
ELECTRICAL DATA
NOTES
HOT WATER PUMP SCHEDULE
j. R12.5, minimum, insulation and 22 ga., minimum, painted steel jacket. Jacket is not required if using elastomeric insulation (ex. Armaflex).
i. 12” x 16", minimum, manway; accessible through insulation/jacketing.
h. 1” male NPT non-ferrous connection for safety relief valve: Top or side conn; accessible from exterior of insulation/jacketing. Safety relief valve to be field-furnished / field-installed.
g. 1-1/2" non-ferrous connection for tank drain: Bottom or bottom of side outlet conn; Extend drain through side of tank base and terminate with male NPT connection; Drain valve to be field-furnished / field-installed.
f. 1/2" NPT non-ferrous connection for immersion-type temperature sensor: Side inlet conn (near top of tank); accessible from exterior of insulation/jacketing.
e. 1" NPT non-ferrous connection for domestic hot water recirculation: Side inlet conn (near top of tank); accessible from exterior of insulation/jacketing.
d. 3" NPT non-ferrous connection for domestic hot water outlet: Top outlet conn; accessible from exterior of insulation/jacketing.
c. 3" NPT non-ferrous connection for domestic cold water inlet: Side inlet conn (below tube bundle heat exchanger); accessible from exterior of insulation/jacketing.
b. Flanged round opening and internal support for bundle-type heat exchanger. See Hot Water Generator Heat Exchanger Schedule, this sheet and coordinate with heat exchanger manufacturer.
a. 10”H base support ring or similar legs or support channels. See tank maximum dimensions in schedule.
3. FURNISH TANK WITH THE FOLLOWING FEATURES AND CONNECTIONS:
2. OPTIONAL TANK DIMENSIONS: (OPTION 2: 70” DIAMETER x 75”H); (OPTION 3: 72” DIAMETER x 72”H)
1. SEE PROJECT SPECIFICATIONS BOOK FOR ADDITIONAL PRODUCT REQUIREMENTS.
NOTES:
HWG-2 POWERHOUSE HUBBELL 1250 DOMESTIC HOT WATER CEMENT-LINED STEEL VERTICAL 1250 WATER 140 150 68" 80" 90" 2460 1, 2, 3
HWG-1 POWERHOUSE HUBBELL 1250 DOMESTIC HOT WATER CEMENT-LINED STEEL VERTICAL 1250 WATER 140 150 68" 80" 90" 2460 1, 2, 3
MANUFACTURER MODEL DIAMETER
HEIGHT
WITHOUT
BASE
HEIGHT
WITH 10"
BASE
WEIGHT
(LBS)
DESIGNATION LOCATION
BASIS OF DESIGN
SERVICE MATERIAL ORIENTATION
NOMINAL
TANK VOLUME
(GALLONS)
FLUID
TYPE
FLUID OPERATING
TEMP (°F)
TANK
PRESSURE
RATING (PSI)
TANK DIMENSIONS (BEFORE INSULATION)
NOTES
HOT WATER GENERATOR TANK SCHEDULE - BASE BID
1. FIELD-FURNISH, FIELD INSTALL SADDLES/SUPPORTS FOR MOUNTING ON EXISTING SUSPENDED ANGLE IRON SUPPORTS.
NOTES:
ET-2 POWERHOUSE AMTROL AX-40-DD HW BOILER #1 LOOP DIAPHRAGM HORIZONTAL 23 11.3 WATER 170 100 12 15 33 66 3/4 1
ET-1 POWERHOUSE AMTROL AX-40-DD HW BOILER #1 LOOP DIAPHRAGM HORIZONTAL 23 11.3 WATER 170 100 12 15 33 66 3/4 1
MANUFACTURER MODEL DIA. (IN) LENGTH (IN) WEIGHT (LBS) SYS. CONN. (IN)
DESIGNATION LOCATION
BASIS OF DESIGN
SERVICE TYPE ORIENTATION
TANK VOLUME
(GAL)
ACCEPTANCE
VOLUME (GAL)
FLUID
TYPE
AVG. FLUID TEMP.
(°F)
TANK PRESS.
RATING (PSI)
PRE-CHARGE
PRESSURE (PSI)
DIMENSIONAL DATA
NOTES
EXPANSION TANK SCHEDULE
4. 3" NPT BOILER HW SUPPLY AND RETURN CONNECTIONS
3. HEAT EXCHANGER TUBE BUNDLE TUBES TO BE SEAMLESS DOUBLE-WALL COPPER
2. HEAT EXCHANGER PERFORMANCE IS BASED ON TANK IT SERVES. SEE HOT WATER GENERATOR TANK SCHEDULE THIS SHEET AND COORDINATE WITH TANK MANUFACTURER.
1. SEE PROJECT SPECIFICATIONS BOOK FOR ADDITIONAL PRODUCT REQUIREMENTS.
NOTES:
HWG-2 POWERHOUSE DOMESTIC HW BELL & GOSSETT TCW-1260-4 U-TUBE TANK HEATER 4 1250 WATER 180 160 125 WATER 40 140 1500 1, 2, 3, 4
HWG-1 POWERHOUSE DOMESTIC HW BELL & GOSSETT TCW-1260-4 U-TUBE TANK HEATER 4 1250 WATER 180 160 125 WATER 40 140 1500 1, 2, 3, 4
FLUID TYPE
ENTERING
FLUID TEMP (°F)
LEAVING FLUID
TEMP (°F)
FLOW (GPM) FLUID TYPE
ENTERING
FLUID TEMP (°F)
LEAVING FLUID
TEMP (°F)
FLOW
(GPH)
DESIGNATION LOCATION SERVICE MANUFACTURER MODEL TYPE
NO. OF
PASSES
LOAD
(MBH)
TUBE SIDE TANK SIDE
NOTES
HOT WATER GENERATOR HEAT EXCHANGER SCHEDULE
BID ALTERNATE NO. 1: FABRICATE HOT WATER TANK WITH GRADE 2205 (DUPLEX) STAINLESS STEEL IN LIEU OF CEMENT-LINED STEEL
WIRING DEVICES
DUPLEX RECEPTACLE, WALL MOUNT
DOUBLE DUPLEX RECEPTACLE, GFCI, WALL MOUNT
SIMPLEX RECEPTACLE, WALL MOUNT
DUPLEX RECEPTACLE, GFCI, WALL MOUNT
DOUBLE DUPLEX RECEPTACLE, WALL MOUNT
J JUNCTION BOX, WALL MOUNT
J JUNCTION BOX, CEILING MOUNT
DUPLEX RECEPTACLE, CEILING MOUNT
DOUBLE DUPLEX RECEPTACLE, CEILING MOUNT
SPECIAL RECEPTACLE AS NOTED, WALL MOUNT
SPECIAL RECEPTACLE AS NOTED, CEILING MOUNT
W# WALL BOX, W# INDICATES TYPE, REFERENCE SCHEDULE
F# FLOOR BOX, F# INDICATES TYPE, REFERENCE SCHEDULE
DEAD-FRONT GFCI DEVICE, WALL MOUNT
PUSH BUTTON, BUTTON QUANTITY AS REQUIRED
MULTI-OUTLET ASSEMBLY AS INDICATED
MOTOR-RATED SWITCH
R RELAY
GENERAL NOTE
ALL SYMBOLS, ABBREVIATIONS, NOTES, ETC. MAY NOT BE USED ON ALL PROJECTS.
ANNOTATIONS
LIGHTING CONTROL TAG, REFERENCE SOOXXX
# KEY NOTE, AS INDICATED
PANEL ZONE BOUNDARY
DAYLIGHT ZONE BOUNDARY, P = PRIMARY AND S = SECONDARY
WHERE PRESENT
UNDERGROUND WIRING / CONDUIT
LIGHTING CONTROL AREA
NOT IN SCOPE AREA
FEEDER TAG, REFERENCE SCHEDULEXXX-X
FOOD SERVICE EQUIPMENT TAG, REFERENCE SCHEDULEXXX
EXX MISCELLANEOUS EQUIPMENT TAG, REFERENCE SCHEDULE
X
X: DEVICE TYPE, REFERENCE BELOW
#: CIRCUIT NUMBER
DEVICE TYPES
WIRING DEVICE TAGS - WHERE APPLICABLE
AC ABOVE COUNTER
C CONTROLLED
D DROP CORD
F SURFACE MOUNT
H HORIZONTALLY MOUNTED
R CORD REEL
S SWITCHED
T TAMPER RESISTANT
U USB
W WEATHERPROOF IN-USE TYPE COVER
POWER DISTRIBUTION
PANELBOARD, SURFACE MOUNT, AS INDICATED
PANELBOARD, RECESS MOUNT, AS INDICATED
M METER
NON-FUSED DISCONNECT SAFETY SWITCH
FUSED DISCONNECT SAFETY SWITCH
MOTOR STARTER
COMBINATION MOTOR STARTER / FUSED DISCONNECT SAFETY SWITCH
SPD SURGE PROTECTIVE DEVICE
VFD VARIABLE FREQUENCY DRIVE
ENCLOSED CIRCUIT BREAKER
MH MANHOLE
HH HANDHOLE
T INTERIOR DRY-TYPE TRANSFORMER AS INDICATED
M MOTOR
GROUND BAR, AS INDICATED
ELECTRICAL EQUIPMENT ON CONCRETE PAD, AS INDICATED
RGAP REMOTE GENERATOR ANNUNCIATOR PANEL
PAD MOUNT UTILITY TRANSFORMER
T
POLE MOUNT UTILITY TRANSFORMER
CONTINUATION
# REVISION, AS INDICATED
CONDUIT STUB
XX
CALLOUT; ## INDICATES VIEW, XX INDICATES SHEET
DEMOLISHED ITEM / AREA
STANDARD MOUNTING HEIGHTS UNO
MOUNTING HEIGHT NOTES
WHERE IN CONFLICT, ARCHITECTURAL DRAWINGS SHALL TAKE PRECEDENCE OVER
MOUNTING HEIGHTS INDICATED ON ELECTRICAL DRAWINGS. THE INDICATED DIMENSIONS
ARE TO CENTERLINE UNO.
RFERENCE WALL DEVICE MOUNTING ELEVATION FOR FURTHER INFORMATION
RECEPTACLES IN EQUIPMENT ROOMS 46"
EXTERIOR AND GARAGE RECEPTACLES 24"
PANELBOARDS 72" (TOP BREAKER)
CONTROL PANELS 66" (TOP)
ANNUNCIATOR PANELS 48" (TOP)
54"SAFETY DISCONNECT SWITCHES
54"STARTERS
OTHER ALARMS, SWITCHES, AND CONTROL DEVICES
NOT INDICATED HERE OR ON WALL DEVICE MOUNTING
ELEVATION
46"
18"JUNCTION BOXES
UTIL
UTIL
EMERGENCY POWER, MOUNTING AS INDICATED
DUPLEX RECEPTACLE, GFCI, CEILING MOUNT (CORD REEL / DROP CORD
ONLY)
DOUBLE DUPLEX RECEPTACLE, GFCI, CEILING MOUNT (CORD REEL /
DROP CORD ONLY)
HORIZONTAL CABLE PATHWAY TAG, REFERENCE SCHEDULEHXXX
PP POWER POLE
AAA
PANEL ZONE BOUNDARY TAG
AAA = NORMAL CIRCUIT
BBB = EMERGENCY/LIFE SAFETY CIRCUIT (WHEN PRESENT)
CCC = REQUIRED STANDBY/CRITICAL CIRCUIT (WHEN PRESENT)
DDD = OPTIONAL STANDBY CIRCUIT (WHEN PRESENT)
BBB
CCC
DDD
APPLICABLE CODES:
A. 2015 INTERNATIONAL BUILDING CODE AS ADOPTED BY IOWA ADMINISTRATIVE
RULES 661-201 AND 661-301
B. 2015 INTERNATIONAL EXISTING BUILDING CODE AS ADOPTED BY IOWA
ADMINISTRATIVE RULE 661-301 AND 661-350, AS APPLICABLE.
C. 2010 AMERICANS WITH DISABILITIES ACT AS ADOPTED BY IOWA
ADMINISTRATIVE RULE 661-302
MEP ENGINEER:
RESOURCE CONSULTING
ENGINEERS, LLC
301 ALEXANDER AVENUE
SUITE C
AMES, IA 50010
515-292-2500 www.resourcece.com
PROJECT NO:
ISSUED:
DATEMARK
©2025
RESOURCE CONSULTING
ENGINEERS, LLC
REVISION INFORMATION
KEY PLAN
DESCRIPTION
2024.029
N O
R T
H C
E N
T R
A L
C O
R R
E C
T
IO
N A
L
F A
C
IL
IT
Y
P
O W
E R
H O
U S
E
.0
D O
C N
C C
F P
O W
E R
H O
U S
E W
A T
E R
H E
A T
E R
R E
P L
A C
E M
E N
T S
C D
E000
ELECTRICAL SYMBOL
LEGEND
L
A N
E D
A L
E
R O
C K
W E
L L
C
IT
Y
IA
3/14/2025
THESE DOCUMENTS HAVE BEEN PREPARED BY RESOURCE
CONSULTING ENGINEERS, LLC FOR THE 9458.00 - DOC NCCF
POWERHOUSE WATER HEATER REPLACEMENTS PROJECT. THE
DOCUMENTS SHALL REMAIN THE PROPERTY OF RESOURCE
CONSULTING ENGINEERS, LLC, AND SHALL NOT BE USED ON OTHER
PROJECTS, OR IN OTHER LOCATIONS WITHOUT THE EXPRESS
WRITTEN APPROVAL AND PARTICIPATION OF RESOURCE
CONSULTING ENGINEERS, LLC. RESOURCE CONSULTING ENGINEERS,
LLC SHALL RETAIN ALL COMMON LAW, STATUTORY, AND OTHER
RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
ELECTRICAL SHEET INDEX
SHEET DESCRIPTION
E000 ELECTRICAL SYMBOL LEGEND
E001 ELECTRICAL PROJECT NOTES AND ABBREVIATIONS
E002 ELECTRICAL PROJECT SCHEDULES
ED101 LEVEL 1 - ELECTRICAL PLAN - DEMOLITION
E201 LEVEL 1 - POWER PLAN - NEW WORK
E820 POWER SCHEDULES
GENERAL NOTE
ALL SYMBOLS, ABBREVIATIONS, NOTES, ETC. MAY NOT BE USED ON ALL PROJECTS.
GENERAL PROJECT NOTES
A. THE ENTIRE INSTALLATION SHOWN IN THE CONSTRUCTION DOCUMENTS SHALL BE
IN ACCORDANCE WITH THE REQUIREMENTS INDICATED BELOW. IN THE EVENT OF
CONFLICT BETWEEN THESE CONSTRUCTION DOCUMENTS AND THE INDICATED
REQUIREMENTS, THE STRICTER SHALL APPLY. ANY ADDITIONAL COSTS
ASSOCIATED WITH ENSURING THE PROJECT COMPLIES WITH THE INDICATED
REQUIREMENTS SHALL BE INCLUDED IN THE PROJECT BID(S).
a. ALL APPLICABLE LOCAL, CITY, STATE, AND NATIONAL CODES, LAWS, ACTS, AND ORDINANCES
b. ALL AUTHORITIES HAVING JURISDICTION
c. THE OWNER'S INSURANCE COMPANY REQUIREMENTS
d. UTILITY COMPANY REQUIREMENTS
e. APPLICABLE INDUSTRY STANDARDS OF GOOD PRACTICE AND SAFETY
f. THE MANUFACTURER'S STRICTEST REQUIREMENTS AND RECOMMENDATIONS
FOR EQUIPMENT AND PRODUCT APPLICATION AND INSTALLATION
B. THE CONSTRUCTION DOCUMENTS ARE SCHEMATIC IN NATURE AND SHALL BE
ADAPTED TO ACTUAL SITE CONDITIONS AND OWNER'S REQUIREMENTS AS
REQUIRED AT NO ADDITIONAL COST. THE CONSTRUCTION DOCUMENTS ARE NOT
INTENDED TO CONTAIN EVERY DETAIL THAT IS APPLICABLE TO THE PROJECT. IT IS
THE CONTRACTOR'S RESPONSIBILITY TO REVIEW ALL CONTRACT DOCUMENTS AND
TO COORDINATE WITH ALL OTHER TRADES AND EXISTING/SITE CONDITIONS TO
PROVIDE A FULLY FUNCTIONAL SYSTEM PER THE INDICATED DESIGN INTENT.
C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CLEAN UP DURING AND AT
CONCLUSION OF CONSTRUCTION PERIOD. NO MATERIALS SHALL BE LEFT ON SITE
WHEN WORK IS COMPLETED, UNLESS REQUESTED BY OWNER'S REPRESENTATIVE.
ALL MATERIALS SHALL BE DISPOSED OF PROPERLY.
D. THE CONTRACTOR SHALL COORDINATE SERVICE INTERRUPTIONS WITH THE
OWNER'S REPRESENTATIVE A MINIMUM OF 10 DAYS IN ADVANCE.
E. ELECTRICAL WORK SHALL BE PERFORMED ON DE-ENERGIZED SYSTEMS ONLY.
WHERE WORK ON EXISTING SYSTEMS WILL REQUIRE INTERRUPTION OF
ELECTRICAL SERVICE, THEN TEMPORARY PROVISIONS ACCEPTABLE TO THE OWNER
FOR TEMPORARY POWER SHALL BE UTILIZED UNTIL THE WORK IS COMPLETE.
F. COORDINATE FINAL LOCATIONS OF DEVICES IN UNFINISHED AREAS WITH PIPING,
DUCTWORK, EQUIPMENT, CABLE TRAY, ETC. TO AVOID CONFLICTS. MAKE MINOR
ADJUSTMENTS TO DEVICE LOCATIONS AS REQUIRED.
G. WORK INDICATED IN THESE DOCUMENTS SHALL BE PERFORMED BY INDIVIDUALS
LICENSED TO PERFORM SUCH WORK BY THE STATE IN WHICH THE WORK IS
PERFORMED AND ADEQUATELY QUALIFIED TO WORK ON THE ASSOCIATED
EQUIPMENT, SYSTEM, ETC.
H. OBTAIN ALL PERMITS REQUIRED TO FULLY COMPLETE INDICATED WORK.
I. PROVIDE PULL AND JUNCTION BOXES AS REQUIRED TO MEET CODE AND
INSTALLATION REQUIREMENTS. PULL AND JUNCTION BOXES SHALL BE
CONCEALED IN FINISHED SPACES.
J. ALL DEVICES, EQUIPMENT, HARDWARE, COMPONENTS, ETC. USED ON THE PROJECT
SHALL BE LISTED AND LABELED IN ACCORDANCE WITH THE NEC BY A QUALIFIED
ELECTRICAL TESTING LABORATORY RECOGNIZED BY AUTHORITIES HAVING
JURISDICTION AND MARKED FOR INTENDED LOCATION AND APPLICATION.
K. EQUIPMENT, DEVICES, ETC. SHALL BE TESTED FOR PROPER CONNECTIVITY AND
FUNCTIONALITY AFTER INSTALLATION. COMPLY WITH MANUFACTURER’S
RECOMMENDATIONS AND INDUSTRY STANDARDS. REMOVE AND REPLACE
DEFECTIVE EQUIPMENT, DEVICES, ETC. AND RETEST UNTIL PROPER
FUNCTIONALITY IS CONFIRMED.
L. EQUIPMENT, DEVICES, CONDUCTORS, CABLES, ETC. INSTALLED IN PLENUM SPACES
SHALL BE PLENUM RATED.
M. PROTECT EQUIPMENT, DEVICES, ETC. FROM MOISTURE DURING SHIPPING,
STORAGE, AND HANDLING.
N. EQUIPMENT, DEVICES, ETC. SHALL BE DELIVERED IN MFR'S ORIGINAL UNOPENED
AND UNDAMAGED PACKAGES WITH MFR'S LABELS LEGIBLE AND INTACT. INSPECT
MFR'S PACKAGES UPON RECEIPT.
O. EQUIPMENT, DEVICES, ETC. SHALL BE SECURELY FASTENED TO STRUCTURAL
SUPPORT WITHOUT DISTORTION AND INSTALLED LEVEL, PLUMB, AND SQUARE
WITH CEILINGS, WALLS, FLOORS, AND FINISHED GRADE AS APPLICABLE UNO.
P. PROVIDE ANY PROPRIETARY EQUIPMENT AND SOFTWARE REQUIRED TO MAINTAIN,
REPAIR, ADJUST, OR IMPLEMENT FUTURE CHANGES TO DEVICES/EQUIPMENT
INSTALLED AS A PART OF THIS PROJECT.
Q. AFTER INSTALLATION, PROTECT DEVICES, EQUIPMENT, ETC. FROM CONSTRUCTION
ACTIVITIES. REMOVE AND REPLACE ITEMS THAT ARE CONTAMINATED, DEFACED,
DAMAGED, OR OTHERWISE CAUSED TO BE UNFIT FOR USE PRIOR TO ACCEPTANCE
BY OWNER.
R. EXAMINE WALLS, FLOORS, CEILINGS, ROOFS, ETC. FOR SUITABLE MOUNTING
MOUNTING CONDITIONS PRIOR TO INSTALLING DEVICES, EQUIPMENT, ETC.
S. VISIBLY INSPECT ALL DEVICES, EQUIPMENT, ETC. FOR PHYSICAL AND MECHANICAL
CONDITION, CLEANLINESS, ETC. PRIOR TO INSTALLATION. REPLACE ANY ITEMS
THAT ARE DAMAGED, DEFECTIVE, OR OTHERWISE UNSUITABLE FOR INSTALLATION.
T. FOR ANY SYSTEMS, DEVICES, ETC. REQUIRING CONNECTION TO OWNER'S IT
INFRASTRUCTURE, COORDINATE WITH OWNER'S IT REPRESENTATIVE AS REQUIRED
PRIOR TO COMMENCING CONSTRUCTION.
ABBREVIATIONS
A AMPERE
AC AIR CONDITIONER
ADO…