RFB941800-00 - Drawings.pdf
PDF 2 MB Posted
- Attached to
- HCR BAS Replacement
- Solicitation number
- 005-RFBCON-1364-2025
- Issued by
- Allamakee County, Iowa
About this file
This document is a set of mechanical drawings and project specifications for the building automation system (BAS) improvements at the Honey Creek Resort in Moravia, Iowa. The project is being led by the State of Iowa Department of Administrative Services (DAS) and designed by the Farnsworth Group. The project scope includes replacing existing controllers, sensors, and sequences of operation for air handling units, heat pumps, exhaust fans, pool systems, domestic hot water systems, and other building systems. The project will be commissioned, and the contractor is required to coordinate with the commissioning agent. The project is scheduled to be completed by September 20, 2024.
The drawings and specifications provide detailed information on the new controls, including points lists, sequence of operations, and control schematics for the various mechanical systems. Pricing terms, funding sources, and other contractual details are not included in this document. The incumbent contractor is not specified. The project will be publicly bid, and the contractor will need to meet all state and local requirements to be awarded the contract.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFB941800-00 - Notice to Bidders.pdf | ||
| RFB941800-00 - Bid Form.pdf | ||
| 1268901-event.pdf | ||
| RFB941800-00 - Project Manual.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OWNER: STATE OF IOWA DAS PROJECT NUMBER: 9418.00
DESIGNER: FARNSWORTH GROUP
SHEET NUMBER:
SHEET of
HONEY CREEK LODGE - BAS
DAS PROJECT NAME: DNR HCR Building Automation System Improvements
/2
/2
:2 :4
A
M
9418.00 - HONEY CREEK RESORT
BUILDING AUTOMATION SYSTEM
IMPROVEMENTS
12633 Resort Dr, Moravia, IA 52571
09/20/2024
M0.00
PAGES OR DIVISIONS COVERED:
LICENSE RENEWAL DATE:
DATE:
NAME:
SIGNATURE:
THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW
WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL
Wade Ross
12/31/2025
ALL
SUPERVISION. I AM A DULY LICENSED ENGINEER UNDER THE
LAWS OF THE STATE OF IOWA.
9/20/2024
BD BOILER BLOW DOWN
CD CONDENSATE DRAIN
CWS CONDENSER WATER SUPPLY
HCWS DUAL TEMPERATURE SUPPLY
HPS HIGH PRESSURE STEAM
HRS HEAT RECOVERY SUPPLY
HTWS HIGH TEMP WATER SUPPLY
HWS HOT WATER SUPPLY
LPS LOW PRESSURE STEAM
LS LOOP SUPPLY
MPS MEDIUM PRESSURE STEAM
PD PUMP DISCHARGE
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
CHR CHILLED WATER RETURN
CWR CONDENSER WATER RETURN
HCWR DUAL TEMPERATURE RETURN
HPR HIGH PRESSURE STEAM CONDENSATE RETURN
HRR HEAT RECOVERY RETURN
HTWR HIGH TEMP WATER RETURN
HWR HOT WATER RETURN
LPR LOW PRESSURE STEAM CONDENSATE RETURN
LR LOOP RETURN
MPR MEDIUM PRESSURE STEAM CONDENSATE RETURN
ABOVE CEILING/AIR CONDITIONERAC
OUTDOOR AIROA
AIR COOLED CONDENSERACC
AIR FILTERAF
ABOVE FINISHED FLOORAFF
AIR HANDLING UNITAHU
AIR MEASURING STATIONAMS
AIR SEPARATORAS
AUTOMATIC AIR VENTAV
BOILERB
BUILDING AUTOMATION SYSTEMBAS
BACKDRAFT DAMPERBDD
BELOW FINISHED CEILINGBFC
BACKFLOW PREVENTION DEVICEBFP
BETWEEN JOISTSBJ
BOTTOM OF DUCTBOD
BOTTOM OF PIPEBOP
BRITISH THERMAL UNITS PER HOURBTUH
COMPRESSED AIRCA
COUNTER BALANCED SHUTTERCBS
COOLING COILCC
CEILING / CIRCULATING FANCF
CUBIC FEET PER MINUTECFM
CHILLERCH
CHILLED WATER PUMPCHP
CHILLED WATER RETURNCHR
CHILLED WATER SUPPLYCHS
CONVECTORCNV
CONDENSATECOND
CONDENSATE PUMPCP
COMPUTER ROOM AIR CONDITIONERCRAC
COOLING TOWERCT
CONDENSING UNITCU
CABINET UNIT HEATERCUH
CONTROL VALVECV
DOMESTIC COLD WATERCW
CONDENSER WATER PUMPCWP
CONDENSER WATER RETURNCWR
CONDENSER WATER SUPPLYCWS
DRY COOLERDC
DN DOWN
DP DIFFERENTIAL PRESSURE
DS DUCT SILENCER
EA EXHAUST AIR
EBB ELECTRIC BASEBOARD HEATER
EF EXHAUST FAN
EG EXHAUST GRILLE (LESS DAMPER)
EHC ELECTRIC HEATING COIL
EL ELEVATION
ER EXHAUST REGISTER
ERV ENERGY RECOVERY VENTILATOR
ET EXPANSION TANK
FA FRESH AIR
FD FIRE DAMPER
FDC FLEXIBLE DUCT CONNECTION
FFA FROM FLOOR ABOVE
FFB FROM FLOOR BELOW
FPC FLEXIBLE PIPE CONNECTION
FPT FAN POWERED AIR TERMINAL
FT FINNED TUBE RADIATION
GF GAS FURNACE
GIH GRAVITY INTAKE HOOD
GPM GALLONS PER MINUTE
GR GLYCOL RETURN
GS GLYCOL SUPPLY
GUH GAS UNIT HEATER
HU HUMIDIFIER
HC HEATING COIL
HCWR DUAL TEMPERATURE RETURN
HCWS DUAL TEMPERATURE SUPPLY
HP HEAT PUMP
HPR HIGH PRESSURE STEAM RETURN
HPS HIGH PRESSURE STEAM SUPPLY
HRC HEAT RECOVERY COIL
HS HUMIDITY SENSOR
HWP HOT WATER PUMP
HWR HOT WATER RETURN
LOW PRESSURE STEAM SUPPLY
LOW PRESSURE STEAM RETURN
KITCHEN HOOD - COMMERCIAL
HEAT EXCHANGER
HOT WATER SUPPLY
LPS
LPR
KH
HX
HWS
THOUSANDS OF BTU PER HOUR
MOTORIZED DAMPER
MAKEUP AIR UNIT
MIXED AIR
MBH
MD
MAU
MA
OBD OPPOSED BLADE DAMPER
P PUMP
PBD PARALLEL BLADE DAMPER
PRV PRESSURE RELIEF VALVE
PS PRESSURE SWITCH
PSI POUNDS PER SQUARE INCH
PTAC
RA RETURN AIR
RF RETURN AIR FAN
RG RETURN GRILLE (LESS DAMPER)
RH ROOF HOOD
RHC REHEAT COIL
RLFA RELIEF AIR
RPZ REDUCED PRESSURE BFP
RR RETURN REGISTER (WITH DAMPER)
RTU ROOFTOP AIR HANDLING UNIT
SA SUPPLY AIR
SAS SELF-ACTING SHUTTER
SD SUPPLY DIFFUSER/SMOKE DAMPER
SF SUPPLY FAN / SQUARE FOOT
SFD SMOKE/FIRE DAMPER
SG SUPPLY GRILLE
SR SUPPLY REGISTER
TCAC TEMP. CONTROL AIR COMPRESSOR
TCAD TEMP. CONTROL AIR DRYER
TDV TRIPLE DUTY VALVE
TFA TO FLOOR ABOVE
TFB TO FLOOR BELOW
TOD TOP OF DUCT
TOP TOP OF PIPE
UC UNIT COOLER
UFD UNDERFLOOR DUCT
UH UNIT HEATER
UV UNIT VENTILATOR
VAV VARIABLE AIR VOLUME TERMINAL
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
AUTOMATIC AIR VENT
TEMPERATURE SENSOR/SWITCH
PRESSURE GAUGE
THERMOMETER
PIPE ANCHOR
PIPE GUIDES
MANUAL AIR VENT
FLOW SENSOR/SWITCH
PIPE EXPANSION JOINT
PIPE UNION
CONCENTRIC REDUCER
ECCENTRIC REDUCER
WYE STRAINER
WYE STRAINER W/DRAIN VALVE
DIRECTION OF FLOW
STEAM BUCKET TRAP
STEAM F&T TRAP
BACKFLOW PREVENTER
PIPE TURNING UP
PIPE TURNING DOWN
TEE OFF TOP
TEE OFF BOTTOM
PIPE TEE
PIPE CAP
PLAN 90 DEGREE ELBOW
PLAN 45 DEGREE ELBOW
PIPING SYSTEM (SOLID LINE)
PIPING SYSTEM (DASHED LINE)
MOTORIZED SHUTTER
NOT TO SCALE
MS
NTS
GENERAL
HYDRONIC VENTILATION
GENERAL NOTES
DEMOLITION
UFT UNDERFLOOR FAN TERMINAL
HRV HEAT RECOVERY VENTILATOR (SENSIBLE)
EUH ELECTRIC UNIT HEATER
ESP EXTERNAL STATIC PRESSURE
INTERNAL STATIC PRESSUREISP
TSP TOTAL STATIC PRESSURE
PUMP
PC PLUMBING CONTRACTOR
EC ELECTRICAL CONTRACTOR
GC GENERAL CONTRACTOR
FLEXIBLE PIPE CONNECTOR
FCU FAN COIL UNIT
ALUMINUMAL
VRP VERTICAL RADIANT PANEL
WAC WINDOW / WALL AIR CONDITIONER
DOOR AIR CURTAINDAC
DH DEHUMIDIFIER
DOAS DEDICATED OUTDOOR AIR SYSTEM
DSU DUCTLESS SPLIT UNIT
DX DX COOLING COIL
ERP ELECTRIC RADIANT PANEL
GRH GAS RADIANT HEATER
LOUVERL
PDH POOL ROOM DEHUMIDIFIER
PACKAGED TERMINAL AIR CONDITIONER
RP RADIANT PANEL
S1 12x12
EXISTING
EQUIPMENT TYPE
EQUIPMENT MARK
SHEET #
DETAIL #
AIRFLOW IN CFM
THROAT SIZE
MECHANICAL EQUIPMENT TAG
AIR TERMINAL DESIGNATION
KEYNOTE
DETAIL OR SECTION MARK
POINT OF NEW CONNECTION
CAP EXISTING PIPE OR DUCT
BOLD TEXT INDICATES PROPOSED ITEM
ITALIC TEXT INDICATES EXISTING ITEM
NEW
PRESSURE/TEMPERATURE PLUG
AHU-1
GUARD LOCKABLE GUARD WHERE INDICATED
EQUIPMENT TO BE CONTROLLED
GUARD
TEMP
HUMID
CO
ELEMENT TO BE MONITORED
LOCKABLE GUARD WHERE INDICATED
HUMIDISTAT
THERMOSTAT
SENSOR
SUPPLY DIFFUSER/REGISTER
RETURN REGISTER/GRILLE
EXHAUST REGISTER/GRILLE
DIFFUSER AIRFLOW PATTERN IF
OTHER THAN 4-WAY BLOW
FLEXIBLE BRANCH RUNOUT TO SUPPLY
DIFFUSER, 36" MAX LENGTH
CEILING RETURN REGISTER WITH LINED
DUCT FOR SOUND ATTENUATION OPEN
TO CEILING PLENUM
FLEXIBLE DUCT CONNECTION TO
EQUIPMENT OR BETWEEN DUCTS
VOLUME DAMPER
MOTORIZED DAMPER
FIRE DAMPER
SMOKE DAMPER
COMBINATION FIRE/SMOKE DAMPER
SUPPLY AIR DUCT TOWARDS
SUPPLY AIR DUCT AWAY
RETURN/OUTDOOR AIR DUCT TOWARDS
RETURN/OUTDOOR AIR DUCT AWAY
TRANSFER AIR
A. INSTALL EQUIPMENT TO ALLOW MAXIMUM POSSIBLE HEADROOM UNLESS SPECIFIC MOUNTING
HEIGHTS ARE INDICATED
B. INSTALL EQUIPMENT LEVEL AND PLUMB, PARALLEL AND PERPENDICULAR TO OTHER BUILDING
SYSTEMS AND COMPONENTS IN EXPOSED INTERIOR SPACES, UNLESS OTHERWISE INDICATED
C. INSTALL HVAC EQUIPMENT TO FACILITATE SERVICE, MAINTENANCE, AND REPAIR OR REPLACEMENT OF COMPONENTS. CONNECT EQUIPMENT FOR EASE OF REMOVAL, WITH MINIMUM INTERFERENCE TO
OTHER INSTALLATIONS
D. THE INSTALLING CONTRACTOR ASSUMES FULL RESPONSIBILITY FOR ALL MECHANICAL EQUIPMENT
PUT INTO OPERATION PRIOR TO THE INSTALLATION OF A WORKING CONTROL SYSTEM.
A. VERIFY EXACT SIZE AND LOCATION OF EXISTING UTILITIES PRIOR TO START OF DEMOLITION WORK
B. RELOCATE, REMOVE, AND ADJUST ALL MECHANICAL AND ELECTRICAL ITEMS AS REQUIRED TO
ACCOMPLISH SCOPE OF NEW WORK
C. EXISTING MECHANICAL ITEMS ARE SHOWN IN SCHEMATIC FORM BASED UPON EXISTING
CONSTRUCTION DOCUMENTS AND/OR FIELD INVESTIGATION
D. FIXTURES AND EQUIPMENT INDICATED TO BE REUSED OR SALVAGED SHALL REMAIN THE
PROPERTY OF THE OWNER AND BE STORED IN A LOCATION AS DIRECTED BY OWNER'S
REPRESENTATIVE
E. IN LOCATIONS WHERE EXISTING CONSTRUCTION IS REMOVED AND NO ADDITIONAL CONSTRUCTION IS INDICATED, PATCH EXISTING CONSTRUCTION TO MATCH ADJACENT SURFACES AND FINISHES
MECHANICAL EQUIPMENT INSTALLATION
PRESSURE SENSOR/SWITCH
EXHAUST AIR DUCT TOWARDS
EXHAUST AIR DUCT AWAY
TJ THROUGH JOISTS
CHS CHILLED WATER SUPPLY
CO2
3-WAY CONTROL VALVE
ANGLE GATE VALVE
ANGLE GLOBE VALVE
BALANCING/SHUTOFF VALVE
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
CALIBRATED BALANCING VALVE
CONTROL VALVE
EXPANSION VALVE
GATE VALVE
GLOBE VALVE
QUICK OPEN VALVE
SAFETY RELIEF VALVE
SOLENOID VALVE
VACUUM RELIEF VALVE
GAS COCK
PLUG VALVE
PRESSURE REDUCING VALVE (WATER)
PRESSURE REGULATOR (GAS)
PIPE SLOPE ARROW
WALL SWITCH
H
S
T
CFM
F
P
T
FLAT OVAL DUCT12x8Φ
ROUND DUCT12"ø
RECTANGULAR DUCT12x8
AHU
METERM
MECHANICAL CONTRACTORMC
SYMBOLS LEGEND
NOTE: NOT ALL SYMBOLS ARE USED IN CONSTRUCTION DOCUMENTS
ABBREVIATIONS
LINE STYLE INDICATES DEMOLISHED ITEM
DDC CONTROLS
PROVIDE NEW FRONT END NETWORK MANAGER WITH WEB CABILITY. 1 YEAR SOFTWARE
MAINTENANCE AGREEEMENT, NEW GRAPHICS, ALARMING CAPABILITY FROM REMOTE LOCATION
THROUGH PHONE, TABLET, COMPUTER.
REPLACE EXISTING CONTROLLERS WITH NEW. PROVIDE NEW SENSORS WHERE INDICATED
THE PROJECT WILL BE COMMISSIONED. THE COMMISSIONING AGENT WILL BE HIRED BY THE OWNER.
COORDINATE EFFORTS WITH THE COMMISSIONING AGENT AND SPECIFICATIONS.
www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
100 WALNUT STREET, SUITE 200
PEORIA, ILLINOIS 61602
(309) 689-9888 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:2 :4
A
M M0.1
GENERAL
INFORMATION
LDE
WCR
0241027.00
9418.00 - HONEY
CREEK RESORT
BUILDING
AUTOMATION
SYSTEM
IMPROVEMENTS
12633 Resort Dr, Moravia, IA 52571
09/20/2024
WCR
PERMIT SET
SHEET LIST
Discipline No. Description
MECHANICAL M0.00 COVER SHEET
MECHANICAL M0.1 GENERAL INFORMATION
MECHANICAL M1.1 LOWER LEVEL AREA A
MECHANICAL M1.2 LOWER LEVEL AREA B
MECHANICAL M1.3 FIRST FLOOR PLAN AREA A
MECHANICAL M1.4 FIRST FLOOR PLAN AREA B
MECHANICAL M1.5 FIRST FLOOR PLAN AREA C
MECHANICAL M1.6 SECOND FLOOR PLAN AREA A
MECHANICAL M1.7 SECOND FLOOR PLAN AREA B
MECHANICAL M1.8 THIRD FLOOR PLAN AREA A
MECHANICAL M1.9 THIRD FLOOR PLAN AREA B
MECHANICAL M5.1 CONTROLS DIAGRAMS
MECHANICAL M5.2 CONTROLS DIAGRAMS
MECHANICAL M5.3 CONTROLS DIAGRAMS
MECHANICAL M5.4 CONTROLS DIAGRAMS
1 09/20/24 Permit Set
T T T T T T T T
T
ERV
ERV
ATA
ATA
ATA
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
4 4 4 4 4 4
4 44 44 44
T
ATA-2
T ATA-1
ELEC. ROOM
A006
T
ATA-1
T H
EF
EF
(TYP 4)
T
EF
www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
100 WALNUT STREET, SUITE 200
PEORIA, ILLINOIS 61602
(309) 689-9888 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:2 :4
A
M M1.1
LOWER LEVEL AREA
A
LDE
WCR
0241027.00
9418.00 - HONEY
CREEK RESORT
BUILDING
AUTOMATION
SYSTEM
IMPROVEMENTS
12633 Resort Dr, Moravia, IA 52571
09/20/2024
WCR
PERMIT SET
0 4 8 16
NORTH
TRUE
D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.
C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.
B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR
EQUIPMENT SHUT DOWNS.
A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR
OTHER EQUIPMENT IS REMOVED.
GENERAL NOTES
SCALE: 1/8" = 1'-0"
FIRST FLOOR VENTILATION PLAN
#KEYNOTES
1 REPLACE EXISTING THERMOSTAT FOR EXISTING AIR TO AIR HEAT PUMP WITH PROGRAMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT PUMP. PROVIDE NEW LEAVING AIR TEMPERATURE SENSOR AND FILTER DIFFERENTIAL
PRESSURE SWITCH. REVISE SEQUENCE OF OPERATION.
2 REPLACE EXISTING CONTROLS FOR ERV-2. REVISE SEQUENCE OF OPERATIONS PER DETAIL 2 ON SHEET M5.2.
RECOMMISSION AND REBALANCE UNIT.
3 EXISTING ERV SERVING THE POOL AREA. REPLACE EXISTING CONTROLS, THERMOSTAT AND HUMIDSTAT. REFER TO
DETAIL 2 ON SHEET M5.4.
4 REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT PUMP WITH PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT PUMP.REMOVE ALL WIRING. PROVIDE NEW LEAVING AIR TEMPERATURE SENSOR, WATER SENSOR AND FILTER DIFFERENTIAL PRESSURE SWITCH. PROVIDE NEW WIRING AND CONDUIT AS
REQUIRED. REVISE SEQUENCE OF OPERATION, REFER TO DETAIL 1 ON SHEET M5.1.
5 REMOVE AND REPLACE EXISTING DDC CONTROLLERS. PROVIDE NEW WIRING TO EXISTING AND NEW CONTROLS.
6 FOUR EXISTING 24X32 MOTORIZED DAMPERS LOCATED IN EXISTING DUCTWORK. REPLACE THE EXISTIGN ACTUATORS AND PROVIDE NEW CONTROLS, REFER TO DETAIL 3 ON M5.2 FOR NEW SEQUENCE OF OPERATION.
7 POOL ROOM EXHAUST FAN AND MOTORIZED DAMPER. REPLACE THE EXISTING ACTUATOR. PROVIDE NEW CONTROLS.
REFER TO DETAIL 1 ON SHEET M5.2 FOR NEW SEQUENCE OF OPERATION.
8 REPLACE EXISTING THERMOSTAT AND PROVIDE NEW CONTROLS AND SEQUENCE FOR ELEVATOR ROOM FAN
CONTROLS. REFER TO DETAIL 3 ON SHEET M5.1 FOR NEW SEQUENCE OF OPERATION.
9 PROVIDE NEW CONTROLLER FOR WADING POOL CONTROLS, INCLUDING HEATER, FILTER DP, PUMP AND TEMPERATURE
SENSORS. REFER TO DETAIL 6 ON SHEET M5.3 FOR NEW SEQUENCE OF OPERATION.
10 PROVIDE NEW CONTROLLER FOR PLUNGE POOL CONTROLS, INCLUDING HEATER, FILTER DP, PUMP AND TEMPERATURE
SENSORS. REFER TO DETAIL 6 ON SHEET M5.3 FOR NEW SEQUENCE OF OPERATION.
11 PROVIDE NEW CONTROLLER FOR SPA POOL CONTROLS, INCLUDING HEATER, FILTER DP, PUMP AND TEMPERATURE
SENSORS. REFER TO DETAIL 6 ON SHEET M5.3 FOR NEW SEQUENCE OF OPERATION.
12 PROVIDE NEW TEMPERATURE SENSOR. SENSOR TO MONITOR TEMPERATURE IN SPACE AND REPORT BACK TO FRONT
END DDC SYSTEM.
13 POOL SLIDE FAN. PROVIDE NEW CONTROLS, INCLUDING NEW TEMPERATURE SENSOR. REFER TO DETAIL 3, SHEET M5.1.
T T T T
T T
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A 1 1 1 1 1 1
1111 T
T2 www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
100 WALNUT STREET, SUITE 200
PEORIA, ILLINOIS 61602
(309) 689-9888 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:2 :4
A
M M1.2
LOWER LEVEL AREA
B
LDE
WCR
0241027.00
9418.00 - HONEY
CREEK RESORT
BUILDING
AUTOMATION
SYSTEM
IMPROVEMENTS
12633 Resort Dr, Moravia, IA 52571
09/20/2024
WCR
PERMIT SET
D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.
C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.
B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR
EQUIPMENT SHUT DOWNS.
A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR
OTHER EQUIPMENT IS REMOVED.
GENERAL NOTES
0 4 8 16
NORTH
TRUE
#KEYNOTES
1 REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT
PUMP WITH PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT
PUMP. REMOVE ALL WIRING. PROVIDE NEW WIRING AND CONDUIT AS
REQUIRED.PROVIDE NEW LEAVING AIR TEMPERATURE WATER SENSOR AND FILTER
DIFFERENTIAL PRESSURE SWITCH. REVISE SEQUENCE OF OPERATION, REFER TO
DETAIL 1 ON SHEET M5.1
2 PROVIDE NEW TEMPERATURE SENSOR. SENSOR TO MONITOR TEMPERATURE IN
SPACE AND REPORT BACK TO FRONT END DDC SYSTEM.
SCALE: 1/8" = 1'-0"
FIRST FLOOR VENTILATION PLAN
T T T T T T T T T T T T
TTTTTTTT
ATA
ATA
ATA
ATA
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
1 1
1 1 1 1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1
1 1
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
T
T ATA-7
ATA-6
TATA-5
T ATA-4
T
Domestic Water
Pump Circle
T
4T www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
100 WALNUT STREET, SUITE 200
PEORIA, ILLINOIS 61602
(309) 689-9888 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:2 :4
A
M M1.3
FIRST FLOOR PLAN
AREA A
LDE
WCR
0241027.00
9418.00 - HONEY
CREEK RESORT
BUILDING
AUTOMATION
SYSTEM
IMPROVEMENTS
12633 Resort Dr, Moravia, IA 52571
09/20/2024
WCR
PERMIT SET
D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.
C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.
B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR
EQUIPMENT SHUT DOWNS.
A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR
OTHER EQUIPMENT IS REMOVED.
GENERAL NOTES
0 4 8 16
NORTH
TRUE
#KEYNOTES
1 REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT
PUMP WITH PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT
PUMP.REMOVE ALL WIRING. PROVIDE NEW WIRING AND CONDUIT AS REQUIRED.
PROVIDE NEW LEAVING AIR TEMPERATURE SENSOR, WATER SENSOR SWITCH AND
FILTER DIFFERENTIAL PRESSURE SWITCH. REVISE SEQUENCE OF OPERATION,
REFER TO DETAIL 1 ON SHEET M5.1.
2 REPLACE EXISTING THERMOSTAT FOR EXISTING AIR TO AIR HEAT PUMP WITH
PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT PUMP. REMOVE
ALL WIRING. PROVIDE NEW WIRING AND CONDUIT AS REQUIRED. PROVIDE NEW
LEAVING AIR TEMPERATURE SENSOR AND FILTER DIFFERENTIAL PRESSURE
SWITCH. REVISE SEQUENCE OF OPERATION, REFER TO DETAIL 1 ON SHEET M5.1.
3 PROVIDE NEW CONTROLS FOR DOMESTIC WATER RECIRCULATION PUMP. MONITOR
PER DETAIL 3 ON SHEET M5.2.
4 PROVIDE NEW DOMESTIC LEAVING WATER TEMPERATURE SENSOR, MONITOR
TEMPERATURE AND PROVIDE GRAPHICS. REFER TO DETAIL 5 ON SHEET M5.1.
5 PROVIDE NEW TEMPERATURE SENSOR. SENSOR TO MONITOR TEMPERATURE IN
SPACE AND REPORT BACK TO FRONT END DDC SYSTEM.SCALE: 1/8" = 1'-0"
SECOND FLOOR VENTILATION PLAN
TTTT
T T
T T T
T T
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
1 1 1 1 1
1 11
11 1 1 1 1
T T
EXISTING ELECTRIC HEATEREXISTING ELECTRIC HEATER
T
WTA-13
T
WTA-14
EXISTING ELECTRIC HEATEREXISTING ELECTRIC HEATER
2 2
T
T
6 6 www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
100 WALNUT STREET, SUITE 200
PEORIA, ILLINOIS 61602
(309) 689-9888 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:2 :4
A
M M1.4
FIRST FLOOR PLAN
AREA B
LDE
WCR
0241027.00
9418.00 - HONEY
CREEK RESORT
BUILDING
AUTOMATION
SYSTEM
IMPROVEMENTS
12633 Resort Dr, Moravia, IA 52571
09/20/2024
WCR
PERMIT SET
D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.
C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.
B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR
EQUIPMENT SHUT DOWNS.
A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR
OTHER EQUIPMENT IS REMOVED.
GENERAL NOTES
0 4 8 16
NORTH
TRUE
#KEYNOTES
1 REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT
PUMP WITH PREOGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT
PUMP REVISE SEQUENCE OF OPERATION,REMOVE ALL WIRING. PROVIDE NEW
WIRING AND CONDUIT AS REQUIRED. REFER TO DETAIL 1 ON SHEET M5.1.
2 REPLACE EXISTING THERMOSTAT FOR EXISTING AIR TO AIR HEAT PUMP WITH
PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT PUMP. REVISE
SEQUENCE OF OPERATION, REMOVE ALL WIRING. PROVIDE NEW WIRING AND
CONDUIT AS REQUIRED. REFER TO DETAIL 1 ON SHEET M5.1.
3 REPLACE THERMOSTAT AND CONTROLS FOR EXISTING WATER TO AIR HEAT PUMP.
REFER TO DETAIL 1 ON SHEET M5.3. HEAT PUMP IS LOCATED ON SHEET M1.5.
4 REPLACE THERMOSTAT AND CONTROLS FOR EXISTING WATER TO AIR HEAT PUMP.
REFER TO DETAIL 1 ON SHEET M5.3. HEAT PUMP IS LOCATED ON SHEET M1.5
5 PROVIDE NEW TEMPERATURE SENSOR. SENSOR TO MONITOR TEMPERATURE IN
SPACE AND REPORT BACK TO FRONT END DDC SYSTEM.
6 EXISTING ELECTRIC HEATER, REFER TO DETAIL 3 ON M5.3.SCALE: 1/8" = 1'-0"
SECOND FLOOR VENTILATION PLAN
WTA
WTA
WTA
WTA
WTA
WTA
WTA
WTA
11 ERV
WTA
WTA
WTA
WTA
WTA
RTU
RTU
WTA
RTU
WTA
WTA
WTA
WTA
WTA
ERV
WTA
WTA
T WTA 19
TWTA 20
TWTA 17,18
TWTA 11
T WTA 21
T WTA 12
T
WTA 28
T WTA 31
TWTA 22 TWTA 23 T WTA 24
T WTA 27
T WTA 26
T WTA 25
TWTA 30
WTA
T WTA 29
T
WTA 16
T
WTA 15
P
P
P
P
ET
1 JANITOR/MECH
C160
WTW
WTW
2 2
2 2
P
1P
2 EXISTING DDC
CONTROLLERS
2 2 2
T
T
SALES
MANAGER
C107
GENERAL
MANAGER
C108
ASSISTANT
MANAGER
C111
BUSINESS
CENTER
C103
REBALANCE
TO 250 CFM
REBALANCE
TO 250 CFM
x x
8"ø
12x12
REBALANCE
EXISTING HEAT
PUMP
TO 750 CFM
H9
H 9 H 9 H9
H
H 9
H 9
10 10 www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
100 WALNUT STREET, SUITE 200
PEORIA, ILLINOIS 61602
(309) 689-9888 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:2 :4
A
M M1.5
FIRST FLOOR PLAN
AREA C
LDE
WCR
0241027.00
9418.00 - HONEY
CREEK RESORT
BUILDING
AUTOMATION
SYSTEM
IMPROVEMENTS
12633 Resort Dr, Moravia, IA 52571
09/20/2024
WCR
PERMIT SET
0 4 8 16 N O R
TH
TRUE
SCALE: 1/8" = 1'-0"
SECOND FLOOR VENTILATION PLAN
D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.
C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.
B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR
EQUIPMENT SHUT DOWNS.
A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR
OTHER EQUIPMENT IS REMOVED.
GENERAL NOTESKEYNOTES
1 REPLACE EXISTING CONTROLS FOR ERV-4 AND ERV-5. REVISE SEQUENCE OF
OPERATIONS PER DETAIL 2 ON SHEET M5.2. RECOMMISSION AND REBALANCE UNIT.
REVISE SEQUENCE OF OPERATION.
2 REPLACE EXISTING THERMOSTAT FOR EXISTING WATER TO AIR HEAT PUMP WITH
PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT PUMP.REMOVE
ALL WIRING. PROVIDE NEW WIRING AND CONDUIT AS REQUIRED. HEAT PUMP IS
LOCATED ABOVE CEILING. REVISE SEQUENCE OF OPERATION, REFER TO DETAIL 1
ON SHEET M5.3.
3 REPLACE EXISTING CONTROLS FOR ROOFTOP UNIT SERVING AS A MAKE UP AIR
UNIT AND HVAC FOR THE KITCHEN AREA. UNIT HAS TO BACNET CONTROLLER, PULL
IN ALL POINTS AND PROVIDE GRAPHICS FOR UNIT. REFER TO DETAIL 4 ON SHEET
M5.2.
4 REPLACE EXISTING CONTROLS FOR ROOFTOP UNIT SERVING AS A MAKE UP AIR
UNIT FOR THE KITCHEN HOODS. REVISE SEQUENCE OF OPERATION, REFER TO
DETAIL 1 ON SHEET M5.4.
5 REVISE CONTROL SEQUENCE FOR GROUND LOOP PUMPS. REFER TO DETAIL 2 ON
SHEET M5.1.
6 REVISE CONTROL SEQUENCE FOR WATER TO WATER HEAT PUMPS AND
ASSOCIATED PUMPS, REFER TO DETAIL 5 ON SHEET M5.3.
7 REVISE CONTROL SEQUENCE FOR BUILDING LOOP PUMPS. REFER TO DETAIL 4 ON
SHEET M5.1.
8 PROVIDE NEW TEMPERATURE SENSOR. SENSOR TO MONITOR TEMPERATURE IN
SPACE AND REPORT BACK TO FRONT END DDC SYSTEM.
9 EXISTING HUMIDISTAT, MONITOR STATUS AND ALARM AT 800 PPM.
10 PROVIDE NEW CONTROLS FOR DOMESTIC WATER CIRC PUMP. MONITOR PER
DETAIL 3 ON SHEET M5.2
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
T T T T T T T T T T T T
TTTTTTTTTTTTTT
ATA
A
1 1 1 1 1 1 1 11 11 11
1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 1 1 1 1
11 11 11 11 11
ERV
ATA
ATA
CORRIDOR
A201
TT ATA-9 ATA-8
www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
100 WALNUT STREET, SUITE 200
PEORIA, ILLINOIS 61602
(309) 689-9888 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:2 :4
A
M M1.6
SECOND FLOOR
PLAN AREA A
LDE
WCR
0241027.00
9418.00 - HONEY
CREEK RESORT
BUILDING
AUTOMATION
SYSTEM
IMPROVEMENTS
12633 Resort Dr, Moravia, IA 52571
09/20/2024
WCR
PERMIT SET
0 4 8 16
NORTH
TRUE
SCALE: 1/8" = 1'-0"
THIRD FLOOR VENTILATION PLAN
D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.
C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.
B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR
EQUIPMENT SHUT DOWNS.
A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR
OTHER EQUIPMENT IS REMOVED.
GENERAL NOTESKEYNOTES
1 REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT
PUMP WITH PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT
PUMP. PROVIDE NEW LEAVING AIR TEMPERATURE SENSOR, WATER SENSOR
SWITCH AND FILTER DIFFERENTIAL PRESSURE SWITCH. REMOVE ALL WIRING.
PROVIDE NEW WIRING AND CONDUIT AS REQUIRED. REVISE SEQUENCE OF
OPERATION, REFER TO DETAIL1 ON SHEET M5.1.
2 REPLACE EXISTING THERMOSTAT FOR EXISTING AIR TO AIR HEAT PUMP WITH
PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT PUMP. PROVIDE
NEW LEAVING AIR TEMPERATURE SENSOR, WATER SENSOR SWITCH AND FILTER
DIFFERENTIAL PRESSURE SWITCH. REMOVE ALL WIRING. PROVIDE NEW WIRING
AND CONDUIT AS REQUIRED. REVISE SEQUENCE OF OPERATION, REFER TO DETAIL
1 ON SHEET M5.1.
3 REPLACE EXISTING CONTROLS FOR ERV-2. REVISE SEQUENCE OF OPERATIONS
PER DETAIL 2 ON SHEET M5.2. RECOMMISSION AND REBALANCE UNIT. REVISE
SEQUENCE OF OPERATION.
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
T T T T
T T
T T T T T T
111111
1 1 1 1 1 1
1 1
1 11 1 www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
100 WALNUT STREET, SUITE 200
PEORIA, ILLINOIS 61602
(309) 689-9888 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:2 :4
A
M M1.7
SECOND FLOOR
PLAN AREA B
LDE
WCR
0241027.00
9418.00 - HONEY
CREEK RESORT
BUILDING
AUTOMATION
SYSTEM
IMPROVEMENTS
12633 Resort Dr, Moravia, IA 52571
09/20/2024
WCR
PERMIT SET
0 4 8 16
NORTH
TRUE
SCALE: 1/8" = 1'-0"
THIRD FLOOR VENTILATION PLAN
D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.
C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.
B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR
EQUIPMENT SHUT DOWNS.
A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR
OTHER EQUIPMENT IS REMOVED.
GENERAL NOTESKEYNOTES
1 REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT
PUMP WITH PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT
PUMP. PROVIDE NEW LEAVING AIR TEMPERATURE SENSOR, WATER SENSOR
SWITCH AND FILTER DIFFERENTIAL PRESSURE SWITCH. REMOVE ALL WIRING.
PROVIDE NEW WIRING AND CONDUIT AS REQUIRED. REVISE SEQUENCE OF
OPERATION, REFER TO DETAIL 1 ON SHEET M5.1.
T
T
T
T
T
T
T
T
T
T T
T
T
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
1 1
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A 1 1 1 1 1 1
1 1 1 1
ATA
A
ATA
A 1 1
1 1 1 1 1 1
1 1
1 1
T
T www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
100 WALNUT STREET, SUITE 200
PEORIA, ILLINOIS 61602
(309) 689-9888 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:2 :4
A
M M1.8
THIRD FLOOR PLAN
AREA A
LDE
WCR
0241027.00
9418.00 - HONEY
CREEK RESORT
BUILDING
AUTOMATION
SYSTEM
IMPROVEMENTS
12633 Resort Dr, Moravia, IA 52571
09/20/2024
WCR
PERMIT SET
0 4 8 16
NORTH
TRUE
SCALE: 1/8" = 1'-0"
THIRD FLOOR PLAN A
D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.
C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.
B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR
EQUIPMENT SHUT DOWNS.
A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR
OTHER EQUIPMENT IS REMOVED.
GENERAL NOTESKEYNOTES
1 REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT
PUMP WITH PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT
PUMP. PROVIDE NEW LEAVING AIR TEMPERATURE SENSOR, WATER SENSOR
SWITCH AND FILTER DIFFERENTIAL PRESSURE SWITCH. REMOVE ALL WIRING.
PROVIDE NEW WIRING AND CONDUIT AS REQUIRED. REVISE SEQUENCE OF
OPERATION, REFER TO DETAIL1 ON SHEET M5.1.
T T
TTT
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
ATA
A
1 1 11
1 1
11 1 1 www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
100 WALNUT STREET, SUITE 200
PEORIA, ILLINOIS 61602
(309) 689-9888 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:2 :4
A
M M1.9
THIRD FLOOR PLAN
AREA B
LDE
WCR
0241027.00
9418.00 - HONEY
CREEK RESORT
BUILDING
AUTOMATION
SYSTEM
IMPROVEMENTS
12633 Resort Dr, Moravia, IA 52571
09/20/2024
WCR
PERMIT SET
0 4 8 16
NORTH
TRUE
D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.
C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.
B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR
EQUIPMENT SHUT DOWNS.
A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR
OTHER EQUIPMENT IS REMOVED.
GENERAL NOTESKEYNOTES
1 1. REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT
PUMP WITH PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT
PUMP. PROVIDE NEW LEAVING AIR TEMPERATURE SENSOR, WATER SENSOR
SWITCH AND FILTER DIFFERENTIAL PRESSURE SWITCH. REVISE SEQUENCE OF
OPERATION, REFER TO DETAIL 1 ON SHEET M5.1.
SCALE: 1/8" = 1'-0"
THIRD FLOOR PLAN B
H L
AI - FILTER DIFFERENTIAL PRESSURE
SCR
BO - HEATING ENABLE
HP
BI - SMOKE DETECTOR
T
AI - DISCHARGE AIR TEMP
BI - ZONE OVERRIDE
AI - ZONE SETPOINT ADJUST
OA
RA
DA
T
AI - ZONE TEMP
SEQUENCE OF OPERATION - AIR SOURCE HEAT PUMP (TYPICAL OF 114)
RUN CONDITIONS - SCHEDULED:
THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES:
• OCCUPIED MODE: THE UNIT SHALL MAINTAIN
• A 74°F (ADJ.) COOLING SETPOINT
• A 70°F (ADJ.) HEATING SETPOINT
• UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN
• A 85°F (ADJ.) COOLING SETPOINT.
• A 55°F (ADJ.) HEATING SETPOINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).
• LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).
• THE EXISTING AIR TO AIR HEAT PUMPS ARE CURRENTLY NOT ON THE EXISTING BAS.
• PROVIDE A NEW CONTROLLER FOR EACH OF THE 9 DUCTED AIR TO AIR HEAT PUMPS WITH OCCUPIED AND UNOCCUPIED MODES.
THE SUPPLY FAN SHALL RUN CONTINUOUSLY IN OCCUPIED MODE. THE HEAT PUMP SHALL RUN ON ITS OWN CONTROLS TO
MAINTAIN SPACE TEMPERATURE.
• FURNISH NEW LEAVING AIR TEMPERATURE SENSOR AND FILTER DIFFERENTIAL PRESSURE SENSOR.
• PROVIDE NEW WIRING AND CONTROLS FOR EXISTING UNITS. PROVIDE NEW GRAPHICS WITH THE NOTED CONTROL POINTS.
FILTER DIFFERENTIAL PRESSURE MONITOR:
THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE FILTER.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• FILTER CHANGE REQUIRED: FILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
DISCHARGE AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE.
- WATER IS DETECTED AT WATER SENSOR SWITCH
• HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).
• LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS THAN 40°F (ADJ.).
MANUAL VD
MANUAL VD
BO - HEAT PUMP ENABLE
WS
BI - WATER SENSOR STATUS
CONTRACTOR TO PROVIDE
NEW WATER SENSOR TO
ALL HOTELING ROOM UNITS.
CONTRACTOR TO PROVIDE
NEW FILTER DIFFERENTIAL
PRESSURE SWITCH TO ALL
UNITS (TYP ALL)
CONTRACTOR TO PROVIDE NEW DISCHARGE AIR SENSOR TO UNIT DUCTWORK (TYP ALL)
GLRGLR
T
AI - GEOTHERMAL LOOP RETURN TEMP
T
AI - GROUND LOOP SUPPLY TEMP
GLS
GLR
VFD
VFD
BI - GEOTHERMAL LOOP 3 VFD FAULT
AO - GEOTHERMAL LOOP 3 VFD SPEED
P3
P4
M
M
CT
CT
BI - GEOTHERMAL LOOP 3 STATUS
BI - GEOTHERMAL LOOP 4 STATUS
BO - GEOTHERMAL LOOP 3 START/STOP
GLS GLS
SEQUENCE OF OPERATION - GEOTHERMAL LOOP PUMPS (TYPICAL OF 1)
GEOTHERMAL LOOP PUMP SYSTEM - RUN CONDITIONS:
THE GEOTHERMAL LOOP PUMPS SHALL BE ENABLED WHENEVER:
• THE GEOTHERMAL LOOP PUMPS ILL RUN WHEN THE TEMPERATURE OF
THE BUILDING LOOP RETURN WATER TEMPERATURE EXCEEDS 60F OR
DROPS BELOW 45F FOR 15 MINUTES OR MORE.
• IF THE BUILDING LOOP TEMPERATURE IS BETWEEN 45F AND 60F THE
PUMPS WILL BE OFF.
TO PREVENT SHORT CYCLING, THE GEOTHERMAL LOOP PUMP SYSTEM
SHALL RUN FOR AND BE OFF FOR MINIMUM ADJUSTABLE TIMES (BOTH
USER DEFINABLE).
GEOTHERMAL LOOP PUMP LEAD/LAG OPERATION:
THE TWO VARIABLE SPEED GEOTHERMAL LOOP PUMPS SHALL OPERATE
IN A LEAD/LAG FASHION.
• THE LEAD PUMP SHALL RUN FIRST.
• ON FAILURE OF THE LEAD PUMP, THE LAG PUMP SHALL RUN AND THE
LEAD PUMP SHALL TURN OFF.
THE DESIGNATED LEAD PUMP SHALL ROTATE UPON ONE OF THE
FOLLOWING CONDITIONS (USER SELECTABLE):
• MANUALLY THROUGH A SOFTWARE SWITCH
• IF PUMP RUNTIME (ADJ.) IS EXCEEDED
• DAILY
• WEEKLY
• MONTHLY
GEOTHERMAL LOOP PROVIDED AS FOLLOWS:
• GEOTHERMAL LOOP PUMP 1
• FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE
LIMIT.
• VFD FAULT.
• GEOTHERMAL LOOP PUMP 2
• FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE
LIMIT.
• VFD FAULT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH GEOTHERMAL LOOP DIFFERENTIAL PRESSURE: IF THE
GEOTHERMAL LOOP DIFFERENTIAL PRESSURE IS 25% (ADJ.) GREATER
THAN SETPOINT.
• LOW GEOTHERMAL LOOP DIFFERENTIAL PRESSURE: IF THE
GEOTHERMAL LOOP DIFFERENTIAL PRESSURE IS 25% (ADJ.) LESS THAN
SETPOINT.
GEOTHERMAL LOOP TEMPERATURE MONITORING:
THE FOLLOWING TEMPERATURES SHALL BE MONITORED:
• GEOTHERMAL LOOP SUPPLY.
• GEOTHERMAL LOOP RETURN.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH GEOTHERMAL LOOP SUPPLY TEMP: IF THE GEOTHERMAL LOOP
SUPPLY TEMPERATURE IS GREATER THAN 55°F (ADJ.).
• LOW GEOTHERMAL LOOP SUPPLY TEMP: IF THE GEOTHERMAL LOOP
SUPPLY TEMPERATURE IS LESS THAN 38°F (ADJ.).
BI - GEOTHERMAL LOOP 4 VFD FAULT
AO - GEOTHERMAL LOOP 4 VFD SPEED
BO - GEOTHERMAL LOOP 4 START/STOP
L
H
AI - LOOP WATER DIFFERENTIAL PRESSURE
SEQUENCE OF OPERATION - EXHAUST FAN - COOLING (TYPICAL OF 2)
RUN CONDITIONS - SCHEDULED:
THE UNIT SHALL BE ENABLED ACCORDING TO A USER DEFINABLE TIME
SCHEDULE IN THE FOLLOWING MODES:
• OCCUPIED MODE: THE UNIT SHALL MAINTAIN A ZONE TEMPERATURE
COOLING SETPOINT OF 78°F (ADJ.).
• UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN A
ZONE TEMPERATURE COOLING SETPOINT OF 85°F (ADJ.).
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE
COOLING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).
FAN:
THE FAN SHALL RUN ANYTIME THE ZONE TEMPERATURE RISES BELOW
COOLING SETPOINT, UNLESS SHUTDOWN ON SAFETIES. THE FAN SPEEDS
SHALL BE INDEXED AS FOLLOWS:
• LOW SPEED SHALL RUN ANYTIME THE ZONE
TEMPERATURE RISES ABOVE SETPOINT.
• MEDIUM SPEED SHALL RUN ANYTIME THE ZONE
TEMPERATURE RISES FURTHER ABOVE SETPOINT BY A USER DEFINABLE
AMOUNT (ADJ.).
• HIGH SPEED SHALL RUN ANYTIME THE ZONE TEMPERATURE RISES EVEN
FURTHER ABOVE SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).
EXHAUST AIR DAMPER:
THE EXHAUST AIR DAMPER SHALL OPEN ANYTIME THE UNIT RUNS AND
SHALL CLOSE ANYTIME THE UNIT STOPS. THE EXHAUST AIR DAMPER SHALL
CLOSE 30 SEC (ADJ.) AFTER THE FAN STOPS.
FILTER DIFFERENTIAL PRESSURE MONITOR:
THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS
THE FILTER.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• FILTER CHANGE REQUIRED: FILTER DIFFERENTIAL PRESSURE EXCEEDS
A USER DEFINABLE LIMIT (ADJ.).
DAMPER STATUS:
THE FAN SHALL BE ENABLED AFTER THE DAMPER STATUS HAS PROVEN.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• DAMPER FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED.
• DAMPER IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN.
FAN STATUS:
THE CONTROLLER SHALL MONITOR THE FAN STATUS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• FAN RUNTIME EXCEEDED: FAN STATUS RUNTIME EXCEEDS A USER
DEFINABLE LIMIT (ADJ.).
BI - EXHAUST AIR DAMPER STATUS
N.C.
S
BO - EXHAUST AIR DAMPER
BO - FAN LOW SPEED
BO - FAN HIGH SPEED
BO - FAN MEDIUM SPEED
CT
BI - FAN STATUS
EA
AI - ZONE TEMP
T
M
L H
AI - FILTER DIFFERENTIAL PRESSURE
TYPICAL OF EF-8
GTS
GTS
AI - LOOP WATER SUPPLY TEMP
BI - LOOP WATER FLOW STATUS
GTS
GTS
T
T
AI - LOOP WATER RETURN TEMP
BO - LOOP WATER PUMP 5 START/STOP
AO - LOOP WATER PUMP 5 VFD SPEED
BI - LOOP WATER PUMP 5 VFD FAULT
GTS
GTS
AI - LOOP WATER DIFFERENTIAL PRESSURE
H
L
VFD
VFD
P5
P6
M
M
CT
CT
BI - LOOP WATER PUMP 5 STATUS
SEQUENCE OF OPERATION - LOOP MONITOR AND PUMPS (TYPICAL OF 2)
WATER SOURCE HEAT PUMP LOOP MONITOR - RUN CONDITIONS:
THE LOOP MONITOR SHALL RUN WHENEVER:
• ANY ZONE IS OCCUPIED.
• OR A DEFINABLE NUMBER OF UNOCCUPIED ZONES NEED HEATING OR
COOLING.
THE FOLLOWING LOOP WATER CONDITIONS SHALL BE MONITORED:
• FLOW STATUS.
• SUPPLY TEMPERATURE.
• RETURN TEMPERATURE.
ALARMS AND A HEAT PUMP SHUTDOWN SIGNAL SHALL BE GENERATED
UPON ANY OF THE FOLLOWING LOOP WATER CONDITIONS:
• NO LOOP FLOW.
• HIGH LOOP WATER SUPPLY TEMP SHUTDOWN: IF THE LOOP WATER
SUPPLY TEMPERATURE IS GREATER THAN 92°F (ADJ.).
• LOW LOOP WATER SUPPLY TEMP SHUTDOWN: IF THE LOOP WATER
SUPPLY TEMPERATURE IS LESS THAN 58°F (ADJ.).
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH LOOP WATER SUPPLY TEMP: IF THE LOOP WATER SUPPLY
TEMPERATURE IS GREATER THAN 90°F (ADJ.).
• LOW LOOP WATER SUPPLY TEMP: IF THE LOOP WATER SUPPLY
TEMPERATURE IS LESS THAN 60°F (ADJ.).
LOOP WATER PUMP LEAD/LAG OPERATION:
THE TWO LOOP WATER PUMPS SHALL OPERATE IN A LEAD/LAG FASHION.
• THE LEAD PUMP SHALL RUN FIRST.
• ON FAILURE OF THE LEAD PUMP, THE LAG PUMP SHALL RUN AND THE
LEAD PUMP SHALL TURN OFF.
• THE VFD WILL CONTROL THE MINIMUM FLOW TO BE 40% OF THE
MAXIMUM FLOW
THE DESIGNATED LEAD PUMP SHALL ROTATE UPON ONE OF THE
FOLLOWING CONDITIONS (USER SELECTABLE):
• MANUALLY THROUGH A SOFTWARE SWITCH
• IF PUMP RUNTIME (ADJ.) IS EXCEEDED
• DAILY
• WEEKLY
• MONTHLY
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• LOOP WATER PUMP 1
• FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE
LIMIT.
• VFD FAULT.
• LOOP WATER PUMP 2
• FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE
LIMIT.
• VFD FAULT.
LOOP WATER DIFFERENTIAL PRESSURE CONTROL:
THE CONTROLLER SHALL MEASURE LOOP WATER DIFFERENTIAL
PRESSURE AND MODULATE THE LOOP WATER PUMP VFDS IN SEQUENCE
TO MAINTAIN ITS LOOP WATER DIFFERENTIAL PRESSURE SETPOINT. THE
FOLLOWING SETPOINTS ARE RECOMMENDED VALUES. ALL SETPOINTS
SHALL BE FIELD ADJUSTED DURING THE COMMISSIONING PERIOD TO MEET
THE REQUIREMENTS OF ACTUAL FIELD CONDITIONS.
THE CONTROLLER SHALL MODULATE LOOP WATER PUMP SPEEDS TO
MAINTAIN A LOOP WATER DIFFERENTIAL PRESSURE OF 12LBF/IN2 (ADJ.).
THE VFD MINIMUM SPEED SHALL NOT DROP BELOW 40% FLOW (ADJ.).
ON DROPPING LOOP WATER DIFFERENTIAL PRESSURE, THE VFDS SHALL
STAGE ON AND RUN TO MAINTAIN SETPOINT AS FOLLOWS:
• THE CONTROLLER SHALL MODULATE THE LEAD VFD TO MAINTAIN
SETPOINT.
• IF THE LEAD VFD SPEED IS GREATER THAN A SETPOINT OF 90% (ADJ.),
THE LAG VFD SHALL STAGE ON.
• THE LAG VFD SHALL RAMP UP TO MATCH THE LEAD VFD SPEED AND
THEN RUN IN UNISON WITH THE LEAD VFD TO MAINTAIN SETPOINT.
ON RISING LOOP WATER DIFFERENTIAL PRESSURE, THE VFDS SHALL
STAGE OFF AS FOLLOWS:
• IF THE VFD SPEEDS THEN DROPS BACK TO 60% (ADJ.) BELOW SETPOINT,
THE LAG VFD SHALL STAGE OFF.
• THE LEAD VFD SHALL CONTINUE TO RUN TO MAINTAIN SETPOINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH LOOP WATER DIFFERENTIAL PRESSURE: IF THE LOOP WATER
DIFFERENTIAL PRESSURE IS 25% (ADJ.) GREATER THAN SETPOINT.
• LOW LOOP WATER DIFFERENTIAL PRESSURE: IF THE LOOP WATER
DIFFERENTIAL PRESSURE IS 25% (ADJ.) LESS THAN SETPOINT.
BI - LOOP WATER PUMP 6 STATUS
BO - LOOP WATER PUMP 6 START/STOP
AO - LOOP WATER PUMP 6 VFD SPEED
BI - LOOP WATER PUMP 6 VFD FAULT
H W
C W
TAI - DOM. HW TEMP
EXISTING
MIXING VALVE
T W
PROVIDE NEW TEMPERATURE SENSOR ON THE TEMPERED WATER
DOWNSTREAM OF THE MIXING VALVE. MONITOR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH WATER TEMPERATURE: IF WATER TEMPERATURE IS
ABOVE 125 DEG.
• LOW WATER TEMPERATURE: IF WATER TEMPERATURE IS
BELOW 100 DEG.
SEQUENCE OF OPERATION - TYPICAL 1
www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
100 WALNUT STREET, SUITE 200
PEORIA, ILLINOIS 61602
(309) 689-9888 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:2 :4
A
M M5.1
CONTROLS
DIAGRAMS
LDE
WCR
0241027.00
9418.00 - HONEY
CREEK RESORT
BUILDING
AUTOMATION
SYSTEM
IMPROVEMENTS
12633 Resort Dr, Moravia, IA 52571
09/20/2024
WCR
PERMIT SET
SCALE: No Scale
AIR SOURCE HEAT PUMP CONTROLS
SCALE: No Scale
GEOTHERMAL LOOP PUMP CONTROLS
SCALE: No Scale
EXHAUST FAN - COOLING CONTROLS
SCALE: No Scale
BUILDING LOOP PUMP CONTROLS
SCALE: No Scale
DOMESTIC WATER TEMPERATURE CONTROLS
Fan Runtime Exceeded x
Fan in Hand x
Fan Failure x
Exhaust Air Damper in Hand x
Exhaust Air Damper Failure x
Filter Change Required x
High Zone Temp x
Schedule x
Cooling Setpoint x x x
Exhaust Air Damper x x x
Fan Low Speed x x x
Fan High Speed x x x
Fan Medium Speed x x x
Fan Status x x x
Exhaust Air Damper Status x x x
Filter Differential Pressure x x x
Zone Temp x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
Low Discharge Air Temp x
High Discharge Air Temp x
Filter Change Required x
Low Zone Temp x
High Zone Temp x
Cooling Setpoint x x
Heating Setpoint x x
Schedule x
Emergency Shutdown x x x x
Zone Carbon Dioxide PPM Setpoint x x x
Heating Enable x x x
Compressor Enable x x x
Smoke Detector x x x x
Zone Override x x x
Discharge Temp x x x
Filter Differential Pressure x x x
Zone Setpoint Adjust x x x
Zone Temp x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
Loop Water Pump 4 Runtime Exceeded x
Loop Water Pump 4 Running in Hand x
Loop Water Pump 4 Failure x
Loop Water Pump 3 Runtime Exceeded x
Loop Water Pump 3 Running in Hand x
Loop Water Pump 3 Failure x
Low Loop Water Differential Pressure x
High Loop Water Differential Pressure x
Loww Loop Water Supply Temp x
High Loop Water Supply Temp x
Low Loop Water Supply Temp Shutdown x
High Loop Water Supply Temp Shutdown x
Loop Water Differential Pressure Setpoint x x
Outside Air Temp x x
Loop Water Pump 4 Start/stop x x
Loop Water Pump 3 Start/Stop x x
Loop Water Pump 4 Status x x x
Loop Water Pump 3 Status x x x
Loop Water Pump 4 VFD Fault x x x
Loop Water Pump 3 VFD Fault x x x
Loop Water Pump 4 VFD Speed x x x
Loop Water Pump 3 VFD Speed x x x
Loop Water Differential Pressure x x x
Loop Water Supply Temp x x x
Loop Water Return Temp x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
Loop Water Pump 5 Runtime Exceeded x
Loop Water Pump 5 Running in Hand x
Loop Water Pump 5 Failure x
Loop Water Pump 4 Runtime Exceeded x
Loop Water Pump 4 Running in Hand x
Loop Water Pump 4 Failure x
Low Loop Water Differential Pressure x
High Loop Water Differential Pressure x
Loww Loop Water Supply Temp x
High Loop Water Supply Temp x
Low Loop Water Supply Temp Shutdown x
High Loop Water Supply Temp Shutdown x
No Loop Flow x
Loop Water Differential Pressure Setpoint x x
Outside Air Temp x x
Loop Water Pump 5 Start/stop x x
Loop Water Pump 4 Start/Stop x x
Loop Water Pump 5 Status x x x
Loop Water Pump 4 Status x x x
Loop Water Pump 5 VFD Fault x x x
Loop Water Pump 4 VFD Fault x x x
Loop Water Flow Status x x
Loop Water Pump 5 VFD Speed x x x
Loop Water Pump 4 VFD Speed x x x
Loop Water Differential Pressure x x x
Loop Water Supply Temp x x x
Loop Water Return Temp x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
Domestic HW Low Temp x
Domestic HW High Temp x
Domestic HW Temp x x x
POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic
HARDWARE POINTS SOFTWARE POINTS
SEQUENCE OF OPERATION - EXHAUST FAN - ON/OFF (TYPICAL OF 1)
RUN CONDITIONS - SCHEDULED:
THE FAN SHALL RUN ACCORDING TO A USER DEFINABLE SCHEDULE.
FAN:
THE FAN SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.
EXHAUST AIR DAMPER:
THE EXHAUST AIR DAMPER SHALL OPEN ANYTIME THE UNIT RUNS AND
SHALL CLOSE ANYTIME THE UNIT STOPS. THE EXHAUST AIR DAMPER SHALL
CLOSE 30 SEC (ADJ.) AFTER THE FAN STOPS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• DAMPER FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED.
• DAMPER IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN.
DAMPER STATUS:
THE FAN SHALL BE ENABLED AFTER THE DAMPER STATUS HAS PROVEN.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• DAMPER FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED.
• DAMPER IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN.
FAN STATUS:
THE CONTROLLER SHALL MONITOR THE FAN STATUS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• FAN RUNTIME EXCEEDED: FAN STATUS RUNTIME EXCEEDS A USER
DEFINABLE LIMIT (ADJ.).
CT
BI - FAN STATUS
BI - EXHAUST AIR DAMPER STATUS
N.C.
S
BO - EXHAUST AIR DAMPER
BO - FAN START/STOP
EA
M
TYPICAL OF EF-6
SEQUENCE OF OPERATION - MAKEUP AIR UNIT - SUPPLY AIR TEMP - HYDRONIC HEATING/COOLING (TYPICAL OF 4)
RUN CONDITIONS - SCHEDULED:
THE UNIT SHALL RUN BASED UPON AN OPERATOR ADJUSTABLE SCHEDULE.
EMERGENCY SHUTDOWN:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN EMERGENCY SHUTDOWN SIGNAL.
FREEZE PROTECTION:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A FREEZESTAT STATUS.
SMOKE DETECTION:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A SMOKE DETECTOR STATUS.
DEMAND LIMITING - SETPOINT ADJUST:
TO LOWER POWER CONSUMPTION, THE SUPPLY AIR TEMPERATURE SETPOINT SHALL AUTOMATICALLY RELAX (RAISED FOR COOLING; LOWERED FOR HEATING) WHEN THE FACILITY POWER CONSUMPTION EXCEEDS DEFINABLE THRESHOLDS. THE AMOUNT
OF RELAXATION SHALL BE ACCOMPLISHED BY ONE OF THE FOLLOWING METHODS:
• THE SUPPLY AIR TEMPERATURE SETPOINT SHALL RELAX BY 2°F (ADJ.) FOR EACH DEMAND THRESHOLD EXCEEDED.
• THE SETPOINTS IN THE ZONES SUPPLIED BY THIS UNIT SHALL BE RELAXED AS SPECIFIED IN THE SEQUENCE OF OPERATIONS FOR
THE ZONES. THIS SHALL IN TURN RELAX THE UNIT'S SUPPLY AIR TEMPERATURE SETPOINT BY A USER DEFINABLE AMOUNT.
ALL SETPOINTS SHALL AUTOMATICALLY RETURN TO THEIR PREVIOUS SETTINGS WHEN THE FACILITY POWER CONSUMPTION DROPS
BELOW THE THRESHOLDS.
OUTSIDE AIR DAMPER:
THE OUTSIDE AIR DAMPER SHALL OPEN ANYTIME THE UNIT RUNS AND SHALL CLOSE ANYTIME THE UNIT STOPS. THE SUPPLY FAN SHALL START ONLY AFTER THE DAMPER STATUS HAS PROVEN THE DAMPER IS OPEN. THE OUTSIDE AIR DAMPER SHALL CLOSE
4SEC (ADJ.) AFTER THE SUPPLY FAN STOPS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• OUTSIDE AIR DAMPER FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED.
• OUTSIDE AIR DAMPER IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN.
HEAT RECOVERY WHEEL - VARIABLE SPEED:
THE CONTROLLER SHALL MODULATE THE HEAT WHEEL FOR ENERGY RECOVERY AS FOLLOWS.
COOLING RECOVERY MODE:
THE CONTROLLER SHALL MEASURE THE HEAT WHEEL DISCHARGE AIR TEMPERATURE AND MODULATE THE HEAT WHEEL SPEED TO MAINTAIN A SETPOINT 2°F (ADJ.) LESS THAN THE UNIT SUPPLY AIR TEMPERATURE SETPOINT. THE HEAT WHEEL SHALL RUN FOR
COOL RECOVERY WHENEVER:
• UNIT RETURN AIR TEMPERATURE IS 5°F (ADJ.) OR MORE BELOW THE OUTSIDE AIR TEMPERATURE.
• AND THE UNIT IS IN A COOLING MODE.
• AND THE SUPPLY FAN IS ON.
HEATING RECOVERY MODE:
THE CONTROLLER SHALL MEASURE THE HEAT WHEEL DISCHARGE AIR TEMPERATURE AND MODULATE THE HEAT WHEEL SPEED TO MAINTAIN A SETPOINT 2°F (ADJ.) GREATER THAN THE UNIT SUPPLY AIR TEMPERATURE SETPOINT. THE HEAT WHEEL SHALL RUN
FOR HEAT RECOVERY WHENEVER:
• UNIT RETURN AIR TEMPERATURE IS 5°F (ADJ.) OR MORE ABOVE THE OUTSIDE AIR TEMPERATURE.
• AND THE UNIT IS IN A HEATING MODE.
• AND THE SUPPLY FAN IS ON.
THE HEAT WHEEL SHALL RUN IN FROST PROTECTION:
• OUTSIDE AIR TEMPERATURE DROPS BELOW 15°F (ADJ.)
• OR WHENEVER EXHAUST AIR TEMPERATURE DROPS BELOW 20°F (ADJ.).
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HEAT WHEEL ROTATION FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• HEAT WHEEL IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• HEAT WHEEL RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
• HEAT WHEEL VFD IN FAULT
SUPPLY FAN:
THE SUPPLY FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN. TO PREVENT SHORT CYCLING, THE SUPPLY FAN
SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME, UNLESS SHUTDOWN ON SAFETIES.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• SUPPLY FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• SUPPLY FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• SUPPLY FAN RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
EXHAUST FAN:
THE EXHAUST FAN SHALL RUN WHENEVER THE SUPPLY FAN RUNS, UNLESS SHUTDOWN ON SAFETIES.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• EXHAUST FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
• EXHAUST FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
• EXHAUST FAN RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
(PROVIDE FOR ERV-4 AMD ERV-5 ONLY)
SUPPLY AIR TEMPERATURE SETPOINT - OUTSIDE AIR RESET:
THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE AND SHALL MAINTAIN SUPPLY AIR TEMPERATURE SETPOINT.
THE SUPPLY AIR TEMPERATURE SETPOINT SHALL RESET FOR COOLING AS FOLLOWS:
AS OUTSIDE AIR TEMPERATURE DROPS FROM 85°F (ADJ.) TO 20°F (ADJ.)
THE SUPPLY AIR TEMPERATURE SETPOINT SHALL RESET UPWARDS FROM 55°F (ADJ.) TO 65°F (ADJ.).
COOLING STAGES:
THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND MODULATE THE COIL CONTROL VALVE COOLING TO MAINTAIN ITS COOLING SETPOINT. TO PREVENT SHORT CYCLING, THERE SHALL BE A USER DEFINABLE (ADJ.) DELAY BETWEEN
STAGES, AND EACH STAGE SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.
THE COIL SHALL BE ENABLED WHENEVER:
• AND THE SUPPLY AIR TEMPERATURE IS ABOVE COOLING SETPOINT OR BELOW ITS HEATING SETPOINT.
• AND THE FAN STATUS IS ON.
PREFILTER DIFFERENTIAL PRESSURE MONITOR:
THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE PREFILTER. PROVIDE TWO NEW SENSORS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• PREFILTER CHANGE REQUIRED: PREFILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• FINAL FILTER CHANGE REQUIRED: FINAL FILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
BI - EXHAUST FAN STATUS
BO - EXHAUST FAN START/STOP
EA
M
CT
STARTER
EF
S
BO - OUTSIDE AIR DAMPER
BI - OUTSIDE AIR DAMPER STATUS
N.C.
BI - SMOKE DETECTORBI - FREEZESTAT
T
M
STARTER
CT
BI - SUPPLY FAN STATUS
BO - SUPPLY FAN START/STOP
OA SA
T
AI - SUPPLY AIR TEMP
H L
AI - PREFILTER DIFFERENTIAL PRESSURE
M
RAEA
VFDCT
BO - HEAT WHEEL START/STOP
BI - HEAT WHEEL STATUS
AO - HEAT WHEEL VFD SPEED
BI - HEAT WHEEL VFD FAULT
CH
H L
AI - PREFILTER DIFFERENTIAL PRESSURE
AO - HEATING/COOLING VALVE
M
CHS
CHR
(TYPICAL OF ERV-2, ERV-3, ERV-4 AND ERV-5)
ERV-4, ERV-5 ONLY
THE FOLLOWING ARE CONTROL SEQUENCES TO COMMISSION IN THE FIELD, WITHOUT BAS
MONITORING. REPORT TO THE ENGINEER IF ANY SEQUENCE CANNOT BE PERFORMED DUE TO
INOPERABLE EQUIPMENT OR SENSORS:
DOMESTIC WATER CIRCULATING PUMPS (TYPICAL OF 1):
AN EXISTING STRAP ON THERMOSTAT ENERGIZES THE PUMP WHEN THE RETURN WATER
TEMPERATURE IS BELOW SETPOINT.
LAUNDRY DRYER (TYPICAL OF 4):
WHEN THE DRYER OPERATES, ITS RESPECTIVE OUTSIDE AIR DAMPER OPENS.
ELEVATOR HOISTWAY DAMPER (TYPICAL OF 1):
WHEN THE FIRE ALARM SMOKE DETECTOR IN THE ELEVATOR HOISTWAY OR THE ELEVATOR
LOBBY IS ACTIVED, THE ELEVATOR HOISTWAY DAMPER WILL OPEN
THE FOLLOWING ARE CONTROL SEQUENCES TO COMMISSION IN THE FIELD AND NEED BAS
MONITORING:
SUMP PUMPS (TYPICAL OF 2)
MONITOR THE EXISTING HIGH LEVEL ALARM CONTACT PROVIDED. PROVIDE ALARM WHEN THE
HIGH LEVEL ALARM STATE IS INDICATED.
MISCELLANEOUS CONTROL SEQUENCES AND POINTS
H
H L T
DX HGR
CT
T
OA
M
N.O.
N.C.
T
DA
M
SEQUENCE OF OPERATION - RTU-1 (TYPICAL OF 1)
RUN CONDITIONS - SCHEDULED:
THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES:
• OCCUPIED MODE: THE UNIT SHALL MAINTAIN
• A 74°F (ADJ.) COOLING SETPOINT
• A 70°F (ADJ.) HEATING SETPOINT.
• UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN
• A 85°F (ADJ.) COOLING SETPOINT.
• A 55°F (ADJ.) HEATING SETPOINT.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT BY A USER DEFINABLE
AMOUNT (ADJ.).
• LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A USER DEFINABLE
AMOUNT (ADJ.).
DEMAND LIMITING - ZONE SETPOINT OPTIMIZATION:
TO LOWER POWER CONSUMPTION, THE ZONE SETPOINTS SHALL AUTOMATICALLY RELAX WHEN THE FACILITY POWER CONSUMPTION EXCEEDS DEFINABLE THRESHOLDS. THE AMOUNT OF RELAXATION SHALL BE INDIVIDUALLY CONFIGURABLE FOR EACH ZONE. THE ZONE SETPOINTS SHALL AUTOMATICALLY RETURN TO THEIR PREVIOUS
SETTINGS WHEN THE FACILITY POWER CONSUMPTION DROPS BELOW THE THRESHOLDS.
ZONE SETPOINT ADJUST:
THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND COOLING SETPOINTS AT THE
ZONE SENSOR.
ZONE OPTIMAL START:
THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START-UP. THIS ALGORITHM SHALL MINIMIZE THE UNOCCUPIED WARM-UP OR COOL-DOWN PERIOD WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE START OF
SCHEDULED OCCUPIED PERIOD.
ZONE UNOCCUPIED OVERRIDE:
A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE EXPIRATION OF THIS TIME, CONTROL OF THE
UNIT SHALL AUTOMATICALLY RETURN TO THE SCHEDULE.
EMERGENCY SHUTDOWN:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN EMERGENCY SHUTDOWN SIGNAL.
SMOKE DETECTION:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A SMOKE DETECTOR STATUS.
FAN…