RFB941800-00 - Drawings.pdf

PDF 2 MB Posted

Attached to
HCR BAS Replacement
Solicitation number
005-RFBCON-1364-2025
Issued by
Allamakee County, Iowa

About this file

This document is a set of mechanical drawings and project specifications for the building automation system (BAS) improvements at the Honey Creek Resort in Moravia, Iowa. The project is being led by the State of Iowa Department of Administrative Services (DAS) and designed by the Farnsworth Group. The project scope includes replacing existing controllers, sensors, and sequences of operation for air handling units, heat pumps, exhaust fans, pool systems, domestic hot water systems, and other building systems. The project will be commissioned, and the contractor is required to coordinate with the commissioning agent. The project is scheduled to be completed by September 20, 2024.

The drawings and specifications provide detailed information on the new controls, including points lists, sequence of operations, and control schematics for the various mechanical systems. Pricing terms, funding sources, and other contractual details are not included in this document. The incumbent contractor is not specified. The project will be publicly bid, and the contractor will need to meet all state and local requirements to be awarded the contract.

View the file

Other files

File Type Posted
RFB941800-00 - Notice to Bidders.pdf PDF
RFB941800-00 - Bid Form.pdf PDF
1268901-event.pdf PDF
RFB941800-00 - Project Manual.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OWNER: STATE OF IOWA DAS PROJECT NUMBER: 9418.00

DESIGNER: FARNSWORTH GROUP

SHEET NUMBER:

SHEET of

HONEY CREEK LODGE - BAS

DAS PROJECT NAME: DNR HCR Building Automation System Improvements

/2

/2

:2 :4

A

M

9418.00 - HONEY CREEK RESORT

BUILDING AUTOMATION SYSTEM

IMPROVEMENTS

12633 Resort Dr, Moravia, IA 52571

09/20/2024

M0.00

PAGES OR DIVISIONS COVERED:

LICENSE RENEWAL DATE:

DATE:

NAME:

SIGNATURE:

THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW

WAS PREPARED BY ME OR UNDER MY DIRECT PERSONAL

Wade Ross

12/31/2025

ALL

SUPERVISION. I AM A DULY LICENSED ENGINEER UNDER THE

LAWS OF THE STATE OF IOWA.

9/20/2024

BD BOILER BLOW DOWN

CD CONDENSATE DRAIN

CWS CONDENSER WATER SUPPLY

HCWS DUAL TEMPERATURE SUPPLY

HPS HIGH PRESSURE STEAM

HRS HEAT RECOVERY SUPPLY

HTWS HIGH TEMP WATER SUPPLY

HWS HOT WATER SUPPLY

LPS LOW PRESSURE STEAM

LS LOOP SUPPLY

MPS MEDIUM PRESSURE STEAM

PD PUMP DISCHARGE

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID

RS REFRIGERANT SUCTION

CHR CHILLED WATER RETURN

CWR CONDENSER WATER RETURN

HCWR DUAL TEMPERATURE RETURN

HPR HIGH PRESSURE STEAM CONDENSATE RETURN

HRR HEAT RECOVERY RETURN

HTWR HIGH TEMP WATER RETURN

HWR HOT WATER RETURN

LPR LOW PRESSURE STEAM CONDENSATE RETURN

LR LOOP RETURN

MPR MEDIUM PRESSURE STEAM CONDENSATE RETURN

ABOVE CEILING/AIR CONDITIONERAC

OUTDOOR AIROA

AIR COOLED CONDENSERACC

AIR FILTERAF

ABOVE FINISHED FLOORAFF

AIR HANDLING UNITAHU

AIR MEASURING STATIONAMS

AIR SEPARATORAS

AUTOMATIC AIR VENTAV

BOILERB

BUILDING AUTOMATION SYSTEMBAS

BACKDRAFT DAMPERBDD

BELOW FINISHED CEILINGBFC

BACKFLOW PREVENTION DEVICEBFP

BETWEEN JOISTSBJ

BOTTOM OF DUCTBOD

BOTTOM OF PIPEBOP

BRITISH THERMAL UNITS PER HOURBTUH

COMPRESSED AIRCA

COUNTER BALANCED SHUTTERCBS

COOLING COILCC

CEILING / CIRCULATING FANCF

CUBIC FEET PER MINUTECFM

CHILLERCH

CHILLED WATER PUMPCHP

CHILLED WATER RETURNCHR

CHILLED WATER SUPPLYCHS

CONVECTORCNV

CONDENSATECOND

CONDENSATE PUMPCP

COMPUTER ROOM AIR CONDITIONERCRAC

COOLING TOWERCT

CONDENSING UNITCU

CABINET UNIT HEATERCUH

CONTROL VALVECV

DOMESTIC COLD WATERCW

CONDENSER WATER PUMPCWP

CONDENSER WATER RETURNCWR

CONDENSER WATER SUPPLYCWS

DRY COOLERDC

DN DOWN

DP DIFFERENTIAL PRESSURE

DS DUCT SILENCER

EA EXHAUST AIR

EBB ELECTRIC BASEBOARD HEATER

EF EXHAUST FAN

EG EXHAUST GRILLE (LESS DAMPER)

EHC ELECTRIC HEATING COIL

EL ELEVATION

ER EXHAUST REGISTER

ERV ENERGY RECOVERY VENTILATOR

ET EXPANSION TANK

FA FRESH AIR

FD FIRE DAMPER

FDC FLEXIBLE DUCT CONNECTION

FFA FROM FLOOR ABOVE

FFB FROM FLOOR BELOW

FPC FLEXIBLE PIPE CONNECTION

FPT FAN POWERED AIR TERMINAL

FT FINNED TUBE RADIATION

GF GAS FURNACE

GIH GRAVITY INTAKE HOOD

GPM GALLONS PER MINUTE

GR GLYCOL RETURN

GS GLYCOL SUPPLY

GUH GAS UNIT HEATER

HU HUMIDIFIER

HC HEATING COIL

HCWR DUAL TEMPERATURE RETURN

HCWS DUAL TEMPERATURE SUPPLY

HP HEAT PUMP

HPR HIGH PRESSURE STEAM RETURN

HPS HIGH PRESSURE STEAM SUPPLY

HRC HEAT RECOVERY COIL

HS HUMIDITY SENSOR

HWP HOT WATER PUMP

HWR HOT WATER RETURN

LOW PRESSURE STEAM SUPPLY

LOW PRESSURE STEAM RETURN

KITCHEN HOOD - COMMERCIAL

HEAT EXCHANGER

HOT WATER SUPPLY

LPS

LPR

KH

HX

HWS

THOUSANDS OF BTU PER HOUR

MOTORIZED DAMPER

MAKEUP AIR UNIT

MIXED AIR

MBH

MD

MAU

MA

OBD OPPOSED BLADE DAMPER

P PUMP

PBD PARALLEL BLADE DAMPER

PRV PRESSURE RELIEF VALVE

PS PRESSURE SWITCH

PSI POUNDS PER SQUARE INCH

PTAC

RA RETURN AIR

RF RETURN AIR FAN

RG RETURN GRILLE (LESS DAMPER)

RH ROOF HOOD

RHC REHEAT COIL

RLFA RELIEF AIR

RPZ REDUCED PRESSURE BFP

RR RETURN REGISTER (WITH DAMPER)

RTU ROOFTOP AIR HANDLING UNIT

SA SUPPLY AIR

SAS SELF-ACTING SHUTTER

SD SUPPLY DIFFUSER/SMOKE DAMPER

SF SUPPLY FAN / SQUARE FOOT

SFD SMOKE/FIRE DAMPER

SG SUPPLY GRILLE

SR SUPPLY REGISTER

TCAC TEMP. CONTROL AIR COMPRESSOR

TCAD TEMP. CONTROL AIR DRYER

TDV TRIPLE DUTY VALVE

TFA TO FLOOR ABOVE

TFB TO FLOOR BELOW

TOD TOP OF DUCT

TOP TOP OF PIPE

UC UNIT COOLER

UFD UNDERFLOOR DUCT

UH UNIT HEATER

UV UNIT VENTILATOR

VAV VARIABLE AIR VOLUME TERMINAL

VD VOLUME DAMPER

VFD VARIABLE FREQUENCY DRIVE

AUTOMATIC AIR VENT

TEMPERATURE SENSOR/SWITCH

PRESSURE GAUGE

THERMOMETER

PIPE ANCHOR

PIPE GUIDES

MANUAL AIR VENT

FLOW SENSOR/SWITCH

PIPE EXPANSION JOINT

PIPE UNION

CONCENTRIC REDUCER

ECCENTRIC REDUCER

WYE STRAINER

WYE STRAINER W/DRAIN VALVE

DIRECTION OF FLOW

STEAM BUCKET TRAP

STEAM F&T TRAP

BACKFLOW PREVENTER

PIPE TURNING UP

PIPE TURNING DOWN

TEE OFF TOP

TEE OFF BOTTOM

PIPE TEE

PIPE CAP

PLAN 90 DEGREE ELBOW

PLAN 45 DEGREE ELBOW

PIPING SYSTEM (SOLID LINE)

PIPING SYSTEM (DASHED LINE)

MOTORIZED SHUTTER

NOT TO SCALE

MS

NTS

GENERAL

HYDRONIC VENTILATION

GENERAL NOTES

DEMOLITION

UFT UNDERFLOOR FAN TERMINAL

HRV HEAT RECOVERY VENTILATOR (SENSIBLE)

EUH ELECTRIC UNIT HEATER

ESP EXTERNAL STATIC PRESSURE

INTERNAL STATIC PRESSUREISP

TSP TOTAL STATIC PRESSURE

PUMP

PC PLUMBING CONTRACTOR

EC ELECTRICAL CONTRACTOR

GC GENERAL CONTRACTOR

FLEXIBLE PIPE CONNECTOR

FCU FAN COIL UNIT

ALUMINUMAL

VRP VERTICAL RADIANT PANEL

WAC WINDOW / WALL AIR CONDITIONER

DOOR AIR CURTAINDAC

DH DEHUMIDIFIER

DOAS DEDICATED OUTDOOR AIR SYSTEM

DSU DUCTLESS SPLIT UNIT

DX DX COOLING COIL

ERP ELECTRIC RADIANT PANEL

GRH GAS RADIANT HEATER

LOUVERL

PDH POOL ROOM DEHUMIDIFIER

PACKAGED TERMINAL AIR CONDITIONER

RP RADIANT PANEL

S1 12x12

EXISTING

EQUIPMENT TYPE

EQUIPMENT MARK

SHEET #

DETAIL #

AIRFLOW IN CFM

THROAT SIZE

MECHANICAL EQUIPMENT TAG

AIR TERMINAL DESIGNATION

KEYNOTE

DETAIL OR SECTION MARK

POINT OF NEW CONNECTION

CAP EXISTING PIPE OR DUCT

BOLD TEXT INDICATES PROPOSED ITEM

ITALIC TEXT INDICATES EXISTING ITEM

NEW

PRESSURE/TEMPERATURE PLUG

AHU-1

GUARD LOCKABLE GUARD WHERE INDICATED

EQUIPMENT TO BE CONTROLLED

GUARD

TEMP

HUMID

CO

ELEMENT TO BE MONITORED

LOCKABLE GUARD WHERE INDICATED

HUMIDISTAT

THERMOSTAT

SENSOR

SUPPLY DIFFUSER/REGISTER

RETURN REGISTER/GRILLE

EXHAUST REGISTER/GRILLE

DIFFUSER AIRFLOW PATTERN IF

OTHER THAN 4-WAY BLOW

FLEXIBLE BRANCH RUNOUT TO SUPPLY

DIFFUSER, 36" MAX LENGTH

CEILING RETURN REGISTER WITH LINED

DUCT FOR SOUND ATTENUATION OPEN

TO CEILING PLENUM

FLEXIBLE DUCT CONNECTION TO

EQUIPMENT OR BETWEEN DUCTS

VOLUME DAMPER

MOTORIZED DAMPER

FIRE DAMPER

SMOKE DAMPER

COMBINATION FIRE/SMOKE DAMPER

SUPPLY AIR DUCT TOWARDS

SUPPLY AIR DUCT AWAY

RETURN/OUTDOOR AIR DUCT TOWARDS

RETURN/OUTDOOR AIR DUCT AWAY

TRANSFER AIR

A. INSTALL EQUIPMENT TO ALLOW MAXIMUM POSSIBLE HEADROOM UNLESS SPECIFIC MOUNTING

HEIGHTS ARE INDICATED

B. INSTALL EQUIPMENT LEVEL AND PLUMB, PARALLEL AND PERPENDICULAR TO OTHER BUILDING

SYSTEMS AND COMPONENTS IN EXPOSED INTERIOR SPACES, UNLESS OTHERWISE INDICATED

C. INSTALL HVAC EQUIPMENT TO FACILITATE SERVICE, MAINTENANCE, AND REPAIR OR REPLACEMENT OF COMPONENTS. CONNECT EQUIPMENT FOR EASE OF REMOVAL, WITH MINIMUM INTERFERENCE TO

OTHER INSTALLATIONS

D. THE INSTALLING CONTRACTOR ASSUMES FULL RESPONSIBILITY FOR ALL MECHANICAL EQUIPMENT

PUT INTO OPERATION PRIOR TO THE INSTALLATION OF A WORKING CONTROL SYSTEM.

A. VERIFY EXACT SIZE AND LOCATION OF EXISTING UTILITIES PRIOR TO START OF DEMOLITION WORK

B. RELOCATE, REMOVE, AND ADJUST ALL MECHANICAL AND ELECTRICAL ITEMS AS REQUIRED TO

ACCOMPLISH SCOPE OF NEW WORK

C. EXISTING MECHANICAL ITEMS ARE SHOWN IN SCHEMATIC FORM BASED UPON EXISTING

CONSTRUCTION DOCUMENTS AND/OR FIELD INVESTIGATION

D. FIXTURES AND EQUIPMENT INDICATED TO BE REUSED OR SALVAGED SHALL REMAIN THE

PROPERTY OF THE OWNER AND BE STORED IN A LOCATION AS DIRECTED BY OWNER'S

REPRESENTATIVE

E. IN LOCATIONS WHERE EXISTING CONSTRUCTION IS REMOVED AND NO ADDITIONAL CONSTRUCTION IS INDICATED, PATCH EXISTING CONSTRUCTION TO MATCH ADJACENT SURFACES AND FINISHES

MECHANICAL EQUIPMENT INSTALLATION

PRESSURE SENSOR/SWITCH

EXHAUST AIR DUCT TOWARDS

EXHAUST AIR DUCT AWAY

TJ THROUGH JOISTS

CHS CHILLED WATER SUPPLY

CO2

3-WAY CONTROL VALVE

ANGLE GATE VALVE

ANGLE GLOBE VALVE

BALANCING/SHUTOFF VALVE

BALL VALVE

BUTTERFLY VALVE

CHECK VALVE

CALIBRATED BALANCING VALVE

CONTROL VALVE

EXPANSION VALVE

GATE VALVE

GLOBE VALVE

QUICK OPEN VALVE

SAFETY RELIEF VALVE

SOLENOID VALVE

VACUUM RELIEF VALVE

GAS COCK

PLUG VALVE

PRESSURE REDUCING VALVE (WATER)

PRESSURE REGULATOR (GAS)

PIPE SLOPE ARROW

WALL SWITCH

H

S

T

CFM

F

P

T

FLAT OVAL DUCT12x8Φ

ROUND DUCT12"ø

RECTANGULAR DUCT12x8

AHU

METERM

MECHANICAL CONTRACTORMC

SYMBOLS LEGEND

NOTE: NOT ALL SYMBOLS ARE USED IN CONSTRUCTION DOCUMENTS

ABBREVIATIONS

LINE STYLE INDICATES DEMOLISHED ITEM

DDC CONTROLS

PROVIDE NEW FRONT END NETWORK MANAGER WITH WEB CABILITY. 1 YEAR SOFTWARE

MAINTENANCE AGREEEMENT, NEW GRAPHICS, ALARMING CAPABILITY FROM REMOTE LOCATION

THROUGH PHONE, TABLET, COMPUTER.

REPLACE EXISTING CONTROLLERS WITH NEW. PROVIDE NEW SENSORS WHERE INDICATED

THE PROJECT WILL BE COMMISSIONED. THE COMMISSIONING AGENT WILL BE HIRED BY THE OWNER.

COORDINATE EFFORTS WITH THE COMMISSIONING AGENT AND SPECIFICATIONS.

www.f-w.com Engineers | Architects | Surveyors | Scientists

GROUP

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

100 WALNUT STREET, SUITE 200

PEORIA, ILLINOIS 61602

(309) 689-9888 / info@f-w.com

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/2

/2

:2 :4

A

M M0.1

GENERAL

INFORMATION

LDE

WCR

0241027.00

9418.00 - HONEY

CREEK RESORT

BUILDING

AUTOMATION

SYSTEM

IMPROVEMENTS

12633 Resort Dr, Moravia, IA 52571

09/20/2024

WCR

PERMIT SET

SHEET LIST

Discipline No. Description

MECHANICAL M0.00 COVER SHEET

MECHANICAL M0.1 GENERAL INFORMATION

MECHANICAL M1.1 LOWER LEVEL AREA A

MECHANICAL M1.2 LOWER LEVEL AREA B

MECHANICAL M1.3 FIRST FLOOR PLAN AREA A

MECHANICAL M1.4 FIRST FLOOR PLAN AREA B

MECHANICAL M1.5 FIRST FLOOR PLAN AREA C

MECHANICAL M1.6 SECOND FLOOR PLAN AREA A

MECHANICAL M1.7 SECOND FLOOR PLAN AREA B

MECHANICAL M1.8 THIRD FLOOR PLAN AREA A

MECHANICAL M1.9 THIRD FLOOR PLAN AREA B

MECHANICAL M5.1 CONTROLS DIAGRAMS

MECHANICAL M5.2 CONTROLS DIAGRAMS

MECHANICAL M5.3 CONTROLS DIAGRAMS

MECHANICAL M5.4 CONTROLS DIAGRAMS

1 09/20/24 Permit Set

T T T T T T T T

T

ERV

ERV

ATA

ATA

ATA

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

4 4 4 4 4 4

4 44 44 44

T

ATA-2

T ATA-1

ELEC. ROOM

A006

T

ATA-1

T H

EF

EF

(TYP 4)

T

EF

www.f-w.com Engineers | Architects | Surveyors | Scientists

GROUP

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

100 WALNUT STREET, SUITE 200

PEORIA, ILLINOIS 61602

(309) 689-9888 / info@f-w.com

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/2

/2

:2 :4

A

M M1.1

LOWER LEVEL AREA

A

LDE

WCR

0241027.00

9418.00 - HONEY

CREEK RESORT

BUILDING

AUTOMATION

SYSTEM

IMPROVEMENTS

12633 Resort Dr, Moravia, IA 52571

09/20/2024

WCR

PERMIT SET

0 4 8 16

NORTH

TRUE

D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.

C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.

B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR

EQUIPMENT SHUT DOWNS.

A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR

OTHER EQUIPMENT IS REMOVED.

GENERAL NOTES

SCALE: 1/8" = 1'-0"

FIRST FLOOR VENTILATION PLAN

#KEYNOTES

1 REPLACE EXISTING THERMOSTAT FOR EXISTING AIR TO AIR HEAT PUMP WITH PROGRAMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT PUMP. PROVIDE NEW LEAVING AIR TEMPERATURE SENSOR AND FILTER DIFFERENTIAL

PRESSURE SWITCH. REVISE SEQUENCE OF OPERATION.

2 REPLACE EXISTING CONTROLS FOR ERV-2. REVISE SEQUENCE OF OPERATIONS PER DETAIL 2 ON SHEET M5.2.

RECOMMISSION AND REBALANCE UNIT.

3 EXISTING ERV SERVING THE POOL AREA. REPLACE EXISTING CONTROLS, THERMOSTAT AND HUMIDSTAT. REFER TO

DETAIL 2 ON SHEET M5.4.

4 REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT PUMP WITH PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT PUMP.REMOVE ALL WIRING. PROVIDE NEW LEAVING AIR TEMPERATURE SENSOR, WATER SENSOR AND FILTER DIFFERENTIAL PRESSURE SWITCH. PROVIDE NEW WIRING AND CONDUIT AS

REQUIRED. REVISE SEQUENCE OF OPERATION, REFER TO DETAIL 1 ON SHEET M5.1.

5 REMOVE AND REPLACE EXISTING DDC CONTROLLERS. PROVIDE NEW WIRING TO EXISTING AND NEW CONTROLS.

6 FOUR EXISTING 24X32 MOTORIZED DAMPERS LOCATED IN EXISTING DUCTWORK. REPLACE THE EXISTIGN ACTUATORS AND PROVIDE NEW CONTROLS, REFER TO DETAIL 3 ON M5.2 FOR NEW SEQUENCE OF OPERATION.

7 POOL ROOM EXHAUST FAN AND MOTORIZED DAMPER. REPLACE THE EXISTING ACTUATOR. PROVIDE NEW CONTROLS.

REFER TO DETAIL 1 ON SHEET M5.2 FOR NEW SEQUENCE OF OPERATION.

8 REPLACE EXISTING THERMOSTAT AND PROVIDE NEW CONTROLS AND SEQUENCE FOR ELEVATOR ROOM FAN

CONTROLS. REFER TO DETAIL 3 ON SHEET M5.1 FOR NEW SEQUENCE OF OPERATION.

9 PROVIDE NEW CONTROLLER FOR WADING POOL CONTROLS, INCLUDING HEATER, FILTER DP, PUMP AND TEMPERATURE

SENSORS. REFER TO DETAIL 6 ON SHEET M5.3 FOR NEW SEQUENCE OF OPERATION.

10 PROVIDE NEW CONTROLLER FOR PLUNGE POOL CONTROLS, INCLUDING HEATER, FILTER DP, PUMP AND TEMPERATURE

SENSORS. REFER TO DETAIL 6 ON SHEET M5.3 FOR NEW SEQUENCE OF OPERATION.

11 PROVIDE NEW CONTROLLER FOR SPA POOL CONTROLS, INCLUDING HEATER, FILTER DP, PUMP AND TEMPERATURE

SENSORS. REFER TO DETAIL 6 ON SHEET M5.3 FOR NEW SEQUENCE OF OPERATION.

12 PROVIDE NEW TEMPERATURE SENSOR. SENSOR TO MONITOR TEMPERATURE IN SPACE AND REPORT BACK TO FRONT

END DDC SYSTEM.

13 POOL SLIDE FAN. PROVIDE NEW CONTROLS, INCLUDING NEW TEMPERATURE SENSOR. REFER TO DETAIL 3, SHEET M5.1.

T T T T

T T

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A 1 1 1 1 1 1

1111 T

T2 www.f-w.com Engineers | Architects | Surveyors | Scientists

GROUP

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

100 WALNUT STREET, SUITE 200

PEORIA, ILLINOIS 61602

(309) 689-9888 / info@f-w.com

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/2

/2

:2 :4

A

M M1.2

LOWER LEVEL AREA

B

LDE

WCR

0241027.00

9418.00 - HONEY

CREEK RESORT

BUILDING

AUTOMATION

SYSTEM

IMPROVEMENTS

12633 Resort Dr, Moravia, IA 52571

09/20/2024

WCR

PERMIT SET

D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.

C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.

B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR

EQUIPMENT SHUT DOWNS.

A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR

OTHER EQUIPMENT IS REMOVED.

GENERAL NOTES

0 4 8 16

NORTH

TRUE

#KEYNOTES

1 REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT

PUMP WITH PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT

PUMP. REMOVE ALL WIRING. PROVIDE NEW WIRING AND CONDUIT AS

REQUIRED.PROVIDE NEW LEAVING AIR TEMPERATURE WATER SENSOR AND FILTER

DIFFERENTIAL PRESSURE SWITCH. REVISE SEQUENCE OF OPERATION, REFER TO

DETAIL 1 ON SHEET M5.1

2 PROVIDE NEW TEMPERATURE SENSOR. SENSOR TO MONITOR TEMPERATURE IN

SPACE AND REPORT BACK TO FRONT END DDC SYSTEM.

SCALE: 1/8" = 1'-0"

FIRST FLOOR VENTILATION PLAN

T T T T T T T T T T T T

TTTTTTTT

ATA

ATA

ATA

ATA

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

1 1

1 1 1 1 1

1 1 1 1 1 1 1 1

1 1 1 1 1 1

1 1

1 1 1 1 1 1 1 1

1 1 1 1 1 1 1 1

T

T ATA-7

ATA-6

TATA-5

T ATA-4

T

Domestic Water

Pump Circle

T

4T www.f-w.com Engineers | Architects | Surveyors | Scientists

GROUP

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

100 WALNUT STREET, SUITE 200

PEORIA, ILLINOIS 61602

(309) 689-9888 / info@f-w.com

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/2

/2

:2 :4

A

M M1.3

FIRST FLOOR PLAN

AREA A

LDE

WCR

0241027.00

9418.00 - HONEY

CREEK RESORT

BUILDING

AUTOMATION

SYSTEM

IMPROVEMENTS

12633 Resort Dr, Moravia, IA 52571

09/20/2024

WCR

PERMIT SET

D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.

C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.

B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR

EQUIPMENT SHUT DOWNS.

A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR

OTHER EQUIPMENT IS REMOVED.

GENERAL NOTES

0 4 8 16

NORTH

TRUE

#KEYNOTES

1 REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT

PUMP WITH PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT

PUMP.REMOVE ALL WIRING. PROVIDE NEW WIRING AND CONDUIT AS REQUIRED.

PROVIDE NEW LEAVING AIR TEMPERATURE SENSOR, WATER SENSOR SWITCH AND

FILTER DIFFERENTIAL PRESSURE SWITCH. REVISE SEQUENCE OF OPERATION,

REFER TO DETAIL 1 ON SHEET M5.1.

2 REPLACE EXISTING THERMOSTAT FOR EXISTING AIR TO AIR HEAT PUMP WITH

PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT PUMP. REMOVE

ALL WIRING. PROVIDE NEW WIRING AND CONDUIT AS REQUIRED. PROVIDE NEW

LEAVING AIR TEMPERATURE SENSOR AND FILTER DIFFERENTIAL PRESSURE

SWITCH. REVISE SEQUENCE OF OPERATION, REFER TO DETAIL 1 ON SHEET M5.1.

3 PROVIDE NEW CONTROLS FOR DOMESTIC WATER RECIRCULATION PUMP. MONITOR

PER DETAIL 3 ON SHEET M5.2.

4 PROVIDE NEW DOMESTIC LEAVING WATER TEMPERATURE SENSOR, MONITOR

TEMPERATURE AND PROVIDE GRAPHICS. REFER TO DETAIL 5 ON SHEET M5.1.

5 PROVIDE NEW TEMPERATURE SENSOR. SENSOR TO MONITOR TEMPERATURE IN

SPACE AND REPORT BACK TO FRONT END DDC SYSTEM.SCALE: 1/8" = 1'-0"

SECOND FLOOR VENTILATION PLAN

TTTT

T T

T T T

T T

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

1 1 1 1 1

1 11

11 1 1 1 1

T T

EXISTING ELECTRIC HEATEREXISTING ELECTRIC HEATER

T

WTA-13

T

WTA-14

EXISTING ELECTRIC HEATEREXISTING ELECTRIC HEATER

2 2

T

T

6 6 www.f-w.com Engineers | Architects | Surveyors | Scientists

GROUP

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

100 WALNUT STREET, SUITE 200

PEORIA, ILLINOIS 61602

(309) 689-9888 / info@f-w.com

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/2

/2

:2 :4

A

M M1.4

FIRST FLOOR PLAN

AREA B

LDE

WCR

0241027.00

9418.00 - HONEY

CREEK RESORT

BUILDING

AUTOMATION

SYSTEM

IMPROVEMENTS

12633 Resort Dr, Moravia, IA 52571

09/20/2024

WCR

PERMIT SET

D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.

C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.

B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR

EQUIPMENT SHUT DOWNS.

A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR

OTHER EQUIPMENT IS REMOVED.

GENERAL NOTES

0 4 8 16

NORTH

TRUE

#KEYNOTES

1 REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT

PUMP WITH PREOGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT

PUMP REVISE SEQUENCE OF OPERATION,REMOVE ALL WIRING. PROVIDE NEW

WIRING AND CONDUIT AS REQUIRED. REFER TO DETAIL 1 ON SHEET M5.1.

2 REPLACE EXISTING THERMOSTAT FOR EXISTING AIR TO AIR HEAT PUMP WITH

PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT PUMP. REVISE

SEQUENCE OF OPERATION, REMOVE ALL WIRING. PROVIDE NEW WIRING AND

CONDUIT AS REQUIRED. REFER TO DETAIL 1 ON SHEET M5.1.

3 REPLACE THERMOSTAT AND CONTROLS FOR EXISTING WATER TO AIR HEAT PUMP.

REFER TO DETAIL 1 ON SHEET M5.3. HEAT PUMP IS LOCATED ON SHEET M1.5.

4 REPLACE THERMOSTAT AND CONTROLS FOR EXISTING WATER TO AIR HEAT PUMP.

REFER TO DETAIL 1 ON SHEET M5.3. HEAT PUMP IS LOCATED ON SHEET M1.5

5 PROVIDE NEW TEMPERATURE SENSOR. SENSOR TO MONITOR TEMPERATURE IN

SPACE AND REPORT BACK TO FRONT END DDC SYSTEM.

6 EXISTING ELECTRIC HEATER, REFER TO DETAIL 3 ON M5.3.SCALE: 1/8" = 1'-0"

SECOND FLOOR VENTILATION PLAN

WTA

WTA

WTA

WTA

WTA

WTA

WTA

WTA

11 ERV

WTA

WTA

WTA

WTA

WTA

RTU

RTU

WTA

RTU

WTA

WTA

WTA

WTA

WTA

ERV

WTA

WTA

T WTA 19

TWTA 20

TWTA 17,18

TWTA 11

T WTA 21

T WTA 12

T

WTA 28

T WTA 31

TWTA 22 TWTA 23 T WTA 24

T WTA 27

T WTA 26

T WTA 25

TWTA 30

WTA

T WTA 29

T

WTA 16

T

WTA 15

P

P

P

P

ET

1 JANITOR/MECH

C160

WTW

WTW

2 2

2 2

P

1P

2 EXISTING DDC

CONTROLLERS

2 2 2

T

T

SALES

MANAGER

C107

GENERAL

MANAGER

C108

ASSISTANT

MANAGER

C111

BUSINESS

CENTER

C103

REBALANCE

TO 250 CFM

REBALANCE

TO 250 CFM

x x

8"ø

12x12

REBALANCE

EXISTING HEAT

PUMP

TO 750 CFM

H9

H 9 H 9 H9

H

H 9

H 9

10 10 www.f-w.com Engineers | Architects | Surveyors | Scientists

GROUP

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

100 WALNUT STREET, SUITE 200

PEORIA, ILLINOIS 61602

(309) 689-9888 / info@f-w.com

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/2

/2

:2 :4

A

M M1.5

FIRST FLOOR PLAN

AREA C

LDE

WCR

0241027.00

9418.00 - HONEY

CREEK RESORT

BUILDING

AUTOMATION

SYSTEM

IMPROVEMENTS

12633 Resort Dr, Moravia, IA 52571

09/20/2024

WCR

PERMIT SET

0 4 8 16 N O R

TH

TRUE

SCALE: 1/8" = 1'-0"

SECOND FLOOR VENTILATION PLAN

D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.

C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.

B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR

EQUIPMENT SHUT DOWNS.

A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR

OTHER EQUIPMENT IS REMOVED.

GENERAL NOTESKEYNOTES

1 REPLACE EXISTING CONTROLS FOR ERV-4 AND ERV-5. REVISE SEQUENCE OF

OPERATIONS PER DETAIL 2 ON SHEET M5.2. RECOMMISSION AND REBALANCE UNIT.

REVISE SEQUENCE OF OPERATION.

2 REPLACE EXISTING THERMOSTAT FOR EXISTING WATER TO AIR HEAT PUMP WITH

PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT PUMP.REMOVE

ALL WIRING. PROVIDE NEW WIRING AND CONDUIT AS REQUIRED. HEAT PUMP IS

LOCATED ABOVE CEILING. REVISE SEQUENCE OF OPERATION, REFER TO DETAIL 1

ON SHEET M5.3.

3 REPLACE EXISTING CONTROLS FOR ROOFTOP UNIT SERVING AS A MAKE UP AIR

UNIT AND HVAC FOR THE KITCHEN AREA. UNIT HAS TO BACNET CONTROLLER, PULL

IN ALL POINTS AND PROVIDE GRAPHICS FOR UNIT. REFER TO DETAIL 4 ON SHEET

M5.2.

4 REPLACE EXISTING CONTROLS FOR ROOFTOP UNIT SERVING AS A MAKE UP AIR

UNIT FOR THE KITCHEN HOODS. REVISE SEQUENCE OF OPERATION, REFER TO

DETAIL 1 ON SHEET M5.4.

5 REVISE CONTROL SEQUENCE FOR GROUND LOOP PUMPS. REFER TO DETAIL 2 ON

SHEET M5.1.

6 REVISE CONTROL SEQUENCE FOR WATER TO WATER HEAT PUMPS AND

ASSOCIATED PUMPS, REFER TO DETAIL 5 ON SHEET M5.3.

7 REVISE CONTROL SEQUENCE FOR BUILDING LOOP PUMPS. REFER TO DETAIL 4 ON

SHEET M5.1.

8 PROVIDE NEW TEMPERATURE SENSOR. SENSOR TO MONITOR TEMPERATURE IN

SPACE AND REPORT BACK TO FRONT END DDC SYSTEM.

9 EXISTING HUMIDISTAT, MONITOR STATUS AND ALARM AT 800 PPM.

10 PROVIDE NEW CONTROLS FOR DOMESTIC WATER CIRC PUMP. MONITOR PER

DETAIL 3 ON SHEET M5.2

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

T T T T T T T T T T T T

TTTTTTTTTTTTTT

ATA

A

1 1 1 1 1 1 1 11 11 11

1 1 1 1 1 1 1 1 1 1 1 1 1 1

1 1 1 1 1 1 1 1 1 1 1 1

11 11 11 11 11

ERV

ATA

ATA

CORRIDOR

A201

TT ATA-9 ATA-8

www.f-w.com Engineers | Architects | Surveyors | Scientists

GROUP

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

100 WALNUT STREET, SUITE 200

PEORIA, ILLINOIS 61602

(309) 689-9888 / info@f-w.com

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/2

/2

:2 :4

A

M M1.6

SECOND FLOOR

PLAN AREA A

LDE

WCR

0241027.00

9418.00 - HONEY

CREEK RESORT

BUILDING

AUTOMATION

SYSTEM

IMPROVEMENTS

12633 Resort Dr, Moravia, IA 52571

09/20/2024

WCR

PERMIT SET

0 4 8 16

NORTH

TRUE

SCALE: 1/8" = 1'-0"

THIRD FLOOR VENTILATION PLAN

D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.

C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.

B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR

EQUIPMENT SHUT DOWNS.

A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR

OTHER EQUIPMENT IS REMOVED.

GENERAL NOTESKEYNOTES

1 REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT

PUMP WITH PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT

PUMP. PROVIDE NEW LEAVING AIR TEMPERATURE SENSOR, WATER SENSOR

SWITCH AND FILTER DIFFERENTIAL PRESSURE SWITCH. REMOVE ALL WIRING.

PROVIDE NEW WIRING AND CONDUIT AS REQUIRED. REVISE SEQUENCE OF

OPERATION, REFER TO DETAIL1 ON SHEET M5.1.

2 REPLACE EXISTING THERMOSTAT FOR EXISTING AIR TO AIR HEAT PUMP WITH

PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT PUMP. PROVIDE

NEW LEAVING AIR TEMPERATURE SENSOR, WATER SENSOR SWITCH AND FILTER

DIFFERENTIAL PRESSURE SWITCH. REMOVE ALL WIRING. PROVIDE NEW WIRING

AND CONDUIT AS REQUIRED. REVISE SEQUENCE OF OPERATION, REFER TO DETAIL

1 ON SHEET M5.1.

3 REPLACE EXISTING CONTROLS FOR ERV-2. REVISE SEQUENCE OF OPERATIONS

PER DETAIL 2 ON SHEET M5.2. RECOMMISSION AND REBALANCE UNIT. REVISE

SEQUENCE OF OPERATION.

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

T T T T

T T

T T T T T T

111111

1 1 1 1 1 1

1 1

1 11 1 www.f-w.com Engineers | Architects | Surveyors | Scientists

GROUP

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

100 WALNUT STREET, SUITE 200

PEORIA, ILLINOIS 61602

(309) 689-9888 / info@f-w.com

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/2

/2

:2 :4

A

M M1.7

SECOND FLOOR

PLAN AREA B

LDE

WCR

0241027.00

9418.00 - HONEY

CREEK RESORT

BUILDING

AUTOMATION

SYSTEM

IMPROVEMENTS

12633 Resort Dr, Moravia, IA 52571

09/20/2024

WCR

PERMIT SET

0 4 8 16

NORTH

TRUE

SCALE: 1/8" = 1'-0"

THIRD FLOOR VENTILATION PLAN

D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.

C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.

B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR

EQUIPMENT SHUT DOWNS.

A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR

OTHER EQUIPMENT IS REMOVED.

GENERAL NOTESKEYNOTES

1 REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT

PUMP WITH PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT

PUMP. PROVIDE NEW LEAVING AIR TEMPERATURE SENSOR, WATER SENSOR

SWITCH AND FILTER DIFFERENTIAL PRESSURE SWITCH. REMOVE ALL WIRING.

PROVIDE NEW WIRING AND CONDUIT AS REQUIRED. REVISE SEQUENCE OF

OPERATION, REFER TO DETAIL 1 ON SHEET M5.1.

T

T

T

T

T

T

T

T

T

T T

T

T

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

1 1

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A 1 1 1 1 1 1

1 1 1 1

ATA

A

ATA

A 1 1

1 1 1 1 1 1

1 1

1 1

T

T www.f-w.com Engineers | Architects | Surveyors | Scientists

GROUP

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

100 WALNUT STREET, SUITE 200

PEORIA, ILLINOIS 61602

(309) 689-9888 / info@f-w.com

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/2

/2

:2 :4

A

M M1.8

THIRD FLOOR PLAN

AREA A

LDE

WCR

0241027.00

9418.00 - HONEY

CREEK RESORT

BUILDING

AUTOMATION

SYSTEM

IMPROVEMENTS

12633 Resort Dr, Moravia, IA 52571

09/20/2024

WCR

PERMIT SET

0 4 8 16

NORTH

TRUE

SCALE: 1/8" = 1'-0"

THIRD FLOOR PLAN A

D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.

C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.

B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR

EQUIPMENT SHUT DOWNS.

A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR

OTHER EQUIPMENT IS REMOVED.

GENERAL NOTESKEYNOTES

1 REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT

PUMP WITH PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT

PUMP. PROVIDE NEW LEAVING AIR TEMPERATURE SENSOR, WATER SENSOR

SWITCH AND FILTER DIFFERENTIAL PRESSURE SWITCH. REMOVE ALL WIRING.

PROVIDE NEW WIRING AND CONDUIT AS REQUIRED. REVISE SEQUENCE OF

OPERATION, REFER TO DETAIL1 ON SHEET M5.1.

T T

TTT

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

ATA

A

1 1 11

1 1

11 1 1 www.f-w.com Engineers | Architects | Surveyors | Scientists

GROUP

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

100 WALNUT STREET, SUITE 200

PEORIA, ILLINOIS 61602

(309) 689-9888 / info@f-w.com

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/2

/2

:2 :4

A

M M1.9

THIRD FLOOR PLAN

AREA B

LDE

WCR

0241027.00

9418.00 - HONEY

CREEK RESORT

BUILDING

AUTOMATION

SYSTEM

IMPROVEMENTS

12633 Resort Dr, Moravia, IA 52571

09/20/2024

WCR

PERMIT SET

0 4 8 16

NORTH

TRUE

D. CONTRACTOR TO REMOVE AND REINSTALL CEILING TILES AS REQUIRED.

C. CONTRACTOR TO COORDINATE AFTER HOURS OR WEEKEND WORK WITH OWNER.

B. CONTRACTOR TO PROVIDE 48 HOURS NOTICE TO OWNER FOR ANY UTILITY OR

EQUIPMENT SHUT DOWNS.

A. CONTRACTOR TO PATCH AND PAINT WALLS WHERE SENSORS, CONTROLLERS OR

OTHER EQUIPMENT IS REMOVED.

GENERAL NOTESKEYNOTES

1 1. REPLACE EXISTING THERMOSTAT FOR EXISTING LODGE ROOM AIR TO AIR HEAT

PUMP WITH PROGRAMMABLE THERMOSTAT AND CONNECT TO EXISTING HEAT

PUMP. PROVIDE NEW LEAVING AIR TEMPERATURE SENSOR, WATER SENSOR

SWITCH AND FILTER DIFFERENTIAL PRESSURE SWITCH. REVISE SEQUENCE OF

OPERATION, REFER TO DETAIL 1 ON SHEET M5.1.

SCALE: 1/8" = 1'-0"

THIRD FLOOR PLAN B

H L

AI - FILTER DIFFERENTIAL PRESSURE

SCR

BO - HEATING ENABLE

HP

BI - SMOKE DETECTOR

T

AI - DISCHARGE AIR TEMP

BI - ZONE OVERRIDE

AI - ZONE SETPOINT ADJUST

OA

RA

DA

T

AI - ZONE TEMP

SEQUENCE OF OPERATION - AIR SOURCE HEAT PUMP (TYPICAL OF 114)

RUN CONDITIONS - SCHEDULED:

THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES:

• OCCUPIED MODE: THE UNIT SHALL MAINTAIN

• A 74°F (ADJ.) COOLING SETPOINT

• A 70°F (ADJ.) HEATING SETPOINT

• UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN

• A 85°F (ADJ.) COOLING SETPOINT.

• A 55°F (ADJ.) HEATING SETPOINT.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).

• LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).

• THE EXISTING AIR TO AIR HEAT PUMPS ARE CURRENTLY NOT ON THE EXISTING BAS.

• PROVIDE A NEW CONTROLLER FOR EACH OF THE 9 DUCTED AIR TO AIR HEAT PUMPS WITH OCCUPIED AND UNOCCUPIED MODES.

THE SUPPLY FAN SHALL RUN CONTINUOUSLY IN OCCUPIED MODE. THE HEAT PUMP SHALL RUN ON ITS OWN CONTROLS TO

MAINTAIN SPACE TEMPERATURE.

• FURNISH NEW LEAVING AIR TEMPERATURE SENSOR AND FILTER DIFFERENTIAL PRESSURE SENSOR.

• PROVIDE NEW WIRING AND CONTROLS FOR EXISTING UNITS. PROVIDE NEW GRAPHICS WITH THE NOTED CONTROL POINTS.

FILTER DIFFERENTIAL PRESSURE MONITOR:

THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE FILTER.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• FILTER CHANGE REQUIRED: FILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINABLE LIMIT (ADJ.).

DISCHARGE AIR TEMPERATURE:

THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE.

- WATER IS DETECTED AT WATER SENSOR SWITCH

• HIGH DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).

• LOW DISCHARGE AIR TEMP: IF THE DISCHARGE AIR TEMPERATURE IS LESS THAN 40°F (ADJ.).

MANUAL VD

MANUAL VD

BO - HEAT PUMP ENABLE

WS

BI - WATER SENSOR STATUS

CONTRACTOR TO PROVIDE

NEW WATER SENSOR TO

ALL HOTELING ROOM UNITS.

CONTRACTOR TO PROVIDE

NEW FILTER DIFFERENTIAL

PRESSURE SWITCH TO ALL

UNITS (TYP ALL)

CONTRACTOR TO PROVIDE NEW DISCHARGE AIR SENSOR TO UNIT DUCTWORK (TYP ALL)

GLRGLR

T

AI - GEOTHERMAL LOOP RETURN TEMP

T

AI - GROUND LOOP SUPPLY TEMP

GLS

GLR

VFD

VFD

BI - GEOTHERMAL LOOP 3 VFD FAULT

AO - GEOTHERMAL LOOP 3 VFD SPEED

P3

P4

M

M

CT

CT

BI - GEOTHERMAL LOOP 3 STATUS

BI - GEOTHERMAL LOOP 4 STATUS

BO - GEOTHERMAL LOOP 3 START/STOP

GLS GLS

SEQUENCE OF OPERATION - GEOTHERMAL LOOP PUMPS (TYPICAL OF 1)

GEOTHERMAL LOOP PUMP SYSTEM - RUN CONDITIONS:

THE GEOTHERMAL LOOP PUMPS SHALL BE ENABLED WHENEVER:

• THE GEOTHERMAL LOOP PUMPS ILL RUN WHEN THE TEMPERATURE OF

THE BUILDING LOOP RETURN WATER TEMPERATURE EXCEEDS 60F OR

DROPS BELOW 45F FOR 15 MINUTES OR MORE.

• IF THE BUILDING LOOP TEMPERATURE IS BETWEEN 45F AND 60F THE

PUMPS WILL BE OFF.

TO PREVENT SHORT CYCLING, THE GEOTHERMAL LOOP PUMP SYSTEM

SHALL RUN FOR AND BE OFF FOR MINIMUM ADJUSTABLE TIMES (BOTH

USER DEFINABLE).

GEOTHERMAL LOOP PUMP LEAD/LAG OPERATION:

THE TWO VARIABLE SPEED GEOTHERMAL LOOP PUMPS SHALL OPERATE

IN A LEAD/LAG FASHION.

• THE LEAD PUMP SHALL RUN FIRST.

• ON FAILURE OF THE LEAD PUMP, THE LAG PUMP SHALL RUN AND THE

LEAD PUMP SHALL TURN OFF.

THE DESIGNATED LEAD PUMP SHALL ROTATE UPON ONE OF THE

FOLLOWING CONDITIONS (USER SELECTABLE):

• MANUALLY THROUGH A SOFTWARE SWITCH

• IF PUMP RUNTIME (ADJ.) IS EXCEEDED

• DAILY

• WEEKLY

• MONTHLY

GEOTHERMAL LOOP PROVIDED AS FOLLOWS:

• GEOTHERMAL LOOP PUMP 1

• FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

• RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

• RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE

LIMIT.

• VFD FAULT.

• GEOTHERMAL LOOP PUMP 2

• FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

• RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

• RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE

LIMIT.

• VFD FAULT.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• HIGH GEOTHERMAL LOOP DIFFERENTIAL PRESSURE: IF THE

GEOTHERMAL LOOP DIFFERENTIAL PRESSURE IS 25% (ADJ.) GREATER

THAN SETPOINT.

• LOW GEOTHERMAL LOOP DIFFERENTIAL PRESSURE: IF THE

GEOTHERMAL LOOP DIFFERENTIAL PRESSURE IS 25% (ADJ.) LESS THAN

SETPOINT.

GEOTHERMAL LOOP TEMPERATURE MONITORING:

THE FOLLOWING TEMPERATURES SHALL BE MONITORED:

• GEOTHERMAL LOOP SUPPLY.

• GEOTHERMAL LOOP RETURN.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• HIGH GEOTHERMAL LOOP SUPPLY TEMP: IF THE GEOTHERMAL LOOP

SUPPLY TEMPERATURE IS GREATER THAN 55°F (ADJ.).

• LOW GEOTHERMAL LOOP SUPPLY TEMP: IF THE GEOTHERMAL LOOP

SUPPLY TEMPERATURE IS LESS THAN 38°F (ADJ.).

BI - GEOTHERMAL LOOP 4 VFD FAULT

AO - GEOTHERMAL LOOP 4 VFD SPEED

BO - GEOTHERMAL LOOP 4 START/STOP

L

H

AI - LOOP WATER DIFFERENTIAL PRESSURE

SEQUENCE OF OPERATION - EXHAUST FAN - COOLING (TYPICAL OF 2)

RUN CONDITIONS - SCHEDULED:

THE UNIT SHALL BE ENABLED ACCORDING TO A USER DEFINABLE TIME

SCHEDULE IN THE FOLLOWING MODES:

• OCCUPIED MODE: THE UNIT SHALL MAINTAIN A ZONE TEMPERATURE

COOLING SETPOINT OF 78°F (ADJ.).

• UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN A

ZONE TEMPERATURE COOLING SETPOINT OF 85°F (ADJ.).

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE

COOLING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).

FAN:

THE FAN SHALL RUN ANYTIME THE ZONE TEMPERATURE RISES BELOW

COOLING SETPOINT, UNLESS SHUTDOWN ON SAFETIES. THE FAN SPEEDS

SHALL BE INDEXED AS FOLLOWS:

• LOW SPEED SHALL RUN ANYTIME THE ZONE

TEMPERATURE RISES ABOVE SETPOINT.

• MEDIUM SPEED SHALL RUN ANYTIME THE ZONE

TEMPERATURE RISES FURTHER ABOVE SETPOINT BY A USER DEFINABLE

AMOUNT (ADJ.).

• HIGH SPEED SHALL RUN ANYTIME THE ZONE TEMPERATURE RISES EVEN

FURTHER ABOVE SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.).

EXHAUST AIR DAMPER:

THE EXHAUST AIR DAMPER SHALL OPEN ANYTIME THE UNIT RUNS AND

SHALL CLOSE ANYTIME THE UNIT STOPS. THE EXHAUST AIR DAMPER SHALL

CLOSE 30 SEC (ADJ.) AFTER THE FAN STOPS.

FILTER DIFFERENTIAL PRESSURE MONITOR:

THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS

THE FILTER.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• FILTER CHANGE REQUIRED: FILTER DIFFERENTIAL PRESSURE EXCEEDS

A USER DEFINABLE LIMIT (ADJ.).

DAMPER STATUS:

THE FAN SHALL BE ENABLED AFTER THE DAMPER STATUS HAS PROVEN.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• DAMPER FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED.

• DAMPER IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN.

FAN STATUS:

THE CONTROLLER SHALL MONITOR THE FAN STATUS.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

• FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

• FAN RUNTIME EXCEEDED: FAN STATUS RUNTIME EXCEEDS A USER

DEFINABLE LIMIT (ADJ.).

BI - EXHAUST AIR DAMPER STATUS

N.C.

S

BO - EXHAUST AIR DAMPER

BO - FAN LOW SPEED

BO - FAN HIGH SPEED

BO - FAN MEDIUM SPEED

CT

BI - FAN STATUS

EA

AI - ZONE TEMP

T

M

L H

AI - FILTER DIFFERENTIAL PRESSURE

TYPICAL OF EF-8

GTS

GTS

AI - LOOP WATER SUPPLY TEMP

BI - LOOP WATER FLOW STATUS

GTS

GTS

T

T

AI - LOOP WATER RETURN TEMP

BO - LOOP WATER PUMP 5 START/STOP

AO - LOOP WATER PUMP 5 VFD SPEED

BI - LOOP WATER PUMP 5 VFD FAULT

GTS

GTS

AI - LOOP WATER DIFFERENTIAL PRESSURE

H

L

VFD

VFD

P5

P6

M

M

CT

CT

BI - LOOP WATER PUMP 5 STATUS

SEQUENCE OF OPERATION - LOOP MONITOR AND PUMPS (TYPICAL OF 2)

WATER SOURCE HEAT PUMP LOOP MONITOR - RUN CONDITIONS:

THE LOOP MONITOR SHALL RUN WHENEVER:

• ANY ZONE IS OCCUPIED.

• OR A DEFINABLE NUMBER OF UNOCCUPIED ZONES NEED HEATING OR

COOLING.

THE FOLLOWING LOOP WATER CONDITIONS SHALL BE MONITORED:

• FLOW STATUS.

• SUPPLY TEMPERATURE.

• RETURN TEMPERATURE.

ALARMS AND A HEAT PUMP SHUTDOWN SIGNAL SHALL BE GENERATED

UPON ANY OF THE FOLLOWING LOOP WATER CONDITIONS:

• NO LOOP FLOW.

• HIGH LOOP WATER SUPPLY TEMP SHUTDOWN: IF THE LOOP WATER

SUPPLY TEMPERATURE IS GREATER THAN 92°F (ADJ.).

• LOW LOOP WATER SUPPLY TEMP SHUTDOWN: IF THE LOOP WATER

SUPPLY TEMPERATURE IS LESS THAN 58°F (ADJ.).

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• HIGH LOOP WATER SUPPLY TEMP: IF THE LOOP WATER SUPPLY

TEMPERATURE IS GREATER THAN 90°F (ADJ.).

• LOW LOOP WATER SUPPLY TEMP: IF THE LOOP WATER SUPPLY

TEMPERATURE IS LESS THAN 60°F (ADJ.).

LOOP WATER PUMP LEAD/LAG OPERATION:

THE TWO LOOP WATER PUMPS SHALL OPERATE IN A LEAD/LAG FASHION.

• THE LEAD PUMP SHALL RUN FIRST.

• ON FAILURE OF THE LEAD PUMP, THE LAG PUMP SHALL RUN AND THE

LEAD PUMP SHALL TURN OFF.

• THE VFD WILL CONTROL THE MINIMUM FLOW TO BE 40% OF THE

MAXIMUM FLOW

THE DESIGNATED LEAD PUMP SHALL ROTATE UPON ONE OF THE

FOLLOWING CONDITIONS (USER SELECTABLE):

• MANUALLY THROUGH A SOFTWARE SWITCH

• IF PUMP RUNTIME (ADJ.) IS EXCEEDED

• DAILY

• WEEKLY

• MONTHLY

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• LOOP WATER PUMP 1

• FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

• RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

• RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE

LIMIT.

• VFD FAULT.

• LOOP WATER PUMP 2

• FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

• RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

• RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE

LIMIT.

• VFD FAULT.

LOOP WATER DIFFERENTIAL PRESSURE CONTROL:

THE CONTROLLER SHALL MEASURE LOOP WATER DIFFERENTIAL

PRESSURE AND MODULATE THE LOOP WATER PUMP VFDS IN SEQUENCE

TO MAINTAIN ITS LOOP WATER DIFFERENTIAL PRESSURE SETPOINT. THE

FOLLOWING SETPOINTS ARE RECOMMENDED VALUES. ALL SETPOINTS

SHALL BE FIELD ADJUSTED DURING THE COMMISSIONING PERIOD TO MEET

THE REQUIREMENTS OF ACTUAL FIELD CONDITIONS.

THE CONTROLLER SHALL MODULATE LOOP WATER PUMP SPEEDS TO

MAINTAIN A LOOP WATER DIFFERENTIAL PRESSURE OF 12LBF/IN2 (ADJ.).

THE VFD MINIMUM SPEED SHALL NOT DROP BELOW 40% FLOW (ADJ.).

ON DROPPING LOOP WATER DIFFERENTIAL PRESSURE, THE VFDS SHALL

STAGE ON AND RUN TO MAINTAIN SETPOINT AS FOLLOWS:

• THE CONTROLLER SHALL MODULATE THE LEAD VFD TO MAINTAIN

SETPOINT.

• IF THE LEAD VFD SPEED IS GREATER THAN A SETPOINT OF 90% (ADJ.),

THE LAG VFD SHALL STAGE ON.

• THE LAG VFD SHALL RAMP UP TO MATCH THE LEAD VFD SPEED AND

THEN RUN IN UNISON WITH THE LEAD VFD TO MAINTAIN SETPOINT.

ON RISING LOOP WATER DIFFERENTIAL PRESSURE, THE VFDS SHALL

STAGE OFF AS FOLLOWS:

• IF THE VFD SPEEDS THEN DROPS BACK TO 60% (ADJ.) BELOW SETPOINT,

THE LAG VFD SHALL STAGE OFF.

• THE LEAD VFD SHALL CONTINUE TO RUN TO MAINTAIN SETPOINT.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• HIGH LOOP WATER DIFFERENTIAL PRESSURE: IF THE LOOP WATER

DIFFERENTIAL PRESSURE IS 25% (ADJ.) GREATER THAN SETPOINT.

• LOW LOOP WATER DIFFERENTIAL PRESSURE: IF THE LOOP WATER

DIFFERENTIAL PRESSURE IS 25% (ADJ.) LESS THAN SETPOINT.

BI - LOOP WATER PUMP 6 STATUS

BO - LOOP WATER PUMP 6 START/STOP

AO - LOOP WATER PUMP 6 VFD SPEED

BI - LOOP WATER PUMP 6 VFD FAULT

H W

C W

TAI - DOM. HW TEMP

EXISTING

MIXING VALVE

T W

PROVIDE NEW TEMPERATURE SENSOR ON THE TEMPERED WATER

DOWNSTREAM OF THE MIXING VALVE. MONITOR TEMPERATURE.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• HIGH WATER TEMPERATURE: IF WATER TEMPERATURE IS

ABOVE 125 DEG.

• LOW WATER TEMPERATURE: IF WATER TEMPERATURE IS

BELOW 100 DEG.

SEQUENCE OF OPERATION - TYPICAL 1

www.f-w.com Engineers | Architects | Surveyors | Scientists

GROUP

DATE:

DRAWN:

REVIEWED:

SHEET TITLE:

SHEET NUMBER:

PROJECT NO.:

PROJECT:

100 WALNUT STREET, SUITE 200

PEORIA, ILLINOIS 61602

(309) 689-9888 / info@f-w.com

ISSUE:

# DATE: DESCRIPTION:

DESIGNED:

/2

/2

:2 :4

A

M M5.1

CONTROLS

DIAGRAMS

LDE

WCR

0241027.00

9418.00 - HONEY

CREEK RESORT

BUILDING

AUTOMATION

SYSTEM

IMPROVEMENTS

12633 Resort Dr, Moravia, IA 52571

09/20/2024

WCR

PERMIT SET

SCALE: No Scale

AIR SOURCE HEAT PUMP CONTROLS

SCALE: No Scale

GEOTHERMAL LOOP PUMP CONTROLS

SCALE: No Scale

EXHAUST FAN - COOLING CONTROLS

SCALE: No Scale

BUILDING LOOP PUMP CONTROLS

SCALE: No Scale

DOMESTIC WATER TEMPERATURE CONTROLS

Fan Runtime Exceeded x

Fan in Hand x

Fan Failure x

Exhaust Air Damper in Hand x

Exhaust Air Damper Failure x

Filter Change Required x

High Zone Temp x

Schedule x

Cooling Setpoint x x x

Exhaust Air Damper x x x

Fan Low Speed x x x

Fan High Speed x x x

Fan Medium Speed x x x

Fan Status x x x

Exhaust Air Damper Status x x x

Filter Differential Pressure x x x

Zone Temp x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

Low Discharge Air Temp x

High Discharge Air Temp x

Filter Change Required x

Low Zone Temp x

High Zone Temp x

Cooling Setpoint x x

Heating Setpoint x x

Schedule x

Emergency Shutdown x x x x

Zone Carbon Dioxide PPM Setpoint x x x

Heating Enable x x x

Compressor Enable x x x

Smoke Detector x x x x

Zone Override x x x

Discharge Temp x x x

Filter Differential Pressure x x x

Zone Setpoint Adjust x x x

Zone Temp x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

Loop Water Pump 4 Runtime Exceeded x

Loop Water Pump 4 Running in Hand x

Loop Water Pump 4 Failure x

Loop Water Pump 3 Runtime Exceeded x

Loop Water Pump 3 Running in Hand x

Loop Water Pump 3 Failure x

Low Loop Water Differential Pressure x

High Loop Water Differential Pressure x

Loww Loop Water Supply Temp x

High Loop Water Supply Temp x

Low Loop Water Supply Temp Shutdown x

High Loop Water Supply Temp Shutdown x

Loop Water Differential Pressure Setpoint x x

Outside Air Temp x x

Loop Water Pump 4 Start/stop x x

Loop Water Pump 3 Start/Stop x x

Loop Water Pump 4 Status x x x

Loop Water Pump 3 Status x x x

Loop Water Pump 4 VFD Fault x x x

Loop Water Pump 3 VFD Fault x x x

Loop Water Pump 4 VFD Speed x x x

Loop Water Pump 3 VFD Speed x x x

Loop Water Differential Pressure x x x

Loop Water Supply Temp x x x

Loop Water Return Temp x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

Loop Water Pump 5 Runtime Exceeded x

Loop Water Pump 5 Running in Hand x

Loop Water Pump 5 Failure x

Loop Water Pump 4 Runtime Exceeded x

Loop Water Pump 4 Running in Hand x

Loop Water Pump 4 Failure x

Low Loop Water Differential Pressure x

High Loop Water Differential Pressure x

Loww Loop Water Supply Temp x

High Loop Water Supply Temp x

Low Loop Water Supply Temp Shutdown x

High Loop Water Supply Temp Shutdown x

No Loop Flow x

Loop Water Differential Pressure Setpoint x x

Outside Air Temp x x

Loop Water Pump 5 Start/stop x x

Loop Water Pump 4 Start/Stop x x

Loop Water Pump 5 Status x x x

Loop Water Pump 4 Status x x x

Loop Water Pump 5 VFD Fault x x x

Loop Water Pump 4 VFD Fault x x x

Loop Water Flow Status x x

Loop Water Pump 5 VFD Speed x x x

Loop Water Pump 4 VFD Speed x x x

Loop Water Differential Pressure x x x

Loop Water Supply Temp x x x

Loop Water Return Temp x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

Domestic HW Low Temp x

Domestic HW High Temp x

Domestic HW Temp x x x

POINT NAME AI AO BI BO AV BV Loop Sched Trend Alarm Show on Graphic

HARDWARE POINTS SOFTWARE POINTS

SEQUENCE OF OPERATION - EXHAUST FAN - ON/OFF (TYPICAL OF 1)

RUN CONDITIONS - SCHEDULED:

THE FAN SHALL RUN ACCORDING TO A USER DEFINABLE SCHEDULE.

FAN:

THE FAN SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.

EXHAUST AIR DAMPER:

THE EXHAUST AIR DAMPER SHALL OPEN ANYTIME THE UNIT RUNS AND

SHALL CLOSE ANYTIME THE UNIT STOPS. THE EXHAUST AIR DAMPER SHALL

CLOSE 30 SEC (ADJ.) AFTER THE FAN STOPS.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• DAMPER FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED.

• DAMPER IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN.

DAMPER STATUS:

THE FAN SHALL BE ENABLED AFTER THE DAMPER STATUS HAS PROVEN.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• DAMPER FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED.

• DAMPER IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN.

FAN STATUS:

THE CONTROLLER SHALL MONITOR THE FAN STATUS.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

• FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

• FAN RUNTIME EXCEEDED: FAN STATUS RUNTIME EXCEEDS A USER

DEFINABLE LIMIT (ADJ.).

CT

BI - FAN STATUS

BI - EXHAUST AIR DAMPER STATUS

N.C.

S

BO - EXHAUST AIR DAMPER

BO - FAN START/STOP

EA

M

TYPICAL OF EF-6

SEQUENCE OF OPERATION - MAKEUP AIR UNIT - SUPPLY AIR TEMP - HYDRONIC HEATING/COOLING (TYPICAL OF 4)

RUN CONDITIONS - SCHEDULED:

THE UNIT SHALL RUN BASED UPON AN OPERATOR ADJUSTABLE SCHEDULE.

EMERGENCY SHUTDOWN:

THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN EMERGENCY SHUTDOWN SIGNAL.

FREEZE PROTECTION:

THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A FREEZESTAT STATUS.

SMOKE DETECTION:

THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A SMOKE DETECTOR STATUS.

DEMAND LIMITING - SETPOINT ADJUST:

TO LOWER POWER CONSUMPTION, THE SUPPLY AIR TEMPERATURE SETPOINT SHALL AUTOMATICALLY RELAX (RAISED FOR COOLING; LOWERED FOR HEATING) WHEN THE FACILITY POWER CONSUMPTION EXCEEDS DEFINABLE THRESHOLDS. THE AMOUNT

OF RELAXATION SHALL BE ACCOMPLISHED BY ONE OF THE FOLLOWING METHODS:

• THE SUPPLY AIR TEMPERATURE SETPOINT SHALL RELAX BY 2°F (ADJ.) FOR EACH DEMAND THRESHOLD EXCEEDED.

• THE SETPOINTS IN THE ZONES SUPPLIED BY THIS UNIT SHALL BE RELAXED AS SPECIFIED IN THE SEQUENCE OF OPERATIONS FOR

THE ZONES. THIS SHALL IN TURN RELAX THE UNIT'S SUPPLY AIR TEMPERATURE SETPOINT BY A USER DEFINABLE AMOUNT.

ALL SETPOINTS SHALL AUTOMATICALLY RETURN TO THEIR PREVIOUS SETTINGS WHEN THE FACILITY POWER CONSUMPTION DROPS

BELOW THE THRESHOLDS.

OUTSIDE AIR DAMPER:

THE OUTSIDE AIR DAMPER SHALL OPEN ANYTIME THE UNIT RUNS AND SHALL CLOSE ANYTIME THE UNIT STOPS. THE SUPPLY FAN SHALL START ONLY AFTER THE DAMPER STATUS HAS PROVEN THE DAMPER IS OPEN. THE OUTSIDE AIR DAMPER SHALL CLOSE

4SEC (ADJ.) AFTER THE SUPPLY FAN STOPS.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• OUTSIDE AIR DAMPER FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED.

• OUTSIDE AIR DAMPER IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN.

HEAT RECOVERY WHEEL - VARIABLE SPEED:

THE CONTROLLER SHALL MODULATE THE HEAT WHEEL FOR ENERGY RECOVERY AS FOLLOWS.

COOLING RECOVERY MODE:

THE CONTROLLER SHALL MEASURE THE HEAT WHEEL DISCHARGE AIR TEMPERATURE AND MODULATE THE HEAT WHEEL SPEED TO MAINTAIN A SETPOINT 2°F (ADJ.) LESS THAN THE UNIT SUPPLY AIR TEMPERATURE SETPOINT. THE HEAT WHEEL SHALL RUN FOR

COOL RECOVERY WHENEVER:

• UNIT RETURN AIR TEMPERATURE IS 5°F (ADJ.) OR MORE BELOW THE OUTSIDE AIR TEMPERATURE.

• AND THE UNIT IS IN A COOLING MODE.

• AND THE SUPPLY FAN IS ON.

HEATING RECOVERY MODE:

THE CONTROLLER SHALL MEASURE THE HEAT WHEEL DISCHARGE AIR TEMPERATURE AND MODULATE THE HEAT WHEEL SPEED TO MAINTAIN A SETPOINT 2°F (ADJ.) GREATER THAN THE UNIT SUPPLY AIR TEMPERATURE SETPOINT. THE HEAT WHEEL SHALL RUN

FOR HEAT RECOVERY WHENEVER:

• UNIT RETURN AIR TEMPERATURE IS 5°F (ADJ.) OR MORE ABOVE THE OUTSIDE AIR TEMPERATURE.

• AND THE UNIT IS IN A HEATING MODE.

• AND THE SUPPLY FAN IS ON.

THE HEAT WHEEL SHALL RUN IN FROST PROTECTION:

• OUTSIDE AIR TEMPERATURE DROPS BELOW 15°F (ADJ.)

• OR WHENEVER EXHAUST AIR TEMPERATURE DROPS BELOW 20°F (ADJ.).

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• HEAT WHEEL ROTATION FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

• HEAT WHEEL IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

• HEAT WHEEL RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).

• HEAT WHEEL VFD IN FAULT

SUPPLY FAN:

THE SUPPLY FAN SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN. TO PREVENT SHORT CYCLING, THE SUPPLY FAN

SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME, UNLESS SHUTDOWN ON SAFETIES.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• SUPPLY FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

• SUPPLY FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

• SUPPLY FAN RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).

EXHAUST FAN:

THE EXHAUST FAN SHALL RUN WHENEVER THE SUPPLY FAN RUNS, UNLESS SHUTDOWN ON SAFETIES.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• EXHAUST FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

• EXHAUST FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

• EXHAUST FAN RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).

(PROVIDE FOR ERV-4 AMD ERV-5 ONLY)

SUPPLY AIR TEMPERATURE SETPOINT - OUTSIDE AIR RESET:

THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE AND SHALL MAINTAIN SUPPLY AIR TEMPERATURE SETPOINT.

THE SUPPLY AIR TEMPERATURE SETPOINT SHALL RESET FOR COOLING AS FOLLOWS:

AS OUTSIDE AIR TEMPERATURE DROPS FROM 85°F (ADJ.) TO 20°F (ADJ.)

THE SUPPLY AIR TEMPERATURE SETPOINT SHALL RESET UPWARDS FROM 55°F (ADJ.) TO 65°F (ADJ.).

COOLING STAGES:

THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND MODULATE THE COIL CONTROL VALVE COOLING TO MAINTAIN ITS COOLING SETPOINT. TO PREVENT SHORT CYCLING, THERE SHALL BE A USER DEFINABLE (ADJ.) DELAY BETWEEN

STAGES, AND EACH STAGE SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.

THE COIL SHALL BE ENABLED WHENEVER:

• AND THE SUPPLY AIR TEMPERATURE IS ABOVE COOLING SETPOINT OR BELOW ITS HEATING SETPOINT.

• AND THE FAN STATUS IS ON.

PREFILTER DIFFERENTIAL PRESSURE MONITOR:

THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE PREFILTER. PROVIDE TWO NEW SENSORS.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• PREFILTER CHANGE REQUIRED: PREFILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINABLE LIMIT (ADJ.).

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• FINAL FILTER CHANGE REQUIRED: FINAL FILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINABLE LIMIT (ADJ.).

BI - EXHAUST FAN STATUS

BO - EXHAUST FAN START/STOP

EA

M

CT

STARTER

EF

S

BO - OUTSIDE AIR DAMPER

BI - OUTSIDE AIR DAMPER STATUS

N.C.

BI - SMOKE DETECTORBI - FREEZESTAT

T

M

STARTER

CT

BI - SUPPLY FAN STATUS

BO - SUPPLY FAN START/STOP

OA SA

T

AI - SUPPLY AIR TEMP

H L

AI - PREFILTER DIFFERENTIAL PRESSURE

M

RAEA

VFDCT

BO - HEAT WHEEL START/STOP

BI - HEAT WHEEL STATUS

AO - HEAT WHEEL VFD SPEED

BI - HEAT WHEEL VFD FAULT

CH

H L

AI - PREFILTER DIFFERENTIAL PRESSURE

AO - HEATING/COOLING VALVE

M

CHS

CHR

(TYPICAL OF ERV-2, ERV-3, ERV-4 AND ERV-5)

ERV-4, ERV-5 ONLY

THE FOLLOWING ARE CONTROL SEQUENCES TO COMMISSION IN THE FIELD, WITHOUT BAS

MONITORING. REPORT TO THE ENGINEER IF ANY SEQUENCE CANNOT BE PERFORMED DUE TO

INOPERABLE EQUIPMENT OR SENSORS:

DOMESTIC WATER CIRCULATING PUMPS (TYPICAL OF 1):

AN EXISTING STRAP ON THERMOSTAT ENERGIZES THE PUMP WHEN THE RETURN WATER

TEMPERATURE IS BELOW SETPOINT.

LAUNDRY DRYER (TYPICAL OF 4):

WHEN THE DRYER OPERATES, ITS RESPECTIVE OUTSIDE AIR DAMPER OPENS.

ELEVATOR HOISTWAY DAMPER (TYPICAL OF 1):

WHEN THE FIRE ALARM SMOKE DETECTOR IN THE ELEVATOR HOISTWAY OR THE ELEVATOR

LOBBY IS ACTIVED, THE ELEVATOR HOISTWAY DAMPER WILL OPEN

THE FOLLOWING ARE CONTROL SEQUENCES TO COMMISSION IN THE FIELD AND NEED BAS

MONITORING:

SUMP PUMPS (TYPICAL OF 2)

MONITOR THE EXISTING HIGH LEVEL ALARM CONTACT PROVIDED. PROVIDE ALARM WHEN THE

HIGH LEVEL ALARM STATE IS INDICATED.

MISCELLANEOUS CONTROL SEQUENCES AND POINTS

H

H L T

DX HGR

CT

T

OA

M

N.O.

N.C.

T

DA

M

SEQUENCE OF OPERATION - RTU-1 (TYPICAL OF 1)

RUN CONDITIONS - SCHEDULED:

THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES:

• OCCUPIED MODE: THE UNIT SHALL MAINTAIN

• A 74°F (ADJ.) COOLING SETPOINT

• A 70°F (ADJ.) HEATING SETPOINT.

• UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN

• A 85°F (ADJ.) COOLING SETPOINT.

• A 55°F (ADJ.) HEATING SETPOINT.

ALARMS SHALL BE PROVIDED AS FOLLOWS:

• HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT BY A USER DEFINABLE

AMOUNT (ADJ.).

• LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A USER DEFINABLE

AMOUNT (ADJ.).

DEMAND LIMITING - ZONE SETPOINT OPTIMIZATION:

TO LOWER POWER CONSUMPTION, THE ZONE SETPOINTS SHALL AUTOMATICALLY RELAX WHEN THE FACILITY POWER CONSUMPTION EXCEEDS DEFINABLE THRESHOLDS. THE AMOUNT OF RELAXATION SHALL BE INDIVIDUALLY CONFIGURABLE FOR EACH ZONE. THE ZONE SETPOINTS SHALL AUTOMATICALLY RETURN TO THEIR PREVIOUS

SETTINGS WHEN THE FACILITY POWER CONSUMPTION DROPS BELOW THE THRESHOLDS.

ZONE SETPOINT ADJUST:

THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND COOLING SETPOINTS AT THE

ZONE SENSOR.

ZONE OPTIMAL START:

THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START-UP. THIS ALGORITHM SHALL MINIMIZE THE UNOCCUPIED WARM-UP OR COOL-DOWN PERIOD WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE START OF

SCHEDULED OCCUPIED PERIOD.

ZONE UNOCCUPIED OVERRIDE:

A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE EXPIRATION OF THIS TIME, CONTROL OF THE

UNIT SHALL AUTOMATICALLY RETURN TO THE SCHEDULE.

EMERGENCY SHUTDOWN:

THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN EMERGENCY SHUTDOWN SIGNAL.

SMOKE DETECTION:

THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A SMOKE DETECTOR STATUS.

FAN…