RFB927950-01 - Project Manual.pdf
PDF 21 MB Posted
- Attached to
- HHS WRC Campus Utility Decentralization Phase 5
- Solicitation number
- RFB927950-01
- Issued by
- Dallas County, Iowa
About this file
This is a Project Manual and Hazardous Building Materials Survey Report prepared for the Iowa Department of Administrative Services (IDAS) regarding the WRC Decentralization Phase 5 tunnel abandonment project at Woodward Resource Center in Woodward, Iowa. The project, identified as IDAS Project #9279.50 and SH Project #2240007040, involves the demolition of utilities in tunnels, rerouting of water lines, and filling of tunnels with grout. The survey was conducted on October 10-11, 2024, and issued for construction on April 24, 2026. The project manual includes comprehensive specifications across multiple divisions including demolition, concrete work, waterproofing, plumbing, HVAC, and electrical work, with professional engineering certifications provided by licensed Professional Engineers Matthew A. Mettemeyer (License #20396), John D. Baumhover (License #25737), and Kevin J. Bruxvoort (License #19927). Construction is anticipated to begin July 6, 2026, and conclude June 30, 2028.
The hazardous building materials survey identified substantial asbestos-containing materials (ACM) throughout the tunnel system, with 50 samples collected and analyzed, resulting in 44 samples testing positive for asbestos content exceeding 1 percent. The identified ACM includes thermal system insulation (TSI) on pipes ranging from 1 to 16 inches in diameter, with asbestos content ranging from 7 percent to 80 percent, predominantly consisting of chrysotile and amosite varieties in quantities totaling approximately 11,000 linear feet and 200 mechanical fittings. No lead-based paint was identified during the inspection, and no other hazardous building materials were detected. The report recommends retention of a State of Iowa certified abatement contractor for proper removal and disposal in accordance with NESHAP and OSHA regulations, with notification required to the Iowa Department of Natural Resources at least 10 business days prior to abatement activities. Contractors must exercise caution during construction activities and comply with federal, state, and local regulations regarding hazardous materials handling and disposal.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFB927950-01 - Drawings.pdf | ||
| RFB927950-01 - Bid Form.pdf | ||
| RFB927950-01 - Notice to Bidders.pdf | ||
| RFB927950-01 - Addendum #1.pdf | ||
| 1390845-event.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
THIS PAGE
INTENTIONALLY
LEFT BLANK
IDAS - WRC Decentralization Ph
5- Tunnel Abandonment
IDAS Project # 9279.50
SH Project # 2240007040
Issued for Construction
04-24-2026
Certifications Page
00 0105 - 1
SECTION 00 0105
CERTIFICATIONS PAGE
STATE OF IOWA
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly licensed Professional Engineer under the laws of the State of Iowa.
Signature Date
Printed or typed name: Matthew A. Mettemeyer
License Number: 20396
My license renewal date is: 12-31-2026
Pages, Sheets, or Divisions covered by this Seal:
Divisions 02, 03, and 07
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly licensed Professional Engineer under the laws of the State of Iowa.
Signature Date
Printed or typed name: John D. Baumhover License Number: 25737 My license renewal date is: 12-31-2026 Pages, Sheets, or Divisions covered by this Seal: Division 22 and 23
I hereby certify that this engineering document was prepared by me or under my direct personal supervision and that I am a duly licensed Professional Engineer under the laws of the State of Iowa.
Signature Date
Printed or typed name: Kevin J. Bruxvoort License Number: 19927 My license renewal date is: 12-31-2027 Pages, Sheets, or Divisions covered by this Seal: Division
04/27/2026
04/27/2026
04/27/2026
PROJECT 9279.50 TABLE OF CONTENTS 00 0110 - 1
SECTION 00 0110
TABLE OF CONTENTS
PROCUREMENT AND CONTRACTING REQUIREMENTS
1.01 DIVISION 00 – PROCUREMENT AND CONTRACTING REQUIREMENTS
A. 00 0101 Project Title Page B. 00 0105 Certifications Page
C. 00 0110 Table of Contents D. 00 0115 List of Drawing Sheets E. 00 0116 Bid Submittal Checklist F. 00 1113 Notice to Bidders
G. 00 2113 Instructions to Bidders H. 00 2113.01 IMPACS Electronic Procurement System Instructions I. 00 2113.02 Sample Contractor Certificate of Insurance J. 00 3113 Preliminary Schedule K. 00 3126 Existing Hazardous Material Information
L. 00 3143 Permit Application M. 00 4116 Bid Form N. 00 4116.01 Non Discrimination Clause Information O. 00 4116.02 Targeted Small Business Information
P. 00 4313 Bid Security Forms Q. 00 5200 Agreement Form R. 00 6000 Payment Bond and Performance Bond Forms
SPECIFICATIONS
1.02 DIVISION 01 – GENERAL REQUIREMENTS
A. 01 1200 Contract Summary B. 01 2500 Substitution Procedures C. 01 2600 Contract Modification Procedures D. 01 2900 Payment Procedures
E. 01 3100 Project Management and Coordination F. 01 3100.01 Web Based Construction Management G. 01 3200 Construction Progress Documentation H. 01 3300 Submittal Procedures I. 01 4000 Quality Requirements
J. 01 5000 Temporary Facilities and Controls K. 01 6000 Product Requirements L. 01 7300 Execution M. 01 7700 Closeout Procedures
N. 01 9000 Asbestos Abatement Specification
1.03 DIVISION 02 – EXISTING CONDITIONS
A. 02 4100 Demolition
PROJECT 9279.50 TABLE OF CONTENTS 00 0110 - 2
1.04 DIVISION 03 – CONCRETE
A. 03 3000 Cast-In-Place Concrete
1.05 DIVISION 07 – THERMAL AND MOISTURE PROTECTION
A. 07 1300 Sheet Waterproofing
1.06 DIVISION 22 – PLUMBING
A. 22 0500 Common Work Results for Plumbing B. 22 0523 General-Duty Valves for Plumbing Piping
C. 22 0529 Hangers and Supports for Plumbing Piping and Equipment D. 22 0700 Plumbing Insulation E. 22 1116 Domestic Water Piping
1.07 DIVISION 23 – HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)
A. 23 0500 Common Work Results for HVAC B. 23 1113 Facility Fuel-Oil Piping C. 23 2213 Steam and Condensate Heating Piping
1.08 DIVISION 26 – ELECTRICAL
A. 26 0505 Selective Demolition for Electrical
END OF SECTION
4503 East 50th Street, Suite 800, Des Moines, Iowa 50317
515.981.4528 | oneatlas.com
L I M I T E D H A Z A R D O U S B U I L D I N G M A T E R I A L S S U R V E Y
PREPARED FOR:
Iowa Department of Administrative Services 109 SE 13th Street
Des Moines, Iowa 50319
PROJECT LOCATION:
Woodward Resource Center – Phase 4 Decentralization Project #9279 Tunnel System
1251 334th Street Woodward, Iowa
Project Date: October 10 and 11, 2024
Report Date: December 2, 2024
Atlas Project ID: 204BS07475
PREPARED BY:
Atlas Technical Consultants LLC 4503 East 50th Street, Suite 800
Des Moines, IA 50317 i
December 2, 2024
Ms. Jennifer Kleene Iowa Department of Administrative Services 109 SE 13th Street Des Moines, IA 50319
Re: Hazardous Building Materials Survey Report – Tunnel System
Woodward Resource Center – Phase 4 Decentralization Project #9279 1251 334th Street Woodward, Iowa 50276
Atlas Project Number: 204BS07475
Atlas is pleased to submit the attached Hazardous Building Materials Survey Report for the above-referenced site. This report includes procedures, methodologies and analytical laboratory results.
Atlas appreciates the opportunity to perform these services for the Iowa Department of Administrative Services (IDAS), and we look forward to working with you in the future. If you need any assistance with the implementation of the recommendations contained in this report, please feel free to give us a call at (515) 981-4528 and we will respond promptly to your needs.
Sincerely, ATLAS TECHNICAL CONSULTANTS LLC
Eric Brown Steve Hudson, MS, CIH Iowa Inspector Senior Project Manager
(515) 981-4528 (402) 670-3842
T A B L E O F C O N T E N T S
LETTER OF TRANSMITTAL ............................................................................................... i
1.0 SCOPE OF SERVICES
2.0 GENERAL SITE CONDITIONS
3.0 ASBESTOS SURVEY
3.1 Regulation Review
3.2 Homogeneous Areas
3.3 Sampling Strategy
3.4 Laboratory Analytical Results
3.5 Suspect Asbestos-Containing Materials
4.0 LEAD PAINT CHIP TESTING
4.1 Inspection
4.2 Lead Paint Testing
5.0 HAZARDOUS MATERIALS ASSESSMENT
6.0 CONCLUSIONS
6.1 Asbestos
6.2 Lead
6.3 Hazardous Building Materials
7.0 ASSUMPTIONS AND LIMITATIONS
APPENDICES
APPENDIX A: Asbestos Analytical Report and Chain of Custody
APPENDIX B: Asbestos Photo Log
APPENDIX C: Inspector Accreditations
Hazardous Building Materials Survey Report – Tunnel System
Woodward Rescource Center Phase 4 Decentralization Project #9279
December 2, 2024 Project No. 204BS07475
H A Z A R D O U S B U I L D I N G M A T E R I A L S
S U R V E Y R E P O R T
Woodward Resource Center – Tunnel System Phase 4 Decentralization Project #9279
1251 334th Street Woodward, Iowa
Atlas Project Number: 204BS07475
1.0 SCOPE OF SERVICES
The purpose of this project was to perform a survey to identify hazardous building materials at the above-referenced property.
Atlas provided a representative asbestos survey in accordance with the referenced agreement and as outlined below:
1. Review any existing hazardous building material survey reports relating to the site, if available.
2. Identify suspect asbestos-containing materials (ACM), surface coatings potentially containing lead paint, and hazardous building materials throughout the tunnel system.
3. Collect and analyze bulk samples of suspect asbestos containing materials and collect paint chip samples from representative surface coatings potentially containing lead-based or lead-containing paint.
4. Provide laboratory analysis of collected samples.
5. Provide a report of findings with copies and interpretation of analytical results and identifying the locations of asbestos-containing materials, lead paint, and hazardous building materials.
2.0 GENERAL SITE CONDITIONS
The survey was conducted in the tunnel system at the Woodward Resource Center located at 1251 334th Street in Woodward, Iowa.
3.0 ASBESTOS SURVEY
On October 10 and 11, 2024, the Tunnel System was inspected for ACMs by inspector Eric Brown of Atlas. Mr. Brown has completed the requisite training for asbestos accreditation as inspectors at a state approved training provider under TSCA Title II. Mr. Brown’s State of Iowa Inspector number is 24-11418.
The Tunnel System was visually inspected for the presence of suspect ACMs. Materials that were hidden, not accessible, or when sampled would damage the integrity of the structure, were not sampled as part of this survey. Materials visibly identified as non-asbestos (fibrous glass, foam rubber, wood, etc.) were not sampled. The asbestos survey consisted of three basic steps: 1) a visual inspection of the proposed work areas; 2) a determination of homogeneous areas with suspect surfacing, thermal system insulation, and miscellaneous materials; and 3) sampling accessible, friable and non-friable, suspect materials.
3.1 Regulation Review
The United States Environmental Protection Agency (USEPA) qualifies ACM as materials with an asbestos content greater than 1%. The following definitions are taken from Section 61.141 of Subpart M, Part 61 of Title 40: Protection of Environment of the Code of Federal Regulations
(CFR).
• “Category I non-friable ACM” is defined as asbestos-containing packings, gaskets, resilient floor covering, and asphalt roofing products containing more than 1% asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763, section 1, Polarized Light Microscopy (PLM).
• “Category II non-friable ACM” is defined as any material, excluding Category I non-friable ACM, containing more than 1% asbestos as determined using the methods specified in appendix E, subpart E, 40 CFR part 763, section 1, PLM that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.
• “Friable asbestos material” is defined as any material containing more than 1% asbestos as determined using the methods specified in appendix E, subpart E, 40 CFR part 763, section 1, PLM that when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. If the asbestos content is less than 10% as determined by a method other than point counting by PLM, verify the asbestos content by point counting using PLM.
3.2 Homogeneous Areas
Prior to sampling, homogeneous areas were identified in order to facilitate a sampling strategy. A homogeneous sampling area can be described as one or more areas with suspect material similar in appearance and texture that have the same installation date and function. The actual number of samples collected from each homogeneous sampling area may vary, dependent upon material type and the professional judgment of the inspector.
3.3 Sampling Strategy
The sampling strategy incorporated Asbestos Hazard Emergency Response Acts (AHERA) requirements, quantities of suspect material, and the inspector’s judgment to aid in the identification of suspect asbestos-containing materials. If the analytical results indicated that all the samples collected per homogeneous area did not contain asbestos, then the homogeneous area (material) was considered non-asbestos-containing. However, if the analytical results of one or more of the samples collected per homogeneous area indicated that asbestos was present in quantities greater than one percent asbestos (as defined by EPA), all of the homogeneous area (material) was treated as an asbestos-containing material regardless of any other analytical results. Materials which were visually determined to be non-asbestos (i.e. fibrous glass, foam rubber, etc.) by the accredited inspector were not required to be sampled. Actual collection of a bulk asbestos sample involves physically removing approximately one square inch (1 in2) of material and placing it in an airtight sample container. Sample containers were marked with a unique identification number, which was documented in the field notes.
3.4 Laboratory Analytical Results
A total of 50 samples were collected from building materials suspected of containing asbestos. The samples were submitted under chain of custody to EMSL Analytical, Inc. (EMSL) located at 200 Route 130 North in Cinnaminson, New Jersey, for analysis by polarized light microscopy (PLM) with dispersion staining techniques per the USEPA Method for the Determination of Asbestos in Bulk Building Materials (600/R-93-116). The percentage of asbestos, if applicable, was established by microscopic visual estimation. EMSL is an accredited laboratory by the National Voluntary Laboratory Accreditation Plan (NVLAP) No. 101048-0. Any material that contains greater than one percent (>1%) asbestos is considered an ACM and must be handled according to Occupational Safety and Health Administration (OSHA), USEPA, and all applicable state and local regulations.
Laboratory test results are provided in Appendix A.
3.5 Suspect Asbestos-Containing Materials
The following table contains a list of suspect asbestos containing materials sampled:
T A B L E 1 : S U S P E C T A S B E S T O S M A T E R I A L S
Material Location Sample Number
TSI Largest Pipe 16” Diameter Run Intersection with Birches/Oak/Power Plant T-1
TSI Largest Pipe 16” Diameter Run Intersection w/medical T-2
TSI Largest Pipe 16” Diameter Run Intersection of Orchard & Cedar T-3
TSI 6” diameter pipe run Intersection with Birches/Oak/Power Plant T-4
TSI 6” diameter pipe run Intersection w/medical T-5
TSI 6” diameter pipe run Intersection of Orchard & Cedar T-6
TSI-Aircell Intersection w/medical T-7
TSI Largest Pipe 16” Diameter Elbow Intersection of Orchard & Cedar T-8
TSI Largest Pipe 16” Diameter Elbow Intersection of Orchard & Cedar T-9
TSI Largest Pipe 16” Diameter Elbow Intersection of Orchard & Cedar T-10
TSI Unmarked pipe located above hot water pipe
Intersection of Orchard & Cedar T-11
TSI High Pressure Steam Elbow Tunnel Intersection with Myers T-12
TSI Hot Water Elbow 200 ft from welder’s access hatch T-13
TSI Hot Water Elbow 200 ft from welder’s access hatch T-14
TSI Hot Water Elbow 200 ft from welder’s access hatch T-15
TSI – Unmarked Pipe Run 200 ft from welder’s access hatch T-16
TSI - Aircell Intersection with Myers branch tunnel T-17
TSI High Pressure Steam Elbow Larches Tunnel End T-18
TSI Hot Water Elbow Larches Tunnel End T-19
TSI – Aircell Myers Tunnel End T-20
TSI Hot Water Run Under street by admin T-21
TSI – Return Steam Run Under street by admin T-22
TSI- 2” Head height mystery pipe run E-home Branch T-23
T A B L E 1 : S U S P E C T A S B E S T O S M A T E R I A L S
Material Location Sample Number
TSI- 2” Head height mystery Elbow E-home Branch T-24
TSI – 4” Pipe Elbow E-home Branch T-25
TSI – 4” Pipe Run E-home Branch T-26
TSI – 2” top pipe run Maple Branch T-27
TSI – 6” top pipe run Maple Branch T-28
TSI – 2” middle pipe run near wall Maple Branch T-29
TSI – 1” bottom pipe run Maple Branch T-30
TSI – 2” bottom pipe run near wall Maple Branch T-31
TSI – Aircelll Run Medical Branch T-32
TSI – 2” pipe run Medical Branch T-33
TSI – Larger diameter Aircelll Run Medical Branch T-34
TSI – Smaller diameter Aircelll Run Medical Branch T-35
TSI- Steam pipe Elbow Medical Branch T-36
TSI- Middle pipe Elbow Medical Branch T-37
4” diameter pipe Elbow Medical Branch T-38
Unmarked pipe adjacent to Hot water Pipe 75ft from “strange” air stack T-39
TSI – Sealant Birches Branch T-40
TSI – Aircelll 2nd pipe from wall Birches Branch T-41
2.5” pipe furthest from wall - TSI Birches Branch T-42
Low Pressure Pipe - TSI Birches Branch T-43
2.5” High Pressure Pipe - TSI Birches Branch T-44
TSI-Hot water pipe Oak Hall Branch T-45
TSI-High Pressure Steam Oak Hall Branch T-46
TSI – Low Pressure Steam Oak Hall Branch T-47
TSI – Low Pressure Steam Oak Hall Branch T-48
TSI-High Pressure Steam Oak Hall Branch T-49
TSI – Hot water Elbow Oak Hall Branch T-50
The following table is a summary of the suspect asbestos-containing materials that have been determined, through laboratory analysis, to contain asbestos:
T A B L E 2 : A S B E S T O S - C O N T A I N I N G M A T E R I A L S
Sample Number
Material Location Approx.
Quantity
Asbestos Content
T-1
TSI Low Pressure Steam 16” Diameter Run
Intersection with Birches/Oak/Power Plant
4,000 LF
40% - 65% Chrysotile T-2 Intersection w/medical
T-3 Intersection of Orchard & Cedar
T-4 TSI High Pressure Steam
6” diameter pipe run Intersection with
Birches/Oak/Power Plant
4,000 LF
70% Chrysotile
Sample Number
Material Location Approx.
Quantity
Asbestos Content
T-5 Intersection w/medical 22% Amosite
10% Chrysotile
T-6 Intersection of Orchard & Cedar 28% Amosite 7% Chrysotile
T-7 TSI – Aircell Intersection w/medical 50 LF 65% Chrysotile
T-8 TSI Low Pressure Steam
16” Diameter Elbow Intersection of Orchard & Cedar 4 MF
60% to 70% Chrysotile
T-9
T-10
T-11 TSI Unmarked Pipe located above Hot Water Pipe
Intersection of Orchard & Cedar 1,000 LF 40% Chrysotile
T-12 TSI High Pressure Steam
Elbow Tunnel Intersection with Myers 2 MF 70% Chrysotile
T-13
TSI Hot Water Elbow 200 ft from welder’s access hatch 4 MF 60% to 65% Chrysotile T-14
T-15
T-16 TSI – Unmarked Pipe
Run 200 ft from welder’s access hatch 1,000 LF 35% Chrysotile
T-17 TSI - Aircell Intersection with Myers branch tunnel 400 LF 70% Chrysotile
T-18 TSI High Pressure Steam
Elbow Larches End 50 MF 65% Chrysotile
T-19 TSI Hot Water Elbow Larches End 2 MF 60% Chrysotile
T-20 TSI - Aircell Myers End 400 LF 80% Chrysotile
T-23 TSI- 2” Head Height Unmarked Pipe Run
E-home Branch 250 LF 50% Chrysotile
T-24 TSI- 2” Head Height
Unmarked Elbow E-home Branch 4 MF
7% Amosite 55% Chrysotile
T-25 TSI – 4” Pipe Elbow E-home Branch 4 MF 60%
Chrysotile
T-26 TSI – 4” Pipe Run E-home Branch 250 LF 22% Amosite 7% Chrysotile
T-27 TSI – 2” Top Pipe Run Maple Branch 160 LF 10% Amosite
17% Chrysotile
T-28 TSI – 6” Top Pipe Run Maple Branch 160 LF 15% Amosite
20% Chrysotile
T-29 TSI – 2” Middle Pipe Run near Wall Maple Branch 160 LF
30% Amosite 20% Chrysotile
Sample Number
Material Location Approx.
Quantity
Asbestos Content
T-30 TSI – 1” Bottom pipe run Maple Branch 160 LF 33% Amosite
20% Chrysotile
T-31 TSI – 2” Bottom pipe run near wall Maple Branch 160 LF
33% Amosite 20% Chrysotile
T-32 TSI – Aircell Run Medical Branch 50 LF 65%
Chrysotile
T-33 TSI – 2” pipe run Medical Branch 50 LF 38%
Chrysotile
T-34 TSI – Larger diameter
Aircell Run Medical Branch 50 LF
70% Chrysotile
T-35 TSI – Smaller diameter
Aircell Run Medical Branch 50 LF
60% Chrysotile
T-36 TSI- Steam pipe Elbow Medical Branch 3 MF 65%
Chrysotile
T-37 TSI- Middle pipe Elbow Medical Branch 3 MF 12%
Chrysotile
T-38 4” diameter pipe Elbow Medical Branch 3 MF 7%
Chrysotile
T-39 Unmarked pipe adjacent to Hot water Pipe 75ft from strange air stack 100 LF
55% Chrysotile
T-41 TSI – Aircell 2nd pipe from wall Birches Branch 300 LF
65% Chrysotile
T-42 2.5” pipe furthest from wall - TSI Birches Branch 300 LF
40% Chrysotile
T-43 TSI – Low Pressure Pipe Birches Branch 300 LF 26% Amosite
10% Chrysotile
T-44 2.5” High Pressure Pipe -
TSI
Birches Branch 2 MF
60% Chrysotile
T-46 TSI – High Pressure
Steam Oak Hall Branch 650 LF
30% Amosite 15% Chrysotile
T-47 TSI – Low Pressure
Steam Oak Hall Branch 650 LF
25% Chrysotile
T-48 TSI – Low Pressure
Steam Oak Hall Branch 650 LF
25% Chrysotile 10%
Crocidolite
T-49 TSI-High Pressure Steam Oak Hall Branch 650 LF 60%
Chrysotile
T-50 TSI – Hot water Elbow Oak Hall Branch 2 MF 65%
Chrysotile
SF = Square Feet, LF = Linear Feet; MF = Mechanical Fitting
4.0 LEAD PAINT CHIP TESTING
Atlas collected paint chip samples from representative surface coatings that may be impacted by renovation activities.
Surface coatings that were collected were considered to be representative of materials in a homogeneous area if:
1. They exhibited similar physical characteristics (suspect materials alike in appearance, substrate, color, and time of application were tested as homogenous areas)
2. The application of the tested surface could be associated to an application of an unsampled surface.
Atlas did not identify any suspect lead containing surface coatings and therefore paint chip samples were not collected.
The USEPA has defined LBP as “paint or other surface coatings that contain lead in excess of 0.5 percent by weight (>0.5%)”. Results less than 0.5% by weight indicate that lead is not present at or above the USEPA regulatory level; however, lead may be present in lower concentrations above the laboratory detection limit in other surfaces tested and these are classified as lead-containing paint (LCP). Negative results do not mean that lead is not present.
4.1 Inspection
The disturbance and disposal of materials with surface coatings that contain lead paint are regulated by the USEPA, OSHA and the State of Iowa. The Resource Conservation and Recovery Act (RCRA) provides the USEPA with the authority to regulate the waste status of demolition or renovation debris, including lead-containing materials. Specific notification and testing requirements must be addressed prior to transporting, treating, storing, or disposing of hazardous wastes.
Construction work covered by 29 CFR 1926.62 includes any repair, renovation or other activities that disturb in-place, lead-containing materials, but does not include routine cleaning and repainting where there is insignificant damage, wear or corrosion of existing lead-containing coatings or substrates. Unless adequately protected, employee exposures to lead must not exceed airborne concentrations >50 micrograms per cubic meter (g/m3) averaged over an 8-hour period.
Occupational exposure to lead occurring in the course of construction work, including maintenance activities, painting, alteration and repairs is subject to the OSHA Lead standard (29 CFR 1926.62). The lead standard applies to any detectable concentration of lead in paint, as even small concentrations of lead can result in unacceptable employee exposures depending upon the method of removal and other workplace conditions.
The disposal of lead-based paint waste, as well as paint waste containing other heavy metals, is regulated by the USEPA and State of Iowa. Wastes generated by industrial businesses, commercial businesses, and government institutions are subject to regulation. Commercial business owners and removal contractors are required to determine if paint waste generated from nonresidential structures (such as public and commercial buildings, warehouses, bridges, water towers, and transmission towers) contains heavy metals that would cause the debris to be considered a hazardous waste. Disposal options and applicable management requirements for collected debris will be based upon whether the waste stream is considered a hazardous waste and the amount of debris generated. Removal contractors and building owners need to include these factors when preparing and responding to bid specifications. Specific notification and testing requirements must be addressed prior to transporting, treating, storing, or disposing of hazardous wastes. Lead-containing wastes are considered hazardous waste under RCRA if Toxicity Characteristic Leachate Procedure (TCLP) results exceed 5 milligrams per liter (mg/L). The USEPA has made exceptions for the handling and disposal of lead wastes generated from residential housing.
Specific notification and testing requirements must be addressed prior to transporting, treating, storing, or disposing of hazardous wastes. Lead-containing wastes are considered hazardous waste under RCRA if Toxicity Characteristic Leachate Procedure (TCLP) results exceed 5 milligrams per liter (mg/L). The USEPA has made exceptions for the handling and disposal of lead wastes generated from residential housing.
The above overview is not intended to be inclusive of all potentially pertinent regulatory information. The relevant USEPA, OSHA and State of Iowa regulations should be consulted prior to undertaking activities involving the demolition, renovation or maintenance of surface coatings that contain lead.
4.2 Lead Paint Testing
The following surface coatings were collected as part of the lead paint testing:
bolded = lead-based paint
This evaluation report can help the Owner develop a plan for renovating the building by having concentrations of lead in the paint identified. It is our understanding that the information in this report will be provided to the contractors so that appropriate precautions can be made to minimize worker exposure to lead. If surface coatings with lead containing paint are handled improperly, exposure could occur to workers and future occupants of the facility.
5.0 HAZARDOUS MATERIALS ASSESSMENT
Atlas completed a visual inspection of areas throughout the tunnel system in an attempt to identify hazardous wastes or universal wastes that may be impacted by planned renovation activities.
T A B L E 3 : L E A D P A I N T S U M M A R Y
Sample Number
Sample Location
Representative Material Paint Color
Lead Concentration (% by weight)
No suspect lead containing surface coatings were identified
The survey included a visual inspection of: light fixtures and other equipment for the presence of Polychlorinated Biphenyls (PCBs); light bulbs, thermostats, switches, and other equipment for the presence of mercury; refrigerants, batteries, and devices with potential radioactive materials.
T A B L E 4 : H A Z A R D O U S B U I L D I N G M A T E R I A L S
Category Material Estimated Quantity
Batteries
Lead Acid NA
Nickel Cadmium NA
Lithium-Ion NA
Mercury
Thermostats NA
Fluorescent Light Tubes NA
High Intensity Discharge Bulbs NA
Strobes NA
Poly-Chlorinated Biphenyl (PCBs) Light Ballasts NA
Transformers NA
Low Level Radioactive Sources (LLR) Tritium Exit Signs NA
Smoke Detectors NA
Chlorofluorocarbons (CFCs) or Hydro Chlorofluorocarbons (HCFCs)
Refrigerator/Cooler NA
Freezer NA
Water Fountain NA
6.0 CONCLUSIONS
6.1 Asbestos
The NESHAP and OSHA regulations govern the removal of ACM. Atlas recommends that a State of Iowa certified abatement contractor be retained to properly abate and dispose of ACM identified in Table 1 above and in accordance with local, state, and federal regulations.
The owner and/or operator are responsible for NESHAP regulatory compliance regarding he proper removal, handling, and disposal of ACM containing >1% asbestos prior to renovation or demolition. Also, per state regulations, please be aware that the owner and/or operator must submit a notification to the Iowa Department of Natural Resources (IDNR) 10-buisness days prior to asbestos abatement at certain quantity thresholds and prior to renovation/demolition activities.
6.2 Lead
No suspect lead containing surface coatings were identified.
Contractors should use caution during construction-related activities as concealed surface coatings containing lead paints that were not previously tested may be encountered. If materials not sampled during this investigation are later identified to contain regulated quantities of lead concentrations, then they should be removed, controlled and/or disposed in accordance with federal, state and local regulations, prior to disturbance. OSHA considers any detectable level of lead as LCP and disturbance of these surface coatings is subject to the training and work practices in OSHA 29 CFR 1926.62 “Lead in Construction”.
6.3 Hazardous Building Materials
No hazardous buildings materials were identified.
7.0 ASSUMPTIONS AND LIMITATIONS
The results, findings, conclusions, and recommendations expressed in this report are based solely on conditions noted during the October 10 and 11, 2024, hazardous building materials survey of the Woodward Resource Center – Tunnel System in Woodward, Iowa.
Atlas did not perform destructive sampling -- it was not within Atlas’s scope of work to remove surface materials to investigate portions of the structure or materials that may lay beneath the surface -- thus, any materials that could not be visually identified on the surface were not inspected and would not be noted in this report. Atlas’s selection of sample locations and frequency of sampling was based on the inspector’s assumption that like materials in the same area are homogeneous in content.
The report is designed to aid the building owner, architect, construction manager, general contractor, and potential abatement contractor in locating hazardous building materials. Under no circumstances is the report to be utilized as a bidding document or as a project specification document since it does not have all the components required to serve as a Project Design document or an Abatement Work plan.
Our professional services have been performed, our findings obtained, and our conclusions and recommendations prepared in accordance with customary principles and practices in the fields of environmental science and engineering. This statement is in lieu of other statements either expressed or implied. This report does not warrant against future operations or conditions, nor does it warrant against operations or conditions present of a type or at a location not investigated.
This report is intended for the sole use of IDAS. The scope of services performed in execution of this evaluation may not be appropriate to satisfy the needs of other users, and use or re-use of this document or the findings, conclusions, or recommendations is at the risk of said user.
Atlas recommendations are based in part on federal, state, local regulations, and guidelines. Atlas does not undertake responsibility for reporting to any local, state, or federal public agencies of conditions at the site that may present a potential danger to public health or safety. Atlas recommends that the Client comply with regulations and response actions in accordance with federal, state, and local regulations.
APPENDIX A
ASBESTOS ANALYTICAL RESULTS AND CHAIN OF CUSTODY
EMSL Analytical, Inc.
200 Route 130 North Cinnaminson, NJ 08077
Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
042421269EMSL Order:
Customer ID: ATC55
Customer PO:
Project ID:
Attention: Phone:Eric Brown (402) 697-9747
Fax:Atlas Technical (402) 597-8532
Received Date:11117 Mockingbird Drive 10/14/2024 8:50 AM
Analysis Date:Omaha, NE 68137 10/15/2024
Collected Date: 10/10/2024
Project: 204BS07475 / Woodward Tunnel Survey
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
T-1
042421269-0001
40% ChrysotileNon-fibrous (Other)60%White
Fibrous
Homogeneous
Tunnel - Intersection w Birches/Oak/Power
Plant - TSI - Largest
16" dia. Pipe Run
T-2-TSI
042421269-0002
65% ChrysotileNon-fibrous (Other)35%White
Fibrous
Homogeneous
Tunnel - Intersection w Medical - TSI - LP
Steam Pipe 16" dia.
T-2-Wrap
042421269-0002A
None DetectedNon-fibrous (Other)10%Cellulose90%Brown
Fibrous
Homogeneous
Tunnel - Intersection w Medical - TSI - LP
Steam Pipe 16" dia.
T-3
042421269-0003
65% ChrysotileNon-fibrous (Other)35%White
Fibrous
Homogeneous
Tunnel - Intersection of Orchard & Cedar -
TSI - LP Steam Pipe
Run
T-4
042421269-0004
70% ChrysotileNon-fibrous (Other)30%Gray
Fibrous
Homogeneous
Tunnel - Intersection w Birches/Oak/Power
- TSI - 6" next to
Largest Pipe Run
T-5-TSI
042421269-0005
22%
10%
Amosite
Chrysotile
Non-fibrous (Other)68%Gray
Fibrous
Homogeneous
Tunnel - Intersection w Medical - TSI - 6" next to LP Steam
Pipe Run
T-5-Wrap
042421269-0005A
None DetectedNon-fibrous (Other)10%Cellulose90%Brown
Fibrous
Homogeneous
Tunnel - Intersection w Medical - TSI - 6" next to LP Steam
Pipe Run
T-6
042421269-0006
28%
7%
Amosite
Chrysotile
Non-fibrous (Other)65%Gray
Fibrous
Homogeneous
Tunnel - Intersection of Orchard & Cedar -
TSI - 6" next to LP
Steam Pipe Run
T-7
042421269-0007
65% ChrysotileNon-fibrous (Other)5%Cellulose30%White
Fibrous
Homogeneous
Tunnel - Intersection w Medical - TSI -
Airocell
T-8
042421269-0008
70% ChrysotileNon-fibrous (Other)30%Gray
Fibrous
Homogeneous
Tunnel - Intersection of Orchard & Cedar -
TSI - Elbow - LP
Steam Pipe
T-9-TSI Elbow
042421269-0009
60% ChrysotileNon-fibrous (Other)40%Gray
Fibrous
Homogeneous
Tunnel - Intersection of Orchard & Cedar -
TSI - Elbow - LP
Steam Pipe
T-9-Wrap
042421269-0009A
<1% ChrysotileNon-fibrous (Other)10%Cellulose90%Gray
Fibrous
Heterogeneous
Tunnel - Intersection of Orchard & Cedar -
TSI - Elbow - LP
Steam Pipe
Result includes a small amount of inseparable attached material
T-10
042421269-0010
60% ChrysotileNon-fibrous (Other)40%Gray
Fibrous
Homogeneous
Tunnel - Intersection of Orchard & Cedar -
TSI - Elbow - LP
Steam Pipe
Initial report from: 10/15/2024 16:28:29
Page 1 of 5ASB_PLM_0008_0002 - 2.31 Printed: 10/15/2024 4:28 PM
Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
042421269EMSL Order:
Customer ID: ATC55
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
T-11
042421269-0011
40% ChrysotileNon-fibrous (Other)60%White
Fibrous
Homogeneous
Tunnel - Intersection of Orchard & Cedar -
TSI - Unknown Pipe above Hot Water
T-12
042421269-0012
70% ChrysotileNon-fibrous (Other)30%Gray
Fibrous
Homogeneous
Tunnel - Intersection w Myers - TSI - Elbow
HP Steam Pipe
T-13
042421269-0013
60% ChrysotileNon-fibrous (Other)40%Gray
Fibrous
Homogeneous
Tunnel - 200ft from
Welders Access
Hatch - TSI - Hot
Water Elbow
T-14
042421269-0014
60% ChrysotileNon-fibrous (Other)40%Brown
Fibrous
Homogeneous
Tunnel - 200ft from
Welders Access
Hatch - TSI - Hot
Water Elbow
T-15-TSI
042421269-0015
65% ChrysotileNon-fibrous (Other)35%Gray
Fibrous
Homogeneous
Tunnel - 200ft from
Welders Access
Hatch - TSI - Hot
Water Elbow
T-15-Wrap
042421269-0015A
None DetectedNon-fibrous (Other)10%Cellulose90%Tan/White
Fibrous
Homogeneous
Tunnel - 200ft from
Welders Access
Hatch - TSI - Hot
Water Elbow
T-16
042421269-0016
35% ChrysotileNon-fibrous (Other)65%Brown/White
Fibrous
Homogeneous
Tunnel - 200ft from
Welders Access
Hatch - TSI - Mystery
Pipe Run
T-17
042421269-0017
70% ChrysotileNon-fibrous (Other)5%Cellulose25%White
Fibrous
Homogeneous
Tunnel - Intersection w Branch Myers
Tunne; - TSI - Airocell
T-18-TSI Elbow
042421269-0018
65% ChrysotileNon-fibrous (Other)35%Gray
Fibrous
Homogeneous
Tunnel - Larches End
- TSI - Elbow HP
Steam
T-18-Wrap
042421269-0018A
None DetectedNon-fibrous (Other)20%Cellulose80%Tan/White
Fibrous
Homogeneous
Tunnel - Larches End
- TSI - Elbow HP
Steam
T-19
042421269-0019
60% ChrysotileNon-fibrous (Other)40%Gray
Fibrous
Homogeneous
Tunnel - Larches End
- TSI - Hot Water
Elbow
T-20
042421269-0020
80% ChrysotileNon-fibrous (Other)20%White
Fibrous
Homogeneous
Tunnel - Myers End -
TSI - Airocell
T-21-TSI
042421269-0021
None DetectedNon-fibrous (Other)5%Glass95%Brown/Gray
Fibrous
Homogeneous
Tunnel - under Street by Admin - TSI - Hot
Water Run
T-21-TSI 2
042421269-0021A
None DetectedNon-fibrous (Other)5%Cellulose95%White
Fibrous
Homogeneous
Tunnel - under Street by Admin - TSI - Hot
Water Run
T-21-Wrap
042421269-0021B
None DetectedNon-fibrous (Other)10%Cellulose90%Tan/White
Fibrous
Homogeneous
Tunnel - under Street by Admin - TSI - Hot
Water Run
T-22
042421269-0022
None DetectedNon-fibrous (Other)5%Glass95%Yellow
Fibrous
Homogeneous
Tunnel - under Street by Admin - TSI -
Return Steam Run
T-23-TSI
042421269-0023
50% ChrysotileNon-fibrous (Other)50%Brown/Black
Fibrous
Homogeneous
Tunnel - E-Home
Branch - TSI -
Mystery Pipe Run - 2"
Height
Page 2 of 5ASB_PLM_0008_0002 - 2.31 Printed: 10/15/2024 4:28 PM
Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
042421269EMSL Order:
Customer ID: ATC55
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
T-23-TSI 2
042421269-0023A
None DetectedNon-fibrous (Other)10%Cellulose
Synthetic
70%
20%
Brown
Fibrous
Homogeneous
Tunnel - E-Home
Branch - TSI -
Mystery Pipe Run - 2"
Height
T-24
042421269-0024
7%
55%
Amosite
Chrysotile
Non-fibrous (Other)33%Cellulose5%Gray
Fibrous
Homogeneous
Tunnel - E-Home
Branch - Mystery Pipe
- 2" Elbow
T-25-TSI Elbow
042421269-0025
60% ChrysotileNon-fibrous (Other)40%Gray
Fibrous
Homogeneous
Tunnel - E-Home
Branch - TSI - Elbow -
4" Pipe
T-25-Wrap
042421269-0025A
None DetectedNon-fibrous (Other)10%Cellulose90%Tan
Fibrous
Homogeneous
Tunnel - E-Home
Branch - TSI - Elbow -
4" Pipe
T-26-TSI
042421269-0026
22%
7%
Amosite
Chrysotile
Non-fibrous (Other)71%White
Fibrous
Homogeneous
Tunnel - E-Home
Branch - TSI - Run -
4" Pipe
T-26-Wrap
042421269-0026A
None DetectedNon-fibrous (Other)5%Cellulose95%Tan
Fibrous
Homogeneous
Tunnel - E-Home
Branch - TSI - Run -
4" Pipe
T-27
042421269-0027
10%
17%
Amosite
Chrysotile
Non-fibrous (Other)73%White
Fibrous
Homogeneous
Tunnel - Maple
Branch - TSI - Run -
2" Top Pipe
T-28
042421269-0028
15%
20%
Amosite
Chrysotile
Non-fibrous (Other)65%White
Fibrous
Homogeneous
Tunnel - Maple
Branch - TSI - Run -
6" Top Pipe
T-29-TSI
042421269-0029
30%
20%
Amosite
Chrysotile
Non-fibrous (Other)50%White
Fibrous
Homogeneous
Tunnel - Maple
Branch - TSI - 2"
Middle Shelf Run against Wall
T-29-Wrap
042421269-0029A
<1%
<1%
Amosite
Chrysotile
Non-fibrous (Other)10%Cellulose90%Tan/White
Fibrous
Heterogeneous
Tunnel - Maple
Branch - TSI - 2"
Middle Shelf Run against Wall
Result includes a small amount of inseparable attached material
T-30
042421269-0030
33%
20%
Amosite
Chrysotile
Non-fibrous (Other)47%White
Fibrous
Homogeneous
Tunnel - Maple
Branch - TSI - Run -
1" Bottom Shelf
T-31
042421269-0031
33%
20%
Amosite
Chrysotile
Non-fibrous (Other)47%White
Fibrous
Homogeneous
Tunnel - Maple
Branch - TSI - Run -
2" Bottom Shelf against Wall
T-32-TSI
042421269-0032
65% ChrysotileNon-fibrous (Other)5%Cellulose30%Gray
Fibrous
Homogeneous
Tunnel - Medical
Branch - TSI - Airocell
Run
T-32-Wrap
042421269-0032A
None DetectedNon-fibrous (Other)5%Cellulose95%Tan
Fibrous
Homogeneous
Tunnel - Medical
Branch - TSI - Airocell
Run
T-33
042421269-0033
38% ChrysotileNon-fibrous (Other)56%Cellulose6%White
Fibrous
Homogeneous
Tunnel - Medical
Branch - TSI - 2" Pipe
Run
T-34-TSI
042421269-0034
70% ChrysotileNon-fibrous (Other)5%Cellulose25%White
Fibrous
Homogeneous
Tunnel - Medical
Branch - TSI - Larger
Diameter Airocell Run
T-34-Wrap
042421269-0034A
None DetectedNon-fibrous (Other)5%Cellulose95%Tan
Fibrous
Homogeneous
Tunnel - Medical
Branch - TSI - Larger
Diameter Airocell Run
Page 3 of 5ASB_PLM_0008_0002 - 2.31 Printed: 10/15/2024 4:28 PM
Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
042421269EMSL Order:
Customer ID: ATC55
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
T-35
042421269-0035
60% ChrysotileNon-fibrous (Other)5%Cellulose35%White
Fibrous
Homogeneous
Tunnel - Medical
Branch - TSI - Small
Diameter Airocell Run
T-36
042421269-0036
65% ChrysotileNon-fibrous (Other)35%White
Fibrous
Homogeneous
Tunnel - Medical
Branch - Steam Pipe
Elbow
T-37
042421269-0037
12% ChrysotileNon-fibrous (Other)43%Cellulose
Min. Wool
5%
40%
Brown/Gray
Fibrous
Homogeneous
Tunnel - Medical
Branch - Middle Pipe
Elbow
T-38
042421269-0038
7% ChrysotileNon-fibrous (Other)53%Min. Wool40%Gray
Fibrous
Homogeneous
Tunnel - Medical
Branch - 4" Pipe
Diameter Elbow
T-39
042421269-0039
55% ChrysotileNon-fibrous (Other)45%Tan/White
Fibrous
Homogeneous
Tunnel - 75 fom
Strange Air Stack -
Mystery Pipe adj to
HW near Wall
T-40
042421269-0040
None DetectedNon-fibrous (Other)100%Tan/White
Non-Fibrous
Homogeneous
Tunnel - Birches
Branch - TSI -
Sealant
T-41-TSI Aerocell
042421269-0041
65% ChrysotileNon-fibrous (Other)5%Cellulose30%White
Fibrous
Homogeneous
Tunnel - Birches
Branch - TSI - Airocell
Run 2nd Pipe from
Wall
T-41-TSI Aerocell 2
042421269-0041A
None DetectedNon-fibrous (Other)5%Cellulose95%Brown
Fibrous
Homogeneous
Tunnel - Birches
Branch - TSI - Airocell
Run 2nd Pipe from
Wall
T-42-TSI Aerocell
042421269-0042
40% ChrysotileNon-fibrous (Other)5%Cellulose55%White
Fibrous
Homogeneous
Tunnel - Birches
Branch - TSI - Airocell
Run 2.5 Pipe furthest from High Pressure
Wall
T-42-Wrap
042421269-0042A
None DetectedNon-fibrous (Other)5%Cellulose95%Tan
Fibrous
Homogeneous
Tunnel - Birches
Branch - TSI - Airocell
Run 2.5 Pipe furthest from High Pressure
Wall
T-43-TSI
042421269-0043
26%
10%
Amosite
Chrysotile
Non-fibrous (Other)64%Tan
Fibrous
Homogeneous
Tunnel - Birches
Branch - TSI Run -
Lower Pressure Pipe
T-43-Wrap
042421269-0043A
None DetectedNon-fibrous (Other)20%Cellulose80%Gray
Fibrous
Homogeneous
Tunnel - Birches
Branch - TSI Run -
Lower Pressure Pipe
T-44
042421269-0044
60% ChrysotileNon-fibrous (Other)40%White
Fibrous
Homogeneous
Tunnel - Birches
Branch - TSI - 2.5 in
High Pressure Elbow
T-45-TSI
042421269-0045
None DetectedNon-fibrous (Other)30%Cellulose70%Tan/White
Fibrous
Homogeneous
Tunnel - Oak Hall
Branch - Hot Water
Pipe TSI Run
T-45-TSI 2
042421269-0045A
None DetectedNon-fibrous (Other)5%Glass95%Yellow
Fibrous
Homogeneous
Tunnel - Oak Hall
Branch - Hot Water
Pipe TSI Run
T-46-TSI
042421269-0046
30%
15%
Amosite
Chrysotile
Non-fibrous (Other)55%White
Fibrous
Homogeneous
Tunnel - Oak Hall
Branch - High
Pressure Steam TSI
Run
Page 4 of 5ASB_PLM_0008_0002 - 2.31 Printed: 10/15/2024 4:28 PM
Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
042421269EMSL Order:
Customer ID: ATC55
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
T-46-Wrap
042421269-0046A
<1%
<1%
Amosite
Chrysotile
Non-fibrous (Other)20%Cellulose80%Tan/White
Fibrous
Heterogeneous
Tunnel - Oak Hall
Branch - High
Pressure Steam TSI
Run
Result includes a small amount of inseparable attached material
T-47
042421269-0047
25% ChrysotileNon-fibrous (Other)40%Cellulose35%White
Fibrous
Homogeneous
Tunnel - Oak Hall
Branch - Low
Pressure Steam TSI
Run
T-48
042421269-0048
25%
10%
Chrysotile
Crocidolite
Non-fibrous (Other)65%White
Fibrous
Homogeneous
Tunnel - Oak Hall
Branch - Low
Pressure Steam TSI
Run
T-49-TSI
042421269-0049
60% ChrysotileNon-fibrous (Other)40%White
Fibrous
Homogeneous
Tunnel - Oak Hall
Branch - High
Pressure Steam Run
TSI
T-49-Wrap
042421269-0049A
<1% ChrysotileNon-fibrous (Other)20%Cellulose80%Tan/White
Fibrous
Heterogeneous
Tunnel - Oak Hall
Branch - High
Pressure Steam Run
TSI
Result includes a small amount of inseparable attached material
T-50
042421269-0050
65% ChrysotileNon-fibrous (Other)35%Gray
Fibrous
Homogeneous
Tunnel - Oak Hall
Branch - Hot Water
Elbow TSI
Analyst(s)
Brett Polumbo (69) Samantha Rundstrom, Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.
Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NVLAP Lab Code 101048-0, AIHA LAP, LLC-IHLAP Lab 100194, PA ID# 68-00367, LA #04127
Page 5 of 5ASB_PLM_0008_0002 - 2.31 Printed: 10/15/2024 4:28 PM
OrderID: 042421269
APPENDIX B
ASBESTOS PHOTO LOG
Photograph Log
Tunnels
1251 334th Street
Atlas Technical Consultants, LLC
4503 East 50th Street, Suite 800, Des Moines, IA 50317
(515) 981-4528
Project No. 204BS07475
View of the Powerhouse Tunnel Entrance. 1
View of the Asbestos Containing Low Pressure Pipe.
(T-1, 2, & 3, 40% - 65% Chrysotile)
Des Moines, IA 50317
View of the Asbestos Containing High Pressure TSI. (T-4, 70% Chrysotile) 3
View of the Asbestos Containing High Pressure Pipe.
(T-5, & 6, 22% - 28% Amosite & 7% - 10% Chrysotile) 4
Des Moines, IA 50317
View of the Asbestos Containing TSI Airocell.
(T-7, 17, 20, 32, 34, 35, 41, & 42, 40% - 80% Chrysotile) 5
View of the Asbestos Containing High Pressure TSI Elbow.
(T-8, 9, & 10, 60% - 70% Chrysotile)
Des Moines, IA 50317
View of the Asbestos Containing Pipe (above Hot Water at Orchard and Cedar
Intersection). (T-11, 40% Chrysotile) 7
View of the Asbestos Containing Hot Water Elbows.
(T-13, 14, 15, & 19, 60% - 65% Chrysotile) 8
Des Moines, IA 50317
View of the Asbestos Containing High Pressure Elbow.
(T-12 & 18, 65% & 70% Chrysotile)
View of the Asbestos Containing 2” Pipe Run. (T-23, 50% Chrysotile)
Des Moines, IA 50317
View of the Asbestos Containing 2” Elbow. (T-24, 7% Amosite & 55% Chrysotile)
View of the Asbestos Containing 4” Elbow. (T-25, 60% Chrysotile) 12
Des Moines, IA 50317
View of the Asbestos Containing 4” Pipe Run in E Home Branch.
(T-26, 22% Amosite & 7% Chrysotile) 13
View of the Asbestos Containing 2” Pipe Run in Maple Branch.
(T-27, 10% Amosite & 17% Chrysotile) 14
Des Moines, IA 50317
View of the Asbestos Containing High Pressure Pipe in Maple Branch.
(T-28, 15% Amosite & 20% Chrysotile)
View of the Asbestos Containing 2” Pipe on Middle Shelf in Maple Branch.
(T-29, 30% Amosite & 20% Chrysotile)
Des Moines, IA 50317
View of the Asbestos Containing 1” Pipe on Bottom Shelf in Maple Branch.
(T-30, 33% Amosite & 20% Chrysotile) 17
View of the Asbestos Containing 2” Pipe on Bottom Shelf in Maple Branch.
(T-31, 33% Amosite & 20% Chrysotile)
Des Moines, IA 50317
View of the Asbestos Containing 2” Pipe Run in Medical Branch.
(T-33, 38% Chrysotile)
View of the Asbestos Containing Steam Pipe Elbow in Medical Branch.
(T-36, 65% Chrysotile)
Des Moines, IA 50317
View of the Asbestos Containing Middle Pipe Elbow in Medical Branch.
(T-37, 12% Chrysotile)
View of the Asbestos Containing 4” Pipe Elbow in Medical Branch.
(T-38, 7% Chrysotile) 22
Des Moines, IA 50317
View of the Asbestos Containing Pipe Insulation. (T-39, 55% Chrysotile) 23
View of the Asbestos Containing Low Pressure Pipe in Birches Branch.
(T-43, 26% Amosite & 10% Chrysotile)
Des Moines, IA 50317
View of the Asbestos Containing High Pressure Pipe Elbow. (T-44, 60% Chrysotile) 25
View of the Asbestos Containing High Pressure Pipe in Oak Hall Branch.
(T-46 & 49, 30% Amosite & 15% Chrysotile, & 60% Chrysotile)
Des Moines, IA 50317
View of the Asbestos Containing Low Pressure Pipe in Oak Hall.
(T-47 & 48, 25% Chrysotile, & 25% Chrysotile and 10 % Crocidolite) 27
View of the Asbestos Containing Hot Water Pipe Elbow in Oak Hall Branch.
(T-50, 65% Chrysotile)
APPENDIX C
INSPECTOR ACCREDITATIONS
HAZARDOUS BUILDING MATERIALS
SURVEY
CHILLER BUILDING
WRC CAMPUS UTILITY DECENTRALIZATION PHASE 5
PROJECT 9279.50
1251 334TH STREET
WOODWARD, IOWA
204BS07475
PREPARED FOR:
Iowa Department of Administrative Services 109 SE 13th Street Des Moines, IA 50319
PREPARED BY:
Atlas Technical Consultants LLC 11117 Mockingbird Drive Omaha, NE 68137 May 5, 2026
Page | i
Omaha, NE 68137
(402) 697-9747 | oneatlas.com
April 21, 2026
Ms. Jennifer Kleene
Iowa Department of Administrative Services
109 SE 13th Street
Des Moines, IA 50319
Subject: Hazardous Building Materials Survey
Chiller Building
WRC Campus Utility Decentralization Phase 5 Project 9279.50
1251 334th Street
Atlas No: 204BS07475
Dear Ms. Kleene:
Atlas Technical Consultants LLC (Atlas) is pleased to submit the attached Hazardous Building
Materials Survey Report conducted at the above-referenced site. This report includes procedures, methodologies and analytical laboratory results.
Atlas appreciates the opportunity to perform these services for the Iowa Department of
Administrative Services (IDAS) and we look forward to working with you in the future. If you need any assistance with the implementation of the recommendations contained in this report, please feel free to contact the us and we will respond promptly to your needs.
Respectfully submitted, Atlas Technical Consultants LLC
Phillip Thomas, OHST, CHMM Steve Hudson, CIH Iowa Asbestos Inspector Sr. Project Manager
Atlas No. 204BS07475 Page | ii
T A B L E O F C O N T E N T S
LETTER OF TRANSMITTAL .................................................................................... i
1.0 SCOPE OF SERVICES
2.0 GENERAL SITE CONDITIONS
3.0 ASBESTOS SURVEY
3.1 Regulation Review
3.2 Homogeneous Areas
3.3 Sampling Strategy
3.4 Laboratory Analytical Results
3.5 Suspect Asbestos-Containing Materials
3.5 Asbestos-Containing Materials
4.0 LEAD PAINT TESTING
4.1 Regulation Review
4.2 Summary of Findings
5.0 HAZARDOUS BUIDLING MATERIALS
6.0 CONCLUSIONS
6.1 Asbestos
6.2 Lead
6.3 Hazardous Materials
7.0 LIMITATIONS
APPENDICES
APPENDIX A: Laboratory Analytical Report
APPENDIX B: Lead Analytical Report and Chain of Custody
APPENDIX C: Drawings with Sample Locations
APPENDIX D: Asbestos Containing Materials Photo Log
APPENDIX E: Staff and Company Accreditations
Page | 1
Hazardous Building Materials Survey
Chiller Building WRC Campus Utility Decentralization Phase 5 Project 9279.50
1251 334th Street
Atlas No.: 204BS07475
1.0 SCOPE OF SERVICES
The purpose of this project was to perform a Limited Hazardous Building Materials (HBM) Survey of the above-referenced property prior to proposed renovation and demolition activities.
2.0 GENERAL SITE CONDITIONS
The survey was conducted at the Chiller Building as part of the WRC Campus Utility Decentralization Phase 5 Project 9279.50 located at 1251 334th Street in Woodward, Iowa. The survey area was conducted to identify asbestos containing materials (ACM) and lead containing paint as part of proposed renovation/demolition activities.
3.0 ASBESTOS SURVEY
On September 25, 2025 and April 1, 2026, the Chiller Building was inspected for ACM by Mr. Eric Brown and Mr. Steve Hudson of Atlas. Mr. Brown and Mr. Hudson have completed the requisite training for asbestos accreditation as an inspector at a state approved training provider under TSCA Title II. Mr.
Brown’s and Mr. Hudson’s State of Iowa Inspector numbers are 24-11418 and 26-15559.
Atlas conducted an asbestos survey of the identified building as required by United States Environmental Protection Agency (USEPA) regulation 40 Code of Federal Regulations (CFR) Part 61, the asbestos National Emissions Standards for Hazardous Air Pollutants (NESHAP)…