RFB 938300-01 Addendum #3.pdf
PDF 435 KB Posted
- Attached to
- DOC MPCF Apprenticeship Building
- Solicitation number
- RFB938300-01
- Issued by
- Henry County, Iowa
About this file
This document is an Addendum #3 to a Request for Bids (RFB) for the DOC MPCF New Apprenticeship Building project at the Mount Pleasant Correctional Facility in Mount Pleasant, Iowa. The RFB is being issued by the Iowa Department of Administrative Services. The addendum provides responses to questions related to electrical and data routing, builder's risk insurance, building permit fees, water and electrical connections, and in-floor heating system requirements. It also includes a list of approved substitutions and revisions to the electrical drawings and symbols. The project involves the construction of a new apprenticeship building at the correctional facility.
The addendum does not provide details on pricing, set asides, incumbents, funding sources, or other salient contract information. It is focused on technical clarifications and changes to the bid documents.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFB938300-01 - Bid Form.pdf | ||
| RFB938300-01 - Project Manual.pdf | ||
| RFB 938300-01 Addendum #2.pdf | ||
| RFB938300-01 - Drawings.pdf | ||
| RFB938300-01 - Notice.pdf | ||
| RFB 938300-01 Addendum #1.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM #3
Project Name: DOC MPCF New Apprenticeship Building
DAS#9383.00
RFB938300-01
Addendum #3
Dated: July 29, 2024
This Addendum forms a part of the Request For Bids documents. This Addendum supersedes and supplements all portions of the original Request For Bids with which it conflicts.
ACKNOWLEDGE RECEIPT OF THIS ADDENDUM IN THE REQUEST FOR PROPOSAL. FAILURE TO
DO SO MAY SUBJECT TO DISQUALIFICATION.
1. Questions:
a. How is electrical and data getting to building if alternate is not done? Answer: Electrical and data would still be routed down the existing tunnel, contractor to provide pathway from existing tunnel to new building mechanical room.
b. Is Builder’s Risk insurance provided by the owner, or is it by contractor? Answer: By owner
c. Who is responsible for the building permit fee? Answer: No building permit required.
d. Water and electrical connection are to be by owner, but usage rates and temp installs are to be by
Contractor? Can you please confirm this? Answer: Water and electrical connections will be provided by the owner, contractor to connect. Usage rates/monitoring not needed.
e. Looking through the drawing for option three on the in-floor heat. I don’t see drawings or equipment for the two in floor heat loops to connect to anything. Are we just installing the tubing and the two headers as the option for this project or is there equipment and piping drawings to make this a operating system. Answer: You are to install the tubing, headers, and insulation as shown on the drawings. Provide pathway from building to existing tunnel as drawings indicate. Owner to provide and install other ancillary equipment at a later date.
f. Please clarify the required PEMB insulation requirements in the walls and roof? There are several conflicting notes on the drawings and specs. Answer: Requirements are per 2012
IECC: Roof – R-19 + R-11 Liner System. Walls – R-13 + R-13ci or system U-Value of 0.052 or better (Simple Saver or similar).
2. Substitution Requests:
a. Spec Section: 23 3416 HVAC Power Ventilators
Item: Sidewall Axial Fans
Manufacturer: JencoFan by S&P, Twin City Fan
b. Item: Restroom Ceiling Exhaust Fans
Manufacturer: Soler Palau, Twin City Fan
c. Spec Section: 23 8239 Electric Unit Heaters
Item: Unit Heaters
Manufacturer: Redd-I of TPI Corp
d. Spec Section: 23 0923 Gas Instruments
Item: CO / NO2 Gas Detection System
Manufacturer: Honeywell Analytics
e. Spec Section: 08 9119 Louvers
Item: Sidewall Louver
Manufacturer: United Enertech
f. Spec Section: 26 5100 Interior Lighting
Item/Manufacturer:
D1| Lithonia, Halo
Exit| Lithonia, Sure-Lites
L1/L1-EM| Lithonia
W1-EM| Lithonia, Halo
W2| Lithonia, Halo
3. Drawings:
a. Drawing E-001 Electrical Symbols
1. Removed Note-16
b. Drawing E-602 Electrical Lighting Schedules
1. Updated Lighting Schedule
4. Attachments:
a. Drawing E-001 Electrical Symbols
b. Drawing E-602 Electrical Lighting Schedules
END OF ADDENDUM
ELECTRICAL ABBREVIATIONS
ELECTRICAL DEVICE TAGS: UPPERCASE LETTER(S)
INDICATES PANEL ID AND CIRCUIT NUMBER.
LOWERCASE LETTER INDICATES DESIGNATION OF
CONTROLLING SWITCH (WHERE APPLICABLE).
SWITCH ID INDICATED BY A LOWERCASE LETTER.
SWITCH IDS ARE UNIQUE PER SPACE. A SWITCH WITH
AN ID "A" CONTROLS ALL DEVICES WITHIN THE SPACE
IN WHICH IT IS LOCATED TAGGED WITH "A". A
SWITCH WITHOUT A TAGGED ID CONTROLS ALL
LIGHTING FIXTURES WITHIN A SPACE. ID TAGS MAY BE
USED ON CONTROL DEVICES OTHER THAN SWITCHES,
SUCH AS OCCUPANCY SENSORS OR CONTACTORS.
EQUIPMENT TAGS: EQUIPMENT ID IS INDICATED BY
AN UNDERLINED TAG ADJACENT TO THE
EQUIPMENT. SEE THE EQUIPMENT CONNECTION
SCHEDULE FOR DESCRIPTION, ELECTRICAL
REQUIREMENTS, AND PANEL AND CIRCUIT
NUMBER. SYMBOLS/GRAPHIC APPEARANCE OF
EQUIPMENT VARIES.
SOLID, ARCED LINES CONNECTING EQUIPMENT,
DEVICES, OR FIXTURES INDICATE UNSWITCHED
POWER CIRCUITING. WIRES ARE ONLY INTENDED
TO INDICATE TO WHAT CIRCUIT DEVICES ARE
CONNECTED. ACTUAL CONNECTIONS, CIRCUIT
ROUTING, INSTALLATION, JUNCTION BOXES, ETC.
SHALL BE FIELD-DETERMINED BY THE CONTRACTOR.
HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE
EQUIPMENT NAME AND CIRCUIT NUMBER(S) ARE
INDICATED, SEPARATED BY A HYPHEN. HOMERUNS
ARE ONLY INTENDED TO INDICATE PANEL AND
CIRCUIT NUMBER. ACTUAL HOMERUN LOCATION
SHALL BE FIELD-DETERMINED BY THE CONTRACTOR.
POWER SYMBOLS
ELECTRICAL SYMBOL LEGEND
EXIT LIGHT, WALL-MOUNTED.
SHADING AND ARROWS INDICATE FACES AND
DIRECTIONAL CHEVRONS.
WALL-MOUNTED FIXTURES, TYPICAL
(VARIOUS SYMBOLS)
EMERGENCY LIGHTING UNIT, WALL-MOUNTED,
REMOTE BATTERY
EMERGENCY LIGHTING UNIT, WALL-MOUNTED,
INTEGRAL BATTERY
EMERGENCY LIGHTING UNIT, CEILING-MOUNTED,
INTEGRAL BATTERY
EMERGENCY LIGHTING UNIT, CEILING-MOUNTED,
REMOTE BATTERY
LIGHTING FIXTURES, TYPICAL, RECTANGULAR
(VARIOUS SYMBOLS)
FILLED CIRCLES INDICATE RECESSED.
OPEN CIRCLES INDICATE SURFACE-MOUNTED.
DIAGONAL LINE INDICATES LENSED.
OUTER DOTS INDICATE SUSPENDED.
LIGHTING FIXTURES, TYPICAL, ROUND
(VARIOUS SYMBOLS)
CENTER DOT INDICATES PENDANT.
DIAGONAL LINE INDICATES LENSED.
CHEVRON INDICATES WALL WASH.
STRIP FIXTURE
DIRECTIONAL LIGHT, TRACK LIGHT, FLOOD LIGHT
EXIT LIGHT, CEILING-MOUNTED.
SHADING AND ARROWS INDICATE FACES AND
DIRECTIONAL CHEVRONS.
LINEAR LIGHT, TAPE LIGHT
EXIT/ELU COMBO
DIAGONAL HATCH INDICATES LIGHT ON AN
EMERGENCY OR LIFE SAFETY CIRCUIT.
PROPOSED LIGHT FIXTURE
POLE/AREA LIGHTS
POST-TOP AREA LIGHT
BOLLARD LIGHT
SINGLE-POLE SWITCH
THREE-POLE SWITCH
SWITCH MODIFIERS:
3: 3-WAY
4: 4-WAY
K: KEYED
D: DIMMING
T: TIMER
V: VOLUME
OS: OCCUPANCY SENSOR
VS: VACANCY SENSOR
AC: ABOVE-COUNTER
LV: LOW-VOLTAGE
M: MOTOR-RATED
LIGHTING CONTACTOR
LIGHTING CONTROL PANEL
OCCUPANCY SENSOR
DAYLIGHT HARVESTING SENSOR
SMOKE DETECTOR
HEAT DETECTOR
CARBON MONOXIDE DETECTOR
BEAM DETECTOR T: TRANSMITTER R:
RECEIVER
COMBINATION DETECTOR (UP TO
THREE)
DUCT SMOKE DETECTOR
MANUAL PULL STATION
HORN, WALL
HORN, CEILING
STROBE, WALL, CANDELA AS
INDICATED
STROBE, CEILING, CANDELA AS
INDICATED
HORN/STROBE, WALL, CANDELA AS
INDICATED
HORN/STROBE, CEILING, CANDELA AS
INDICATED
REMOTE INDICATOR W/ TEST
SWITCH, WALL
REMOTE INDICATE W/ TEST SWITCH,
CEILING
DOOR HOLDER
DOOR CLOSER
FIRE SERVICE PHONE
ADDRESSABLE MODULE
AIM: ADDRESSABLE INPUT
MODULE
AOM:ADDRESSABLE OUTPUT
CONTROL MODULE
AIO: ADDRESSABLE INPUT/OUTPUT
MODULEFIRE ALARM CONTROL UNIT
EVAC: VOICE EVACUATION
CONTROL PANEL
FAA: FIRE ALARM ANNUNCIATOR
FACP: FIRE ALARM CONTROL
PANEL
FATC: FIRE ALARM TERMINAL
CABINET
NACP: NOTIFICATION APPLIANCE
CIRCUIT PANEL
FAMN: FIRE ALARM MASS
NOTIFICATION CONTROL PANEL
SUPERVISORY OR INTERFACE DEVICE
PIV: POST INDICATOR VALVE
SUPERVISORY
PS: PRESSURE SWITCH
R: NON-ADDRESSABLE RELAY
VS: VALVE SUPERVISORY SWITCH
WF: WATER FLOW SWITCH
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE
SPECIAL RECEPTACLE, TYPE AS INDICATED
W A
LL
C E
IL
IN
G
F
LO
O R
RECEPTACLE MODIFIERS:
##": HEIGHT AFF OC
AC: ABOVE COUNTER
GFI: GROUND-FAULT CIRCUIT INTERRUPTER
WP: WEATHERPROOF IN-USE COVER
HALF SHADING INDICATES SPLIT
(TYPICALLY SWITCHED)
OUTSIDE SHADING INDICATES
EMERGENCY CIRCUIT
CENTER SHADING INDICATES
ISOLATED GROUND
MULTIOUTLET ASSEMBLY
FILLED SQUARES INDICATE 120V OUTLET
OPEN SQUARES INDICATE WITH USB
CORD REEL, DEVICE VARIES
DROP CORD, DEVICE VARIES
JUNCTION BOX
FLOOR BOX, SEE SCHEDULE FOR TYPE
EMERGENCY POWER OFF
DOOR OPENER PUSH PLATE
POWER METER
SAFETY SWITCH, FUSED
SAFETY SWITCH, UNFUSED
MOTOR STARTER
COMBINATION STARTER/DISCONNECT
GROUND ROD
GROUND ROD WITH TEST WELL
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION CONDUCTOR SPLICE
STATIC GROUND RECEPTACLE
DATA OUTLET
TELEPHONE OUTLET
DATA/TELEPHONE OUTLET
W A
LL
C E
IL
IN
G
F
LO
O R
OUTLET MODIFIERS:
##": HEIGHT AFF OC
AC: ABOVE COUNTER
WIRELESS ACCESS POINT
TV OUTLET
LIGHTING SYMBOLS
CONTACTOR
FIRE ALARM SYMBOLS
GROUNDING AND LIGHTNING PROTECTION SYMBOLS
SECURITY CAMERA
PTZ: PAN/TILT/ZOOM
CARD READER
CARD READER WITH KEYPAD
CLOSED CIRCUIT TV OUTLET
DOOR CONTACT
ELECTRIC STRIKE
INTERCOM
MAGNETIC LOCK
REQUEST TO EXIT BUTTON
REQUEST TO EXIT SENSOR
MOTION DETECTOR
SECURITY CONTROL UNIT
SCP: SECURITY CONTROL PANEL
SPS: SECURITY POWER SUPPLY
UNIT
TELECOM SYMBOLS
SECURITY SYMBOLS
EQUIPMENT IS TAGGED WITH PANEL NAME AND WITH
PANEL ID IN PARENTHESES. PANEL ID IS INTENDED AS A
DESIGN DOCUMENTATION AID ONLY. DO NOT INCLUDE
PANEL ID IN FIELD-APPLIED CIRCUIT DIRECTORIES OR
LABELS.
HATCHED FILL INDICATES DISTRIBUTION PANEL OR
SWITCHBOARD.
SOLID FILL INDICATES BRANCH PANEL OR LOAD CENTER.
DASHED BOX INDICATES CODE-REQUIRED CLEARANCE
(WIDTH AND DEPTH).
DOOR INDICATES FRONT OF RECESSED PANEL.
PANELBOARDS ARE ASSIGNED AN ABBREVIATED INDICATOR
(OR PANEL ID) FOR USE WITH CIRCUIT NUMBERS. PANEL ID
IS LISTED WITHIN THE PANEL SCHEDULE AND IN THE PANEL
ABBREVIATION SCHEDULE.
POWER DISTRIBUTION EQUIPMENT
DEVICES AND FIXTURES ARE TAGGED WITH PANEL ID AND
CIRCUIT NUMBER. FOR EXAMPLE, A DEVICE TAGGED WITH
"A1" INDICATES THE DEVICE IS CIRCUITED TO PANEL
DESIGNATED "A," CIRCUIT NUMBER 1. THE PANEL
SCHEDULE CIRCUIT NUMBER CONTAINS BOTH THE PANEL
ABBREVIATION AND THE CIRCUIT NUMBER.
TRANSFORMER: TYPICALLY TRANSFORMER NAMES
BEGIN WITH OR CONTAIN THE LETTER "T". SEE
SINGLE-LINE DIAGRAM FOR DESCRIPTION AND
REQUIREMENTS.
DASHED, ARCED LINES CONNECTING EQUIPMENT,
DEVICES, OR FIXTURES INDICATE SWITCHED POWER.
ABSENCE OF A SWITCH DESIGNATION ON A LIGHTING
FIXTURE INDICATES FIXTURE IS CONTROLLED BY THE ONLY
SWITCH IN THE SPACE. AN "X" IN PLACE OF THE SWITCH
DESIGNATION INDICATES UNSWITCHED.
BOTTOM VALUE, LOWERCASE LETTER: SWITCH ID
LIGHTING TAGS
TOP VALUE: FIXTURE TYPE ID
(UNDERLINED)
BOTTOM VALUE, UPPERCASE LETTER(S): PANEL ID
BOTTOM VALUE, NUMBER(S): CIRCUIT NUMBER
WIRING
POWER DEVICE AND EQUIPMENT TAGS
CONSTRUCTION PHASING
EXISTING TO REMAIN
EXISTING TO BE DEMOLISHED
NEW
(TYPICAL ALL SYMBOLS AND EQUIPMENT)
EXISTING TO BE
DEMOLISHED
AREA NOT IN
CONTRACT
MISCELLANEOUS
KEYNOTE
CALLOUT:
TOP VALUE: DETAIL NUMBER
ON SHEET
BOTTOM VALUE: SHEET
NUMBER OF DETAIL
ROOM NAME AND
NUMBER
SMOKE DAMPER
OS
DL
a
OS
a a
A a
LCP
J
J
F1
DO
M a
XX-1
SB1(S) M
D
P (A
H P
A
(B
LP
A (C
T1
CR
CK
TV
CC
DC
ES
IC
ML
RX
REX
MD
XXX
X-XXX
X
F
F
F
CO
T
CO
DH
DCL
XXX
XXXX
XX
TV
WAP
ELECTRICAL GENERAL NOTES
1P 1 POLE (2P, 3P, 4P, ETC.)
A, AMP AMPERE
AC ABOVE COUNTER
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPERATOR
AF AMP FRAME
AFG ABOVE FINISHED GRADE
ALT ALTERNATE
AMP AMPERE
AMPL AMPLIFIER
ANNUN ANNUNCIATOR
APPROX APPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BD BOARD
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT
CAB CABINET
CAT CATALOG
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
CMPR COMPRESSOR
COMB COMBINATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
CONV CONVECTOR
CP CIRCULATING PUMP
CRT CATHODE-RAY TUBE
CT CURRENT TRANSFORMER
CTR CENTER
CU COPPER
DCP DOMESTIC WATER CIRCULATING PUMP
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DPR DAMPER
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
ELU EMERGENCY LIGHTING UNIT
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
FABP FIRE ALARM BOOSTER POWER SUPPLY PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN CONTROL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HOA HANDS-OFF-AUTOMATIC SWITCH
HORIZ HORIZONTAL
HP HORSEPOWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
I/W INTERLOCK WITH
ELECTRICAL GENERAL NOTES
1 CONDUCTORS OPERATING AT 50 VOLTS OR GREATER SHALL BE
IN RACEWAY. RACEWAY WITHIN THE STRUCTURE ABOVE THE
FLOOR SLAB SHALL BE METAL. RACEWAY BELOW THE FLOOR
SLAB AND UNDERGROUND RACEWAY OUTSIDE THE STRUCTURE
SHALL BE PVC.
2 LOW VOLTAGE CABLES OR CONDUCTORS OPERATING AT LESS
THAN 50 VOLTS SHALL BE IN METAL RACEWAY WHERE
INSTALLED WITHIN WALLS OR INACCESSIBLE SPACES. LOW
VOLTAGE CABLES MAY BE RUN IN CABLE TRAY WHERE NOTED.
LOW VOLTAGE CABLES MAY BE RUN IN CABLE SUPPORT HOOKS
ABOVE ACCESSIBLE CEILINGS WHERE NOTED. LOW VOLTAGE
CABLE SHALL BE PLENUM RATED IN PLENUM SPACES.
3 LOW VOLTAGE CABLES OR CONDUCTORS OPERATING AT LESS
THAN 50 VOLTS SHALL BE IN METAL RACEWAY. LOW VOLTAGE
CABLES MAY BE RUN IN CABLE TRAY WHERE NOTED. LOW
VOLTAGE CABLE SHALL BE PLENUM RATED IN PLENUM SPACES.
4 COORDINATE LOCATIONS OF DEVICES WITH ARCHITECTURAL
ELEVATIONS AND DETAILS. ARCHITECTURAL ELEVATIONS AND
DETAILS TAKE PRECEDENCE OVER LOCATIONS SHOWN ON
ELECTRICAL DRAWINGS.
5 PROVIDE CABLE OR CONDUIT AND WIRE AS REQUIRED TO
ACHIEVE CIRCUITING SHOWN. SIZE CONDUCTORS PER NEC
AMPACITY AND WIRE FILL CRITERIA. PROVIDE DEDICATED
NEUTRAL AND GROUND CONDUCTORS FOR CIRCUITING, UNLESS
NOTED OTHERWISE. INCREASE BRANCH CIRCUIT AND/OR
FEEDER CONDUCTORS INCLUDING EQUIPMENT GROUNDING
CONDUCTORS PROPORTIONALLY FOR NO MORE THAN 3%
VOLTAGE DROP ON BRANCH CIRCUITS AND 2%ON FEEDERS PER
ENERGY CODE.
6 IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO
COORDINATE INSTALLATION OF ELECTRICAL SYSTEMS AND
THOSE REQUIRING ELECTRICAL CONNECTIONS TO MAINTAIN
NEC REQUIRED CLEARANCES, INCLUDED BUT NOT LIMITED TO
AREAS ABOVE ACCESSIBLE CEILINGS.
7 COORDINATE WITH OTHER TRADES FOR PROPER INSTALLATION
OF EQUIPMENT. CONSULT THE DRAWINGS OF OTHER TRADES
OR CRAFTS TO AVOID CONFLICTS WITH EQUIPMENT, ETC.
CONFLICTS SHALL BE RESOLVED PRIOR TO ROUGH-IN AND AT NO
ADDITIONAL COST TO THE OWNER.
8 LEAVE THE SITE CLEAN AND READY FOR OCCUPANCY. REMOVE
DIRT, DEBRIS, EMPTY CARTONS, TOOLS, CONDUIT AND WIRE
SCRAPS, AND MISCELLANEOUS SPARE EQUIPMENT AND
MATERIALS USED IN THIS DIVISION OF THE WORK DURING
CONSTRUCTION. COMPONENTS SHALL BE FREE OF DUST, GRIT,
AND FOREIGN MATERIALS AND LEFT AS NEW BEFORE FINAL
ACCEPTANCE OF WORK.
9 THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET
MAY OR MAY NOT BE USED IN THIS SET OF DRAWINGS.
10 PERFORM WORK TO COMPLY WITH THE STANDARD PRACTICES
FOR GOOD WORKMANSHIP PUBLISHED BY NATIONAL
ELECTRICAL CONTRACTORS ASSOCIATION (NECA). COMPLY WITH
THE LATEST ENFORCED EDITION OF THE NATIONAL ELECTRICAL
CODE (NEC), LOCAL CODES, AMENDMENTS, AND ORDINANCES.
11 FIELD COORDINATE FINAL MECHANICAL AND EQUIPMENT
LOCATIONS ALONG WITH CONNECTION REQUIREMENTS AND
CONTROL WIRING PRIOR TO ROUGH-IN. ADJUST
CORRESPONDING CIRCUIT BREAKER RATINGS AND BRANCH
CIRCUITING ACCORDINGLY.
12 ELECTRICAL WORK SHALL BE PERFORMED UNDER THE
SUPERVISION OF A LICENSED MASTER ELECTRICIAN. PROCURE
PERMITS AND LICENSES AND PAY FEES ASSOCIATED WITH THIS
WORK.
13 MATERIALS FURNISHED FOR THIS PROJECT SHALL BE NEW,
COMMERCIAL GRADE, FREE OF DEFECTS, AND LISTED BY A
NATIONALLY RECOGNIZED TESTING LABORATORY UNLESS
NOTED OTHERWISE.
14 PROVIDE COMPLETE OPERATION & MAINTENANCE MANUAL
INCLUDING APPROVED SUBMITTAL DRAWINGS, WARRANTY
INFORMATION FOR PRODUCT SUPPLIED, AND MANUFACTURES
OPERATION AND MAINTENANCE INSTRUCTIONS.
15 THE CONTRACTOR IS RESPONSIBLE FOR MAKING FINAL WIRING
TERMINATIONS TO PRE-INSTALLED RECEPTACLES IN OFFICE
FURNITURE. CONTRACTOR IS RESPONSIBLE FOR WIRING AND
INSTALLING VOICE/DATA DEVICES IN OFFICE FURNITURE.
COORDINATE PLACEMENT OF DEVICES WITH FURNITURE
LAY-OUT.
16 NOT USED
17 CONDUIT AND WIRE SHALL NOT BE INSTALLED BELOW FLOOR
SLAB UNLESS INDICATED ON PLAN BY DASHED CONDUIT.
18 CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ELECTRICAL
ITEMS SHOWN ON DRAWINGS EXCEPT FOR ITEMS LISTED IN
NOTE ‘R’ BELOW.
19 TV OUTLETS, VOLUME CONTROLS, NURSE CALL DOME LIGHTS,
NURSE CALL DEVICES, TELEPHONE OUTLETS, DATA OUTLETS,
AND FIRE ALARM DEVICES SHALL CONSIST OF A BACK BOX WITH
CONDUIT STUBBED ABOVE THE ACCESSIBLE CEILING, SEE STUB
UP DETAIL. VERIFY SIZE OF BACK BOX REQUIRED WITH DEVICE
TO BE INSTALLED. LOCATE BACK BOXES 6" FROM ADJACENT
POWER RECEPTACLE INTENDED FOR COMPUTER USE.
20 FURNISH AND INSTALL CONDUIT FROM BACK BOXES FOR THE
FOLLOWING DEVICES INTO THE ACCESSIBLE CEILING SPACE IN
THE CORRIDOR, UNLESS NOTED OTHERWISE:
1/2"C TV OUTLETS
1/2"C VOLUME CONTROLS
1/2"CDOOR SECURITY DEVICES (CARD READERS, DOOR STRIKES
ETC..)
1/2"C NURSE CALL DOME LIGHTS
3/4"C NURSE CALL DEVICES
3/4"C TELEPHONE OUTLETS
3/4"C INFORMATION OUTLETS
3/4"C FIRE ALARM DEVICES
E
W A
S H
I N
G T
O N
M O
U N
T P
L E
A S
A N
T
I O
W A
DATE:
DRAWN BY:
PROJECT NO:
COPYRIGHT
SHEET TITLE
M
IC
H A
E L
H O
R
IZ
O N
-A R
C H
IT
E
C T
U R
E .C
O M
P H
-4
W W
W .H
O R
IZ
O
N -A
R C
H
IT
E C
T U
R E
.C O
M
IS
S
U E
D F
O R
P E
R M
IT
A
N D
C O
N S
T R
U C
T
IO
N
WWW.AXIOM-CON.COM | 319.519.6220
ELECTRICAL
SYMBOLS
E-001
.0
D O
C M
P C
F N
E W
A P
P R
E N
T I C
E S
H I P
B U
I L D
I N
G
240027
SMF
06/07/2024
ELECTRICAL GENERAL NOTES
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LOC LOCATE OF LOCATION
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
M/C MOMENTARY CONTACT
MAG.S MAGNETIC STARTER
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MSP MOTOR STARTER PANELBOARD
MSS MOTOR STARTER SWITCH
MT MOUNT
MT.C EMPTY CONDUIT
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
N.C. NORMALLY CLOSED
N.O. NORMALLY OPEN
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURER'S
ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
OC ON CENTER
OH OVERHEAD
OL OVERLOADS
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PP POWER POLE
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATION
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QUAN QUANTITY
RCPT RECEPTACLE
REQD REQUIRED
RM ROOM
RSC RIGID STEEL CONDUIT
RTU ROOF TOP UNIT
S/N SOLID NEUTRAL
S/S STOP/START PUSHBUTTONS
SC SURFACE CONDUIT
SEC SECONDARY
SHT SHEET
SIM SIMILAR
SLD SINGLE-LINE DIAGRAM
SP SPARE
SPEC SPECIFICATION
SPKR SPEAKER
SPP SINGLE-POINT POWER
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STA STATION
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
ELECTRICAL GENERAL NOTES
SYS SYSTEM
T-STAT THERMOSTAT
TEL TELEPHONE
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL CABINET
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UH UNIT HEATER
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UV ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
W WATT
W/ WITH
W/O WITHOUT
WG WIRE GUARD
WH WATER HEATER
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
AFF ABOVE FINISHED FLOOR
AFI ARC FAULT CIRCUIT INTERRUPTER
AHU AIR HANDLING UNIT
AL ALUMINUM
VDT VIDEO DISPLAY TERMINAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
@ AT
' FEET
" INCHES
# NUMBER
C CENTER LINE
P PLATE
M A R K
D
A T E
S C R
IP
T
IO
N
/2
/2
A d d e n d u m
ADD
OCCUPANCY SENSOR
V A
C A
N C
Y M
O
(M
N U
A L
O N
O C
C U
P A
N C
Y
M O
D E
A
U T
O O
N
SMALL BAY/AUTO REPAIR GARAGE
ROOM NAME
LIGHTING SEQUENCE OF OPERATION
TIME CLOCK WALL SWITCH DAYLIGHT SENSOR
D U
A L
T E
C H
N O
LO
G
Y
S C
H E
D U
LE
O
N T
IM
E
S C
H E
U
LD
E O
F F
T
IM
E
S C
H E
D U
LE
O V
E R
R
ID
E S
W
IT
C H
M A
N U
A L
(O N
/O F
F
M A
N U
A L
D
IM
M
IN
G
S W
IT
C
H
IN
G
(O N
/O F
F
N O
T E
S
OTHER
P H
O T
O C
E
LL
P A
S S
IV
E
I R
N E
T W
O R
K E
D
1. L1EM FIXTURE SHOULD BE ON AN UN CONTROLLED NIGHT LIGHT CIRCUIT.
2. BATHROOM: PROVIDE WALL SWITCH WITH BUILT IN PIR OCC SENSOR – LUTRON MS-OPS2
3. MECH ROOM: PROVIDE ON/OFF TOGGLE SWITCH
4. EXTERIOR FIXTURES CONTROLLED VIA INTEGRAL PHOTOCELL
RESTROOM
MECHANICAL
X X
X
X
EXTERIOR
4X
1st FLOOR
0"
ROOF
192"
1ST FLOOR
0"
ROOF
16' - 0"
W2
W1-EM
W2
1st FLOOR
0"
ROOF
192"
1 2
1ST FLOOR
0"
ROOF
16' - 0"
1 2
W2
W1-EM
E
W A
S H
I N
G T
O N
M O
U N
T P
L E
A S
A N
T
I O
W A
DATE:
DRAWN BY:
PROJECT NO:
COPYRIGHT
SHEET TITLE
M
IC
H A
E L
H O
R
IZ
O N
-A R
C H
IT
E
C T
U R
E .C
O M
P H
-4
W W
W .H
O R
IZ
O
N -A
R C
H
IT
E C
T U
R E
.C O
M
IS
S
U E
D F
O R
P E
R M
IT
A
N D
C O
N S
T R
U C
T
IO
N
WWW.AXIOM-CON.COM | 319.519.6220
ELECTRICAL
LIGHTING
SCHEDULES
E-602
.0
D O
C M
P C
F N
E W
A P
P R
E N
T I C
E S
H I P
B U
I L D
I N
G
240027
SMF
06/07/2024
LIGHTING SCHEDULE
TAG SYMBOL MANUFACTURER MODEL NUMBER DESCRIPTION MOUNTING
TOTAL
LUMENS
LAMP CCT CRI VOLTAGE WATTS
EMERGENCY
COMPONENT
NOTES
D1 PRESCOLITE
LBRST-6RD-M-LSML-CS9-W
H-34
6"
DOWNLIGHT
CEILING 2502 lm INTEGRAL LED 40 K 90 120 V 31 W
EXIT COMPASS COM CE EXIT SIGN WALL | 8' 0 lm INTEGRAL LED 0 K 0 120 V 2 W INTEGRAL BATTERY
L1 LUX DYNAMICS
HIGH-4-6LM-840-U10-SM-
WA-OC-KO
4' STRIP CEILING | 16' 15488 lm INTEGRAL LED 40 K 80 120 V 107 W
L1-EM LUX DYNAMICS
HIGH-4-6LM-840-U10-SM-
WA-E20RL-OC-KO
4' STRIP CEILING | 16' 15488 lm INTEGRAL LED 40 K 80 120 V 107 W INTEGRAL BATTERY
W1-EM ILP
OWM-3L/5L-U-CCTS-BRZ-E
MCT8-PCU
WALL PACK WALL | 8' 5230 lm INTEGRAL LED 40 K 80 120 V 40 W INTEGRAL BATTERY
PROVIDE WITH PHOTOCELL
FIXTURE PROVIDED WITH
SWITCHABLE LUMEN OUTPUT
W2 ILP OWM-3L/5L-CCTS-BRZ-PCU WALL PACK VARIES 5230 lm INTEGRAL LED 40 K 80 120 V 40 W PROVIDE WITH PHOTOCELL
3/16" = 1'-0" E-602
1EAST EXTERIOR LIGHTING_
3/16" = 1'-0" E-602
2WEST EXTERIOR ELEVATION_
M A R K
T
S C R
IP
T
IO
N
/2
/2
A d d e n d u m
NOTES: PROVIDE ALL BRACKETS, MOUNTING PLATES AND SUPPORTS AS REQUIRED FOR INSTALLATION.
ADD
File details come from the government source that posted it. Updated .