RFB 938300-01 Addendum #3.pdf

PDF 435 KB Posted

Attached to
DOC MPCF Apprenticeship Building
Solicitation number
RFB938300-01
Issued by
Henry County, Iowa

About this file

This document is an Addendum #3 to a Request for Bids (RFB) for the DOC MPCF New Apprenticeship Building project at the Mount Pleasant Correctional Facility in Mount Pleasant, Iowa. The RFB is being issued by the Iowa Department of Administrative Services. The addendum provides responses to questions related to electrical and data routing, builder's risk insurance, building permit fees, water and electrical connections, and in-floor heating system requirements. It also includes a list of approved substitutions and revisions to the electrical drawings and symbols. The project involves the construction of a new apprenticeship building at the correctional facility.

The addendum does not provide details on pricing, set asides, incumbents, funding sources, or other salient contract information. It is focused on technical clarifications and changes to the bid documents.

View the file

Other files

File Type Posted
RFB938300-01 - Bid Form.pdf PDF
RFB938300-01 - Project Manual.pdf PDF
RFB 938300-01 Addendum #2.pdf PDF
RFB938300-01 - Drawings.pdf PDF
RFB938300-01 - Notice.pdf PDF
RFB 938300-01 Addendum #1.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ADDENDUM #3

Project Name: DOC MPCF New Apprenticeship Building

DAS#9383.00

RFB938300-01

Addendum #3

Dated: July 29, 2024

This Addendum forms a part of the Request For Bids documents. This Addendum supersedes and supplements all portions of the original Request For Bids with which it conflicts.

ACKNOWLEDGE RECEIPT OF THIS ADDENDUM IN THE REQUEST FOR PROPOSAL. FAILURE TO

DO SO MAY SUBJECT TO DISQUALIFICATION.

1. Questions:

a. How is electrical and data getting to building if alternate is not done? Answer: Electrical and data would still be routed down the existing tunnel, contractor to provide pathway from existing tunnel to new building mechanical room.

b. Is Builder’s Risk insurance provided by the owner, or is it by contractor? Answer: By owner

c. Who is responsible for the building permit fee? Answer: No building permit required.

d. Water and electrical connection are to be by owner, but usage rates and temp installs are to be by

Contractor? Can you please confirm this? Answer: Water and electrical connections will be provided by the owner, contractor to connect. Usage rates/monitoring not needed.

e. Looking through the drawing for option three on the in-floor heat. I don’t see drawings or equipment for the two in floor heat loops to connect to anything. Are we just installing the tubing and the two headers as the option for this project or is there equipment and piping drawings to make this a operating system. Answer: You are to install the tubing, headers, and insulation as shown on the drawings. Provide pathway from building to existing tunnel as drawings indicate. Owner to provide and install other ancillary equipment at a later date.

f. Please clarify the required PEMB insulation requirements in the walls and roof? There are several conflicting notes on the drawings and specs. Answer: Requirements are per 2012

IECC: Roof – R-19 + R-11 Liner System. Walls – R-13 + R-13ci or system U-Value of 0.052 or better (Simple Saver or similar).

2. Substitution Requests:

a. Spec Section: 23 3416 HVAC Power Ventilators

Item: Sidewall Axial Fans

Manufacturer: JencoFan by S&P, Twin City Fan

b. Item: Restroom Ceiling Exhaust Fans

Manufacturer: Soler Palau, Twin City Fan

c. Spec Section: 23 8239 Electric Unit Heaters

Item: Unit Heaters

Manufacturer: Redd-I of TPI Corp

d. Spec Section: 23 0923 Gas Instruments

Item: CO / NO2 Gas Detection System

Manufacturer: Honeywell Analytics

e. Spec Section: 08 9119 Louvers

Item: Sidewall Louver

Manufacturer: United Enertech

f. Spec Section: 26 5100 Interior Lighting

Item/Manufacturer:

D1| Lithonia, Halo

Exit| Lithonia, Sure-Lites

L1/L1-EM| Lithonia

W1-EM| Lithonia, Halo

W2| Lithonia, Halo

3. Drawings:

a. Drawing E-001 Electrical Symbols

1. Removed Note-16

b. Drawing E-602 Electrical Lighting Schedules

1. Updated Lighting Schedule

4. Attachments:

a. Drawing E-001 Electrical Symbols

b. Drawing E-602 Electrical Lighting Schedules

END OF ADDENDUM

ELECTRICAL ABBREVIATIONS

ELECTRICAL DEVICE TAGS: UPPERCASE LETTER(S)

INDICATES PANEL ID AND CIRCUIT NUMBER.

LOWERCASE LETTER INDICATES DESIGNATION OF

CONTROLLING SWITCH (WHERE APPLICABLE).

SWITCH ID INDICATED BY A LOWERCASE LETTER.

SWITCH IDS ARE UNIQUE PER SPACE. A SWITCH WITH

AN ID "A" CONTROLS ALL DEVICES WITHIN THE SPACE

IN WHICH IT IS LOCATED TAGGED WITH "A". A

SWITCH WITHOUT A TAGGED ID CONTROLS ALL

LIGHTING FIXTURES WITHIN A SPACE. ID TAGS MAY BE

USED ON CONTROL DEVICES OTHER THAN SWITCHES,

SUCH AS OCCUPANCY SENSORS OR CONTACTORS.

EQUIPMENT TAGS: EQUIPMENT ID IS INDICATED BY

AN UNDERLINED TAG ADJACENT TO THE

EQUIPMENT. SEE THE EQUIPMENT CONNECTION

SCHEDULE FOR DESCRIPTION, ELECTRICAL

REQUIREMENTS, AND PANEL AND CIRCUIT

NUMBER. SYMBOLS/GRAPHIC APPEARANCE OF

EQUIPMENT VARIES.

SOLID, ARCED LINES CONNECTING EQUIPMENT,

DEVICES, OR FIXTURES INDICATE UNSWITCHED

POWER CIRCUITING. WIRES ARE ONLY INTENDED

TO INDICATE TO WHAT CIRCUIT DEVICES ARE

CONNECTED. ACTUAL CONNECTIONS, CIRCUIT

ROUTING, INSTALLATION, JUNCTION BOXES, ETC.

SHALL BE FIELD-DETERMINED BY THE CONTRACTOR.

HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE

EQUIPMENT NAME AND CIRCUIT NUMBER(S) ARE

INDICATED, SEPARATED BY A HYPHEN. HOMERUNS

ARE ONLY INTENDED TO INDICATE PANEL AND

CIRCUIT NUMBER. ACTUAL HOMERUN LOCATION

SHALL BE FIELD-DETERMINED BY THE CONTRACTOR.

POWER SYMBOLS

ELECTRICAL SYMBOL LEGEND

EXIT LIGHT, WALL-MOUNTED.

SHADING AND ARROWS INDICATE FACES AND

DIRECTIONAL CHEVRONS.

WALL-MOUNTED FIXTURES, TYPICAL

(VARIOUS SYMBOLS)

EMERGENCY LIGHTING UNIT, WALL-MOUNTED,

REMOTE BATTERY

EMERGENCY LIGHTING UNIT, WALL-MOUNTED,

INTEGRAL BATTERY

EMERGENCY LIGHTING UNIT, CEILING-MOUNTED,

INTEGRAL BATTERY

EMERGENCY LIGHTING UNIT, CEILING-MOUNTED,

REMOTE BATTERY

LIGHTING FIXTURES, TYPICAL, RECTANGULAR

(VARIOUS SYMBOLS)

FILLED CIRCLES INDICATE RECESSED.

OPEN CIRCLES INDICATE SURFACE-MOUNTED.

DIAGONAL LINE INDICATES LENSED.

OUTER DOTS INDICATE SUSPENDED.

LIGHTING FIXTURES, TYPICAL, ROUND

(VARIOUS SYMBOLS)

CENTER DOT INDICATES PENDANT.

DIAGONAL LINE INDICATES LENSED.

CHEVRON INDICATES WALL WASH.

STRIP FIXTURE

DIRECTIONAL LIGHT, TRACK LIGHT, FLOOD LIGHT

EXIT LIGHT, CEILING-MOUNTED.

SHADING AND ARROWS INDICATE FACES AND

DIRECTIONAL CHEVRONS.

LINEAR LIGHT, TAPE LIGHT

EXIT/ELU COMBO

DIAGONAL HATCH INDICATES LIGHT ON AN

EMERGENCY OR LIFE SAFETY CIRCUIT.

PROPOSED LIGHT FIXTURE

POLE/AREA LIGHTS

POST-TOP AREA LIGHT

BOLLARD LIGHT

SINGLE-POLE SWITCH

THREE-POLE SWITCH

SWITCH MODIFIERS:

3: 3-WAY

4: 4-WAY

K: KEYED

D: DIMMING

T: TIMER

V: VOLUME

OS: OCCUPANCY SENSOR

VS: VACANCY SENSOR

AC: ABOVE-COUNTER

LV: LOW-VOLTAGE

M: MOTOR-RATED

LIGHTING CONTACTOR

LIGHTING CONTROL PANEL

OCCUPANCY SENSOR

DAYLIGHT HARVESTING SENSOR

SMOKE DETECTOR

HEAT DETECTOR

CARBON MONOXIDE DETECTOR

BEAM DETECTOR T: TRANSMITTER R:

RECEIVER

COMBINATION DETECTOR (UP TO

THREE)

DUCT SMOKE DETECTOR

MANUAL PULL STATION

HORN, WALL

HORN, CEILING

STROBE, WALL, CANDELA AS

INDICATED

STROBE, CEILING, CANDELA AS

INDICATED

HORN/STROBE, WALL, CANDELA AS

INDICATED

HORN/STROBE, CEILING, CANDELA AS

INDICATED

REMOTE INDICATOR W/ TEST

SWITCH, WALL

REMOTE INDICATE W/ TEST SWITCH,

CEILING

DOOR HOLDER

DOOR CLOSER

FIRE SERVICE PHONE

ADDRESSABLE MODULE

AIM: ADDRESSABLE INPUT

MODULE

AOM:ADDRESSABLE OUTPUT

CONTROL MODULE

AIO: ADDRESSABLE INPUT/OUTPUT

MODULEFIRE ALARM CONTROL UNIT

EVAC: VOICE EVACUATION

CONTROL PANEL

FAA: FIRE ALARM ANNUNCIATOR

FACP: FIRE ALARM CONTROL

PANEL

FATC: FIRE ALARM TERMINAL

CABINET

NACP: NOTIFICATION APPLIANCE

CIRCUIT PANEL

FAMN: FIRE ALARM MASS

NOTIFICATION CONTROL PANEL

SUPERVISORY OR INTERFACE DEVICE

PIV: POST INDICATOR VALVE

SUPERVISORY

PS: PRESSURE SWITCH

R: NON-ADDRESSABLE RELAY

VS: VALVE SUPERVISORY SWITCH

WF: WATER FLOW SWITCH

SIMPLEX RECEPTACLE

DUPLEX RECEPTACLE

QUADRUPLEX RECEPTACLE

SPECIAL RECEPTACLE, TYPE AS INDICATED

W A

LL

C E

IL

IN

G

F

LO

O R

RECEPTACLE MODIFIERS:

##": HEIGHT AFF OC

AC: ABOVE COUNTER

GFI: GROUND-FAULT CIRCUIT INTERRUPTER

WP: WEATHERPROOF IN-USE COVER

HALF SHADING INDICATES SPLIT

(TYPICALLY SWITCHED)

OUTSIDE SHADING INDICATES

EMERGENCY CIRCUIT

CENTER SHADING INDICATES

ISOLATED GROUND

MULTIOUTLET ASSEMBLY

FILLED SQUARES INDICATE 120V OUTLET

OPEN SQUARES INDICATE WITH USB

CORD REEL, DEVICE VARIES

DROP CORD, DEVICE VARIES

JUNCTION BOX

FLOOR BOX, SEE SCHEDULE FOR TYPE

EMERGENCY POWER OFF

DOOR OPENER PUSH PLATE

POWER METER

SAFETY SWITCH, FUSED

SAFETY SWITCH, UNFUSED

MOTOR STARTER

COMBINATION STARTER/DISCONNECT

GROUND ROD

GROUND ROD WITH TEST WELL

LIGHTNING PROTECTION AIR TERMINAL

LIGHTNING PROTECTION CONDUCTOR SPLICE

STATIC GROUND RECEPTACLE

DATA OUTLET

TELEPHONE OUTLET

DATA/TELEPHONE OUTLET

W A

LL

C E

IL

IN

G

F

LO

O R

OUTLET MODIFIERS:

##": HEIGHT AFF OC

AC: ABOVE COUNTER

WIRELESS ACCESS POINT

TV OUTLET

LIGHTING SYMBOLS

CONTACTOR

FIRE ALARM SYMBOLS

GROUNDING AND LIGHTNING PROTECTION SYMBOLS

SECURITY CAMERA

PTZ: PAN/TILT/ZOOM

CARD READER

CARD READER WITH KEYPAD

CLOSED CIRCUIT TV OUTLET

DOOR CONTACT

ELECTRIC STRIKE

INTERCOM

MAGNETIC LOCK

REQUEST TO EXIT BUTTON

REQUEST TO EXIT SENSOR

MOTION DETECTOR

SECURITY CONTROL UNIT

SCP: SECURITY CONTROL PANEL

SPS: SECURITY POWER SUPPLY

UNIT

TELECOM SYMBOLS

SECURITY SYMBOLS

EQUIPMENT IS TAGGED WITH PANEL NAME AND WITH

PANEL ID IN PARENTHESES. PANEL ID IS INTENDED AS A

DESIGN DOCUMENTATION AID ONLY. DO NOT INCLUDE

PANEL ID IN FIELD-APPLIED CIRCUIT DIRECTORIES OR

LABELS.

HATCHED FILL INDICATES DISTRIBUTION PANEL OR

SWITCHBOARD.

SOLID FILL INDICATES BRANCH PANEL OR LOAD CENTER.

DASHED BOX INDICATES CODE-REQUIRED CLEARANCE

(WIDTH AND DEPTH).

DOOR INDICATES FRONT OF RECESSED PANEL.

PANELBOARDS ARE ASSIGNED AN ABBREVIATED INDICATOR

(OR PANEL ID) FOR USE WITH CIRCUIT NUMBERS. PANEL ID

IS LISTED WITHIN THE PANEL SCHEDULE AND IN THE PANEL

ABBREVIATION SCHEDULE.

POWER DISTRIBUTION EQUIPMENT

DEVICES AND FIXTURES ARE TAGGED WITH PANEL ID AND

CIRCUIT NUMBER. FOR EXAMPLE, A DEVICE TAGGED WITH

"A1" INDICATES THE DEVICE IS CIRCUITED TO PANEL

DESIGNATED "A," CIRCUIT NUMBER 1. THE PANEL

SCHEDULE CIRCUIT NUMBER CONTAINS BOTH THE PANEL

ABBREVIATION AND THE CIRCUIT NUMBER.

TRANSFORMER: TYPICALLY TRANSFORMER NAMES

BEGIN WITH OR CONTAIN THE LETTER "T". SEE

SINGLE-LINE DIAGRAM FOR DESCRIPTION AND

REQUIREMENTS.

DASHED, ARCED LINES CONNECTING EQUIPMENT,

DEVICES, OR FIXTURES INDICATE SWITCHED POWER.

ABSENCE OF A SWITCH DESIGNATION ON A LIGHTING

FIXTURE INDICATES FIXTURE IS CONTROLLED BY THE ONLY

SWITCH IN THE SPACE. AN "X" IN PLACE OF THE SWITCH

DESIGNATION INDICATES UNSWITCHED.

BOTTOM VALUE, LOWERCASE LETTER: SWITCH ID

LIGHTING TAGS

TOP VALUE: FIXTURE TYPE ID

(UNDERLINED)

BOTTOM VALUE, UPPERCASE LETTER(S): PANEL ID

BOTTOM VALUE, NUMBER(S): CIRCUIT NUMBER

WIRING

POWER DEVICE AND EQUIPMENT TAGS

CONSTRUCTION PHASING

EXISTING TO REMAIN

EXISTING TO BE DEMOLISHED

NEW

(TYPICAL ALL SYMBOLS AND EQUIPMENT)

EXISTING TO BE

DEMOLISHED

AREA NOT IN

CONTRACT

MISCELLANEOUS

KEYNOTE

CALLOUT:

TOP VALUE: DETAIL NUMBER

ON SHEET

BOTTOM VALUE: SHEET

NUMBER OF DETAIL

ROOM NAME AND

NUMBER

SMOKE DAMPER

OS

DL

a

OS

a a

A a

LCP

J

J

F1

DO

M a

XX-1

SB1(S) M

D

P (A

H P

A

(B

LP

A (C

T1

CR

CK

TV

CC

DC

ES

IC

ML

RX

REX

MD

XXX

X-XXX

X

F

F

F

CO

T

CO

DH

DCL

XXX

XXXX

XX

TV

WAP

ELECTRICAL GENERAL NOTES

1P 1 POLE (2P, 3P, 4P, ETC.)

A, AMP AMPERE

AC ABOVE COUNTER

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPERATOR

AF AMP FRAME

AFG ABOVE FINISHED GRADE

ALT ALTERNATE

AMP AMPERE

AMPL AMPLIFIER

ANNUN ANNUNCIATOR

APPROX APPROXIMATELY

AQ-STAT AQUASTAT

ARCH ARCHITECT, ARCHITECTURAL

AS AMP SWITCH

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BATT BATTERY

BD BOARD

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

C CONDUIT

CAB CABINET

CAT CATALOG

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

CMPR COMPRESSOR

COMB COMBINATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

CONV CONVECTOR

CP CIRCULATING PUMP

CRT CATHODE-RAY TUBE

CT CURRENT TRANSFORMER

CTR CENTER

CU COPPER

DCP DOMESTIC WATER CIRCULATING PUMP

DEPT DEPARTMENT

DET DETAIL

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DPR DAMPER

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

ELU EMERGENCY LIGHTING UNIT

EM EMERGENCY

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EP ELECTRIC PNEUMATIC

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

FABP FIRE ALARM BOOSTER POWER SUPPLY PANEL

FACP FIRE ALARM CONTROL PANEL

FCU FAN CONTROL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FU FUSE

FUDS FUSED SAFETY DISCONNECT SWITCH

GA GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTOR

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BD GYPSUM BOARD

HOA HANDS-OFF-AUTOMATIC SWITCH

HORIZ HORIZONTAL

HP HORSEPOWER

HPF HIGH POWER FACTOR

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

I/W INTERLOCK WITH

ELECTRICAL GENERAL NOTES

1 CONDUCTORS OPERATING AT 50 VOLTS OR GREATER SHALL BE

IN RACEWAY. RACEWAY WITHIN THE STRUCTURE ABOVE THE

FLOOR SLAB SHALL BE METAL. RACEWAY BELOW THE FLOOR

SLAB AND UNDERGROUND RACEWAY OUTSIDE THE STRUCTURE

SHALL BE PVC.

2 LOW VOLTAGE CABLES OR CONDUCTORS OPERATING AT LESS

THAN 50 VOLTS SHALL BE IN METAL RACEWAY WHERE

INSTALLED WITHIN WALLS OR INACCESSIBLE SPACES. LOW

VOLTAGE CABLES MAY BE RUN IN CABLE TRAY WHERE NOTED.

LOW VOLTAGE CABLES MAY BE RUN IN CABLE SUPPORT HOOKS

ABOVE ACCESSIBLE CEILINGS WHERE NOTED. LOW VOLTAGE

CABLE SHALL BE PLENUM RATED IN PLENUM SPACES.

3 LOW VOLTAGE CABLES OR CONDUCTORS OPERATING AT LESS

THAN 50 VOLTS SHALL BE IN METAL RACEWAY. LOW VOLTAGE

CABLES MAY BE RUN IN CABLE TRAY WHERE NOTED. LOW

VOLTAGE CABLE SHALL BE PLENUM RATED IN PLENUM SPACES.

4 COORDINATE LOCATIONS OF DEVICES WITH ARCHITECTURAL

ELEVATIONS AND DETAILS. ARCHITECTURAL ELEVATIONS AND

DETAILS TAKE PRECEDENCE OVER LOCATIONS SHOWN ON

ELECTRICAL DRAWINGS.

5 PROVIDE CABLE OR CONDUIT AND WIRE AS REQUIRED TO

ACHIEVE CIRCUITING SHOWN. SIZE CONDUCTORS PER NEC

AMPACITY AND WIRE FILL CRITERIA. PROVIDE DEDICATED

NEUTRAL AND GROUND CONDUCTORS FOR CIRCUITING, UNLESS

NOTED OTHERWISE. INCREASE BRANCH CIRCUIT AND/OR

FEEDER CONDUCTORS INCLUDING EQUIPMENT GROUNDING

CONDUCTORS PROPORTIONALLY FOR NO MORE THAN 3%

VOLTAGE DROP ON BRANCH CIRCUITS AND 2%ON FEEDERS PER

ENERGY CODE.

6 IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO

COORDINATE INSTALLATION OF ELECTRICAL SYSTEMS AND

THOSE REQUIRING ELECTRICAL CONNECTIONS TO MAINTAIN

NEC REQUIRED CLEARANCES, INCLUDED BUT NOT LIMITED TO

AREAS ABOVE ACCESSIBLE CEILINGS.

7 COORDINATE WITH OTHER TRADES FOR PROPER INSTALLATION

OF EQUIPMENT. CONSULT THE DRAWINGS OF OTHER TRADES

OR CRAFTS TO AVOID CONFLICTS WITH EQUIPMENT, ETC.

CONFLICTS SHALL BE RESOLVED PRIOR TO ROUGH-IN AND AT NO

ADDITIONAL COST TO THE OWNER.

8 LEAVE THE SITE CLEAN AND READY FOR OCCUPANCY. REMOVE

DIRT, DEBRIS, EMPTY CARTONS, TOOLS, CONDUIT AND WIRE

SCRAPS, AND MISCELLANEOUS SPARE EQUIPMENT AND

MATERIALS USED IN THIS DIVISION OF THE WORK DURING

CONSTRUCTION. COMPONENTS SHALL BE FREE OF DUST, GRIT,

AND FOREIGN MATERIALS AND LEFT AS NEW BEFORE FINAL

ACCEPTANCE OF WORK.

9 THE SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET

MAY OR MAY NOT BE USED IN THIS SET OF DRAWINGS.

10 PERFORM WORK TO COMPLY WITH THE STANDARD PRACTICES

FOR GOOD WORKMANSHIP PUBLISHED BY NATIONAL

ELECTRICAL CONTRACTORS ASSOCIATION (NECA). COMPLY WITH

THE LATEST ENFORCED EDITION OF THE NATIONAL ELECTRICAL

CODE (NEC), LOCAL CODES, AMENDMENTS, AND ORDINANCES.

11 FIELD COORDINATE FINAL MECHANICAL AND EQUIPMENT

LOCATIONS ALONG WITH CONNECTION REQUIREMENTS AND

CONTROL WIRING PRIOR TO ROUGH-IN. ADJUST

CORRESPONDING CIRCUIT BREAKER RATINGS AND BRANCH

CIRCUITING ACCORDINGLY.

12 ELECTRICAL WORK SHALL BE PERFORMED UNDER THE

SUPERVISION OF A LICENSED MASTER ELECTRICIAN. PROCURE

PERMITS AND LICENSES AND PAY FEES ASSOCIATED WITH THIS

WORK.

13 MATERIALS FURNISHED FOR THIS PROJECT SHALL BE NEW,

COMMERCIAL GRADE, FREE OF DEFECTS, AND LISTED BY A

NATIONALLY RECOGNIZED TESTING LABORATORY UNLESS

NOTED OTHERWISE.

14 PROVIDE COMPLETE OPERATION & MAINTENANCE MANUAL

INCLUDING APPROVED SUBMITTAL DRAWINGS, WARRANTY

INFORMATION FOR PRODUCT SUPPLIED, AND MANUFACTURES

OPERATION AND MAINTENANCE INSTRUCTIONS.

15 THE CONTRACTOR IS RESPONSIBLE FOR MAKING FINAL WIRING

TERMINATIONS TO PRE-INSTALLED RECEPTACLES IN OFFICE

FURNITURE. CONTRACTOR IS RESPONSIBLE FOR WIRING AND

INSTALLING VOICE/DATA DEVICES IN OFFICE FURNITURE.

COORDINATE PLACEMENT OF DEVICES WITH FURNITURE

LAY-OUT.

16 NOT USED

17 CONDUIT AND WIRE SHALL NOT BE INSTALLED BELOW FLOOR

SLAB UNLESS INDICATED ON PLAN BY DASHED CONDUIT.

18 CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ELECTRICAL

ITEMS SHOWN ON DRAWINGS EXCEPT FOR ITEMS LISTED IN

NOTE ‘R’ BELOW.

19 TV OUTLETS, VOLUME CONTROLS, NURSE CALL DOME LIGHTS,

NURSE CALL DEVICES, TELEPHONE OUTLETS, DATA OUTLETS,

AND FIRE ALARM DEVICES SHALL CONSIST OF A BACK BOX WITH

CONDUIT STUBBED ABOVE THE ACCESSIBLE CEILING, SEE STUB

UP DETAIL. VERIFY SIZE OF BACK BOX REQUIRED WITH DEVICE

TO BE INSTALLED. LOCATE BACK BOXES 6" FROM ADJACENT

POWER RECEPTACLE INTENDED FOR COMPUTER USE.

20 FURNISH AND INSTALL CONDUIT FROM BACK BOXES FOR THE

FOLLOWING DEVICES INTO THE ACCESSIBLE CEILING SPACE IN

THE CORRIDOR, UNLESS NOTED OTHERWISE:

1/2"C TV OUTLETS

1/2"C VOLUME CONTROLS

1/2"CDOOR SECURITY DEVICES (CARD READERS, DOOR STRIKES

ETC..)

1/2"C NURSE CALL DOME LIGHTS

3/4"C NURSE CALL DEVICES

3/4"C TELEPHONE OUTLETS

3/4"C INFORMATION OUTLETS

3/4"C FIRE ALARM DEVICES

E

W A

S H

I N

G T

O N

M O

U N

T P

L E

A S

A N

T

I O

W A

DATE:

DRAWN BY:

PROJECT NO:

COPYRIGHT

SHEET TITLE

M

IC

H A

E L

H O

R

IZ

O N

-A R

C H

IT

E

C T

U R

E .C

O M

P H

-4

W W

W .H

O R

IZ

O

N -A

R C

H

IT

E C

T U

R E

.C O

M

IS

S

U E

D F

O R

P E

R M

IT

A

N D

C O

N S

T R

U C

T

IO

N

WWW.AXIOM-CON.COM | 319.519.6220

ELECTRICAL

SYMBOLS

E-001

.0

D O

C M

P C

F N

E W

A P

P R

E N

T I C

E S

H I P

B U

I L D

I N

G

240027

SMF

06/07/2024

ELECTRICAL GENERAL NOTES

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LOC LOCATE OF LOCATION

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

M/C MOMENTARY CONTACT

MAG.S MAGNETIC STARTER

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDC MAIN DISTRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOA MULTIOUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MSP MOTOR STARTER PANELBOARD

MSS MOTOR STARTER SWITCH

MT MOUNT

MT.C EMPTY CONDUIT

MTR MOTOR, MOTORIZED

MTS MANUAL TRANSFER SWITCH

N.C. NORMALLY CLOSED

N.O. NORMALLY OPEN

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURER'S

ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NPF NORMAL POWER FACTOR

NTS NOT TO SCALE

OC ON CENTER

OH OVERHEAD

OL OVERLOADS

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PE PNEUMATIC ELECTRIC

PED PEDESTAL

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

PP POWER POLE

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATION

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QUAN QUANTITY

RCPT RECEPTACLE

REQD REQUIRED

RM ROOM

RSC RIGID STEEL CONDUIT

RTU ROOF TOP UNIT

S/N SOLID NEUTRAL

S/S STOP/START PUSHBUTTONS

SC SURFACE CONDUIT

SEC SECONDARY

SHT SHEET

SIM SIMILAR

SLD SINGLE-LINE DIAGRAM

SP SPARE

SPEC SPECIFICATION

SPKR SPEAKER

SPP SINGLE-POINT POWER

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

STA STATION

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

ELECTRICAL GENERAL NOTES

SYS SYSTEM

T-STAT THERMOSTAT

TEL TELEPHONE

TERM TERMINAL

TL TWIST LOCK

TR TAMPER RESISTANT

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TVTC TELEVISION TERMINAL CABINET

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UH UNIT HEATER

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UV ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VERT VERTICAL

W WATT

W/ WITH

W/O WITHOUT

WG WIRE GUARD

WH WATER HEATER

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

AFF ABOVE FINISHED FLOOR

AFI ARC FAULT CIRCUIT INTERRUPTER

AHU AIR HANDLING UNIT

AL ALUMINUM

VDT VIDEO DISPLAY TERMINAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

@ AT

' FEET

" INCHES

# NUMBER

C CENTER LINE

P PLATE

M A R K

D

A T E

S C R

IP

T

IO

N

/2

/2

A d d e n d u m

ADD

OCCUPANCY SENSOR

V A

C A

N C

Y M

O

(M

N U

A L

O N

O C

C U

P A

N C

Y

M O

D E

A

U T

O O

N

SMALL BAY/AUTO REPAIR GARAGE

ROOM NAME

LIGHTING SEQUENCE OF OPERATION

TIME CLOCK WALL SWITCH DAYLIGHT SENSOR

D U

A L

T E

C H

N O

LO

G

Y

S C

H E

D U

LE

O

N T

IM

E

S C

H E

U

LD

E O

F F

T

IM

E

S C

H E

D U

LE

O V

E R

R

ID

E S

W

IT

C H

M A

N U

A L

(O N

/O F

F

M A

N U

A L

D

IM

M

IN

G

S W

IT

C

H

IN

G

(O N

/O F

F

N O

T E

S

OTHER

P H

O T

O C

E

LL

P A

S S

IV

E

I R

N E

T W

O R

K E

D

1. L1EM FIXTURE SHOULD BE ON AN UN CONTROLLED NIGHT LIGHT CIRCUIT.

2. BATHROOM: PROVIDE WALL SWITCH WITH BUILT IN PIR OCC SENSOR – LUTRON MS-OPS2

3. MECH ROOM: PROVIDE ON/OFF TOGGLE SWITCH

4. EXTERIOR FIXTURES CONTROLLED VIA INTEGRAL PHOTOCELL

RESTROOM

MECHANICAL

X X

X

X

EXTERIOR

4X

1st FLOOR

0"

ROOF

192"

1ST FLOOR

0"

ROOF

16' - 0"

W2

W1-EM

W2

1st FLOOR

0"

ROOF

192"

1 2

1ST FLOOR

0"

ROOF

16' - 0"

1 2

W2

W1-EM

E

W A

S H

I N

G T

O N

M O

U N

T P

L E

A S

A N

T

I O

W A

DATE:

DRAWN BY:

PROJECT NO:

COPYRIGHT

SHEET TITLE

M

IC

H A

E L

H O

R

IZ

O N

-A R

C H

IT

E

C T

U R

E .C

O M

P H

-4

W W

W .H

O R

IZ

O

N -A

R C

H

IT

E C

T U

R E

.C O

M

IS

S

U E

D F

O R

P E

R M

IT

A

N D

C O

N S

T R

U C

T

IO

N

WWW.AXIOM-CON.COM | 319.519.6220

ELECTRICAL

LIGHTING

SCHEDULES

E-602

.0

D O

C M

P C

F N

E W

A P

P R

E N

T I C

E S

H I P

B U

I L D

I N

G

240027

SMF

06/07/2024

LIGHTING SCHEDULE

TAG SYMBOL MANUFACTURER MODEL NUMBER DESCRIPTION MOUNTING

TOTAL

LUMENS

LAMP CCT CRI VOLTAGE WATTS

EMERGENCY

COMPONENT

NOTES

D1 PRESCOLITE

LBRST-6RD-M-LSML-CS9-W

H-34

6"

DOWNLIGHT

CEILING 2502 lm INTEGRAL LED 40 K 90 120 V 31 W

EXIT COMPASS COM CE EXIT SIGN WALL | 8' 0 lm INTEGRAL LED 0 K 0 120 V 2 W INTEGRAL BATTERY

L1 LUX DYNAMICS

HIGH-4-6LM-840-U10-SM-

WA-OC-KO

4' STRIP CEILING | 16' 15488 lm INTEGRAL LED 40 K 80 120 V 107 W

L1-EM LUX DYNAMICS

HIGH-4-6LM-840-U10-SM-

WA-E20RL-OC-KO

4' STRIP CEILING | 16' 15488 lm INTEGRAL LED 40 K 80 120 V 107 W INTEGRAL BATTERY

W1-EM ILP

OWM-3L/5L-U-CCTS-BRZ-E

MCT8-PCU

WALL PACK WALL | 8' 5230 lm INTEGRAL LED 40 K 80 120 V 40 W INTEGRAL BATTERY

PROVIDE WITH PHOTOCELL

FIXTURE PROVIDED WITH

SWITCHABLE LUMEN OUTPUT

W2 ILP OWM-3L/5L-CCTS-BRZ-PCU WALL PACK VARIES 5230 lm INTEGRAL LED 40 K 80 120 V 40 W PROVIDE WITH PHOTOCELL

3/16" = 1'-0" E-602

1EAST EXTERIOR LIGHTING_

3/16" = 1'-0" E-602

2WEST EXTERIOR ELEVATION_

M A R K

T

S C R

IP

T

IO

N

/2

/2

A d d e n d u m

NOTES: PROVIDE ALL BRACKETS, MOUNTING PLATES AND SUPPORTS AS REQUIRED FOR INSTALLATION.

ADD