This is architectural and engineering design documentation for the Dane County Department of Waste & Renewables Maintenance Shop, a component of the Dane County Sustainability Campus initial construction project located at 4402 Brandt Road, Madison, Wisconsin. The project encompasses the design and construction of a maintenance shop facility consisting of approximately 10,601 gross square feet (9,078 square feet on the first floor and 1,523 square feet on the mezzanine level) with an overall building height of 33 feet to the highest point of the roof. The facility is designed as a mixed-use building classified under International Building Code (IBC) 2021 standards, incorporating motor vehicle repair and accessory storage (Group S-1, Moderate-hazard storage) totaling 8,678 square feet, office space (Group B, Business) of 400 square feet, and additional mezzanine storage of 1,523 square feet. The structure is designed as Type 5B construction with full fire sprinkler protection per NFPA 13 and fire alarm systems with initiation and notification devices. Design loads include a 21 psf design snow load, ultimate wind speed of 107 miles per hour, and seismic design criteria based on Risk Category II with a seismic design category of B. The project incorporates comprehensive mechanical systems including variable refrigerant flow (VRF) heat pump units, gas-fired infrared heaters, ceiling fans for destratification, energy recovery ventilators, duct furnaces, and dedicated HVAC systems for the air compressor room. Plumbing systems are designed to support vehicle maintenance operations with features including trench drain systems, oil interceptor basins, fluid dispensing stations with bulk storage tanks (three 400-gallon tanks with secondary containment), emergency eyewash and safety shower stations, and sanitary fixtures. Electrical systems include a 600-ampere, 480-volt three-phase service with 200-ampere emergency power capacity via manual transfer switch, multiple distribution panels (LDP, L1-L5, HP1), lighting controls with occupancy sensors and daylight harvesting, and provisions for an alternate 92-kilowatt solar photovoltaic array. Fire protection systems provide full sprinkler coverage with main and secondary supply lines, riser systems, and both sidewall and standard sprinkler heads. Technology infrastructure includes structured cabling with CAT-6A minimum copper and fiber optic backbone systems, wireless access points, closed-circuit television cameras with network video recording, access control systems with card readers and electric strikes, and integrated intrusion detection. The mandatory pre-bid meeting is scheduled for Wednesday, April 22, 2026 at 10:00 am at 7102 Maahic Way, Madison, Wisconsin, with all bidder questions due by Friday, May 8, 2026 at 5:00 pm and responses provided by May 14, 2026. Sealed bids must be submitted electronically through Dane County's eProcurement Portal by Thursday, May 21, 2026 at 2:00 pm, with the project requiring substantial completion by September 30, 2027 assuming a July 6, 2026 start date.
The project is subject to an Emerging Small Business (ESB) set-aside goal requiring minimum ten percent participation, with bidders required to demonstrate good faith efforts to award at least ten percent of work value to ESBs or face disqualification; all bidders must submit confirmation of an Emerging Small Business Report submission to the Office of Equity and Inclusion within ten business days of the bid due date. All bids must be accompanied by a bid guarantee of no less than five percent of the total bid price in the form of a bid bond, cashier's check, or bank certified check made payable to Dane County, with performance and payment bonds required from a surety company licensed to do business in Wisconsin. Non-resident bidders must comply with Wisconsin Statute Section 71.80(16)(a) regarding surety bond requirements equal to three percent of contract price for contracts of $50,000 or more. The bid pricing structure includes four base bids, three alternate bids (3-sided structure addition, solar photovoltaic array at maintenance shop, and sound masking system), unit pricing for unsuitable soil and rock removal, and a $100,000 lump sum allowance for unforeseen field conditions. Qualified contractors must demonstrate minimum experience with at least one completed project of 50 percent or greater size or value in similar work types, and bidders must be pre-qualified as Best Value Contractors prior to the bid due date with subcontractors required to become pre-qualified ten days before commencing work. The contract will be awarded to the lowest qualified responsible bidder, subject to Owner approval of the bidder's qualifications and experience with projects of similar size and scope. All work must comply with the 2021 International Building Code, Wisconsin Commercial Building Code, 2017 National Electrical Code, and prevailing wage laws.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTURAL MECHANICAL
STRUCTURAL ELECTRICAL
ARCHITECTURAL DESIGN, FIRE PROTECTION DESIGN, MECHANICAL,
ELECTRICAL, AND PLUMBING ENGINEERING
STRANG, INC.
STRUCTURAL ENGINEERING
MP-SQUARED STRUCTURAL ENGINEERS, LLC
LANDSCAPE DESIGN ARCHITECTURE
SAIKI DESIGN, INC.
TECHNOLOGY DESIGN
NETWORK TECHNOLOGIES, INC.
DESIGN TEAM PROJECT IMAGE
SHEET INDEX
STAMPS
SITE LOCATION MAP
D R
A W
IN
G
S E
T
D A
T E
COPYRIGHT STRANG, INC. 2026
R E
V
IS
IO
N
S
P R
O
JE
C T
N O
4402 BRANDT ROAD
MADISON, WI 53718 PROJECT NO. : 2024131
DANE COUNTY DEPT OF WASTE & RENEWABLES - MAINTENANCE SHOP
B R
A N
D T
R O
A D
M A
D
IS
O N
, W I
C D
/3
1/
T
IT
LE
S
H E
E T
D A
N E
C O
U N
T Y
D E
P T
O F
W A
S T
E
R E
N E
W A
B
LE
S
M A
IN
T
E N
A N
C E
S H
O P
BG000
GENERAL
BG000 TITLE SHEET
BG001 GENERAL INFORMATION
BG002 LIFE SAFETY PLAN & CODE INFORMATION
STRUCTURAL
BS001 STRUCTURAL NOTES
BS002 STRUCTURAL NOTES
BS003 SPECIAL INSPECTION
BS004 SPECIAL INSPECTION CONT.
BS101 FOUNDATION PLAN - SHOP
BS102 FOUNDATION PLAN - VEHICLE SHED
BS201 MEZZANINE FRAMING PLAN - SHOP
BS501 FOUNDATION DETAILS
BS502 FOUNDATION DETAILS
BS503 FOUNDATION DETAILS
BS504 FOUNDATION DETAILS
BS601 MASONRY DETAILS
BS602 MASONRY DETAILS
BS801 STEEL DETAILS
BS802 STEEL DETAILS
ARCHITECTURAL
BA001 PARTITION, WALL AND ROOF TYPES
BA002 INTERIOR FINISH SCHEDULE
BA003 DOOR & HARDWARE SCHEDULE, DOOR AND FRAME TYPES, AND
EXTERIOR STOREFRONT ELEVATIONS
BA004 DOOR AND FRAME DETAILS
BA201 FIRST FLOOR PLAN
BA202 MEZZANINE PLAN
BA210 ROOF PLAN
BA261 FIRST FLOOR INTERIOR FINISH PLAN
BA271 FIRST FLOOR SIGNAGE PLAN
BA272 MEZZANINE SIGNAGE PLAN
BA301 FIRST FLOOR REFLECTED CEILING PLAN
BA401 EXTERIOR ELEVATIONS
BA402 EXTERIOR ELEVATIONS
BA403 VEHICLE SHED - EXTERIOR ELEVATIONS
BA410 EXTERIOR SIGNAGE ELEVATIONS
BA411 EXTERIOR SIGNAGE ELEVATIONS
BA501 BUILDING SECTIONS
BA502 VEHICLE SHED - BUILDING SECTIONS
BA503 WALL SECTIONS
BA504 WALL SECTIONS
BA505 WALL SECTIONS
BA506 WALL SECTIONS
BA601 VEHICLE SHED - FLOOR PLAN AND ROOF PLAN
BA602 VEHICLE SHED - REFLECTED CEILING PLAN AND FINISH PLAN
BA603 PARTIAL PLANS AND ENLARGED RESTROOM PLANS
N
BA604 STAIR PLANS AND SECTIONS
BA701 INTERIOR ELEVATIONS
BA801 EXTERIOR DETAILS
BA802 EXTERIOR DETAILS
BA803 EXTERIOR DETAILS
BA804 EXTERIOR DETAILS
BA805 EXTERIOR DETAILS
BA901 INTERIOR DETAILS
BA902 INTERIOR DETAILS
BA903 INTERIOR SIGNAGE DETAILS
FURNITURE
BF201 FIRST FLOOR FURNITURE & EQUIPMENT PLAN
BF202 MEZZANINE FURNITURE & EQUIPMENT PLAN
PROJECT LOCATION
MADISON
IMAGE IS FOR ILLUSTRATION PURPOSES ONLY AND SHOULD NOT BE USED FOR BIDDING OR CONSTRUCTION
FIRE PROTECTION
BFP001 FIRE PROTECTION SYMBOLS, ABBREVIATIONS AND GENERAL
NOTES
BFP201 FIRST FLOOR FIRE PROTECTION PLAN - MAINTENANCE SHOP
BFP202 MEZZANINE FIRE PROTECTION PLAN - MAINTENANCE SHOP
PLUMBING
BP001 PLUMBING SYMBOLS, ABBREVIATIONS AND GENERAL NOTES
BP200U UNDERSLAB PLUMBING PLAN - MAINTENANCE SHOP
BP201 FIRST FLOOR PLUMBING WASTE PLAN - MAINTENANCE SHOP
BP202 MEZZANINE PLUMBING WASTE PLAN - MAINTENANCE SHOP
BP301 FIRST FLOOR PLUMBING SUPPLY PLAN - MAINTENANCE SHOP
BP302 MEZZANINE PLUMBING SUPPLY PLAN - MAINTENANCE SHOP
BP701 PLUMBING ISOMETRIC - MAINTENANCE SHOP - SUPPLY
BP702 PLUMBING ISOMETRIC - MAINTENANCE SHOP - WASTE
BP703 PLUMBING ISOMETRIC - MAINTENANCE SHOP - COMPRESSED
AIR AND BULK FLUID SYSTEMS
BP801 PLUMBING DETAILS - MAINTENANCE SHOP
BP802 PLUMBING DETAILS - MAINTENANCE SHOP
BP803 PLUMBING DETAILS - MAINTENANCE SHOP
BP901 PLUMBING SCHEDULES - MAINTENANCE SHOP
MECHANICAL
BM001 MECHANICAL SYMBOLS, ABBREVIATIONS AND GENERAL NOTES
BM201 FIRST FLOOR MECHANICAL PLAN
BM202 MEZZANINE MECHANICAL PLAN
BM601 ENLARGED MECHANICAL PLANS AND SECTIONS
BM701 MECHANICAL CONTROL DIAGRAMS
BM801 MECHANICAL DETAILS
BM901 MECHANICAL SCHEDULES
ELECTRICAL
BE001 ELECTRICAL SYMBOLS, ABBREVIATIONS AND GENERAL NOTES
BE201 FIRST FLOOR ELECTRICAL LIGHTING PLAN - SHOP
BE202 FIRST FLOOR ELECTRICAL LIGHTING PLAN - VEHICLE SHED
BE203 MEZZANINE ELECTRICAL LIGHTING PLAN
BE301 FIRST FLOOR ELECTRICAL POWER PLAN - SHOP
BE302 FIRST FLOOR ELECTRICAL POWER PLAN - VEHICLE SHED
BE303 MEZZANINE ELECTRICAL POWER PLAN
BE304 ELECTRICAL SOLAR PV ROOF PLAN - ALTERNATE
BE401 FIRST FLOOR ELECTRICAL FIRE ALARM PLAN - SHOP
BE403 MEZZANINE ELECTRICAL FIRE ALARM PLAN
BE501 ELECTRICAL SECTIONS / ELEVATIONS
BE601 ENLARGED ELECTRICAL PLANS
BE701 ELECTRICAL ONE-LINE DIAGRAM
BE801 ELECTRICAL DETAILS
BE901 ELECTRICAL PANELBOARD SCHEDULES
BE902 ELECTRICAL PANELBOARD SCHEDULES
BE903 ELECTRICAL PANELBOARD SCHEDULES
BE911 ELECTRICAL SCHEDULES
N O
D
E S
C R
IP
T
IO
N
D A
T E
TECHNOLOGY
BT000 PROJECT REQUIREMENTS & SPECIFICATIONS
BT001 PROJECT REQUIREMENTS & SPECIFICATIONS
BT002 SYMBOLS & LEGENDS
BT003 SYMBOLS & LEGENDS
BT004 SYMBOLS & LEGENDS
BT005 COMPONENTS SPECIFICATIONS & NOTES
BT201 FIRST FLOOR PLAN
BT202 MEZZANINE LEVEL FLOOR PLAN
BT800 ENLARGED EQUIPMENT ROOM LAYOUTS
BT900 EQUIPMENT RACK DETAILS
BT901 SECURITY SYSTEM DETAILS
BT902 INSTALLATION DETAILS
BT903 INSTALLATION DETAILS
DETAIL REFERENCE
Detail Number
Sheet Number
SECTION REFERENCE
Section Number
Sheet Number
BUILDING SECTION REFERENCE
Building Section Number
Sheet Number
INTERIOR ELEVATION
Interior Elevation Number
Sheet Number
EXTERIOR ELEVATION
Exterior Elevation Number
Sheet Number
REVISION
(Cloud Around Revision)
ROOM NAME/
ROOM NUMBER
PARTITION TYPE
SPECIFIC ELEVATION NOTE
SPECIFIC PLAN NOTE
CEILING TYPE AND HEIGHT
WINDOW/BORROWED LIGHT TYPE
VERTICAL ELEVATION
COLUMN GRID NUMBER#
NAME
ELEVATION
ROOM NAME
RM ##
BL-#
SPECIFIC DEMOLITION NOTE#
TYPE
HT
ELEV
TYPE
CURTAINWALL / STOREFRONT
TYPE AND ELEVATION
EXTERIOR WALL AND ROOF
SYSTEM TYPE
WS-#
RS-#
PRECAST CONCRETE
CONCRETE MASONRY UNIT (SECTION)
BRICK (SECTION)
STEEL (SECTION)
RIGID INSULATION (SECTION)
EXTERIOR INSULATION AND FINISH SYSTEM (ELEVATION)
PLYWOOD (SECTION)
GRANULAR FILL
SOIL, INFILL
SOIL, UNDISTURBED
6" MAX
3' - 0" MIN 3' - 6" MIN
12" MAX
T
.O . S
E A
T
1'
" 3'
A T
A C
C E
S S
IB
LE
U N
IT
1'
NOTE:
- ALL FIXTURE MOUNTING INSTALLATION & CLEARANCE DIMENSIONS SHALL MEET ALL ADA
ACCESSIBILITY STANDARDS AND NO ACCESSORY SHALL PROJECT MORE THAN 4" FROM WALL.
- PROVIDE BLOCKING IN WALLS FOR ALL WALL MOUNTED EQUIPMENT, ACCESSORIES, AND
CABINETRY AS REQUIRED; INCLUDING OWNER ITEMS.
- ALL ITEMS SHOWN ARE NOT NECESSARILY IN THIS PROJECT.
ELONGATED RIM
GRAB BAR (GB)
1' - 6"1' - 6"
18" GRAB BAR (GB)
WATER CLOSET URINAL
2'
3' - 5 1/2"
TOILET PAPER
DISPENSER (TPD)
GRAB BAR (GB)
3'
3' - 3 1/2"
T O
R E
F
LE
C T
IV
E
S U
R F
A C
E
3'
2'
0"
2'
M
IN
MIRROR (MIR)
BOTTOM OF
APRON
INSULATE PIPE DRAIN &
HOT WATER SUPPLY @
ALL SINKS WHERE P.LAM
PANEL IS NOT SHOWN
3'
SOAP DISPENSER (SD)
T O
O P
E R
A B
LE
C
O N
T R
O
LS
3'
M A
X
T O
O P
E R
A B
LE
C
O N
T R
O
LS
3'
M A
X
PAPER TOWEL DISPENSER /
RECEPTACLE (PTD/R)
SANITARY NAPKIN DISPENSER (SND)
SANITARY NAPKIN
RECEPTACLE (SNR)
T O
S P
O U
T O
U T
LE
T
3'
M A
X
2'
M
IN
ELECTRIC WATER
COOLER (EWC)
ACCESSORIES
B .O
. C A
B
IN
E T
2'
FIRE EXTINGUISHER
CABINET (FEC)
5' -0
M
A X
0L B
4' -0
M
A X
0L B
FIRE
EXTINGUISHER (FE)
3' - 0"
3'
3'
4' - 4"
4" MAX
CLEAR FLOOR
SPACE
BACK WALL
S E
A T
W A
LL
C O
N T
R O
L W
A
LL
1' - 6"
BACK WALL
G R
IP
P
IN
G
S U
R F
A C
E
T
O P
O F
M
IN
M A
X
G R
IP
P
IN
G
S U
R F
A C
E
T
O P
O F
3"
"1'
M
IN
CONTROLS
AREA
CONTROL WALL
1' - 3" MAX. 4"
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
D R
A W
IN
G
S E
T
D A
T E
R E
V
IS
IO
N
S
P R
O
JE
C T
N O
COPYRIGHT STRANG, INC. 2026
B R
A N
D T
R O
A D
M A
D
IS
O N
, W I
C D
/3
1/
G E
N E
R A
L
IN
F O
R M
A T
IO
N
D A
N E
C O
U N
T Y
D E
P T
O F
W A
S T
E
R E
N E
W A
B
LE
S
M A
IN
T
E N
A N
C E
S H
O P
BG001
# POUND, NUMBER
& AND
< ANGLE
@ AT
A-100 A LABEL - 100 MINUTE FIRE RATING
B-90 B LABEL - 90 MINUTE FIRE RATING
C-45 C LABEL - 45 MINUTE FIRE RATING
D-20 D LABEL - 20 MINUTE FIRE RATING
Ø DIAMETER, ROUND, PHASE
AB ANCHOR BOLT
ABBR ABBREVIATION
ACB ACOUSTICAL CEILING BAFFLE
ACOUS ACOUSTICAL
ACP ACOUSTICAL CEILING PANEL
ACR ACRYLIC, ACRYLIC MARKER BOARD
ADJ ADJUSTABLE, ADJACENT
AFF ABOVE FINISH FLOOR
AFS AIR FLOW STATION
AGGR AGGREGATE
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECTURAL, ARCHITECT
ASPH ASPHALT
AV AIR VALVE
AWP ACOUSTICAL WALL PANEL
BAF BAFFLES
BD BOARD
BHD BULKHEAD
BITUM BITUMINOUS
BL BORROWED LITE
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BN BULLNOSE
BO BOTTOM OF
BOT BOTTOM
BP BASE PLATE
BRG BEARING
BSC BIO-SAFETY CABINET
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
BTW BETWEEN
BUR BUILT-UP ROOF
C CONVECTOR, CHANNEL
CAB CABINET
CB CATCH BASIN
CEM CEMENT
CER CERAMIC
CFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED
CFM CUBIC FEET PER MINUTE
CG CORNER GUARD
CH COAT HOOK
CHBD CHALKBOARD
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLOS CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONJ CONSTRUCTION JOINT
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTROL
CONTR CONTRACTOR
CORR CORRIDOR
CPT SHEET CARPETING
CR CARD READER
CS CAST STONE
CT CERAMIC TILE
CTR CENTER
CTSK COUNTERSINK
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CYL CYLINDER
D DEPTH
DBA DECK BEARING ANGLE
DBL DOUBLE
DEMO DEMOLITION, DEMOLISH
DEPT DEPARTMENT
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DISP DISPENSER
DN DOWN
DO DO OVER, DITTO
DP DAMPPROOFING
DR DOOR
DS DOWNSPOUT
DSD DUCT SMOKE DETECTOR
DT DRAIN TILE
DTL DETAIL
DWG DRAWING
DWL DOWEL
E EAST
EA EACH, EXHAUST AIR
EC ELECTRICAL CONTRACTOR, EXPOSED CONCRETE
EF EXHAUST FAN
EHD ELECTRIC HAND DRYER
EIFS EXTERIOR INSULATION FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ABBREVIATIONS MATERIAL LEGEND
SYMBOL LEGEND
ELEC ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSURE
EP ELECTRIC PANEL, EPOXY
EQ EQUAL
EQUIP EQUIPMENT
ES EXPOSED STRUCTURE
ETR EXISTING TO REMAIN
EW EACH WAY
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXH EXHAUST
EXP EXPANSION
EXPO EXPOSED
EXST EXISTING
EXT EXTERIOR
FA FIRE ALARM
FB FACE BRICK, FLOOR BOX
FCTY FACTORY
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEB FIRE EXTINGUISHER BRACKET
FEC FIRE EXTIINGUISHER CABINET
FF FINISH FLOOR
FFLR FITNESS FLOOR
FH FUME HOOD, FIRE HOSE
FHC FIRE HOSE CABINET
FIN FINISH
FIX FIXTURE
FL FLOOR
FLUOR FLUORESCENT
FO FINISHED OPENING
FOC FACE OF CONCRETE
FOS FACE OF STUD
FPRF FIREPROOFING
FRP FIBERGLASS REINFORCED PLASTIC, FIBERGLASS
REINFORCED PANELING
FRT FIRE RETARDANT
FRZ FREEZER
FT FOOT, FEET
FTG FOOTING
FURR FURRING
FUT FUTURE
FV FIELD VERIFY
G GAS
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GL GLASS
GMGS GLASS MAT GYPSUM SHEATING
GND GROUND
GWB GYPSUM WALL BOARD
GYP GYPSUM
H HIGH
HB HOSE BIBB
HBD HARDBOARD
HC HOLLOW CORE
HDWD HARDWOOD
HDWE HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HORSEPOWER
HPC HIGH PERFORMANCE COATING
HR HOUR
HSS HOLLOW STRUCTURAL STEEL
HT HEIGHT
HVAC HEATING, VENTILATION, & AIR CONDITIONING
HWD HARDWOOD
ID INSIDE DIAMETER
IE INVERT ELEVATION
IF INSIDE FACE
IMP INSULATED METAL PANEL
INSUL INSULATION
INT INTERIOR
ITD IMPACT TRAFFIC DOOR
JAN JANITOR
JBE JOIST BEARING ELEVATION
JT JOINT
KIT KITCHEN
KO KNOCKOUT
KP KICK PLATE
KS KNEE SPACE
L LENGTH, ANGLE
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT LIGHT
LVT LUXURY VINYL TILE
LWC LIGHT WEIGHT CONCRETE
MATL MATERIAL
MAX MAXIMUM
MB MOP BASIN
MC MECHANICAL CONTRACTOR
MECH MECHANICAL
MEMB MEMBRANE
MEP MECHANICAL, ELECTRICAL, PLUMBING
MEZZ MEZZANINE
MFR MANUFACTURER
MH MANHOLE, MOP HOLDER
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
ML&P METAL LATH & PLASTER
MO MASONRY OPENING
MTD MOUNTED
MTL METAL
MUL MULLION
N NORTH
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NP NON POTABLE WATER
NTS NOT TO SCALE
OA OVERALL, OUTSIDE AIR
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OFF OFFICE
OFOI OWNER FURNISHED OWNER INSTALLED
OH OVERHEAD
OHCD OVERHEAD COILING DOOR
OHSD OVERHEAD SECTIONAL DOOR
OP OPERABLE PARTITION
OPG OPENING
OPNG OPENING
OPP OPPOSITE
OPP-H OPPOSITE HAND
PA PUBLIC ADDRESS
PC PLUMBING CONTRACTOR
PCON POLISHED CONCRETE
PDO POWER DOOR OPERATOR
PERP PERPENDICULAR
PL PLATE, PROPERTY LINE
PLAM PLASTIC LAMINATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PR PAIR
PT PAINT
PTD PAPER TOWEL DISPENSER
PTD/R PAPER TOWEL DISPENSER / RECEPTACLE
PTN PARTITION
PTR PAPER TOWEL RECEPTACLE
PVT PAVER TILE
QSM QUARTZ SURFACING MATERIAL
QT QUARRY TILE
R RADIUS, RISER
RA RETURN AIR
RB RESILIENT BASE
RBC RESILIENT BASE COVED
RBS RESILIENT BASE STRAIGHT
RD ROOF DRAIN
REF REFERENCE, REFRIGERATOR
REFR REFRIGERATOR
REINF REINFORCED
REM REMOVE
REQ REQUIRED
REQD REQUIRED
RF RESINOUS FLOORING
RM ROOM, RATED METAL
RO ROUGH OPENING
RSF RUBBER SHEET FLOORING
RSF RUBBER SHEET FLOORING
RT RUBBER TILE
RTF RUBBER TILE FLOORING
RUB RUBBER
RWD REDWOOD
S SOUTH, SINK, SUPPLY
S&V STAIN & VARNISH
SAB SOUND ATTENUATION BLANKET
SAN SANITARY
SB SOIL BORING
SC SOLID CORE
SCD SEAT COVER DISPENSER
SCHED SCHEDULE
SCON SEALED CONCRETE
SD SOAP DISPENSER
SECT SECTION
SF SQUARE FOOT
SH SHELF
SHR SHOWER
SHT SHEET
SIM SIMILAR
SND SANITARY NAPKIN DISPENSER
SNR SANITARY NAPKIN RECEPTACLE
SOG SLAB ON GRADE
SPEC SPECIFICATION
SQ SQUARE
SS STAINLESS STEEL
SSM SOLID SURFACE MATERIAL
ST STONE
STA STATION
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURAL
SUSP SUSPENDED
SWC SUSPENDED WOOD CEILING
SYM SYMMETRICAL
T TREAD, THRESHOLD
T&B TOP & BOTTOM
T&G TONGUE & GROOVE
TEL TELEPHONE
TEMP TEMPORARY, TEMPERATURE
TER TERRAZZO
THK THICK
TKBD TACK BOARD
TOB TOP OF BEAM
TOF TOP OF FOOTING
TOS TOP OF STEEL
TPD TOILET PAPER DISPENSER
TRANS TRANSPARENT
TRZ TERRAZZO
TV TELEVISION
TW TOP OF WALL
TYP TYPICAL
UH UNIT HEATER
UNF UNFINISHED
UNO UNLESS NOTED OTHERWISE
UR URINAL
V VENT, VOLT, VALVE
VAC VACUUM
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VSF VINYL SHEET FLOORING
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
TWC TACKABLE WALL COVERING
W WEST, WIDTH, WIDE, WATT, WASTE, WATER
W/ WITH
W/O WITHOUT
WB WOOD BASE
WC WATER CLOSET
WD WOOD
WF WIDE FLANGE
WM WIRE MESH
WP WATERPROOF, WEATHERPROOF, WALL PROTECTION
WR WATER RESISTANT, WATER RECEPTACLE
WT WEIGHT
WWF WELDED WIRE FABRIC
YD YARD
STANDARD MOUNTING HEIGHTS
N O
D
E S
C R
IP
T
IO
N
D A
T E
UP
D N
UP
NOT TO SCALE
LIFE SAFETY PLAN LEGEND
FIRE EXTINGUISHER CABINET
AND FIRE EXTINGUISHER
EGRESS WIDTH AND DIRECTION
67" Ø WHEELCHAIR TURNING SPACE
1 HOUR FIRE SEPARATION
FEC FE
EXIT0"##
AED FA OFOI ITEMS: AUTOMATED
EXTERNAL DEFIBRILLATOR
(AED) AND FIRST AID KIT (FA)
CLASSIFICATION OF WORK:
New Building
BUILDING AREA:
First Floor 9,078 gross sq. ft.
Mezzanine 1,523 gross sq. ft.
Building Total 10,601 gross sq. ft.
BUILDING HEIGHT:
One story above grade plane 33'-0" to highest point of roof
PRIMARY BUILDING USES: (IBC 2021 Chapter 3)
MIXED USE
Occupancies Occupancy group Floor area Motor Vehicle Repair* & Accessory Storage Group S-1, Moderate-hazard storage 8,678 gsf
*Hazardous materials do not exceed maximum allowable quantities per Table 307.1(1) Office area Group B, Business 400 gsf Mezzanine Storage Group S-1, Moderate-hazard storage 1,523 gsf
TYPE OF CONSTRUCTION: (IBC 2021 Chapter 6) 5B
FIRE SPRINKLER SYSTEM:
Fully sprinklered per NFPA 13
FIRE ALARM SYSTEM:
Fire Alarm Initiation and Notification Devices
GAS DETECTION:
None; CNG used in vehicles is odorized
ALLOWABLE AREA CALCULATIONS: (IBC 2021 Table 506.2) 36,000 sq.ft. Allowable Area per S-1 Occupancy (most restrictive), Fully Sprinklered
ALLOWABLE HEIGHT CALCULATIONS: (IBC 2021 Tables 504.3 and 504.4) 2 stories 60 feet Allowable Height per S-1 Occupancy (most restrictive), Fully Sprinklered
FIRE RESISTANCE RATINGS: (IBC 2021 Table 601) Primary Structural Frame 0 Hour Bearing Walls, Exterior 0 Hour Bearing Walls, Interior 0 Hour Floor Construction 0 Hour Roof Construction 0 Hour
OCCUPANT LOAD CALCULATIONS: (IBC 2021 Table 1004.5) Accessory Storage and Equipment Areas 937 gsf / 300 = 4 persons Mezzanine Storage Areas 1,523 gsf / 300 = 6 persons Vehicle Repair Areas (Industrial) 7,741 gsf / 100 = 78 persons Office Areas 400 gsf / 150 = 3 persons Total occupancy 91 persons
PLUMBING FIXTURE CALCULATIONS: (IBC 2021 Table 2902.1)
Type of Use Occupant load Water closets Lavatories Drinking Service fountains sink
Vehicle Repair Areas 78 0.78 0.78 0.20 1 Office Areas (B) 3 0.12 0.08 0.03 0* Storage and Equipment 10 0.10 0.10 0.01 1
Total required for 1 1 1 1 entire building
Total provided for entire building 1 1 0* 1
Notes * Table 2902.1 footnote "e"
** Building not for public use; bottled water will be provided in Open Office
CODE INFORMATION
EXIT WIDTH CALCULATIONS: (IBC 2021 Section 1005.3.1 & 1005.3.2)
With Sprinkler System & Emergency Communication System:
Stairs, Required Stairs, Provided Other Egress, Required Other Egress, Provided (Mezzanine) 6 persons x 50 inches (Mezzanine) 91 persons x 99 inches
0.2 = 1.2 inches 0.15 = 13.7 inches
APPLICABLE CODES:
Wisconsin Commercial Building Code Accessibility: ICC/ANSI A117.1-2017 Edition Commercial Building: 2021 IBC as amended Electrical: 2017 NEC as amended Energy Conservation: 2021 IECC as amended Fire Protection: 2021 IFC as amended Mechanical: 2021 IMC as amended Plumbing: 2021 IPC as amended
HAZARDOUS MATERIALS: (IBC 2021 Chapter 50) Control Area: Entire Building Maximum Quantities*
Material Category Open Storage Maximum In Approved Cabinets Maximum Aerosols Level 3 500 lbs 1,000 lbs Aerosols Level 2 1,000 lbs 2,000 lbs Oxygen, Oxidizing Gases 3,000 cu. ft gas or 300 gal liquid 4,500 cu ft gas or 450 gal liquid Acetylene, Propane, Flammable gases 2,000 cu ft gas or 300 gal liquid 3,000 cu ft gas or 450 gal liquid Inert gases No Limits No Limits Bulk Engine oil, hydraulic fluid, waste oil, No Limits No Limits Class IIIB combustible liquids Kerosene, Class II combustible liquids 240 gal 360 gal Gasoline, Class IB/IC flammable liquids 240 gal 360 gal Fuels stored in in tanks or on vehicles No limits No limits
* BUILDING OWNER DOES NOT EXCEED LISTED QUANTITIES IN EXISTING COMPARABLE LOCATION
B101
WORKING BAYS
B102
ELECTRICAL / IT
B103
OPEN
OFFICE
B104
CORR
B105
JANITOR
B106
SHOWER
B107
PARTS STORAGE
EXIT DIST: 58' - 6"
EXIT DIST: 146' - 5"
EXIT DIST: 91' - 4"
EXIT33"
EXIT 33"
E X
IT
33"
ACCESSIBLE RESTROOM
AEROSOL STORAGE CAGE
FE
AED
FA
FA AED
FEC
FA
AED
FE
FA
AED
FE
ACCESSIBLE ROUTE TO
ACCESSIBLE PARKING -
SEE CIVIL DRAWINGS
4' - 2"
B201
MEZZANINE
B202
AIR
COMPRESSOR
E X
IT
50"
EXIT DISTANCE INCLUDING
STAIR TRAVEL AND LOWER
LEVEL: 160'-6"
OPEN TO BELOW
COMBUSTIBLE LIQUID CLASS IIIB
STORAGE TANKS WITH
SECONDARY CONTAINMENT:
750 GAL MAX CAPACITY
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
D R
A W
IN
G
S E
T
D A
T E
R E
V
IS
IO
N
S
P R
O
JE
C T
N O
COPYRIGHT STRANG, INC. 2026
B R
A N
D T
R O
A D
M A
D
IS
O N
, W I
C D
/3
1/
LI
F
E S
A F
E T
Y P
LA
N
C
O D
E
IN
F O
R M
A T
IO
N
D A
N E
C O
U N
T Y
D E
P T
O F
W A
S T
E
R E
N E
W A
B
LE
S
M A
IN
T
E N
A N
C E
S H
O P
BG002
GENERAL LIFE SAFETY PLAN NOTES
1 WIDTHS NOTED ON LIFE SAFETY PLANS ARE CLEAR EGRESS WIDTHS
2 SEE SITE PLAN FOR ACCESSIBLE ROUTE TO ACCESSIBLE PARKING STALLS.
PNTN
SCALE: 3/32" = 1'-0"BG002
1 FIRST FLOOR LIFE SAFETY PLAN
PNTN
SCALE: 3/32" = 1'-0"BG002
2 MEZZANINE FLOOR LIFE SAFETY PLAN
N O
D
E S
C R
IP
T
IO
N
D A
T
LOADING
1. DESIGNED IN ACCORDANCE WITH THE CURRENT WISCONSIN COMMERCIAL BUILDING CODE BASED ON THE 2021
INTERNATIONAL BUILDING CODE.
2. DESIGN LOADS:
A. ROOF DEAD LOADS (PER PEMB DWGS):
3 PSF ROOF SECONDARY & PANEL (VERIFY W/ PEMB MANUFACTURER)
B. ROOF COLLATERAL GRAVITY LOAD:
5 PSF SOLAR PANEL EQUIPMENT
5 PSF MISC MECHANICAL
10 PSF TOTAL AT SHOP
5 PSF TOTAL AT VEHICLE SHED (MISC MECHANICAL)
C. ROOF LIVE LOAD:
20 PSF REDUCIBLE
D. MEZZANINE FLOOR DEAD LOADS:
60 PSF TOP CHORD
5 PSF BOTTOM CHORD (COLLATERAL FOR MISC MECHANICAL)
65 PSF TOTAL ROOF DEAD LOAD + FRAMING WEIGHT
E. MEZZANINE FLOOR LIVE LOAD:
250 PSF EQUIPMENT/ STORAGE
F. DESIGN SNOW LOAD:
Pg = 30 PSF Pf = 0.7(Ce)(Ct)(I)(Pg) = 21 PSF Ce = 1.0 Cs = 1.0 Ct = 1.0 I = 1.0
DRIFTING SNOW: SEE PLAN
G. WIND DESIGN CRITERIA:
ULTIMATE WIND SPEED = 107 MPH
NOMINAL WIND SPEED = 82.9 MPH
EXPOSURE = C
I = 1.0 Kzt = 1.0 GCpi = +/- 0.18 SHOP
+/- 0.55 VEHICLE SHED
H. SEISMIC DESIGN CRITERIA:
RISK CATEGORY = II
SITE CLASS = D
SS = 0.076; S1 = 0.048
SDS = 0.081; SD1 = 0.077
SEISMIC DESIGN CATEGORY = B
SEISMIC RESISTING SYSTEM = STRUCTURAL STEEL SYSTEMS NOT SPECIFICALLY DETAILED FOR SEISMIC R = 3
DESIGN BASE SHEAR = 0.027*W
GENERAL
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFICATION OF ALL CONDITIONS PRIOR TO BIDDING.
THIS INCLUDES ENSURING ERECTION CAN BE PERFORMED AS DETAILED ON THE PLANS. IF MODIFICATIONS ARE NEEDED TO FACILITATE ERECTABILITY THE BIDDING CONTRACTOR SHALL NOTIFY THE OWNER, ARCHITECT AND ENGINEER AND CLEARLY COMMUNICATE ASSUMPTIONS IN BID DOCUMENTS. THE ENGINEER WILL NOT BE RESPONSIBLE FOR ADDITIONAL COSTS DUE TO REQUIRED MODIFICATIONS OF THESE PLANS TO FACILITATE
ERECTION SEQUENCING ETCETERA.
2. THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION. THE CONTRACTOR IS RESPONSIBLE FOR HAVING AN INDEPENDENT ENGINEER DESIGN AND FURNISH ALL TEMPORARY BRACING AND/OR SUPPORT THAT MAY BE REQUIRED AS THE RESULT OF THE CONTRACTOR'S CONSTRUCTION METHODS AND/OR SEQUENCES. THE STRUCTURAL ENGINEER SEAL ON THESE DRAWINGS ASSUMES NO
LIABILITY FOR THE STRUCTURE DURING CONSTRUCTION.
3. THE CONTRACTOR IS RESPONSIBLE FOR ALL MEANS AND METHODS OF CONSTRUCTION AND ALL JOB SITE
SAFETY.
4. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO CONSTRUCTION.
NOTIFY THE ENGINEER AND ARCHITECT OF ANY DISCREPANCY IMMEDIATELY.
5. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF ALL BUILDING MATERIALS AND COMPONENTS.
COMPONENT LOCATIONS ARE SHOWN FOR DESIGN INTENT, NOT EXACT LOCATION, UNLESS NOTED SPECIFICALLY. INDEPENDENTLY PREPARED SHOP DRAWINGS ARE REQUIRED OF ALL TRADES FOR COORDINATION AND BEST PRACTICE. ERRORS OR OMISSIONS IN INSTALLATION DUE TO THE CONTRACTOR'S
FAILURE TO COORDINATE THE WORK WILL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR
6. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS.
A. ALL SHOP DRAWINGS MUST BE THOROUGHLY REVIEWED BY THE CONTRACTOR AND STAMPED AS
REVIEWED PRIOR TO SUBMITTING TO THE ENGINEER FOR FURTHER REVIEW.
B. THE CONTRACTOR SHALL PROVIDE THEIR REVIEWED SUBMITTAL TO THE ENGINEER IN PDF FORMAT.
C. THE OMISSION OF SHOP DRAWINGS OF ANY MATERIAL SHALL NOT RELIEVE THE CONTRACTOR OF THE
RESPONSIBILITY OF FURNISHING AND INSTALLING SUCH MATERIALS.
D. SHOP DRAWINGS SHALL BE FURNISHED TO THE ENGINEER TO ALLOW FOR 10 WORKING DAYS TO REVIEW
AND RETURN.
BRICK VENEER
1. WALL ANCHORS TO BE MINIMUM W1.7 ADJUSTABLE WIRE ANCHORS, HOT DIPPED GALVANIZED, TWO-PIECE PER
ASTM A 153 CLASS B2.
2. PROVIDE HORIZONTAL JOINT REINFORCING AT 16” O.C. WHEN MASONRY BRICK VENEER IS USED IN LIEU OF CLAY
BRICK.
3. ALL HORIZONTAL JOINT REINFORCEMENT SHALL HAVE A MINIMUM OF 5/8” COVER AND BE HOT DIP
GALVANIZED.
4. PROVIDE MINIMUM ONE ANCHOR PER 2 SQ FT OF WALL AREA.
5. VERTICAL SPACING OF ANCHORS NOT TO EXCEED 16” O.C.
6. HORIZONTAL SPACING OF ANCHORS NOT TO EXCEED 32” O.C.
7. SECURELY ATTACH ANCHORS TO STUD WALL FRAMING THROUGH THE SHEATHING, NOT TO THE SHEATHING
ALONE.
8. MORTAR SHALL COMPLY WITH ASTM C 270 AND HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 2,500
PSI, 75% WATER RETENTION AND 12% AIR CONTENT.
9. STEEL LOOSE LINTELS AND SHELF ANGLES SHOULD CONFORM TO ASTM A36/A36M. SPECIFICATION FOR
CARBON STRUCTURAL STEEL.
10. ALL STEEL FRAMING MEMBERS, CONNECTION PLATES, FASTENERS AND ANCHOR BOLTS TO HAVE HOT-DIP GALVANIZED FINISH. APPLY COATING BY THE HOT-DIP PROCESS FOR GALVANIZING ACCORDING TO ASTM A 123.
11. REFER TO ARCHITECTURAL DRAWINGS FOR FLASHING REQUIREMENTS, BRICK CONTROL JOINT LOCATIONS, VENEER TYPE, FINISH, ETC.
PRE-ENGINEERED METAL BUILDINGS
1. ALL LOADS SHALL BE PROPORTIONED AND APPLIED IN ACCORDANCE WITH THE CURRENT WISCONSIN
ENROLLED COMMERCIAL BUILDING CODE AND AS INDICATED IN THE GENERAL NOTES. BUILDING LOADS SHALL INCLUDE UNBALANCED SNOW LOADING, DRIFTING, SKIP LOADING AND OTHER CONSIDERATIONS
REQUIRED BY CODE.
2. DEFLECTION REQUIREMENTS SHALL BE IN ACCORDANCE WITH THE APPLICABLE PROVISIONS OF THE AISC STEEL DESIGN GUIDE SERIES 3 – SERVICEABILITY DESIGN CONSIDERATIONS FOR LOW-RISE BUILDINGS OR
THE BUILDING CODE, WHICHEVER IS MORE RESTRICTIVE.
3. SUBMIT SEALED ANCHOR BOLT PLACEMENT PLAN AND COLUMN REACTIONS. A MINIMUM OF 4 -ANCHOR BOLTS HAVING A DIAMETER OF ¾” OR MORE SHALL BE USED FOR EACH COLUMN. ALL ANCHOR BOLTS MUST
BE CENTERED A MINIMUM OF 4” FROM THE FOUNDATION OR PIER LINE.
4. BUILDING COLUMN SIZES SHALL NOT EXCEED THOSE SHOWN ON PLAN OR PIER SIZE SHOWN. IT SHALL BE THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR ORDERING THE BUILDING TO VERIFY COLUMN BASES FIT ON PIERS SHOWN. THE CONTRACTOR SHOULD THEN COORDINATE WITH THE SUPPLIER OR MP2 IF
MODIFICATIONS ARE NEEDED.
5. THE METAL BUILDING SUPPLIER SHALL SUBMIT FRAME REACTIONS THAT INCLUDE UN-FACTORED
REACTIONS FOR EACH INDIVIDUAL LOAD TYPE.
6. THE BUILDING ERECTOR SHALL HAVE A MINIMUM OF THREE YEARS EXPERIENCE IN THE ERECTION OF STEEL
BUILDING SYSTEMS.
7. THE ERECTOR SHALL FURNISH TEMPORARY GUYS AND BRACING WHERE NEEDED FOR SQUARING, PLUMBING, AND SECURING THE STRUCTURAL FRAMING AGAINST LOADS, SUCH AS WIND LOADS ACTING ON THE EXPOSED FRAMING, AS WELL AS LOADS DUE TO ERECTION EQUIPMENT AND ERECTION OPERATION, BUT NOT INCLUDING LOADS RESULTING FROM THE PERFORMANCE OF WORK BY OTHERS. BRACING FURNISHED BY THE MANUFACTURER FOR THE METAL BUILDING SYSTEM CANNOT BE ASSUMED TO BE ADEQUATE DURING ERECTION. THE TEMPORARY GUYS, BRACES, FALSEWORKS AND CRIBBING ARE THE PROPERTY OF THE ERECTOR, AND THE ERECTOR SHALL REMOVE THEM IMMEDIATELY UPON THE COMPLETION OF THE
ERECTION.
MISCELLANEOUS
1. ALL DRAWINGS ARE OF EQUAL IMPORTANCE IN DEFINING THE WORK OF THE CONTRACT DOCUMENTS.
CONTRACTOR SHALL CAREFULLY REVIEW AND COMPARE ALL DRAWINGS DURING THE BIDDING PERIOD AND BEFORE INSTALLATION OF THEIR WORK. ANY INCONSISTENCIES IN THE DRAWINGS SHALL BE REPORTED
PROMPTLY TO THE ENGINEER AND ARCHITECT FOR CLARIFICATION.
2. EVERY EFFORT HAS BEEN MADE TO PROVIDE TO SCALE DRAWINGS, HOWEVER THE DRAWINGS ARE NOT
NECESSARILY TO SCALE - USE GIVEN DIMENSIONS.
3. ALL ANCHOR BOLTS SHOULD HAVE A MIN SPACING OF 6*BOLT DIAMETER FROM EACH OTHER AND EDGE OF
PIER/BUILDING LINE.
FOUNDATION
1. ALLOWABLE SOIL BEARING CAPACITY = 3,000 PSF
GEOTECHNICAL INFORMATION TAKEN FROM:
SOIL & ENGINEERING SERVICES, INC.
GEOTECHNICAL INVESTIGATION REPORT
DANE COUNTY SUSTAINABILITY CAMPUS
4402 BRANDT ROAD
MADISON, WI
AUGUST 12, 2025
2. PROJECT GEOTECHNICAL REPORT SUPERSEDES GEOTECHNICAL INFORMATION PROVIDED ON STRUCTURAL
PLANS.
3. THE GENERAL CONTRACTOR (GC) SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION PROCEDURES THAT MAY AFFECT ADJACENT EXISTING STRUCTURES, ROADS, OR OTHER SIGNIFICANT PROPERTY. IT IS THE RESPONSIBILITY OF THE GC TO RETAIN A SPECIALTY FOUNDATION DESIGN CONSULTANT, GEOTECHNICAL
ENGINEER, OR OTHER ENGINEERING CONSULTANT BEFORE EXCAVATION & AS REQUIRED DURING
CONSTRUCTION. THE CONSULTANT SHALL PROVIDE ENGINEERED SOIL RETENTION/STABILIZATION SYSTEM, INSTALLATION GUIDANCE, AND ADJACENT PROPERTY MONITORING AS NEEDED DURING CONSTRUCTION. THE ARCHITECT AND/OR EOR SHALL BE NOTIFIED IMMEDIATELY IF ADJACENT PROPERTY (FOUNDATION
MOVEMENT, CRACKING, ETC) IS DETECTED.
4. CONTRACTOR SHALL READ AND FOLLOW ALL RECOMMENDATIONS PROVIDED IN SOIL REPORT. CONTRACTOR SHALL ENGAGE SOIL & ENGINEERING SERVICES, INC. OR OTHER QUALIFIED COMPANY TO MONITOR SOIL
DURING CONSTRUCTION.
5. GRADE AREAS IN ACCORDANCE WITH ELEVATIONS AND GRADES SHOWN ON THE SITE DRAWINGS AND AS
REQUIRED FOR DRAINAGE.
6. SLAB ON GROUND TO BE CONSTRUCTED ON A MINIMUM OF 6” OF CRUSHED STONE OR GRANULAR FILL
COMPACTED TO 95% MODIFIED PROCTOR OR AS DIRECTED BY THE GEOTECHNICAL ENGINEER.
7. ALL FILL MATERIAL USED IN GRADING OPERATIONS SHALL BE GRANULAR MATERIAL AND BE FREE OF DEBRIS, BOULDERS OR ORGANIC MATERIAL. FILL SHALL BE PLACED IN MAXIMUM OF 12” LIFTS AND COMPACTED TO 95% OF MODIFIED PROCTOR MAXIMUM DRY DENSITY OR AS DIRECTED BY THE GEOTECHNICAL ENGINEER.
8. THE BOTTOM OF ALL EXTERIOR FOOTINGS SHALL BE A MINIMUM OF 4'- 0” BELOW FINISHED GRADE.
9. ALL FOUNDATIONS AND FOOTINGS SHALL BEAR ON NATIVE SOIL OR COMPACTED GRANULAR FILL HAVING A
MINIMUM ALLOWABLE BEARING CAPACITY EQUAL TO THE PRESUMPTIVE CAPACITY ABOVE.
10. THE ENGINEER SHALL BE NOTIFIED IF ACTUAL FIELD CONDITIONS DO NOT MEET BEARING REQUIREMENTS, OR IF QUESTIONABLE SOIL CONDITIONS ARE DISCOVERED INCLUDING BUT NOT LIMITED TO PEAT AND OTHER HIGH
ORGANIC SOILS.
11. ALL BEARING SOIL OR FILL MUST BE PROTECTED FROM FREEZING. THE CONTRACTOR SHALL PROVIDE PROTECTION TO PREVENT FROST PENETRATION BELOW THE CONCRETE BEARING ELEVATIONS. ANY FROZEN SOIL BELOW THE FOUNDATION BEARING LEVEL MUST BE REMOVED PRIOR TO PLACING CONCRETE.
12. ALL SLABS ON GRADE AREAS SHALL BE PROOF ROLLED. ALL SOFT SPOTS SHALL BE REMOVED AND
REPLACED WITH COMPACTABLE FILL.
13. THE CONTRACTOR SHALL USE CONTROLLED GRANULAR FILL APPROVED BY THE GEOTECHNICAL ENGINEER TO
BE PLACED AGAINST ALL CANTILEVERED RETAINING WALLS.
14. WHEN IT IS POSSIBLE FOR GROUND WATER TO SEEP TOWARD SUBGRADE FOUNDATIONS AND RETAINING WALLS, THESE WALLS SHALL HAVE A POSITIVE DRAINAGE SYSTEM AT THE BASE OF THE WALL CONSISTING OF A PERFORATED DRAIN PIPE PROTECTED BY A GEOTEXTILE FABRIC SURROUNDED BY CONCRETE SAND (TORPEDO SAND). NEAR THE BASE OF THE WALL. OTHER BACK FILL MATERIAL SHALL BE SAND WITH LESS
THAN 12% PASSING THE #200 SIEVE.
15. DO NOT USE EXCESSIVE COMPACTION EFFORTS ADJACENT TO RETAINING WALLS. SUCCESSIVE PASSES OF HEAVY COMPACTION EQUIPMENT, SUCH AS ROLLERS, CAN RESULT IN WALL PRESSURE BUILD UP BEYOND THE DESIGN INTENT. HEAVY EQUIPMENT SHOULD BE KEPT A MINIMUM OF 10 FEET FROM THE TOP OF BASEMENT OR RETAINING WALLS. USE HAND-OPERATED COMPACTION EQUIPMENT SUCH AS VIBRATORY PLATES.
16. FULLY COMPACT SOIL IN FRONT OF RETAINING WALLS.
17. REFER TO THE GEOTECHNICAL INVESTIGATION FOR INFORMATION REGARDING REQUIRED UNDERCUT, EXCAVATION, SIDE SLOPES, SUB-GRADE PREPARATION, AND FILL RECOMMENDATIONS.
18. PROVIDE SUB-GRADE PREPARATION AS PER THE PLANS OR PROJECT GEOTECHNICAL REPORT.
19. REMOVE TOPSOIL FROM BENEATH ALL PROPOSED CONSTRUCTION AREAS. SALVAGE AND STOCK PILE
TOPSOIL, CUT/FILL MATERIAL AS NECESSARY TO MATCH GRADES SHOWN ON DRAWINGS.
20. NON-FROST SUSCEPTIBLE FILL SHALL BE FREELY DRAINING GRANULAR FILL W/ 12% MAX FINES PASSING
THROUGH A #200 SIEVE. SEE PLAN FOR REQUIRED LOCATIONS.
CONCRETE CONSTRUCTION (CONTINUED)
3. ALL CONCRETE REINFORCING STEEL TO BE ASTM A615 GRADE 60. ALL WELDED WIRE FABRIC (WWF) TO BE ASTM A1064 GR. 65 MIN. ALL REINFORCING SHALL BE DETAILED AND PLACED IN ACCORDANCE WITH ACI 315
AND 315R.
4. ALL REINFORCING BARS AND WWF SHALL BE SET ON CHAIRS AND TIED IN PLACE.
5. WELDING OF ASTM A615 REBAR SHALL NOT BE PERMITTED. WHEN WELDING IS REQUIRED ASTM A706 BAR
MUST BE USED.
6. ALL LAPS SHALL BE “B” SPLICES UNLESS NOTED OTHERWISE ON THE DRAWINGS OR UNLESS SPECIAL CARE IS
TAKEN FOR THE REINFORCING TO BE DETAILED AND PLACED TO PROVIDE STAGGERED LAPS.
7. UNLESS NOTED OTHERWISE ON THE DRAWINGS ALL REINFORCING SHALL BE LAPPED TO DEVELOP ITS
CAPACITY AS FOLLOWS:
8. WELDED PLAIN WIRE REINFORCEMENT FABRIC FOR CONCRETE SHALL CONFORM TO ASTM A185.
9. CONCRETE SLABS ON GROUND CONTAINING WELDED WIRE REINFORCEMENT FABRIC (WWF) OR REINFORCING BARS SHALL BE PLACED IN THE UPPER ONE-THIRD OF THE SLAB AS SHOWN ON THE DRAWINGS.
REINFORCEMENT SHALL BE SUPPORTED AT 3’ (WWF) OR 4’ (REBAR) ON CENTER MAXIMUM. LIFTING
REINFORCING AFTER CONCRETE IS PLACED SHALL NOT BE ALLOWED.
10. THREADED ANCHOR RODS SHALL HAVE A HEAVY HEX NUT SECURED TO THE EMBEDDED END IN ONE OF THE
FOLLOWING WAYS:
A. F1554 GRADE 36 ANCHOR RODS - WELD, DOUBLE NUT OR THREAD PEENING.
B. F1554 GRADE 55 OR HIGHER ANCHOR RODS - DOUBLE NUT OR THREAD PEENING.
11. PLACING OF CONCRETE SHALL BE DONE IN CONFORMANCE WITH ACI-306 FOR COLD WEATHER AND ACI-305
FOR HOT WEATHER.
12. CONCRETE SHALL BE CURED ABOVE 50°F (10°C) AND IN A MOIST CONDITION FOR AT LEAST THE FIRST SEVEN DAYS AFTER PLACEMENT. DO NOT PLACE CONCRETE WHEN THE MEAN DAYLIGHT TEMPERATURE IS LESS
THEN 20 DEGREES F.
13. UNLESS OTHERWISE APPROVED, ALL EXPOSED CONCRETE WALLS SHALL BE CURED WITH FORMS LEFT IN PLACE FOR SEVEN DAYS. IF FORMS CAN NOT BE LEFT IN PLACE THE CONTRACTOR SHALL SUBMIT IN WRITING
TO THE ENGINEER ALL PROPOSED CURING METHODS.
14. AFTER CONCRETING HAS STARTED, IT SHALL BE CARRIED ON AS A CONTINUOUS OPERATION UNTIL PLACING OF A PANEL OR SECTION, AS DEFINED BY ITS BOUNDARIES OR PREDETERMINED JOINTS, IS COMPLETED.
CONCRETE SHALL BE DEPOSITED AS NEARLY AS PRACTICABLE TO ITS FINAL POSITION TO AVOID
SEGREGATION DUE TO REHANDLING OR FLOWING.
15. CONCRETING OPERATIONS SHALL BE CARRIED ON AT SUCH A RATE THAT THE CONCRETE IS AT ALL TIMES
PLASTIC AND FLOWS READILY INTO SPACES BETWEEN REINFORCEMENT.
16. RETEMPERED CONCRETE, CONCRETE THAT HAS BEEN REMIXED AFTER INITIAL SET OR PARTIALLY HARDENED
SHALL NOT BE USED IN THE STRUCTURE.
17. CONCRETE SHALL BE THOROUGHLY CONSOLIDATED BY SUITABLE MEANS DURING PLACEMENT AND SHALL BE THOROUGHLY WORKED AROUND REINFORCEMENT AND EMBEDDED FIXTURES AND INTO CORNERS OF THE
FORMS. THE TOP SURFACES OF VERTICALLY FORMED LIFTS SHALL BE GENERALLY LEVEL.
18. CRACKS DUE TO IMPROPER CURING METHODS, OR WEATHER PROTECTION SHALL BE THE RESPONSIBILITY OF
THE CONTRACTOR.
19. ALL FLAT WORK CONCRETE MUST BE CURED. FLAT WORK IS RECOMMENDED TO BE COVERED IMMEDIATELY FOLLOWING SAW CUTTING AND MAINTAINED CONTINUOUSLY WET FOR 7-DAYS. CURING COMPOUNDS MAY BE USED INSTEAD OF WET CURE WHEN APPROVED BY THE ARCHITECT AND MUST BE APPLIED PER THE
MANUFACTURER'S RECOMMENDATIONS. SUBMIT PRODUCT DATA TO A/E FOR APPROVAL.
20. EXPOSED FOUNDATION WALLS SHALL HAVE VERTICAL CONTROL JOINTS SPACED PER DETAILS. THE LOCATION
OF WALL CONTROL JOINTS SHALL BE MID BAY BETWEEN COLUMNS.
21. EXPOSED FOUNDATIONS AND RETAINING WALLS SHALL HAVE EXPANSION JOINTS LOCATED AT EVERY FOURTH CONTROL/CONTRACTION JOINT WITH A MAX SPACING OF 100'. SEE CONCRETE DETAILS FOR SPECIFIC
CONSTRUCTION REQUIREMENTS.
22. FLOOR SLAB CONTROL JOINTS SHALL FOLLOW THE INTENT SHOWN ON THE PLAN BUT SHALL NOT EXCEED AN ASPECT RATIO OF 1.5 TO 1.0. ALL REENTRANT CORNERS SHALL HAVE CONTROL JOINTS EXTENDING OUT FROM THE INSIDE CORNER. DEAD- END “T” CONTROL JOINTS INTO CONTINUOUS JOINTS SHALL BE AVOIDED.
23. CONSTRUCTION JOINTS SHALL BE LOCATED AT CONTROL JOINTS AS REQUIRED UNLESS NOTED OTHERWISE
ON PLAN.
24. SLAB-ON-GRADE FLOOR LEVELNESS (FL) AND FLOOR FLATNESS (FF) REQUIREMENTS SHALL BE
COORDINATED WITH THE ARCHITECT.
25. A 10-MIL. (MIN.- VERIFY W/ ARCH) POLYETHYLENE VAPOR BARRIER WITH JOINTS LAPPED NOT LESS THAN 6”
SHALL BE PLACED BETWEEN THE BASE COURSE OR SUBGRADE AND THE CONCRETE FLOOR.
26. PIPE SLEEVES OVER 1 1/2” IN DIAMETER WHICH PASS THROUGH CONCRETE WALLS OR SLABS SHALL BE SCHEDULE 40 GALVANIZED STEEL PIPE. ALL OTHER SLEEVES SHALL BE 18 GAUGE SHEET METAL. SLEEVES SHALL BE ONE SIZE LARGER THAN OUTSIDE DIAMETER OF PIPE PASSING THROUGH SLEEVE. VERIFY SIZE AND
NUMBER WITH MECHANICAL, ELECTRICAL, AND PLUMBING CONTRACTORS.
27. ALUMINUM CONDUIT SHALL NOT BE EMBEDDED IN CONCRETE.
CONCRETE COMPRESSIVE STRENGTH f'c=3,000 PSI
#3
UNCOATED STANDARD & CLASS "B" TENSION LAP LENGTHS1, 5
CONCRETE COMPRESSIVE STRENGTH f'c=4,000 PSI
BAR
SIZE
BTM
BARS
TOP
BARS4
BTM
BARS
TOP
BARS4
STD DEVELOPMENT
LENGTH2
CLASS "B" TENSION
LAP LENGTH3
STD DEVELOPMENT
LENGTH2
CLASS "B" TENSION
LAP LENGTH3
BAR
SIZE
BTM
BARS
TOP
BARS4
BTM
BARS
TOP
BARS4
#4
#5
#6
#7
#8
#3
#4
#5
#6
#7
#8
17"
22"
28"
33"
48"
55"
22"
29"
36"
43"
63"
72"
22"
29"
36"
43"
63"
72"
28"
38"
47"
56"
81"
93"
15"
19"
24"
29"
42"
48"
19"
25"
31"
37"
54"
62"
19"
25"
31"
37"
54"
62"
25"
33"
41"
49"
71"
81"
NOTES:
1. BASED ON ℓd VALUES FROM SECTION IN ACI 318:
1.1 GRADE 60 REINFORCEMENT BARS
1.2 NORMAL WEIGHT CONCRETE (Ѱ=1.0)
1.3 NON-EPOXY COATED BARS (Ѱ=1.0)
1.4 CLEAR COVER > 1.0db; CLEAR SPACING > 2.0db; NOTIFY ENGINEER IF COVER NOT MET.
2. STANDARD LAP SPLICES ARE TO BE USED WHEN < 50% OF BARS ARE LAPPED AT THE SAME
LOCATION, INCLUDING TEMPERATURE AND SHRINKAGE LAP SPLICES.
2.1 PROVIDE CLASS B LAP SPLICES UNLESS DETAILED AND APPROVED BY ENGINEER.
3. CLASS B LAP SPLICES ARE TO BE USED WHEN > 50% OF BARS ARE LAPPED AT THE SAME LOCATION, INCLUDING TEMPERATURE AND SHRINKAGE LAP SPLICES.
4. HORIZONTAL (TOP) BARS HAVE MORE THAN 12" OF FRESH CONCRETE PLACED BELOW
REINFORCEMENTS. SPLICE LENGTHS ARE ROUNDED UP TO THE NEAREST INCH.
CONCRETE CONSTRUCTION
1. ALL CONCRETE DESIGN AND CONSTRUCTION SHALL CONFORM TO THE LOCAL BUILDING CODE REQUIREMENTS AND THOSE OF THE LATEST EDITION OF THE FOLLOWING STANDARDS: ACI 318, ACI 315, ACI 301, AND ACI 305 & 306.
2. ALL CONCRETE UNLESS SPECIFICALLY NOTED SHALL BE NORMAL WEIGHT (145 PCF) AND SHALL ACHIEVE A
MIX DESIGN CRITERIA AS FOLLOWS:
FOOTINGS
CONCRETE MIX DESIGN CRITERIA
LOCATION
EXTERIOR FDTN WALLS, PIERS, & GRADE BEAMS
INTERIOR SLAB ON GROUND < 6" THICK
ALL OTHER CONCRETE
28 DAY
MIN f'c
(PSI)1
1. INDICATES MINIMUM 28 DAY COMPRESSIVE STRENGTH (fc').
2. WATER/CEMENT RATIO SHALL MEET DURABILITY REQUIREMENTS OF ACI 318 BASED ON EXPOSURE
CLASS NOTED. CORROSION EXPOSURE SHALL BE F0, S0, W0, C0 UNLESS NOTED OTHERWISE IN THE
EXPOSURE CLASS TABLE COLUMN ABOVE.
3. ALL CONCRETE WITHOUT SUPERPLASTICIZERS SHALL HAVE A MAXIMUM SLUMP OF 4”.
4. ALL MIX DESIGNS SHALL UTILIZE THE STATED TOP AGGREGATE SIZE IN AN EVENLY DISTRIBUTED
AGGREGATE GRADATION.
5. ALL CONCRETE MIX DESIGNS SHALL MINIMIZE SHRINKAGE AS MUCH AS IS PRACTICAL. INCLUDING
SELECTION OF AGGREGATE TYPE, SIZE, GRADATIONS W/ C RATIO AND ADD MIXTURES.
6. CALCIUM CHLORIDE AND OR ADMIXTURES CONTAINING CALCIUM CHLORIDE SHALL NOT BE USED.
3,000
4,000
4,000
4,500
3,000
6%
AIR
ENTRAIN
(+/-1.5%)
6%
MAX TOP
AGGREGATE
SIZE5
3/4"
3/4"
1"
1 1/2"
1 1/2"
INTERIOR SLAB ON GROUND ≥ 6" THICK 5,000 1 1/2"-
EXTERIOR SLAB ON GROUND < 6" THICK
EXPOSURE
CLASS2
(ACI 318)
INTERIOR SLAB ON METAL DECK 4,000 - 3/8"
FLOWABLE FILL 1,000 - -
F1
F2
C1
C1
C2
MASONRY CONSTRUCTION
1. MASONRY DESIGN AND CONSTRUCTION SHALL CONFORM TO THE LATEST EDITION OF THE FOLLOWING
STANDARDS: ACI- 530, ACI- 530.1
2. STABILITY OF THE MASONRY WALL(S) DURING CONSTRUCTION IS THE RESPONSIBILITY OF THE GENERAL/ SUB
CONTRACTOR UNTIL THE WALLS ARE PROPERLY ATTACHED TO THE FRAMING SYSTEM.
3. NET COMPRESSIVE STRENGTH (f'CMU) FOR INDIVIDUAL MASONRY UNITS SHALL BE NOT LESS THAN 3,250 PSI WHEN TESTED IN CONFORMANCE WITH ASTM C140 RESULTING IN A MINIMUM ALLOWABLE COMPRESSIVE STRENGTH OF MASONRY (f’m) = 2,500 PSI (PER TABLE 2 FROM TMS 602).
4. MORTAR SHALL COMPLY WITH ASTM C 270 TYPE S.
5. GROUT SHALL COMPLY WITH ASTM C 476 AND HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3,000 PSI.
6. ALL WALLS SHALL BE RUNNING BOND UNLESS NOTED OTHERWISE ON PLAN.
7. ALL VERTICAL AND HORIZONTAL REINFORCING STEEL BARS IN MASONRY SHALL BE ASTM A615 GRADE 60.
8. HOLLOW CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90 FOR NORMAL WEIGHT UNITS. ALL CONCRETE MASONRY UNITS ON EXTERIOR WALLS, REGARDLESS OF EXTERIOR FINISHES, SHALL BE TYPE 1
(MOISTURE CONTROLLED BLOCK).
9. TEST RESULTS FOR NET COMPRESSIVE STRENGTH MUST BE SUBMITTED FOR REVIEW PRIOR TO
CONSTRUCTION.
10. IN ALL WALLS PROVIDE HORIZONTAL LADDER TYPE JOINT REINFORCEMENT CONSISTING OF 2- W1.7 (9GA) WIRES LOCATED AT 16” ON CENTER VERTICALLY OR FROM BOND BEAMS. INSTALL JOINT REINFORCEMENT IN THE FIRST AND SECOND BED JOINTS IMMEDIATELY ABOVE AND BELOW WALL OPENINGS. EXTEND THE
HORIZONTAL REINFORCEMENT 2 FEET PAST WALL OPENINGS.
11. ALL HORIZONTAL JOINT REINFORCEMENT SHALL HAVE A MINIMUM OF 5/8” COVER AND BE HOT DIP
GALVANIZED.
12. FOR ALL NON LOAD BEARING MASONRY PARTITION WALLS, PROVIDE FULLY GROUTED HORIZONTAL BOND BEAMS WITH TWO NUMBER 4-BARS AT THE TOP OF WALLS, AT 8’-0” ON CENTER AND ABOVE ALL WALL
OPENINGS AND STEEL LINTELS.
13. UNLESS NOTED OTHERWISE ON PLANS PROVIDE 2X THE TYPICAL VERTICAL REINFORCING BAR IN THE FIRST FULL HEIGHT CELL EACH SIDE OF DOOR JAMBS, WINDOW OR WALL OPENINGS, CONTROL JOINTS OR OTHER
DISCONTINUITIES, AND EDGE OF LINTEL BEARING.
14. CELLS UNDER LINTEL BEAMS SPANNING 6’-0” OR MORE SHALL BE FULLY GROUTED WITH TYPICAL VERTICAL
REINFORCING.
15. ALL CELLS CONTAINING VERTICAL REINFORCEMENT SHALL BE GROUTED SOLID WITH 2500 PSI GROUT. GROUT LIFT HEIGHTS SHALL NOT EXCEED 4’-0”, GROUT POUR HEIGHTS SHALL NOT EXCEED 24’-0”. MECHANICAL CONSOLIDATION BETWEEN LIFTS IS REQUIRED. CLEAN OUT CELLS ARE REQUIRED AT THE BASE OF EACH
GROUT POUR THAT EXCEEDS 5’-0”.
16. GROUT SHALL BE STOPPED 1.5” FROM COURSING JOINT TO CREATE A KEY AT THE POUR JOINT.
17. REINFORCING BAR SUPPORTS ARE REQUIRED AT TOP, BOTTOM AND 10’-0” ON CENTER ALONG THE LENGTH
OF THE BAR. REINFORCING BARS SHALL BE PLACED PRIOR TO GROUTING CELLS.
18. HORIZONTAL REINFORCEMENT EMBEDDED IN GROUT SUCH AS LINTEL BEAMS SHALL HAVE A CLEAR
THICKNESS OF GROUT BETWEEN THE MASONRY UNIT AND THE REINFORCEMENT OF 1/2”.
19. LINTELS AND BOND BEAMS ARE REQUIRED AT ALL WALL OPENINGS GREATER THAN 8- INCHES.
20. USE ONLY U SHAPED LINTEL BLOCK FOR MASONRY LINTELS. CENTERLINE OF REINFORCING TO BE LOCATED
MAXIMUM OF 3” UP FROM BOTTOM OF LINTEL BLOCK.
21. ALL BOLTS AND ANCHORS IN MASONRY SHALL BE GROUTED INTO POSITION OR BE INSTALLED IN SOLID GROUTED MASONRY AS NOTED ON PLAN. ANCHORS SHALL NOT BE INSTALLED IN UNGROUTED MASONRY
UNLESS SPECIFICALLY SHOWN IN DETAILS.
22. FOR ALL LINTEL AND BOND BEAM HORIZONTAL REINFORCING LAP #4 BARS 36” AND ALL #5 BARS 60”. FOR VERTICAL WALL REINFORCING LAP ALL #4 AND #5 BARS 30”. LAP VERTICAL BARS 36X DIAMETER U.N.O. (#5 = 30”).
23. ALL MASONRY IN CONTACT WITH THE EARTH SHALL BE GROUTED SOLID.
24. SLUMP OF GROUT SHALL BE IN THE RANGE OF 7 TO 11 INCHES
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
D R
A W
IN
G
S E
T
D A
T E
R E
V
IS
IO
N
S
P R
O
JE
C T
N O
COPYRIGHT STRANG, INC. 2025
B R
A N
D T
R O
A D
M A
D
IS
O N
, W I
C D
3/
/2
S T
R U
C T
U R
A L
N O
T E
S
D A
N E
C O
U N
T Y
D E
P T
O F
W A
S T
E
R E
N E
W A
B
LE
S
M A
IN
T
E N
A N
C E
S H
O P
BS001
N O
D
E S
C R
IP
T
IO
N
D A
T
. 2026
STRUCTURAL STEEL FRAMING
1. STRUCTURAL STEEL DESIGN AND FABRICATION SHALL BE IN ACCORDANCE WITH THE AISC ASD 15TH EDITION
STEEL CONSTRUCTION MANUAL.
2. W-SHAPES SHALL CONFORM TO ASTM A992 (Fy = 50 KSI).
3. ALL STRUCTURAL STEEL ANGLE AND CHANNEL SHAPES SHALL CONFORM TO ASTM A36 (Fy =36 KSI) UNLESS
NOTED OTHERWISE.
4. PLATE STEEL SHALL CONFORM TO ASTM A36 (Fy = 36 KSI).
5. THE STRUCTURAL STEEL FABRICATOR SHALL BE RESPONSIBLE FOR THE SELECTION, DESIGN AND DETAILING
OF ALL CONNECTIONS NOT FULLY DETAILED ON THE CONTRACT DRAWINGS.
A. CONNECTION DETAILS ARE INDICATED ON THE DRAWINGS FOR DESIGN INTENT ONLY. WHEN BOLTS ARE SHOWN ON SPECIFIC DETAILS, UNLESS THE NUMBER OF BOLTS IS SHOWN NUMERICALLY, USE GRAPHICAL
REPRESENTATION FOR DESIGN CONCEPT ONLY.
B. WHERE MOMENT CONNECTIONS ARE INDICATED, PROVIDE CONNECTION TO DEVELOP FULL MOMENT
CAPACITY OF WEAKER SECTION TO BE CONNECTED, UNLESS A SPECIFIC VALUE IS SHOWN.
6. ALL CONNECTION BOLTING IS TO BE WITH A 3/4" DIAMETER A-325n BOLTS UNLESS NOTED OTHERWISE. BOLTS
NEED ONLY BE TIGHTENED TO THE SNUG-TIGHT CONDITIONS.
7. ALL GALVANIZED MEMBERS SHALL BE GALVANIZED BY THE “DRY GALVANIZING PROCESS” AS DEFINED BY AGA (FLUX AND GALVANIZING APPLIED IN SEPARATE STEPS). PROVIDE ALTERNATE COST TO GALVANIZE PER THE “WET” METHOD (FLUX AND GALVANIZING IN ONE STEP). GALVANIZED MEMBERS SHALL NOT BE QUENCH
COOLED.
8. ALL WELDING OF GALVANIZED MATERIAL SHALL BE PERFORMED IN SUCH A MANOR AS TO SATISFY ALL OSHA AND AWS REQUIREMENTS. ALL FIELD WELDED LOCATIONS SHALL BE PREPARED AND PRIMED WITH A ZINC RICH PRIMER PRIOR TO PAINTING PER THE MANUFACTURER’S RECOMMENDATIONS. THE SPECIFIC PRIMER TO BE USED SHALL BE TNEMEC SERIES 90-97 TNEMEC-ZINC @ 3.0-4.0 mils DFT OR APPROVED EQUAL.
9. STUD ANCHORS ARE TO BE NELSON STUDS OR EQUIVALENT.
10. ALL WELDING OF NEW STEEL TO BE WITH E70XX ELECTRODES.
11. ALL WELDING SHALL COMPLY WITH THE AWS STRUCTURAL WELDING CODES. ALL WELDING TO BE PERFORMED
BY AWS PRE- QUALIFIED WELDERS CERTIFIED FOR THE GIVEN APPLICATION.
12. ALL EXTERIOR EXPOSED STEEL SHALL BE HOT DIP GALVANIZED OR PRIMED WITH A ZINC RICH PRIMER AND PAINTED WITH AN APPROPRIATE EXTERIOR PAINT. ALL PAINTING AND STEEL PREP SHALL BE IN CONFORMANCE
WITH MANUFACTURER'S SPECIFICATION.
13. UNLESS SPECIFIED OTHERWISE REMOVE PAINT PRIOR TO WELDING NEW TO EXISTING STEEL. PRIME PAINT MAY BE WIRE BRUSHED, HOWEVER THE PRIMER COMPOSITION AND THICKNESS MUST BE COMPATIBLE WITH WELDING.
INSPECT FOR POROSITY IN WELDS REMOVE AND RE-WELD ANY DEFECTIVE WELDS. DO NOT PAINT WELDS PRIOR
TO INSPECTION.
14. SUBMIT PRODUCT DATA FOR EACH TYPE OF PRODUCT SPECIFIED. SUBMIT MIL TEST REPORTS SIGNED BY
MANUFACTURES CERTIFYING THAT THEIR PRODUCTS COMPLY WITH REQUIREMENTS.
15. ALL INSTALLED STEEL SHALL BE SMOOTH - HAZARD FREE.
16. SUBMIT SHOP DRAWINGS DETAILING FABRICATION OF STRUCTURAL STEEL COMPONENTS.
17. THE GENERAL CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER OF ANY FABRICATION OR ERECTION ERRORS OR DEVIATIONS FROM THE STRUCTURAL DOCUMENTS, AND MUST RECEIVE WRITTEN
APPROVAL FROM THE STRUCTURAL ENGINEER BEFORE ANY FIELD CORRECTIONS ARE MADE.
18. OPENINGS MAY NOT BE MADE THROUGH STRUCTURAL STEEL FRAMING TO ACCOMMODATE THE WORK OF OTHER TRADES UNLESS SPECIFICALLY INDICATED ON THE STRUCTURAL DRAWINGS OR APPROVED IN ADVANCE BY THE STRUCTURAL ENGINEER. THIS INCLUDES, BUT IS NOT LIMITED TO, MODIFICATIONS SUCH AS
BEAM WEB OPENINGS AND COLUMN WEB OPENINGS.
STEEL JOISTS
1. MANUFACTURER MUSH BE CERTIFIED BY SJI TO MANUFACTURE JOISTS SIMILAR TO THOSE INDICATED FOR
THIS PROJECT AND WITH A RECORD OF SUCCESSFUL IN-SERVICE PERFORMANCE.
2. JOISTS AND SEAT CONNECTION SHALL BE DESIGNED TO RESIST AXIAL AND WIND LOADS AS NOTED, OR TO RESIST A HORIZONTAL FORCE ACTING PARALLEL TO THE JOIST, NOT LESS THAN 5 PERCENT OF THE DEAD
PLUS LIVE LOAD REACTION, WHICHEVER IS GREATER.
3. JOIST BRIDGING WHERE SHOWN IS SCHEMATIC IN NATURE ONLY. SUPPLIER SHALL DESIGN AND INDICATE LOCATION AND CONNECTION DETAILS OF ALL BRIDGING ON JOIST ERECTION DRAWINGS. SUPPLIER SHALL
FURNISH ALL BRIDGING MATERIAL.
4. BRIDGING CONNECTION TO WALLS AND STEEL FRAMING BY JOIST SUPPLIER.
5. WHEN CONCENTRATED LOADS THAT ARE GREATER THAN 100 LBS ARE APPLIED AT POINTS OTHER THAN PANEL POINTS, THE JOIST SUPPLIER/DESIGNER SHALL DESIGN FOR THE LOCALIZED CHORD BENDING, OR ADDITIONAL WEB MEMBERS SHALL BE PROVIDED AND FIELD INSTALLED BY THE CONTRACTOR AS SHOWN IN
THE DRAWINGS.
6. CONCENTRATED LOADS APPLIED TO JOIST TOP OR BOTTOM CHORDS MUST BE CONNECTED SO THAT LOAD IS APPLIED EQUALLY (CONCENTRICALLY) TO BOTH MEMBERS OF THE CHORD TO PREVENT INDUCING TORSION INTO THE CHORD MEMBERS. FOR EXAMPLE, HANGER CLAMPS WHICH ATTACH ONLY TO ONE OUTSTANDING
LEG OF A BOTTOM CHORD ANGLE WILL NOT BE PERMITTED.
7. JOIST SEATS SHALL HAVE A CAPACITY TO RESIST A LATERAL LOAD APPLIED TO THE TOP CHORD AND PERPENDICULAR TO THE SPAN. THIS "ROLLOVER" LOAD SHALL BE A MINIMUM OF 2000 LBS FOR 2 ½" DEEP SEATS, 1500 LBS FOR SEATS BETWEEN 2 ½" AND 5" DEEP AND 1000 LBS FOR SEAT DEPTHS 5" AND
GREATER.
8. SUBMIT SHOP DRAWINGS SHOWING LAYOUT, MARK, NUMBER, TYPE, LOCATION, AND SPACING OF JOISTS.
INCLUDE JOINING AND ANCHORAGE DETAILS, BRACING, BRIDGING, ACCESSORIES, ETC.
9. SUBMIT FOR RECORD CALCULATIONS AND ASSOCIATED REFERENCED ERECTION DRAWINGS. CALCULATIONS MUST BE SIGNED AND SEALED BY A REGISTERED PROFESSIONAL ENGINEER IN THE STATE WHERE THE
PROJECT IS LOCATED.
10. MANUFACTURER MUST BE CERTIFIED BY SJI TO MANUFACTURE JOISTS SIMILAR TO THOSE INDICATED FOR
THIS PROJECT AND WITH A RECORD OF SUCCESSFUL IN-SERVICE PERFORMANCE.
11. JOIST MANUFACTURING, DESIGN, HANDLING, INSTALLATION, CAMBER, ETC. TO COMPLY WITH SJI
SPECIFICATIONS.
12. COMPLY WITH AWS REQUIREMENTS AND PROCEDURES FOR SHOP WELDING, APPEARANCE, QUALITY OF
WELDS, AND METHODS USED IN CORRECTING WELDING WORK.
13. PROVIDE FINISH AS REQUIRED PER THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS.
14. ALL JOISTS SHALL BE DESIGNED FOR A MINIMUM 5 PSF BOTTOM CHORD APPLIED COLLATERAL LOAD.
15. PROVIDE SPECIAL JOISTS AND CONNECTIONS CAPABLE OF WITHSTANDING THE DESIGN LOADS AS SHOWN ON THE DRAWINGS. INCLUDE ALL SNOW DRIFTING, HVAC EQUIPMENT, AND OTHER LOADING AS INDICATED.
16. PROVIDE THE FOLLOWING MAXIMUM ALLOWABLE DEFLECTION CRITERIA:
L/360 LIVE LOAD
L/240 TOTAL LOAD
STEEL DECK
1. STEEL DECK SHALL COMPLY WITH THE PROVISIONS OF THE LATEST EDITIONS OF THE FOLLOWING STANDARDS:
AISI, AWS, AND SDI.
2. WELDING PROCESSES AND WELDING OPERATORS SHALL BE QUALIFIED BY THE AWS "STANDARD
QUALIFICATION PROCEDURE."
3. SUBMIT SHOP DRAWINGS SHOWING LAYOUT AND TYPES OF DECK UNITS, FASTENER PATTERNS, SUPPLEMENTARY FRAMING, ETC.
4. PROVIDE DECK CONFIGURATIONS COMPLYING WITH SDI "ROOF DECK SPECIFICATIONS" RELATING TO THE
SECTION PROPERTIES AS INDICATED ON THE DRAWINGS.
5. INSTALL DECK UNITS AND ACCESSORIES IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS AND
FINAL SHOP DRAWINGS.
6. AFTER DECKING INSTALLATION WIRE BRUSH, CLEAN, AND PAINT SCARRED AREAS, WELDS, AND RUST SPOTS
ON TOP AND BOTTOM SURFACES OF DECKING UNITS AND SUPPORTING STEEL MEMBERS.
7. IN AREAS WHERE SHOP PAINTED SURFACES ARE TO BE EXPOSED APPLY TOUCH-UP PAINT TO BLEND INTO
ADJACENT SURFACES.
STRUCTURAL ABBREVIATIONS
@ AT
AB ANCHOR BOLT
ACCOM ACCOMMODATE
AFF ABOVE FINISH FLOOR
AGG AGGREGATE
ALT ALTERNATE
ARCH ARCHITECT/ ARCHITECTURAL
B- B BACK- TO- BACK
BL BUILDING LINE
BLDG BUILDING
BLK BLOCK
BM BEAM
BOT BOTTOM
BRG BEARING
BS BOTH SIDES
C CHANNEL DESIGNATION
CB CATCH BASIN
C/ C CENTER- TO- CENTER
CG CENTER OF GRAVITY
CI CAST IRON
CIP CAST- IN- PLACE
CJ CONTROL OR CONSTRUCTION JT
CL CENTERLINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMP COMPOSITE
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
CONTR CONTRACTOR
D DEPTH
Ø DIAMETER
DIA DIAMETER
DIM DIMENSION
DN DOWN
DTL DETAIL
DWG DRAWING
DWL DOWEL
EA EACH
EC ELECTRICAL CONTRACTOR
EJ EXPANSION JOINT
EL ELEVATION
ELEV ELEVATOR
ENG ENGINEER
EOD EDGE OF DECK
EOG EDGE OF GRATING
EQ EQUAL
EW EACH WAY
E- W EAST- WEST DIRECTION
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FB FLANGE BRACE
FD FLOOR DRAIN
FDN FOUNDATION
FF FINISH FLOOR
F- F FACE- TO- FACE
FL FRAME LINE
FLG FLANGE
FUT FUTURE
FV FIELD VERIFY
FTG FOOTING
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GL GRID LINE
HC HVAC CONTRACTOR
HK HOOK
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HIGH POINT
HT HEIGHT
HVAC HEATING, VENTILATING, & AIR COND
HWS HEADED WELDED STUD
ID INSIDE DIAMETER
INSUL INSULATION
INT INTERIOR
JT JOINT
KB KNEE BRACE
L STEEL ANGLE DESIGNATION
LG LONG/ LENGTH
LGMF LIGHT GAGE METAL FRAMING
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LP LOW POINT
LVL LAMINATED VENEER LUMBER
MAX MAXIMUM
MBW MASONRY BEARING WALL
MECH MECHANICAL
MFG MANUFACTURE
MIN MINIMUM
MISC MISCELLANEOUS
MTL METAL
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
N- S NORTH- SOUTH DIRECTION
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVER HEAD
OPP OPPOSITE
OS ONE SIDE
PC PLUMBING CONTRACTOR
P/ C PRECAST/ PRESTRESSED
PDF POWDER DRIVEN FASTENER
PEMB PRE- ENGINEERED METAL
BUILDING
PERM PERIMETER
PJF PRE- FORMED JOINT FILLER
⅊ PLATE
PL PLATE
P/ T POST TENSIONED
PROJ PROJECTION
PVMT PAVEMENT
R RADIUS
R/ C REINFORCED CONCRETE
RD ROOF DRAIN
REINF REINFORCING
REQD REQUIRED
SCHED SCHEDULE
SIM SIMILAR
SHT SHEET
SPA SPACE/ SPACES
SPEC SPECIFICATION
SQ SQUARE
SSTL STAINLESS STEEL
STL STEEL
STR STRUCTURAL
TBE TRUSS BEARING ELEVATION
THK THICK
TO TOP OF
TC TOP OF CURB ELEVATION
TL TOP OF LEDGE ELEVATION
TP TOP OF PIER ELEVATION
TW TOP OF WALL ELEVATION
TOS TOP OF STEEL ELEVATION
TSL TOP OF SLAB ELEVATION
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VIF VERIFY IN FIELD
W WIDTH
W/ WITH
W/ O WITHOUT
WCJ WALL CONTROL JOINT
WD WOOD
WF WIDE FLANGE
WP WORKING POINT
WSBW WOOD STUD BEARING WALL
WWF WELDED WIRE FABRIC
DELEGATED DESIGN:
1. DELEGATED DESIGN CONSISTS OF ELEMENTS OF THE WORK THAT ARE NOT INCLUDED IN THE INITIAL PERMIT SUBMITTAL AND ARE REQUIRED TO BE SUBMITTED AT A LATER DATE TO THE BUILDING OFFICIAL, ARCHITECT, AND/OR ENGINEER OF RECORD.
2. ALL DELEGATED DESIGN SUBMITTALS SHALL BE PREPARED, SIGNED, AND SEALED BY A LICENSED PROFESSIONAL ENGINEER IN THE STATE IN WHICH THE PROJECT IS LOCATED.
This is the start of the file's text. The full file is on GovTribe.