RFB 326002 - Volume 2: Design and Engineering Documentation
This document comprises the architectural, structural, mechanical, electrical, plumbing, and technology design drawings for the Dane County Department of Waste & Renewables Education and Administration Center, a new two-story, 23,806 gross square foot mixed-use building located at 4402 Brandt Road, Madison, Wisconsin. The project is being delivered as part of the Dane County Sustainability Campus initial construction phase under RFB 326002, with sealed bids due Thursday, May 21, 2026 at 2:00 pm and a mandatory pre-bid meeting scheduled for Wednesday, April 22, 2026 at 10:00 am. The Education and Administration Center will serve as an administrative and public assembly facility with anticipated occupancy of 429 persons (368 on the first floor and 63 on the second floor), featuring break rooms, assembly spaces, business offices, wellness and fitness areas, conference rooms, restrooms, locker rooms, laundry facilities, and mechanical/electrical support spaces. The building is designed as Type 5B construction with full fire sprinkler protection per NFPA 13, meeting Wisconsin Commercial Building Code requirements based on 2021 IBC standards. Construction is anticipated to commence July 6, 2026, with substantial completion required by September 30, 2027.
The design documents establish comprehensive technical requirements across all building systems, including structural steel framing with open-web steel joists, concrete foundations with footings extending to a minimum of 4 feet below finished grade on 3,000 PSF bearing capacity soil, mechanical systems with chilled water loops and air handling units, electrical distribution with emergency backup power capability, plumbing systems with fixture calculations per IBC Table 2902.1, fire protection sprinkler systems, and technology/audio-visual infrastructure. Special inspections are required for soils, concrete construction, structural steel, open-web steel joists, steel deck, and masonry per 2021 IBC Table 1705 requirements. The project incorporates sustainable design features including provisions for future solar photovoltaic array installation (5 PSF design load allocation on roof), accessible design meeting ICC/ANSI A117.1-2009 standards, and stormwater management infrastructure. All structural design, delegated design items including open-web steel joists and cold-formed steel stud wall framing, and shop drawings require professional engineer review and certification prior to fabrication. The bid structure includes a lump sum base bid, three alternate bids, unit pricing for unsuitable soil and rock removal, and a $100,000 allowance for unforeseen field conditions, with bidders required to demonstrate minimum project experience of 50 percent or greater size or value in similar work and maintain Best Value Contractor pre-qualification status.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTURAL MECHANICAL
STRUCTURAL ELECTRICAL
ARCHITECTURAL DESIGN, FIRE PROTECTION DESIGN, MECHANICAL,
ELECTRICAL, AND PLUMBING ENGINEERING
STRANG, INC.
STRUCTURAL ENGINEERING
MP-SQUARED STRUCTURAL ENGINEERS, LLC
LANDSCAPE ARCHITECTURE
SAIKI DESIGN, INC.
TECHNOLOGY DESIGN
NETWORK TECHNOLOGIES, INC.
DESIGN TEAM PROJECT IMAGE
SHEET INDEX
STAMPS
SITE LOCATION MAP
D R
A W
IN
G
S E
T
D A
T E
COPYRIGHT STRANG, INC. 2026
R E
V
IS
IO
N
S
P R
O
JE
C T
N O
4402 BRANDT ROAD
MADISON, WI 53718 PROJECT NO. : 2024131
DANE COUNTY DEPT OF WASTE & RENEWABLES - EDUCATION AND
ADMIN CENTER
B R
A N
D T
R O
A D
M A
D
IS
O N
, W I
C D
/3
1/
T
IT
LE
S
H E
E T
D A
N E
C O
U N
T Y
D E
P T
O F
W A
S T
E
R E
N E
W A
B
LE
S
E D
U C
A T
IO
N
A N
D A
D M
IN
C
E N
T E
R
AG000
GENERAL
AG000 TITLE SHEET
AG001 GENERAL INFORMATION
AG002 LIFE SAFETY PLAN & CODE INFORMATION
AG003 FIRST FLOOR LIFE SAFETY PLAN
AG004 SECOND FLOOR LIFE SAFETY PLAN
STRUCTURAL
AS001 STRUCTURAL NOTES
AS002 STRUCTURAL NOTES AND SCHEDULES
AS003 SPECIAL INSPECTION
AS004 SPECIAL INSPECTION CONT.
AS101 FOUNDATION PLAN
AS201 SECOND FLOOR FRAMING PLAN
AS301 ROOF FRAMING PLAN
AS302 MECHANICAL SCREENWALL FRAMING
AS401 MASONRY WALL ELEVATIONS
AS501 CONCRETE DETAILS
AS502 CONCRETE DETAILS
AS503 CONCRETE DETAILS
AS601 MASONRY DETAILS
AS602 MASONRY DETAILS
AS801 STEEL DETAILS
AS802 STEEL DETAILS
AS803 STEEL DETAILS
AS804 STEEL DETAILS
ARCHITECTURAL
AA001 PARTITION, WALL AND ROOF TYPES
AA002 INTERIOR FINISH SCHEDULE
AA003 DOOR SCHEDULES AND DOOR & FRAME TYPES
AA004 INTERIOR DOOR AND FRAME DETAILS
AA005 EXTERIOR STOREFRONT ELEVATIONS
AA006 EXTERIOR CURTAINWALL ELEVATIONS
AA201 FIRST FLOOR PLAN
AA202 SECOND FLOOR PLAN
AA210 ROOF PLAN
AA261 FIRST FLOOR INTERIOR FINISH PLAN
AA262 SECOND FLOOR INTERIOR FINISH PLAN
AA271 FIRST FLOOR SIGNAGE PLAN
AA272 SECOND FLOOR SIGNAGE PLAN
AA301 FIRST FLOOR REFLECTED CEILING PLAN
AA302 SECOND FLOOR REFLECTED CEILING PLAN
AA401 EXTERIOR ELEVATIONS
AA402 EXTERIOR ELEVATIONS
AA403 EXTERIOR ELEVATIONS
AA410 EXTERIOR SIGNAGE ELEVATIONS
AA501 BUILDING SECTIONS
AA502 BUILDING SECTIONS
AA511 WALL SECTIONS
N
AA512 WALL SECTIONS
AA513 WALL SECTIONS
AA514 WALL SECTIONS
AA515 WALL SECTIONS
AA601 PARTIAL FLOOR PLANS
AA602 ENLARGED RESTROOM AND LOCKER ROOM PLANS
AA603 ENLARGED STAIR AND ELEVATOR PLANS
AA604 STAIR AND ELEVATOR SECTIONS
AA605 STAIR AND ELEVATOR SECTIONS
AA606 ENLARGED PLANS - STAIR B
AA620 ENLARGED CANOPY PLANS
AA621 ENLARGED CANOPY PLANS
AA701 INTERIOR ELEVATIONS
AA702 INTERIOR ELEVATIONS
AA703 INTERIOR ELEVATIONS
AA704 INTERIOR ELEVATIONS
AA705 INTERIOR ELEVATIONS
AA706 INTERIOR ELEVATIONS
AA801 EXTERIOR OPENING DETAILS
AA802 EXTERIOR OPENING DETAILS
AA803 EXTERIOR OPENING DETAILS
AA804 EXTERIOR SECTION DETAILS
AA805 EXTERIOR SECTION DETAILS
AA806 EXTERIOR SECTION DETAILS
AA807 EXTERIOR SECTION DETAILS
AA808 EXTERIOR ROOF SCREEN AND SCREEN WALL DETAILS
AA809 EXTERIOR PLAN DETAILS
AA810 EXTERIOR PLAN DETAILS
AA901 INTERIOR DETAILS
AA902 INTERIOR DETAILS
AA903 INTERIOR DETAILS
AA904 INTERIOR DETAILS
AA905 INTERIOR DETAILS
AA906 INTERIOR DETAILS
AA907 INTERIOR DETAILS
AA908 INTERIOR DETAILS
AA909 INTERIOR SIGNAGE DETAILS
FURNITURE
AF001 EQUIPMENT SCHEDULE
AF201 FIRST FLOOR FURNITURE & EQUIPMENT PLAN
AF202 SECOND FLOOR FURNITURE & EQUIPMENT PLAN
FIRE PROTECTION
AFP001 FIRE PROTECTION SYMBOLS, ABBREVIATIONS AND GENERAL NOTES
AFP201 FIRST FLOOR FIRE PROTECTION PLAN - ADMINISTRATION BUILDING
AFP202 SECOND FLOOR FIRE PROTECTION PLAN - ADMINISTRATION BUILDING
PLUMBING
AP001 PLUMBING SYMBOLS, ABBREVIATIONS AND GENERAL NOTES
AP200U UNDERSLAB PLUMBING PLAN - ADMINISTRATION BUILDING
AP201 FIRST FLOOR PLUMBING WASTE PLAN - ADMINISTRATION BUILDING
AP202 SECOND FLOOR PLUMBING WASTE PLAN - ADMINISTRATION BUILDING
AP203 ROOF PLUMBING PLAN - ADMINISTRATION BUILDING
AP301 FIRST FLOOR PLUMBING SUPPLY PLAN - ADMINISTRATION
AP302 SECOND FLOOR PLUMBING SUPPLY PLAN - ADMINISTRATION BUILDING
AP701 PLUMBING ISOMETRIC - WASTE
AP702 PLUMBING ISOMETRIC - SUPPLY
AP703 PLUMBING ISOMETRIC - STORM
AP801 PLUMBING DETAILS - ADMINISTRATION BUILDING
AP802 PLUMBING DETAILS - ADMINISTRATION BUILDING
AP803 PLUMBING DETAILS - ADMINISTRATION BUILDING
AP901 PLUMBING SCHEDULES - ADMINISTRATION BUILDING
AP902 PLUMBING SCHEDULES - ADMINISTRATION BUILDING
MECHANICAL
AM001 MECHANICAL SYMBOLS, ABBREVIATIONS AND GENERAL NOTES
AM201 FIRST FLOOR MECHANICAL PLAN
AM202 SECOND FLOOR MECHANICAL PLAN
AM203 ROOF MECHANICAL PLAN
AM301 FIRST FLOOR MECHANICAL PIPING PLAN
AM302 SECOND FLOOR MECHANICAL PIPING PLAN
AM701 MECHANICAL CONTROL DIAGRAMS
AM801 MECHANICAL DETAILS
AM802 MECHANICAL DETAILS
AM901 MECHANICAL SCHEDULES
AM902 MECHANICAL SCHEDULES
PROJECT LOCATION
MADISON
IMAGE IS FOR ILLUSTRATION PURPOSES ONLY AND SHOULD NOT BE USED FOR BIDDING OR CONSTRUCTIION.
ELECTRICAL
AE001 ELECTRICAL SYMBOLS, ABBREVIATIONS AND GENERAL NOTES
AE201 FIRST FLOOR ELECTRICAL LIGHTING PLAN
AE202 SECOND FLOOR ELECTRICAL LIGHTING PLAN
AE301 FIRST FLOOR ELECTRICAL POWER PLAN
AE302 SECOND FLOOR ELECTRICAL POWER PLAN
AE303 ROOF ELECTRICAL POWER PLAN
AE304 ROOF ELECTRICAL SOLAR PV PLAN
AE401 FIRST FLOOR ELECTRICAL FIRE ALARM PLAN
AE402 SECOND FLOOR ELECTRICAL FIRE ALARM PLAN
AE501 ELECTRICAL SECTIONS / ELEVATIONS
AE601 ENLARGED ELECTRICAL PLANS
AE701 ELECTRICAL ONE-LINE DIAGRAM
AE801 ELECTRICAL DETAILS
AE901 ELECTRICAL PANELBOARD SCHEDULES
AE902 ELECTRICAL PANELBOARD SCHEDULES
AE911 ELECTRICAL LIGHTING SCHEDULES
AE912 ELECTRICAL LIGHTING SCHEDULES
AE921 ELECTRICAL POWER SCHEDULES
TECHNOLOGY
AT000 PROJECT REQUIREMENTS & SPECIFICATIONS
AT001 PROJECT REQUIREMENTS & SPECIFICATIONS
AT002 SYMBOLS & LEGENDS
AT003 SYMBOLS & LEGENDS
AT004 SYMBOLS & LEGENDS
AT005 COMPONENTS SPECIFICATIONS & NOTES
AT201 FIRST FLOOR PLAN
AT202 SECOND FLOOR PLAN
AT800 ENLARGED EQUIPMENT ROOM LAYOUTS
AT900 EQUIPMENT RACK DETAILS
AT901 SECURITY SYSTEM DETAILS
AT902 ENLARGED MECHANICAL PLANS
AT903 ENLARGED MECHANICAL PLANS
AUDIO/VISUAL
ATA000 PROJECT REQUIREMENTS & SPECIFICATIONS
ATA001 PROJECT REQUIREMENTS & SPECIFICATIONS
ATA002 SYMBOLS & LEGENDS
ATA003 SYMBOLS & LEGENDS
ATA201 FIRST FLOOR PLAN
ATA202 SECOND FLOOR PLAN
ATA301 FIRST FLOOR REFLECTED CEILING PLAN
ATA302 SECOND FLOOR REFLECTED CEILING PLAN
ATA700 ONE-LINE DIAGRAM
ATA701 ONE LINE DIAGRAM
ATA702 ONE LINE DIAGRAM
ATA703 ONE LINE DIAGRAM
ATA704 ONE LINE DIAGRAM
ATA900 DETAILS
N O
D
E S
C R
IP
T
IO
N
D A
T E
DETAIL REFERENCE
Detail Number
Sheet Number
SECTION REFERENCE
Section Number
Sheet Number
BUILDING SECTION REFERENCE
Building Section Number
Sheet Number
INTERIOR ELEVATION
Interior Elevation Number
Sheet Number
EXTERIOR ELEVATION
Exterior Elevation Number
Sheet Number
ROOM NAME/
ROOM NUMBER
PARTITION TYPE
SPECIFIC ELEVATION NOTE
SPECIFIC PLAN NOTE
CEILING TYPE AND HEIGHT
WINDOW/BORROWED LIGHT TYPE
VERTICAL ELEVATION
COLUMN GRID NUMBER
REVISION
(Cloud Around Revision)
NAME
ELEVATION
ROOM NAME
RM ##
BL-#
SPECIFIC DEMOLITION NOTE#
TYPE
HT
ELEV
TYPE
CURTAINWALL / STOREFRONT
TYPE AND ELEVATION
EXTERIOR WALL AND ROOF
SYSTEM TYPE
WS-#
RS-#
PRECAST CONCRETE
CONCRETE MASONRY UNIT (SECTION)
BRICK (SECTION)
STEEL (SECTION)
RIGID INSULATION (SECTION)
EXTERIOR INSULATION AND FINISH SYSTEM (ELEVATION)
PLYWOOD (SECTION)
GRANULAR FILL
SOIL, INFILL
SOIL, UNDISTURBED
6" MAX
3' - 0" MIN 3' - 6" MIN
12" MAX
T
.O . S
E A
T
1'
" 3'
A T
A C
C E
S S
IB
LE
U N
IT
1'
NOTE:
- ALL FIXTURE MOUNTING INSTALLATION & CLEARANCE DIMENSIONS SHALL MEET ALL ADA
ACCESSIBILITY STANDARDS AND NO ACCESSORY SHALL PROJECT MORE THAN 4" FROM WALL.
- PROVIDE BLOCKING IN WALLS FOR ALL WALL MOUNTED EQUIPMENT, ACCESSORIES, AND
CABINETRY AS REQUIRED; INCLUDING OWNER ITEMS.
- ALL ITEMS SHOWN ARE NOT NECESSARILY IN THIS PROJECT.
ELONGATED RIM
GRAB BAR (GB)
1' - 6"1' - 6"
18" GRAB BAR (GB)
WATER CLOSET URINAL
2'
3' - 5 1/2"
TOILET PAPER
DISPENSER (TPD)
GRAB BAR (GB)
3'
3' - 3 1/2"
T O
R E
F
LE
C T
IV
E
S U
R F
A C
E
3'
2'
0"
2'
/2
M
IN
MIRROR (MIR)
BOTTOM OF
APRON
INSULATE PIPE DRAIN &
HOT WATER SUPPLY @
ALL SINKS WHERE P.LAM
PANEL IS NOT SHOWN
3'
SOAP DISPENSER (SD)
T O
O P
E R
A B
LE
C
O N
T R
O
LS
3'
M A
X
T O
O P
E R
A B
LE
C
O N
T R
O
LS
3'
M A
X
2'
PAPER TOWEL DISPENSER /
RECEPTACLE (PTD/R)
SANITARY NAPKIN DISPENSER (SND)
SANITARY NAPKIN
RECEPTACLE (SNR)
T O
S P
O U
T O
U T
LE
T
3'
M A
X
2'
M
IN
ELECTRIC WATER
COOLER (EWC)
ACCESSORIES
B .O
. C A
B
IN
E T
2'
FIRE EXTINGUISHER
CABINET (FEC)
5' -0
M
A X
0L B
4' -0
M
A X
0L B
FIRE
EXTINGUISHER (FE)
SANITARY NAPKIN
RECEPTACLE (SNR)
G R
IP
P
IN
G
S U
R F
A C
E
T
O P
O F
1' - 6"
BACK WALL
M
IN
M A
X G R
IP
P
IN
G
S U
R F
A C
E
T
O P
O F
3" -6
1'
M
IN
CONTROLS
AREA
1' - 3" MAX 4"
CONTROL WALL
3' - 0"
3'
3'
4' - 4"
4" MAX
CLEAR FLOOR
SPACE
BACK WALL
S E
A T
W A
LL
C O
N T
R O
L W
A
LL
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
D R
A W
IN
G
S E
T
D A
T E
R E
V
IS
IO
N
S
P R
O
JE
C T
N O
COPYRIGHT STRANG, INC. 2026
B R
A N
D T
R O
A D
M A
D
IS
O N
, W I
C D
/3
1/
G E
N E
R A
L
IN
F O
R M
A T
IO
N
D A
N E
C O
U N
T Y
D E
P T
O F
W A
S T
E
R E
N E
W A
B
LE
S
E D
U C
A T
IO
N
A N
D A
D M
IN
C
E N
T E
R
AG001
# POUND, NUMBER
& AND
< ANGLE
@ AT
A-100 A LABEL - 100 MINUTE FIRE RATING
B-90 B LABEL - 90 MINUTE FIRE RATING
C-45 C LABEL - 45 MINUTE FIRE RATING
D-20 D LABEL - 20 MINUTE FIRE RATING
Ø DIAMETER, ROUND, PHASE
AB ANCHOR BOLT
ABBR ABBREVIATION
ACB ACOUSTICAL CEILING BAFFLE
ACOUS ACOUSTICAL
ACP ACOUSTICAL CEILING PANEL
ACR ACRYLIC, ACRYLIC MARKER BOARD
ADJ ADJUSTABLE, ADJACENT
AFF ABOVE FINISH FLOOR
AFS AIR FLOW STATION
AGGR AGGREGATE
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECTURAL, ARCHITECT
ASPH ASPHALT
AV AIR VALVE
AWP ACOUSTICAL WALL PANEL
BAF BAFFLES
BD BOARD
BHD BULKHEAD
BITUM BITUMINOUS
BL BORROWED LITE
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BN BULLNOSE
BO BOTTOM OF
BOT BOTTOM
BP BASE PLATE
BRG BEARING
BSC BIO-SAFETY CABINET
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
BTW BETWEEN
BUR BUILT-UP ROOF
C CONVECTOR, CHANNEL
CAB CABINET
CB CATCH BASIN
CEM CEMENT
CER CERAMIC
CFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED
CFM CUBIC FEET PER MINUTE
CG CORNER GUARD
CH COAT HOOK
CHBD CHALKBOARD
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLOS CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONJ CONSTRUCTION JOINT
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTROL
CONTR CONTRACTOR
CORR CORRIDOR
CPT SHEET CARPETING
CR CARD READER
CS CAST STONE
CT CERAMIC TILE
CTR CENTER
CTSK COUNTERSINK
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CYL CYLINDER
D DEPTH
DBA DECK BEARING ANGLE
DBL DOUBLE
DEMO DEMOLITION, DEMOLISH
DEPT DEPARTMENT
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DISP DISPENSER
DN DOWN
DO DO OVER, DITTO
DP DAMPPROOFING
DR DOOR
DS DOWNSPOUT
DSD DUCT SMOKE DETECTOR
DT DRAIN TILE
DTL DETAIL
DWG DRAWING
DWL DOWEL
E EAST
EA EACH, EXHAUST AIR
EC ELECTRICAL CONTRACTOR, EXPOSED CONCRETE
EF EXHAUST FAN
EHD ELECTRIC HAND DRYER
EIFS EXTERIOR INSULATION FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ABBREVIATIONS MATERIAL LEGEND
SYMBOL LEGEND
ELEC ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSURE
EP ELECTRIC PANEL, EPOXY
EQ EQUAL
EQUIP EQUIPMENT
ES EXPOSED STRUCTURE
ETR EXISTING TO REMAIN
EW EACH WAY
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXH EXHAUST
EXP EXPANSION
EXPO EXPOSED
EXST EXISTING
EXT EXTERIOR
FA FIRE ALARM
FB FACE BRICK, FLOOR BOX
FCTY FACTORY
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEB FIRE EXTINGUISHER BRACKET
FEC FIRE EXTIINGUISHER CABINET
FF FINISH FLOOR
FFLR FITNESS FLOOR
FH FUME HOOD, FIRE HOSE
FHC FIRE HOSE CABINET
FIN FINISH
FIX FIXTURE
FL FLOOR
FLUOR FLUORESCENT
FO FINISHED OPENING
FOC FACE OF CONCRETE
FOS FACE OF STUD
FPRF FIREPROOFING
FRP FIBERGLASS REINFORCED PLASTIC, FIBERGLASS
REINFORCED PANELING
FRT FIRE RETARDANT
FRZ FREEZER
FT FOOT, FEET
FTG FOOTING
FURR FURRING
FUT FUTURE
FV FIELD VERIFY
G GAS
GA GAUGE
GALV GALANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GFRG GLASS FIBER REINFORCED GYPSUM
GL GLASS
GMGS GLASS MAT GYPSUM SHEATING
GND GROUND
GWB GYPSUM WALL BOARD
GYP GYPSUM
H HIGH
HB HOSE BIBB
HBD HARDBOARD
HC HOLLOW CORE
HDWD HARDWOOD
HDWE HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HORSEPOWER
HPC HIGH PERFORMANCE COATING
HR HOUR
HSS HOLLOW STRUCTURAL STEEL
HT HEIGHT
HVAC HEATING, VENTILATION, & AIR CONDITIONING
HWD HARDWOOD
ID INSIDE DIAMETER
IE INVERT ELEVATION
IF INSIDE FACE
IMP INSULATED METAL PANEL
INSUL INSULATION
INT INTERIOR
ITD IMPACT TRAFFIC DOOR
JAN JANITOR
JBE JOIST BEARING ELEVATION
JT JOINT
KIT KITCHEN
KO KNOCKOUT
KP KICK PLATE
KS KNEE SPACE
L LENGTH, ANGLE
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT LIGHT
LVT LUXURY VINYL TILE
LWC LIGHT WEIGHT CONCRETE
MATL MATERIAL
MAX MAXIMUM
MB MOP BASIN
MC MECHANICAL CONTRACTOR
MECH MECHANICAL
MEMB MEMBRANE
MEP MECHANICAL, ELECTRICAL, PLUMBING
MEZZ MEZZANINE
MFR MANUFACTURER
MH MANHOLE, MOP HOLDER
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
ML&P METAL LATH & PLASTER
MO MASONRY OPENING
MTD MOUNTED
MTL METAL
MUL MULLION
N NORTH
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NP NON POTABLE WATER
NTS NOT TO SCALE
OA OVERALL, OUTSIDE AIR
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OFF OFFICE
OFOI OWNER FURNISHED OWNER INSTALLED
OH OVERHEAD
OHCD OVERHEAD COILING DOOR
OHSD OVERHEAD SECTIONAL DOOR
OP OPERABLE PARTITION
OPG OPENING
OPNG OPENING
OPP OPPOSITE
OPP-H OPPOSITE HAND
PA PUBLIC ADDRESS
PC PLUMBING CONTRACTOR
PCON POLISHED CONCRETE
PDO POWER DOOR OPERATOR
PERP PERPENDICULAR
PL PLATE, PROPERTY LINE
PLAM PLASTIC LAMINATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PR PAIR
PT PAINT
PTD PAPER TOWEL DISPENSER
PTD/R PAPER TOWEL DISPENSER / RECEPTACLE
PTN PARTITION
PTR PAPER TOWEL RECEPTACLE
PVT PAVER TILE
QSM QUARTZ SURFACING MATERIAL
QT QUARRY TILE
R RADIUS, RISER
RA RETURN AIR
RB RESILIENT BASE
RBC RESILIENT BASE COVED
RBS RESILIENT BASE STRAIGHT
RD ROOF DRAIN
REF REFERENCE, REFRIGERATOR
REFR REFRIGERATOR
REINF REINFORCED
REM REMOVE
REQ REQUIRED
REQD REQUIRED
RF RESINOUS FLOORING
RM ROOM, RATED METAL
RO ROUGH OPENING
RSF RUBBER SHEET FLOORING
RSF RUBBER SHEET FLOORING
RT RUBBER TILE
RTF RUBBER TILE FLOORING
RUB RUBBER
RWD REDWOOD
S SOUTH, SINK, SUPPLY
S&V STAIN & VARNISH
SAB SOUND ATTENUATION BLANKET
SAN SANITARY
SB SOIL BORING
SC SOLID CORE
SCD SEAT COVER DISPENSER
SCHED SCHEDULE
SCON SEALED CONCRETE
SD SOAP DISPENSER
SECT SECTION
SF SQUARE FOOT
SH SHELF
SHR SHOWER
SHT SHEET
SIM SIMILAR
SND SANITARY NAPKIN DISPENSER
SNR SANITARY NAPKIN RECEPTACLE
SOG SLAB ON GRADE
SPEC SPECIFICATION
SQ SQUARE
SS STAINLESS STEEL
SSM SOLID SURFACE MATERIAL
ST STONE
STA STATION
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURAL
SUSP SUSPENDED
SWC SUSPENDED WOOD CEILING
SYM SYMMETRICAL
T TREAD, THRESHOLD
T&B TOP & BOTTOM
T&G TONGUE & GROOVE
TEL TELEPHONE
TEMP TEMPORARY, TEMPERATURE
TER TERRAZZO
THK THICK
TKBD TACK BOARD
TOB TOP OF BEAM
TOF TOP OF FOOTING
TOS TOP OF STEEL
TPD TOILET PAPER DISPENSER
TRANS TRANSPARENT
TRZ TERRAZZO
TV TELEVISION
TW TOP OF WALL
TYP TYPICAL
UH UNIT HEATER
UNF UNFINISHED
UNO UNLESS NOTED OTHERWISE
UR URINAL
V VENT, VOLT, VALVE
VAC VACUUM
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VSF VINYL SHEET FLOORING
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
TWC TACKABLE WALL COVERING
W WEST, WIDTH, WIDE, WATT, WASTE, WATER
W/ WITH
W/O WITHOUT
WB WOOD BASE
WC WATER CLOSET
WD WOOD
WF WIDE FLANGE
WM WIRE MESH
WP WATERPROOF, WEATHERPROOF, WALL PROTECTION
WR WATER RESISTANT, WATER RECEPTACLE
WT WEIGHT
WWF WELDED WIRE FABRIC
YD YARD
STANDARD MOUNTING HEIGHTS
N O
D
E S
C R
IP
T
IO
N
D A
EV
PA
RK
ING EV
PA
RK
ING EV
RE
AD
Y
CODE INFORMATION
APPLICABLE CODES:
Wisconsin Commercial Building Code Accessibility: ICC/ANSI A117.1-2009 Edition Commercial Building: 2021 IBC as amended Electrical: 2017 NEC as amended Energy Conservation: 2021 IECC as amended Fire Protection: 2021 IFC as amended Mechanical: 2021 IMC as amended Plumbing: 2021 IPC as amended
CLASSIFICATION OF WORK:
New Building
BUILDING AREA:
First Floor 14,484 gross sq. ft.
Second Floor 9,322 gross sq. ft.
Building Total 23,806 gross sq. ft.
BUILDING HEIGHT:
Two stories above grade plane 29'-6" to surface of highest roof 38'-3" to top of highest parapet
PRIMARY BUILDING USES: (IBC 2021 Chapter 3) Mixed-Use
Occupancies Occupancy group Floor area First Floor Break Room Group A-2, Assembly 969 nsf First Floor Assembly Areas & Accessory Storage Group A-3, Assembly 4,793 nsf First Floor Business Areas & Accessory Storage Group B, Business 8,722 gsf Second Floor Business Areas Group B, Business 9,322 gsf
TYPE OF CONSTRUCTION: (IBC 2021 Chapter 6) 5B
FIRE SPRINKLER SYSTEM:
Fully sprinklered per NFPA 13
FIRE ALARM SYSTEM:
Fire Alarm Initiation and Notification Devices
ALLOWABLE AREA CALCULATIONS: (IBC 2021 Table 506.2) 18,000 sq. ft. per floor Allowable Area per A-2/A-3 Occupancy (most restrictive), Fully Sprinklered
ALLOWABLE HEIGHT CALCULATIONS: (IBC 2021 Tables 504.3 and 504.4) 2 stories 60 feet Allowable Height per A-2/A-3 Occupancy (most restrictive), Fully Sprinklered
FIRE RESISTANCE RATINGS: (IBC 2021 Table 601) Fire Resistance Hourly Ratings for Structural Components:
Primary Structural Frame 0 Hour Bearing Walls, Exterior 0 Hour Bearing Walls, Interior 0 Hour Floor Construction 0 Hour Roof Construction 0 Hour
Fire Resistance Hourly Ratings for Separations:
Corridors 0 Hour, building is fully fire sprinklered (IBC 2021 Table 1020.1) Mechanical Room, equipment > 400,000 Btu / hr 0 Hour, building is fully fire sprinklered (IBC 2021 Table 509.1) Laundry Room over 100 sq. ft. 0 Hour, building is fully fire sprinklered (IBC 2021 Table 509.1) Emergency Electrical Room (> 1,000 AMP) 1 Hour (NFPA 110 7.2.3) Interior Exit Stairways 1 Hour, less than four stories (IBC 2021 1023.2)
A-3
A-2
B
EXIT66"
E X
IT
E X
IT
E X
IT
E X
IT
ACCESSIBLE ROUTE TO ACCESSIBLE PARKING
ACCESSIBLE ROUTES TO PUBLIC WAY
GENERATOR
XFMR
GROUND-MOUNTED
EQUIPMENT SCREEN WALL
DUMPSTERS
BICYCLE RACKS
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
D R
A W
IN
G
S E
T
D A
T E
R E
V
IS
IO
N
S
P R
O
JE
C T
N O
COPYRIGHT STRANG, INC. 2026
B R
A N
D T
R O
A D
M A
D
IS
O N
, W I
C D
/3
1/
LI
F
E S
A F
E T
Y P
LA
N
C
O D
E
IN
F O
R M
A T
IO
N
D A
N E
C O
U N
T Y
D E
P T
O F
W A
S T
E
R E
N E
W A
B
LE
S
E D
U C
A T
IO
N
A N
D A
D M
IN
C
E N
T E
R
AG002
PNTN
SCALE: 1/16" = 1'-0"AG002
1 FIRST FLOOR LIFE SAFETY PLAN
N O
D
E S
C R
IP
T
IO
N
D A
UP
A119
MECH/PLBG
A116
ELECTRICAL
A115
SERVER
A111
LOADING
A113
JANITOR
A112
DRY CHEM
A110
MEETING / MORNING
STANDUP
A109
MUD ROOM /
EQUIPMENT
A108
QUIET BREAK
A106
BREAK ROOM
A105
STORAGE
A104
MEETING
A139
LOCKER ROOM
A138
LAUNDRY / PPE
A114
SCADA
A133
CORRIDOR
A132
CORRIDOR
A128
CORRIDOR
A101
PREFUNCTION
A103
STORAGE
A102
MULTIPURPOSE
A100
VESTIBULE
A140
CORRIDOR
A121
RECORDS
A122
WELLNESS / FITNESS
A123
CONFERENCE
A129
WELL
A130
WELL/
MOTHER
A126
ELEVATOR
A125
MEN
A124
GENDER NEUTRAL /
FAMILY
A131
WOMEN
A134
SHOWER
A135
CHANGING
A136
CHANGING
A137
SHOWER
FE
FEC
FEC
FEC
FE
FEC
A107
QUIET BREAK
AED
FA
AED
AED
FA
AEDFA
AED
FAAED
FA
A117
EM ELECTRICAL
A118
STORAGE
A201C
STAIR
A127
STORAGE
A128
CORRIDOR
A120
STAIR B
ASSEMBLY - TABLE & CHAIRS
969 nsf; 65 persons
E X
IT
EXIT
66"
E X
IT
EXIT 33"
E X
IT
EXIT DIST: 172' - 5"
ASSEMBLY - TABLE & CHAIRS
1,412 nsf; 95 persons
ASSEMBLY - GALLERY SPACE
1,719 nsf; 58 persons
ASSEMBLY - TABLES AND CHAIRS
1,421 nsf; 95 persons
FA
E X
IT
E X
IT
EXIT
33"
E X
IT
NOT TO SCALE
LIFE SAFETY PLAN LEGEND
FIRE EXTINGUISHER CABINET (FEC)
AND FIRE EXTINGUISHER (FE)
EGRESS WIDTH AND DIRECTION 67" Ø WHEELCHAIR TURNING SPACE
1 HOUR FIRE SEPARATION
FEC FE
EXIT0"##
AED FA OFOI ITEMS: AUTOMATED
EXTERNAL DEFIBRILLATOR
(AED) AND FIRST AID KIT (FA)
30" x 48" CLEAR FLOOR SPACE
FIRST FLOOR PLUMBING FIXTURE CALCULATIONS: (IBC 2021 Table 2902.1)
Type of Use Occupant load Water closets Lavatories Drinking Service fountains sink
Men Women Men Women Men Women
Break Room Areas 33 33 0.44 0.44 0.17 0.17 0.14 1 Assembly Areas 157 157 1.26 2.42 0.79 0.79 0.63 1 Business Areas 8 8 0.32 0.32 0.05 0.05 0.16 1 Storage & Equipment 5 5 0.05 0.05 0.05 0.05 0.01 1
Total required for 3 4 2 2 1 1 First Floor
Total provided for First Floor 5* 7** 3 5 2*** 1
Notes * Provided fixtures are one water closet, two urinals, and two single-occupant gender neutral toilet rooms
** Provided fixtures are four water closets and three single-occupant gender neutral toilet rooms *** In addition to two drinking fountains, filtered water for employees provided via fridge in Break Room
EXIT WIDTH CALCULATIONS: (IBC 2021 Section 1005.3.1 & 1005.3.2)
With Sprinkler System & Emergency Communication System:
Stairs, Required Stairs, Provided Other Egress, Required Other Egress, Provided
63 persons x 98 inches 429 persons x 231 inches
0.2 = 12.6 inches 0.15 = 64.4 inches
OCCUPANT LOAD CALCULATIONS: (IBC 2021 Table 1004.5) First Floor Accessory Storage and Equipment areas 2,942 gsf / 300 = 10 persons
Assembly - Gallery Space 1,674 nsf / 30 = 28 persons
Assembly - Tables and Chairs 3,802 nsf / 15 = 255 persons
Business areas 2,382 gsf / 150 = 16 persons
Exercise & Locker Rooms 1,429 gsf / 50 = 29 persons First Floor Total 368 persons
Second Floor Business Areas 9,322 gsf / 150 = 63 persons
Second Floor Total 63 persons Total 429 persons
CODE INFORMATION
PNTN
SCALE: 1/8" = 1'-0"AG003
1 FIRST FLOOR LIFE SAFETY PLAN
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
D R
A W
IN
G
S E
T
D A
T E
R E
V
IS
IO
N
S
P R
O
JE
C T
N O
COPYRIGHT STRANG, INC. 2026
B R
A N
D T
R O
A D
M A
D
IS
O N
, W I
C D
/3
1/
F
IR
S T
F
LO
O R
L
IF
E S
A F
E T
Y P
LA
N
D A
N E
C O
U N
T Y
D E
P T
O F
W A
S T
E
R E
N E
W A
B
LE
S
E D
U C
A T
IO
N
A N
D A
D M
IN
C
E N
T E
R
AG003
N O
D
E S
C R
IP
T
IO
N
D A
DN
A213
OFFICE
A212
OFFICE
A211
OFFICE
A210
OFFICE
A209
OFFICE
A208
OFFICE
A207
EXEC OFFICE
A206
EXEC OFFICE
A216
HVAC
A228
COPY/PRINT A221
RR
A220
RR
A219
RR
A218
JANITOR
A205
CONFERENCE
A204
CONFERENCE
A225
OPEN OFFICE
A201
COFFEE
FEC
FEC
FE
EXIT DIST: 246' - 11"
1790.87 SF
A217
TENANT
A222
ELEVATOR
AED
FA
AED
AED
FA
A202
FOCUS
A203
FOCUS
A223
CORRIDOR
A215
STAIR B
A224
STAIR A
A214
STAIR VESTIBULE
ROOF BELOW
OPEN TO BELOW
EXIT DIST: 199' - 2"
EXIT33"
E X
IT
EXIT33"
EXIT44"
E X
IT
E X
IT
EXIT54"
FA
EXIT PATH CONTINUES ON FIRST FLOOR
STARTING AT THIS POINT. EXITS THE
BUILDING THROUGH VESTIBULE A100
NOT TO SCALE
LIFE SAFETY PLAN LEGEND
FIRE EXTINGUISHER CABINET (FEC)
AND FIRE EXTINGUISHER (FE)
EGRESS WIDTH AND DIRECTION 67" Ø WHEELCHAIR TURNING SPACE
1 HOUR FIRE SEPARATION
FEC FE
EXIT0"##
AED FA OFOI ITEMS: AUTOMATED
EXTERNAL DEFIBRILLATOR
(AED) AND FIRST AID KIT (FA)
30" x 48" CLEAR FLOOR SPACE
SECOND FLOOR PLUMBING FIXTURE CALCULATIONS: (IBC 2021 Table 2902.1)
Type of Use Occupant load Water closets Lavatories Drinking Service fountains sink
Business Areas 63 2.26 1.58 0.63 1
Total required for 3 3 1 1 First Floor
Total provided for First Floor 3* 3 0** 1
Notes * Provided fixtures area three single-occupant gender neutral toilet rooms
** Second floor space for employees only. Filtered water for employees provided via fridge in Break Room
EXIT WIDTH CALCULATIONS: (IBC 2021 Section 1005.3.1 & 1005.3.2)
With Sprinkler System & Emergency Communication System:
Stairs, Required Stairs, Provided Other Egress, Required Other Egress, Provided
63 persons x 98 inches 708 persons x 231 inches
0.2 = 12.6 inches 0.15 = 106.2 inches
OCCUPANT LOAD CALCULATIONS: (IBC 2021 Table 1004.5) First Floor Accessory Storage and Equipment areas 2,942 gsf / 300 = 10 persons
Assembly - Standing Space 1,674 nsf / 5 = 335 persons
Assembly - Tables and Chairs 3,802 nsf / 15 = 255 persons
Business areas 2,382 nsf / 150 = 16 persons
Exercise & Locker Rooms 1,429 gsf / 50 = 29 persons First Floor Total 645 persons
Second Floor Business Areas 9,322 gsf / 150 = 63 persons
Second Floor Total 63 persons Total 708 persons
CODE INFORMATION
PNTN
SCALE: 1/8" = 1'-0"AG004
1 SECOND FLOOR LIFE SAFETY PLAN
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
D R
A W
IN
G
S E
T
D A
T E
R E
V
IS
IO
N
S
P R
O
JE
C T
N O
COPYRIGHT STRANG, INC. 2026
B R
A N
D T
R O
A D
M A
D
IS
O N
, W I
C D
/3
1/
S E
C O
N D
F
LO
O R
L
IF
E S
A F
E T
Y P
LA
N
D A
N E
C O
U N
T Y
D E
P T
O F
W A
S T
E
R E
N E
W A
B
LE
S
E D
U C
A T
IO
N
A N
D A
D M
IN
C
E N
T E
R
AG004
N O
D
E S
C R
IP
T
IO
N
D A
LOADING
1. DESIGNED IN ACCORDANCE WITH THE CURRENT WISCONSIN COMMERCIAL BUILDING CODE BASED ON
THE 2021 INTERNATIONAL BUILDING CODE.
2. DESIGN LOADS:
A. FLOOR DEAD LOAD:
65 PSF TOTAL
B. ROOF DEAD LOAD:
24 PSF TOTAL (INCLUDES 5 PSF FOR FUTURE SOLAR PANEL ARRAY)
C. FLOOR LIVE LOAD:
50 PSF OFFICE
100 PSF LOBBIES AND FIRST FLOOR CORRIDORS
100 PSF STAIRS AND EXIST WAYS
80 PSF CORRIDORS ABOVE FIRST FLOOR
15 PSF PARTITIONS
D. ROOF LIVE LOAD:
20 PSF REDUCIBLE
E. DESIGN SNOW LOAD:
Pg = 30 PSF Pf = 0.7(Ce)(Ct)(I)(Pg) = 21.0 PSF Ce = 1.0 Cs = 1.0 Ct = 1.0 I = 1.0
DRIFTING & UNBALANCED SNOW: PER CODE, SEE PLAN
F. WIND DESIGN CRITERIA
WIND SPEED = 107 MPH (ULTIMATE)
WIND SPEED = 82.9 MPH (SERVICE)
EXPOSURE = C
I = 1.0 Kzt = 1.0 GCpi = +/- 0.18
G. SEISMIC DESIGN CRITERIA
SEISMIC USE GROUP = II
SITE CLASS = D
SS = 0.076 S1 = 0.048
SDS = 0.081; SD1 = 0.077
SEISMIC DESIGN CATEGORY = B
SEISMIC RESISTING SYSTEM = STRUCTURAL STEEL SYSTEMS NOT SPECIFICALLY
DESIGNED FOR SEISMIC RESISTANCE (R=3.0)
DESIGN BASE SHEAR = 0.027*W
GENERAL
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFICATION OF ALL CONDITIONS PRIOR TO BIDDING. THIS INCLUDES ENSURING ERECTION CAN BE PERFORMED AS DETAILED ON THE PLANS. IF
MODIFICATIONS ARE NEEDED TO FACILITATE ERECTABILITY THE BIDDING CONTRACTOR SHALL
NOTIFY THE OWNER, ARCHITECT AND ENGINEER AND CLEARLY COMMUNICATE ASSUMPTIONS IN BID DOCUMENTS. THE ENGINEER WILL NOT BE RESPONSIBLE FOR ADDITIONAL COSTS DUE TO REQUIRED
MODIFICATIONS OF THESE PLANS TO FACILITATE ERECTION SEQUENCING ETCETERA.
2. THE CONTRACTOR IS RESPONSIBLE FOR LIMITING THE AMOUNT OF CONSTRUCTION LOAD IMPOSED
UPON NEW OR EXISTING STRUCTURAL FRAMING. CONSTRUCTION LOADS SHALL NOT EXCEED THE
DESIGN CAPACITY OF THE FRAMING AT THE TIME THE LOADS ARE IMPOSED.
3. THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION. THE CONTRACTOR IS
RESPONSIBLE FOR HAVING AN INDEPENDENT ENGINEER DESIGN AND FURNISH ALL TEMPORARY
BRACING AND/OR SUPPORT THAT MAY BE REQUIRED AS THE RESULT OF THE CONTRACTOR'S
CONSTRUCTION METHODS AND/OR SEQUENCES. THE STRUCTURAL ENGINEER SEAL ON THESE
DRAWINGS ASSUMES NO LIABILITY FOR THE STRUCTURE DURING CONSTRUCTION.
4. THE CONTRACTOR IS RESPONSIBLE FOR ALL MEANS AND METHODS OF CONSTRUCTION AND ALL
JOB SITE SAFETY.
5. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO
CONSTRUCTION. NOTIFY THE ENGINEER AND ARCHITECT OF ANY DISCREPANCY IMMEDIATELY.
6. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF ALL BUILDING MATERIALS AND
COMPONENTS. COMPONENT LOCATIONS ARE SHOWN FOR DESIGN INTENT, NOT EXACT LOCATION,
UNLESS NOTED SPECIFICALLY. INDEPENDENTLY PREPARED SHOP DRAWINGS ARE REQUIRED OF
ALL TRADES FOR COORDINATION AND BEST PRACTICE. ERRORS OR OMISSIONS IN INSTALLATION
DUE TO THE CONTRACTOR'S FAILURE TO COORDINATE THE WORK WILL BE THE SOLE
RESPONSIBILITY OF THE CONTRACTOR
7. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS.
A. ALL SHOP DRAWINGS MUST BE THOROUGHLY REVIEWED BY THE CONTRACTOR AND STAMPED
AS REVIEWED PRIOR TO SUBMITTING TO THE ENGINEER FOR FURTHER REVIEW.
B. THE CONTRACTOR SHALL PROVIDE THEIR REVIEWED SUBMITTAL TO THE ENGINEER IN PDF
FORMAT.
C. THE OMISSION OF SHOP DRAWINGS OF ANY MATERIAL SHALL NOT RELIEVE THE CONTRACTOR
OF THE RESPONSIBILITY OF FURNISHING AND INSTALLING SUCH MATERIALS.
D. SHOP DRAWINGS SHALL BE FURNISHED TO THE ENGINEER TO ALLOW FOR 10 WORKING DAYS
TO REVIEW AND RETURN.
8. THE ARCHITECT AND PLUMBING DESIGNER SHALL DESIGN AND DETAIL SUITABLE DRAINAGE
SYSTEM INCLUDING SECONDARY DRAINAGE FOR ALL ROOFS NOT DESIGNED TO HAVE RAINWATER
DRAIN OVER A LOW EAVE. IN NO CASE SHALL THE HEIGHT BETWEEN PRIMARY AND SECONDARY
DRAIN EXCEED 2 INCHES.
9. FOR ALL ROOFS WHERE ROOF DRAINS ARE REQUIRED, OVERFLOW DRAINS HAVING THE SAME SIZE AS PRIMARY ROOF DRAINS SHALL BE INSTALLED WITH INLET FLOW POSITIONED NO MORE THAN 2
INCHES ABOVE THE LOW POINT OF THE ROOF. ALTERNATIVELY, OVERFLOW SCUPPERS HAVING
MINIMUM OF THREE TIMES THE WIDTH OF THE PRIMARY DRAIN AND 4 INCHES HIGH LOCATED NO
MORE THAN 2 INCHES ABOVE THE LOW POINT OF THE ROOF MAY BE USED
MISCELLANEOUS
1. ALL DRAWINGS ARE OF EQUAL IMPORTANCE IN DEFINING THE WORK OF THE CONTRACT DOCUMENTS.
CONTRACTOR SHALL CAREFULLY REVIEW AND COMPARE ALL DRAWINGS DURING THE BIDDING
PERIOD AND BEFORE INSTALLATION OF THEIR WORK. ANY INCONSISTENCIES IN THE DRAWINGS
SHALL BE REPORTED PROMPTLY TO THE ENGINEER AND ARCHITECT FOR CLARIFICATION.
2. EVERY EFFORT HAS BEEN MADE TO PROVIDE TO SCALE DRAWINGS, HOWEVER THE DRAWINGS ARE
NOT NECESSARILY TO SCALE - USE GIVEN DIMENSIONS.
3. ALL WINDOW FRAMES SHALL BE INSTALLED TO ALLOW FOR A MINIMUM OF L/600 OR 1/2 INCH
VERTICAL DEFLECTION OF THE HEADER WHICHEVER IS LESS.
4. DIMENSIONS OF EXISTING CONSTRUCTION OR CONSTRUCTION IN PROGRESS SHALL BE VERIFIED AND
COORDINATED PRIOR TO FABRICATION OF STRUCTURAL COMPONENTS.
DELEGATED DESIGN
1. CALCULATIONS AND DRAWINGS SIGNED AND SEALED BY A REGISTERED PROFESSIONAL ENGINEER
IN THE STATE OF PROJECT SHALL BE SUBMITTED TO PROJECT EOR FOR REVIEW PRIOR TO
FABRICATION FOR ALL DELEGATED DESIGN ITEMS.
2. DELEGATED DESIGN ITEMS INCLUDE:
A. OPEN WEB STEEL JOISTS
B. STEEL FRAMED STAIR SYSTEM
C. COLD FORMED STEEL STUD WALL FRAMING
MASONRY CONSTRUCTION
1. MASONRY DESIGN AND CONSTRUCTION SHALL CONFORM TO THE LATEST EDITION OF THE
FOLLOWING STANDARDS: ACI - 530, ACI - 530.1
2. STABILITY OF THE MASONRY WALL(S) DURING CONSTRUCTION IS THE RESPONSIBILITY OF THE
GENERAL/ SUB CONTRACTOR UNTIL THE WALLS ARE PROPERLY ATTACHED TO THE FRAMING
SYSTEM.
3. NET COMPRESSIVE STRENGTH FOR INDIVIDUAL MASONRY UNITS SHALL BE NOT LESS THAN
3050 PSI WHEN TESTED IN CONFORMANCE WITH ASTM C140 RESULTING IN A MINIMUM
ALLOWABLE COMPRESSIVE STRENGTH OF MASONRY (f’m) = 2000 PSI.
4. MORTAR SHALL COMPLY WITH ASTM C 270 TYPE M OR S, 75% WATER RETENTION AND 12% AIR
CONTENT.
5. GROUT SHALL COMPLY WITH ASTM C 476 AND HAVE A MINIMUM COMPRESSIVE STRENGTH OF
2500 PSI.
6. ALL WALLS SHALL BE RUNNING BOND UNLESS NOTED OTHERWISE ON PLAN.
7. ALL VERTICAL AND HORIZONTAL REINFORCING STEEL BARS IN MASONRY SHALL BE ASTM A615
GRADE 60.
8. HOLLOW CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90 FOR NORMAL WEIGHT
UNITS. ALL CONCRETE MASONRY UNITS ON EXTERIOR WALLS, REGARDLESS OF EXTERIOR
FINISHES, SHALL BE TYPE 1 (MOISTURE CONTROLLED BLOCK).
9. TEST RESULTS FOR NET COMPRESSIVE STRENGTH MUST BE SUBMITTED FOR REVIEW PRIOR TO
CONSTRUCTION.
10. IN ALL WALLS PROVIDE HORIZONTAL LADDER TYPE JOINT REINFORCEMENT CONSISTING OF 2 -
W1.7 (9GA) WIRES LOCATED AT 16” ON CENTER VERTICALLY OR FROM BOND BEAMS. INSTALL
JOINT REINFORCEMENT IN THE FIRST AND SECOND BED JOINTS IMMEDIATELY ABOVE AND
BELOW WALL OPENINGS. EXTEND THE HORIZONTAL REINFORCEMENT 2 FEET PAST WALL
OPENINGS.
11. ALL HORIZONTAL JOINT REINFORCEMENT SHALL HAVE A MINIMUM OF 3/16” COVER AND BE HOT
DIP GALVANIZED.
12. FOR ALL NON LOAD BEARING MASONRY PARTITION WALLS, PROVIDE FULLY GROUTED
HORIZONTAL BOND BEAMS WITH TWO NUMBER 4 - BARS AT THE TOP OF WALLS, AT 8’ - 0” ON
CENTER AND ABOVE ALL WALL OPENINGS AND STEEL LINTELS.
13. UNLESS NOTED OTHERWISE ON PLANS PROVIDE 2X THE TYPICAL VERTICAL REINFORCING BAR IN
THE FIRST FULL HEIGHT CELL EACH SIDE OF DOOR JAMBS, WINDOW OR WALL OPENINGS,
CONTROL JOINTS OR OTHER DISCONTINUITIES, AND EDGE OF LINTEL BEARING.
14. CELLS UNDER LINTEL BEAMS SPANNING 6’ - 0” OR MORE SHALL BE FULLY GROUTED WITH
TYPICAL VERTICAL REINFORCING.
15. ALL CELLS CONTAINING VERTICAL REINFORCEMENT SHALL BE GROUTED SOLID WITH 2500 PSI
GROUT. GROUT LIFT HEIGHTS SHALL NOT EXCEED 4’ - 0”, GROUT POUR HEIGHTS SHALL NOT
EXCEED 24’ - 0”. MECHANICAL CONSOLIDATION BETWEEN LIFTS IS REQUIRED. CLEAN OUT
CELLS ARE REQUIRED AT THE BASE OF EACH GROUT POUR THAT EXCEEDS 5’ - 0”.
16. GROUT SHALL BE STOPPED 1.5” FROM COURSING JOINT TO CREATE A KEY AT THE POUR JOINT.
17. REINFORCING BAR SUPPORTS ARE REQUIRED AT TOP, BOTTOM AND 10’ - 0” ON CENTER ALONG
THE LENGTH OF THE BAR. REINFORCING BARS SHALL BE PLACED PRIOR TO GROUTING CELLS.
18. HORIZONTAL REINFORCEMENT EMBEDDED IN GROUT SUCH AS LINTEL BEAMS SHALL HAVE A
CLEAR THICKNESS OF GROUT BETWEEN THE MASONRY UNIT AND THE REINFORCEMENT OF 1/
2”.
19. LINTELS AND BOND BEAMS ARE REQUIRED AT ALL WALL OPENINGS GREATER THAN 8 - INCHES.
20. USE ONLY U SHAPED LINTEL BLOCK FOR MASONRY LINTELS. CENTERLINE OF REINFORCING TO
BE LOCATED MAXIMUM OF 3” UP FROM BOTTOM OF LINTEL BLOCK.
21. ALL BOLTS AND ANCHORS IN MASONRY SHALL BE GROUTED INTO POSITION OR BE INSTALLED IN
SOLID GROUTED MASONRY AS NOTED ON PLAN. ANCHORS SHALL NOT BE INSTALLED IN
UNGROUTED MASONRY UNLESS SPECIFICALLY SHOWN IN DETAILS.
22. FOR ALL LINTEL AND BOND BEAM HORIZONTAL REINFORCING LAP #4 BARS 36” AND ALL #5
BARS 60”. FOR VERTICAL WALL REINFORCING LAP ALL #4 AND #5 BARS 30”. LAP VERTICAL
BARS 36X DIAMETER U.N.O. (#5 = 30”).
23. ALL MASONRY IN CONTACT WITH THE EARTH SHALL BE GROUTED SOLID.
24. SLUMP OF GROUT SHALL BE IN THE RANGE OF 7 TO 11 INCHES
FOUNDATION
1. ALLOWABLE SOIL BEARING CAPACITY = 3,000 PSF
GEOTECHNICAL INFORMATION TAKEN FROM:
SOILS & ENGINEERING SERVICES, INC.
GEOTECHNICAL INVESTIGATION REPORT 25.001
DANE COUNTY SUSTAINABILITY CAMPUS
4402 BRANDT ROAD
MADISON, WI
AUGUST 12, 2025
2. PROJECT GEOTECHNICAL REPORT SUPERSEDES GEOTECHNICAL INFORMATION PROVIDED ON
STRUCTURAL PLANS.
3. THE GENERAL CONTRACTOR (GC) SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION PROCEDURES
THAT MAY AFFECT ADJACENT EXISTING STRUCTURES, ROADS, OR OTHER SIGNIFICANT
PROPERTY. IT IS THE RESPONSIBILITY OF THE GC TO RETAIN A SPECIALTY FOUNDATION DESIGN
CONSULTANT, GEOTECHNICAL ENGINEER, OR OTHER ENGINEERING CONSULTANT BEFORE
EXCAVATION & AS REQUIRED DURING CONSTRUCTION. THE CONSULTANT SHALL PROVIDE
ENGINEERED SOIL RETENTION/STABILIZATION SYSTEM, INSTALLATION GUIDANCE, AND ADJACENT PROPERTY MONITORING AS NEEDED DURING CONSTRUCTION. THE ARCHITECT AND/OR EOR SHALL BE NOTIFIED IMMEDIATELY IF ADJACENT PROPERTY (FOUNDATION MOVEMENT, CRACKING, ETC) IS
DETECTED.
4. THE BUILDING FINISHED FLOOR ELEVATION IS 100.00 AND EQUALS EL 882.00 ON THE SITE PLAN.
5. GRADE AREAS IN ACCORDANCE WITH ELEVATIONS AND GRADES SHOWN ON THE SITE DRAWINGS AND
AS REQUIRED FOR DRAINAGE.
6. SLAB ON GROUND TO BE CONSTRUCTED ON A MINIMUM OF 6” OF CRUSHED STONE OR GRANULAR FILL COMPACTED TO 95% MODIFIED PROCTOR OR AS DIRECTED BY THE GEOTECHNICAL ENGINEER.
7. ALL FILL MATERIAL USED IN GRADING OPERATIONS SHALL BE GRANULAR MATERIAL AND BE FREE OF DEBRIS, BOULDERS OR ORGANIC MATERIAL. FILL SHALL BE PLACED IN MAXIMUM OF 12” LIFTS AND COMPACTED TO 95% OF MODIFIED PROCTOR MAXIMUM DRY DENSITY OR AS DIRECTED BY THE
GEOTECHNICAL ENGINEER.
8. THE BOTTOM OF ALL EXTERIOR FOOTINGS SHALL BE A MINIMUM OF 4'- 0” BELOW FINISHED GRADE.
9. ALL FOUNDATIONS AND FOOTINGS SHALL BEAR ON NATIVE SOIL OR COMPACTED GRANULAR FILL HAVING A MINIMUM ALLOWABLE BEARING CAPACITY EQUAL TO THE PRESUMPTIVE CAPACITY ABOVE.
10. THE ENGINEER SHALL BE NOTIFIED IF ACTUAL FIELD CONDITIONS DO NOT MEET BEARING REQUIREMENTS, OR IF QUESTIONABLE SOIL CONDITIONS ARE DISCOVERED INCLUDING BUT NOT
LIMITED TO PEAT AND OTHER HIGH ORGANIC SOILS.
11. ALL BEARING SOIL OR FILL MUST BE PROTECTED FROM FREEZING. THE CONTRACTOR SHALL
PROVIDE PROTECTION TO PREVENT FROST PENETRATION BELOW THE CONCRETE BEARING
ELEVATIONS. ANY FROZEN SOIL BELOW THE FOUNDATION BEARING LEVEL MUST BE REMOVED PRIOR
TO PLACING CONCRETE.
12. ALL SLABS ON GRADE AREAS SHALL BE PROOF ROLLED. ALL SOFT SPOTS SHALL BE REMOVED AND
REPLACED WITH COMPACTABLE FILL.
13. THE CONTRACTOR SHALL USE CONTROLLED GRANULAR FILL APPROVED BY THE GEOTECHNICAL
ENGINEER TO BE PLACED AGAINST ALL CANTILEVERED RETAINING WALLS.
14. WHEN IT IS POSSIBLE FOR GROUND WATER TO SEEP TOWARD SUBGRADE FOUNDATIONS AND
RETAINING WALLS, THESE WALLS SHALL HAVE A POSITIVE DRAINAGE SYSTEM AT THE BASE OF THE
WALL CONSISTING OF A PERFORATED DRAIN PIPE PROTECTED BY A GEOTEXTILE FABRIC
SURROUNDED BY CONCRETE SAND (TORPEDO SAND). NEAR THE BASE OF THE WALL. OTHER BACK
FILL MATERIAL SHALL BE SAND WITH LESS THAN 12% PASSING THE #200 SIEVE.
15. DO NOT USE EXCESSIVE COMPACTION EFFORTS ADJACENT TO RETAINING WALLS. SUCCESSIVE PASSES OF HEAVY COMPACTION EQUIPMENT, SUCH AS ROLLERS, CAN RESULT IN WALL PRESSURE BUILD UP BEYOND THE DESIGN INTENT. HEAVY EQUIPMENT SHOULD BE KEPT A MINIMUM OF 10
FEET FROM THE TOP OF BASEMENT OR RETAINING WALLS. USE HAND-OPERATED COMPACTION
EQUIPMENT SUCH AS VIBRATORY PLATES.
16. FULLY COMPACT SOIL IN FRONT OF RETAINING WALLS.
17. REFER TO THE GEOTECHNICAL INVESTIGATION FOR INFORMATION REGARDING REQUIRED UNDERCUT, EXCAVATION, SIDE SLOPES, SUB-GRADE PREPARATION, AND FILL RECOMMENDATIONS.
18. DO NOT BACKFILL AGAINST BASEMENT WALLS UNTIL ALL FLOOR SYSTEMS ARE IN PLACE AND
FASTENED OR UNTIL WALLS ARE ADEQUATELY BRACED. BRACING DESIGN SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR.
19. BELOW GRADE WALLS SHALL BE BRACED DURING CONSTRUCTION, BACKFILLING, AND COMPACTION.
THE BRACING SHALL REMAIN IN PLACE UNTIL THE BELOW GRADE FLOOR SLAB IS IN PLACE FOR CANTILEVERED WALLS AND UNTIL THE FLOOR SLAB AT THE BASE AND TOP OF WALL IS IN PLACE
FOR RESTRAINED RETAINING (BASEMENT) WALLS.
20. PROVIDE SUB-GRADE PREPARATION AS PER THE PLANS OR PROJECT GEOTECHNICAL REPORT.
21. WHEN UNDERPINNING IS REQUIRED EXISTING FOOTINGS SHALL BE SEQUENTIALLY UNDERPINNED
WITH UNDERMINED FOOTING SEGMENTS NOT TO EXCEED 4’-0” AT ANY TIME WITHOUT PRIOR
AUTHORIZATION. THE GENERAL CONTRACTOR SHALL SUBMIT FOR REVIEW TO THE PROJECT
STRUCTURAL ENGINEER A DETAILED CONSTRUCTION SEQUENCE PLAN. THE PLAN SHALL INCLUDED INTENDED METHODS, MATERIALS AND A PRECONSTRUCTION SURVEY OF THE EXISTING BUILDING
AND HAVE PROVISIONS FOR MONITORING THE EXISTING CRACKS.
22. REMOVE TOPSOIL FROM BENEATH ALL PROPOSED CONSTRUCTION AREAS. SALVAGE AND STOCK
PILE TOPSOIL, CUT/FILL MATERIAL AS NECESSARY TO MATCH GRADES SHOWN ON DRAWINGS.
23. NON-FROST SUSCEPTIBLE FILL SHALL BE FREELY DRAINING GRANULAR FILL W/ 12% MAX FINES
PASSING THROUGH A #200 SIEVE. SEE PLAN FOR REQUIRED LOCATIONS.
CONCRETE CONSTRUCTION
1. ALL CONCRETE DESIGN AND CONSTRUCTION SHALL CONFORM TO THE LOCAL BUILDING CODE REQUIREMENTS AND THOSE OF THE LATEST EDITION OF THE FOLLOWING STANDARDS: ACI 318, ACI 315, ACI 301, AND ACI 305 & 306.
2. ALL CONCRETE UNLESS SPECIFICALLY NOTED SHALL BE NORMAL WEIGHT (145 PCF) AND SHALL ACHIEVE A
MIX DESIGN CRITERIA AS FOLLOWS:
3. ALL CONCRETE REINFORCING STEEL TO BE ASTM A615 GRADE 60. ALL WELDED WIRE FABRIC (WWF) TO BE ASTM A1064 GR. 65 MIN. ALL REINFORCING SHALL BE DETAILED AND PLACED IN ACCORDANCE WITH ACI 315
AND 315R.
4. ALL REINFORCING BARS AND WWF SHALL BE SET ON CHAIRS AND TIED IN PLACE.
5. WELDING OF ASTM A615 REBAR SHALL NOT BE PERMITTED. WHEN WELDING IS REQUIRED ASTM A706 BAR
MUST BE USED.
6. ALL LAPS SHALL BE “B” SPLICES UNLESS NOTED OTHERWISE ON THE DRAWINGS OR UNLESS SPECIAL CARE IS
TAKEN FOR THE REINFORCING TO BE DETAILED AND PLACED TO PROVIDE STAGGERED LAPS.
7. UNLESS NOTED OTHERWISE ON THE DRAWINGS ALL REINFORCING SHALL BE LAPPED TO DEVELOP ITS
CAPACITY AS FOLLOWS:
8. WELDED PLAIN WIRE REINFORCEMENT FABRIC FOR CONCRETE SHALL CONFORM TO ASTM A185.
9. CONCRETE SLABS ON GROUND CONTAINING WELDED WIRE REINFORCEMENT FABRIC (WWF) OR REINFORCING BARS SHALL BE PLACED IN THE UPPER ONE-THIRD OF THE SLAB AS SHOWN ON THE DRAWINGS.
REINFORCEMENT SHALL BE SUPPORTED AT 3’ (WWF) OR 4’ (REBAR) ON CENTER MAXIMUM. LIFTING
REINFORCING AFTER CONCRETE IS PLACED SHALL NOT BE ALLOWED.
10. CONCRETE SLABS ON GROUND CONTAINING MACRO FIBER REINFORCEMENT SHALL USE A MINIMUM FIBERMESH 300 (OR EQUIVALENT) AT A DOSING NOT LESS THAN 3 LBS/YD3 AND BE USED IN ACCORDANCE
WITH THE MANUFACTURER’S SPECIFICATIONS.
11. THREADED ANCHOR RODS SHALL HAVE A HEAVY HEX NUT SECURED TO THE EMBEDDED END IN ONE OF THE
FOLLOWING WAYS:
A. F1554 GRADE 36 ANCHOR RODS - WELD, DOUBLE NUT OR THREAD PEENING.
B. F1554 GRADE 55 OR HIGHER ANCHOR RODS - DOUBLE NUT OR THREAD PEENING.
12. PLACING OF CONCRETE SHALL BE DONE IN CONFORMANCE WITH ACI-306 FOR COLD WEATHER AND ACI-305
FOR HOT WEATHER.
13. CONCRETE SHALL BE CURED ABOVE 50°F (10°C) AND IN A MOIST CONDITION FOR AT LEAST THE FIRST SEVEN DAYS AFTER PLACEMENT. DO NOT PLACE CONCRETE WHEN THE MEAN DAYLIGHT TEMPERATURE IS LESS
THEN 20 DEGREES F.
14. UNLESS OTHERWISE APPROVED, ALL EXPOSED CONCRETE WALLS SHALL BE CURED WITH FORMS LEFT IN PLACE FOR SEVEN DAYS. IF FORMS CAN NOT BE LEFT IN PLACE THE CONTRACTOR SHALL SUBMIT IN WRITING
TO THE ENGINEER ALL PROPOSED CURING METHODS.
CONCRETE COMPRESSIVE STRENGTH f'c=3,000 PSI
#3
UNCOATED STANDARD & CLASS "B" TENSION LAP LENGTHS1, 5
CONCRETE COMPRESSIVE STRENGTH f'c=4,000 PSI
BAR
SIZE
BTM
BARS
TOP
BARS4
BTM
BARS
TOP
BARS4
STD DEVELOPMENT
LENGTH2
CLASS "B" TENSION
LAP LENGTH3
STD DEVELOPMENT
LENGTH2
CLASS "B" TENSION
LAP LENGTH3
BAR
SIZE
BTM
BARS
TOP
BARS4
BTM
BARS
TOP
BARS4
#4
#5
#6
#7
#8
#3
#4
#5
#6
#7
#8
17"
22"
28"
33"
48"
55"
22"
29"
36"
43"
63"
72"
22"
29"
36"
43"
63"
72"
28"
38"
47"
56"
81"
93"
15"
19"
24"
29"
42"
48"
19"
25"
31"
37"
54"
62"
19"
25"
31"
37"
54"
62"
25"
33"
41"
49"
71"
81"
NOTES:
1. BASED ON ℓd VALUES FROM SECTION IN ACI 318:
1.1 GRADE 60 REINFORCEMENT BARS
1.2 NORMAL WEIGHT CONCRETE (Ѱ=1.0)
1.3 NON-EPOXY COATED BARS (Ѱ=1.0)
1.4 CLEAR COVER > 1.0db; CLEAR SPACING > 2.0db; NOTIFY ENGINEER IF COVER NOT MET.
2. STANDARD LAP SPLICES ARE TO BE USED WHEN < 50% OF BARS ARE LAPPED AT THE SAME
LOCATION, INCLUDING TEMPERATURE AND SHRINKAGE LAP SPLICES.
2.1 PROVIDE CLASS B LAP SPLICES UNLESS DETAILED AND APPROVED BY ENGINEER.
3. CLASS B LAP SPLICES ARE TO BE USED WHEN > 50% OF BARS ARE LAPPED AT THE SAME LOCATION, INCLUDING TEMPERATURE AND SHRINKAGE LAP SPLICES.
4. HORIZONTAL (TOP) BARS HAVE MORE THAN 12" OF FRESH CONCRETE PLACED BELOW
REINFORCEMENTS. SPLICE LENGTHS ARE ROUNDED UP TO THE NEAREST INCH.
FOOTINGS
CONCRETE MIX DESIGN CRITERIA
LOCATION
EXTERIOR FDTN WALLS, PIERS, & GRADE BEAMS
INTERIOR SLAB ON GROUND < 6" THICK
INTERIOR BEAMS & COLUMNS
ALL OTHER CONCRETE
28 DAY
MIN f'c
(PSI)1
1. INDICATES MINIMUM 28 DAY COMPRESSIVE STRENGTH (fc').
2. WATER/CEMENT RATIO SHALL MEET DURABILITY REQUIREMENTS OF ACI 318 BASED ON EXPOSURE
CLASS NOTED. CORROSION EXPOSURE SHALL BE F0, S0, W0, C0 UNLESS NOTED OTHERWISE IN THE
EXPOSURE CLASS TABLE COLUMN ABOVE.
3. ALL CONCRETE WITHOUT SUPERPLASTICIZERS SHALL HAVE A MAXIMUM SLUMP OF 4”.
4. ALL MIX DESIGNS SHALL UTILIZE THE STATED TOP AGGREGATE SIZE IN AN EVENLY DISTRIBUTED
AGGREGATE GRADATION.
5. ALL CONCRETE MIX DESIGNS SHALL MINIMIZE SHRINKAGE AS MUCH AS IS PRACTICAL. INCLUDING
SELECTION OF AGGREGATE TYPE, SIZE, GRADATIONS W/ C RATIO AND ADD MIXTURES.
6. CALCIUM CHLORIDE AND OR ADMIXTURES CONTAINING CALCIUM CHLORIDE SHALL NOT BE USED.
3,000
4,000
4,000
4,500
4,000
3,000
6%
AIR
ENTRAIN
(+/-1.5%)
6%
MAX TOP
AGGREGATE
SIZE5
3/4"
3/4"
1"
TOPPING ON PRECAST 4,000
3/8"
1 1/2"
1"
1 1/2"
INTERIOR SLAB ON GROUND ≥ 6" THICK 4,000 1 1/2"-
4,500 6% 1 1/2"
EXTERIOR SLAB ON GROUND < 6" THICK
EXTERIOR SLAB ON GROUND ≥ 6" THICK
EXPOSURE
CLASS2
(ACI 318)
INTERIOR SLAB ON METAL DECK 4,000 - 3/8"
FLOWABLE FILL 1,000 - -
F1
F2
F2
C1
C1
C2
C2
15. AFTER CONCRETING HAS STARTED, IT SHALL BE CARRIED ON AS A CONTINUOUS OPERATION UNTIL PLACING OF A PANEL OR SECTION, AS DEFINED BY ITS BOUNDARIES OR PREDETERMINED JOINTS, IS COMPLETED. CONCRETE SHALL BE DEPOSITED AS NEARLY AS PRACTICABLE TO ITS FINAL POSITION
TO AVOID SEGREGATION DUE TO REHANDLING OR FLOWING.
16. CONCRETING OPERATIONS SHALL BE CARRIED ON AT SUCH A RATE THAT THE CONCRETE IS AT ALL
TIMES PLASTIC AND FLOWS READILY INTO SPACES BETWEEN REINFORCEMENT.
17. RETEMPERED CONCRETE, CONCRETE THAT HAS BEEN REMIXED AFTER INITIAL SET OR PARTIALLY
HARDENED SHALL NOT BE USED IN THE STRUCTURE.
18. CONCRETE SHALL BE THOROUGHLY CONSOLIDATED BY SUITABLE MEANS DURING PLACEMENT AND
SHALL BE THOROUGHLY WORKED AROUND REINFORCEMENT AND EMBEDDED FIXTURES AND INTO
CORNERS OF THE FORMS. THE TOP SURFACES OF VERTICALLY FORMED LIFTS SHALL BE GENERALLY
LEVEL.
19. CRACKS DUE TO IMPROPER CURING METHODS, OR WEATHER PROTECTION SHALL BE THE
RESPONSIBILITY OF THE CONTRACTOR.
20. ALL FLAT WORK CONCRETE MUST BE CURED. FLAT WORK IS RECOMMENDED TO BE COVERED
IMMEDIATELY FOLLOWING SAW CUTTING AND MAINTAINED CONTINUOUSLY WET FOR 7-DAYS. CURING COMPOUNDS MAY BE USED INSTEAD OF WET CURE WHEN APPROVED BY THE ARCHITECT AND MUST BE APPLIED PER THE MANUFACTURER'S RECOMMENDATIONS. SUBMIT PRODUCT DATA TO A/E FOR
APPROVAL.
21. FLOOR SLAB CONTROL JOINTS SHALL FOLLOW THE INTENT SHOWN ON THE PLAN BUT SHALL NOT EXCEED AN ASPECT RATIO OF 1.5 TO 1.0. ALL REENTRANT CORNERS SHALL HAVE CONTROL JOINTS EXTENDING OUT FROM THE INSIDE CORNER. DEAD- END “T” CONTROL JOINTS INTO CONTINUOUS
JOINTS SHALL BE AVOIDED.
22. CONSTRUCTION JOINTS SHALL BE LOCATED AT CONTROL JOINTS AS REQUIRED UNLESS NOTED
OTHERWISE ON PLAN.
23. SLAB-ON-GRADE FLOOR LEVELNESS (FL) AND FLOOR FLATNESS (FF) REQUIREMENTS SHALL BE
COORDINATED WITH THE ARCHITECT BUT SHALL NOT BE LESS THAN FL=35 AND FF=45.
24. A 10-MIL. (MIN.) POLYETHYLENE VAPOR BARRIER WITH JOINTS LAPPED NOT LESS THAN 6” SHALL
BE PLACED BETWEEN THE BASE COURSE OR SUBGRADE AND THE CONCRETE FLOOR.
25. PIPE SLEEVES OVER 1 1/2” IN DIAMETER WHICH PASS THROUGH CONCRETE WALLS OR SLABS SHALL
BE SCHEDULE 40 GALVANIZED STEEL PIPE. ALL OTHER SLEEVES SHALL BE 18 GAUGE SHEET
METAL. SLEEVES SHALL BE ONE SIZE LARGER THAN OUTSIDE DIAMETER OF PIPE PASSING THROUGH SLEEVE. VERIFY SIZE AND NUMBER WITH MECHANICAL, ELECTRICAL, AND PLUMBING CONTRACTORS.
26. ALUMINUM CONDUIT SHALL NOT BE EMBEDDED IN CONCRETE.
27. GROUT USED TO PROVIDE LEVEL BEARING OF COLUMN BASE PLATES SHALL BE NON-SHRINK, NON-
METALLIC GROUT WITH A MINIMUM COMPRESSIVE STRENGTH 2X THE CONCRETE COMPRESSIVE
STRENGTH OF THE SUPPORTING CONCRETE MEMBER.
28. ALL POST-INSTALLED ANCHORED BARS OR RODS SHALL BE A INSTALLED PER MANUFACTURER
REQUIREMENTS.
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
D R
A W
IN
G
S E
T
D A
T E
R E
V
IS
IO
N
S
P R
O
JE
C T
N O
COPYRIGHT STRANG, INC. 2025
B R
A N
D T
R O
A D
M A
D
IS
O N
, W I
C D
3/
/2
S T
R U
C T
U R
A L
N O
T E
S
D A
N E
C O
U N
T Y
D E
P T
O F
W A
S T
E
R E
N E
W A
B
LE
S
E D
U C
A T
IO
N
A N
D A
D M
IN
C
E N
T E
R
AS001
DRAWING INDEX
SHEET TITLE
AS001 STRUCTURAL NOTES
AS002 STRUCTURAL NOTES AND SCHEDULES
AS003 SPECIAL INSPECTION
AS004 SPECIAL INSPECTION CONT.
AS101 FOUNDATION PLAN
AS201 SECOND FLOOR FRAMING PLAN
AS301 ROOF FRAMING PLAN
AS302 MECHANICAL SCREENWALL FRAMING
AS401 MASONRY WALL ELEVATIONS
AS501 CONCRETE DETAILS
AS502 CONCRETE DETAILS
AS503 CONCRETE DETAILS
AS601 MASONRY DETAILS
AS602 MASONRY DETAILS
AS801 STEEL DETAILS
AS802 STEEL DETAILS
AS803 STEEL DETAILS
AS804 STEEL DETAILS
N O
D
E S
C R
IP
T
IO
N
D A
COLUMN PIER MARK (SEE PIER SCHEDULE)
CONCRETE FOOTING
CONCRETE PIER
TOP OF PIER ELEVATION
COLUMN GRID MARK
COLUMN FOOTING MARK (SEE FOUNDATION SCHEDULE)
TOP OF COLUMN FOOTING ELEVATION
CONCRETE WALL & FOOTING
TOP OF WALL FOOTING ELEVATION
TOP OF LEDGE ELEVATION
TOP OF WALL ELEVATION
FOOTING STEP
FOOTING MARK
EXPANSION JOINT-SEE NOTES FOR
WALL CONTROL JOINT SPACING
FOUNDATION LEGEND
F X X'-X" P X X'-X"
WX
TL=X'-X"
TW=X'-X"
COLUMN PIER MARK
TOP OF PIER ELEVATION
COLUMN FOOTING MARK
TOP OF COLUMN FOOTING
ELEVATION
F X X'-X" P X X'-X"
A
X'-X"
TF=X'-X"
X'
XX
INDICATES BEAM FRAMING
OVER TUBE COL
TOP OF STEEL ELEVATION
COLUMN DESIGNATION CX
BEAM DESIGNATION
INDICATES LOCATION OF BEAM SPLICE
INDICATES BEAM FRAMING
INTO SIDE OF BEAM
INDICATES BEAM FRAMING
OVER WF COL
INDICATES BEAM FRAMING
INTO SIDE OF COL
W
B
EA
M
INDICATES BEAM FRAMING
OVER BEAM
INDICATES MOMENT
CONNECTION
STRUCTURAL STEEL LEGEND
STRUCTURAL ABBREVIATIONS
@ AT
AB ANCHOR BOLT
ACCOM ACCOMMODATE
AFF ABOVE FINISH FLOOR
AGG AGGREGATE
ALT ALTERNATE
ARCH ARCHITECT/ ARCHITECTURAL
B- B BACK- TO- BACK
BL BUILDING LINE
BLDG BUILDING
BLK BLOCK
BM BEAM
BOT BOTTOM
BRG BEARING
BS BOTH SIDES
C CHANNEL DESIGNATION
CB CATCH BASIN
C/ C CENTER- TO- CENTER
CG CENTER OF GRAVITY
CI CAST IRON
CIP CAST IN PLACE
CJ CONTRACTION OR
CONSTRUCTION JOINT
CL CENTERLINE
CLJ CONTROL JOINT
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMP COMPOSITE
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
CONTR CONTRACTOR
D DEPTH
Ø DIAMETER
DIA DIAMETER
DIM DIMENSION
DN DOWN
DTL DETAIL
DWG DRAWING
DWL DOWEL
EA EACH
EC ELECTRICAL CONTRACTOR
EJ EXPANSION JOINT
EL ELEVATION
ELEV ELEVATOR
ENG ENGINEER
EQ EQUAL
EW EACH WAY
E- W EAST- WEST DIRECTION
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FB FLANGE BRACE
FD FLOOR DRAIN
FDN FOUNDATION
FF FINISH FLOOR
F- F FACE- TO- FACE
FL FRAME LINE
FLG FLANGE
FUT FUTURE
FV FIELD VERIFY
FTG FOOTING
GA GAGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GL GRID LINE
HC HVAC CONTRACTOR
HK HOOK
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HIGH POINT
HT HEIGHT
HVAC HEATING, VENTILATING, & AIR
CONDITIONING
HWS HEADED WELDED STUD
ID INSIDE DIAMETER
INSUL INSULATION
INT INTERIOR
JT JOINT
KB KNEE BRACE
L STEEL ANGLE DESIGNATION
LG LONG/ LENGTH
LGMF LIGHT GAGE METAL FRAMING
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LP LOW POINT
LVL LAMINATED VENEER LUMBER
MAX MAXIMUM
MBW MASONRY BEARING WALL
MECH MECHANICAL
MFG MANUFACTURE
MIN MINIMUM
MISC MISCELLANEOUS
MTL METAL
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
N- S NORTH- SOUTH DIRECTION
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVER HEAD
OPP OPPOSITE
OS ONE SIDE
PC PLUMBING CONTRACTOR
P/ C PRECAST/ PRESTRESSED
PDF POWDER DRIVEN FASTENER
PEMB PRE- ENGINEERED METAL
BUILDING
PERM PERIMETER
PJF PRE- FORMED JOINT FILLER
⅊ PLATE
PL PLATE
P/ T POST TENSIONED
PROJ PROJECTION
PVMT PAVEMENT
R RADIUS
R/ C REINFORCED CONCRETE
RD ROOF DRAIN
REINF REINFORCING
REQD REQUIRED
SCHED SCHEDULE
SIM SIMILAR
SHT SHEET
SPA SPACE/ SPACES
SPEC SPECIFICATION
SQ SQUARE
SSTL STAINLESS STEEL
STL STEEL
STR STRUCTURAL
TBE TRUSS BEARING ELEVATION
THK THICK
TO TOP OF
TC TOP OF CURB ELEVATION
TL TOP OF LEDGE ELEVATION
TP TOP OF PIER ELEVATION
TW TOP OF WALL ELEVATION
TOS TOP OF STEEL ELEVATION
TSL TOP OF SLAB ELEVATION
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VIF VERIFY IN FIELD
W WIDTH
W/ WITH
W/ O WITHOUT
WCJ WALL CONTROL JOINT
WD WOOD
WF WIDE FLANGE
WP WORKING POINT
WSBW WOOD STUD BEARING WALL
WWF WELDED WIRE FABRIC
STRUCTURAL STEEL FRAMING
1. STRUCTURAL STEEL DESIGN AND FABRICATION SHALL BE IN ACCORDANCE WITH THE AISC ASD 14TH
EDITION STEEL CONSTRUCTION MANUAL.
2. W-SHAPES SHALL CONFORM TO ASTM A992 (FY = 50 KSI).
3. ALL STRUCTURAL STEEL ANGLE AND CHANNEL SHAPES SHALL CONFORM TO ASTM A36 (FY =36 KSI)
UNLESS NOTED OTHERWISE.
4. PLATE STEEL SHALL CONFORM TO ASTM A36 (FY = 36 KSI).
5. ALL SQUARE AND RECTANGULAR HSS SHALL CONFORM TO ASTM A500, GRADE B (FY = 46 KSI).
6. ALL SQUARE AND ROUND BARS SHALL CONFORM TO ASTM A36 (FY = 36 KSI) UNLESS NOTED
OTHERWISE.
7. THE STRUCTURAL STEEL FABRICATOR SHALL BE RESPONSIBLE FOR THE SELECTION, DESIGN, AND
DETAILING OF ALL CONNECTIONS NOT FULLY DETAILED ON THE CONTRACT DRAWINGS.
A. CONNECTION DETAILS ARE INDICATED ON THE DRAWINGS FOR DESIGN INTENT ONLY. WHEN BOLTS
ARE SHOWN ON SPECIFIC DETAILS, UNLESS THE NUMBER OF BOLTS IS SHOWN NUMERICALLY, USE
GRAPHICAL REPRESENTATION FOR DESIGN CONCEPT ONLY.
8. WHERE MOMENT CONNECTIONS ARE INDICATED, PROVIDE CONNECTION TO DEVELOP FULL MOMENT
CAPACITY OF WEAKER SECTION TO BE CONNECTED, UNLESS A SPECIFIC VALUE IS SHOWN.
9. ALL CONNECTION BOLTING IS TO BE WITH A 3/4" DIAMETER A-325N BOLTS UNLESS NOTED OTHERWISE.
EXCEPT AT MOMENT CONNECTIONS AND SLIP CRITICAL (SC) BOLT LOCATIONS, BOLTS NEED ONLY BE TIGHTENED TO THE SNUG-TIGHT CONDITIONS. LOAD INDICATOR BOLTS SHALL BE USED AT MOMENT
CONNECTIONS AND SLIP CRITICAL CONNECTIONS.
10. ALL SHEAR CONNECTIONS NOT SPECIFICALLY DETAILED ON THE DRAWING SHALL BE SELECTED AND DETAILED BY THE FABRICATOR. ALL CONNECTIONS SHALL BE SELECTED FROM AISC ASD LOAD TABLES TO SUPPORT MAXIMUM LOADS SHOWN ON DRAWINGS OR FOR THE FULL UNIFORM LOAD CAPACITY OF
THE MEMBER PER AISC. DOUBLE ANGLE CONNECTIONS ARE PREFERRED WHEN POSSIBLE.
11. ALL WELDING OF NEW STEEL TO BE WITH E70XX ELECTRODES.
12. ALL WELDING SHALL COMPLY WITH THE AWS STRUCTURAL WELDING CODES. ALL WELDING TO BE PERFORMED BY AWS PRE-QUALIFIED WELDERS CERTIFIED FOR THE GIVEN APPLICATION. ANY LOCAL
AND OR STATE LICENSING REQUIREMENTS SHALL BE VERIFIED BY THE GENERAL CONTRACTOR.
13. ALL EXTERIOR EXPOSED STEEL SHALL BE PRIMED WITH A ZINC RICH PRIMER AND PAINTED WITH AN APPROPRIATE EXTERIOR PAINT UNLESS NOTED OTHERWISE.