REQUIREMENTS LIST

Quantity 1 - Generac Industrial diesel engine-driven generator set with turbocharged/aftercooled 6-cylinder 6.7L engine, consisting of the following features and accessories:

Stationary Emergency-Standby rated 100 kW Rating, wired for 277/480 VAC three phase, 60 Hz Permanent Magnet Excitation Level 1 Acoustic Enclosure, Aluminum o Industrial Grey Baked-On Powder Coat Finish

UL2200

EPA Certified H-100 Control Panel o Meets NFPA 99 and 110 requirements o Temp Range -40 to 70 degrees C o Digital Microprocessor:

Two 4-line x 20 displays, full system status 3 Phase sensing, +/-0.25% digital voltage regulation RS232, RS485 and Canbus remote ports Waterproof connections All engine sensors are 4-20ma for minimal interference Programmable I/O Built-in PLC for special applications o Engine function monitoring and control:

Full range standby operation; programmable auto crank, Emergency Stop, Auto-Off-

Manual switch Isochronous Governor, +/-0.25% frequency regulation Full system status on all AC output and engine function parameters Service reminders, trending, fault history (alarm log) I2T function for full generator protection Selectable low-speed exercise o HTS transfer switch function monitoring and control o 2-wire start controls for any 2-wire transfer switch

21 Light Annunciator - Surface Remote Emergency Stop Switch, Surface-Mount, shipped loose 110 AH, 925 CCA Group 31 Battery, with rack, installed Standard MLCB, 80% rated thermal-magnetic o 175 Amp Battery Charger, 10 Amp, NFPA 110 compliant, installed Coolant Heater, 1500W 36" 693 Gallon Double-Wall UL142 Basetank o Mechanical fuel level indicator gauge o Electronic fuel level sender o Emergency Vent o 13" Fuel Fill Extension

Pad Vibration Isolators 3 Owner's Manuals 120V GFCI and 240V Outlet Standard 2-Year Limited Warranty

SD0100KG176.7D18HPSY3

Quantity 1 - TRANSFER SWITCH - TX SERIES

200 Amp, 3 pole, 277/480 VAC three phase, 60 Hz, with 2-Wire Start Circuit o Utility Voltage Sensing Controls:

Adjustable Drop-out and Pick-up

Adjustable Utility Interrupt Delay o Adjustable Logic Controls:

Minimum Standby Voltage Minimum Standby Frequency Engine Warmup Return to Utility Engine Cooldown Transfer on Exercise

Enclosure Heater Double Set of Form C Auxiliary Contacts UL Listed 1008 by ETL Controller and Circuit Breaker Covers, Padlockable, Black NEMA 3R Enclosure 3 Owner's Manuals 42KA Contactor Withstand and Closing Rating Service Entrance Rated In Phase Only Transfer Standard two year basic warranty

TX301NS0200K3CH