viledon_mv85.pdf

PDF 723 KB Posted

Attached to
RECOVERY - Fresno HVAS and BAS improvement
Solicitation number
RECOVERY-GS-09P-10-KS-C-0042
Issued by

About this file

Cut sheets for filters

View the file

Other files

File Type Posted
Feb 15 Revised SF 1442.pdf PDF
Agreement R1.doc DOC document
FRESNO_MECH_SIGN_IN.pdf PDF
Energy Meter Spec 020910.doc DOC document
Feb 10 Revised SF 1442.pdf PDF
Fresno - Solar DHW System Size Parameters.pdf PDF
Subcontracting Plan as of 2009.doc DOC document
Standard for PBS CAD Deliverables.pdf PDF
Specifications Fresno Mechanical 012510.docx DOCX document
Solar DHW Heating Installers.xlsx XLSX spreadsheet
SOWs specs etc.zip ZIP file
MANDATORY REFERENCE FORM.doc DOC document
SF 1442.pdf PDF
Solicitation instructions R1.doc DOC document
FBO Solicitation.zip ZIP file
SOWs specs etc.zip ZIP file
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Media is resistant to physical damage from moisture and chemicals.

The light weight of the MV provides easy handling and reduced cost for transport, shipping and disposal.

The entire filter element is free of metals, halogens, and glass fibers. The filter element is also corrosion proof and fully incinerable. These features allow for lower disposal costs.

Moisture-resistant up to 100% relative humidity.

Temperature Resistance: Continuous 160°F, Peaks 175°F.

UL 900 Class 2 Covered by US Patent No 6447566. (1” Recess) Microbial Resistance level 4 (ASTM D632G)

The viledon MV Extended Surface Filter meets all requirements of standard air handling systems as to frame dimensions, depth, and filter performance. viledon’s filtration superiority is known as the viledon difference.

viledon filters have been developed specifically for intake, exhaust, and recirculated air filtration HVAC systems that have stringent requirements for clean air quality and cost efficiency.

Patented 1” recess design for “V” style filters drastically lowers pressure drop when used in conjunction with pleated or panel style pre-filters on the face of the filter. The patented 1” recess provides full utilization of the entire prefilter media area.

The MV85 V-Banks are potted into a high strength all plastic frame. This assures the user of maximum operational dependability and consistent filtration throughout each specific application.

The sturdy construction assures optimum performance under turbulent flow conditions and load changes. This means that the risk of particle or fiber shedding is practically eliminated.

viledon develops and manufactures its own organic synthetic filter media.

Fine, progressively structured, thermally bonded media provide exceptionally low pressure drop at high efficiency levels.

All plastic construction eliminates corrosion

Patented offset optimizes airflow when used with prefilters

MV85

GREENGUARD INDOOR

AIR QUALITY CERTIFIED®

Extended Surface V-Style Filter MERV 13

V-Shaped pleats eliminates obstruction to air flow for lower pressure drop.

Technical Data- viledon MV85 1/1

Particle Removal Efficiency Resistance Curve

Performance Unit MV85 Rated Air Flow CFM 1968

Initial Resistance “w.g. .23

Final Resistance “w.g. 1.50

MERV@1968 1-16 13

ASHRAE 52.1 Equivalent Efficiency* % 80-90%

ASHRAE 52.2

AFTL 13060

Performance Unit MV85 Burst Strength “w.g. >12

ADDITIONAL DATA

MV 85 Characteristic Chart

*Ref. Ashrae 2008 Handbook Chpt.28 Sec. 11

Characteristics unit 1/1 (24x24)

1/2 (12x24)

5/5 (20x20)

5/6 (20x24)

Header Size in. 23-3/8x23-3/8 11-3/8x23-3/8 19-3/8x19-3/8 19-3/8x23-3/8

Depth 1’’ Recess in. 12-1/2 12-1/2 N/A 12-1/2

Depth Non-Recess in. 11-1/2 11-1/2 11-1/2 11-1/2

Weight lb. 10 5.0 6.5 8.3

Media Area ft2 170 85 119 142

Freudenberg Filtration Technologies LP 2975 Pembroke Road Hopkinsville, Ky 42240 Tel: 1-270-887-5145 Fax: 1-270-890-0743 www.freudenberg-filter.com

0.1 1 10

Particle Diameter (um)

R em o va l E ff ic ie n cy

Initial Load 1 Load 2 Load 3 Load 4 Load 5

The figures given are mean values subject to tolerances due to normal production fluctuations. Our explicit written confirmation is always required for the correctness and applicability of the information involved in any particular case.

viledon® is a registered trademark of Freudenberg

0.06

0.11

0.16

0.23

0.31

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

492 984 1476 1968 2460

Air Flow Rate (CFM)

R es is ta n ce in

W G