This document is a Quote Item List for a water-cooled package air conditioning unit for the McNary Lock & Dam Visitor Center project. The solicitation, issued by the US Army Corps of Engineers Walla Walla District, seeks a vertical single-piece HVAC unit with specific technical requirements, including 12.5 tons nominal capacity, 150,000 BTU/hr total heat capacity, A2L refrigerant with low global warming potential, and 5,400 CFM fan output. The unit requires 460 VAC power, a 3 HP motor, belt-driven fan, four-sided filter rack, and features like a Cupro-Nickel heat exchanger, stainless steel drain pan, and leak detection.
The pre-solicitation (Solicitation Number W912EF25QA033) is a sources sought notice aimed at identifying businesses capable of providing the specialized air conditioning unit, with a targeted delivery timeline of eight weeks after award. Potential vendors are requested to submit specific information including business size, point of contact, Unique Entity Identifier, and delivery capability confirmation. The document includes an evaluation matrix where vendors must indicate product equivalence and confirm delivery timeline compliance, with space for pricing and vendor contact details to be completed.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| TECHNICAL SPECIFICATIONS.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MCNARY LOCK & DAM
QUOTE ITEM LIST
MCNARY PROJECT NAVIGATION LOCK VISITOR CENTER REPLACEMENT WATER COOLED PACKAGE UNIT
29 APRIL
Vendor Name: _____________-______________________________________________ Address: _________________________________________________________________ Phone #: ___________________________ Email:__________________________________________ DUNs #: ________________________ Cage Code: ____________________
Registered In SAM: _________ (Yes/No)
QUOTE ITEM LIST
| ITEM |
| DESCRIPTION |
| QNTY |
| U/M |
| U/Price |
| AMOUNT |
| 001 |
| Vertical Single Piece Unit. Rear Air Return, Top Air Discharge. |
12.5 Tons Nominal Capacity (MBH).
150,000 British Thermal Unit (BTU/Hr.) Hour total heat capacity of American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) Standard Rating Conditions of 80 Deg F Dry Bulb and 67 Deg F Wet Bulb.
Refrigerant with a Global Warming Potential (GWP) less than 700.
Total Fan Output averaging 5,400 Cubic Feet per Minute (CFM) at resulting Static Pressure (S.P.) allowing a minimum of Three Quarters Inches H2O for exiting ducts and outlets.
Staged Air Volume (SAV) with Variable Frequency Drive Installed.
460 VAC, 3 Phase, 60 Hertz, 3 HP Motor.
Belt Drive Fan.
Unit is Cooling Only.
Four Sided 2” Filter Rack.
Cupro-Nickel Coaxial Heat Exchanger.
Closed-Cell Foam Insulation.
Mute Package on Scroll Compressor(s).
A2L refrigerant Leak Detection.
Stainless Steel drain pan with condensate overflow sensor.
Standard Unit Protection Module (UPM).
Stainless Steel Braided Hose Connection Kit – 24 Inches. Supply and Return Hose, Swivel connection between unit and hoses, and adapters from hoses to supply and return piping
| 1 |
| EACH |
| Total |
| 1 |
| EACH |
In addition to your quote, please answer each of the following questions on the following page:
EVALUATION FACTOR 1:
Check one—
|_| This quote is based on a product equivalent to the Brand Name listed in the specifications AND descriptive materials regarding the quoted product are attached.
EVALUATION FACTOR 2:
Check one— |_| This quote includes meeting the delivery requirement of No Later Than EIGHT (8) weeks after award.
|_| This quote does not include meeting the delivery requirement of No Later Than EIGHT (8) weeks after award. Delivery will occur on ____________________ .