Quad Cities UPS Attachment A.xlsx

XLSX spreadsheet 20 KB Posted

Attached to
EMA - Quad Cities GEMS Facility UPS - 20KVA
Solicitation number
23-588IEMA-DIVNU-B-35718
Issued by
Illinois

About this file

This document appears to be the technical specifications for an Eaton 9355 UPS (Uninterruptible Power Supply) system to be installed at the Quad Cities Nuclear Generating Station. The UPS system is rated for 20 KVA / 18W at 0.9 power factor, with a double conversion topology, 208/120V 3-phase 4-wire Wye input, and 208/120V 3-phase 4-wire Wye output. It includes a VRLA battery backup with a typical runtime of over 100 minutes at full load. The UPS has various certifications, diagnostics, communications, and network capabilities, as well as a 1-year warranty with 24/7 on-site emergency response. The vendor must be certified to perform the initial startup of the unit per the manufacturer's requirements.

The document does not contain any information about pricing, set-asides, incumbents, funding sources, or other contractual details. It solely focuses on the technical specifications and requirements for the UPS system to be installed at the Quad Cities Nuclear Generating Station.

View the file

Other files

File Type Posted
standard-terms-and-conditions~24.pdf PDF
standard-illinois-certifications-v.23.1~7.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1 GEMS UPS Technical Specifications

Tech Specs
ModelEaton 9355
Power
Ratings20 KVA / 18W @ 0.9 P.F.
TopologyDouble Conversion
Input
Input Voltage208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye
Input Frequency60 Hz ± 5 Hz
Voltage Correction Range176-228.8V AC
Power Factor (Full Load)0.99 typical
Output
Waveform (On-Line)Sinewave
Waveform (On-Battery)Sinewave
Output Voltage (RMS)208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye
Output Frequency60 Hz
Efficiency (Full Load / On-Line)91% typical
Voltage Regulation± 1%
Input Current Distortion< 5% THD
Overload Capabilities125% (1 min.) / 150% (5 sec.) / 110% (10 mins.)
Battery
Battery TypeVRLA, 9AH, maintenance free (Field replacable)
Typical Backup Time (Full Load)> 100 min @ full load (> 10 hours @ 15% full load)
Operation / General
DiagnosticsFull system self-test @ startup
UPS BypassAutomatic on overload or UPS failure
On-Line Transfer Time1 ms typical
Audible Noise (Full Load @ 1m)< 58 dBA
Communications
Minimum RequirementsGraphical LCD w/ backlight display, RS-232, X-slot Industrial Relay Card, network communications card
Network typeFactory Installed MS Network Card (SNMP)
Certifications
QualityISO 9001
Warranty
Standard1 Year Full Parts & Labor, including 24/7 on-site emergency response within 8 hours of notification.
Customer Service
Initial Start UpVendor must be certified to perform initial startup of the unit per manufacturer requirements. Location: On-site @ Quad Cities Nuclear Generating Station
Tech Support Availability24/7 (Unlimited)

File details come from the government source that posted it. Updated .