Quad Cities UPS Attachment A.xlsx
XLSX spreadsheet 20 KB Posted
- Attached to
- EMA - Quad Cities GEMS Facility UPS - 20KVA
- Solicitation number
- 23-588IEMA-DIVNU-B-35718
- Issued by
- Illinois
About this file
This document appears to be the technical specifications for an Eaton 9355 UPS (Uninterruptible Power Supply) system to be installed at the Quad Cities Nuclear Generating Station. The UPS system is rated for 20 KVA / 18W at 0.9 power factor, with a double conversion topology, 208/120V 3-phase 4-wire Wye input, and 208/120V 3-phase 4-wire Wye output. It includes a VRLA battery backup with a typical runtime of over 100 minutes at full load. The UPS has various certifications, diagnostics, communications, and network capabilities, as well as a 1-year warranty with 24/7 on-site emergency response. The vendor must be certified to perform the initial startup of the unit per the manufacturer's requirements.
The document does not contain any information about pricing, set-asides, incumbents, funding sources, or other contractual details. It solely focuses on the technical specifications and requirements for the UPS system to be installed at the Quad Cities Nuclear Generating Station.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| standard-terms-and-conditions~24.pdf | ||
| standard-illinois-certifications-v.23.1~7.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1 GEMS UPS Technical Specifications
| Tech Specs | |
| Model | Eaton 9355 |
| Power | |
| Ratings | 20 KVA / 18W @ 0.9 P.F. |
| Topology | Double Conversion |
| Input | |
| Input Voltage | 208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye |
| Input Frequency | 60 Hz ± 5 Hz |
| Voltage Correction Range | 176-228.8V AC |
| Power Factor (Full Load) | 0.99 typical |
| Output | |
| Waveform (On-Line) | Sinewave |
| Waveform (On-Battery) | Sinewave |
| Output Voltage (RMS) | 208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye |
| Output Frequency | 60 Hz |
| Efficiency (Full Load / On-Line) | 91% typical |
| Voltage Regulation | ± 1% |
| Input Current Distortion | < 5% THD |
| Overload Capabilities | 125% (1 min.) / 150% (5 sec.) / 110% (10 mins.) |
| Battery | |
| Battery Type | VRLA, 9AH, maintenance free (Field replacable) |
| Typical Backup Time (Full Load) | > 100 min @ full load (> 10 hours @ 15% full load) |
| Operation / General | |
| Diagnostics | Full system self-test @ startup |
| UPS Bypass | Automatic on overload or UPS failure |
| On-Line Transfer Time | 1 ms typical |
| Audible Noise (Full Load @ 1m) | < 58 dBA |
| Communications | |
| Minimum Requirements | Graphical LCD w/ backlight display, RS-232, X-slot Industrial Relay Card, network communications card |
| Network type | Factory Installed MS Network Card (SNMP) |
| Certifications | |
| Quality | ISO 9001 |
| Warranty | |
| Standard | 1 Year Full Parts & Labor, including 24/7 on-site emergency response within 8 hours of notification. |
| Customer Service | |
| Initial Start Up | Vendor must be certified to perform initial startup of the unit per manufacturer requirements. Location: On-site @ Quad Cities Nuclear Generating Station |
| Tech Support Availability | 24/7 (Unlimited) |
File details come from the government source that posted it. Updated .