Q&A Memo - D0SHV00004.pdf

PDF 181 KB Posted

Attached to
New Fire Alarm System Installation in Orange and Rockland Counties
Solicitation number
2113199
Issued by
Orange County, Rockland County, Cheektowaga CDP, New York

About this file

This is a Questions and Answers document from the Office for People With Developmental Disabilities (OPWDD) Contract Management Unit regarding Project No. D0SHV00004 for New Fire Alarm System Installation at Grove IRA and Greycourt SOIRA facilities, dated October 9, 2024. The document addresses four specific technical questions about the fire alarm installation project, including clarifications that door holders are not required at either site, details about linear heat detector placement at Greycourt (needed in attic space above bedrooms, office, and garage, but not in vaulted ceiling area), and confirmation that only Edwards IO Series IO64 control panels are approved for use with no alternate options permitted. An addendum (Addendum 1 – D0SHV00004) has been issued to address questions about duct smoke detectors referenced in Electrical Note 13.

The document does not contain any pricing terms, funding information, or contract award details. It is purely technical in nature, providing clarifications on specific installation requirements and equipment specifications for the fire alarm system project at these two OPWDD facilities located in Pomona (Grove) and Chester (Greycourt).

View the file

Other files

File Type Posted
Drawings - Grove IRA Revised.pdf PDF
ADDENDUM 1 - D0SHV00004.pdf PDF
CR Bid Results D0SHV00004.pdf PDF
Final Project Manual D0SHV00004.pdf PDF
Drawings -Greycourt SOIRA Revised.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OPWDD Contract Management Unit | eny.nyc.li.contracthub@opwdd.ny.gov

26 Center Circle, Wassaic, NY 12592 │ TEL: 845-877-6821 x3122, FAX: 845-877-3004 │www.opwdd.ny.gov

KATHY HOCHUL

Governor

WILLOW BAER

Acting Commissioner

October 9, 2024

Re: Official Responses to questions asked regarding Project No. D0SHV00004, New Fire Alarm System Installation for Grove IRA and Greycourt SOIRA

Questions and Answers:

Question 1: The drawings for D0SHV00004 dwellings do not have door holders for both Greycourt and the dwelling in Pomona [Grove], will they be required?

Answer: No, door holders are not required for these two sites.

Question 2: The drawings for D0SHV00004 dwellings do not show an air handler unit or ductwork, whereas Electrical Note 13 says, “Provide photoelectric type duct smoke detectors with remote test stations.” The dwelling in Chester [Greycourt] has a unit in the attic that is not reflected on the prints and the dwelling in Pomona [Grove] has no air handling unit. Please clarify location and implementation of duct detector in fire alarm system.

Answer: An addendum, Addendum 1 – D0SHV00004, has been issued to address Electrical Note 13 on the drawings for Grove IRA and Greycourt SOIRA. Please see Addendum 1 – D0SHV00004.

Question 3: The Greycourt dwelling in Chester has a vaulted ceiling (no attic space) in the center area (kitchen, dining area and living room) upon inspection during pre-bid. Please clarify specific location for linear heat detector in attic space above bedroom areas and the space above the office and bathroom areas.

Answer: Linear heat detection is needed in the attic space above the bedrooms, in the attic space above the office, and in the garage as well. No linear heat detection for vaulted ceiling area.

Question 4: On the drawings that accompany Project No. D0SHV00004, the Device Legend says, “Fire Alarm Control Panel – Edwards IO Series IO64 or Owner approved alternate”. Are there any Owner approved alternates for this project?

Answer: No, there are no Owner approved alternates.

mailto:eny.nyc.li.comtracthub@opwdd.ny.gov