Q&A Memo - D0SHV00004.pdf

PDF 181 KB Posted

Attached to
New Fire Alarm System Installation in Orange and Rockland Counties
Solicitation number
2113199
Issued by
Rockland County, Cheektowaga CDP, New York

About this file

This document is a Q&A Memo from the OPWDD Contract Management Unit regarding Project No. D0SHV00004 for the installation of a new fire alarm system at the Grove IRA and Greycourt SOIRA facilities in Pomona, NY and Chester, NY. The memo addresses questions related to the necessity of door holders, the location and implementation of duct smoke detectors, the need for linear heat detection in the attic spaces, and the lack of approved alternates for the fire alarm control panel.

The related state and local contract opportunity is for the installation of new fire alarm systems at these two facilities in Orange and Rockland Counties, New York. The contract is being solicited by the OPWDD Contract Management Unit, Design and Construction, on behalf of the Hudson Valley DDSOO. Mandatory site visits are scheduled for September 11 and 12, 2024, and bids are due by October 22, 2024 at 3:00 PM. The contract term is to be determined. There are no minority, women-owned, or service-disabled veteran-owned business goals associated with this contract, and no identical or substantially similar contracts have been awarded in the past five years.

View the file

Other files

File Type Posted
Final Project Manual D0SHV00004.pdf PDF
Drawings - Grove.pdf PDF
ADDENDUM 1 - D0SHV00004.pdf PDF
Drawings -Greycourt.pdf PDF
Drawings -Greycourt SOIRA Revised.pdf PDF
Drawings - Grove IRA Revised.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OPWDD Contract Management Unit | eny.nyc.li.contracthub@opwdd.ny.gov

26 Center Circle, Wassaic, NY 12592 │ TEL: 845-877-6821 x3122, FAX: 845-877-3004 │www.opwdd.ny.gov

KATHY HOCHUL

Governor

WILLOW BAER

Acting Commissioner

October 9, 2024

Re: Official Responses to questions asked regarding Project No. D0SHV00004, New Fire Alarm System Installation for Grove IRA and Greycourt SOIRA

Questions and Answers:

Question 1: The drawings for D0SHV00004 dwellings do not have door holders for both Greycourt and the dwelling in Pomona [Grove], will they be required?

Answer: No, door holders are not required for these two sites.

Question 2: The drawings for D0SHV00004 dwellings do not show an air handler unit or ductwork, whereas Electrical Note 13 says, “Provide photoelectric type duct smoke detectors with remote test stations.” The dwelling in Chester [Greycourt] has a unit in the attic that is not reflected on the prints and the dwelling in Pomona [Grove] has no air handling unit. Please clarify location and implementation of duct detector in fire alarm system.

Answer: An addendum, Addendum 1 – D0SHV00004, has been issued to address Electrical Note 13 on the drawings for Grove IRA and Greycourt SOIRA. Please see Addendum 1 – D0SHV00004.

Question 3: The Greycourt dwelling in Chester has a vaulted ceiling (no attic space) in the center area (kitchen, dining area and living room) upon inspection during pre-bid. Please clarify specific location for linear heat detector in attic space above bedroom areas and the space above the office and bathroom areas.

Answer: Linear heat detection is needed in the attic space above the bedrooms, in the attic space above the office, and in the garage as well. No linear heat detection for vaulted ceiling area.

Question 4: On the drawings that accompany Project No. D0SHV00004, the Device Legend says, “Fire Alarm Control Panel – Edwards IO Series IO64 or Owner approved alternate”. Are there any Owner approved alternates for this project?

Answer: No, there are no Owner approved alternates.

mailto:eny.nyc.li.comtracthub@opwdd.ny.gov

OPWDD Contract Management Unit | eny.nyc.li.contracthub@opwdd.ny.gov

26 Center Circle, Wassaic, NY 12592 │ TEL: 845-877-6821 x3122, FAX: 845-877-3004 │www.opwdd.ny.gov

Respectfully, Rebecca Whitaker CMS 2, Contract Management Unit OFFICE: (845) 877-6821 ext. 3704 | FAX: (845) 877-3004 designandconstruction@opwdd.ny.gov mailto:eny.nyc.li.comtracthub@opwdd.ny.gov mailto:designandconstruction@opwdd.ny.gov

File details come from the government source that posted it. Updated .