Q and A for W50SLF24Q1074 5.14.2024.docx

DOCX document 102 KB Posted

Attached to
Electrical Material Supplies Federal contract opportunity
Solicitation number
W50SLF-24-Q-1074
Issued by
Department of the Army National Guard

About this file

This document is a Q&A regarding a federal solicitation for Electrical Material Supplies, Solicitation Number W50SLF-24-Q-1074. The solicitation is for various electrical equipment and materials, including a 600A 120/208V 3 phase NEMA 3R distribution panel board, transformers, circuit breakers, and fuses. Key details include:

The solicitation has been updated to incorporate Q&As, provide additional details on the 600A panel board, and update the list of materials with NLT dates. Quotes are due by 2:00 pm HST on May 16, 2024. This is an unrestricted acquisition, and the government intends to award without discussions. DFARS provisions 252.225-7000 and 252.225-7001 apply, indicating domestic source restrictions. Acceptable transformer windings are either copper or aluminum. The solicitation is for the Department of the Army National Guard.

View the file

Other files for this federal contract opportunity

Other files attached to Electrical Material Supplies, newest first.
File Type Posted
Q and A for W50SLF24Q1074 5.20.2024 Rev1.docx DOCX document
1.List of Materials - Revised 5.20.2024.xlsx XLSX spreadsheet
Q and A for W50SLF24Q1074 5.20.2024.docx DOCX document
Q and A for W50SLF24Q1074 5.16.2024.docx DOCX document
Combined Synopsis Solicitation 5.15.2024.pdf PDF
Q and A for W50SLF24Q1074 5.15.2024.docx DOCX document
1.List of Materials - NLT Dates Revised 5.14.2024.xlsx XLSX spreadsheet
Combined Synopsis Solicitation.5.14.2024.pdf PDF
600 Amp Panel Board.pdf PDF
2.Delivery Location.pdf PDF
3.Full Text Provisions and Clauses.pdf PDF
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Electrical Material Supplies - Question & Answers Q1: Junction Box, NEMA 4X, Screw Cover, PVC: junction box pvc size A1: PVC: 12" x 12" x 6": see photo below

Q2: 225 kVA 480 VAC primary 120/208 VAC secondary XFMR - Equivalent of attachment: XFMR indoor/outdoor?

A2: outdoor (NEMA 3R) transformer

Q3: 600A 120/208V 3 phase NEMA 3R distribution panel board w/ main breaker: 600A main breaker doesn’t exist, I have quoted a main lug A3: Main Lug will work - but it will need to be double lugged Q3.1: Transformer does not include lugs, will the AU-600 be used for the transformer? If not I will need another list. Sorry there are other lugs on the order as well, KA29U, I assume they will be used for the transformer.

A3.1: See line item 49, Double Barrel Mechanical Lug (600 kcmil - 2 AWG). Match properties of item in link provided.

Q3.2: 600a panel will be at least 30 space, what amperage they want for the main breaker?

A3.2: Follow specs in PDF – 600 Amp Panel Board.

Q4: 300 A dual element fuses: 3-100 amp fuses or 3-300 amp fuses A4: (3) 300 A fuses

Q5: 600 AMP breaker with dual tapes: 600 amp breaker with dual tapes, need more clarification A5: 3 pole 600 amp breaker that has double lugs

Q5.1: will be a breaker enclosure, open breaker, aic rating?
A5.1: Follow specs in PDF – 600 Amp Panel Board.

Q6: 600 AMP breaker with dual tapes? As per one of our suppliers:

Unfortunately, we have never heard of anything on a breaker referred to as "tapes". For taps that is usually used when speaking about a transformer not a circuit breaker.

A6: “Taps” not “tapes”. See PDF – 600 Amp Panel Board for details.

Q7: Could you please confirm breaker specs and tap size. Also, we need to know if the transformer is Copper or Aluminum windings and if Made in USA is required since its being installed at PMRF. Copper is normally used as well on the transformers too.

A7: See PDF – 600 Amp Panel Board for details. Either Copper or Aluminum is acceptable. DFARS Provision 252.225-7000 and Clause 252.225-7001 applies to this solicitation/pending purchase order.

Q8: Line 60 - 600 AMP breaker with dual tapes: is this a separate breaker or does it need to be in the DP Panel?

A8: In the panel. See PDF – 600 Amp Panel Board.