PWS_SF6_Calibration_1.docx
DOCX document 41 KB Posted
- Attached to
- CALIBRATION SERVICE - DILO SF6 GAS ANALYZER
- Solicitation number
- 140R1725Q0056
About this file
This Performance Work Statement (PWS) outlines calibration and repair services for six DILO SF6 Multi-Analyzers owned by the Bureau of Reclamation's Grand Coulee Power Office. The requirements include comprehensive calibration, testing, sensor replacement, and repair services by DILO-certified technicians, with a mandatory 2-year calibration cycle. Services must comply with ANSI/ISO 9001:2015 quality standards, and include detailed documentation, certification, and equipment tagging.
The related federal contract opportunity is a Sources Sought notice for small business contractors, targeting NAICS code 541380 with a small business size standard of $19 million. The government intends to award a firm-fixed price purchase order for calibration services. Interested small businesses must submit capabilities statements by 5:00 PM ET on June 12, 2025, to Don Richer via email, including company details, unique entity identifier, small business certification, service capabilities, and past performance. The place of performance is Grand Coulee, Washington, and the solicitation number is 140R1725Q0056.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Performance Work Statement Calibration and Repair Services DILO SF6 Multi-Analyzer
1.0 General
1.1 Background
This performance work statement (PWS) outlines the requirements necessary to provide services to include calibrating, testing, replacement of sensors (if needed) and repairing six (6) DILO SF6 multi-analyzer owned by and utilized by Government.
1.2 Scope
The Bureau of Reclamation, Grand Coulee Power Office require services that include testing, calibrating, repairing as needed, certifying, adjustments and performing traceable measurement documentation. The Contractor shall provide all OEM parts, labor, tooling, test equipment and facilities necessary to perform calibration and repairs of equipment in the Government Furnished Propery listing.
2.0 Calibration Cycle/Interval
2.1 Calibration Cycle/Interval
2.1.1 The Calibration cycle shall be as specified by manufacturer which is currently 2 calendar years. Bureau of Reclamation will ensure shipment of equipment to DILO at the time of calibration expiration.
2.2 Handling
The Contractor shall ensure the safety of instrumentation and documentation during return shipping. Once calibrations or repairs authorized by the Contracting Officer have been completed, all instrumentation shall be returned in a Ready for Issue (RFI) condition, unless the Contracting Officer or COR directs the equipment to be returned “As-Is”.
3.0 Contractor (Services to be provided)
3.1 General Requirements
3.1 All calibration, testing and repair services provided under this contract shall be performed by fully qualified DILO certified technicians.
3.2 All calibration and repair services performed under the contract shall be completed to manufacture’s requirements and ANSI/ISO 9001:2015, Quality Management Systems-Requirements and a signed certification of calibration provided in addition to affixed decal on equipment.
3.2.1 All documentation, labels, certificates, manuals, ect. will be provided in English language.
3.2.2 All analyzers shall be repaired to ensure compliance with original equipment performance specifications.
4.0 Calibration Identification
The Contractor shall tag all calibrated tooling and equipment by affixing a calibration decal to the equipment. Decals shall be of sufficient size to be easily read by the naked eye. The decal shall show the date of calibration (day, month, year), date due for calibration (day, month, year), and include legible initials of the certifying technician. The previous calibration decal shall be removed from tools/equipment and the new decal affixed in the same location.
4.1 Decals shall be applied in such a manner that will not cause damage to the equipment at a later date when the decal is removed.
4.1.1 Decals shall not be applied to the glass or plastic meter faces of electrical/electronic equipment or the screen of an analyzer or other location that would hinder or prevent proper use/operation of equipment.
5.0 Repairs
The Contractor shall provide a written failed and adjusted calibration report on all analyzers that has failed calibration or has been adjusted at no additional cost to the Government. The report shall include information describing the equipment that failed (i.e. serial number and nomenclature). A failure report shall be submitted via email to the COR, for review within five (5) business days that the equipment failed calibration.
5.1 If the failed equipment can be repaired, the Contractor, upon request shall submit a repair quote to the Contracting Officer and COR within five (5) business days from the date the item failed calibration. The quotation shall be valid for thirty (30) calendar days and the documentation shall include:
· Description of each repair needed
· Number of man-hours required to repair item(s)
· Itemized breakdown of materials with part numbers traceable to the original equipment manufacturer (OEM)
· Parts costs (if the part is not listed on the separately priced parts list, this shall be notated in the quotation)
· Total dollar amount for each repair
· Total dollar amount for complete list of repairs If a quotation is declined by the COR, the contractor shall return the item “As-Is”. The contractor will be paid the firm-fixed service price established in contract line item.
5.1.1 If equipment fails calibration, and the Government decides to have the items returned “As-Is”, a decal or tag shall be attached to equipment, which identifies the item as failed and briefly state why and how the equipment was rejected.
6.0 Government Furnished Property (GFP)
Pursuant to Clause 52.245-1, Alternate 1 titled “Government Furnished Property.” The Government will issue to the contractor on an as-is basis, the following equipment for use only in the performance of this contract.
MANUFACTURER
MODEL
DESCRIPTION
SERIAL NO.
Year entered into inventory
DILO Company
03-038R-R303
SF6 Analyzer
7100017273
9/2021
| DILO Company |
| 03-038R-R303 |
| SF6 Analyzer |
| 7100017289 |
| 9/2021 |
| DILO Company |
| 03-038R-R303 |
| SF6 Analyzer |
| 7100017290 |
| 9/2021 |
| DILO Company |
| 03-038R-R303 |
| SF6 Analyzer |
| 2000014897 |
| 7/2020 |
| DILO Company |
| 03-038R-R303 |
| SF6 Analyzer |
| 2000014898 |
| 7/2020 |
| DILO Company |
| 03-038R-R303 |
| SF6 Analyzer |
| 2000014899 |
| 7/2020 |
7.0 Performance Requirements Summary
Requirements (PWS Task)
| Surveillance Method |
| Performance Standards |
| Acceptable Quality Level |
Remedy
| Para 3, 4, 5. Calibration and repair services |
| Physical inspection of equipment |
| 100 percent |
| Fully certified and function of equipment except for non-repairable equipment |
| At contractor’s expense return of equipment for calibration and repair |
8.0 Shipping Instructions
Equipment will be returned via commercial carrier to the following address:
US Bureau of Reclamation Grand Coulee Power Office Attn: O&M Engineering Supervisor Hwy 155, Industrial Area, Whse B, Door 6 Grand Coulee, WA 99133