PW#2025-077_W_Magnolia_Plan_Set-_signed.pdf
PDF 14 MB Posted
- Attached to
- W Magnolia S PF Lighting Replacements
- Solicitation number
- PW#2025-077
- Issued by
- King County, Spokane City, Washington
About this file
This is a project plan set for the W Magnolia South Playfield Lighting Replacements project administered by the City of Seattle Department of Parks and Recreation, with the Department of Finance and Administrative Services serving as the contract owner. The project involves the demolition of existing wooden floodlight poles and associated lighting infrastructure at Magnolia Playfield located at 2518 34th Avenue West, Seattle, Washington, followed by installation of new LED floodlight systems with modern electrical controls. The scope of work includes removing existing treated wood poles (potentially containing Pentachlorophenol, Chromated Copper Arsenate, or CCA), disposing of contaminated materials appropriately, installing new metal poles with shielded LED floodlights, replacing electrical panels with new circuit breakers and lighting control systems, and performing necessary tree pruning to accommodate the new lighting installation. The project plan set includes comprehensive design documents encompassing topographic surveys, electrical site plans, single-line diagrams, electrical details, stormwater control specifications, tree protection plans, and construction details prepared by DMD Consulting Engineers Ltd.
The engineer's estimate for the project totals $1,219,433.60, with funding provided through the Seattle Parks District. The project is identified as PW#2025-077 with project number PRK730300-331 and tax parcel number 222503-9016. Key project assets include the athletic field lighting system, electrical system components, electrical panels, and the magnolia community center electrical service connection. The project team includes Mike Fernandes as Project Manager (206-430-0818), Myles Long as the city contact (206.255.8943), and Don McLean as the design engineer primary contact (604-830-1533). All contractors are required to call 811 before digging and verify underground utilities through a commercial location service while also contacting the SPR Inspection Request Line at (206) 684-7034.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| W_Magnolia_S_PF_-Bid_Forms.pdf | ||
| PW#2025-077-_W_Magnolia_S_PF_-Project_Manual_-_signed.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT TEAM
OWNER
CITY OF SEATTLE
DEPARTMENT OF FINANCE AND
ADMINISTRATIVE SERVICES
ADMINISTRATIVE DEPARTMENT
SEATTLE PARKS AND RECREATION
PLANNING AND DEVELOPMENT DIVISION
SUITE 100 - 300 ELLIOTT AVE W,
SEATTLE, WA 98119
CONTACT: MYLES LONG
PHONE: 206.255.8943
COVER
TOPOGRAPHIC SURVEY
DEMO PLAN
ELECTRICAL SITE PLAN
SINGLE LINE DIAGRAM
DETAILS
ELEC RM MODIFICATION
ELECTRICAL DETAILS
SURVEYOR
ELECTRICAL ENGINEER
DMD CONSULTING ENGINEERS LTD.
#12-17358 104 A AVE.
SURREY, BC V4N 5M3 CANADA
CONTACT: DON McLEAN
PHONE: 604.830.1533
G0.00 V-101
SV1.0
E0.01
E0.03 E0.04 E0.05 E0.06
PURCHASING AND CONTRACTING DIVISION
CITY OF SEATTLE
SPR SURVEY AND MAPPING
300 ELLIOTT AVE W, MS#26
SEATTLE, WA 98119
CONTACT: Thomas Barger
PHONE: (206) 684-4954
9 of 14 ELECTRICAL SITE PLANE0.02
3 of 14 TOPOGRAPHIC SURVEYV-102
14 of 14 GENERAL NOTES, POLE AND FOUNDATION DETAILSS0.01
5 of 14 CONSTRUCTION STORMWATER CONTROLL0.01
7 of 14 EXISTING IRRIGATIONL0.03 6 of 14 TREE PROTECTION SITE PLANL0.02
PROJECT ASSET LIST
GENERAL NOTES
LEGAL DESCRIPTIONPROJECT ADDRESS
2518 34TH AVE W
SEATTLE, WA
PROJECT SITE LOCATION
ADMINISTERING DEPARTMENT:
CITY OF SEATTLE DEPARTMENT OF PARKS AND RECREATION
PLANNING AND CAPITAL DEVELOPMENT BRANCH
300 ELLIOTT AVENUE WEST, SUITE 100, SEATTLE, WA 98119
PROJECT MANAGER: MIKE FERNANDES, 206-430-0818
OWNER:
CITY OF SEATTLE DEPARTMENT OF FINANCE AND ADMINISTRATIVE SERVICES,
PURCHASING & CONTRACTING
PROJECT DESIGN TEAM:
DMD CONSULTING ENGINEERS LTD.
PRIMARY CONTACT: DON McLEAN 604-830-1533
G.0.00
NTS
05-06-2025
W MAGNOLIA S PF
COVER
LIGHTING
REPLACEMENTS
DON McLEAN
R. FRASER
DANIEL J. WONG
NO SHT ID SHEET TITLE
SHEET INDEX PW#2025-077 PROJECT#PRK730300-331
FUNDING SOURCE: SEATTLE PARKS DISTRICT
ALSO, VERIFY ALL UNDERGROUND UTILITIES NOT
LOCATED BY THE 811 SERVICE BY USING A
COMMERCIAL LOCATION SERVICE AND CALL SPR
INSPECTION REQUEST LINE (206) 684-7034.
<<<CAUTION>>>
CALL 811 BEFORE YOU DIG!
WWW.CALL811.COM
VICINITY MAP
NOT TO SCALE
CITY OF SEATTLE - NOT TO SCALE
EXISTING ASSETS
Project Asset List (PAL) | PRK730300-331 | W Magnolia Playfield South Athletic Field Lighting Replacement
ASSET ID ASSET DESCRIPTION CATEGORY DESCRIPTION
LIGHT-WMGLPF-ATH W MAGNOLIA PF S ATH FIELD LIGHTING ATHL FIELD AND SEC LIGHT SYS
ELECSYS-WMGLPF W MAGNOLIA PLYFLD ELECTRICAL SYS EXT PROPERTY ELECTRICAL SYSTEM
ELECPAN-WMGLPFCS W MAGNOLIA PF SOUTH CS-ELEC PANEL ELECTRICAL PANEL
ELECSER-MGLCC MAGNOLIA CC ELECTRICAL SERVICE ELECTRICAL SERVICE
TAX PARCEL NUMBER: 222503-9016
FAS PMA NUMBER: 319
LEGAL DESCRIPTION (ABBREVIATED FROM KING COUNTY ASSESSOR):
POR SE 1/4 OF NE 1/4 SEC 22-25-3 LY W OF 32ND AVE W & E OF 34TH AVE W
LESS POR FOR W RAY ST LESS S 379 FT TGW LOTS 1 THRU 3 BLK 4 TGW
LOTS 8-9-10 BLK 3 ALL IN PLEASANT VALLEY GARDEN TRACTS TGW PORS
VAC STS ADJ
GENERAL SITE PLAN
SCALE IN FEET
60 30 0 60 120
SOUTH
BASEBALL
NORTH
SOFTBALL
DMD PROJECT No. 8392-25 office@dmdeng.com www.dmdeng.com
DMD Consulting Engineers Ltd.
#12-17358 104A Avenue Surrey, BC, Canada V4N 5M3
604/589-9010
W MAGNOLIA S PF
LIGHTING REPLACEMENTS
09/28/2026
September 29 26 https://seattlegov.na1.adobesign.com/verifier?tx=CBJCHBCAABAAaPjXan6DRvhtyWRLOCWTBj9Q86PuoirE
W MAGNOLIA S PF
TOPOGRAPHIC SURVEY
LIGHTING
REPLACEMENTS
2 14
V-101
Also, verify all underground utilities not located by the 811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.
>>>>CAUTION - CALL 811<<<<
UTILITY NOTIFICATION CENTER
BEFORE YOU DIG!
WWW.CALL811.COM
ALL DRAWINGS AND MATERIAL APPEARING
HEREIN ARE THE ORIGINAL AND UNPUBLISHED
WORK OF THE LAND SURVEYOR AND MAY NOT BE
DUPLICATED, USED, OR DISCLOSED WITHOUT
THE WRITTEN CONSENT OF SEATTLE PARKS AND
RECREATION'S CHIEF LAND SURVEYOR.
PRELIM
IN
ARY
NOT VALID
UNLE
SS SIG
NED
SEE SHEET V-102
09/28/2026
TOPOGRAPHIC SURVEY
V-102
Also, verify all underground utilities not located by the 811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.
>>>>CAUTION - CALL 811<<<<
UTILITY NOTIFICATION CENTER
BEFORE YOU DIG!
WWW.CALL811.COM
ALL DRAWINGS AND MATERIAL APPEARING
HEREIN ARE THE ORIGINAL AND UNPUBLISHED
WORK OF THE LAND SURVEYOR AND MAY NOT BE
DUPLICATED, USED, OR DISCLOSED WITHOUT
THE WRITTEN CONSENT OF SEATTLE PARKS AND
RECREATION'S CHIEF LAND SURVEYOR.
PRELIM
IN
ARY
NOT VALID
UNLE
SS SIG
NED
SEE SHEET V-101
3 14
W MAGNOLIA S PF
LIGHTING
REPLACEMENTS
DEMO PLAN
SV1.0
Also, verify all underground utilities not located by the 811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.
>>>>CAUTION - CALL 811<<<<
UTILITY NOTIFICATION CENTER
BEFORE YOU DIG!
WWW.CALL811.COM
SCALE IN FEET
30 15 0 30 60
W MAGNOLIA S PF
4 14LIGHTING
REPLACEMENTS
FOR CONDUIT AND PANEL
IN BUILDING REFER TO
DRAWINGS E0.05 & E0.06
MAINTAIN OPERATION OF EXISTING LIGHTING
UNTIL NEW LIGHTING IS OPERATIONAL. ANY
DOWNTIME MUST BE APPROVED BY THE CITY
DMD PROJECT No. 8392-25 office@dmdeng.com www.dmdeng.com
DMD Consulting Engineers Ltd.
#12-17358 104A Avenue Surrey, BC, Canada V4N 5M3
604/589-9010
L0.01 Also, verify all underground utilities not located by the
811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.
>>>>CAUTION - CALL 811<<<<
UTILITY NOTIFICATION CENTER
BEFORE YOU DIG!
WWW.CALL811.COM
1 TREE PROTECTION
SCALE: 1/4" = 1'-0"
2 CATCH BASIN INSERT
SCALE: 3/4" = 1'-0"
3 TEMPORARY PLASTIC COVERING
SCALE: 3/4" = 1'-0"
5 14
CONSTRUCTION STORMWATER
CONTROLDMD PROJECT No. 8392-25 office@dmdeng.com www.dmdeng.com
DMD Consulting Engineers Ltd.
#12-17358 104A Avenue Surrey, BC, Canada V4N 5M3
604/589-9010
W MAGNOLIA S PF
LIGHTING
REPLACEMENTS
L0.02
811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.
>>>>CAUTION - CALL 811<<<<
UTILITY NOTIFICATION CENTER
BEFORE YOU DIG!
WWW.CALL811.COM
6 14
TREE PROTECTION SITE PLAN
SCALE IN FEET
30 15 0 30 60
A4B4
A3
C4
B1
A1
A2 B2
C2
7 68
5 4 3 2 1
DMD PROJECT No. 8392-25 office@dmdeng.com www.dmdeng.com
DMD Consulting Engineers Ltd.
#12-17358 104A Avenue Surrey, BC, Canada V4N 5M3
604/589-9010
CONTRACT CITY ARBORIST - ZOE WORLEY, OOC
ARBORICULTURIST - URBAN FORESTRY
SEATTLE PARKS AND RECREATION
ZOE.WORLEY@SEATTLE.GOV
CONSULT SPR URBAN FORESTRY FOR APPROVAL
PRIOR TO ANY TREE PRUNNING/CUTTING.
W MAGNOLIA S PF
LIGHTING
REPLACEMENTS
L0.03
811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.
>>>>CAUTION - CALL 811<<<<
UTILITY NOTIFICATION CENTER
BEFORE YOU DIG!
WWW.CALL811.COM
7 14
EXISTING IRRIGATION
DMD PROJECT No. 8392-25 office@dmdeng.com www.dmdeng.com
DMD Consulting Engineers Ltd.
#12-17358 104A Avenue Surrey, BC, Canada V4N 5M3
604/589-9010
W MAGNOLIA S PF
LIGHTING
REPLACEMENTS
FOR INFORMATION ONLY
ELECTRICAL SITE PLAN
E0.01
Also, verify all underground utilities not located by the 811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.
>>>>CAUTION - CALL 811<<<<
UTILITY NOTIFICATION CENTER
BEFORE YOU DIG!
WWW.CALL811.COM
8 14
A - MATCH LINE - REFER TO DRAWING E0.02 - A
A4
B4
A3
NORTH
SOFTBALL
C4
LEGEND
B1
DMD PROJECT No. 8392-25 office@dmdeng.com www.dmdeng.com
DMD Consulting Engineers Ltd.
#12-17358 104A Avenue Surrey, BC, Canada V4N 5M3
604/589-9010
REFER TO DRAWING E0.05 & E0.06
MAGNOLIA
COMMUNITY
CENTER
DISTRIBUTION VOLTAGES
ARE:
120V 480V
SCALE IN FEET
402001020
10 FT OF PLAY CLEAR ZONE FROM FACE OF POLE (TYP)
W MAGNOLIA S PF
LIGHTING
REPLACEMENTS
SCALE IN FEET
402001020
ELECTRICAL SITE PLAN
E0.02
Also, verify all underground utilities not located by the 811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.
>>>>CAUTION - CALL 811<<<<
UTILITY NOTIFICATION CENTER
BEFORE YOU DIG!
WWW.CALL811.COM
9 14
A - MATCH LINE - REFER TO DRAWING E0.01 - A
SOUTH
BASEBALL
B1
A1
A2
B2
DMD PROJECT No. 8392-25 office@dmdeng.com www.dmdeng.com
DMD Consulting Engineers Ltd.
#12-17358 104A Avenue Surrey, BC, Canada V4N 5M3
604/589-9010
DISTRIBUTION VOLTAGES
ARE:
120V 480V
10 FT OF PLAY CLEAR ZONE FROM FACE OF POLE (TYP)
LEGEND
B1 C2
W MAGNOLIA S PF
LIGHTING
REPLACEMENTS
SINGLE LINE DIAGRAM
E0.03
Also, verify all underground utilities not located by the 811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.
>>>>CAUTION - CALL 811<<<<
UTILITY NOTIFICATION CENTER
BEFORE YOU DIG!
WWW.CALL811.COM
NOTES:
1. REFER TO PROJECT SPECIFICATIONS.
2. DO NOT SPLICE LIGHTING CONDUCTORS IN HANDHOLES UNLESS
SPECIFICALLY NOTED.
3. CONDUCTORS SHALL BE STRANDED COPPER, TYPE THWN-2 INSULATED 600V
UNDERGROUND.
4. ALL WORK SHALL BE PERFORMED AND SUPERVISED BY A REGISTERED
ELECTRICAL CONTRACTOR.
5. CONTRACTOR TO ENSURE LOADS ARE BALANCED.
6. UPGRADE SKYLOGIX COMM MODULE (A10-CM-GPRS-XX) CPU BOARD,
FIRMWARE (A10-CPU-JRV##), AND CABLE & ANTENNA (A10-ANT-L-SMA)
7. UPSIZE BONDING CONDUCTORS TO SUIT THE LARGEST CONDUCTOR IN THE
CONDUIT AS PER NEC
SINGLE LINE DIAGRAM
N.T.S.
ALL BREAKERS AND PANELS SHALL BE RATED
FOR A MINIMUM OF 14kAIC INTERRUPTING CURRENT
(SERIES RATED EQUIPMENT ALLOWED)
TO MATCH EXISTING PANELS
10 14
DMD PROJECT No. 8392-25 office@dmdeng.com www.dmdeng.com
DMD Consulting Engineers Ltd.
#12-17358 104A Avenue Surrey, BC, Canada V4N 5M3
604/589-9010
LEGEND:
PROPOSED WIRING
EXISTING WIRING
BREAKER
LIGHTING CONTACTOR
GROUND
RECEPTACLE
LOAD TABLE
REMOVE EXIST. SPORTS LTG (MH) = -120kW ADD SPORTS LTG. (LED) = 65kW
ADD RECEPT. = 2kW
NET LOAD CHANGE = -53kW
20A 3P
C2 30A-3P
20A 3P
20A 3P
C3 30A-3P
C4 30A-3P
20A 3P
C5 30A-3P
20A 3P
20A 3P
C6 30A-3P
C7 30A-3P
20A 3P
C8
30A-3P LIGHTING
CONTROL
CABINET
SPORTS
LIGHTING
POLE
A2
5.28kW
SPORTS
LIGHTING
POLE
A3
4.05kW
SPORTS
LIGHTING
POLE
A4
3.18kW
SPORTS
LIGHTING
POLE
B1
8.9kW
SPORTS
LIGHTING
POLE
B2
8.36kW
SPORTS
LIGHTING
POLE
B4
5.52kW
N o.
G
R O
U N
D
N o.
G
R O
U N
D
N o.
G
R O
U N
D
N o.
G
R O
U N
D
N o.
G
R O
U N
D
N o.
G
R O
U N
D
SPARE
20A 3P
C1 30A-3P
SPORTS
LIGHTING
POLE
A1
5.28kW
N o.
G
R O
U N
D
SECURITY LIGHTING
1.3kW
NEW LIGHTING PNL 'A1' 277/480V, 400A, 3ɸ, 4W MIN. 60 SPACE (SQ D NF TYPE)
TO POLES
C4,B1,A1, A2,B2
TO POLES
B4,A4,A3, B3,C2
15A 3P
C11 30A-3P
N o.
G R
O U
N D
N o.
G R
O U
N D
N o.
G R
O U
N D
CCT
1,3,5
CCT
2,4,6
CCT
7,9,11
CCT
8,10,12
CCT
13,15,17
CCT
14,16,18
CCT
19,21,23
CCT
20,22,24
CCT
31,33,35
30A 3P
C10 30A-3P
20A 3P
C9 30A-3P
N o.
G
R O
U N
D
N o.
G R
O U
N D
CCT
25,27,29
CCT
26,28,30
SPORTS
LIGHTING
POLE
C4
5.82kW
SPORTS
LIGHTING
POLE
C2
12.02kW
200A 3P
15A-1P 15A-1P
(1000W)
(GFCI)
(1000W)
(GFCI)
SURGE
PROTECTIVE
DEVICE
MERSEN
STP480YN07(M)
15A 1P
15A 1P
15A 3P
CCT
38,40,42
POLE A1POLE A4
SKY LOGIX
ANTENNA
SKY
LOGIX
EXISTING PANEL G
30A 2P
N o.
G
R O
U N
D
CCT
41,43
EXISTING WASHROOM BUILDING
20kW
EXISTING
HANDHOLE
N o.
#3
G R
D
IN
-2
"C
N o.
#6
G R
D
IN
-2
"C
20A 1P
EXISTING
PANEL L
(120/208V)
N o.
G
R O
U N
D
EXISTING
DISCONNECT
SWITCH
EXISTING
25 KVA 480V-120/240V
TRANSFORMER
EXISTING
IRRIGATION
KIOSK
58.46kW
EXIST. PANEL B (120V/208V)
REFER TO DRAWING E0.06
TERMINAL
BLOCK
EXISTING WASHROOM BUILDING
N.T.S.
POLES B4,A4,A3,C2 AND SECURITY CONDUCTORS IN 1-2"C (480V)
POLES C4, B1, A1, A2, B2 AND SECURITY CONDUCTORS IN 1-2"C (480V)
WASHROOM CONDUCTORS IN 1-2"C (480V)
G
B O Y W
EXISTING LUGS
N.T.S.
BUILDING AREA
W MAGNOLIA S PF
LIGHTING
REPLACEMENTS
DETAILS
E0.04
Also, verify all underground utilities not located by the 811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.
>>>>CAUTION - CALL 811<<<<
UTILITY NOTIFICATION CENTER
BEFORE YOU DIG!
WWW.CALL811.COM
SECURITY LIGHT ON ALL POLES
CONDUIT INSTALLATION
TYPICAL WIRING INSIDE AND ON SPORTS
LIGHTING POLE
TYPICAL SPORTSLIGHT POLES
RECEPTACLE MOUNTING DETAIL (POLES)
LOAD = 1000W
MAXIMUM RECEPTACLE
11 14
DMD PROJECT No. 8392-25 office@dmdeng.com www.dmdeng.com
DMD Consulting Engineers Ltd.
#12-17358 104A Avenue Surrey, BC, Canada V4N 5M3
604/589-9010
HANDHOLE DETAIL
W MAGNOLIA S PF
LIGHTING
REPLACEMENTS
E0.05
811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.
>>>>CAUTION - CALL 811<<<<
UTILITY NOTIFICATION CENTER
BEFORE YOU DIG!
WWW.CALL811.COM
12 14
ELEC RM MODIFICATIONDMD PROJECT No. 8392-25 office@dmdeng.com www.dmdeng.com
DMD Consulting Engineers Ltd.
#12-17358 104A Avenue Surrey, BC, Canada V4N 5M3
604/589-9010
SCALE IN FEET
0 2 4 6 2412 18
UP
GYM
CRAWL
SPACE/
1B 1A
STORAGE
1B
HALL
STAIR
FAN
ROOM
BL
EA
C H
ER
S
(E) SLIDING
DOOR
1C
CLOSET
1C
RESTROOMS 16
CATHERINE
BLAINE K-8
N.I.C
BASEMENT
GYM
ELEC.
ROOM
NOTES:
1. PULL BOXES SHALL BE NEMA 3R GALV STEEL
2. ALL HARDWARE SHALL BE GALV STEEL
3. BOND ALL METAL EQUIPMENT AS PER NEC
4. SEAL AND FIRESTOP ALL WALL PENETRATIONS
W MAGNOLIA S PF
LIGHTING
REPLACEMENTS
E0.06
811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.
>>>>CAUTION - CALL 811<<<<
UTILITY NOTIFICATION CENTER
BEFORE YOU DIG!
WWW.CALL811.COM
13 14
ELECTRICAL DETAILS
DMD PROJECT No. 8392-25 office@dmdeng.com www.dmdeng.com
DMD Consulting Engineers Ltd.
#12-17358 104A Avenue Surrey, BC, Canada V4N 5M3
604/589-9010
ELECTRICAL ROOMS
REFER TO DRAWING E0.03 FOR WIRING
ALL EQUIPMENT IS NEW
EXCEPT WHERE SHADED.
SHADED EQUIPMENT IS EXISTING.
PANEL B
120/208V 100A 3Ø
30KVA (E)
480V -
208Y/120V
PANEL
ART
PANEL
Y
PANEL
A
150A
MCB
60A
MLO
225A
MLO
PANEL G
480V
400A
3PH/4W
MCB
HP-1
PANEL L
112.5KVA
480V -
2O8Y/120V
M
LIGHTING
PANEL
480V
I
CONTROL
CABINET400A
MCB
112L
112H
L4 E4 O4
TO 231 HANDHOLE
COMMUNITY CENTER
GYM ELECTRICAL ROOM
UNFINISHED BASEMENT/
CRAWL SPACE
TO RECEPTS
W MAGNOLIA S PF
LIGHTING
REPLACEMENTS
E0.07
811 service by using a commercial location service and call SPR Inspection Request Line (206) 684-7034.
>>>>CAUTION - CALL 811<<<<
UTILITY NOTIFICATION CENTER
BEFORE YOU DIG!
WWW.CALL811.COM
14 14
POLE FOUNDATION
DMD PROJECT No. 8392-25 office@dmdeng.com www.dmdeng.com
DMD Consulting Engineers Ltd.
#12-17358 104A Avenue Surrey, BC, Canada V4N 5M3
604/589-9010
NOTE:
1. THE ELECTRICAL ENGINEER OF RECORD (SEE BELOW) DOES NOT ASSUME
RESPONSIBILITY FOR STRUCTURAL AND CIVIL ITEMS (IE. POLE FOUNDATION DRAWINGS
AND SPU SECTION AND PLAN).
W MAGNOLIA S PF
LIGHTING
REPLACEMENTS
09/28/2026 https://seattlegov.na1.adobesign.com/verifier?tx=CBJCHBCAABAAaPjXan6DRvhtyWRLOCWTBj9Q86PuoirE
| Sheets and Views |
| 8392-25-G0.00 |
| 8392-25-V-101 |
| 8392-25-V-102 |
| 8392-25-SV1.0 |
| 8392-25-L0.01 |
| 8392-25-L0.02 |
| 8392-25-L0.03 |
| 8392-25-E0.01 |
| 8392-25-E0.02 |
| 8392-25-E0.03 |
| 8392-25-E0.04 |
| 8392-25-E0.05 |
| 8392-25-E0.06 |
| 8392-25-E0.07 |
| 2026-09-29T16:38:39+0000 | |
| Certified by Adobe Acrobat Sign |
File details come from the government source that posted it. Updated .