Pump Specs.pdf

PDF 607 KB Posted

Attached to
FCC HAZELTON, FY25 Water Heating System- PRODUCT ONLY
Solicitation number
15B12125Q00000008
Issued by

About this file

This technical specifications document outlines requirements for 4 indirect plate and frame water heaters and 4 accompanying pumps for FCC Hazelton's FY25 Water Heating System.

The water heaters must meet specific dimensional constraints (max 63" height, 22" width, 61" base length) to fit through standard 36" doors, weigh under 1200 lbs, and include features such as ASME double wall heat exchanger, 316L stainless steel construction, 150 psi working pressure, digital display with DHW setpoint range of 90-180°F, and modulating control valve. The accompanying pumps must deliver 130 US GPM flow, 32 ft head, 68.6% efficiency, operate at 60°C water temperature, and include specific flange standards. Quotes must be submitted to Andrea Burke by February 3, 2025 at 2 PM EDT, remain valid for 30 days, and vendors must have active SAM.Gov registration with UEI. The requirement is for products only, without installation services, and includes a 5-year limited warranty/1-year limited parts warranty.

View the file

Other files

File Type Posted
15B12125Q00000008 RFQ.pdf PDF
HW Tank Specs.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXAMPLE OF REQUIRED PUMP - Total of 4 required

File details come from the government source that posted it. Updated .